+ All Categories
Home > Documents > Fire Fighting System

Fire Fighting System

Date post: 24-Oct-2014
Category:
Upload: rachana-meena
View: 57 times
Download: 1 times
Share this document with a friend
Popular Tags:
20
Fire fighting System in Anta Gas power Project
Transcript
Page 1: Fire Fighting System

Fire fighting System in Anta Gas power Project

Page 2: Fire Fighting System

Automated Fire Detection and fire fighting system

Hydrant and Spray Mulsifier system

Helon gas System

Page 3: Fire Fighting System

Hydrant and Spray Mulsifier system

Type of pumps:-(a) AC Hydrant Pump (01)(b) DD Hydrant Pump (01)(c) AC Spray Pump (01)(d) DD Common Pump (01)(e) Jockey pump (02)

Type of Hydrant valves:-• Water Monitors 08• Single Hydrant 92• Foam Hydrant 08• Internal Hydrant 07• Test Hydrant 05

Page 4: Fire Fighting System

Hydrant and Spray Mulsifier system

Hydro pneumatic tank(a) Capacity 18.15 m3(b) Design Pr 11.55 bar

Compressors for H/N tank(a) Type – Single stage

reciprocating air cooled belt drived

(b)FAD – 135 LPM(c) Motor capacity – 2 HP(d)Qty – 02

Page 5: Fire Fighting System

Schematic of Hydrant and spray Pumps

Page 6: Fire Fighting System

Jockey pumps

H/N Tank

AC Spray P/P

DD Common P/P

DD Hydrant P/P

AC Hydrant P/P

Spray water strainers

1

2

Test Hydrants

Spray water Header

Hydrant Header

Page 7: Fire Fighting System

Hydrant Pump Operation

S NO TYPE OF PUMP FLOW M3/HR

AUTO START

HEADER PR. ( BAR)

MOTOR /ENGINE

CAPACITY

MOTOR CURRENT/

DIESEL TANK CAPACITY

1 AC HYDRANT 410 6.5 150 KW 255 AMP

2 AC SPRAY 410 6.0 150KW 255 AMP

3 DD HYDRANT 410 5.5 231 HP 250 Lt

4 DD COMMON 410 5.0 231 HP 250 Lt

5 JOCKEY PUMP 30 at 30% Lvl of H/N TANK

15 KW 22 AMP

Page 8: Fire Fighting System

F/F MULSIFIER SYSTEM

• MAKE - THE RELIABLE AUTOMATIC SPRINKLER CO., INC.

• SIZE - 100MM• OPERATION - PNEUMATICALLY

OPERATED• MODEL - B • LOCATION - GT& ST main Transformers,

Naphtha unloading & storage• TOTAL QTY - 8 Nos.

DELUDGE VALVE SIZE 100 MM

Page 9: Fire Fighting System

F/F MULSIFIER SYSTEM

• MAKE - THE RELIABLE AUTOMATIC SPRINKLER CO., INC.

• SIZE - 65MM• OPERATION - PNEUMATICALLY

OPERATED• MODEL - A • LOCATION - GT& ST Aux Transformers, GRS

Diesel Day tank and Oil room • TOTAL QTY - 8 Nos.

DELUDGE VALVE SIZE 65 MM

Page 10: Fire Fighting System

DELUDGE SYSTEM OF NAPHTHA FOAM SYSTEM

PUSH ROD CHAMBER

LOW PR SWITCH

DELUDGE VALVE

HIGH PR SWITCH

SPRAY WATER HEADER

DIAPHRAGM VALVE

AIR DETECTION HEADER

Page 11: Fire Fighting System

COMMON DELUDGE V/V OF NAPHTHA FOAM SYSTEM

SPRAY WATER LINE

F/F AIR LINE

PUSH ROD CHAMBER

LOW PR SWITCH

DELUDGE VALVE

HIGH PR SWITCH

DIAPHRAGM VALVE

SOLENOID VALVE

FOAM LINE

FOAM TANKS

FOAM PUMPS

12

2 1 Hydrant water

Page 12: Fire Fighting System

DELUDGE SYSTEM OF DISEL DAY TANK –diaphragm type

F/F AIR LINE

PUSH ROD CHAMBER

LOW PR SWITCH

DELUDGE VALVE

HIGH PR SWITCH

AIR DETECTION HEADER

SPRAY WATER HEADER

DIAPHRAGM VALVE

Page 13: Fire Fighting System

DELUDGE VALVE OF GTs AND STG

SPRAY WATER LINE

F/F AIR LINE

PUSH ROD CHAMBER

LOW PR SWITCH

DELUDGE VALVE

HIGH PR SWITCH

DIAPHRAGM VALVE

Hydrant waterTransformer

Page 14: Fire Fighting System

HALON 1301 SYSTEM

Page 15: Fire Fighting System

HALON 1301

- Bromotriflouromethane ( CBrF) or BTM- Liquefied gas chemical - Breaks the chain reaction of fire

Page 16: Fire Fighting System

HALON 1301 SYSTEM

Halon Cylinders and nozzles:-(a) Manufacturer - Amalon(b) Cylinder capacity – 6.8/27.2/56.7/113.4/159 kg(c) Nozzle type - 20 Dia – 180 Deg

20/360, 25/180, 40/180, 40/360(a) System pr – 25 bar(b) Approval FM

Detectors :- Ionization, Optical, Heat Detectors

Page 17: Fire Fighting System

Manual operating lever

Manual operating lever

Solenoid valveSolenoid valve

Junction BoxJunction Box

Shuttle valveFeed pipe

Changeover switch

Container and valve details

Page 18: Fire Fighting System

HALON 1301 SYSTEM

Halon Cylinders and nozzles:-(a) Manufacturer - Amalon(b) Cylinder capacity – 6.8/27.2/56.7/113.4/159 kg(c) Nozzle type - 20 Dia – 180 Deg

20/360, 25/180, 40/180, 40/360

(a) System pr – 25 bar(b) Approval FM

Page 19: Fire Fighting System

New Proposals in fire fighting system

• Changing of Under ground Hydarnt and spray water line to above ground

• Phase out of Halon –1301

Page 20: Fire Fighting System

THANK YOU