F I R E R A T E D A S / N Z 3 0 1 3 : 2 0 0 5 Fire Rated Cable Support Systems AS/NZ 3013:2005 - Classification WS5X – 2 hour fire rating to 1050 Degrees Celsius FIRST CHOICE FOR • TRAY • LADDER • STRUT • HYGROUND • CABLE MESH
Transcript
Page 1: Fire Rated Cable Support Systems - Burndy CSS

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

Fire Rated Cable Support SystemsAS/NZ 3013:2005 - Classification WS5X – 2 hour fire rating to 1050 Degrees Celsius

FIRST CHOICE FOR • TRAY • LADDER • STRUT • HYGROUND • CABLE MESH

Page 2: Fire Rated Cable Support Systems - Burndy CSS

Western Australia 91 - 93 McDowell Street, Welshpool, Western Australia, 6106

Head Office Phone 08 9458 1188

Fax 08 9458 1182

email [email protected]

New South Wales 11 Sunblest Crescent, Mt Druitt, New South Wales 2770

Phone 02 9832 3377

Fax 02 9832 0733

email [email protected]

Tasmania Gordon Wood & Co

31 Sunderland Street, Moonah, Tasmania 7009

Phone 03 627 34455

Fax 03 627 34734

email [email protected]

Queensland Brisbane Branch161 Jackson Road, Sunnybank Hills

Queensland, 4109

Phone 07 3219 6108

Fax 07 3219 6208

email [email protected]

Townsville Branch75 - 81 Toll Street, Mount St John

Queensland, 4818

Phone 1300 287 639

Fax 1300 329 669

email [email protected]

www.burndycss.com.au

February 2019

1300 BURNDY 1300 FAX NOW(1300 287 639) (1300 329 669)

Page 3: Fire Rated Cable Support Systems - Burndy CSS

iFIRE RATED CABLE SUPPORT SYSTEMS

About Burndy

Burndy is an Australian owned and operated company. Our products are Australian made to Australian standards.

Pioneers of the original Laddertray systems, Burndy are considered by many to have established the benchmark for quality and performance in commercial construction applications.

For over 35 years, it has been widely held that Burndy have been leaders in their field. Their continuous efforts at improving both products and services have been rewarded by a wide and growing user base and resellers.

Established in 1982, Phoenix Metalform, the parent company of Burndy, are a significant participant in sheet metal roll forming and fabrication.

With branch offices throughout Australia, Burndy is always conveniently placed to service its customers.

Manufactured in a wide range of materials including Hot Dip Galvanised Steel, Aluminium and Stainless Steel, there is a Burndy product to suit your specific application and environmental conditions.

Always striving to meet the growing demands of a sophisticated market, the Burndy range has evolved to provide a genuine one stop shop with the ability to satisfy your cable support needs.

Our mission is to be your first choice for the supply of cable support systems in Australia, and having a dedicated team of professionals is an essential platform in achieving that goal.

You can be assured of Burndy’s commitment to continually improving our range, our product quality, our value for money and our delivery turnaround time.

i

Company Profile

Page 4: Fire Rated Cable Support Systems - Burndy CSS

ii FIRE RATED CABLE SUPPORT SYSTEMS

Fire Rated AS/NZ 3013:2005

Fire Rated AS/NZ 3013:2005 Introduction

Electrical installations are the number one cause of fire in modern buildings in Australia. Fire rated cable support systems can reduce the human cost of fires as well as limit damage caused by early collapse.

Burndy have played a major role in developing Fire Rated Cable Support Systems in Australia. As an Australian manufacturer established in 1982 we have over 35 years’ experience in Cable Support Systems. In that time we have built up a wealth of knowledge and experience.

Our extensive range of Fire Rated Cable Support Systems has been developed in-house utilising our industry experience. All of our products comply with AS/NZS 3013:2005, WS5X 2 hour fire rating to 1050 degrees.

