Sl. No Description Amount 1 Fire Fighting Arrangement (Wet System) Pumps with other accessories and miscellaneous Electrical Works Rs. Total Rs. FOR INDIAN ASSOCIATION FOR THE CULTIVATION OF SCIENCE SUMMARY AT 2A & 2B RAJA S C MULLICK ROAD, KOLKATA DETAILED ESTIMATE FOR FIRE FIGHTING ARRANGEMENT (WET SYSTEM) PUMPS WITH OTHER ACCESSORIES AND MISCELLANEOUS ELECTRICAL WORKS FOR PROPOSED EXTENSION OF 3 FLOORS OF LIBRARY BUILDING FSQ-1 IACS
Transcript
Page 1: Fire Fighting Sq

Sl. No Description Amount

1 Fire Fighting Arrangement (Wet System) Pumpswith other accessories and miscellaneous ElectricalWorks Rs.

Total Rs.

FOR INDIAN ASSOCIATION FOR THE CULTIVATION OF SCIENCE

SUMMARY

AT 2A & 2B RAJA S C MULLICK ROAD, KOLKATA

DETAILED ESTIMATE FOR FIRE FIGHTING ARRANGEMENT (WET SYSTEM) PUMPS WITH OTHER ACCESSORIES AND MISCELLANEOUS ELECTRICAL WORKS

FOR PROPOSED EXTENSION OF 3 FLOORS OF LIBRARY BUILDING

FSQ-1

IACS

Page 2: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

1 Providing and fixing M S ERW Pipes as per IS3589 and IS 1239 (heavy quality) with necessaryfittings, flanged/threaded/welded joints as perdirection, MS supports/clamps, chase/hole cuttingin walls and floors and mending good the same andearth work in excavation and back filling to propercompaction incluing disposal of surplus earth andpainting the pipes with single coat of epoxy primerand two coats of coal tar epoxy for buried pipes ortwo coats of post office red enamel paint forexposed pipes. After painting the buried pipes withcoal tar epoxy (white tacky) two layers of fibre glasscloth (approx 0.5 mm thick) shall be wrappedaround pipe and further 2 coats of coal tar epoxypaint shall be applied. Drying time shall be 24hours before back filling.

a) 200 mm dia (6.0 mm minimum thickness as per IS3589). Mtrs 300 mtr

b) 150 mm dia (Heavy Quality) - IS : 1239 Mtrs 65 mtr

c) 100 mm dia (Heavy Quality) - IS : 1239 Mtrs 49 mtr

Note : The rates should include all reducers and

flanges to match the companion flange of thefixture viz. pump inlet and outlet ports, landingvalves etc.

2 Providing and fixing CI sluice valve (PN 1.6) ISI

stamped, with flanged ends drilled as per IS 1358and having all cast iron components as per IS :14846 - 2000 with solid forged AISI 304 insidescrew spindle. Spindle nut, valve and seat faces ofhard wear resistance, manufactured from bestquality gun metal, tested to 24/16 kg per sq cmhydraulic pressures as per IS : 14846. Valve to begiven 2 coats of epoxy primer paint and 2 coats ofpost office red enamel paint.

a) 200 mm dia Nos 2 each

b) 150 mm dia Nos 5 each

c) 100 mm dia Nos 4 each

d) 80 mm dia Nos 2 each

PUMPS WITH OTHER ACCESSORIES AND MISCELLANEOUS ELECTRICAL WORKS DETAILED ESTIMATE FOR FIRE FIGHTING ARRANGEMENT (WET SYSTEM)

FSQ-2

IACS

Page 3: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

3 Supplying, fitting and fixing GI pipes of TATA make(IS 1239) with all necessary accessories, specialsviz. socket, bend, tee, union, cross, elbow, nipple,long screw, reducing socket, reducing tee, shortpiece etc fitted with M S galvanisedclamps/brackets, including cutting pipes, makingthreads, fitting, fixing etc complete in all respectincluding cost of all necessary fittings as required,jointing materials and two coats of painting withapproved paint in any position. (Payment will bemade on the centre line measurements of total pipeline including all specials. No separate payment willbe made for accessories, specials).

a) 80 mm dia medium quality. Mtrs 45 mtr -

b) 32 mm dia (Medium Quality) Mtrs 5 mtr

c) 25 mm dia (Medium Quality) Mtrs 2 mtr

Note : Rate should include the cost of earth work inexcavation, back filling and effecting necessaryconnection with existing water main complete.

