Length Tested Accepted Rejected Accepted Rejected (mm) (A) (R) (A) (R) 1 1260 R 2 1971 A 3 2350 R 4 628 A 5 620 R 6 540 A 7 540 R 8 540 A 9 540 A 10 830 A 11 2000 A 12 2420 A 13 2000 R Yes 10 - 15 mins. AWS D1.1 San Tierra Clubhouse Bldg. 2 February 07, 2013 Spot Weld NDT Procedure No. Sample Card No. S-10;SNAC-B2-A-Portal1;SNAC-1B-A-Stair I I 12mm SKC-S / Solvent Removable Findings / Defect Type & Size Manufacturing / Brand Part No. / Weld Joint Identification Penetrant ECDI / RLB Laboratory No. Acceptance Code INSPECTION PROCESS Item No. No Relevant Indication Rounded Indication Material Thickness No Relevant Indication Grid Line K4 Grid Line J3 Developer Type Cleaner Type LIQUID PENETRANT TESTING REPORT Address Drwng. Ref. No. Carbon Steel Location / Site ASME V Tested Item / Part Visible Client Project Name Date of Inspection Inspection Part Type Inspection Procedure Material Specification Sta. Rosa, Laguna XWELL-LPT-2009-02 Sto. Domingo, Sta.Rosa, Laguna 2013-02-LPT-001M 2013-02-005M Wide Flange Method Technique Surface Condition No Relevant Indication No Relevant Indication Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib Performed / Evaluated By: Witnessed By: Authorized Signatory: For and On-Behalf of X'Well Testing Services Inc. NDT Level II / NDT Manager Grid Line C1 Dwell Time Surface Temperature Canopy 10 Stair Portal Shed ******Nothing Follows****** Rounded Indication Examination Result Clean / Smooth Ambient No Relevant Indication Repair Post Cleaning Magnaflux SKL-SP1 / Visible Dye SKD-S2 / Non Aqueous Grid Line D2 Grid Line H'11 Excell Contractors and Developers Inc. Eric Atienza / Benjamin Aguilar Jr. Emul Time N / A No Relevant Indication Grid Line G12 No Relevant Indication Total Length Tested = 16, 239mm Grid Line G10 Grid Line M2 Grid Line A1 GridLine L'3' No Relevant Indication Rounded Indication Grid Line H10 Grid Line B2 Rounded Indication Grid Line L5 Linear Indication NDT Inspector X'WELL Form Rev.1 Page 1 of 10
Transcript
Page 1: February 07, 2013

Length

Tested Accepted Rejected Accepted Rejected

(mm) (A) (R) (A) (R)

1 1260 R

2 1971 A

3 2350 R

4 628 A

5 620 R

6 540 A

7 540 R

8 540 A

9 540 A

10 830 A

11 2000 A

12 2420 A

13 2000 R

Yes

10 - 15 mins.

AWS D1.1

San Tierra Clubhouse Bldg. 2

February 07, 2013

Spot

Weld NDT Procedure No.

Sample Card No.

S-10;SNAC-B2-A-Portal1;SNAC-1B-A-Stair I I12mm

SKC-S / Solvent Removable

Findings / Defect Type & Size

Manufacturing / Brand

Part No. / Weld Joint

Identification

Penetrant

ECDI / RLB

Laboratory No.

Acceptance Code

INSPECTION PROCESS

Item

No.

No Relevant Indication

Rounded Indication

Material Thickness

No Relevant Indication

Grid Line K4

Grid Line J3

Developer Type

Cleaner Type

LIQUID PENETRANT TESTING REPORT

Address

Drwng. Ref. No.

Carbon Steel

Location / Site

ASME V

Tested Item / Part

Visible

Client

Project Name

Date of Inspection

Inspection

Part Type

Inspection Procedure

Material Specification

Sta. Rosa, Laguna

XWELL-LPT-2009-02

Sto. Domingo, Sta.Rosa, Laguna

2013-02-LPT-001M

2013-02-005M

Wide Flange

Method Technique

Surface Condition

No Relevant Indication

No Relevant Indication

Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib

Performed / Evaluated By: Witnessed By: Authorized Signatory:

For and On-Behalf of X'Well Testing Services Inc.

NDT Level II / NDT Manager

Grid Line C1

Dwell Time

Surface Temperature

Canopy 10

Stair

Portal Shed

******Nothing Follows******

Rounded Indication

Examination Result

Clean / Smooth

Ambient

No Relevant Indication

Repair

Post Cleaning

Magnaflux

SKL-SP1 / Visible Dye

SKD-S2 / Non Aqueous

Grid Line D2

Grid Line H'11

Excell Contractors and Developers Inc.

Eric Atienza / Benjamin Aguilar Jr.