Our Fire Rated systems are available in a range of finishes• Hot Dipped Galvanised• Pre Galvanised• Powder Coated in a range of colour options

Widths available 150-600mm

Cable laying depths available 45mm to 105mm

Load ratings up to 150 kg per metre

Providing innovative & value for money solutions

Our aim is to provide our customers Fire Rated AS/NZS 3013:2005 compliant systems. Our wealth of knowledge can ensure compliance as well as innovative economical solutions to ensure our customers obtain the best value for money systems in the market.

Our large range allows us to offer choice in finish, load rating, installation time savings and designs allowing for installation space.

When new regulations are introduced you can trust the team at Burndy has up-to-date compliant systems.

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

Page 5: Fire Rated Cable Support Systems - Burndy CSS

9.1FIRE RATED CABLE SUPPORT SYSTEMS

CONTENTS

9 FIRE RATED 9.1

FR50L Fire Rated Ladder (NEMA 2 Side Rail) 9.2

FR50L AS/NZ 3013:2005 Fire Rated Ladder Arrangement 9.3

FR50VL Fire Rated Ladder (NEMA 2 Side Rail) 9.4

FR50VL AS/NZ 3013:2005 Fire Rated Ladder Arrangement 9.5

FR60L Fire Rated Ladder (NEMA 3 Side Rail) 9.6

FR60L AS/NZ 3013:2005 Fire Rated Ladder Arrangement 9.7

FR70L Fire Rated Ladder (NEMA 4 Side Rail) 9.8

FR70L AS/NZ 3013:2005 Fire Rated Ladder Arrangement 9.9

FR100L Fire Rated Ladder (NEMA 4 Side Rail) 9.10

FR100L AS/NZ 3013:2005 Fire Rated Ladder Arrangement 9.11

FR150L Fire Rated Ladder (NEMA 4 Side Rail) 9.12

FR150L AS/NZ 3013:2005 Fire Rated Ladder Arrangement 9.13

FR50LT3 Fire Rated Laddertray (LT3) 9.14

FR50LT3 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement 9.15

FR12LT5 Fire Rated Laddertray (LT5) 9.16

FR12LT5 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement 9.17

FR20LT5 Fire Rated Laddertray (LT5) 9.18

FR20LT5 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement 9.19

FR7BCM Fire Rated Cable Mesh 9.20

FR7BCM AS/NZ 3013:2005 Fire Rated Cable Mesh Arrangement 9.21

FR5C Fire Rated Cable Channel 9.22

FR5C AS/NZ 3013:2005 Fire Rated Cable Channel Arrangement 9.23

Fire Rated Accessories 9.24

Fire Rated Swivel Bracket Heavy Duty 9.24

Fire Rated Swivel Bracket Medium Duty 9.24

Fire Rated Beam Clamp 9.24

Fire Rated Cantilever Bracket 9.25

Fire Rated Summary Chart 9.26

Page 6: Fire Rated Cable Support Systems - Burndy CSS

9.2 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR50L Fire Rated Ladder (NEMA 2 Side Rail)AS/NZ 3013:2005

FR50L AS/NZ 3013:2005 Fire Rated Ladder Arrangement

Specifications - Standard Length 6.0 metres.

- Cable Ladder Rung Spacing 333 mm

- Cable laying depth 45 mm

Surface Finish Available Finish

Hot Dip Galvanised to AS/NZ 4680:2006

Stainless Steel Gr316 Passivated Finish

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR50L arrangement.

Custom fittings are available upon request.

Uniform load rating of 50 kg per metre.

Maximum support span of 1.5 metres.