4 Supplying, fitting and fixing peets valve fullway gun

metal standard pattern best quality of approvedbrand bearing ISI marking with fittings (tested to 21kg/sq cm).

a) 80 mm dia Nos 2 each

b) 32 mm dia No. 1 each

5 Providing and fixing gun metal non-return valve

vertical/horizontal type (ISI mark).

a) 25 mm dia No. 1 each

6 Providing and fixing cast iron horizontal NRVwithout bypass (PN 1.6) ISI stamped with flangedends (IS 5312), single door pattern forunidirectional flow of water. Flanges to be drilled asper IS 1538. Body with hinge and diaphragn of greycast iron; hinge pin of high tensile brass, nuts/boltsAISI 304, bearing bushes, face and seal ring ofleaded tin brouze.

a) 150 mm dia Nos 2 each

b) 80 mm dia No. 1 each

FSQ-3

IACS

Page 4: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

7 Providing and fixing horizontal centrifugal FirePump rated for 2400 litres per minutes for TDH of70 m pump unit shall be of high efficiency (not lessthan 70%), volute type end suction cast ironhousing and bronze impeller. Pump shall becoupled to a squirrel cage induction motor ofsuitable HP (not less than 55 KW having efficiencynot less than 70%) for the above pump's dischargecapacity and TDH. The motor shall be TEFC withsupply conditions 415V, 3 phase 50 Hz, insulationClass-F, IP-55, appropriate RPM with mountingarrangement, coupling and coupling guard, floormounted type including MSEP fabricated commonbase frame vibration damping synthetic rubber pad,necessary cement concrete base (1:2:4) asrequired, 12 mm thick cement plaster (1:4) andneat cement finish and holding down bolts etccomplete with 25 mm dia rigid PVC drain pipe andvalve, necessary testing and commissioning. Sets 2 set

8 Providing, fitting fixing and commissioningelectrically driven jockey pump rated forapproximately 180 litre per minute at 75 mtrs head,not exceeding 2900 RPM, coupled to horizontalTEFC foot mounted, squirrel cage, induction motor,suitable to operate with 415V + 10% 50 HZ ACsupply and suitable HP (not more than 10 HPhaving efficiency not less than 70%) including allaccessories such as flexible love-joy coupling andcoupling guard, base plate, cement concrete base(1:2:4) as required with 12 mm thick (1:4) cementplaster and neat cement finish and foundationbolts etc complete with 25 mm dia drain pipe andvalve. Painting of pump and motor shall be sameas that of fire pump. Set 1 set

9(i) MCC PANEL

Designing, manufacturing, testing, supplying anderecting at site vertical floor mounting freestanding/wall mounting extensible on either side,compartmentalised cubical type panel board madeof 14 G (= 2.00 mm) CRCA MS sheet suitable for500/415V, 50 HZ, AC, 3 Phase and neutral systemhaving the following features :

i) The panel shall be designed to ensure IP 4X

protection degree also that the weight of thecomponents is adequately supported withoutdeformation or loss in alignment.

FSQ-4

IACS

Page 5: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

9(i) (contd)

ii) The doors of the cubicle shall be fitted with dustexcluding neophrene gaskets with fastners forproper compression of the gaskets.

iii) The panel shall be multitier compartmentalisedcubical type, extensible on either side and shall betreated with all anticorrosive process (Seven tankprocess) before powder coated painting ofapproved shade.

iv) Busbars shall be of continuous rated HDHC tinnedcopper confirming to IS 1897 as ammended up todate adequate for specified rated continuous andshort circuit current covered by proper gradedcolour coded heat shrinkable PVC sleeves.Busbars shall be supported by suitable hylaminsulator supports. High tensile bolts and springwashers are to be provided on all busbars andsuitable drilled holes for connection joints. Thebusbars shall have a through fault withstandcapacity of 31 MVA RMS symmetrical for onesecond. The interconnections between the busbarsand the circuit breakers shall be made bycontinuous rated tinned copper strips suitablycovered by proper graded heat shrinkable colourcoded PVC sleeves or by unarmoured coppercable. The earth busbar/s shall run through thelength of the panel and terminated at two ends.

v) All the MCCBs shall be provided with extended

rotary operated mechanism. Safety interlocks areto be provided to prevent the doors of thecompartments housing the MCCBs to prevent thedoors to open when the MCCBs are in `ON'position.

vi) All control wiring in the panel shall be carried outwith 1.1 KV grade single core PVC insulatedcopper conductors of minimum 2.5 sq mmcrosssection for potential circuits and CT circuits.Wiring should be neatly bunched, adequatelysupported, properly routed and finally crimped.Wires are to be identified by numbered ferules ateither end. Terminal blocks used are of clamp typewith barriered terminals and are to be numbered.

