Fiberglass Reinforced Plastics (FRP) as the
Construction Material of Chimney Liners
and Ducts in Power Plants with Bypass
Conditions and Temperatures up to 300⁰C
Author: Jelle WARNAR, Robert KOENIS
Company: Plasticon Composites
Country: The Netherlands
Index
1. Introduction ............................................................................................................................ 3
1.1 Ambient Air Quality ......................................................................................................... 3
1.2 Flue Gas Desulphurization ............................................................................................... 3
1.3 Reconsideration of material used for construction ........................................................... 3
1.4 Bypass conditions ............................................................................................................. 4
1.5 Temperature resistance of FRP ........................................................................................ 4
1.6 In reality ........................................................................................................................... 5
2. General assumptions and information .................................................................................... 6
2.1 No track record ................................................................................................................. 6
2.2 In short: construction of a FRP laminate .......................................................................... 6
2.2.1 Glass material ................................................................................................................ 6
2.2.2 Resin .............................................................................................................................. 7
2.2.3 HDT of a resin ............................................................................................................... 8
2.3 Calculation methods ......................................................................................................... 8
2.3.1 Example of the assessment of an FRP construction ...................................................... 8
3. Research for temperatures up to 300° Celsius ..................................................................... 10
3.1 Impact of temperature .................................................................................................... 10
3.1.1 Laminate temperature .................................................................................................. 10
3.2 Load design .................................................................................................................... 10
4. The theory behind a high temperature .................................................................................. 12
4.1 Design base .................................................................................................................... 12
4.2 Laminate and stiffeners .................................................................................................. 13
4.3 Check of design / axial stress (dead weight, process & thermal expansion).................. 15
4.4 Check of design / buckling factor (from external pressure) ........................................... 16
5. Degradation of mechanical properties ................................................................................. 17
5.1 Tensile tests by Indian Institute of Technology, Madras ............................................... 17
5.3 Bending tests by University of Aachen .......................................................................... 18
5.4 Outcome of the tests ....................................................................................................... 18
6. Conclusion ............................................................................................................................ 20
1. Introduction
1.1 Ambient Air Quality
As of January 1st, this year, the Indian Government revised the environmental norms for thermal
power plants to cut pollution. The new standard is aimed at reducing emission of particulate
matter (PM), Sulphur Dioxide, and Oxide of Nitrogen, which will in turn help bring about an
improvement in the Ambient Air Quality (AAQ) in and around thermal power stations in India.
This means, India wants to enhance the quality of the air which has positive effects for people’s
health.
1.2 Flue Gas Desulphurization
There are several process techniques available to reduce the Sulphur Dioxide emissions. One
of the proven technologies in Europe and the USA is wet Flue Gas Desulphurization (wet FGD).
This emission technique (removal of ≥ 97.5% of SO2) demands a different design of the thermal
power plant and the use of other materials.
Figure 1: FGD process
1.3 Reconsideration of material used for construction
Back, when FGD found its origin, engineers designed the best equipment for the FGD systems.
The equipment has to endure aggressive gasses and chemicals, this would mean conventional
materials such as steel were analysed and the choice of material was reconsidered. Classic
materials, like mild or stainless steel would corrode within 1-3 years in the wet FGD
installation, making them less suitable and costly. After research, engineers selected FRP,
Fiberglass Reinforced Plastics. And since the eighties, power stations with FGD systems were
equipped with FRP products. This selection of material has proven to be a success and case
histories from then on were built. Not only has FRP proven its excellent corrosion resistance
properties, the mechanical strength and performance at high temperatures were characteristics
contributing to lifetimes of liners more than 30 years with hardly any maintenance. An
extensive low cost of ownership for plant owners was realized.
