Technical Databook
Fire & Smoke ActuatorsSpring-Return and Non-Spring-Return
Version 1
Belimo Asia Pacific
2 Sub
ject
to te
chni
cal c
hang
es.
Spring-Return18Nm/12Nm F11Nm/8.5Nm FG6Nm/4Nm* LF
Angle Rotation max. 95° Blank
Power SupplyAC/DC 24V 24AC/DC 24...48V 24...48 (only for BR..)AC 230V 230
* Torque of BLF24-SR is 4Nm/4Nm.
* FSAF24(-S) US power supply is AC/DC 24V.
Fire & Smoke Actuator Standard Type Naming
max. 180° G
Open/Close BlankModulating DC 2(0)...10V control -SRThermal trip -T
Product Naming
Fire and Smoke Actuator (CE Certification) B
Non-Spring-Return40Nm E24Nm15Nm
SBS(E) system connection -ST
EGLE / R
Spring-Return15Nm AF7.9Nm NF3.5Nm LF
Power Supply
AC 24V* 24AC 230V 230
Spring-Return
Products meet the America sales and applications standard
Open/Close BlankModulating DC 2(0)...10V control -SRAuxiliary Switch -S
Product Naming FS LF 24 -S US
Fire and Smoke Actuator (UL555/UL555S) FS
B F G 24 -SR
Sub
ject
to te
chni
cal c
hang
es.
3
Contents
Note:
The modification and mounting of the actuator to the fire damper is made by the manufacturer of the damper.
For this reason, the Fire & Smoke Actuator is supplied directly to fire damper manufacturers. The manufacturer then bears over all responsi-bility for a proper function of the damper.
The enclosure of the actuator equipment may only be opened by the manufacturer. It contains no components which the user can replace or repair.
BLF24(-T)(-ST)6BLF24-SR7
Fire and Smoke Spring-Return Actuators, 6/4Nm
BLF230(-T)
8BF24(-T)(-ST)9
Fire and Smoke Spring-Return Actuators, 18/12Nm
BF230(-T)BF24-SR(-T)
10
11BFG24(-T)(-ST)12
Fire and Smoke Spring-Return Actuators, 11/8.5Nm
BFG230(-T)
FSLF24(-S) US 13FSLF230(-S) US 14
FSNF230(-S) US 16
Fire and Smoke Spring-Return Actuators, 3.5Nm
FSNF24(-S) US 15
Fire and Smoke Spring-Return Actuators, 7.9Nm
FSAF24(-S) US 17FSAF230(-S) US 18
Fire and Smoke Spring-Return Actuators, 15Nm
5
4
Control and monitoring, power unit
SBS(E)-Control system overview
Connections and display devices /
34
35
Block diagram
B..E../BR.. series 29
Accessories
Wiring diagrams
BAE72B (-S) 32
33
Application information
30
ZTPC600-B
28FS..US series 26B..F.. series
B..F../FS..US series B..E.. series 31
BE24(-12)(-ST) 23
Smoke Control Non-Spring-Return Actuators, 40Nm
BE230(-12) 24
BEG230 22BEG24(-ST) 21
Smoke Control Non-Spring-Return Actuators, 24Nm
BLE24(-ST) 19
Smoke Control Non-Spring-Return Actuators, 15Nm
BLE230 20
BR24-48-F-ST 25
Smoke Control Non-Spring-Return Actuators, 15Nm
Product overviewB..F..
FS.. US
B..E..
BR..
•
•
* For BLF24-SR, the motor torque is 4Nm and the spring return torque is 4Nm, motor running time is 150s.** BLF24-SR has 1 SPDT auxiliary switch built-in.***BLF24-SR has no manual override function.
Fire and Smoke protection Spring-Return Actuator BLF.. BF.. BFG.. FSLF..US FSNF..US FSAF..USAgency listing
Torque -Motor 6Nm 18Nm 11Nm
Open/Close
-Spring return 4Nm 12Nm 8.5Nm
AC 24V 50/60Hz, DC 24V BLF24 BF24 BFG24 FSAF24 US
AC 24V 50/60Hz, DC 24V with thermal trip (72oC) BLF24-T BF24-T BFG24-T
AC/DC 24V with plug connect to BKN230-24 BLF24-ST BF24-ST BFG24-ST
AC 24V 50/60Hz, DC 24V with thermal trip andplug connect to BKN230-24 BLF24-T-ST BF24-T-ST BFG24-T-ST
AC 24V 50/60Hz FSLF24 US FSNF24 US
AC 230V 50/60Hz BLF230 BF230 BFG230 FSLF230 US FSNF230 US FSAF230 US
AC 230V 50/60Hz with thermal trip BLF230-T BF230-T BFG230-T
Modulating (AC 24V 50/60Hz, DC 24V)
Feedback signal DC 2...10VControl signal DC 2(0)...10V
BLF24-SR* BF24-SR(-T) FSAF24-SR(-S) US
Running time -Motor 40..75s 140s 140s 15s 15s 75s-Spring return 20s 16s 20s 15s 15s 20s
Built-in 2 SPDT auxiliary switch FSNF24-S USFSNF230-S US
Built-in 2 SPST auxiliary switch FSLF24-S USFSLF230-S US
FSAF24-S USFSAF230-S US
Form-fit 10x10mm
Clamp
Manual override function Yes
Angle of rotation Max.180°
Direction of rotation selectable by L/R mounting
Max. 95° Max. 95°
CE certification UL555 and UL555S
Yes
12x12mm,(10x10mm with adapter)
3.5Nm 7.9Nm 15Nm
Built-in**
Yes***
Smoke control Non-Spring-Return Actuator BLE.. BE.. BEG.. BR..Agency listing
Torque 15Nm 40Nm 24Nm 15Nm
Open/Close
AC 24V 50/60Hz, DC 24V BLE24 BE24 BEG24
AC/DC 24V with plug connect to BKNE230-24 BLE24-ST BE24-ST BEG24-ST
AC 24...48V compatible with control unit for pulse triggering BSIA24-48(-R) BR24-48-F-ST
AC 230V 50/60Hz BLE230 BE230 BEG230
Running time 30s 60s 60s 30s
Form-fit 12x12mm
Yes
BE24-12BE24-12-STBE230-12 Yes Yes
Form-fit 14x14mm YesAngle of rotation Max. 180° Max. 105°
Direction of rotation selectable by L/R mountingBuilt-in 2 SPDT auxiliary switch
Manual override function Yes
CE certification
Yes
Yes
Max. 95°
12.7...20mm 12.7...26mm
4 Sub
ject
to te
chni
cal c
hang
es.
Fire and Smoke Damper Actuator product overview
Sub
ject
to te
chni
cal c
hang
es.
5
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Power consumption 5W @ running / 2.5W @ holding
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Wire sizing 7VA (Imax 5.8A @ 5ms)
Connection cable -Motor 1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Functional data Torque - Motor Min. 6Nm Min. 4Nm
Direction of rotation Selectable by L/R installation
Angle of rotation
Running time - Motor
Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)
40...75s (0...6Nm)~20s @ -20...+50°C/max. 60s @ -30°C
Position indication Mechanical with pointerService life >60,000 cycles
Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54
Ambient temperature - Normal duty -30...+50°C
- Safety duty
Non-operation temperature -40...+50°C (-40...+80°C without thermal trip)Humidity test 95%RH, non condensingMaintenance Maintenance-free
Dimensions / weight Dimensions (L x W x H) 185x98x57.6mmShaft diameter Form-fit 12x12mm (10mm with adapter supplied)Weight BLF24 (-ST) Approximately 1540g
BLF24-T(-ST) Approximately 1630g
Fire and Smoke Spring-Return Actuator BLF24(-T)(-ST)
- Spring return
- Spring return
Thermal trip (-T: BAE72B-S)
EMC CE according to 2004/108/EC
Dimensions [mm]
BLF24-ST
( ..-ST with plug connectors, suitable for BKN230-24)
Safe position will be attained up to max. 75°C
BAE72B-S: see page 32
• For control of Fire and Smoke Dampers • in HVAC systems • Torque: 6/4Nm • Nominal voltage: AC/DC 24V • Manual override function• Control: Open/Close
-Auxiliary switch
Mode of operation Type 1.AA.B
Auxiliary switch-Switching points fixed at 5° , 80°
Max. 95° (incl. 5° spring pretensioning) 57
.657
185
155
93 18
8012.249
6.5
10 25
120
98
2 SPDT, 1mA...3(0.5)A, DC 5V...AC 250V
Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)
when initiated by a thermal trip
6 Sub
ject
to te
chni
cal c
hang
es.
