RSH ENGINEERING, INC. FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 1 Client: John Doe Address: 1234 Anywhere St, Anywhere, TX PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION 2006, RSH ENGINEERING, INC. 1 FRONT VIEW OF HOUSE INSPECTED 2 LEFT SIDE OF HOUSE: SEE PIC. # 3 TO PIC. # 15 FOR DETAILS 3 LEFT SIDE OF HOUSE: THE SPRINKLER HEAD IS BROKEN OFF AND SOIL HAS WASHED OUT FROM BASE OF SLAB. REPAIR SPRINKLER AND REPLACE THE SOIL. 4 LEFT SIDE OF HOUSE: CONDENSER PAD IS BELOW THE SURFACE OF THE SOIL. RECOMMEND INSTALLING A FRAMEWORK OF LANDSCAPE TIMBERS AROUND THE CONDENSER PAD AND FILLING IT WITH WHITE LANDSCAPE STONE AND PLACE THE CONDENSER PAD ON THE BED OF STONES. 5 LEFT SIDE OF HOUSE: THE FRESH AIR INTAKE DUCT IS MISSING THE COVER. 6 LEFT SIDE OF HOUSE: SCREW MISSING FROM THE CONDENSER COVER. 7 LEFT SIDE OF HOUSE: CLEAN THE BRICKS ALL AROUND THE HOUSE. 8 LEFT SIDE OF HOUSE: FOR CLOSE-UP AND DETAILS SEE PIC. # 9 TO PIC. # 11.
Transcript
Page 1: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 1Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

1

FRONT VIEW OF HOUSE INSPECTED

2

LEFT SIDE OF HOUSE:SEE PIC. # 3 TO PIC. # 15 FOR DETAILS

3

LEFT SIDE OF HOUSE:THE SPRINKLER HEAD IS BROKEN OFF ANDSOIL HAS WASHED OUT FROM BASE OFSLAB. REPAIR SPRINKLER AND REPLACETHE SOIL.

4

LEFT SIDE OF HOUSE:CONDENSER PAD IS BELOW THE SURFACEOF THE SOIL. RECOMMEND INSTALLING AFRAMEWORK OF LANDSCAPE TIMBERSAROUND THE CONDENSER PAD ANDFILLING IT WITH WHITE LANDSCAPE STONEAND PLACE THE CONDENSER PAD ON THEBED OF STONES.

5

LEFT SIDE OF HOUSE:THE FRESH AIR INTAKE DUCT IS MISSINGTHE COVER.

6

LEFT SIDE OF HOUSE:SCREW MISSING FROM THE CONDENSERCOVER.

7

LEFT SIDE OF HOUSE:CLEAN THE BRICKS ALL AROUND THEHOUSE.

8

LEFT SIDE OF HOUSE:FOR CLOSE-UP AND DETAILS SEE PIC. # 9 TOPIC. # 11.

Page 2: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 2Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

9

LEFT SIDE OF HOUSE:CLOSE-UP OF PIC. # 8.GENERAL NOTE: FILL/SEAL THE VOIDSWITH MORTAR. DON’T KNOW WHY THESEHOLES ARE PRESENT AT THIS HEIGHTTHROUGH OUT THE HOUSE. THIS IS THEFIRST TIME WE HAVE SEEN HOLES (WEEPHOLES???) AT THIS HEIGHT. THISLOCATION DOES NOT MAKE

10

LEFT SIDE OF HOUSE:CLOSE-UP OF PIC. # 8.FILL/SEAL THE VOIDS WITH MORTAR.

11

LEFT SIDE OF HOUSE:CLOSE-UP OF PIC. # 8.FILL/SEAL THE VOIDS WITH MORTAR.

12

LEFT SIDE OF HOUSE:FOR CLOSE-UP AND DETAILS SEE PIC. # 13.

13

LEFT SIDE OF HOUSE:CLOSE-UP OF PIC. # 12.CAULK WINDOW FRAME/BRICK INTERFACETO PREVENT AIR DRAFT AND WATERLEAKS TO THE INSIDE.