Chemical Max. concentration
H₂O 25.6 [vol%]
SO₂ 2,500 [mg/m3]
SO₃ 20 [mg/m3]
HCl 20 - 200 [mg/m3]
HF 5 – 30 [mg/m3]
CO 500 [mg/m3]
NOₓ 400 [mg/m3]
Figure 2: The composition of the flue gas
1.4 Bypass conditions
Very often, FGD systems are being added to existing power stations, in other words
‘refurbishments’ of the existing absorbers, chimneys and ducts. Shutting down a running station
would mean a great loss of income. So, in order to keep the power supply, continue as much as
possible (depending on the structure and layout of each power plant), replacement of the ducts
and liners is done in different phases, each gas outlet system is handled one by one. During each
step, a liner is replaced and a bypass system is set up. A bypass duct system is installed and
gasses from the absorber will be transported temporarily through this bypass to a new or
existing chimney.
Obviously, this approach influences the capacity of the station. Power engineers have proven
this solution throughout the past decades, when many coal-fired power stations were
refurbished. These measurements enabled plant owners to avoid major losses.
This requirement however is important to take in consideration when determining the design
requirements for the FRP equipment. This is because the design conditions between operating
and during bypass conditions is vastly different when the wet FGD (WFGD) scrubber is online.
Figure 3: FRP Bypass system at Power Station Poland (2014)
1.5 Temperature resistance of FRP
For a normal set up FGD process, FRP has proven itself to be excellent choice of material for
ducts and liners. Under normal circumstances, a wet FGD installation operates at a temperature
of about 70°C. Therefore engineers cope with the question: how would FRP perform during
bypass conditions? Process engineers examined the circumstances during a bypass operation.
Chemical resistance, mechanical strength and practical topics (easy to construct?) turned out to
be nonetheless a reason to stick with FRP. However, engineers defined the operating
temperature under severe bypass conditions to be unregular and high peeks could occur.
The bypass system however has to be designed for an excursion temperature up to 300 °Celsius
(30 min).
1.6 In reality
Practically, it turns out that during start up after a shutdown, the power plant firstly uses with
heavy oil under bypass condition. During by-pass operation, the temperature of the system can
reach temperatures up to max 165°C and with maximum SO2 concentrations. During operation,
there is a small possibility that once in the lifetime of a power plant, the temperature of the flue
gas will go up to a temperature of 300°C for no longer than a period of 30 minutes.
Different engineering companies in India have stated that this is a condition that should be taken
in count. The reason might be that all possible risks must of course be avoided. Besides, the
refurbishment constructions of existing coal-fired power stations with FGD systems is
something relatively unknown for the Indian market.
However, with this new requirement added, more focus was created to explore the
temperature resistance at a temperature of 300 °C FRP for a duration of no longer than 30-
minutes time. These requirements come from the engineers from leading EPC’s responsible
for the design and projects of refurbishments of some key coal-fired power stations in India.
Figure 4: FRP Duct works at Power Station in Poland
2. General assumptions and information
In order to understand the question about the temperatures and the effect on FRP materials,
one needs to have a deeper understanding of the raw materials used, how FRP is designed and
manufactured.
2.1 No track record
Never before did the market demand an excursion temperature resistance of 300 °C of FRP
material. For instance, high temperature equipment used for waste incineration plants was a
combination of FRP and Fluor Plastic lining materials, known for its high temperature and
chemical resistant characteristics. In these cases severe conditions were expected and
investment are done based on these operations. Normal conditions at coal-fired Power
Stations are less severe and the equipment does not necessarily operate under temperatures
higher than 70 °C. What needs to be stated:
Till today, no problems ever occurred related to high temperatures and FRP ducts and liners.
Leading European engineers and designers from companies with extensive experience in
designing power stations, FGD processes and other gas cleaning systems, such as MHPS,
BNG or Alstom Power.
2.2 In short: construction of a FRP laminate
Making a suitable FRP duct, chimney, absorber or any product for industrial usage requires
design and engineering by people with extensive FRP experience and knowledge. FRP,
Fibreglass Reinforced Plastic, is a composition of resin and glass fibres. Both resin and glass
are to be selected based on the application. The FRP product consists of a 1) inner laminate,
called a CBL, Chemical Barrier Layer; 2) the structural layer; 3) top layer. The type and
percentage of glass fibres varies from 30% wt. up to 70% wt. depending on the functionality
of the layer.