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Power consumption 2.5W @ running / 1W @ holding
Nominal voltage range AC 19.2 ... 28.8V, DC 21.6...28.8V
Wire sizing 5VA (Imax 5.8A @ 5ms)
Connection cable -Motor 1m, 4x0.75mm2 (halogen-free)1m, 3x0.75mm2 (halogen-free)
Functional data Torque - Motor Min. 4Nm Min. 4Nm
Direction of rotation -Motor-Spring return
Selectable by L/R switchSelectable by L/R installation
Angle of rotation Max. 95°Running time - Motor
Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)
150s~20s (@ tamb=20°C)
Position indication Mechanical with pointer
Control signal DC 2 (0) ...10V (input impedance 100kΩ)Feedback signal DC 2...10V
Service life >60,000 cyclesWorking conditions Protection class III (safety extra-low voltage)
Degree of protection IP54EMC CE according to 2004/108/ECMode of operation Type 1.AA.BAmbient temperature - Normal duty -30...+50°C
- Safety duty Safe position will be attained up to max. 75°C
Non-operation temperature -40...+80°CHumidity test 95%RH, non condensingMaintenance Maintenance-free
Dimensions / weight Dimensions (L x W x H) 185x98x57.6mmShaft diameter Form-fit 12x12mm (10mm with adapter supplied)Weight Approximately 1630g
Fire and Smoke Spring-Return Actuator BLF24-SR
- Spring return
- Spring return
Dimensions [mm]
• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 4/4Nm• Nominal voltage: AC/DC 24V• Control signal: DC 2(0)...10V• Position feedback: DC 2...10V
Auxiliary switch 1 SPDT, 1mA...3(0.5)A, AC 250Vfixed at 5°
57.657
185
155
93 18
8012.249
6.5
10 25
120
98
-Auxiliary Switch
Sub
ject
to te
chni
cal c
hang
es.
7
Technical data
Electrical data Nominal voltage AC 230V 50/60Hz
Power consumption 6W @ running/3W @ holding
Nominal voltage range AC 198 ... 264V
Wire sizing 7VA (Imax. 150mA @ 10ms)
Connection cable -Motor 1m, 2x0.75mm2 (halogen-free)
1m, 6x0.75mm2 (halogen-free)
Functional data Torque - Motor Min. 6Nm
Min. 4Nm
Direction of rotation Selectable by L/R installationAngle of rotation Max. 95°Running time - Motor
Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)
40...75s (0...6Nm)
Position indication Mechanical with pointerService life >60,000 cycles
Working conditions Protection class II (all insulated)Degree of protection IP54
Ambient temperature - Normal duty -30...+50°C- Safety duty Safe position will be attained up to max. 75°C
when initiated by a thermal trip
Non-operation temperature
Humidity test 95%RH, non condensingMaintenance Maintenance-free
Dimensions / weight Dimensions (L x W x H) 185x98x57.6mmShaft diameter Form-fit 12x12mm (10mm with adapter supplied)Weight Approximately 1730g
Fire and Smoke Spring-Return Actuator BLF230(-T)
- Spring return
- Spring return
Thermal trip (-T: BAE72B-S) Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)
EMC CE according to 2004/108/EC
Dimensions [mm]
185
155
93 18
57.657
8012.249
6.5
10 25
120
98
BAE72B-S: see page 32
• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 6/4Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close
-Auxiliary switch
Auxiliary switch 2 SPDT, 1mA...3(0.5)A, DC 5V...AC 250Vfixed at 5° , 80°-Switching points
(incl. 5° spring pretensioning)
-40...+50°C (-40...+80°C without thermal trip)
Type 1.AA.B Mode of operation
~20s @-20...+50°C/max. 60s @ -30°C
8 Sub
ject
to te
chni
cal c
hang
es.
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Power consumption 7W @ running / 2W @ holding
Nominal voltage range AC 19.2...28.8V, DC 21.6 ... 28.8V
Wire sizing 10VA (Imax 8.3A @ 5ms)
Connection cable - Motor - Auxiliary Switch
1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Functional data Torque - Motor Min. 18Nm Min. 12Nm
Direction of rotation Selectable by L/R installation
Angle of rotation Max. 95°
Running time - Motor
Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)
140s~16s (@tamb=20°C)
Position indication Mechanical with pointerService life >60,000 cycles
Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54
Ambient temperature - Normal duty -30...+50°C- Safety duty Safe position will be attained up to max. 75°C
when initiated by a thermal trip
Non-operation temperatureHumidity test 95%RH, non condensingMaintenance Maintenance-free
Dimensions / weight Dimensions (L x W x H) 248x98x58.6mm
Shaft diameter Form-fit 12x12mm (10mm with adapter supplied)
Weight Approximately 2800g
Fire and Smoke Spring-Return Actuator BF24(-T)(-ST)
- Spring return
- Spring return
(..-T..) operating temperaturethermal trips BAE72B-S
Tf1: duct outside temperature 72°C *Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)
Dimensions [mm]
L
40
6.5
18850 10
ø5.2
248
175.6
27.2
4040
8098
1717
5.1
1
12.2
58.6
BF24-ST
BAE72B-S: see page 32
( ..-ST with plug connectors, suitable for BKN230-24)
• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 18/12Nm• Nominal voltage: AC/DC 24V• Manual override function• Control: Open/Close
Auxiliary switch 2 SPDT, 1mA...6(3)A, DC 5V...AC 250V-Switching points fixed at 5° , 80°
Mode of operation Type 1.AA.B
-40...+50°C (-40...+80°C without thermal trip)
(incl. 5° spring pretensioning)
EMC CE according to 2004/108/EC
Sub
ject
to te
chni
cal c
hang
es.
9
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Power consumption 7W @ running / 2W @ holding
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Wire sizing 10VA (Imax 8.3A @ 5ms)
Connection cable -Motor -Auxiliary switch
1m, 4x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Functional data Torque - Motor Min. 18Nm Min. 12Nm
Direction of rotation Selectable by L/R installation
Angle of rotation Max. 95°
Auxiliary switch- Switching points
2 SPDT, 1mA...6(3)A, DC 5V...AC 250Vfixed at 5° , 80°
Running time - Motor
Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)
150s~16s (@tamb=20°C)
Position indication Mechanical with pointer
Control signal DC 2 (0)...10V (input impedance 100k Ω)Feedback signal DC 2...10V
Service life >60,000 cycles
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP54
EMC CE according to 2004/108/EC
Ambient temperature - Normal duty -30...+50°C- Safety duty -30...+75°C (24hr)
Non-operation temperatureHumidity test 95%RH, non condensingMaintenance Maintenance-free
Dimensions / weight Dimensions (L x W x H) 248x98x58.6mmShaft diameter Form-fit 12x12mm (10mm with adapter supplied)Weight Approximately 2800g
Fire and Smoke Spring-Return Actuator BF24-SR(-T)
- Spring return
- Spring return
Dimensions [mm]
L
40
6.5
18850 10
Ø5.2
248
175.6
27.2
4040
8098
1717
5.1
1
12.2
58.6
Thermal trip (-T: BAE72B-S) Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)
BAE72B-S see page 32
• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 18/12Nm • Nominal voltage: AC/DC 24V• Manual override function• Control signal: DC 2 (0)...10V • Position feedback: DC 2...10V
-40...+50°C
Mode of operation Type 1.AA.B
10 Sub
ject
to te
chni
cal c
hang
es.
fixed at 5° , 80°
Technical data
Electrical data Nominal voltage AC 230V 50/60Hz
Power consumption 8W @ running/3W @ holding
Nominal voltage range AC 198...264V
Wire sizing 12.5VA (Imax 500mA @ 5ms)
Connection cable -Motor -Auxiliary switch
1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Functional data Torque - Motor Min. 18Nm Min. 12Nm
Direction of rotation Selectable by L/R installation
Angle of rotation Max. 95° (incl. 5° spring pretensioning)
Auxiliary switch 2 SPDT, 1mA...6(3)A, DC 5V...250V
Running time - Motor
Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)
140s~16s (tamb=20°C)
Position indication Mechanical with pointer
Service life >60,000 cycles
Working conditions Protection class II (all insulated)Degree of protection IP54
Ambient temperature - Normal duty -30...+50°C- Safety duty
Non-operation temperature
Humidity test 95%RH, non condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (L x W x H) 248x98x58.6mm
Shaft diameter Form-fit 12x12mm (10mm with adapter supplied)
Weight Approximately 3100g
Fire and Smoke Spring-Return Actuator BF230(-T)
• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 18/12Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close
- Spring return
- Spring return
Thermal trip (-T: BAE72B-S) Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)
EMC CE according to 2004/108/EC
Mode of operation Type 1.AA.B
Dimensions [mm]
L
40
6.5
18850 10
ø5.2
248
175.6
27.2
4040
8098
1717
5.1
1
12.2
58.6
Safe position will be attained up to max. 75°Cwhen initiated by a thermal trip
-Switching points
BAE72B-S see page 32
-40...+50°C (-40...+80°C without thermal trip)
Sub
ject
to te
chni
cal c
hang
es.
