10/02/2016 1 Fire Protection for Heritage Buildings Steve Emery National Fire Adviser for Historic England How many fires are there in heritage buildings? Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002
Transcript
Page 1: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

1

Fire Protection for Heritage

Buildings

Steve Emery

National Fire Adviser for

Historic England

How many fires are there

in heritage buildings?

Uppark 1986

Prior Park College 1991

Windsor Castle 1992

Edinburgh 2002

ENGLISH HERITAGE Chester 2002

Page 2: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

2

Wardington Manor 2004

Wardington Manor 2004 Hereford 2010

Dartmouth 2010

Sydenham House 2012

Cumin Museum 2013

Glasgow School of Arts 2014

Page 3: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

3

Battersea Arts Centre 2015

Randolph Hotel

Oxford

2015

Clandon Park 2015

Sudbury 2015

We do not know how many fires we have in heritage buildings !

There are no statistics

90% of accidental fires self-extinguish

or are dealt with by occupiers

Not enough fuel

Not enough oxygen

Switching off electrical circuits

Water

sand

Page 4: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

4

Triangle Of

Fire

5M Unventilated

Page 5: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

5

12 Chatham Row, Bath English Heritage

12 Chatham Row, Bath

Chatham Row Fire Test

0

200

400

600

800

1000

1200

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44

Time in Minutes

tem

pe

ratu

re C

. Series1

Series2

Series3

Series4

Series5

Series6

Page 6: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

6

*>143.7°C

*<20.0°C

20.0

40.0

60.0

80.0

100.0

120.0

140.0

Star t plus 37 minutes

Determination by Secretary of State 2008

It is considered that the existing doors (even with self closing

devices fitted) cannot be relied upon to prevent the egress of

smoke at the early stages of a fire.

The existing bedroom doors cannot be described as smoke

stopping doors and the corridor is not adequately protected from

smoke.

If the rooms in dispute are continued to be used as bedrooms it is

considered appropriate to undertake the following measures

which enable an appropriate balance to be struck between

ensuring sufficient fire safety measures are in place for the safety

of people and maintaining the historic fabric and character of the

building:

(i) Upgrade the doors to achieve a period of fire resistance of 30

minutes, with smoke seals; and self closing devices

4.6. The above measures are commensurate with the

enforcement notice issued by the Fire and Rescue Authority.

Page 7: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

7

BRE Fire Testing 3M Double Cube

1MW

34 Minutes

Page 8: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

8

5M Ventilated

66 Minutes

0

50

100

150

200

250

300

350

400

450

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

Tem

per

atu

re (

°C)

Time (s)

2900mm

2800

mm

2500mm

0

50

100

150

200

250

300

350

400

450

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

Tem

per

atu

re (

°C)

Time (s)

2900mm

2800mm

2500mm

3m Unventilated

0

50

100

150

200

250

300

350

400

450

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

Tem

per

atu

re (

°C)

Time (s)

3900mm3800

mm3500mm3000mm2500

mm

0

50

100

150

200

250

300

350

400

450

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

Tem

per

atu

re (

°C)

Time (s)

4900mm4800mm4500mm4000mm3500

mm3000

mm

66 mins

0

50

100

150

200

250

300

350

400

450

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

Tem

per

atu

re (

°C)

Time (s)

4900mm

4800mm

4500

mm

4000

mm

3500

mm

3m Ventilated

65 mins

46 mins 83 mins

56 mins

64 mins

4M Ventilated

5M Ventilated

4M Unventilated

5M Unventilated

353 C 356 C

285 C

214 C

197 C

161 C

416 C

288 C

224 C 177 C

205 C

149 C

Approved Document B v2 Buildings of special architectural or historic interest

• 0.35 Some variation of the provisions set out in this

document may also be appropriate where Part B applies

to existing buildings of special architectural or historic

interest, where adherence to the guidance in this

document might prove unduly restrictive.

• In such cases it would be appropriate to take into

account a range of fire safety features, some of which

are dealt with in this document and some of which are

not addressed in any detail and to set these against an

assessment of the hazard and risk peculiar to the

particular case.

Approved Document B

• 0.32 Factors that should be taken into account include:

• The anticipated probability of a fire starting

• The anticipated fire severity

• The ability of the structure to resist the spread of fire and

smoke and;

• The consequential danger to people in and around the

building

The Secretary of State has determined that the appropriate

remedy, is for the responsible person to prepare a new risk

assessment in which the absence of intumescent strips and

cold smoke seals on the existing bedroom fire doors is

recorded and justified.

Page 9: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

9

27M x 13 M = 351 Sq M x 12 M = 4212 Cubic M

200 Chairs & 0.2 MW each = 40MW

40/351 = 0.1 Mw/M

Door FR 20

Glasgow School of Arts Fire

12.29 May 23rd 2014

Page 10: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

10

Page 11: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

11

Page 12: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

12

Cost of Sprinklers

£16 per square Metre

Plus tanks and pumps

Page 13: Fire Protection for Heritage Buildings€¦ · Uppark 1986 Prior Park College 1991 Windsor Castle 1992 Edinburgh 2002 ENGLISH HERITAGE Chester 2002. 10/02/2016 . 2 . Wardington Manor

10/02/2016

13

1155 square Metres x 5 Floors & 3 Floor voids x £16 = £155,840

Cost of Sprinklers Cost of Sprinklers

There are other costs!

• Moving the objects £4000 per room (£320,000 )

• plus specialist conservators if carpet is fragile

• Project Collections Care Assistant and conservator for

supervision (15 months for 12 month project £45,000 &

£22000 for CCA

• Documentation for object movement £ 22,000

• Possibility of an electrician to move chandeliers, picture

lights case lights, etc.

Cost of Sprinklers

• Protection of in situ objects

• Packing material for moving and storing small objects

• Purchase of racking within rooms used for temporary storage

• Building works, lifting floorboards, notching joists, chasing

walls and making good.

• Project manager for works

• Loss of income during project

£16.00 per Square Metre

£73 per Square Metre

Cost of Sprinklers

£674,520 £155,840

Stokesay Gatehouse

How do you prioritise?