1) The Chemical Barrier Layer protects the structural layer against influences from the
inside (flue gas), it consists of 70% resin and 30% glass;
2) The Structural Layer carries the load, it consists of 30% resin and 70% glass;
3) The Top Layer protects the Structural Layer against influences from the outside.
Figure 5: Production of FRP Duct at mobile facility
2.2.1 Glass material
Different types of technical glass roving’s and fabrics are available, but for FGD applications
E-CR glass is used. This is specified by industrial standards and selected due to its excellent
performance in corrosive environments, such as FGD systems. Requirements for the E-CR
glass fibre are written in the EN 13121-1 or ASTM D5364. Depending on the design
requirements, different types of glass reinforcements can be used to build up a laminate.
Figure 6: Glass fibre - at a mobile facility for the production of FRP Ducts and Chimneys
2.2.2 Resin
For FGD applications Epoxy Vinyl Ester resins are applied. The minimum properties of those
resins are specified in the EN 13121-1 code or ASTM D5364. The selection of resin is highly
important for the design of an FRP product. Within a laminate, the resin provides the matrix
for strength and stability but is also essential for the corrosion resistance.
In addition, the temperature resistance of a FRP laminate strongly depends on the used resin.
For FGD systems with temperatures up to 100°C, a so called Bisphenol-A resin can be used.
For FGD systems above these temperatures, a Novolac-Epoxy resin is selected. Both resins
are considered as ‘Vinyl ester Resins’.
The history of Vinyl ester Resins in FGD applications goes back to the eighties. Dozens of
documented case histories are available from leading resin manufacturers. Only reputable
resin manufacturers who have proven themselves are qualified suppliers, naming a few:
Ashland, AOC and Reichold. The resin supplier is always asked to analyse the resin for a
described (FGD) process before the FRP manufacturer actually selects the resin.
Figure 7: Glass fibre strings dipped in resin bath
2.2.3 HDT of a resin
One of the important characteristics of a resin is the Heat Distortion Temperature, HDT. The
HDT is the maximum temperature a resin (and therefore the laminate) can handle before it
loses most of its strength properties. The HDT depends on the chemical backbone of the resin.
In general, Vinyl esters have the highest HDT of commercially available resins. A higher
HDT value means thermal stability up to higher temperatures. For flue gas liners affected by
high temperatures, Derakane 470 HT- 400 (Ashland brand) or equivalent is often used due to
its excellent thermal stability. For this resin a HDT of 180°C is specified by Ashland.
According the EN 13121-3 the maximum temperature of the load carrying structural layer
should be at least 20°C below the HDT of the chosen resin. If this is not the case a different
resin should be chosen.
2.3 Calculation methods
Design of a chimney or duct is typically done by setting up a FEA model. The model assesses
the outcome by comparing with the allowable values determined from the code. To set up a
proper FEA model, the following should be known:
Geometry: based on General Arrangement (GA) drawings and the preliminary FRP design;
Properties: the FRP manufacturer’s laminate properties based on historical data;
Loads: all loads from process, dead weight and factors from the EN 1990/ASTM/CICIND
specs;
FEA model: define e.g. the minimum mesh and other boundary constrains.
To assess the outcome of the FEA analysis, a design code should be selected. In Europe, the
EN 13121-3 is commonly applied to do so. In the USA, the assessment is mostly executed by
the ASTM D5364 as a starting point. The parameters of CICIND are used as well for both
European as American assessments. The approach of different design codes, makes it less
transparent, however the outcome is very similar.
2.3.1 Example of the assessment of an FRP construction
Two examples are described below, about how to verify a design by comparing the minimum
design-factor K (strength) and F (stability) according the EN 13121-3 code with the available
factors from the FEA analyses per load case.
Figure 8: Material data sheet Epoxy Vinyl Ester Resin
Figure 9: Stress load in a DN8000 horizontal gas duct. In the x-direction the maximum tensile stress is 10.43 Mpa.