11
25° , 145° (angles of rotation of damper: 5° , 80° )
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Power consumption 7W @ running / 2W @ holding
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Wire sizing 10VA (Imax 8.3A @ 5ms) / (..T type: Imax 5.8A @ 5ms)
Connection cable - Motor - Auxiliary switch
1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Functional data Torque - Motor Min. 11Nm Min. 8.5Nm
Direction of rotation Selectable by L/R installation
Auxiliary switch 2 SPDT, 1mA...6(3)A, DC 5V...AC 250V
Running time - Motor
Sound power level Motor max. 45d(A), Spring return approximately 62dB(A)
140s~20s (tamb=20°C)
Position indication Mechanical with pointerService life >50,000 cycles
Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54EMCMode of operationAmbient temperature - Normal duty
- Safety duty
Non-operation temperature
Humidity test 95%RH, non condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (L x W x H) 248x98x58.6mm
Shaft diameter Form-fit 10x10mm
Weight Approximately 2800g
Fire and Smoke Spring-Return Actuator BFG24(-T)(-ST)
• For control of Fire and Smoke Dampers in HVAC systems• Torque motor: 11/8.5Nm• Nominal voltage: AC/DC 24V• Manual override function• Control: Open/Close
- Spring return
- Spring return
Dimensions [mm]
Angle of rotation Max. 180°
BFG24-ST
Thermal trip (-T: BAE72B-S)
-30...+50°C
Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)
(..ST with plug connectors, suitable for BKN230-24)
Safe position will be attained up to max. 75°Cwhen initiated by a thermal trip
L
40
6.5
18850 10
ø5.2
248
175.6
27.2
4040
8098
1717
5.1
1
10.2
58.6BAE72B-S: see page 32
-Switching points
CE according to 2004/108/ECType 1.AA.B
-40...+50°C (-40...+80°C without thermal trip)
12 Sub
ject
to te
chni
cal c
hang
es.
Technical data
Electrical data Nominal voltage AC 230V 50/60Hz
Power consumption 8W @ running / 3W @ holding
Nominal voltage range AC 198...264V
Wire sizing 12.5VA (Imax 500mA @ 5ms )
Connection cable - Motor - Auxiliary switch
1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Functional data Torque - Motor Min. 11Nm Min. 8.5Nm
Direction of rotation Selectable by L/R installation
Auxiliary switch
Running time - Motor
Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)
140s~20s ( tamb=20°C)
Position indication Mechanical with pointerService life >50,000 cycles
Working conditions Protection class II (all insulated)Degree of protection IP54EMC
Ambient temperature - Normal duty -30...+50°C- Safety duty Safe position will be attained up to max. 75°C
when initiated by a thermal tripNon-operation temperatureHumidity test 95%RH, non condensingMaintenance Maintenance-free
Dimensions / weight Dimensions (L x W x H) 248x98x58.6mmShaft diameter Form-fit 10x10mm Weight Approximately 3100g
• For control of Fire and Smoke Dampers• in HVAC systems • Torque: 11/8.5Nm•• Nominal voltage: AC 230V• Manual override function• Control: Open/Close
- Spring return
- Spring return
Dimensions [mm]
Angle of rotation Max. 180°
Thermal trip (-T: BAE72B-S) Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)
-Switching points
L
40
6.5
18850 10
ø5.2
248
175.6
27.2
4040
8098
1717
5.1
1
10.2
58.6
CE according to 2004/108/ECMode of operation
BAE72B-S: see page 32
Fire and Smoke Spring-Return Actuator BFG230(-T)
2 SPDT, 1mA...6(3) A, DC 5V...AC 250V25° , 145° (angles of rotation of damper: 5° , 80° )
-40...+50°C (-40...+80°C without thermal trip)
Type 1.AA.B
Class 2 supply
Sub
ject
to te
chni
cal c
hang
es.
13
Technical data
Electrical data AC 24V 50/60Hz
Power consumption 5VA @ running / 3.5VA @ holding
Power supply
5VA (Class 2 power supply)
Connection cable -Motor 1m, 18ga, 2 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector
Functional data
Working conditions
Dimensions / weight
Torque Min. 3.5Nm
Direction of rotation Selectable by CW/CCW installation
Angle of rotation Max. 95°
Auxiliary switch (-S) 2 SPST, 1mA @ DC 5V, 3(0.5)A, 120/250Vfixed at 10° and 85°
Running time - Motor <15s at rated voltage and torque<15s
Position indication Mechanical
Protection class
Degree of protection IP 30 / Enclosure type 1
Mode of operation Type 1.AA.B
Agency listed UL60730-1, UL60730-2-14 and CAN/CSA E60730-1:02
Ambient temperature - Normal duty 0...+50°C- Safety duty 3 Open/Close cycles after 1/2hr @ 177°C
Non-operation temperature -40...+80°C
Humidity test 5...95%RH, non condensing
Maintenance Maintenance-free
179x98x82mm
Shaft diameter 12.7...20mm
Weight Approximately 1700g
Fire and Smoke Spring-Return Actuator FSLF24(-S) US
• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 3.5Nm• Running time: 15s• Control: Open/Close•
- Spring return
Transformer sizing
Dimensions (L x W x H)
Dimensions [mm]
12.7...20
Nominal voltage range AC 21.6...26.4V
19 [0.75"]
6 [0.24"]
[2.24"]
179[7.03"]173
[6.81"]11[0.45"] 28
[1.1"]
min 12.7[0.5"]
max 20[0.79"]
98[3.86"]
138[5.42"]
60[2.37"]
5[0.2"]
57
-Auxiliary switch (-S)
14 Sub
ject
to te
chni
cal c
hang
es.
Technical data
Electrical data AC 230V 50/60Hz
Power consumption 17VA @ running / 8VA @ holding (50Hz)17VA @ running / 6VA @ holding (60Hz)
Power supply
5VA
Connection cable - Motor 1m, 18ga, 3 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector
Functional data
Working conditions
Dimensions / weight
Torque Min. 3.5Nm
Direction of rotation Selectable by CW/CCW installation
Angle of rotation Max. 95°
Auxiliary switch (-S) 2 SPST, 1mA@ DC 5V, 3(0.5)A, 120/250Vfixed at 10° and 85°
Running time - Motor <15s at rated voltage and torque<15s
Position indication Mechanical
Protection class
Degree of protection IP30 / Enclosure type 1
Mode of operation Type 1. AA. B
Agency listed UL60730-1, UL60730-2-14 and CAN/CSA E60730-1:02
Ambient temperature - Normal duty 0...+50°C- Safety duty 3 Open/Close cycles after 1/2hr @ 177°C
Non-operation temperature -40...+80°CHumidity test 5...95%RH, non condensing
Maintenance Maintenance-free179x98x82mm
Shaft diameter 12.7...20mmWeight Approximately 1700g
Fire and Smoke Spring-Return Actuator FSLF230(-S) US
• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 3.5Nm• Running time: 15s• Control: Open/Close•• 1 wire control
- Spring return
Transformer sizing
Dimensions (L x W x H)
Dimensions [mm]
12.7...20
Nominal voltage range AC 207...253V
Grounded enclosure
19 [0.75"]
6 [0.24"]
[2.24"]
179[7.03"]173
[6.81"]11 [0.45"] 28
[1.1"]
min 12.7[0.5"]
max 20[0.79"]
98[3.86"]
138[5.42"]
60[2.37"]
5[0.2"]
57
- Auxiliary switch (-S)
Technical data
Electrical data AC 24V 50/60Hz
Power consumption
Power supply
27VA Class 2 power supply
Connection cable - Motor 1m, 18ga, 2 color coded leads1m, 18ga, 6 appliance leads1/2" conduit connector
Functional data
Working conditions
Dimensions / weight
Torque Min. 7.9Nm
Direction of rotation Selectable by CW/CCW installation
Angle of rotation Max. 95°
Auxiliary switch (-S) 2 SPDT, 7(2.5)A @ AC 125/250Vfixed at 5° and 85°
Running time - Motor <15s at rated voltage and torque<15s
Position indication Mechanical
Protection class
Degree of protection NEMA type 1
Agency listed UL 873 and CAN / CSA C22.2 No.24
Ambient temperature - Normal duty 0...+50°C- Safety duty 3 Open/Close cycles after 1/2hr @ 177°C
Non-operation temperature -40...+80°C
Humidity test 5...95%RH, non condensing
Maintenance Maintenance-free
259x98x78mm
Shaft diameter 12.7...20mm (10...20mm optional)
Weight Approximately 2750g
• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 7.9Nm• Running time: 15s • Control: Open/Close
- Spring return
Transformer sizing
Dimensions (L x W x H)
Dimensions [mm]
Nominal voltage range AC 19.2...28.8V
27VA @ running / 10VA @ holding
50
80 [3
.15"
]
98 [3
.86"
]78
[3.1
0"]
57[2
.24"
]
5 [0
.19"
]
[1.97"]
49
[1.9
3"]
73.5
[2.8
9"]
67[2.64"]
6.5 [0.26"]148.5 [5.85"]
259 [10.20"]
9 [0.35"]
10 [0.39"]
16.5 [0.65"]
5 [0.19"]
[Ø41.2]Ø1.62"
[7.54"]
191.6
-S models only
Standard:12.7 to 26 mm[1/2" to 1.05"]
Optional*10 to 20mm[3/8" to 3/4"]
*with K4 US clamp
Shaft Size
Class 2 supply
Sub
ject
to te
chni
cal c
hang
es.