FSQ-5

IACS

Page 6: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

9(i) (contd)

vii) Adequate cabling space should be available in thepanel with cable supports, cable alleys etc.Provision for top/bottom entry and termination ofrequired number of A2XFY/A2X WY cable asindicated in the SLD shall be provided. The positionof control switches, push buttons, levers, etcrequiring manual operation shall be at a height notexceeding 1850 mm from the finished floor level.

viii) The panel shall also comprise of necessary meters,

CTs, protection MCBs fuses, indication lamps,thermal relays, contactors, auto manual switches,lifting bolts, label inscriptions (metallic engravedidentification tags) describing the rating of thebreakers, designation of the feeders etc includingall other accessories, complete as per IE Rules andregulations conforming to relevant IS and dulyapproved and inspected at works aftermanufacturing by IACS/Consultant. The rate shallinclude necessary cutting chases and mendinggood damages during installation. The panel shallhave the following major components.

Note : All MCCBs should have adjustable thermaland fixed magnetic releases unless statedotherwise.

Incoming

a) 1 No. - 250A 4P ATS (Category : AC 23A atleast)with in-built time delay.

b) 1 No - 250A, 4P MCCB of rated service voltageupto 690V, Icu not less than 35/36 KA, Ics = 100%Icu at 415V, 50 Hz with adjustable thermal andfixed magnetic release including extended rotaryoperated mechanism, auxiliary contacts, spreaders,etc.

c) 1 Set (3 Nos) - 250/5A, CL-1.0, 5 VA cast resintype current transformers.

d) 1 Set - 0 - 250A analogue type CL-1.0 ammeter(MISC) (96 mm sq and pointer deflection 0 … 90degree) with selector switch.

e) 1 Set - 0 - 500V AC, analogue type CL-1.0voltmeter (96 mm sq) (MISC) with 1 No. TP 6Acontrol MCB (C-curve) with selector switch.

FSQ-6

IACS

Page 7: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

9(i) (contd)

f) 1 Set (3 Nos) - R-Y-B cluster type phase indicationlamps (LED Cluster Type).

g) 1 Set (3 Nos) - ON-OFF-TRIP indication typeLamps (LED Cluster Type) for the above breaker

Busbars

1 Set - 415V, 50 HZ, 31 MVA RMS symmetricalcontinuous rated HDHC tinned copper busbars (4Nos 25 x 10 mm busbars for each phases andneutral) mounted on suitable FRP/DMC/SMCinsulator supports with proper graded colour codedheat shrinkable PVC sleeves.

Outgoing

Feeder-1 & 2

a) 1 Set - 160A, TP MCCB of rated service voltageupto 690V, Icu not less than 35/36 KA, Ics = 100%Icu at 415V, 50 HZ with magnetic release includingextended rotary operated mechanism, auxiliarycontacts, spreaders, etc.

b) 1 Set (3 Nos) - ON-OFF-TRIP indication clustertype LED Lamps for the above breaker.

c) 1 Set (3 Nos) - 200/5A, CL-1.0, 5 VA, CTs (castresin type).

d) 1 Set - 0 - 200A analogue type, CL-1.0 ammeter(96 mm sq, pointer deflection 0 ….. 90 degree)(MISC) with selector switch.

e) 1 Set - Overload Relay of category-10A at 415V, 50HZ.

f) 1 Set - TP contactors (AC3), star/delta timer,illuminated start/stop push buttons, cluster typeLED indication lamps for ON/OFF indication,control fuse auto/manual selector switch, etc tosatisfy star/delta starting of 55 KW Motor havingefficiency not less than 70%.

Feeder-3a) 1 Set - 32A, TP MCCB of rated service voltage

upto 690V, Icu not less than 35/36 KA, Ics = 100%Icu at 415V, 50 HZ with magnetic release includingextended rotary operated mechanism, auxiliarycontacts, etc.

