+ All Categories
Home > Documents > FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

Date post: 07-Aug-2018
Category:
Upload: lethanhvan186
View: 240 times
Download: 1 times
Share this document with a friend

of 35

Transcript
  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    1/84

    Designing a Chiller Plant Room to be the

    Most Efficient

    Session 2 of 3 of the Series:

    Optimizing Your Chiller Plant Room

    Moderated by Laxmi Rao

    Presented by Roy Hubbard and Bill Stewart

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    2/84

    © Johnson Controls, Inc. 20122

    Welcome

    - Webinar Duration: 1 hour 30 minutes

    - Panelists: Please silence /shut cell phones.

    - Questions to Presenters: Please type in Questions in the Q&A box at the lower

    right hand corner of screen. Questions will be answered after the end of the

    presentation.

    - Moderator will hand Questions to presenters. Responses to unanswered questions

    will be provided by Jill Woltkamp after the webinar.

    - If you are just dialed in with audio, also send questions to [email protected]

    - Webinar (function) questions : Please chat with Cheryl. Use the Chat box in the

    middle right hand section of the screen and choose - “Chat privately to Cheryl”.

    - Survey: Please complete the survey following the webinar 

    - Webinar Download: Recording and Presentation slides will be available at

    www.districtenergy.org

    - Note: Session 2 will be more meaningful after viewing Session 1. “Using variable

    Speed drives in Central Plants with Multiple Chillers”

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    3/84

    © Johnson Controls, Inc. 20123

    SELECT, DESIGN, OPTIMIZE 

    #1

    #2

    #3

    Optimizing Your Chiller Plant RoomWebinar Program:

    Using Variable Speed Drives in Central Plants with Multiple Chillers

    Designing a Chiller Plant to be the Most Efficient

    Defining and Implementing Chiller Plant Optimization

    #2

    #3

     August 16, 2012

    October 11, 2012

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    4/84

    © Johnson Controls, Inc. 20124

    Review the 5 VSD Myths

    Myth # 6 – Water Flow Tracks Load

    Myth # 7 – Pump Speed Tracks Flow

    Myth # 8 – Pumps/Towers Use More Energy

    Than Chillers Can Save

    Summary

    Q&A

    Agenda

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    5/84

    © Johnson Controls, Inc. 20125

     The 5 Variable SpeedDrive Myths are:

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    6/84

    © Johnson Controls, Inc. 20126

    In a central plant:

    Run the fewest number

    of constant speedchillers, as heavily

    loaded as possible

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    7/84

    © Johnson Controls, Inc. 20127

    In a central plant:

    Run the fewest number

    of constant speedchillers, as heavily

    loaded as possible

     The most efficient place to run your

    chiller today is at PART LOAD

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    8/84

    © Johnson Controls, Inc. 20128

    Chillers cannot run

    on cold tower water

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    9/84

    © Johnson Controls, Inc. 20129

    Chillers cannot run

    on cold tower water

     Variable Orifice Technology allows the

    ability to use cold tower water

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    10/84

    © Johnson Controls, Inc. 201210

    Do not use VSDs onFully Loaded Chillers in

    a Central Plant

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    11/84

    © Johnson Controls, Inc. 201211

     VSD technology saves an additional 17%

    energy on a fully loaded chiller with 55°F ECWT 

    Do not use VSDs onFully Loaded Chillers in

    a Central Plant

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    12/84

    © Johnson Controls, Inc. 201212

     Variable Speed

    Drives Only SaveEnergy on a Single

    Chiller

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    13/84

    © Johnson Controls, Inc. 201213

     Variable Speed

    Drives Only SaveEnergy on a Single

    Chiller

    Run ll Chillers at Part Load with

    Variable Speed Drives to Save Energy

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    14/84

    © Johnson Controls, Inc. 201214

    0.50 kW/ton, average, is Best-in-Class Efficiency for Chillers

    in a Central Plant

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    15/84

    © Johnson Controls, Inc. 201215

    0.50 kW/ton, average, is Best-in-Class Efficiency for Chillers

    in a Central Plant

    0.40 and lower, average, is achievable with

    Part Load, Variable Speed Drive Chillers

    Review

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    16/84

    © Johnson Controls, Inc. 201216

    Completed.. Up Next....