14

LEFT SIDE OF HOUSE:GENERAL NOTE: WINDOWSILL NOT ATMINIMUM 15 DEGREE ANGLE/SLOPE ASSPECIFIED BY THE BRICK INSTITUTE OFAMERICA (BIA) – CORRECT SLOPE OF ALLWINDOWSILLS NOT MEETING THISREQUIREMENT. THE BUILDING CODE(S) -INTERNATIONAL ONE-AND-TWO FAMILYDWELLING CODE # 703.7 -REQUIRESWINDOWSILLS TO HAVE A POSITIVE SLOPEAWAY FROM THE HOUSE ALSO 2000 IRCSECTION # 703.7 REQUIRES THIS POSITIVESLOPE.SEE NEXT PICTURE FOR CLOSEUP.

15

LEFT SIDE OF HOUSE:CLOSE-UP OF PIC. # 14.CLOSE-UP OF THE WINDOWSILL ANGLEMEASUREMENT SHOWING ZERO SLOPE.

16

FRONT SIDE OF HOUSE:SEE PIC. # 17 TO PIC. # 31 FOR DETAILS

Page 3: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 3Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

17

FRONT SIDE OF HOUSE:CAULK WINDOW FRAME/BRICK INTERFACETO PREVENT AIR DRAFT AND WATERLEAKS TO THE INSIDE.

18

FRONT SIDE OF HOUSE:1. LIGHT FIXTURES ARE LOOSE – RE-

TIGHTEN.2. SEAL/CAULK AT THE LIGHT FIXTURE

BASE.

19

FRONT SIDE OF HOUSE:1. FILL/SEAL THE VOIDS WITH MORTAR.2. CAULK AND PAINT THE TRIM JOINTS.

20

FRONT SIDE OF HOUSE:CAULK AND PAINT THE TRIM AND TRIMJOINTS.

21

FRONT SIDE OF HOUSE:CAULK AND PAINT THE TRIM AND TRIMJOINTS.

22

FRONT SIDE OF HOUSE:WEEP HOLE MISSING – ADD WEEP HOLE.WEEP HOLES SHOULD BE LOCATED AT THEFIRST COURSE ABOVE THE FOUNDATIONWALL OR SLAB, AND OTHER POINTS OFSUPPORT, INCLUDING STRUCTURALFLOORS, SHELF ANGLES AND LINTELS (1999STANDARD BUILDING CODE # 2111.1.3)AND 2000 IRC SECTION 703.7.5.

23

FRONT SIDE OF HOUSE:GENERAL NOTE: WEEP HOLES ARE NOTCLEAR OF MORTAR – CLEAR ALLWEEPHOLES OF MORTAR.

24

FRONT SIDE OF HOUSE:CAULK WINDOW FRAME/BRICK INTERFACETO PREVENT AIR DRAFT AND WATERLEAKS TO THE INSIDE.

Page 4: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 4Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

25

FRONT SIDE OF HOUSE:FILL/SEAL THE VOIDS WITH MORTAR.

26

FRONT SIDE OF HOUSE:FILL/SEAL THE VOIDS WITH MORTAR.

27

FRONT SIDE OF HOUSE:GENERAL NOTE: WINDOWSILL NOT ATMINIMUM 15 DEGREE ANGLE/SLOPE ASSPECIFIED BY THE BRICK INSTITUTE OFAMERICA (BIA) – CORRECT SLOPE OF ALLWINDOWSILLS NOT MEETING THISREQUIREMENT. THE BUILDING CODE(S) -INTERNATIONAL ONE-AND-TWO FAMILYDWELLING CODE # 703.7 -REQUIRESWINDOWSILLS TO HAVE A POSITIVE SLOPEAWAY FROM THE HOUSE ALSO 2000 IRCSECTION # 703.7 REQUIRES THIS POSITIVESLOPESEE NEXT PICTURE FOR CLOSEUP.

28

FRONT SIDE OF HOUSE:CLOSE-UP OF THE WINDOWSILL ANGLEMEASUREMENT SHOWING A NEGATIVESLOPE.