Ladder

Ordering Code Width mm Length mm No of Rungs

N2L150RIH-F6 150 6000 18

N2L300RIH-F6 300 6000 18

N2L450RIH-F6 450 6000 18

N2L600RIH-F6 600 6000 18

Kit Ordering Code FR50L<width>

Page 7: Fire Rated Cable Support Systems - Burndy CSS

9.3FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR50L Fire Rated Ladder (NEMA 2 Side Rail)AS/NZ 3013:2005

4040

6.0

6.0

41

.3

41.3

82

.6

94

.6

30.01

4.0

30.0

2.0

15

0.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

HANGING TRAPEZE FR NEMA 3ISOMETRIC VIEW

4040

6.0

6.0

41.3

41.3

82.6

94.6

89

WIDTH

132

30

27

16

WIDTH

51

94.0

26.8

15.0

1.6

16.0NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

ITEM NO. QTY. WEIGHT MATERIAL PART NUMBER DESCRIPTION COMMENT

1 1 0.51 HDG TS600FRH HANGING BEAM 710LG (B1001 & 4 SPACER ) INC. IN CS09

2 4 0.00 NYLON BTHF12 M12 TOP HAT WASHER INC. IN CS09

3 4 0.01 S/S 316 FW12S M12 ROUND WASHER INC. IN CS09

4 4 0.01 S/S 316 HN12S M12 HEX NUT INC. IN CS09

5 4 0.00 S/S 316 SW12S M12 SPRING WASHER INC. IN CS09

6 2 0.05 HDG B1008H M10 CHANNEL NUT INC. IN CS09

7 2 0.01 HDG HDH HOLD DOWN BRACKET INC. IN CS09

8 2 0.03 HDG HS1030H M10 HEX BOLT INC. IN CS09

9 2 - S/S 316 TR12S M12 S/S THREADED ROD NOT INC.

10 1 - HDG NEMA 3 FR 600 NEMA 3 LADDER FR 600 NOT INC. REFER CLK6

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MCHDG 390 (MINIMUM) WD

18.05.17 12.06.17 E18.05.17CS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

Page 8: Fire Rated Cable Support Systems - Burndy CSS

9.4 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR50VL Fire Rated Ladder (NEMA 2 Side Rail)AS/NZ 3013:2005

FR50VL AS/NZ 3013:2005 Fire Rated Ladder Arrangement

Specifications - Standard Length 6.0 metres.

- Cable Ladder Rung Spacing 333 mm

- Cable laying depth 45 mm

Surface Finish Available Finish

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR50L arrangement.

Custom fittings are available upon request.

Uniform load rating of 50 kg per metre.

Maximum support span of 1.0 metres.

Ladder

Ordering Code Width mm Length mm No of Rungs

N2L150RIH-F6 150 6000 18

N2L300RIH-F6 300 6000 18

N2L450RIH-F6 450 6000 18

N2L600RIH-F6 600 6000 18

Kit Ordering Code FR50VL<width>

Page 9: Fire Rated Cable Support Systems - Burndy CSS

9.5FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR50VL Fire Rated Ladder (NEMA 2 Side Rail)AS/NZ 3013:2005

CABLE SUPPORT SYSTEMS

11.4

FR50VL Fire Rated Ladder (Nema 2 Side Rail)AS/NZ 3013:2005

FR50VL AS/NZ 3013:2005 Fire Rated Ladder Arrangement

CABLE SUPPORT SYSTEMS

11.4

FR50VL Fire Rated Ladder (Nema 2 Side Rail)AS/NZ 3013:2005

FR50VL AS/NZ 3013:2005 Fire Rated Ladder Arrangement

/Drawing No.

Title

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF BURNDY ELECTRICAL PRODUCTS

FAX - (07) 3219 6208PHONE - (07) 3219 6108

Queensland 4109Sunybank Hills161 Jackson Road

Burndy ElectricalSheetRevision

DateDrawn By

DD

CC

BB

AA

6

6

5

5

4

4 3

2

2

1

1

Approved ByAQ

1A4 1

27/10/2014

BURNDY-141027-1

N3LRI-VFR-T2E

FERNANDO.D 1000

1000

1000

1000

1000

A

DETAIL A

NEMA 2/3 CABLE LADDER

CABLE LADDER RUNG

SQUARE WASHERB1064H

HN12HDG

HKD 2HR FIRE RATED

THREADED RODTR12HDG

NOTE:

TEST REFERENCE EWFA 26786700.1

/Drawing No.