    Review the

    5 Variable

    Speed Drive

    Myths

    Present the

    basics of a

    Primary /Secondary

    System

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    17/84

    © Johnson Controls, Inc. 201217

    Primary (Constant) / Secondary (Variable)

    Primary Pumps

    Secondary Pumps

    Decoupler / Bypass

    Primary Load = Flow X Delta T

    Secondary Load = Flow X Delta T

    Typical Load with 2-Way Valve

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    18/84

    © Johnson Controls, Inc. 201218

    Primary / Secondary System at Design

    9000 GPM (34000 LPM) @ 56°F (13°C)

    No flow

    6000 ton (21,000 kW) chillers9000 GPM (34000 LPM) Each

    56-40°F (13-4°C)

    100% System Load

    Primary Pumps

    9000 GPM (34000 LPM)

    56°F(13°C)

    56°F(13°C)

    56°F(13°C)

    40°F(4°C)

    40°F(4°C)

    40°F(4°C)

    Typical

    Coil

    40°F(4°C)

    56°F(13°C)

    Secondary Pumps

    9000 GPM (34,000 LPM)

    @ 40°F (4°C)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    19/84

    © Johnson Controls, Inc. 201219

    Primary / Secondary System at Part Load

    9000 GPM (34000 LPM) @ 52°F (11°C)

    75% System Load

    Secondary Pumps

    6750 GPM (25500 LPM)

    @ 40°F (4°C)

    2250 GPM (8500 LPM) @

    40°F (4°C)

    6750 GPM (25500 LPM)

    @ 56°F (13°C)

    Typical

    Coil

    40°F(4°C)

    56°F(13°C)

    40°F(4°C)

    40°F(4°C)

    40°F(4°C)

    52°F(11°C)

    52°F(11°C)

    52°F(11°C)

    Primary Pumps

    9000 GPM (34000 LPM)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    20/84

    © Johnson Controls, Inc. 201220

    Primary / Secondary System

    6000 GPM (22700 LPM) @ 52°F (11°C)

    50% System Load

    Primary Pumps

    6000 GPM (22700 LPM)

    Secondary Pumps

    4500 GPM (17000 LPM)

    @ 40°F (4°C)

    1500 GPM (5700 LPM)

    @ 40°F (4°C)

    4500 GPM (17000 LPM)

    @ 56°F (13°C)

    OFF

    40°F(4°C)

    40°F(4°C)

    52°F(11°C)

    52°F(11°C)

    Typical

    Coil

    40°F(4°C)

    56°F(13°C)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    21/84

    © Johnson Controls, Inc. 201221

    Primary / Secondary System

    3000 GPM (11000 LPM) @ 52°F (11°C)

    25% System Load

    Primary Pumps

    3000 GPM (11000 LPM)

    Secondary Pumps

    2250 GPM (8500 LPM)

    @ 40°F (4°C)

    750 GPM (2800 LPM)

    @ 40°F (4°C)

    2250 GPM (8500 LPM)

    @ 56°F (13°C)

    OFF

    OFF

    40°F(4°C)

    52°F(11°C)

    Typical

    Coil

    40°F(4°C)

    56°F(13°C)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    22/84

    © Johnson Controls, Inc. 201222

    Completed.. Up Next....

    Review

    Myth #6Present the

    basics of aPrimary /

    Secondary

    System

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    23/84

    © Johnson Controls, Inc. 201223

    Chilled Water Flow TracksCampus Cooling Load

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    24/84

    © Johnson Controls, Inc. 201224

    56°F (13°C)

    Typical

    Coil

    40°F

    (4°C)

    56°F

    (13°C)

    Design Delta T = 16ºF (-9ºC)

    Low Delta T Syndrome

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    25/84

    © Johnson Controls, Inc. 201225

    Major Causes of Low Delta T

    Dirty Coils

    Controls Calibration

    Leaky 2-Way Valves

    Coils Piped-Up Backwards

    Mixing 2-Way with 3-Way Valves

    Etc., Etc.