The ultimate stress at rupture for this duct is 180 Mpa. The K-factor for this project was
determined 6.22. The realized K-factor is 180 Mpa/10.43 Mpa = 17.25. Because 17.25 > 6.22
the assessment shows that the construction fulfils the requirements according EN13121-3.
Figure 10: Cylinder with stiffeners loaded by external pressure (vacuum)
For stability (overall and local) an identical approach is followed. The overall and local
buckling factors are determined and compared to the minimum F-factor as per EN 13121-3
design. The buckling factor achieved should be higher than the - for that load case required -
F-factor.
3. Research for temperatures up to 300° Celsius
The R&D and Design & Engineering department of Plasticon Composites, were assigned to
research the requested temperatures for a duration of the estimated time, by engineers who
specified this operating temperature.
From a process point of view, three different operating scenarios for FRP ducts or chimneys
applied in a FGD system are defined:
1) Operating conditions ≈ 60°, over ≤ 50 years.
2) By-Pass conditions ≤ 150°C, over ≤ 10 years within the FGD’s life time
3) Excursion ≤ 300°C, once per FGD’s life time, ≤ 30 minutes
3.1 Impact of temperature
The maximum applied temperature of the Structural Layer is an important aspect during the
design of a FRP liner. Laminate properties determined at 20°C should be divided by the
partial load factor A3 to have the properties at a temperature “x”
To determine the A3 factor the following equation according EN13121-3 should be used.
Where TS is the laminate temperature in °C and HDT a resin specific value in °C. The A3
factor should not exceed a value of 1.4. If this is the case another resin (with a higher HDT)
should be used.
3.1.1 Laminate temperature
The temperature of the Structural Layer can be calculated by knowing the flue gas
temperature, gas velocity inside and air velocity outside the liner, the wall thicknesses and the
heat transfer coefficients per CICIND code. An example of a CFD calculation is given below
where a flue gas temperature of 150°C results in a structural laminate (SL) temperature of less
than 100°C.
Figure 11: An example of a CFD calculation is given below where a flue gas temperature of 150°C results in a SL
temperature of less than 100°C
3.2 Load design
Per load scenario the so-called design factor should be determined. Some loads have
significant impact but because their duration is very short the overall impact is not normative.
Other loads are relatively low but occur during the complete 50 years of lifetime. Therefore,
the impact is rather high.
Design factors will be determined for either strength (stress) or stability (buckling factor). To
assess the impact on the construction per load scenario the overall design factor for strength
and stability is determined per load scenario.
The design factors according the EN 13121-3:2016 code are built-up from several partial
material and load factors each covering a degradation aspect of the FRP, the time factor
(duration of a load) and covering normal variances in production, materials and loads.
Factor Description Operating
conditions
By-Pass
conditions
Exceptional
situation Remark
A1 Material properties based on
historical test data or theory 1.20 1.20 1.20 Plasticon has test data available from
different laboratory tested for the last
decades
A2 Resistance of resins against process
environment (corrosion) 1.20 1.20 1.20 For resins recommended by the resin
manufacture factor 1.2
A3 Influence of temperature 1.10 1.30 1.37 See 6.1
A4 Load cycles (fatigue) 1.00 1.00 1.00 Not applicable for FGD
A5 Duration of a load scenario
(resulting in creep) 1.70 / 1.40 1.60 / 1.30 1.00 / 1.00 Axial / Circumferential creep factors are
based on historical test data. Shorter
duration means lower factor
Ɣm Material variation coefficient 1.40 1.40 1.40 Standard factor for FRP according the EN
1990 code
Ɣf Load variation coefficient 1.50 1.50 1.00 Standard factor for FRP according the EN
1990 code
Overall factor for strength
A1 * A2 * A3 *A4 * A5 * Ɣm * Ɣf K= 6.0 6.3 2.8 - -
Overall factor for stability
A1 * A2 * A3 *A4 * √A5 * Ɣm * Ɣf F= 3.9 4.5 2.8 - -
Figure 12: Load design factor table
In this example the combination of load duration (A5) and temperature (A3) during By-Pass
condition is normative for the design.