15
Fire and Smoke Spring-Return Actuator FSNF24(-S) US
- Auxiliary switch (-S)
16 Sub
ject
to te
chni
cal c
hang
es.
Technical data
Electrical data
Power consumption
Power supply
27VA
Connection cable -Motor -Auxiliary switch (-S)
Functional data
Working conditions
Dimensions /weight
Torque Min. 7.9Nm
Direction of rotation Selectable by CW/CCW installation
Angle of rotation Max. 95°
Auxiliary switch (-S) 2 SPDT, 7(2.5)A @ AC 125/250Vfixed at 5° and 85°
Running time - Motor <15s at rated voltage and torque<15s
Position indication Mechanical
Protection class
Degree of protection NEMA type 1
Agency listed UL 873 and CAN/ CSA C22.2 No. 24
Ambient temperature - Normal duty 0...+50°C- Safety duty 3 Open/Close cycles after 1/2hr @ 177°C
Non-operation temperature -40...+80°CHumidity test 5...95%RH, non condensing Maintenance Maintenance-free
259x98x78mmShaft diameter 12.7...20mm (10...20mm optional ) Weight Approximately 2750g
Fire and Smoke Spring-Return Actuator FSNF230(-S) US
• UL555/UL555S rated Fire and Smoke dampers in HVAC systems• Torque: 7.9Nm• Running time: 15s • Control: Open/Close
- Spring return
Transformer sizing
Dimensions (L x W x H)
Dimensions [mm]
Nominal voltage range
AC 230V 50/60Hz
1m, 18ga, 3 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector
AC 207...253V
50
80 [3
.15"
]
98 [3
.86"
]78
[3.1
0"]
57[2
.24"
]
5 [0
.19"
]
[1.97"]
49[1
.93"
]73
.5[2
.89"
]
67[2.64"] 6.5 [0.26"]
148.5 [5.85"]259 [10.20"]
9 [0.35"]
10 [0.39"]
16.5 [0.65"]
5 [0.19"]
[Ø41.2]Ø1.62"
[7.54"]
191.6
-S models only
Standard:12.7 to 26 mm[1/2" to 1.05"]
Optional*10 to 20mm[3/8" to 3/4"]
*with K4 US clamp
Shaft Size
Grounded enclosure
27VA @ running / 10VA @ holding (50Hz)17VA @ running / 6VA @ holding (60Hz)
Sub
ject
to te
chni
cal c
hang
es.
17
Technical data
Electrical data AC 24V 50/60Hz, DC 24V
Power consumption 7.5W @ running / 2W @ holding
Nominal voltage
10VA (Class 2 power supply)
Connection cable - Motor - Auxiliary switch (-S)
1m, 18ga, 2 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector
Functional data
Working conditions
Dimensions / weight
Torque Min. 15Nm
Direction of rotation Selectable by CW/CCW installation
Angle of rotation Max. 95°
Auxiliary switch (-S) 2 SPST, 7(2.5)A @ AC 120/250Vone fixed at 10° and one is adjustable from 30° to 90°
Running time - Motor <75s at rated voltage and torque<20s
Position indication Mechanical
Sound power level Motor max. 45dB(A), Spring approximately 62dB(A)
Protection class
Degree of protection NEMA type 1
Agency listed UL 873 and CAN/CSA C22.2 No.24-93, CE.Ambient temperature - Normal duty -30°C...+50°C
- Safety duty 3 Open/Close cycles after 1/2hr @ 121°C
Non-operation temperature -40°C...+80°C
Humidity test 5...95%RH, non condensing Maintenance Maintenance-free
259x98x78mmShaft diameter 12.7...20mm (10...20mm optional ) Weight Approximately 2700g
Fire and Smoke Spring-Return Actuator FSAF24(-S) US
• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 15Nm• Running time: motor 75s, spring return 20s• Manual override function• Control: Open/Close
- Spring return
Transformer sizing
Dimensions (L x W x H)
Dimensions [mm]
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Class 2 supply
1.97"
3.15
" [80
]
3.86
" [98
]3.
10" [
78]
2.24
"[5
7]
[50]
1.93
"[4
9]
2.64"[67]
0.26" [6.5]5.85" [148.5]
10.59" [269]
0.35" [9]
0.39" [10]
0.65" [16.5]
0.19" [5]
Standard:1/2" to 1.05"
Optional* 3/8" to 3/4"
3/8" to 5/8"
*with K4 US clamp
18 Sub
ject
to te
chni
cal c
hang
es.
Technical data
Electrical data
Power consumption
Nominal voltage
10VA
Connection cable - Motor 1m, 18ga, 2 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector
Functional data
Working conditions
Dimensions / weight
Torque Min. 15Nm
Direction of rotation Selectable by CW/CCW installation
Angle of rotation Max. 95°
Auxiliary switch (-S) 2 SPST, 7(2.5)A @ AC 120/250Vone fixed at 10° and one is adjustable from 30° to 90°
Running time - Motor <75s at rated voltage and torque<20s
Position indication Mechanical
Protection class
Degree of protection NEMA type 1
Agency listed UL 873 and CAN/CSA C22.2 No.24-93
Ambient temperature - Normal duty -30°C...+50°C- Safety duty 3 ON/OFF cycles after 1/2hr @ 121°C
Non-operation temperature -40°C...+80°C
Humidity test 5...95%RH, non condensing
Maintenance Maintenance-free
259x98x78mm
Shaft diameter 12.7...20mm (10...20mm optional)
Weight Approximately 3100g
Fire and Smoke Spring-Return Actuator FSAF230(-S) US
• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 15Nm• Running time: motor 75s, spring return 20s• Manual override function• Control: Open/Close
- Spring return
Transformer sizing
Dimensions (L x W x H)
Dimensions [mm]
Nominal voltage range
AC 230V 50/60Hz
11W @ running / 3.5W @ holding
AC 197.8...262.2V
Double insulated
Sound power level Motor max. 45dB(A), Spring approximately 62dB(A)
1.97"
3.15
" [80
]
3.86
" [98
]3.
10" [
78]
2.24
"[5
7]
[50]
1.93
"[4
9]
2.64"[67]
0.26" [6.5]5.85" [148.5]
10.59" [269]
0.35" [9]
0.39" [10]
0.65" [16.5]
0.19" [5]
Standard:1/2" to 1.05"
Optional* 3/8" to 3/4"
3/8" to 5/8"
*with K4 US clamp
- Auxiliary switch (-S)
Sub
ject
to te
chni
cal c
hang
es.
