Applications
Product Features
Type: None / manual speed controller / smallscale centralized speed controller
Speed Controller
Casing ConstructionMaterial: Galvalume / stainless steel / aluminium
High efficiency blowerLow Energy Consumption
High total static pressureLow Noise Level
FFU Sound Pressure Level Curve (Octave Band)
Uniformity of Air Distribution
SPL dB(A)
NC70NC65NC60NC55NC50NC45NC40NC35NC30NC25NC20NC15
90
80
70
60
50
40
30
20
10
063 125 250 500 1000 2000 4000 8000
Ensure the deviation of face velocity is within ±10%
Frequency (Hz) FFU Octave Band Sound Pressure Level Curve
Fan Filter Unit
FFU
Air Velocity Distribution 3D Diagram
High Efficiency, Low noise level
Air inlet prefilter, downstream diffuser, pressuregauge, pressure guage port for filter pressure dropmonitoring, cleanliness monitoring port, DOPtesting port, air inlet collar, five-speed controller,humidity monitoring port, remote control, Europeanplug and others
Optional Accessories
Uniform Air Flow Distribution
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
V(m
/s)
Semiconductor
Food ProcessingIndustry
Pharmaceutical& Laboratories
Cleanroom
FFU
Clean Air· Our Futurewww.mayairgroup.com
52
Fan Filter Unit
FFU
SERIES F-22AL F-23AL F-24AL F-24AM
WxL(mm) 250
AC Motor Technical Data
Series F-22AL F-23AL
WxL (mm) 600x600/575x575 600x900/575x875 600x1200/575x1175
H (mm)Air Velocity (m/s)
Static Pressure (Pa)
Power Consumption (W)
Noise Level dB(A)
Vibration Level (mm/s)
0.45
250
80
50
0.7
F-24AM
2750.45
310
155
53
1.2
0.45
220
110
51
0.8
250
Series F-34AM F-34AH
WxL (mm) 900x1200/875x1175 1200x1200/1175x1175
H (mm)Air Velocity (m/s)
Static Pressure (Pa)
Power Consumption (W)
Noise Level dB(A)
Vibration Level (mm/s)
F-44AHF-44AM1
Power Input: 1 220V - 240V 50Hz
2750.45
250
175
53.5
1.2
2750.45
275
225
53
1.2
0.45
205
245
55
1.3
2750.45
285
305
53.5
1.4
275
250
EC Motor Technical Data
Series F-22EL F-23EL
WxL(mm) 600x600/575x575 600x900/575x875 600x1200/575x1175
H(mm)Air Velocity (m/s)
Static Pressure (Pa)
Power Consumption (W)
Noise Level dB(A)
Vibration Level (mm/s)
0.45
270
55
49
0.7
F-24EM
2750.45
415
90
51
1.2
F-24EL
2500.45
210
85
51.5
1.2
0.45
250
70
50.5
0.8
250
Series F-34EM F-34EH
WxL (mm) 900x1200/875x1175 1200x1200/1175x1175
H (mm)Air Velocity (m/s)
Static Pressure (Pa)
Power Consumption (W)
Noise Level dB(A)
Vibration Level (mm/s)
F-44EH
2750.45
320
120
53
1.2
2750.45
430
125
52.5
1.2
0.45
360
180
53.5
1.4
275
Power Input: 1 200V - 277V 50Hz
Remarks: 1. Test point of noise is 1.5m below filter downstream. 2. Test point of air velocity is 0.15m below the filter. 3. FFU sizes can be customised upon request. 4. FFU power consumption in above tables is based on FFU initial performance.
