FCM-1 Supervised Control Module Installation And Maintenance Instructions
Before InstallingThis information is includedasaquickreference installationguide.Refer to thecontrolpanel installationmanual fordetailedsysteminformation.Ifthemoduleswillbeinstalledinanexistingoperationalsystem,informtheoperatorandlocalauthoritythatthesystemwillbetemporarilyoutofservice.Disconnectpowertothecontrolpanelbeforeinstallingthemodules.
NOTICE:Thismanualshouldbeleftwiththeowner/userofthisequipment.
General DescriptionFCM-1SupervisedControlModulesareintendedforuseinintelligent,two-wiresystems,wheretheindividualaddressofeachmoduleisselectedusingthebuilt-inrotaryswitches.Thismoduleisusedtoswitchanexternalpowersupply,whichcanbeaDCpowersupplyoranaudioamplifier(upto80VRMS),tonotificationappliances.ItalsosupervisesthewiringtotheconnectedloadsandreportstheirstatustothepanelasNORMAL,OPEN,orSHORTCIRCUIT.TheFCM-1hastwopairsofoutputterminationpointsavailableforfault-tolerantwiringandapanel-controlledLEDindicator.ThismodulecanbeusedtoreplaceaCMX-2modulethathasbeenconfiguredforsupervisedwiringoperation.
Compatibility RequirementsToensureproperoperation,thismoduleshallbeconnectedtoacompatibleNotifiersystemcontrolpanelsonly(listavail-ablefromNotifier).
MountingTheFCM-1mountsdirectlyto4˝squareelectricalboxes(seeFigure2A).Theboxmusthaveaminimumdepthof21/8˝.Surfacemountedelectricalboxes(SMB500)areavailable.
SpecificationsNormalOperatingVoltage: 15to32VDCMaximumCurrentDraw: 6.5mA(LEDon)AverageOperatingCurrent: 375µA(LEDflashing-ingrouppollmode)350µA(LEDofflashing-indirectpollmode) 485µAMax.(LEDflashing,NACshorted)MaximumNACLineLoss: 4VDCExternalSupplyVoltage: (betweenTerminalsT3andT4) Maximum(NAC): Regulated24VDC Maximum(Speakers): 70.7VRMS,50WDrainonExternalSupply: 1.7mAMaximumusing24VDCsupply;2.2mAMaximumusing80VRMSsupplyMaxNACCurrentRatings: ForclassBwiringsystem,thecurrentratingis3A ForclassAwiringsystem,thecurrentratingis2ATemperatureRange: 32°Fto120°F(0°Cto49°C)Humidity: 10%to93%Non-condensingDimensions: 41/2˝H×4˝W×11/4˝D(Mountstoa4˝squareby21/8˝deepbox.)Accessories: SMB500ElectricalBox;CB500Barrier
MODULE
FROM PANEL OR (+) (–) TO NEXT
(+) (–)
DEVICE
(+) (–)
CONTROL
(–)
(+)
(–)
(+)
TO NEXT CONTROL MODULE LAST MODULE MUST RETURN WIRES FOR SUPERVISION
MODULE POLARITIES ARE SHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE
AUDIO CIRCUIT
3 & 4. BREAK WIRE TO ENSURE SUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE AROUND TERMINALS
ALL WIRING SHOWN IS SUPERVISED.
(+)
NOTIFIER CONTROL PANELS ONLY
PREVIOUS DEVICE
47 K EOL RESISTOR ELR-47K
32 VDC MAX. TWISTED PAIR
IS RECOMMENDED
SIGNAL LINE CIRCUIT (SLC)
(–) AUDIO AMPLIFIER, 70.7 Vrms MAX. USE ONLY MODELS AA-30, AA100 OR AA-120. AMPLIFIER
MUST PROVIDE WIRING SUPERVISION PER NFPA.
SPEAKER SWITCHING CIRCUIT - NFPA STYLE W SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFER
TO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD.
WIRES MUST BE SUPERVISED PER NFPA
ALL TERMINAL WIRING IS POWER LIMITED.
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
SUPERVISION
9
8
7
6
5 4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
TENS
ONES ADDRESS LOOP
0
7 8 6 5 4 3 2
1
9 10 11 12 13
14 15
MODULE
FROM PANEL OR(+)(–)TO NEXT
(+)(–)
DEVICE
(+)(–)
CONTROL
TO NEXT CONTROL MODULE LAST MODULE MUST RETURNWIRES FOR SUPERVISION
MODULE POLARITIES ARESHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE
AUDIO CIRCUIT
3 & 4. BREAK WIRE TO ENSURESUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE AROUND TERMINALS
ALL WIRING SHOWN IS SUPERVISED.
(+)
NOTIFIER CONTROL PANELS ONLY
PREVIOUS DEVICE
47 K EOLRESISTORIS INTERNALAT TERMINALS8 AND 9
32 VDC MAX.TWISTED PAIR
IS RECOMMENDED
SIGNAL LINE CIRCUIT (SLC)
(–) AUDIO AMPLIFIER, 70.7 Vrms MAX.USE ONLY MODELS AA-30, AA100 OR AA-120. AMPLIFIER
MUST PROVIDE WIRING SUPERVISION PER NFPA.
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFERTO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD.
WIRES MUST BE SUPERVISED PER NFPA
ALL TERMINAL WIRING IS POWER LIMITED.
