10
Applications Product Features Type: None / manual speed controller / small scale centralized speed controller Speed Controller Casing Construction Material: Galvalume / stainless steel / aluminium High efficiency blower Low Energy Consumption High total static pressure Low Noise Level FFU Sound Pressure Level Curve (Octave Band) Uniformity of Air Distribution SPL dB(A) NC70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30 NC25 NC20 NC15 90 80 70 60 50 40 30 20 10 0 63 125 250 500 1000 2000 4000 8000 Ensure the deviation of face velocity is within ±10% Frequency (Hz) FFU Octave Band Sound Pressure Level Curve Fan Filter Unit FFU Air Velocity Distribution 3D Diagram High Efficiency, Low noise level Air inlet prefilter, downstream diffuser, pressure gauge, pressure guage port for filter pressure drop monitoring, cleanliness monitoring port, DOP testing port, air inlet collar, five-speed controller, humidity monitoring port, remote control, European plug and others Optional Accessories Uniform Air Flow Distribution 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 V(m/s) Semiconductor Food Processing Industry Pharmaceutical & Laboratories Cleanroom FFU Clean Air · Our Future www.mayairgroup.com 52
Transcript

Applications

Product Features

Type: None / manual speed controller / smallscale centralized speed controller

Speed Controller

Casing ConstructionMaterial: Galvalume / stainless steel / aluminium

High efficiency blowerLow Energy Consumption

High total static pressureLow Noise Level

FFU Sound Pressure Level Curve (Octave Band)

Uniformity of Air Distribution

SPL dB(A)

NC70NC65NC60NC55NC50NC45NC40NC35NC30NC25NC20NC15

90

80

70

60

50

40

30

20

10

063 125 250 500 1000 2000 4000 8000

Ensure the deviation of face velocity is within ±10%

Frequency (Hz) FFU Octave Band Sound Pressure Level Curve

Fan Filter Unit

FFU

Air Velocity Distribution 3D Diagram

High Efficiency, Low noise level

Air inlet prefilter, downstream diffuser, pressuregauge, pressure guage port for filter pressure dropmonitoring, cleanliness monitoring port, DOPtesting port, air inlet collar, five-speed controller,humidity monitoring port, remote control, Europeanplug and others

Optional Accessories

Uniform Air Flow Distribution

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0.0

V(m

/s)

Semiconductor

Food ProcessingIndustry

Pharmaceutical& Laboratories

Cleanroom

FFU

Clean Air· Our Futurewww.mayairgroup.com

52

Fan Filter Unit

FFU

SERIES F-22AL F-23AL F-24AL F-24AM

WxL(mm) 250

AC Motor Technical Data

Series F-22AL F-23AL

WxL (mm) 600x600/575x575 600x900/575x875 600x1200/575x1175

H (mm)Air Velocity (m/s)

Static Pressure (Pa)

Power Consumption (W)

Noise Level dB(A)

Vibration Level (mm/s)

0.45

250

80

50

0.7

F-24AM

2750.45

310

155

53

1.2

0.45

220

110

51

0.8

250

Series F-34AM F-34AH

WxL (mm) 900x1200/875x1175 1200x1200/1175x1175

H (mm)Air Velocity (m/s)

Static Pressure (Pa)

Power Consumption (W)

Noise Level dB(A)

Vibration Level (mm/s)

F-44AHF-44AM1

Power Input: 1 220V - 240V 50Hz

2750.45

250

175

53.5

1.2

2750.45

275

225

53

1.2

0.45

205

245

55

1.3

2750.45

285

305

53.5

1.4

275

250

EC Motor Technical Data

Series F-22EL F-23EL

WxL(mm) 600x600/575x575 600x900/575x875 600x1200/575x1175

H(mm)Air Velocity (m/s)

Static Pressure (Pa)

Power Consumption (W)

Noise Level dB(A)

Vibration Level (mm/s)

0.45

270

55

49

0.7

F-24EM

2750.45

415

90

51

1.2

F-24EL

2500.45

210

85

51.5

1.2

0.45

250

70

50.5

0.8

250

Series F-34EM F-34EH

WxL (mm) 900x1200/875x1175 1200x1200/1175x1175

H (mm)Air Velocity (m/s)

Static Pressure (Pa)

Power Consumption (W)

Noise Level dB(A)

Vibration Level (mm/s)

F-44EH

2750.45

320

120

53

1.2

2750.45

430

125

52.5

1.2

0.45

360

180

53.5

1.4

275

Power Input: 1 200V - 277V 50Hz

Remarks: 1. Test point of noise is 1.5m below filter downstream. 2. Test point of air velocity is 0.15m below the filter. 3. FFU sizes can be customised upon request. 4. FFU power consumption in above tables is based on FFU initial performance.