29

FRONT SIDE OF HOUSE:CLOSE-UP OF THE WINDOWSILL ANGLEMEASUREMENT SHOWING A NEGATIVESLOPE.

30

FRONT SIDE OF HOUSE:GENERAL NOTE: WINDOWSILL NOT ATMINIMUM 15 DEGREE ANGLE/SLOPE ASSPECIFIED BY THE BRICK INSTITUTE OFAMERICA (BIA) – CORRECT SLOPE OF ALLWINDOWSILLS NOT MEETING THISREQUIREMENT. THE BUILDING CODE(S) -INTERNATIONAL ONE-AND-TWO FAMILYDWELLING CODE # 703.7 -REQUIRESWINDOWSILLS TO HAVE A POSITIVE SLOPEAWAY FROM THE HOUSE ALSO 2000 IRCSECTION # 703.7 REQUIRES THIS POSITIVESLOPESEE NEXT PICTURE FOR CLOSEUP.

31

FRONT SIDE OF HOUSE:CLOSE-UP OF THE WINDOWSILL ANGLEMEASUREMENT SHOWING ZERO SLOPE.

32

RIGHT SIDE OF HOUSE:SEE PIC. # 33 TO PIC. # 47 FOR DETAILS

Page 5: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 5Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

33

RIGHT SIDE OF HOUSE:THE EXHAUST VENT DUCT FOR THE RANGEIS MISSING A COVER.

34

RIGHT SIDE OF HOUSE:REMOVE MORTAR FROM THE CLEANOUTCOVER.

35

RIGHT SIDE OF HOUSE:1. CAULK AND PAINT THE TRIM/SIDING

INTERFACES TO PREVENT AIR DRAFTS(ENERGY LOSS) AND WATER LEAKS(WATER DAMAGE AND MOLD) TO THEINSIDE.

2. CAULK TRIM/BRICK INTERFACE TOPREVENT WATER LEAKS (WATERDAMAGE AND MOLD) TO THE INSIDE.

36

RIGHT SIDE OF HOUSE:CAULK AND PAINT THE TRIM/SIDINGINTERFACES TO PREVENT AIR DRAFTS(ENERGY LOSS) AND WATER LEAKS(WATER DAMAGE AND MOLD) TO THEINSIDE.

37

RIGHT SIDE OF HOUSE:SEE NOTES AT PIC. # 36.

38

RIGHT SIDE OF HOUSE:SEE NOTES AT PIC. # 36.

39

RIGHT SIDE OF HOUSE:SEAL/CAULK AND PAINT BOTTOM OF BAYWINDOW AT ALL TRI M/SIDINGINTERFACES.

40

RIGHT SIDE OF HOUSE:CLEAN THE BRICKS ALL AROUND THEHOUSE.

Page 6: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 6Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

41

RIGHT SIDE OF HOUSE:CAULK WINDOW FRAME/BRICK INTERFACETO PREVENT AIR DRAFT AND WATERLEAKS TO THE INSIDE.

42

RIGHT SIDE OF HOUSE:FILL/SEAL THE VOIDS WITH MORTAR.

43

RIGHT SIDE OF HOUSE:WEEP HOLE MISSING – ADD WEEP HOLE.WEEP HOLES SHOULD BE LOCATED AT THEFIRST COURSE ABOVE THE FOUNDATIONWALL OR SLAB, AND OTHER POINTS OFSUPPORT, INCLUDING STRUCTURALFLOORS, SHELF ANGLES AND LINTELS (1999STANDARD BUILDING CODE # 2111.1.3)AND 2000 IRC SECTION 703.7.5.

44

RIGHT SIDE OF HOUSE:GENERAL NOTE: WINDOWSILL NOT ATMINIMUM 15 DEGREE ANGLE/SLOPE ASSPECIFIED BY THE BRICK INSTITUTE OFAMERICA (BIA) – CORRECT SLOPE OF ALLWINDOWSILLS NOT MEETING THISREQUIREMENT. THE BUILDING CODE(S) -INTERNATIONAL ONE-AND-TWO FAMILYDWELLING CODE # 703.7 -REQUIRESWINDOWSILLS TO HAVE A POSITIVE SLOPEAWAY FROM THE HOUSE ALSO 2000 IRCSECTION # 703.7 REQUIRES THIS POSITIVESLOPESEE NEXT PICTURE FOR CLOSEUP.