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    26/84

    © Johnson Controls, Inc. 201226

    Chilled Water Coil

    AIR FLOW

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    27/84

    © Johnson Controls, Inc. 201227

    100% Flow = 9000 GPM (34,000 LPM)

    100% Load = 100% Sec Flow

    Primary Pumps

    Secondary Pumps

    Primary (Constant) / Secondary (Variable)

    Ideal Operation 

    100% Flow = 9000 GPM (34,000 LPM)

    16

    Decoupler /

    Bypass

    0 GPM (0 LPM)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    28/84

    © Johnson Controls, Inc. 201228

    Primary (Constant) / Secondary (Variable)

    Ideal Operation 

    75% Load = 75% Sec Flow

    Primary Pumps

    Secondary Pumps

    75% Flow = 6750 GPM (25500 LPM)

    16

    Decoupler / Bypass

    2250 GPM (8500 LPM)

    100% Flow = 9000 GPM (34,000 LPM)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    29/84

    © Johnson Controls, Inc. 201229

    Primary (Constant) / Secondary (Variable)

    Low Delta T Operation 

    75% Load = 86% Sec Flow

    Primary Pumps

    Secondary Pumps

    86% Flow = 7714 GPM (29100 LPM)

    (964 over-pumped)

    14

    Decoupler / Bypass

    1286 GPM (4800 LPM)100% Flow = 9000 GPM (34,000 LPM)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    30/84

    © Johnson Controls, Inc. 201230

    Primary (Constant) / Secondary (Variable)

    Low Delta T Operation 

    75% Load = 86% Sec Flow

    Secondary Pumps

    Primary Pumps

    86% Flow = 7714 GPM (29100 LPM)

    (964 over-pumped)

    14

    Decoupler / Bypass

    1286 GPM (4800 LPM)100% Flow = 9000 GPM (34,000 LPM)

    % LOAD = % FLOW

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    31/84

    © Johnson Controls, Inc. 201231

    Primary (Constant) / Secondary (Variable)

    Low Delta T Operation 

    100% Flow = 6000 GPM (22700 LPM)

    67% Load = 76% Sec Flow

    Primary Pumps

    Secondary Pumps

    Decoupler / Bypass

    857 GPM (3200 LPM)

    76% Flow = 6857 GPM (26000 LPM)

    (857 over-pumped) @ 41.7 °F (5.4°C)

    14

    OFF?

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    32/84

    © Johnson Controls, Inc. 201232

    Primary / Secondary Rule of Flow

    Primary Flow Must Always

    be EQUAL TO or GREATERTHAN Secondary Flow

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    33/84

    © Johnson Controls, Inc. 201233

    Primary (Constant) / Secondary (Variable)

    Low Delta T Operation 

    67% Load = 76% Sec Flow

    Primary Pumps

    Secondary Pumps

    Decoupler / Bypass

    2143 GPM (8100 LPM)

    76% Flow = 6857 GPM

    (857 over-pumped) back to 40 °F

    14

    % LOAD = % FLOW

    100% Flow = 9000 GPM (34,000 LPM)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    34/84

    © Johnson Controls, Inc. 201234

    Chilled Water Flow TracksCampus Cooling Load

    Real world operating systems will always develop low delta T;

    requiring more flow than needed for load.

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    35/84

    © Johnson Controls, Inc. 201235

    Increased Flow for a Given Load – Pumps have to run faster and use

    more energy

    Can’t load-up chillers greater than the low delta T ratio (actual delta T

    / design delta T)

    Increased Plant Energy – Must run more chiller systems than needed

    Impact of Low Delta T

    Solve at Load,

    Mitigate at Plant

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    36/84

    © Johnson Controls, Inc. 201236

    Mitigation of Low Delta T in Plant

    Load (chillers capacity) = Flow x Delta T

    Increase Delta T across chillers with CHW Re-set (down)

    Use VPF Headered Pumping Systems (mitigates energy waste

    in plant)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    37/84

    © Johnson Controls, Inc. 201237

    Completed.. Up Next....