FFU

Clean Air· Our Futurewww.mayairgroup.com

53

FFUFan Filte r UnitFFU Performance Curves

Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-22AL)

300

250

200

150

100

50

0

160

140

120

100

180

60

40

20

0

500 1000 1500 2000

Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-24AM)

320

280

240

200

160

120

80

40

0

400

350

300

250

200

150

100

50

0

500 1000 1500 2000 2500 3000

Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-23AL)

300

250

200

150

100

50

0

160

140

120

100

180

60

40

20

0

500 1000 1500 2000Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-34AM)

320

280

240

200

160

120

80

40

0

400

350

300

250

200

150

100

50

0

500 1000 1500 2000 2500 3000

AC Motor

Total Static Pressure - Air Flow curve Power - Air Flow curve HEPA/ULPA filter initial pressure drop - Air Flow curve (Thickness: 70mm)

FFU

Clean Air· Our Futurewww.mayairgroup.com

54

FFUFan Filter UnitFFU Performance Curves

AC Motor

Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-34AH)

400

380

360

340

320

300

280

260

240

220

200

500

450

400

350

300

250

200

150

100

50

0

0 500 1000 1500 2000 2500 3000 3500

Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-44AH)

400

380

360

340

320

300

280

260

240

220

200

500

450

400

350

300

250

200

150

100

50

0

0 500 1000 1500 2000 2500 3000 3500

Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-44AM1)

400

350

300

250

200

150

100

50

0

310

290

270

250

230

210

190

170

150

0 500 1000 1500 2000 2500 3000

Total Static Pressure - Air Flow curve Power - Air Flow curve HEPA/ULPA filter initial pressure drop - Air Flow curve (Thickness: 70mm)

FFU

Clean Air· Our Futurewww.mayairgroup.com

55

FFUFan Filter UnitFFU Performance Curves

EC Motor

Total Static Pressure (Pa)

Power (W

)

300

250

200

150

100

50

0

160

140

120

100

180

60

40

20

0

Air Flow (CMH)FFU Performence Curve (F-22EL)

0 500 1000 1500 2000Total Static Pressure (Pa)

Power (W

)

300

250

200

150

100

50

0

160

140

120

100

180

60

40

20

0

Air Flow (CMH)FFU Performence Curve (F-23EL)

0 500 1000 1500 2000

Total Static Pressure (Pa)

Power (W

)

300

250

200

150

100

50

0

160

140

120

100

180

60

40

20

0

Air Flow (CMH)FFU Performence Curve (F-24EL)

0 500 1000 1500 2000 0 500 1000 1500 2000 2500 3000

Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-24EM)

300

270

240

210

190

150

120

90

60

30

0

500

450

400

350

300

250

200

150

100

50

0

Total Static Pressure - Air Flow curve Power - Air Flow curve HEPA/ULPA filter initial pressure drop - Air Flow curve (Thickness: 70mm)

FFU

Clean Air· Our Futurewww.mayairgroup.com

56

0 500 1000 1500 2000 2500 3000

Total Static Pressure (Pa)

Power (W

)

Air Flow (CMH)FFU Performence Curve (F-34EM)

300

270

240

210

190

150

120

90

60

3 0

0

500

450

400

350

300

250

200

150

100

50

0

FFUFan Filter UnitFFU Performance Curves

EC Motor

0 500 1000 1500 2000 2500 3000 3500Total Static Pressure (Pa)

Power (W

)

500

450

400

350

300

250

200

150

100

50

0

400

360

320

280

240

200

160

120

80

40

0

Air Flow (CMH)FFU Performence Curve (F-34EH)

0 500 1000 1500 2000 2500 3000 3500

Total Static Pressure (Pa)

Power (W

)