19
(referred to 0...90° )
Non-Spring-Return Smoke Control Actuator BLE24(-ST)
Technical Data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Power consumption 7.5W @ running / 0.5W @ holdingWire sizing 9 VA (Imax. 2.7A @ 5ms)
Auxiliary switch- Switching points
2 SPDT, 1mA...3A, DC 5V...AC 250V3° , 87°
Connection cable - Motor- Auxiliary switch
1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)(..-ST with plug connectors, suitable for BKNE230-24)
Functional data Torque (nominal torque) Min. 15Nm
Blocking torque - Dynamic - Steady-state
Min. 15NmMin. 20Nm
Direction of rotation Selected by L/R installationAngle of rotation Max. 105° (incl. mechanical overrun on each side)Running time 30s/90°Sound power level Max. 62dB(A)Service life >10’000 cycles
Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54EMCLow voltage directive
CE according to 2004/108/ECCE according to 2006/95/EC
Mode of operation Type 1.B Ambient temperature - Normal duty
- Safety duty–30...+50°CSee “Safety function” on page 31
Non-operating temperature –40...+80°CHumidity test 95%RH, non condensing Maintenance Maintenance-free
Dimensions / weight Dimensions ( L x W x H ) 185x98x57.6mmShaft diameter Form-fit 12x12mmWeight Approximately 1680g
Dimensions [mm]
.756
57
185
155
93 18
80
212
.
49
6. 5
10 25
120
89
• For control of Fire and Smoke Dampers in HVAC systems• Torque: 15Nm• Nominal voltage: AC/DC 24V• Manual override function • Control: Open/Close
BFG24-ST
20 Sub
ject
to te
chni
cal c
hang
es.
(referred to 0...90° )
Non-Spring-Return Smoke Control Actuator BLE230
Technical Data
Electrical data Nominal voltage AC 230V 50/60HzNominal voltage range AC 198...264V
Power consumption
Wire sizing5W @ running / 1W @ holding
12VA (Imax, 6A @ 5ms)
Auxiliary switch-Switching points
2 SPDT, 1mA...3A, DC 5V...AC 250V 3° , 87°
Connecting cable - Motor - Auxiliary switch
1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Functional data Torque (nominal torque) Min. 15Nm
Blocking torque - Dynamic - Steady-state
Min. 15NmMin. 20Nm
Direction of rotation Selected by L/R installation
Angle of rotation Max. 105° (incl. mechanical overrun on each side)Running time 30s/90°
Sound power level Max. 62dB(A)
Position indication Mechanical with pointerService life >10‘000 cycles
Working conditions Protection class II (totally insulated) Degree of protection IP54
EMCLow voltage directive
CE according to 2004/108/ECCE according to 2006/95/EC
Mode of operation Type 1.B
Ambient temperature - Normal duty - Safety duty
–30...+50°CSee “Safety function” on page 31
Non-operating temperature –40...+80°C
Ambient humidity range 95%RH, non condensingMaintenance Maintenance-free
Dimensions / weight Dimensions ( L x W x H ) 185x98x57.6mm
Weight Approximately 1680gShaft diameter Form-fit 12x12mm
Dimensions [mm]
657
.57
185
155
93 18
0812.294
6.5
10 25
120
89
• For control of Fire and Smoke Dampers in HVAC systems• Torque: 15Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close
Sub
ject
to te
chni
cal c
hang
es.
21
Technical data
Electrical data Nominal voltage
Power consumption
Nominal voltage range
Wire sizing
Connection cable -Motor-Auxiliary switch
Functional data Torque
Direction of rotation
Angle of rotation
Auxiliary switch
Running time
Sound power level
Position indication
Service life
Working conditions Protection class
Degree of protection
Ambient temperature - Normal duty- Safety duty
Non-operationing temperature
Humidity test
MaintenanceDimensions / weight Dimensions (L x W x H)
Shaft diameter
EMC
Dimensions [mm]
-Switching points
Blocking torque - Dynamic- Steady-state
AC 24V 50/60Hz, DC 24V
13W @ running / 0.5W @ holding
AC 19.2...28.8V, DC 21.6...28.8V
18VA (Imax 8.2A @ 5ms )
1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Min. 24Nm
Selectable by L/R installation
Max. 180°
2 SPDT, 1mA...6A, DC 5V...AC 250V5° , 175° (referred to 0...90° )
Max. 62dB(A)
<60s
Mechanical with pointer
>10,000 cycles
III (safety extra-low voltage)
IP54
-30...+50°C
-40...+80°C
Mode of operation Type 1.B
95%RH, non condensing
Maintenance-free
248x98x71mm
Form-fit 12x12mm
Weight Approximately 2700g
CE according to 2004/108/EC
Min. 24NmMin. 30Nm
40
6.5
18850 10
248
175.6
27.2
4040
5.1
71
98
1
5º
12.2
Non-Spring-Return Smoke Control Actuator BEG24(-ST)
• For control of Fire and Smoke Dampers in HVAC systems • Torque: 24Nm• Nominal voltage: AC/DC 24V• Manual override function• Control: Open/Close
(..-ST with plug connectors, suitable for BKNE230-24)
See “Safety function” on page 31
BFG24-ST
22 Sub
ject
to te
chni
cal c
hang
es.
Technical data
Electrical data Nominal voltage
Power consumption 8W @ running / 0.5W @ holding
Nominal voltage range
Wire sizing
Connection cable - Motor- Auxiliary switch
1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Functional data Torque
Direction of rotation
Angle of rotation
Auxiliary switch
Running time
Sound power level
<60s
Position indication
Service lifeWorking conditions Protection class II (totally insulated)
Degree of protection
Ambient temperature -Normal duty-Safety duty
Storage temperature
Humidity test
Maintenance
Dimensions / weight Dimensions (L x W x H)
Weight
Shaft diameter
EMCLow-voltage directive
CE according to 2004/108/ECCE according to 2006/95/EC
Dimensions [mm]
- Switching points
Blocking torque - Dynamic- Steady-state
40
6.5
18850 10
248
175.6
27.2
4040
5.1
71
98
1
5º
12.2
Non-Spring-Return Smoke Control Actuator BEG230
• For control of Fire and Smoke Dampers • in HVAC systems • Torque: 24Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close
5° , 175° ( referred to 0...90° )
Mode of operation
AC 230V 50/60Hz
AC 198...264V
15VA ( Imax 7.9A @ 5ms )
Min. 24Nm
Min. 24NmMin. 30Nm
Selectable by L/R installation
Max. 180°
2 SPDT, 1mA...6A, DC 5V...AC 250V
Max. 62dB(A)
Mechanical with pointer
>10,000 cycles
IP54
-30...+50°C
-40...+80°C
95%RH, non condensing
Maintenance-free
248x98x71mm
Approximately 2700g
Form-fit 12X12mm
Type 1.B
See “Safety function” on page 31
Technical data
Electrical data Nominal voltage
Power consumption
Nominal voltage range
Wire sizing
Connection cable - Motor- Auxiliary switch
Functional data Torque
Direction of rotation
Angle of rotation
Auxiliary switch
Running time
Sound power level
Shaft diameter BE24(-ST) BE24-12(-ST)
Position indication
Service life
Working conditions Protection class
Degree of protection
Ambient temperature - Normal duty- Safety duty
Storage temperature
Humidity test
Maintenance
Dimensions / weight Dimensions (L x W x H)
Weight
EMC
Dimensions [mm]
-Switching points
Blocking torque - Dynamic - Steady-state
• For control of fire and smoke dampers in HVAC systems• Torque: 40Nm• Nominal voltage: AC/DC 24V• Manual override function• Control: Open/Close
AC 24V 50/60Hz, DC 24V
12W @ running / 0.5W @ holding
AC 19.2...28.8V, DC 21.6...28.8V
18VA (Imax 8.2A @ 5ms)
1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Min. 40Nm
Selectable by L/R installation
100° (including 5° mechanical overrun at the ends)
2 SPDT, 1mA...6A, DC 5V...AC 250V
3° , 87° (referred to 0...90° )
Max. 62dB(A)
Form-fit 14x14mmForm-fit 12x12mm
<60s for 90°
Mechanical with pointer
>10,000 cycles
III (safety extra-low voltage)
IP54
-30...+50°C
-40...+80°C
95%RH, non condensing
Maintenance-free
248x98x71mm
Approximately 2700g
CE according to 2004/108/EC
Min. 40NmMin. 50Nm
(..-ST with plug connectors, suitable for BKNE230-24)
Mode of operation Type 1.B
BE24(-12)-ST
*Type Damper driverBE24
BE24-12
Form-fit 14.2mm
Form-fit 12.2mm
17
1
40
188 5010
248
175.6
27.2
04
08
04
895°
*
5°90°
See “Safety function” on page 31
Non-Spring-Return Smoke Control Actuator BE24(-12)(-ST)
6.5
5.1
Sub
ject
to te
chni
cal c
hang
es.