FSQ-7

IACS

Page 8: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

10(i) (contd)

b) 1 Set (3 Nos) - ON-OFF-TRIP indication clustertype LED lamps for the above breaker.

c) 1 Set (3 Nos) - 40/5A, CL-1.0, 5VA, CTs (Castresin type).

d) 1 Set - 0 - 40A analogue type, CL-1.0 ammeter (96

mm sq, pointer deflection 0 … 90 degree) (MISC)with selector switch.

e) 1 Set - Overload Relay of category-10A at 415V, 50Hz.

f) 1 Set - TP Contactor (AC3), illuminated start/stoppush buttons, with cluster type LED indicationLamps for ON/OFF indication, control fuseauto/manual selector switch, etc to satisfy DOLstarting of not more than 10 HP Motor havingefficiency not less than 70%.

Feeder-4

a) 1 Set - 16A, TP MCB (10 KA).

b) 1 Set (3 Nos) - 20/5A, CL-1.0, 5 VA, CTs (castresin type).

c) 1 Set - 0 - 20A analogue type, CL-1.0 ammeter (96mm sq, pointer deflection 0 …. 90 degree) (MISC)with selector switch.

d) 1 Set - Overload Relay of Category - 10A at 415V,50 Hz.

e) 1 Set - TP Contactor (AC 3), illuminated start/stoppush buttons with cluster type LED IndicationLamps for ON/OFF Indication, control fuseauto/manual selector switch, etc to satisfy DOLstarting of motor not more than 1 HP havingefficiency not less than 70%.

Note : The panel shall have the provision to sendsignal to the D G for auto start of the same andnecessary change over of the ATS at the incomerof the panel. All materials required to satisfy theabove function shall be considered.

FSQ-8

IACS

Page 9: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

9(i) (contd)

Earth Busbar

1 Set - 25 mm x 10 mm Cu busbar running alongthe base frame covering entire length of the panelwith high tensile bolts, nuts, washers, etc andnumber of drilled holes as required for earthconnection.

1 No. - Danger Board

Complete Board as stated above. Set 1 set

9(ii) Supply, installation, testing and commissioning ofdouble metal door (reversible) surface/recessmounting horizontal type, 8-way, SPN DB not lessthan IP-42 protection with front MS coverconfirming to IS 8623, incommer and outgoingMCBs with electrolytic copper main bus bars andneutral bus bar with insulation, earth bus bars withscrews, interconnections, cable ties for cablemanagement and all other accessories includingdoor earthing, cutting chases and mending gooddamages in case of recess mounting and fixing ofMS flat iron frame (20 mm x 5 mm), GI bolts, nuts,washers, etc for surface mounting, earthing,painting, complete as follows.

Note : All MCBs shall be above 9 KA short circuitrating. The DB shall be installed as per thedirection of IACS/Consultant.

a) 1 No. - 32A DP MCB (C-curve) as incomer.

b) 2 Nos - 6A SP MCB (C-curve) as outgoing.

c) 2 Nos - 16A SP MCB (C-curve) as outgoing.

d) 2 Nos - SP Blank Plates. Set 1 set

9(iii) Supply and laying of ISI marked BEMS conduit withall accessories, MS Junction Box/Draw-in-Box (16G), GI fish wire for drawing wires as perrequirement including cutting, chipping andmending good damages with all labour andmaterials as required complete.

a) 25 mm dia BEMS Conduit. Mtrs 40 mtr

FSQ-9

IACS

Page 10: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

9(iv) Power point wiring in stranded (1100 V) grade PVCFR insulated copper wire including earth wireconfirming to IS 694 in prelaid 25 mm dia BEMSconduit with all accessories complete.

a) With 2 x 4 sq mm and 1 x 4 sq mm (earth) PVC FR

insulated copper wires. Mtrs 50 mtr

9(v) Supplying and fixing of 6/16A socket with switch onseparate board with bakelite hylam cover and allaccessories including necessary connections asrequired.

a) 16A socket with switch on separate board. Nos 2 each

9(vi) Point wiring including circuit wiring with 1.1 KV

grade 3 x 2.5 sq mm (Cu) PVC FR insulatedmultistrand copper wire confirming to IS 694 inscrewed type BEMS conduit including supply ofrequisite length of 25 mm dia BEMS conduit, 25mm dia metal flexible conduit as necessary andsupply of piano key type switch, bakelite hylamcover, MS box (= 1.6 mm thick), nuts, washers, CIcircular box, MS bar saddles, ceiling rose etccomplete.