Emul Time N / A

No Relevant Indication

Grid Line G12 No Relevant Indication

Total Length Tested = 16, 239mm

Grid Line G10

Grid Line M2

Grid Line A1

GridLine L'3'

No Relevant Indication

Rounded Indication

Grid Line H10

Grid Line B2 Rounded Indication

Grid Line L5 Linear Indication

NDT Inspector

X'WELL Form Rev.1 Page 1 of 10

Page 2: February 07, 2013

SCE

SCE

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Eric Atienza / Benjamin Aguilar Jr. Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib

NDT Inspector ECDI / RLBNDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

Performed / Evaluated By: Witnessed By: Authorized Signatory:

LEGEND:

Accepted

Rejected

GRID LINE J3

BUTT WELD @ JOINT CONNECTION AT GRID LINE J3

GLJ3

LEFT SIDE

RIGHT SIDE

GLJ3

GL J 3BOTTOM

GLJ3TOP

GRID LINE K4

FILLET WELD @ JOINT CONNECTION AT GRID LINE J3

X'WELL Form Rev.1 Page 2 of 10

Page 3: February 07, 2013

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Edison A. Walit / Nima Khatib

NDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

Authorized Signatory:

X'WELL Form Rev.1 Page 2 of 10

Page 4: February 07, 2013

SCE

SCE

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Performed / Evaluated By: Witnessed By: Authorized Signatory:

Eric Atienza / Benjamin Aguilar Jr. Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib

LEGEND:

Accepted

Rejected

NDT Inspector ECDI / RLBNDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

GLL5

GRID LINE L5

BUTT WELD @ JOINT CONNECTION AT GRID LINE L5

RIGHT SIDE LEFT SIDE

GLL5

FILLET WELD @ JOINT CONNECTION AT GRID LINE L5

GLL5TOP

GLL5BOTTOM

GRID LINE L'3'

FILLET WELD @ JOINT CONNECTION AT GRID LINE L'3'

GLL'3'

X'WELL Form Rev.1 Page 3 of 10

Page 5: February 07, 2013

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Authorized Signatory:

Edison A. Walit / Nima Khatib

NDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

X'WELL Form Rev.1 Page 3 of 10

Page 6: February 07, 2013

SCE

SCE

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Performed / Evaluated By: Witnessed By: Authorized Signatory:

Eric Atienza / Benjamin Aguilar Jr. Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib

LEGEND:

Accepted

Rejected

NDT Inspector ECDI / RLBNDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

GRID LINE M2

BUTT WELD @ JOINT CONNECTION AT GRID LINE M2

GLL3

GRID LINE A1

FILLET WELD @ JOINT CONNECTION AT GRID LINE A1

GLA1

X'WELL Form Rev.1 Page 4 of 10

Page 7: February 07, 2013

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Authorized Signatory:

Edison A. Walit / Nima Khatib

NDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

X'WELL Form Rev.1 Page 4 of 10

Page 8: February 07, 2013

SCE

SCE

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Performed / Evaluated By: Witnessed By: Authorized Signatory:

Eric Atienza / Benjamin Aguilar Jr. Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib

LEGEND:

Accepted

Rejected

NDT Inspector ECDI / RLBNDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

GRID LINE B2

FILLET WELD @ JOINT CONNECTION AT GRID LINE B2

GRID LINE C1

FILLET WELD @ JOINT CONNECTION AT GRID LINE C1

GRID LINE D2

FILLET WELD @ JOINT CONNECTION AT GRID LINE D2

GRID LINE G10

FILLET WELD @ JOINT CONNECTION AT GRID LINE G10

GLG10

GLB2 GLC1 GLD2

X'WELL Form Rev.1 Page 5 of 10

Page 9: February 07, 2013

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Authorized Signatory:

Edison A. Walit / Nima Khatib

NDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

WELD @ JOINT CONNECTION AT GRID LINE D2

X'WELL Form Rev.1 Page 5 of 10

Page 10: February 07, 2013

SCE

SCE

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Performed / Evaluated By: Witnessed By: Authorized Signatory:

Eric Atienza / Benjamin Aguilar Jr. Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib

LEGEND:

Accepted

Rejected

NDT Inspector ECDI / RLBNDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

GRID LINE G12

FILLET WELD @ JOINT CONNECTION AT GRID LINE G12

GLG12 BOTTOM

GRID LINE H10

BUTT WELD @ JOINT CONNECTION AT GRID LINE H10

GLH10

RIGHT SIDE

GLH10

LEFT SIDE

X'WELL Form Rev.1 Page 6 of 10

Page 11: February 07, 2013

LIQUID PENETRANT TESTING REPORT

Sketch Detail / Part / Joint Location

Authorized Signatory:

Edison A. Walit / Nima Khatib

NDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

X'WELL Form Rev.1 Page 6 of 10

Page 12: February 07, 2013

SCE

SCE

NDT Inspector ECDI / RLBNDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

Performed / Evaluated By: Witnessed By: Authorized Signatory:

Eric Atienza / Benjamin Aguilar Jr. Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib

LEGEND:

Accepted

Rejected

Sketch Detail / Part / Joint Location

LIQUID PENETRANT TESTING REPORT

GRID LINE H'11

FILLET WELD @ JOINT CONNECTION AT GRID LINE H'11

GLH'11

GLH'11

GLH'11

BUTT WELD @ JOINT CONNECTION AT GRID LINE H'11

X'WELL Form Rev.1 Page 7 of 10

Page 13: February 07, 2013

NDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

Authorized Signatory:

Edison A. Walit / Nima Khatib

Sketch Detail / Part / Joint Location

LIQUID PENETRANT TESTING REPORT

X'WELL Form Rev.1 Page 7 of 10

Page 14: February 07, 2013

SCE

SCE

NDT Inspector ECDI / RLBNDT Level II / NDT Manager

For and On-Behalf of X'Well Testing Services Inc.

Performed / Evaluated By: Witnessed By: Authorized Signatory:

Eric Atienza / Benjamin Aguilar Jr. Mario Valdez / Dean Valencia Edison A. Walit / Nima Khatib

LEGEND:

Accepted

Rejected

Sketch Detail / Part / Joint Location

LIQUID PENETRANT TESTING REPORT

X'WELL Form Rev.1 Page 8 of 10


Recommended