23
Technical data
Electrical data Nominal voltage
Power consumption
Nominal voltage range
Wire sizing
Connection cable -Motor-Auxiliary switch
Functional data Torque
Direction of rotation
Angle of rotation
Auxiliary switch
Running time
Shaft diameter BE230 BE230-12
Position indication
Service life
Working conditions Protection class
Degree of protection
Ambient temperature -Normal duty-Safety duty
Non-operation temperature
Humidity test
MaintenanceDimensions / weight Dimensions (L x W x H)
Weight
EMCLow-voltage directive
Dimensions [mm]
-Switching points
Blocking torque - Dynamic -steady-state
AC 230V 50/60Hz
8W @ running / 0.5W @ holding
AC 198...26 V
15VA (Imax 7.9A @ 5ms)
1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)
Min. 40Nm
Selectable by L/R installation
Max. 100° (including 5° mechanical overrun on each side)
2 SPDT, 1mA...6A, DC 5V...AC 250V3° , 87° (referred to 0...90° )
Form-fit 14x14mmForm-fit 12x12mm
< 60s for 90°
Sound power level Max. 62dB(A)
Mechanical with pointer
>10,000 cycles
II (all insulated)
IP54
-30...+50°C
-40...+80°C
95%RH, non condensing
Maintenance-free
248x98x71mm
Approximately 2700g
CE according to 2004/108/ECCE according to 2006/95/EC
Mode of operation Type 1.B
Min. 40NmMin. 50Nm
• For control of Fire and Smoke Dampers in HVAC systems • Torque: 40Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close
* Type Damper driver
BE230 Form-fit 14.2mm
BE230-12 Form-fit 12.2mm
17
1
40
188 5010
248
175.6
27.2
04
08
04
5.1
895°
*
5°90°
See “Safety function” on page 31
6.5
24 Sub
ject
to te
chni
cal c
hang
es.
Non-Spring-Return Smoke Control Actuator BE230(-12)
Sub
ject
to te
chni
cal c
hang
es.
25
Technical data
Electrical data Nominal voltage
Power consumption
Nominal voltage range
Wire sizing
Connection cable - Motor
Functional data Torque
Direction of rotation
Angle of rotation
Auxiliary switch
Running time
Sound power level
Position indication
Service life
Working conditions Protection class
Degree of protection
Ambient temperature - Nomal duty
Humidity test
Maintenance
Dimensions / weight Dimensions (L x W x H)
Shaft diameter
Weight
EMC
Dimensions [mm]
-Switching points
- Safety duty
• For control of Fire and Smoke Dampers in HVAC system• Torque: 15Nm• Nominal voltage: AC/DC 24...48V• Manual override function • Control: Open/Close• Compatible with the control unit for pulse triggering BSIA24-48(-R)
Non-Spring-Return Smoke Control Actuator BR24-48-F-ST
- Steady-state
Non-operation temperature
AC 24...48V 50/60Hz, DC 24...48V
AC/DC 20.4...57.6V
15...30VA
C2 cable 1m, 3x0.75mm2 (with 3-pole plug)C2 cable 1m, 6x0.75mm2 (with 3-pole plug)
Min. 15Nm
Selectable by L/R installation
Max. 95°
2 SPDT 6(3)A, AC 250V5° , 80°
Max. 60dB(A)
< 30s
Mechanical with pointer
>10,000 cycles
III (safety extra-low voltage)
IP54
-30...+50°C
95%RH, non condensing
Maintenance-free
248x98x58mm
Form-fit 12x12mm
Approximately 2200g
CE according to 2004/108/EC
-30...+70°C (24hr guaranteed safety)
Min. 30Nm Blocking torque - Dynamic Min. 15Nm
-40...+80°C
L
40
6.5
18850 10
ø 5.2
248
175.6
27.2
4040
8058
98
1717
5.1
1
12.2
- Auxiliary switch
12...24W @ running / 1.5...3W @ holding
26 Sub
ject
to te
chni
cal c
hang
es.
Wiring diagram: B..F.. series Spring-Return Open/Close Actuators
1 2
BLF24, BLF230M
~
- +
T
AC 24V DC 24V
S1 S2 S3 S4 S5 S6
< 80°< 5°
N L1 AC 230V (for BCF230, BF230)
Notes: • Parallel connection of several actuators is possible.
• Power consumption must be observed.
Wiring diagrams — B..F.. series Spring-Return Open/Close Actuators
1 2
BLF24-T, BLF230-TM
AC 24VDC 24V
S1 S2 S3 S4 S5 S6
< 80°< 5°
N L1 AC 230V (for BLF230-T, BF230-T)
1 2
BFG24BFG230
M
AC 24VDC 24V
S1 S2 S3 S4 S5 S6
< 145° < 25°
N L1 AC 230V (for BFG230)
1 2
M
~
- +
T
AC 24VDC 24V
S1 S2 S3 S4 S5 S6
< 145° < 25°
N L1 AC 230V (for BFG230-T)
BFG24-TBFG230-T
Tf2Tf1 Tf3 LEDBAE72B-S
Tf2Tf1 Tf3 LEDBAE72B-S
Tf2Tf1 Tf3 LEDBAE72B-S
BF24, BF230
BF24-T, BF230-T
Application with the SBS-Controldamper control and monitoring system
Connecting lead with plugs for linking to the communication and power units
S1 S2 S3 S4 S5 S6
<5° <80°
21
T ~
BLF24-T-STBF24-T-ST
Application with the SBS-Controldamper control and monitoring system
Connecting lead with plugs for linking to the communication and power units
S1 S2 S3 S4 S5 S6
<5° <80°
21
T ~
BLF24-STBF24-ST
Application with the SBS-Controldamper control and monitoring system
Connecting lead with plugs for linking to the communication and power units
S1 S2 S3 S4 S5 S6
<25° <145°
21
T ~
BFG24-T-ST
Application with the SBS-Controldamper control and monitoring system
Connecting lead with plugs for linking to the communication and power units
S1 S2 S3 S4 S5 S6
<25° <145°
21
T ~
BFG24-ST
Tf2Tf1 Tf3 LEDBAE72B-S
Connect via safetyisolating transformer
Connect via safetyisolating transformer
Connect via safetyisolating transformer!
!
!
!
Connect via safetyisolating transformer
~
- +
T
~
- +
T
Sub
ject
to te
chni
cal c
hang
es.
27
Notes: • Parallel connection of several actuator is possible.
• Power consumption must be observed.
Wiring diagrams — B..F.. series Modulating Actuators
!
1 2 3 5
AC 24VDC 24V
BLF24-SR
S1 S2 S3
< 5°
Y DC 2(0)...10V
U DC 2...10VL
0.2
.4
.6
.8
1
R0
.2
.4
.6
.8
1
Y = 0 Y = 0 Y = 0 Y = 0
R L R L
Revisible switch
Installation
!
1 2 3 5
AC 24VDC 24V
BF24-SR
S1 S2 S3 S4 S5 S6
< 80°< 5°
Y DC 2(0)..10V
U DC 2..10V
!
1 2 3 5
AC 24VDC 24V
BF24-SR-T
S1 S2 S3 S4 S5 S6
< 80°< 5°
Y DC 2(0)..10V
U DC 2..10V
Tf2Tf1 Tf3 LEDBAE72B-S
Wiring diagram: B..F.. series Spring-Return Modulating(-SR) Actuators
Connect via safetyisolating transformer
Connect via safetyisolating transformer
Connect via safetyisolating transformer
~
- +
T
~
- +
T
~
- +
T
28 Sub
ject
to te
chni
cal c
hang
es.
Wiring diagram: FS.. series Spring-Return Open/Close Actuators
• Parallel connection of several actuators is possible. • Power consumption must be observed.
Wiring diagrams — FS.. US series Spring-Return Open/Close Actuators
1 2
FSAF230 USFSAF24 US
AC 24V
M
~
- +
T
AC 24VDC 24V
1 2
FSAF24-S USFSAF230-S US
M
~
- +
T AC 230V (for FSAF230-S US)
DC 24V
30...90° 10°
!
1 2 3
1 2 3
FSLF24 USFSLF230 US
M
1 2 3
1 2 3
FSLF24-S USFSLF230-S US
MNO
S1 S2 S4 S6
NC
NO
S1 S2 S4 S6
NC
85°10°
Ground
T
AC 24V
FSNF24 USFSNF230 US
FSNF24-S USFSNF230-S US
M
S1 S2 S3 S4 S5 S6
< 85°< 5°
• No ground on 24V models.
• Provide overload protection and disconnect as required.
! • No ground on 24V models.
• Provide overload protection and disconnect as required.
! • No ground connection is required, doubled insulated.• Provide overload protection and disconnect as required.