Note : 1 Point wiring shall be inclusive of continuous wire

lengths upto the connection block of lightfittings/fans.

2 Fan regulators shall be Heavy Duty Electronic Type

(Stepped) unless specified otherwise.

a) 1 light point controlled by 1 No. 6A switch. Sets 6 set

b) Ceiling fan controlled by 1 No. Heavy DutyElectronic Type (Stepped) regulator and 1 No. 6Aswitch. Sets 2 set

9(vii) Supply and fixing of single fluorescent light fittings

with lamps completely wired up to terminal in realceiling including connection with 3 x 1.5 sq mmPVC FR insulated copper wire confirming to IS 694with PVC flexdible conduit of 20 mm dia with fixingscrews, bolts, nuts, washers, etc and otheraccessories complete.

a) 1 x 40 W fluorescent fittings [Philips Make :

TMS205 1 x TL 40W I]. Sets 6 set

9(viii) Supply and fixing of ceiling fan having 1200 mmsweep, suitable to operate with 240V, 50 Hz supplycompletely wired up to terminal, capacitor, downrod, etc complete. Sets 2 set

FSQ-10

IACS

Page 11: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

10 Supply and laying of 1.1 KV grade XLPE insulatedgalvanized steel wire/strip armoured cablesconfirming to IS 7098, Part-1 as amended uptodate having PVC inner sheath and PVC (FR) outersheath of type ST2 of IS 5831 to be layed partly onsurface/cable trench including providing brickprotection (16 Nos of brick per metre), excavationof soil, back filling, soil levelling up and restoringthe surface duly rammed for cable layed withintrench and supplying and fixing MS clamps, GIbolts, nuts, screws, etc including earthing for cablelayed in surface.

i) 3.5C, 150 sq mm A2X FY cable. Mtrs 50 mtr

b) 3C, 50 sq mm A2X WY cable. Mtrs 15 mtr

c) 3C, 16 sq mm A2X WY cable. Mtrs 15 mtr

11 Supply and making indoor type cable endtermination of 1.1 KV grade armoured XLPEinsulated cable complete with supply and fixing ofcadmium plated double compression brass glands,crimping type copper sockets, etc includig hirecharges of tools and tackles as required.

a) 3.5C, 150 sq mm A2X FY Cable Sets 2 set

b) 3C, 50 sq mm A2X FY Cable. Sets 2 set

c) 3C, 16 sq mm A2X WY Cable. Sets 2 set

12 Supplying and laying of 1.1 KV grade copperunarmoured PVC insulated cable confirming to IS1554 on surface including terminations, clamps,screws, etc complete.

a) 10C, 1.5 sq mm PVC armoured cable. Mtrs 15 mtr

b) 5C, 1.5 sq mm PVC armoured cable. Mtrs 15 mtr

c) 3C, 1.5 sq mm PVC armoured cable. Mtrs 15 mtr

13 Supply and fixing of the following GI strip and GIwire for earthing of equipments, viz. starters, motorframe, etc.

a) 25 mm x 3 mm hot dipped GI strips. Mtrs 20 mtr

b) 8 SWG GI wire. Mtrs 20 mtr

FSQ-11

IACS

Page 12: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

14 Earthing with 50 mm dia GI pipe 3.64 mm thick 3mtr long buried on an average depth of 3 mtr belowground level, 2.5 mtr bottom length of the pipehaving 12 mm size drilled holes 75 mm apartcrosswise and the bottom end chisel cut completeas per IS 3043 including providing and fixing 13mm dia x 80 mm long GI bolts and nuts and doublewashers for connecting earth lead includingexcavation of earth, restoring the same andramming of surface, complete. Set 1 set

15 Providing masonry inspection pit having dimension

when completed approx 0.56 m x 0.56 m outsidedimensions 0.45 m deep having 125 mm thick brickwall including inside, outside and top plastering andneat cementing including supplying and fixing castiron ring with lockable cover. Set 1 set