    Present the

    Basics of

    Variable

    Primary Flow

    Understand

    Low Delta Tand

    Bust Myth #6

    Primary / Secondary System

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    38/84

    © Johnson Controls, Inc. 201238

    Primary / Secondary System

    Variable Primary System

    Secondary Pumps

    Typical load with 2-way valvePrimary Pumps

    Primary Pumps

    Flow Meter 

    Bypass

    Valve

     Automatic

    Isolation Valve

    Typical load with 2-way valve

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    39/84

    © Johnson Controls, Inc. 201239

    Energy Use Advantages over Primary / Secondary System

    Better CHW Pump Energy Consumption

    Higher Pump Efficiency

    Lower Pump Design Head

    Primary Only (Variable Flow)

    BHP = GPM X Head

    3960 X PumpEff 

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    40/84

    © Johnson Controls, Inc. 201240

    Energy Use Advantages over Primary / Secondary System

    Better CHW Pump Energy Consumption

    Higher Pump Efficiency

    Lower Pump Design Head

    Total head is variable speed

    Less impact from Low Delta T (Headered Pumping)

    Primary Only (Variable Flow)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    41/84

    © Johnson Controls, Inc. 201241

    9000 GPM (34,000 LPM)

    @ 56°F (13°C)

    Typical

    Load with

    2-Way

    Valve

    Primary Pumps

    9000 GPM(34,000 LPM)

    9000 GPM (34,000 LPM) @ 40°F (4°C)

    Bypass

    Closed

    Variable Primary System at Design

    100% System Load

    16

     Automatic

    Isolation Valve 56°F

    (13°C)

    56°F(13°C)

    56°F(13°C)

    40°F(4°C)

    40°F(4°C)

    40°F(4°C)

    6000 ton (21,000 kW) chillers9000 GPM (34000 LPM) Each

    56-40°F (13-4°C)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    42/84

    © Johnson Controls, Inc. 201242

    6750 GPM (25500 LPM) @ 56°F (13°C)

    Typical

    Load with

    2-Way

    Valve

    Primary Pumps

    6750 GPM(25500 LPM)

    6750 GPM (25500 LPM)@ 40°F (4°C)

    Bypass

    Closed

    Variable Primary System at Part Load

    75% System Load

    16

     Automatic

    Isolation Valve 56°F

    (13°C)

    56°F(13°C)

    56°F(13°C)

    40°F(4°C)

    40°F(4°C)

    40°F(4°C)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    43/84

    © Johnson Controls, Inc. 201243

    6000 GPM (22700 LPM)

    @ 56°F (13°C)

    Typical

    Load with

    2-Way

    Valve

    Primary Pumps

    6000 GPM(22700 LPM)

    6000 GPM (22700 LPM) @40°F (4°C)

    Bypass

    Closed

    Variable Primary System at Part Load

    67% System Load

    16

     Automatic

    Isolation Valve

    Chiller off 

    Pump off ?

    56°F(13°C)

    56°F(13°C)

    40°F(4°C)

    40°F(4°C)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    44/84

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    45/84

    © Johnson Controls, Inc. 201245

    Chilled Water Flow TracksCampus Cooling Load

     VPF Systems mitigate at the plant the negative impact

    of low system delta T 

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    46/84

    © Johnson Controls, Inc. 201246

    Chilled Water Pump Speed Tracks Flow 

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    47/84

    © Johnson Controls, Inc. 201247

    Chilled Water Pump Speed Tracks Flow

    50 % Flow

    50% Speed

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    48/84

    © Johnson Controls, Inc. 201248

    Chilled Water Pump Speed Tracks Flow

    50 % Flow

    62.3 % Speed

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    49/84

    © Johnson Controls, Inc. 201249

    Chilled Water Pump Speed Tracks Flow

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    50/84

    © Johnson Controls, Inc. 201250

     There is always some kind of control or statichead in variable speed systems. Use flow

    meters to track flow.

    Chilled Water Pump Speed Tracks Flow 

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    51/84

    © Johnson Controls, Inc. 201251

    Completed.. Up Next....

    Chiller Plant

    VPF Design

    Considerations

    Busting

    Myth #7

    VPF S t D i /C t l C id ti S

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    52/84

    © Johnson Controls, Inc. 201252

    Chillers

    Equal sized chillers preferred, but not required

    Keep from operating below minimum flow rates with Bypass control (1.5 fps)

    Keep from operating above Max flow rates (11.0 to 12.0 fps) (or 45/67 ft PD)

    Modulating Isolation Valves (or 2-position stroke-able) set to open in 1.5 to 2 min

    (Linear Proportional)

    VPF Systems Design/Control Considerations Summary

    VPF S t D i /C t l C id ti S

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    53/84

    © Johnson Controls, Inc. 201253

    Chillers

    Don’t vary flow too quickly through chillers (VSD pump Ramp rate – typical setting of10%/min)

    Chiller Type (flooded evap, DX evap, centrifugal, absorption, etc.)