~T
AC 24V
~T
AC 24V
AC 230V (for FSNF230 US) N L1
AC 230V (for FSAF230 US) N L1
AC 230V (for FSLF230 US)N L1 AC 230V (for FSLF230-S US)N L1
M
~ ~T
AC 24VAC 230V (for FSNF230-S US)N L1
N L1
Ground
Ground Ground
Sub
ject
to te
chni
cal c
hang
es.
29
Wiring diagram: B..E.. series Non-Spring-Return Actuators
Wiring diagrams--B..E..BR.. series Non-Spring-Return Open/Close Actuators
BE24(-12)-ST < 3 < 87
Application with theSBSE-Control
damper control and monitoring system
T ~
AC 24V
S1 S2 S3 S4 S5 S6
S1 S2 S3 S4 S5 S6
3221
~
Connecting lead with plugs for linking to theBKNE230-24 communication and power unit
BEG24-ST < 5 < 175
Application with theSBSE-Control
damper control and monitoring system
T ~
AC 24V
1 2 3
~
Connecting lead with plugs for linking to theBKNE230-24 communication and power unit
BE24(-12), BE230(-12)
S1 S2 S3 S4 S5 S6
< 3 < 87
1 2
1 2
3
3
2-wire control
AC 24VDC 24V Connect via safety
isolating transformer!
!
BEG24
S1 S2 S3 S4 S5 S6
< 5 < 175
2-wire control
AC 24VDC 24V Connect via safety
isolating transformer
BLE24(-12)-ST
AC 230V (BLE230, BE230(-12))N L
BLE24, BLE230
AC 230V (BEG230)N L
BEG230
Notes: • Parallel connection of several actuators is possible.
• Power consumption and switching thresholds must be observed.
BR24-48-F-ST
AC 24...48VDC 24...48V
1 2 3 S1 S2 S3 S4 S5 S6
<5 <80
Connect via safety islolating transformer!
~
- +
T
~
- +
T
~
- +
T
30 Sub
ject
to te
chni
cal c
hang
es.
B..F../FS..US series technical information
The typical US Fire and Smoke Damper requires 5-15 in-lb torqueper square ft. [6-17 Nm per square meter] at 171°C under dynamic load (2400 fpm [12 m/s] velocity).
Some of multiple actuators application are shown below.
Single sectionfor one actuator
Two sections for two actuators
Maximum areafor one actuator
Maximum areafor two actuators
Large multi-section assemblies
Use of blank-offs between damper sections to provide space for actuator mounting.
Blank-offChannel
Multi-section damper assemblies - typical applications
Product features
mounting
Mode of operation
High function reliability The actuator is overload-proof, needs no limit switches and halts automatically at the end stops.
Internal Aux. switch B..F.. & FS..-S US series: Actuator has two (one for BLF24-SR) internal auxiliary switches.
Manual override function
B..F.. series: Square shaft mounting - mounting the actuator on the damper spindle through a sqaure shaft adaptor. The square shaft adaptor maintains a perfect connection. An anti-rotation device has to be installed by the fire damper manufacturer, or order an anti-rotation strip device separately.
B..F.. & FSAF.. series: Damper can be operated manually and fixed in any required position. Release of the locking mechanism can be achieved manually or automatically by applying the supply voltage.
Thermal tripping device BAE72B-S
Connection to SBS-Control
B..F..-T series: Thermal trip Tf1 operates if the ambient temperature exceeds 72°C. Replaceable thermal trip Tf2/Tf3 operates if the temperature inside the duct exceeds 72°C. Both trips cause the power supply to be interrupted permanently, so that it cannot be uncancelled.
B..F..-ST series: Available with plug connectors fitted to their connecting leads. This allows the actuator to be incorporated into the SBS-Control damper monitoring system via the type BKN230-24 communication and power supply unit.
FS.. series: Direct mounting on the damper spindle by a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The special designed clamp will not crush hollow shafts. An anti-rotation device is supplied.
The actuator moves the damper to its normal working position while tensions the return spring at the same time. If the power supply is interrupted, the energy stored in the spring moves the damper back to its safe position.
Sub
ject
to te
chni
cal c
hang
es.
31
B..E.. series technical information
B.. E.. product features
Mode of operation Open/Close control is effected by means of a 2-wire system. The actuator is overload-proof and therefore remain energised while stationary at the end stops.
Signalling Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions. The position of the damper blade can be read off on a mechanical position indicator.
Manual operation The crank handle supplied with the actuator allows it to be operated manually. It also allows a functional test of the damper to be performed very easily.
Standards and specifications The design of the actuator is based on the following standards and specifications:
• Draft DIN 18232, Part 6, Sept. 1992–Fire protection in industrial buildings–Smoke and heat extraction systems
• Preliminary standard ÖNORM H 6029, May 1997–Ventilation systems–Fire smoke extraction systems
• Extracts from:–CEN/TC191, 1996–pr EN12101-8 (Smoke and heat control systems-specifications for smoke control dampers)
Safety function The safety function is guaranteed within the temperature range shown in the diagram below which is based on standard ÖNORM H 6029 and DIN 18232.
°C
0
50
100
–10 20100
Safety notes
!
TimeMin.
Test temperature acc. to standard temperature-time curve
Temperature on the BE24-ST actuator(protected by thermic isolating)
Temperature
30
• The actuator is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.
• The actuator is adapted and mounted to the fire and smoke damper by the damper manufacturer. For this reason, the actuator is supplied directly to safety damper manufacturers. The manufacturer then bears full responsibility for the proper functioning of the damper.
• Since very high values of torque are exerted on the damper spindle, it is advisable to use steel of at least grade St50.
• The device may only be opened at the manufacturer‘s site. It does not contain any parts which can be replaced or repaired by the user.
• The device contains electronic and electrical components and may not be disposed with the household waste. Observe local regulations and valid laws.
32 Sub
ject
to te
chni
cal c
hang
es.
Technical data
Electrical data
Functional data
Working conditions
Dimensions / weight
Thermoelectric tripping device BAE72B(-S)
Wiring diagram
Maintenance Maintenance-free
EMC CE according to 89/336/EEC
Ambient temperature range –30…+50°C
Non operation temperature –40…+50°C
Humidity test To EN 60730-1
Degree of protection IP54
Protection class III (safety extra-low voltage)
– CNPP Centre National de Prévention et Protection, F-Vernon, to NF S61-937
Testing – VdS Verband der Sachversicherer, D-Köln, to DIN 4102, Part 06
Operating temperature Tf1: duct outside temperature 72°Cthermal trips Tf2, Tf3: duct inside temperature 72°C (replaceable)
Connection Cable 1.2m long, 2×0.5 mm2, BETA flam 145(interchangeable wires)
Through resistance
Rated current Max. 3A
Rated voltage AC/DC 24V
Weight Approx. 85g
(..-S) with test button For function check
Light when- there is a supply voltage
- the test switch is not pressed- the temperature fuses are ok
Dimensions (L x W x H) See “Dimensions”
LED
1 2
M 5° 80 °
Tf1BAE72B-S
Tf2
1 2
- +
T ~
AC 24VDC 24V
Connect via safetyisolating transformer!
BLF24, BF(G)24BLF...-STBF...-ST
1 2 3 4 5 76*
Remove factory fitted jumper!*
BKN230-24...
M 5° 80 °
Tf1BAE72B-S
Tf2
1 2
Tf3
Tf3
ø 9.0 65
27
98
ø 55 40
ø 3.0 ø 3.0
ø 9.5…11
20 20
6
Dimensions [mm]
• Thermoelectric tripping device• BAE72-S, without LED (order separately)• BAE72B-S, with LED (not available for order• separately, only integrated with actuator)
Spare parts:
Thermal trip Tf2/Tf3 ZBAE72Thermal trip Tf2/95°C ZBAE95
Sub
ject
to te
chni
cal c
hang
es.
33
Dimensions [mm]
ZTPC600-B thermal protection case
Witnessed by Lloyds
Note: Cable glands and terminal blocks are not provided. Belimo does not recommend the use of brass fittings at temperatures over 300°C.
Material specification
• The ZTPC600-B thermal case is for the protection of•?Belimo safety actuators operating in an environment of • 300°C for 1 hour • 600°C for 30 minutes.
Tested with the BF actuator in accordance with EN 1210/1999 Part 3 under dynamic load conditions. Protection times quoted are at the rated temperature for the full test time. All tests where witnessed by TUV ( copies of the report available upon request) .