FFU
Clean Air· Our Futurewww.mayairgroup.com
53
FFUFan Filte r UnitFFU Performance Curves
Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-22AL)
300
250
200
150
100
50
0
160
140
120
100
180
60
40
20
0
500 1000 1500 2000
Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-24AM)
320
280
240
200
160
120
80
40
0
400
350
300
250
200
150
100
50
0
500 1000 1500 2000 2500 3000
Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-23AL)
300
250
200
150
100
50
0
160
140
120
100
180
60
40
20
0
500 1000 1500 2000Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-34AM)
320
280
240
200
160
120
80
40
0
400
350
300
250
200
150
100
50
0
500 1000 1500 2000 2500 3000
AC Motor
Total Static Pressure - Air Flow curve Power - Air Flow curve HEPA/ULPA filter initial pressure drop - Air Flow curve (Thickness: 70mm)
FFU
Clean Air· Our Futurewww.mayairgroup.com
54
FFUFan Filter UnitFFU Performance Curves
AC Motor
Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-34AH)
400
380
360
340
320
300
280
260
240
220
200
500
450
400
350
300
250
200
150
100
50
0
0 500 1000 1500 2000 2500 3000 3500
Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-44AH)
400
380
360
340
320
300
280
260
240
220
200
500
450
400
350
300
250
200
150
100
50
0
0 500 1000 1500 2000 2500 3000 3500
Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-44AM1)
400
350
300
250
200
150
100
50
0
310
290
270
250
230
210
190
170
150
0 500 1000 1500 2000 2500 3000
Total Static Pressure - Air Flow curve Power - Air Flow curve HEPA/ULPA filter initial pressure drop - Air Flow curve (Thickness: 70mm)
FFU
Clean Air· Our Futurewww.mayairgroup.com
55
FFUFan Filter UnitFFU Performance Curves
EC Motor
Total Static Pressure (Pa)
Power (W
)
300
250
200
150
100
50
0
160
140
120
100
180
60
40
20
0
Air Flow (CMH)FFU Performence Curve (F-22EL)
0 500 1000 1500 2000Total Static Pressure (Pa)
Power (W
)
300
250
200
150
100
50
0
160
140
120
100
180
60
40
20
0
Air Flow (CMH)FFU Performence Curve (F-23EL)
0 500 1000 1500 2000
Total Static Pressure (Pa)
Power (W
)
300
250
200
150
100
50
0
160
140
120
100
180
60
40
20
0
Air Flow (CMH)FFU Performence Curve (F-24EL)
0 500 1000 1500 2000 0 500 1000 1500 2000 2500 3000
Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-24EM)
300
270
240
210
190
150
120
90
60
30
0
500
450
400
350
300
250
200
150
100
50
0
Total Static Pressure - Air Flow curve Power - Air Flow curve HEPA/ULPA filter initial pressure drop - Air Flow curve (Thickness: 70mm)
FFU
Clean Air· Our Futurewww.mayairgroup.com
56
0 500 1000 1500 2000 2500 3000
Total Static Pressure (Pa)
Power (W
)
Air Flow (CMH)FFU Performence Curve (F-34EM)
300
270
240
210
190
150
120
90
60
3 0
0
500
450
400
350
300
250
200
150
100
50
0
FFUFan Filter UnitFFU Performance Curves
EC Motor
0 500 1000 1500 2000 2500 3000 3500Total Static Pressure (Pa)
Power (W
)
500
450
400
350
300
250
200
150
100
50
0
400
360
320
280
240
200
160
120
80
40
0
Air Flow (CMH)FFU Performence Curve (F-34EH)
0 500 1000 1500 2000 2500 3000 3500
Total Static Pressure (Pa)
Power (W
)
500
450
400
350
300
250
200
150
100
50
0
400
360
320
280
240
200
160
120
80
40
0
Air Flow (CMH)FFU Performence Curve (F-44EH)
Total Static Pressure - Air Flow curve Power - Air Flow curve HEPA/ULPA filter initial pressure drop - Air Flow curve (Thickness: 70mm)
FFU
Clean Air· Our Futurewww.mayairgroup.com
57
Fan Filter UnitAC FFU Group Control System
FFU Group Controller
Power Supply Indicator
Malfunction Indicator
Group Controller
FFU Group Controller Box
Multiple FFU Group Controller
Zone Controller
Zone Controller
Multiple FFU Touch Screen Control Product Features
• Reliable FFU alternating current control system.• Group or single unit alarm indicator.• 3-stage or 5-stsage fan speed controller.• Over-current protection.• RS-485 communication mode can perform. remote control on the systems.