    System Water Volume (more water, more thermal capacitance, faster variance

    allowed) 6-10 Gal/TR

    Chiller Load (min load - no variance, full load - max variance)

     Active Loads (near or far from plant)

    Sequence AHUs On/Off in 10 to 15 min intervals

    Staging Chillers On

    VPF Systems Design/Control Considerations Summary

    V i bl P i S t (St i S d Chill )

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    54/84

    © Johnson Controls, Inc. 201254

    Variable Primary System (Staging on Second Chiller)

    57°F

    (14°C)

    41°F(5°C)

    3300 GPM (12000 LPM)

    @ 57°F (14°C)

    Typical

    Load with

    2-Way

    Valve

    Primary Pumps

    1650 GPM (6200 LPM)Each

    3300 GPM (12000 LPM)@ 41°F (5°C)

    Bypass

    Closed

     Automatic

    Isolation Valve

    3300 GPM(12000 LPM)

    Need to add chiller 

    V i bl P i S t (O I l ti V l )

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    55/84

    © Johnson Controls, Inc. 201255

    Variable Primary System (Open Isolation Valve)

    Typical

    Load with

    2-Way

    Valve

    Primary Pumps

    3300 GPM(12000 LPM)

    Bypass

    Closed

     Automatic

    Isolation Valve

    1650 GPM(6200 LPM)

    1650 GPM(6200 LPM)

    Load = F X DT DT = 16 = 57- 41

    Load = 1/2F X 2DT DT = 32

    LCHWT = 25!

    57°F

    (14°C)

    41°F(5°C)

    3300 GPM (12000 LPM)

    @ 57°F (14°C)

    3300 GPM (12000 LPM)@ 41°F (5°C)

    VPF S t D i /C t l C id ti S

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    56/84

    © Johnson Controls, Inc. 201256

    Use Energy Based Sequencing.

    VPF Systems Design/Control Considerations Summary

    With High Head, Run

    Chillers at High Load.

    With Low Head, Run

    Chillers at Low Load.

    VPF S t D i /C t l C id ti S

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    57/84

    © Johnson Controls, Inc. 201257

    VPF Systems Design/Control Considerations Summary

    Pumps

    Headered arrangement

    Sequence

    Energy Based Sequencing (CPO)

    Stay within pump/motor limits (25% to 100% speed)

    Speed controlled by pressure sensors at end of index circuit (fast

    response important)

    Direct wired or Piggyback –reset pressure sensor

    Optimized valve position of coils (Vary Speed by Valve Position)

    VPF Systems Design/Control Considerations Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    58/84

    © Johnson Controls, Inc. 201258

    VPF Systems Design/Control Considerations Summary

    Bypass Piping and Valve

    Size pipe and valve for minimum flow of largest chiller 

    Needs pressure drop –recommend equal to overriding set-point in

    the system when valve is fully open.

    This is not sized like a common pipe for a Primary/Secondary

    System (8-10 pipe diameters long with zero pressure drop)

    Maintain a minimum chilled water flow rate through the operating chillers

    Differential pressure measurement across each chiller evaporator

    Flow meter required if savings are to be achieved.

    Variable Primary System Min Flow (776 GPM Each)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    59/84

    © Johnson Controls, Inc. 201259

    Variable Primary System – Min Flow (776 GPM Each)

    52°F(11°C)

    40°F(4°C)

    776 GPM (2900 LPM) @ 52°F (11°C)

    Typical

    Load with

    2-WayValve

    Primary Pump

    776 GPM (2900 LPM)

    (one operating)

    450 GPM (1700 LPM) @ 40°F (4°C)

    Bypass Open

    326 GPM

    (1234 LPM)

    @ 40°F (4°C)

     Automatic

    Isolation ValveSystem flow below chiller

    minimum flow of 776.

    Flowmeter  450 GPM (1700 LPM) @ 56°F (13°C)

    Chiller off 

    Chiller off 

    Pumps

    off 

    VPF Systems Design/Control Considerations Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    60/84

    © Johnson Controls, Inc. 201260

    VPF Systems Design/Control Considerations Summary

    Bypass Valve

    Pipe and valve sized for Min flow of operating chillers

    High Range-ability (100:1 or better preferred)

    PSID Ratings for Static, Dynamic, And Close Off = Shut Off Head of

    Pumps + fill pressure

    Linear Proportion (Flow to Valve Position) Characteristic preferred (Linearwith time is good)

    Fast Acting Actuator 

    Locate in Plant around chillers/pumps (preferred)

    Energy saved if located in plant

     Avoid Network traffic (response time is critical to protect chillers

    from potential freeze-up)

    C l t d U N t

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    61/84

    © Johnson Controls, Inc. 201261

    Completed.. Up Next....