500

450

400

350

300

250

200

150

100

50

0

400

360

320

280

240

200

160

120

80

40

0

Air Flow (CMH)FFU Performence Curve (F-44EH)

Total Static Pressure - Air Flow curve Power - Air Flow curve HEPA/ULPA filter initial pressure drop - Air Flow curve (Thickness: 70mm)

FFU

Clean Air· Our Futurewww.mayairgroup.com

57

Fan Filter UnitAC FFU Group Control System

FFU Group Controller

Power Supply Indicator

Malfunction Indicator

Group Controller

FFU Group Controller Box

Multiple FFU Group Controller

Zone Controller

Zone Controller

Multiple FFU Touch Screen Control Product Features

• Reliable FFU alternating current control system.• Group or single unit alarm indicator.• 3-stage or 5-stsage fan speed controller.• Over-current protection.• RS-485 communication mode can perform. remote control on the systems.

FFU

Clean Air· Our Futurewww.mayairgroup.com

58

HUB

RS-232 / 485 Converter

HUB

HUB

MayAir FCS AC FFU Group Control System

Fan Filter UnitAC FFU Group Control System

Product Features

Overcomes large-scale FFU alternating current controlproblem with comprehensive functions.

Multiple working areas/zones group control allows FFUthat are distributed at different floors or different locationsto be controlled according to working area/zone. It alsoallows FFU in same working area/zone but located in different room to be controlled according to group.

RS-485 communication module, integrated hardwareinstallation, system low investment and easy installation.

Centralised control of FFU’s initiation, stop, fan speedand timing. Operation of the system is simpleand energy saving.

Auto display of fan speed and FFU malfunctionindicator allow accrate positioning of FFU and diagnosethe fault message.

Auto initialisation of FFU by group sequence preventspower supply disruption due to large-scale systembeing initiated synchrnously at the same time.

4-stage password control system allows acomprehensive and easy management of user.

User-friendly system incorporated with multiple languages such as English, simplified Chinese and traditionalChinese, suitable for users from different countries and regions.

FFU initiation utilizes low current, thus prevents power supply disruption.

FFU

Clean Air· Our Futurewww.mayairgroup.com

59

Fan Filter UnitEC FFU Group Control System

Repeater

RS-232 / 485 Converter

TCP / IP network(Internet/LAN)

Repeater

Ethernet Switch

I/O modulePLC module (not include in the system)

MayAir EFCS EC FFU Group Control System Product Features

Multiple working areas/zones group control allows FFU that are distributed at different floors or different locations to becontrolled according to working area/zone. It also allows FFU in same working area/zone but located in different room to be controlled according to group.

RS-485 communication module, integrated hardware installation, system low investment and easy installation.

Centralised control of FFU’s initiation, stop, fan speed and timing. Operation of the system is simple and energy saving.

Can operate together with user’s fire alarm system bysynchronising fire alarm grouping with FFU grouping.This allows FFU to slow down or cease operation accordingto the fire alarm signal.

Upon receiving of fire alarm signal, the system will alarm via sound and light system.

Auto display of fan speed and FFU malfunction indicatorallow accrate positioning of FFU and diagnose the fault message.

User can monitor FFU through internet or intranet.

4-stage password control system allows a comprehensive and easy management of user.

User-friendly system incorporated with multiple languagessuch as English, simplified Chinese and traditional Chinese,suitable for users from different countries and regions.

FFU initiation utilizes low current, thus prevents power supplydisruption.

FFU

Clean Air· Our Futurewww.mayairgroup.com

60

Fan Filter UnitFLONET FFU Group Control System

MayAir FLONET Direct Current FFU Group Control System Product Features

High control capacityAble to perform real-time monitoring and control 50,000units FFU.

Short response time.

Convenient installation through ID registration.

Remote control of MayAir FLONET system.

OPC communication protocol.

Optional email service function.

Difference color display feature to indicate the FFU working condition.

Able to perform individual toom, area and all FFU control. This control is done by feature shown in software as individual/ port/ server/ all FFU.

Mouseover function on FFU for speed and exact address display.

Operationg and error log can be recorded by the system.

Able to indicate individual FFU power consumption.

Perform real-time statistic of FFU condition for the whole system.

Timer setting function in MayAir FLONETAble to set FFU operation according to the working hours in factory.