FFU
Clean Air· Our Futurewww.mayairgroup.com
58
HUB
RS-232 / 485 Converter
HUB
HUB
MayAir FCS AC FFU Group Control System
Fan Filter UnitAC FFU Group Control System
Product Features
Overcomes large-scale FFU alternating current controlproblem with comprehensive functions.
Multiple working areas/zones group control allows FFUthat are distributed at different floors or different locationsto be controlled according to working area/zone. It alsoallows FFU in same working area/zone but located in different room to be controlled according to group.
RS-485 communication module, integrated hardwareinstallation, system low investment and easy installation.
Centralised control of FFU’s initiation, stop, fan speedand timing. Operation of the system is simpleand energy saving.
Auto display of fan speed and FFU malfunctionindicator allow accrate positioning of FFU and diagnosethe fault message.
Auto initialisation of FFU by group sequence preventspower supply disruption due to large-scale systembeing initiated synchrnously at the same time.
4-stage password control system allows acomprehensive and easy management of user.
User-friendly system incorporated with multiple languages such as English, simplified Chinese and traditionalChinese, suitable for users from different countries and regions.
FFU initiation utilizes low current, thus prevents power supply disruption.
•
•
•
•
•
•
•
•
•
FFU
Clean Air· Our Futurewww.mayairgroup.com
59
Fan Filter UnitEC FFU Group Control System
Repeater
RS-232 / 485 Converter
TCP / IP network(Internet/LAN)
Repeater
Ethernet Switch
I/O modulePLC module (not include in the system)
MayAir EFCS EC FFU Group Control System Product Features
Multiple working areas/zones group control allows FFU that are distributed at different floors or different locations to becontrolled according to working area/zone. It also allows FFU in same working area/zone but located in different room to be controlled according to group.
RS-485 communication module, integrated hardware installation, system low investment and easy installation.
Centralised control of FFU’s initiation, stop, fan speed and timing. Operation of the system is simple and energy saving.
Can operate together with user’s fire alarm system bysynchronising fire alarm grouping with FFU grouping.This allows FFU to slow down or cease operation accordingto the fire alarm signal.
Upon receiving of fire alarm signal, the system will alarm via sound and light system.
Auto display of fan speed and FFU malfunction indicatorallow accrate positioning of FFU and diagnose the fault message.
User can monitor FFU through internet or intranet.
4-stage password control system allows a comprehensive and easy management of user.
User-friendly system incorporated with multiple languagessuch as English, simplified Chinese and traditional Chinese,suitable for users from different countries and regions.
FFU initiation utilizes low current, thus prevents power supplydisruption.
•
•
•
•
•
•
•
•
•
•
FFU
Clean Air· Our Futurewww.mayairgroup.com
60
Fan Filter UnitFLONET FFU Group Control System
MayAir FLONET Direct Current FFU Group Control System Product Features
High control capacityAble to perform real-time monitoring and control 50,000units FFU.
Short response time.
Convenient installation through ID registration.
Remote control of MayAir FLONET system.
OPC communication protocol.
Optional email service function.
Difference color display feature to indicate the FFU working condition.
Able to perform individual toom, area and all FFU control. This control is done by feature shown in software as individual/ port/ server/ all FFU.
Mouseover function on FFU for speed and exact address display.
Operationg and error log can be recorded by the system.
Able to indicate individual FFU power consumption.
Perform real-time statistic of FFU condition for the whole system.
Timer setting function in MayAir FLONETAble to set FFU operation according to the working hours in factory.
3 level of authorities:Administrator, operator and guest for high security.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
I/O Module
GatewayGatewayGateway
Converter
I/O Module
FFU
Clean Air· Our Futurewww.mayairgroup.com
61