Protection class
Degree of protection IP42Operating temperature range 250°C (90 minutes)
300°C (1 hour)600°C (30 minutes)
MaintenanceWeightColourFlammability
Maintenance-freeLid 2.3kg, Base 2kg (without actuator)GreySelf extinguishing
Application
Principle of operation
Note
The modification and mounting of the thermal case to the fire damper is made by the manufac-turer of the damper. For this reason the thermal case is only supplied directly to the damper manufacturer. The manufacturer then takes overall responsibility for the performance of the damper.
The thermal case consists of three layers: Two intumescence and one insulation. The ZTPC600-B uses the principal of intumescence as the main form of protection. As the fire makes contact with the surface, the outer layer will intumesce or swell by a factor of four or five. A hard forms, that in turn reflects the heat back into the fire. When the first layer has expanded, the next layer intumesces.
The thermal case is designed to allow the BF range of actuators to operate in ambient tempera-tures above their specified rating. The case gives a high degree of mechanical protection and allows for the installation of 2 x M20 cable connectors to facilitate connection of fire proof cable/conduit to the case, and termination of cable to an internal connection block. The fixing of the top shell is done with screws.
439
142
215
110
30
O = 21
A
B
B
Block diagram
1 2 3 4 5 6 7
13 14 15 16 17 18
Fault12
3 54 6
a1................ a6 b1...b6
Input 1
AC 24V
Equipment cubicle
8 9 10 11 12
AC 24V
s0
yaleD
s06
yaleD
NE
PO
DE
SOL
C
tluaF
Input 2
Smoke extraction damper 6
BKNE230-24a b
M
BE(G)24-ST
Smoke extraction damper 1
BKNE230-24a b
M
BE(G)24-ST
SMOKE EXTRACTIONAUTO
CEASE SMOKE EXTRACTION
Firebrigadecontrolpanel
Fire alarm system
BKSE24-6
AC 230V
+
Service pushbutton
SMOKE EXTRACTIONAUTOCEASE SMOKE EXTRACTION
~
~
-
The b-conductors must belinked to the equipment cubicle
A tip:The signal from the Delay 0 soutput can be used as feedbackfor the smoke extraction/cease smoke extraction command.
Power supply AC 230V
Plugging connections for Belimo actuator 24V
Terminal strip, 7-pole
Cable entry for Belimo actuator
Cable entry for 2-wire conductor
LED green (damper position: CLOSED)
LED yellow (damper position: OPEN)
1
7
6
5
4
3
2
2
4
1
7
4
5
6
3
2
Retaining clip
Labelling field (zone/floor)
Labelling fields (dampers)
LED red (fault)
PRG pushbutton
LED yellow (damper position: OPEN)
LED green (damper position: CLOSED)
SET/INIT pushbutton
Plug-in/Screw terminals
1
2
3
4
5
6
7
8
9
1
7
4
5
6
3
2
8
9
Communication and control unit (BKSE24-6)
Communication and Power unit (BKNE230-24)
1 2 3 4 5 6 7 1 2 3 4 5 6
34 Sub
ject
to te
chni
cal c
hang
es.
7
Displays and operating controls / Block diagram (example)
•
Actuators
BLF BF BFG FSLF FSAFAuxiliary Switch1 SPDT
ZSN-BF Bracket for auxiliary switch SN1, SN2
ZA11-BF Insert square shaft 12mm/11mm
ZA18-BF Adapter insert from form-fit to round spindles Ø 20mm
ZA8-BF Insert square shaft 12mm/8mm
ZK-BF Shaft adapter
BAE72(-S) Thermoelectrical tripping device 72°C
ZG-AF Crankarm adapter kit
K4 US
K4-1 US Universal clamp for up to 1.05’’ dia.jackshaft
•
•
FSNF
ZBAE95/72
SN2 Auxiliary Switch2 SPDT
ZSN-BLF Bracket for auxiliary switch SN1, SN2
•
•
•
•
•
•
•
•
•
• •
•
•
•
•
Accessories
SN1
IND-AF2
ZDB-AF2
Thermoelectrical tripping device 95°C/72°C
Damper position indicator
Universal clamp for 3/8’’ to 3/4’’ shafts
Angle of rotation limiter
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Sub
ject
to te
chni
cal c
hang
es.
35
Markets Asia Pacific
ASIA PACIFIC HEADQUARTERSBelimo Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2 Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]
Belimo AUSTRALIAMelbourne Office: Belimo Actuators Pty. Ltd.12 Enterprise Court Mulgrave Business Park Mulgrave, VIC 3170, Australia Tel: +61 (0)3 9545 0844 Fax: +61 (0)3 9545 0855 E-mail: [email protected]
Sydney Office: Belimo Actuators Pty. Ltd. Suite 2.20, 32 Delhi RoadNorth Ryde, NSW 2113Australia Tel: +61 (0)2 9805 1777Fax: +61 (0)2 9805 1722E-mail: [email protected]
Belimo CHINA Shanghai Office:Belimo Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2 Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]
Beijing Office:Belimo Actuators Ltd.Room 605, Hai Chang Edifice44 Liang Ma Qiao RoadBeijing 100016, P.R. ChinaTel: +86 10 6462 1382Fax: +86 10 6462 1383E-mail: [email protected] Chongqing Office:Belimo Actuators Ltd.Room 4, 9th floor, Unit 7, Luoma Jiari GardenNo. 36, QingLong Road, Nan'an District Chongqing 400060, P.R. ChinaTel: +86 23 6275 3155Fax: +86 23 6280 3380 *519E-mail: [email protected] Guangzhou Office:Belimo Actuators Ltd.Room 1202, Skyline Plaza644 Tong Fu East Road, Haizhu AreaGuangzhou 510240, P.R. ChinaTel: +86 20 3435 1860Fax: +86 20 3435 1870 E-mail: [email protected]
Belimo HONG KONGHong Kong Office:Belimo Actuators Ltd.Room 207, 2/F, New Commerce Center19 On Sum Street, Shatin, N.T., Hong KongTel: +852 2687 1716Fax: +852 2687 1795E-mail: [email protected]
Japan Office:Belimo Actuators Ltd. 7th Floor, Honjo-Azumabashi DJ Building 4-19-3, Honjo, Sumida-kuTokyo 130-0004, Japan Tel: +81 3 6823 6961 Fax: +81 3 3626 3911 E-mail: [email protected]
Malaysia Office:Belimo Actuators Ltd.12-1, Jalan PJS 10/2, Subang Indah46000 Petaling Jaya Selangor, MalaysiaTel: +603 5631 2188Fax: +603 5638 2189E-mail: [email protected]
Singapore Office: Belimo Actuators Ltd.1 Tannery Road #08-04, One TannerySingapore 347719Tel: +65 6842 1626Fax: +65 6842 1630 E-mail: [email protected]
Taiwan Office:Belimo Actuators Ltd. 7F-2, No. 343, Jhonghe Road, Yonghe CityTaipei County 234, Taiwan Tel: +886 2 2922 8805 Fax: +886 2 2922 8806 E-mail: [email protected]
Thailand Office:Belimo Actuators Ltd.90/2 Pensiri PlaceSoi Phaholyothin 32, Phaholyothin RoadChandrakasem, JatujakBangkok 10900, ThailandTel: +662 9415582-3Fax: +662 9415584E-mail: [email protected]
Belimo INDIAMumbai Office:Belimo Actuators India Pvt. Ltd. 204 Jaisingh Business Center, Parsiwada Sahar Road, Andheri (East) Mumbai 400099, India Tel: +91 22 6733 2525 / 6733 2501 Fax: +91 22 2822 2643 E-mail: [email protected]
Bangalore Office:Belimo Actuators India Pvt. Ltd. 60/1, 1st Floor, Coles Road, Frazer TownBangalore 560005, India Tel: +91 80 2558 0421 / 6565 6978 Fax: +91 80 2558 0422 E-mail: [email protected]
New Delhi Office:BELIMO Actuators India Pvt. Ltd.Flat No. 516, DLF Tower – B, Jasola Distt. Centre, Jasola, New Delhi – 110025Phone: +91 11 41078501 to 41078507 Fax:� +91 11 41078508E-mail: [email protected]
Innovation, Quality and Consultancy:A partnership for motorising HVAC Actuators
BELIMO Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]
BELIMO Aircontrol (USA), Inc.43 Old Ridgebury RoadDanbury, CT 06813-2928, USATel: +800 543-9038 / 203 791-9915Fax: +800 228-8283 / 203 791-9919
BELIMO Automation AGBrunnenbachstrasse 18340 Hinwil, SwitzerlandTel: +41 43 843 61 11Fax: +41 43 843 62 68E-mail: [email protected]