4. The theory behind a high temperature
The actual theory of safety factors and standards which are described by different known and
leading engineering agencies must be compared. Experience is one, but what about the
standard, how do chimneys perform and which factors are applicable in what conditions?
4.1 Design base
Plasticon R&D team investigated the potential use of FRP liners for emitting the flue gasses
on 275 m height after desulfurization in the FGD for a certain project. This project exists of
two liners of DN7200 meter, each installed in a concrete chimney with a height of 267 meters.
The top of the FRP liner is at 275 m.
The FRP liners are split-up in segments, of 45 m¹ each. Every part is supported by a 360°
support ring at the top and laterally guided at the bottom. To absorb expansion caused by
temperature, compensators are installed every 45 m.
For the feasibility study, it was assumed that following loads impact the liner for
longer/shorter periods.
▪ Pressure : +20 mBar / -20 mBar for 50 years
▪ Ash & condensate : 20 kg/m² for 50 years
▪ Temperature : 60°C for 50 years / 150°C for less than 10 years / 300°C for less than
30 minutes
Figure 13: Setup of chimney liners
4.2 Laminate and stiffeners
Based on Plasticon Composites long term experience and by applying the EN13121-3 design
rules, following draft construction was set-up to be evaluated by use of FEA.
Figure 14: Draft construction of chimney liner
To determine the temperature curve of the cylinder / stiffener construction a thermal model
was set up and analysed by use of FEA:
Figure 15: Construction of the laminate
Figure 16: The temperature curve of this cross-section - per load case
From the graphics above, the following relevant design temperatures could be determined:
60°C / ∞
scenario
150°C /∞
scenario
300°C/ 30 min
scenario
Tmax at surface CBL 57°C 136°C 260°C
Tmax structural laminate 55°C 127°C 232°C
Surface temperature 40°C 57°C 100°C Figure 17: Design temperatures
This would mean, that with the exceptional loading of 300°C/30 minutes, the maximum
temperature of the Structural Layer is higher than the (HDT -/- 20°C) requirement according
EN13121-3. Though, the temperature will decrease by moving outwards in the Structural
Layer of the laminate. Eventually, the temperature will drop to a 100°C at the surface.
The detailed analyses showed that 10 mm into the structural layer the temperature is <160°C.
This means that the outer 10 mm of the Structural Layer is still perfectly able to transfer loads
and to resist buckling loads.
Of course, the applicable stress will be higher and the buckling factor will be lower (due to
reduced “load carrying thickness”). Yet, due to the short timeframe in which this situation
would occur, the calculated design factors are also significantly lower (see figure 11: Load
design table).
4.3 Check of design / axial stress (dead weight, process & thermal expansion)
60°C / ∞
scenario
150°C /∞
scenario
300°C/ 30
min scenario
Required design factor (K) for strength 6.0 6.3 2.8
Achieved design factor for strength 49.2 15.5 10.5
Load carrying thickness of structural
laminate 20.0 mm 20.0 mm 10.0 mm
Assessment Ok Ok Ok Figure 18: Assessment of scenario's with dead weight
Figure 19: Graphical presentation of the thermal axial stress @ 300°C flue gas
As shown in table, figure 17, safety factors are reached in described theoretical operation
conditions.
4.4 Check of design / buckling factor (from external pressure)
60°C / ∞
Scenario
150°C /∞
scenario
300°C/ 30
min scenario
Required design factor (F) for stability 3.9 4.5 2.8
Achieved design factor for strength 4.8 4.8 3.2
Load carrying thickness of structural laminate 20.0 mm 20.0 mm 10.0 mm
Assessment Ok Ok Ok Figure 20: Assessment of scenario’s with buckling factor
Figure 21: Graphical presentation of the local and global buckling of the '10 mm load carrying cylinder’ @ 300°C flue gas
5. Degradation of mechanical properties
In general, FRP properties will degrade less or more linear until the Tg of the resin has been
reached (Tg: glass transition temperature: the temperature when the resin loses its properties,
shape and characteristics). Above that temperature reduction will continue less linear and
stabilize at 300°C finally on a level of ± 25% of the original properties.