Title

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF BURNDY ELECTRICAL PRODUCTS

FAX - (07) 3219 6208PHONE - (07) 3219 6108

Queensland 4109Sunybank Hills161 Jackson Road

Burndy ElectricalSheetRevision

DateDrawn By

DD

CC

BB

AA

6

6

5

5

4

4 3

2

2

1

1

Approved ByAQ

1A4 1

27/10/2014

BURNDY-141027-1

N3LRI-VFR-T2E

FERNANDO.D 1000

1000

1000

1000

1000

A

DETAIL A

NEMA 2/3 CABLE LADDER

CABLE LADDER RUNG

SQUARE WASHERB1064H

HN12HDG

HKD 2HR FIRE RATED

THREADED RODTR12HDG

NOTE:

TEST REFERENCE EWFA 26786700.1

Page 10: Fire Rated Cable Support Systems - Burndy CSS

9.6 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR60L Fire Rated Ladder (NEMA 3 Side Rail)AS/NZ 3013:2005

FR60L AS/NZ 3013:2005 Fire Rated Ladder Arrangement

Specifications - Standard Length 6.0 metres.

- Cable Ladder Rung Spacing 333 mm

- Cable laying depth 84 mm

Surface Finish Available Finish

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR60L arrangement.

Custom fittings are available upon request.

Uniform load rating of 60 kg per metre.

Maximum support span of 1.5 metres.

Ladder

Ordering Code Width mm Length mm No of Rungs

N3L150RIH-F6 150 6000 18

N3L300RIH-F6 300 6000 18

N3L450RIH-F6 450 6000 18

N3L600RIH-F6 600 6000 18

Kit Ordering Code FR60L<width>

Page 11: Fire Rated Cable Support Systems - Burndy CSS

9.7FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR60L Fire Rated Ladder (NEMA 3 Side Rail)AS/NZ 3013:2005

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41

.3

41.3

82

.6

94

.6

30.01

4.0

30.0

2.0

15

0.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

HANGING TRAPEZE FR NEMA 3ISOMETRIC VIEW

4040

6.0

6.0

41.3

41.3

82.6

94.6

89.1

WIDTH

132.

0

30.0

27.0

16.0 1.6

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

ITEM NO. QTY. WEIGHT MATERIAL PART NUMBER DESCRIPTION COMMENT

1 1 0.51 HDG TS600FRH HANGING BEAM 710LG (B1001 & 4 SPACER ) INC. IN CS09

2 4 0.00 NYLON BTHF12 M12 TOP HAT WASHER INC. IN CS09

3 4 0.01 S/S 316 FW12S M12 ROUND WASHER INC. IN CS09

4 4 0.01 S/S 316 HN12S M12 HEX NUT INC. IN CS09

5 4 0.00 S/S 316 SW12S M12 SPRING WASHER INC. IN CS09

6 2 0.05 HDG B1008H M10 CHANNEL NUT INC. IN CS09

7 2 0.01 HDG HDH HOLD DOWN BRACKET INC. IN CS09

8 2 0.03 HDG HS1030H M10 HEX BOLT INC. IN CS09

9 2 - S/S 316 TR12S M12 S/S THREADED ROD NOT INC.

10 1 - HDG NEMA 3 FR 600 NEMA 3 LADDER FR 600 NOT INC. REFER CLK6

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MCHDG 390 (MINIMUM) WD

18.05.17 12.06.17 E18.05.17CS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.341.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

Page 12: Fire Rated Cable Support Systems - Burndy CSS

9.8 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR70L Fire Rated Ladder (NEMA 4 Side Rail)AS/NZ 3013:2005

FR70L AS/NZ 3013:2005 Fire Rated Ladder Arrangement

Specifications - Standard Length 6.0 metres.

- Cable Ladder Rung Spacing 333 mm

- Cable laying depth 102 mm

Surface Finish Available Finish

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR70L arrangement.