45

RIGHT SIDE OF HOUSE:CLOSE-UP OF THE WINDOWSILL ANGLEMEASUREMENT SHOWING ZERO SLOPE.

46

RIGHT SIDE OF HOUSE:GENERAL NOTE: WINDOWSILL NOT ATMINIMUM 15 DEGREE ANGLE/SLOPE ASSPECIFIED BY THE BRICK INSTITUTE OFAMERICA (BIA) – CORRECT SLOPE OF ALLWINDOWSILLS NOT MEETING THISREQUIREMENT. THE BUILDING CODE(S) -INTERNATIONAL ONE-AND-TWO FAMILYDWELLING CODE # 703.7 -REQUIRESWINDOWSILLS TO HAVE A POSITIVE SLOPEAWAY FROM THE HOUSE ALSO 2000 IRCSECTION # 703.7 REQUIRES THIS POSITIVESLOPESEE NEXT PICTURE FOR CLOSEUP

47

RIGHT SIDE OF HOUSE:CLOSE-UP OF THE WINDOWSILL ANGLEMEASUREMENT SHOWING ZERO SLOPE.

48

BACK SIDE OF HOUSE:SEE PIC. # 49 TO PIC. # 65 FOR DETAILS

Page 7: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 7Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

49

BACK SIDE OF HOUSE:FOR CLOSE-UP AND DETAILS SEE PIC. # 50.

50

BACK SIDE OF HOUSE:CLOSE-UP OF PIC. # 49.THE SPRINKLER HEAD IS BROKEN OFF ANDSOIL HAS WASHED OUT FROM BASE OFSLAB. REPAIR SPRINKLER AND REPLACETHE SOIL.

51

BACK SIDE OF HOUSE:CAULK THE VERTICAL FRIEZE BOARD /BRICK INTERFACE TO PREVENT WATERLEAKS (WATER DAMAGE AND MOLD) TOTHE INSIDE,

52

BACK SIDE OF HOUSE:SEE NOTES AT PIC. # 51.

53

BACK SIDE OF HOUSE:GENERAL NOTE: SEAL HOLES/GAPS ATTHE BRICK/FRIEZE BOARD INTERFACESALL AROUND HOUSE.

54

BACK SIDE OF HOUSE:SEE NOTES AT PIC. # 51.

55

BACK SIDE OF HOUSE:SEE NOTES AT PIC. # 51.

56

BACK SIDE OF HOUSE:ROUGH SLAB EDGE. SMOOTH THE SLABWITH EPOXY BASED CEMENT.

Page 8: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 8Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

57

BACK SIDE OF HOUSE:ROUGH SLAB EDGE. SMOOTH THE SLABWITH EPOXY BASED CEMENT.

58

BACK SIDE OF HOUSE:SEAT THE NAIL AND RE-PAINT.

59

BACK SIDE OF HOUSE:INSULATE THE WATER PIPES ABOVE THEWATER HEATER AND TAPE THEM SO THEINSULATION STAYS IN PLACE. MAINTAINCLEARANCE BETWEEN THE INSULATIONAND THE FLUE PER THE FLUEMANUFACTURER’S SPECIFICATIONS(USUALLY 1 -INCH).

60

BACK SIDE OF HOUSE:SECURE THE FLUE COLLAR AT THECEILING.

61

BACK SIDE OF HOUSE:SEAL/CAULK AT THE DOOR THRESHOLD/DOOR TRIMS/BRICK INTERFACE.

62

BACK SIDE OF HOUSE:FOR CLOSE-UP AND DETAILS SEE PIC. # 63.

