N500-46-00 4 I56-1169-013 ©2006Notifier

WARNING

Allrelayswitchcontactsareshippedinthestandbystate(open)state,butmayhavetransferredtotheactivated(closed)stateduringshipping.Toensurethattheswitchcontactsareintheircorrectstate,modulesmustbemadetocommunicatewiththepanelbeforeconnectingcircuitscontrolledbythemodule.

N500-46-00 1 I56-1169-013Notifier,12ClintonvilleRd.,Northford,CT06472

FCM-1 Supervised Control Module Installation And Maintenance Instructions

Before InstallingThis information is includedasaquickreference installationguide.Refer to thecontrolpanel installationmanual fordetailedsysteminformation.Ifthemoduleswillbeinstalledinanexistingoperationalsystem,informtheoperatorandlocalauthoritythatthesystemwillbetemporarilyoutofservice.Disconnectpowertothecontrolpanelbeforeinstallingthemodules.

NOTICE:Thismanualshouldbeleftwiththeowner/userofthisequipment.

General DescriptionFCM-1SupervisedControlModulesareintendedforuseinintelligent,two-wiresystems,wheretheindividualaddressofeachmoduleisselectedusingthebuilt-inrotaryswitches.Thismoduleisusedtoswitchanexternalpowersupply,whichcanbeaDCpowersupplyoranaudioamplifier(upto80VRMS),tonotificationappliances.ItalsosupervisesthewiringtotheconnectedloadsandreportstheirstatustothepanelasNORMAL,OPEN,orSHORTCIRCUIT.TheFCM-1hastwopairsofoutputterminationpointsavailableforfault-tolerantwiringandapanel-controlledLEDindicator.ThismodulecanbeusedtoreplaceaCMX-2modulethathasbeenconfiguredforsupervisedwiringoperation.

Compatibility RequirementsToensureproperoperation,thismoduleshallbeconnectedtoacompatibleNotifiersystemcontrolpanelsonly(listavail-ablefromNotifier).

MountingTheFCM-1mountsdirectlyto4˝squareelectricalboxes(seeFigure2A).Theboxmusthaveaminimumdepthof21/8˝.Surfacemountedelectricalboxes(SMB500)areavailable.

SpecificationsNormalOperatingVoltage: 15to32VDCMaximumCurrentDraw: 6.5mA(LEDon)AverageOperatingCurrent: 375µA(LEDflashing-ingrouppollmode)350µA(LEDofflashing-indirectpollmode) 485µAMax.(LEDflashing,NACshorted)MaximumNACLineLoss: 4VDCExternalSupplyVoltage: (betweenTerminalsT3andT4) Maximum(NAC): Regulated24VDC Maximum(Speakers): 70.7VRMS,50WDrainonExternalSupply: 1.7mAMaximumusing24VDCsupply;2.2mAMaximumusing80VRMSsupplyMaxNACCurrentRatings: ForclassBwiringsystem,thecurrentratingis3A ForclassAwiringsystem,thecurrentratingis2ATemperatureRange: 32°Fto120°F(0°Cto49°C)Humidity: 10%to93%Non-condensingDimensions: 41/2˝H×4˝W×11/4˝D(Mountstoa4˝squareby21/8˝deepbox.)Accessories: SMB500ElectricalBox;CB500Barrier

MODULE

FROM PANEL OR (+) (–) TO NEXT

(+) (–)

DEVICE

(+) (–)

CONTROL

(–)

(+)

(–)

(+)

TO NEXT CONTROL MODULE LAST MODULE MUST RETURN WIRES FOR SUPERVISION

MODULE POLARITIES ARE SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

AUDIO CIRCUIT

3 & 4. BREAK WIRE TO ENSURE SUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE AROUND TERMINALS

ALL WIRING SHOWN IS SUPERVISED.

(+)

NOTIFIER CONTROL PANELS ONLY

PREVIOUS DEVICE

47 K EOL RESISTOR ELR-47K

32 VDC MAX. TWISTED PAIR

IS RECOMMENDED

SIGNAL LINE CIRCUIT (SLC)

(–) AUDIO AMPLIFIER, 70.7 Vrms MAX. USE ONLY MODELS AA-30, AA100 OR AA-120. AMPLIFIER

MUST PROVIDE WIRING SUPERVISION PER NFPA.

SPEAKER SWITCHING CIRCUIT - NFPA STYLE W SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFER

TO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD.

WIRES MUST BE SUPERVISED PER NFPA

ALL TERMINAL WIRING IS POWER LIMITED.

AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.

SUPERVISION

9

8

7

6

5 4

3

2

1

0

0 1 2 3 4 5 6 7 8 9

TENS

ONES ADDRESS LOOP

0

7 8 6 5 4 3 2

1

9 10 11 12 13

14 15

MODULE

FROM PANEL OR(+)(–)TO NEXT

(+)(–)

DEVICE

(+)(–)

CONTROL

TO NEXT CONTROL MODULE LAST MODULE MUST RETURNWIRES FOR SUPERVISION

MODULE POLARITIES ARESHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

AUDIO CIRCUIT

3 & 4. BREAK WIRE TO ENSURESUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE AROUND TERMINALS

ALL WIRING SHOWN IS SUPERVISED.

(+)

NOTIFIER CONTROL PANELS ONLY

PREVIOUS DEVICE

47 K EOLRESISTORIS INTERNALAT TERMINALS8 AND 9

32 VDC MAX.TWISTED PAIR

IS RECOMMENDED

SIGNAL LINE CIRCUIT (SLC)

(–) AUDIO AMPLIFIER, 70.7 Vrms MAX.USE ONLY MODELS AA-30, AA100 OR AA-120. AMPLIFIER

MUST PROVIDE WIRING SUPERVISION PER NFPA.

SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFERTO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD.

WIRES MUST BE SUPERVISED PER NFPA

ALL TERMINAL WIRING IS POWER LIMITED.

AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.

SUPERVISION

(–)

(+)

(–)

(+)BYPASS CAPACITORS : 100

A2143-20 NONPOLARIZED <10 A LEAKAGE

9

8

7

6

5 4

3

2

1

0

012345 6 7 8 9

TENS

ONESADDRESSLOOP

0

7 865432

1

910111213

1415

Figure 5. Typical wiring for speaker supervision and switching, NFPA Style Y:

Figure 6. Typical fault tolerant wiring for speaker supervision and switching, NFPA Style Z:

C0879-01

C0880–01

CONNECT MODULES TO LISTED COMPATIBLENOTIFIER CONTROL PANELS ONLY

I56-1169-013

Page 2: FCM-1

N500-46-00 3 I56-1169-013N500-46-00 2 I56-1169-013

MODULE

FROM PANEL OR (+) (-)

TO NEXT (+) (-)

DEVICE

(+) (-)

CONTROL

(-)

(+)

47K EOL RESISTOR ELR-47K

UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL EOLR-1

TO NEXT CONTROL MODULE OR END-OF-LINE-RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO NOTIFIER MANUAL.

MODULE POLARITIES ARE SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE 32 VDC MAX.

IS RECOMMENDED

24 VDC CIRCUIT

3 & 4. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE ON TERMINALS

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

(-) (+)

TWISTED PAIR NOTIFIER CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

PREVIOUS DEVICE

(-)

(+)

24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.

9

8

7

6

5 4

3

2

1

0

0 1 2 3 4 5 6 7 8 9

TENS

ONES ADDRESS LOOP

0

7 8 6 5 4 3 2

1

9 10 11 12 13

14 15

MODULE

FROM PANEL OR(+)

(–)TO NEXT

(+)

(–)

DEVICE

(+)(–)

CONTROL

(–)

(+)

(–)

(+)

UL LISTED EOL RELAYSHOWN ENERGIZED

24VDC COILEOLR-1

MODULE POLARITIES ARESHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

24 VDC CIRCUIT

3 & 4. BREAK WIRE RUN TO PROVIDESUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE ON TERMINALS

ALL WIRING SHOWN IS SUPERVISEDAND POWER LIMITED

(+)

NOTIFIER CONTROL PANELS ONLY

PREVIOUS DEVICE

EOL RESISTOR ISINTERNAL AT

TERMINALS 8 & 9

32 VDC MAX.TWISTED PAIR

IS RECOMMENDED

SIGNAL LINE CIRCUIT (SLC)

(–) 24 VDC POWER SUPPLYISOLATED, REGULATED, POWER LIMITED PER NFPA 70.LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.

TO NEXT CONTROL MODULE OR END-OF-LINE-RELAY.ONE RELAY REQUIRED FOR EACH CIRCUIT.SOME CONTROL PANELS HAVE RELAY BUILT IN ANDDO NOT REQUIRE EXTERNAL WIRING. REFER TO NOTIFIER MANUAL.

9

8

7

6

5 4

3

2

1

0

012345 6 7 8 9

TENS

ONESADDRESSLOOP

0

7 865432

1

910111213

1415

Figure 3. Typical notification appliance circuit configuration, NFPA Style Y:

Figure 4. Typical fault tolerant notification appliance circuit configuration, NFPA Style Z:

C0821-01

C0820-01

LABEL

J1 UNDER LABEL

BACK OFMODULE

Figure 1A. Removing rotary switch stop:

Figure 2A. Module mounting with barrier:

C0219-00

C0217-00

9

8

7

6

5 4

3

2

1

0

012345 6 7 8 9

TENS

ONESADDRESSLOOP

0

7 865432

1

910111213

1415

ISOLATEDQUADRANT

01

23

4

98

76

5

0

TENS

ONES

ADDRESS

LOOP9

87654321

09

87654321 101112131415

01

23

4

98

76

5

0

TENS

ONES

ADDRESS

LOOP9

87654321

09

87654321 101112131415

Figure 1B. Jumper location:

C0458-00

Figure 2B:

C0218-00

WiringNOTE:Allwiringmustconformtoapplicablelocalcodes,ordinances,andregulations.Whenusingcontrolmodulesinnonpowerlimitedapplications,theCB500ModuleBarriermustbeusedtomeetULrequirementsfortheseparationofpower-limitedandnonpower-limitedterminalsandwiring.Thebarriermustbeinsertedintoa4˝×4˝×21/8˝junctionbox,andthecontrolmodulemustbeplacedintothebarrierandattachedtothejunctionbox(Figure2A).Thepower-limitedwiringmustbeplacedintotheisolatedquadrantofthemodulebarrier(Figure2B).

1.Installmodulewiringinaccordancewiththejobdrawingsandappropriatewiringdiagrams.2.Settheaddressonthemoduleperjobdrawings. Note:Somepanelssupportextendedaddressing.Inordertosetthemoduleaboveaddress99oncompatiblesystems,

carefullyremovethestopontheupperrotaryswitchwiththumbinthedirectionshowninFigure1A.3. Securemoduletoelectricalbox(suppliedbyinstaller),asshowninFigure2A.

IMPORTANT: WhenusingtheFCM-1forfirefightertelephoneapplications,removeJumper(J1)anddiscard.TheJumperislocatedonthebackundertheproductlabelasshowninFigure1B.Themoduledoesnotprovideringbackwhenusedasafirefightertelephonecircuit.