    Review

    Myth #8Chiller Plant

    VPF DesignConsiderations

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    62/84

    © Johnson Controls, Inc. 201262

    Pumps/Towers use moreenergy than chillers can save

    Condenser Water Constant Speed – Dedicated Pumps –

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    63/84

    © Johnson Controls, Inc. 201263

    p p

    Typical for Primary Secondary

    Condenser

    Water 

    Pumps

    Bypass

    18000 GPM

    Cooling Tower Load = Flow X Delta T

    100 % Plant Load

    100 % CoolingTower Fan Speed

    Slow Down Condenser Pump and Tower Fan

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    64/84

    © Johnson Controls, Inc. 201264

    Slow Down Condenser Pump and Tower Fan

    Plant Energy –Higher or Lower?

    Plant Energy Usage Comparison (kWH) Assumptions

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    65/84

    © Johnson Controls, Inc. 201265

    Plant Energy Usage Comparison (kWH) Assumptions

    6000 Hours of Annual Operation

    Load Based Sequencing for P/S Plant (Avg Component Load 72%)

    Energy Based Sequencing used for VPF alts (Avg Component Load 58%)

    Reducing Condenser Flow Increases Fouling Rate

    Condenser Water Flow & CT Air Flow Minimum 80%

     All Chillers have VSD’s

    P/S equipped VSD’ s on SCHWP’s and on Tower Fans

    VPF Plants Equipped with VSD’s on Pumps and Towers

    Low Delta T Energy Impact not considered (P/S Plant Energy could be

    higher)

    Plant Energy Usage Comparison (kWH)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    66/84

    © Johnson Controls, Inc. 201266

    P/ S - LOAD

    BASED SEQ

    VPF - ENERGY

    BASED SEQ

    VPF + CWP & CT

    AIR FLOW OPT

    Chilled Water

    Pumps1,374,000 629,000 628,000

    Condenser Water

    Pumps1,424,000 1,464,000 843,000

    Cooling Tower

    Fans1,100,000 1,100,000 569,000

    Chillers 12,855,000 8,577,000 9,307,000

    Total 16,754,000 11,770,000 11,349,000

    Plant Energy Usage Comparison (kWH)

    P/S Plant arrangement same as previously depicted

    Plant Energy Usage Comparison (kWH)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    67/84

    © Johnson Controls, Inc. 201267

    P/ S - LOAD

    BASED SEQ

    VPF - ENERGY

    BASED SEQ

    VPF + CWP & CT

    AIR FLOW OPT

    Chilled Water

    Pumps1,374,000 629,000 628,000

    Condenser Water

    Pumps1,424,000 1,464,000 843,000

    Cooling Tower

    Fans1,100,000 1,100,000 569,000

    Chillers 12,855,000 8,577,000 9,307,000

    Total 16,754,000 11,770,000 11,349,000

    Plant Energy Usage Comparison (kWH)

    P/S & VPF Plant arrangements same as previously depicted

    Plant Energy Usage Comparison (kWH)

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    68/84

    © Johnson Controls, Inc. 201268

    P/ S - LOAD

    BASED SEQ

    VPF - ENERGY

    BASED SEQ

    VPF + CWP & CT

    AIR FLOW OPT*

    Chilled Water

    Pumps1,374,000 629,000 628,000

    Condenser Water

    Pumps1,424,000 1,464,000 843,000

    Cooling Tower

    Fans1,100,000 1,100,000 569,000

    Chillers 12,855,000 8,577,000 9,307,000

    Total 16,754,000 11,770,000 11,349,000

    Plant Energy Usage Comparison (kWH)

    P/S & VPF Plant arrangements same as previously depicted

    *Condenser Water Flow & CT Air Flow at 80% of Design

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    69/84

    © Johnson Controls, Inc. 201269

    Reducing Condenser Water Flow and CT Air Flow

    saves more energy than increase on chiller down to

    about 80% typical.