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
SUPERVISION
(–)
(+)
(–)
(+)BYPASS CAPACITORS : 100
A2143-20 NONPOLARIZED <10 A LEAKAGE
9
8
7
6
5 4
3
2
1
0
012345 6 7 8 9
TENS
ONESADDRESSLOOP
0
7 865432
1
910111213
1415
Figure 5. Typical wiring for speaker supervision and switching, NFPA Style Y:
Figure 6. Typical fault tolerant wiring for speaker supervision and switching, NFPA Style Z:
C0879-01
C0880–01
CONNECT MODULES TO LISTED COMPATIBLENOTIFIER CONTROL PANELS ONLY
I56-1169-013
N500-46-00 3 I56-1169-013N500-46-00 2 I56-1169-013
MODULE
FROM PANEL OR (+) (-)
TO NEXT (+) (-)
DEVICE
(+) (-)
CONTROL
(-)
(+)
47K EOL RESISTOR ELR-47K
UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL EOLR-1
TO NEXT CONTROL MODULE OR END-OF-LINE-RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO NOTIFIER MANUAL.
MODULE POLARITIES ARE SHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE 32 VDC MAX.
IS RECOMMENDED
24 VDC CIRCUIT
3 & 4. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE ON TERMINALS
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
(-) (+)
TWISTED PAIR NOTIFIER CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
PREVIOUS DEVICE
(-)
(+)
24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.
9
8
7
6
5 4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
TENS
ONES ADDRESS LOOP
0
7 8 6 5 4 3 2
1
9 10 11 12 13
14 15
MODULE
FROM PANEL OR(+)
(–)TO NEXT
(+)
(–)
DEVICE
(+)(–)
CONTROL
(–)
(+)
(–)
(+)
UL LISTED EOL RELAYSHOWN ENERGIZED
24VDC COILEOLR-1
MODULE POLARITIES ARESHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE
24 VDC CIRCUIT
3 & 4. BREAK WIRE RUN TO PROVIDESUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE ON TERMINALS
ALL WIRING SHOWN IS SUPERVISEDAND POWER LIMITED
(+)
NOTIFIER CONTROL PANELS ONLY
PREVIOUS DEVICE
EOL RESISTOR ISINTERNAL AT
TERMINALS 8 & 9
32 VDC MAX.TWISTED PAIR
IS RECOMMENDED
SIGNAL LINE CIRCUIT (SLC)
(–) 24 VDC POWER SUPPLYISOLATED, REGULATED, POWER LIMITED PER NFPA 70.LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.
TO NEXT CONTROL MODULE OR END-OF-LINE-RELAY.ONE RELAY REQUIRED FOR EACH CIRCUIT.SOME CONTROL PANELS HAVE RELAY BUILT IN ANDDO NOT REQUIRE EXTERNAL WIRING. REFER TO NOTIFIER MANUAL.
9
8
7
6
5 4
3
2
1
0
012345 6 7 8 9
TENS
ONESADDRESSLOOP
0
7 865432
1
910111213
1415
Figure 3. Typical notification appliance circuit configuration, NFPA Style Y:
Figure 4. Typical fault tolerant notification appliance circuit configuration, NFPA Style Z:
C0821-01
C0820-01
LABEL
J1 UNDER LABEL
BACK OFMODULE
Figure 1A. Removing rotary switch stop:
Figure 2A. Module mounting with barrier:
C0219-00
C0217-00
9
8
7
6
5 4
3
2
1
0
012345 6 7 8 9
TENS
ONESADDRESSLOOP
0
7 865432
1
910111213
1415
ISOLATEDQUADRANT
01
23
4
98
76
5
0
TENS
ONES
ADDRESS
LOOP9
87654321
09
87654321 101112131415
01
23
4
98
76
5
0
TENS
ONES
ADDRESS
LOOP9
87654321
09
87654321 101112131415
Figure 1B. Jumper location:
C0458-00
Figure 2B:
C0218-00
WiringNOTE:Allwiringmustconformtoapplicablelocalcodes,ordinances,andregulations.Whenusingcontrolmodulesinnonpowerlimitedapplications,theCB500ModuleBarriermustbeusedtomeetULrequirementsfortheseparationofpower-limitedandnonpower-limitedterminalsandwiring.Thebarriermustbeinsertedintoa4˝×4˝×21/8˝junctionbox,andthecontrolmodulemustbeplacedintothebarrierandattachedtothejunctionbox(Figure2A).Thepower-limitedwiringmustbeplacedintotheisolatedquadrantofthemodulebarrier(Figure2B).
1.Installmodulewiringinaccordancewiththejobdrawingsandappropriatewiringdiagrams.2.Settheaddressonthemoduleperjobdrawings. Note:Somepanelssupportextendedaddressing.Inordertosetthemoduleaboveaddress99oncompatiblesystems,
carefullyremovethestopontheupperrotaryswitchwiththumbinthedirectionshowninFigure1A.3. Securemoduletoelectricalbox(suppliedbyinstaller),asshowninFigure2A.
IMPORTANT: WhenusingtheFCM-1forfirefightertelephoneapplications,removeJumper(J1)anddiscard.TheJumperislocatedonthebackundertheproductlabelasshowninFigure1B.Themoduledoesnotprovideringbackwhenusedasafirefightertelephonecircuit.