16 Supplying and fixing 25 mm x 6 mm GI strip inside

pump room. Mtrs 10 mtr

17 Supplying and fixing 25 mm x 6 mm GI strip outsidepump room painted with 2 coats of anticorrosivebituminous paint including excavation of 300 mmdeep trench for laying earth lead and backfilling thesame. Mtrs 10 mtr

18 Providing and fixing diaphragm type pressure

gauge with control cock and U-syphon upto 17kg/cm2 150 mm dia dial with shatter proof glass. Nos 3 each

19 Providing and fixing pressure switch bellows type

with differential 0 to 15 kg/sq cm including

controlling cock, damper and adapter etc complete. Nos 3 each

20 Providing and fixing gun metal single head angular

hydrant valve with female instantaneous 63 mm

outlet and 80 mm flanged inlet with gunmetal blank

cap and chain (ISI marked) complete with synthetic

rubber gaskets and galvanised nuts and bolts.

a) As per IS 5290 (Type `A') Nos 9 each

21 Providing and fixing gun metal short branch pipewith 63 mm instantaneous inlet, male threadedoutlet complete with hexagonal based nozzlesheavy quality conforming to IS 903/1975 (ISImarked). Nos 9 each

FSQ-12

IACS

Page 13: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

22 Providing and fixing rubber lined wooven jacketedfire fighting hose (Reinforced rubber lined type)with coupling as per IS 636 type `B' of 63 mm dia(copper wound) tested to a bursting pressure of 32kg/cm2 including gun metal fire hose deliverycoupling of 63 mm size with multi serrated tail anddouble instantaneous spring lock arrangementscomprising of male and female half and rubber capwasher conforming to IS 903. Length of hose 15mtrs. Sets 18 set

23 Providing and fixing fire brigade siamese

connection to the underground ring maincomprising of instantaneous pattern 63 mm diainlets with non return valves and cap with chaincomplete with 150 mm dia CI sluice valve (ISImark). The mainfold shall be mounted in a mildsteel painted cabinet with glass front door. Thecabinet shall be suitable for wall/floor mounting.

a) Three way No. 1 each

24 Providing and fixing M S hose cabinets size 750mm x 610 m x 255 mm deep fabricated from 16gauge annealed sheets to accommodate two nos15 meters length of delivery hose pipe and abranch pipe. The hose cabinet will have 4 mm thickglass fronted door with glass and locks, 2 nos keysand a break glass recess for key (Red colour) withbrass hinges, door handles and necessaryarrangements for suspending the same fromwalls/floors including necessary fixing materials. Nos 9 each

The hose cabinet is to be epoxy powder coatedpost office red after 10 tanks treatment.

25 Providing and fixing CI flanged end foot valve as

per IS 4038/1979 with brass strainer with erectiontesting and commissioning and necessary rubberinsertion/bolts and nuts etc complete.

a) 200 mm dia No. 1 each

26 Providing and fixing CO2 fire extinguishers of 9 ltrscapacity with wall mounting heavy type bracketswith fixing materials and first charge of carbondioxide gas with cartidge etc (ISI marked). No. 1 each

27 Supplying, fitting and fixing Fire Bucket as per IS

2546 including necessary post office red paintingand fixing materials complete with brackets andstand. Nos 5 each

FSQ-13

IACS

Page 14: Fire Fighting Sq

Sl. No. Description Unit Quantity Rate Per Amount

28 Charges for testing as per statutory requirementsthe entire fire fighting system as per norms of FireDirectorate, commissioning and obtaining finalNOC from local Fire Services Directorate includingall incidental works and charges thereof. Item 1 L.S item

29 Supply and installation of signage as per norms ofWest Bengal Fire & Emergency Services (WBFES).Payment shall be made on the basis of PurchaseVoucher and Labour charges shall be consideredas 20% on Purchase Voucher. Item P.S item

30 Supplying, installation, testing and commissioningof suitable centrifugal core-coupled pump set withbrass suction check valve, conforming to followingparameters.

a) Discharge capacity approx 50 lpm.

b) Suction lift - approx 1 m.

c) TDH - 6 m.

d) Water source - floor workings with TSS about 20mg/l.

e) Type of pump - horizontal or vertical.

f) Material of construction - all stainless steel.

g) Make of pump - Grundfos/DPS/CRI/MBH. Set 1 set

Note : The pump can be a monoblock type orcompleted with motor area common base frameMS amp.

Total carried over to Summary