    Pumps/Towers use more

    energy than chillers can save

    Design Considerations

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    70/84

    © Johnson Controls, Inc. 201270

    Design Considerations

    Chillers

    Ensure chillers can provide full or greater capacity at 50-55 °F

    Entering Condenser Water Temps

     At reduced entering condenser water temperature centrifugal

    chillers can produce more than design load.

    VPF Systems Design/Control Considerations Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    71/84

    © Johnson Controls, Inc. 201271

    VPF Systems Design/Control Considerations Summary

    Design Considerations

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    72/84

    © Johnson Controls, Inc. 201272

    Design Considerations

    Chillers

    Ensure chillers can provide full or greater capacity at 50-55 °F

    Entering Condenser Water Temps

    Condenser Flow

    Recommend staying at roughly .8 or 80 % minimum flow

    Must stay above 3.3 fps or tube fouling becomes asymptotic

    Don’t vary flow too fast – recommend 10% per minute

    Don’t exceed 12 fps or 45 ft pressure drop for 2 pass (67 for 3 pass)

    Design Considerations

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    73/84

    © Johnson Controls, Inc. 201273

    Design Considerations

    Cooling Tower 

    Manufacturers do not like flow varying more than +/- 15 % from Design.

    Varying water flow too low

    Creates dry spots in fill resulting in large approach increases . (Chiller

    energy increases with increased approach)

    Varying too low increases CT maintenance

    Increases freezing damage risk

    Condenser Water Pumps

    Headered arrangement

    Energy Based Sequencing (CPO)

    Balancing Valve – minimize use. At least one fully open

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    74/84

    © Johnson Controls, Inc. 201274

     The 3 Central PlantMyths are:

    Summary

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    75/84

    © Johnson Controls, Inc. 201275

    Chilled Water Flow TracksCampus Cooling Load

    Summary

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    76/84

    © Johnson Controls, Inc. 201276

     VPF Systems mitigate at the plant the negative impact

    of low system delta T 

    Summary

    Chilled Water Flow TracksCampus Cooling Load

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    77/84

    © Johnson Controls, Inc. 201277

    Chilled Water Pump Speed Tracks Flow 

    Summary

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    78/84

    © Johnson Controls, Inc. 201278

     There is always some kind of control or statichead in variable speed systems. Use flow

    meters to track flow.

    Chilled Water Pump Speed Tracks Flow 

    Summary

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    79/84

    © Johnson Controls, Inc. 201279

    Pumps/Towers use more energy thanchillers can save

    Summary

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    80/84

    © Johnson Controls, Inc. 201280

    Reducing Condenser Water Flow and CT Air Flow

    saves more energy than increase on chiller down to

    about 80% typical.

    Pumps/Towers use more energy thanchillers can save

    Summary

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    81/84

    © Johnson Controls, Inc. 201281

    - Speed does not track flow, and flow does not track load

    - Reducing condenser flow and tower air flow saves net

    plant energy even though chiller energy increases as long

    as those reductions aren’t too low (80% min typical)

    - Headered VPF Plant mitigates low delta T impact.

    Summary

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    82/84

    © Johnson Controls, Inc. 201282

    CPO is an “off the shelf”control system

    SELECT DESIGN OPTIMIZE

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    83/84

    © Johnson Controls, Inc. 201283

    SELECT, DESIGN, OPTIMIZE 

    #1

    #2

    #3

    Optimizing Your Chiller Plant Room

    Webinar Program:

    Using Variable Speed Drives in Central Plants with Multiple Chillers

    Designing a Chiller Plant to be the Most Efficient

    Defining and Implementing Chiller Plant Optimization

    #2

    #3

     August 16, 2012

    October 11, 2012

    Conclusion

  • 8/20/2019 FINAL PDF Designing a Chiller Plant Room to Be the Most Efficient 10-12-12

    84/84

    - Please type in Q&A box lower right hand corner.

    - Moderator will handle questions to presenter.

    - Please complete the survey following the webinar 

    - Webinar will be recorded and available via download or streaming.

    Presentation slides will be available in pdf format at www.districtenergy.org

    - If you are listening to the webinar recording and have questions, send themto [email protected]

    - Registration information for the next webinar will be distributed towards the

    end of November 


Recommended