63

BACK SIDE OF HOUSE:CLOSE-UP OF PIC. # 62.REMOVE THE LOOSE PIECE OF CONCRETEAND SMOOTH THE EDGE OF THE SLABWITH EPOXY BASED CEMENT.

64

BACK SIDE OF HOUSE:LADDER RUNG IS SPLIT. REPAIR ORREPLACE THE LADDER.

Page 9: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 9Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

65

BACK SIDE OF HOUSE:FILL/SMOOTH THE CEILING AT THE NAILHEADS AND REPAINT THE CEILING.

66

ROOF:GENERAL NOTE: THE ROWS OF SHINGLESAT EACH SIDE OF THE VENT SHOULDOVERLAP THE BASE TO PREVENT WATERLEAKS (WATER DAMAGE AND MOLD) TOTHE INSIDE.

67

ROOF:FOR CLOSE-UP AND DETAILS SEE PIC. # 68.

68

ROOF:CLOSE-UP OF PIC. # 67.

69

ROOF:SEE NOTES AT PIC. # 66.

70

ROOF:SEE NOTES AT PIC. # 66.

71

ROOF:SEE NOTES AT PIC. # 66.

72

ROOF:SEE NOTES AT PIC. # 66.

73

ROOF:SEE NOTES AT PIC. # 66.

74

ROOF:CAULK/SEAL THE FLASHING SLITS ONEACH SIDE AND ABOVE THE FLASHING.

75

ROOF: CAULK AND PAINT THETRIM/SIDING INTERFACES TO PREVENT AIRDRAFTS (ENERGY LOSS) AND WATERLEAKS (WATER DAMAGE AND MOLD) TOTHE INSIDE.

76

ROOF:1. SEAL THE CORNER OF THE CHIMNEY

CAP.2. CAULK/SEAL THE STORM COLLAR /

CHIMNEY CAP INTERFACE.

Page 10: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 10Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

77

ROOF:CAULK AND PAINT THE TRIM/SIDINGINTERFACES TO PREVENT AIR DRAFTS(ENERGY LOSS) AND WATER LEAKS(WATER DAMAGE AND MOLD) TO THEINSIDE.

78

ROOF:CAULK/SEAL THE FLASHING SLITS ONEACH SIDE AND ABOVE THE FLASHING.

79

ROOF:SEE NOTES AT PIC. # 77 .

80

ROOF:CAULK/SEAL THE STORM COLLAR /CHIMNEY CAP INTERFACE.

81

ROOF:GENERAL NOTE: THE ROWS OF SHINGLESAT EACH SIDE OF THE VENT SHOULDOVERLAP THE BASE TO PREVENT WATERLEAKS (WATER DAMAGE AND MOLD) TOTHE INSIDE.

82

ROOF:GENERAL NOTE: NAIL NOT SEATED BELOWSHINGLE CAUSING THE SHINGLE TO LIFTUP. SEAT THE NAIL AND SEAL THESHINGLE WHEREVER THE SHINGLES ARELIFTING UP.

83

ROOF:SEE NOTES AT PIC. # 82.FOR CLOSE-UP AND DETAILS SEE PIC. # 84AND PIC. # 85.

84

ROOF:CLOSE-UP OF PIC. # 83.

Page 11: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 11Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

85

ROOF:CLOSE-UP OF PIC. # 83.GENERAL NOTE: SEAL OVER ALL EXPOSEDNAILS AND/OR STAPLES HOLDING DOWNTHE SHINGLES WITH ROOF CEMENT.

86

ROOF:NAIL NOT SEATED BELOW SHINGLECAUSING THE SHINGLE TO LIFT UP. SEATTHE NAIL AND SEAL THE SHINGLE.

87

ROOF:CLOSE-UP OF PIC. # 86.

88

ROOF:BUMP ON ROOF (IDENTIFIED BY 4-REDSTICKERS IN THE SHAPE OF DIAMOND) –PROVIDE PROPER FRAMING AND/ORBRACING SUPPORT FOR THEDECKING/RAFTERS DIRECTLY BELOW THISSECTION OF ROOF.

