Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin, EPRI Kent Zammit, EPRI John Maulbetsch, Maulbetsch Consulting EPRI Workshop on Advanced Cooling Technologies July 8-9, 2008, Charlotte, NC
Transcript
Page 1: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

Field Testing of Wind Effects on Air-Cooled Condensers

Chuck McGowin, EPRI Kent Zammit, EPRIJohn Maulbetsch,

Maulbetsch Consulting

EPRI Workshop on Advanced Cooling Technologies

July 8-9, 2008, Charlotte, NC

Page 2: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

2© 2008 Electric Power Research Institute, Inc. All rights reserved.

Wind Effects - A Recognized Problem for ACCs

• EPRI ACC Guidelines:– “…represents the major

challenge..with ACC specification, design and performance”

• Test codes---VGB, ASME, CTI– Average winds may not exceed

3 m/s– No gusts above 6 m/s (20 per

hour)

Page 3: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

3© 2008 Electric Power Research Institute, Inc. All rights reserved.

Bighorn Power Plant

Page 4: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

4© 2008 Electric Power Research Institute, Inc. All rights reserved.

Cell Layout and Instrumentation

4 3 2 1

Rows

A

B

North Cluster C

D Wind screen full height Wind screen lower 1/3

E Wind screen upper 2/3

RisersSteam duct

NF

G

SouthCluster H

I

J

Streets

1J

4I 3I 2I 1I

4J 3J 2J

4H 3H 2H 1H

4G 3G 2G 1G

4F 3F 2F 1F

4E 3E 2E 1E

4D 3D 2D 1D

4C 3C 2C 1C

1A

4B 3B 2B 1B

4A 3A 2A

X Fan shroud

Fan bridge

X

Fan motor

X Anemometers below fans

X

Temperature probe

X

Page 5: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

5© 2008 Electric Power Research Institute, Inc. All rights reserved.

Southwestern Plant

Wind Effect

2

3

4

5

6

7

8

9

70 80 90 100 110 120

Ambient Temperature, F

Bac

kpre

ssur

e, in

Hga

0 to 4mph 4 to 8mph 8 to 12mph 12 to 16mph 16 to 20mph > 20mph

> 20 mph

0 to 4 mph

Page 6: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

6© 2008 Electric Power Research Institute, Inc. All rights reserved.

Wind Effects on ACC Performance

•Recirculation•Fan performance degradation

Page 7: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

7© 2008 Electric Power Research Institute, Inc. All rights reserved.

Recirculation

Where and how much?

Page 8: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

8© 2008 Electric Power Research Institute, Inc. All rights reserved.

Page 9: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

9© 2008 Electric Power Research Institute, Inc. All rights reserved.

Bighorn ACC Average Recirculation

0

1

2

3

4

5

6

7

8

6/10/05 6/11/05 6/12/05 6/13/05 6/14/05 6/15/05 6/16/05 6/17/05 6/18/05 6/19/05

Date

AC

C R

ecirc

ulat

ion,

FBighorn Average Recirculation June 10 to 18, 2005

Page 10: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

10© 2008 Electric Power Research Institute, Inc. All rights reserved.

Cell 2I Inlet TemperatureHigh Winds; June 17--20:00h

3D 3C 3A 3B2D 2I 4A 2H 4H 4B 4F 4C 2J 4I 4G 3F 2C 2E 3I 2B 4D 3H 3G 2G 2F 2A 1I 1E

1F3E

1D 1A 3J 1C 4E1B

1H

1G

4J

1J

77

78

79

80

81

82

83

84

85

Cel

l Inl

et T

empe

ratu

res,

F

Page 11: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

11© 2008 Electric Power Research Institute, Inc. All rights reserved.

Cell Velocity Averages--June 18

400

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

6/18/05 12:00PM

6/18/05 1:00PM

6/18/05 2:00PM

6/18/05 3:00PM

6/18/05 4:00PM

6/18/05 5:00PM

6/18/05 6:00PM

6/18/05 7:00PM

6/18/05 8:00PM

6/18/05 9:00PM

Date

Inle

t Vel

ocity

, fpm

Vely 3JAverage Vely 3IAverage Vely 3FAverage

Page 12: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

12© 2008 Electric Power Research Institute, Inc. All rights reserved.

Page 13: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

13© 2008 Electric Power Research Institute, Inc. All rights reserved.

Page 14: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

14© 2008 Electric Power Research Institute, Inc. All rights reserved.

Wind Screens

Page 15: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

15© 2008 Electric Power Research Institute, Inc. All rights reserved.

Conclusions

Recirculation– “Zero wind inlet” temperature hard to define– Predominant at edge and corners downwind– Can be high in a few cells– JSM Opinion: Not very high on average---2 to 4 F

Fan Performance Degradation– Predominant in windward edge fans– Can be significant (50 – 70% reduction) in a few fans– JSM opinion: More important than recirculation

Page 16: Field Testing of Wind Effects on Air-Cooled Condensersmydocs.epri.com/docs/AdvancedCooling... · 8/8/2007  · Field Testing of Wind Effects on Air-Cooled Condensers Chuck McGowin,

16© 2008 Electric Power Research Institute, Inc. All rights reserved.

Conclusions

Wind Screens– Good comparative field data not available– Anecdotal information:

• On a 5 x 6 ACC:– Helped with gusts– Not much effect on “steady state”

• On a 2 x 5 ACC (all edge cells):– Improved performance– Other changes at same time make comparison

difficult


Recommended