Over temperature the reduction of the tensile properties is less than the reduction of the
flexural properties. This has to do with the way the loads are transferred through the laminate.
Due to flexural loads shear stresses between the layers will occur. The shear strength of the
resin reduces at higher temperature. From tensile loads this type of stresses not occur so
impact of temperature is less.
5.1 Tensile tests by Indian Institute of Technology, Madras
The Indian Institute of technology in Madras (India) carried out tensile tests on the FRP
laminates made of Derakane 470 HT-400 (Ashland brand) on higher temperatures.
Figure 22: Source: Comptech, Indian Institute of Technology Madras – February 2017
5.3 Bending tests by University of Aachen
The University of Aachen (Germany) carried out bending tests on higher temperatures on
similar laminates. The trend measured during these tests is shown is visible in the graphs
below.
Figure 23: Source: Ashland / University of Aachen – February 2004
5.4 Outcome of the tests
Taking a filament winded laminate as an example (glass content 65% wt. and made of
Derakane 470 HT-400) the reduction of properties 20°C to 300°C would look like this:
Figure 24: Reduction of properties over temperature
Based on the EN 13121-3 a laminate can absorb and transfer loads up to 20°C below its HDT
value. In this case for Derakane 470-HT 400, up to a temperature of 160°C.
From laboratory tests, it is known that heating up the laminate above 160°C will not affect the
integrity and chemical resistance, however the mechanical properties will indeed be impacted.
Tests showed that in the range 220°C-300°C the properties remain stable on at least 25% of
the original properties at 20°C.
5.5 No irreversible changes
After cooling down, the FRP laminates were inspected on delamination’s or other irreversible
changes: none of those have been found.
Besides this research, Ashland has several well documented cases of chimneys built-up out of
Derakane 470 HT-400, these case histories are built up for decades. These chimneys operate
in a temperature range far above the HDT of the resin. The outcome of those case histories is
that if the structural design considers the high temperatures in a proper way no problem will
occur during the lifetime of the chimney.
6. Conclusion
For the design & engineering phase, as well as the test phase at different independent
institutes in both Europe as India, it was concluded that the exposure to a temperature of
300°C for an FRP laminate, which is constructed with high-temperature resin and for a period
of 30 minutes, would not have any influences on performance.
The FRP laminate that is specially designed for FGD chimneys is proven to have excellent
properties, this is concluded out of different point of views:
1) FRP has proven track record in FGD applications for over 40 years with an expected
life span of 30 years.
2) FEA analysis based using internationally recognized design codes proof 300°C for a
period of 30 minutes is not an issue.
3) Independent institutions concluded detailed tests on FRP laminates, that were
constructed for FGD applications. These tests show that performance of the laminates
will not be affected irreversibly in any way after the exposure to 300°C degrees for a
time of 30 minutes.
Therefore it is proven that FRP ducts and chimneys can resist a short-term excursion
temperature up to 300°C degrees without any permanent damages in the Structural Laminate,
shape or corrosion resistant properties or any other characteristics.
This report writes that FRP laminates and constructions would be a material that could be
selected and considered as suitable material for chimney liners, duct systems as well as bypass
systems for FGD applications. The FGD conditions differ per design and process of each
power station, this challenges engineers to analyse designs and processes and understanding
key standards and case histories.
The reason why the government of India will invest in the refurbishments of coal fired power
stations is the health and safety for its people. Researching all factors and collecting
information on the process designs and constructions are key to come to a solution which
offers long term solutions.
FRP chimney liners and ducts are corrosion resistant and have been proven to be a long term
solution in other regions of the world. Maintenance or repair costs have turned out, the last
decades, to be minimal compared to conventional materials. When a low cost of ownership
for a construction is a reason to select equipment for power stations, the option of FRP
material is to be discussed.