89

ROOF:FOR CLOSE-UP AND DETAILS SEE PIC. # 90.

90

ROOF:CLOSE-UP OF PIC. # 89.

91

ROOF:BUMP ON ROOF (IDENTIFIED BY 4-REDSTICKERS IN THE SHAPE OF DIAMOND) –PROVIDE PROPER FRAMING AND/ORBRACING SUPPORT FOR THEDECKING/RAFTERS DIRECTLY BELOW THISSECTION OF ROOF.

92

ROOF:SEE NOTES AT PIC. # 91.

Page 12: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 12Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

93

ATTIC:PROVIDE A FILTER FOR THE AC UNIT.HAVE THE EVAPORATOR CHECKED TO SEEIF IT NEEDS TO BE CLEANED.

94

ATTIC:MAINTAIN A MINIMUM OF 1 INCH BETWEENCOMBUSTIBLES AND FLUE.

95

ATTIC:THE WEBBING THAT SUSPENDS THE DUCTIS LESS THAN 1-1/2 INCHES WIDE AT THEDUCT AND IS CAUSING THE DUCT TO BERESTRICTED.

96

ATTIC:1. INTERNATIONAL RESIDENTIAL

CODE # 1307.1, 2408.1 AND 2000UNIFORM MECHANICAL CODE # 304.1- INSTALL APPLIANCES TOMANUFACTURER’S SPECIFICATION

2. INSULATION/COMBUSTIBLES INCONTACT WITH THE FLUE – PROVIDECLEARANCE PER THE FLUEMANUFACTURERS’ REQUIREMENTS(USUALLY IT IS AROUND 1-2 INCHESTO ALL COMBUSTIBLES).

97

INSIDE LIVING ROOM:FOR CLOSE-UP AND DETAILS SEE PIC. # 98

98

INSIDE LIVING ROOM:CLOSE-UP OF PIC. #97.PAINT MISMATCH ON CEILING.

99

INSIDE LIVING ROOM:CAULK AROUND THE WINDOW FRAMES.

100

INSIDE FOYER:1. THE DOOR BINDS AND HAS BEEN

TRIMMED IN AN EFFORT TO CORRECTTHIS. THE DOOR CONTINUES TO BIND.ADJUST THE DOOR SHIMS TOACHIEVE PROPER ALIGNMENT OFDOOR AND FRAME.

2. PAINT THE EDGE OF THE DOOR.

Page 13: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 13Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

101

INSIDE FOYER:CLOSE-UP OF PIC. # 100 SHOWING THEINADEQUATE CLEARANCE BETWEEN THEDOOR AND THE FRAME.

102

INSIDE FOYER:SCRAPE MARK ON WALL.

103

INSIDE FOYER:PAINT MISMATCH ON CEILING.

104

INSIDE HALLWAY NEAR FRONT BATH:TEXTURE MISMATCH ON WALL.

105

INSIDE FRONT HALLWAY BATH:DRAWER GUIDES ARE IMPROPERLYINSTALLED. THE DRAWER FACE IS NOTFLUSH WITH THE CABINET WHEN CLOSED.

106

INSIDE FRONT HALLWAY BATH:BASEBOARD IS OVERCUT. REPAIR ORREPLACE THE BASEBOARD.

107

INSIDE FRONT HALLWAY BATH:TEXTURE MISMATCH ON WALL.

108

INSIDE FRONT HALLWAY BATH:PAINT TOP OF DOOR.CAULK TOP OF DOOR TRIM.PAINT TOP OF DOOR TRIM.

Page 14: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 14Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

109

INSIDE LEFT MIDDLE BEDROOM:FOR CLOSE-UP AND DETAILS SEE PIC. # 110

110

INSIDE LEFT MIDDLE BEDROOM :CLOSE-UP OF PIC. # 109.FINISH IS MARRED ON THE HARDWOODFLOORING. REPAIR OR REPLACE.

111

INSIDE HALLWAY NEAR FRONT LEFTBEDROOM:CLEAN PAINT RUN FROM THE BASE TRIM.

112

INSIDE FRONT LEFT BEDROOM:FOR CLOSE-UP AND DETAILS SEE PIC. # 113

113

INSIDE FRONT LEFT BEDROOM:CLOSE-UP OF PIC. # 112.PAINT MISMATCH ON CEILING.

114

INSIDE FRONT HALLWAY:SWITCH PLATE COVER IS LOOSE.

115

INSIDE KITCHEN:ELECTRICAL BOX NOT INSTALLED.

116

INSIDE KITCHEN:ELECTRICAL BOX NOT INSTALLED.

117

INSIDE KITCHEN:ELECTRICAL BOX NOT INSTALLED.

118

INSIDE KITCHEN:REPAIR GAP AT SPLASHBACK INTERFACES.

119

INSIDE KITCHEN:THE EXHAUST DUCT IS NOT INSTALLEDABOVE THE RANGE.

120

INSIDE KITCHEN:BULBS MISSING FROM HOOD VENT.

Page 15: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 15Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

121

INSIDE KITCHEN:IMPROPERLY CUT TRIM.

122

INSIDE KITCHEN:SEPARATION OF CABINET FACING.

123

INSIDE UTILITY ROOM:DRYWALL DAMAGED AT THE DRYER DUCT.

124

INSIDE UTILITY ROOM:CLOSE-UP OF PIC. # 123.

125

INSIDE FRONT LEFT BEDROOM:PAINT DAMAGED ON DOOR. REPAINT THEDOOR.

126

INSIDE FRONT HALLWAY:PAINT DAMAGED ON DOOR. REPAINT THEDOOR.

127

INSIDE FRONT HALLWAY BATH:TEXTURE MISMATCH ON WALL.

128

INSIDE FRONT HALLWAY BATH:CLOSE-UP OF PIC. # 127.

129

INSIDE LIVING ROOM:PAINT DAMAGED AT CORNER.

130

INSIDE HALLWAY NEAR KITCHEN:PAINT MISMATCH ON WALL.

131

INSIDE HALLWAY NEAR MASTERBEDROOM:PAINT MISMATCH ON WALL.

132

INSIDE HALLWAY NEAR MASTERBEDROOM:CLOSE-UP OF PIC. # 131.

Page 16: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 16Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

133

INSIDE HALLWAY NEAR MASTERBEDROOM:PAINT MISMATCH ON WALL.

134

INSIDE HALLWAY NEAR MASTERBEDROOM:PAINT/TEXTURE MISMATCH ON WALL.

135

INSIDE HALLWAY NEAR MASTERBEDROOM: IMPROPER FINISH INDRYWALL.

136

INSIDE MASTER BEDROOM:DOOR DAMAGED

137

INSIDE MASTER CLOSET:CLOTHES ROD(S) NOT SCREWED TOBRACKETS IN CLOSET.

138

INSIDE MASTER CLOSET:TEXTURE MISMATCH ON WALL.

139

INSIDE MASTER CLOSET:DRYWALL DAMAGED IN CORNER ABOVESHELF.

140

INSIDE MASTER CLOSET:TEXTURE MISMATCHES ON WALL.

141

INSIDE MASTER BATH:TEXTURE MISMATCH ON CEILING.

142

INSIDE MASTER BATH :1. ESCUTCHEON MISSING AT DRAIN

PIPE/WALL INTERFACE.2. DRAIN PIPE IS LOOSE AND LEAKS.

143

INSIDE MASTER BATH:SEE NOTES AT PIC. # 142.

144

INSIDE MASTER BATH:TUB INSTALLATION IS INCOMPLETE.

Page 17: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 17Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

145

INSIDE MASTER BATH:BASEBOARD INSTALLATION ISINCOMPLETE.

146

INSIDE MASTER BATH :DOOR IS SPLIT. REPLACE THE DOOR.

147

INSIDE MASTER BATH:DOOR FRAME IS DAMAGED. REPAIR ORREPLACE.

148

INSIDE:DRYWALL IS DAMAGED AT CORNER.

149

INSIDE FAMILY ROOM:1. TEXTURE MISMATCH ON WALL.2. PAINT MISMATCH ON WALL.

150

INSIDE FAMILY ROOM:REMOVE THE PROTRUDING NAIL ANDPATCH WALL.

151

INSIDE FAMILY ROOM:LATCH BROKEN OF WINDOW. REPLACETHE WINDOW.

152

INSIDE KITCHEN:SEPARATION OF CABINET WALL ANDCABINET FLOOR.

153

INSIDE FOYER:THE WALL IS NOT STRAIGHT AT THEENTRANCE TO THE FRONT OFFICE.

154

INSIDE FOYER:BUMP/RIDGE ON CEILING. REMOVE THEDRYWALL AND CORRECT THE FRAMING.

155

INSIDE LIVING ROOM:NAIL POP ON CEILING.

156

INSIDE LIVING ROOM:NAIL POP ON CEILING.

Page 18: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 18Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

157

INSIDE FAMILY ROOM:FOR CLOSE-UP AND DETAILS SEE PIC. # 158.

158

INSIDE FAMILY ROOM:CLOSE-UP OF PIC. # 157.TEXTURE MISMATCH ON CEILING.

159 MASTER BATH:PAINT TOPS OF DOORS.CAULK TOP OF DOOR TRIMS.PAINT TOP OF DOOR TRIMS.

160 FRONT LEFT BEDROOM:CLOTHES ROD(S) NOT SCREWED TOBRACKETS IN CLOSET.

161 LEFT MIDDLE BEDROOM:CLOTHES ROD(S) NOT SCREWED TOBRACKETS IN CLOSET.

162 OTHER NOTES:SEVERAL LIGHT FIXTURES ARE NOTINSTALLED.JOIST MARK OR DRYWALL JOINT VISIBLEIN KITCHEN CEILING ABOVE COUNTERTOP.

Page 19: FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 … · 23 front side of house: general note: weep holes are not clear of mortar – clear all weepholes of mortar. 24 front side

RSH ENGINEERING, INC.FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 19Client: John Doe Address: 1234 Anywhere St, Anywhere, TXPIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION PIC # DESCRIPTION

2006, RSH ENGINEERING, INC.

John Doe,

On 5/02/2006, RSH Engineering, Inc performed a Final Walk-Through Inspection (FWTI) on your property. The following areas were inspected:Structural, Roof Covering, AC/Heat Plant, Water Heater, Electric Panel, Electrical (kitchen, baths, laundry, etc.), Appliances, Attic Insulation,Bath-Wall-Tile, Doors, Windows, Fireplace, Interior & Exterior Finishes, Gas & Carbon Monoxide Leak Test, and Microwave leak test.

Above are the findings of the FWTI. The items highlighted above fall under any one or all of these categories:1. The ones that are functional, however, further evaluation and minor repair or service, or proper installation is recommended.2. Other items identified may be defective or inadequate or improperly installed and further evaluation and major repair or replacement or properinstallation is recommended.3. Any items missing will also be highlighted above.

NOTE: ANY REPAIR WORK RECOMMENDED IN THIS REPORT SHOULD BE PERFORMED BY LICENSED, INSURED, CONTRACTORS ONLY, AND WITHPROPER BUILDING PERMITS. ADDITIONAL DEFECTS MAY BE DISCOVERED BY THE CONTRACTOR PERFORMING THE REPAIR, THAT MAY REQUIREADDITIONAL WORK OR REPLACEMENT ABOVE AND BEYOND THE RECOMMENDATIONS MADE IN THIS REPORT. OTHER ENGINEERS, INSPECTORS,CONTRACTORS, APPRAISERS, ADJUSTERS, OWNERS, REALTORS, ETC., MAY HAVE OPINIONS THAT DIFFER FROM THE OPINIONS OF THIS INSPECTIONCOMPANY.

If you have any questions or comments regarding this FWTI report, please contact me at (972) 203-3003 or via e-mail [email protected].

Regards,

Mathew Joseph, P.E. (License # 78695)PresidentRSH Engineering, Inc.