Custom fittings are available upon request.

Uniform load rating of 70 kg per metre.

Maximum support span of 1.5 metres.

Ladder

Ordering Code Width mm Length mm No of Rungs

N4L150RIH-F6 150 6000 18

N4L300RIH-F6 300 6000 18

N4L450RIH-F6 450 6000 18

N4L600RIH-F6 600 6000 18

Kit Ordering Code FR70L<width>

Page 13: Fire Rated Cable Support Systems - Burndy CSS

9.9FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR70L Fire Rated Ladder (NEMA 4 Side Rail)AS/NZ 3013:2005

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41

.3

41.3

82

.6

94

.6

30.01

4.0

30.0

2.0

15

0.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

Page 14: Fire Rated Cable Support Systems - Burndy CSS

9.10 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR100L Fire Rated Ladder (NEMA 4 Side Rail)AS/NZ 3013:2005

FR100L AS/NZ 3013:2005 Fire Rated Ladder Arrangement

Specifications - Standard Length 6.0 metres.

- Cable Ladder Rung Spacing 333 mm

- Cable laying depth 102 mm

Surface Finish Available Finish

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR100L arrangement.

Custom fittings are available upon request.

Uniform load rating of 100 kg per metre.

Maximum support span of 1.0 metres.

Ladder

Ordering Code Width mm Length mm No of Rungs

N4L900RIH-F6 900 6000 18

Kit Ordering Code FR100L<width>

Page 15: Fire Rated Cable Support Systems - Burndy CSS

9.11FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR100L Fire Rated Ladder (NEMA 4 Side Rail)AS/NZ 3013:2005

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41

.3

41.3

82

.6

94

.6

30.01

4.0

30.0

2.0

15

0.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

Page 16: Fire Rated Cable Support Systems - Burndy CSS

9.12 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR150L Fire Rated Ladder (NEMA 4 Side Rail)AS/NZ 3013:2005

FR150L AS/NZ 3013:2005 Fire Rated Ladder Arrangement

Specifications - Standard Length 6.0 metres.

- Cable Ladder Rung Spacing 333 mm

- Cable laying depth 102 mm

Surface Finish Available Finish

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR150L arrangement.

Custom fittings are available upon request.

Uniform load rating of 150 kg per metre.

Maximum support span of 1.0 metres.

Ladder

Ordering Code Width mm Length mm No of Rungs

N4L150RIH-F6 150 6000 18

N4L300RIH-F6 300 6000 18

N4L450RIH-F6 450 6000 18

N4L600RIH-F6 600 6000 18

Kit Ordering Code FR150L<width>

Page 17: Fire Rated Cable Support Systems - Burndy CSS

9.13FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR150L Fire Rated Ladder (NEMA 4 Side Rail)AS/NZ 3013:2005

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41

.3

41.3

82

.6

94

.6

30.01

4.0

30.0

2.0

15

0.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

4040

6.0

6.0

41.3

41.3

82.6

94.6

30.0

14.0

30.0

2.0

150.0

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS4680.4.FOR LADDER ASSEMBLY AND DETAILS REFER TO PART CLK6.

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

161 Jackson Road,

Sunnybank Hills,

QLD 4109

Ph: 3219 6108

Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD MC WD

ECS09

DRAWN

CARBON STEEL

HDG

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

Page 18: Fire Rated Cable Support Systems - Burndy CSS

9.14 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR50LT3 Fire Rated Laddertray (LT3)AS/NZ 3013:2005

FR50LT3 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement

Specifications - Standard Length 3.0 metres.

- Cable laying depth 40 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR50LT3 arrangement.

Uniform load rating of 50 kg per metre.

Maximum support span of 1.0 metres.

Cable Laying Width mm

Pre-GalvanisedOverall Width

mm150 LT3150G 172

300 LT3300G 322

450 LT3450G 472

600 LT3600G 622

Kit Ordering Code FR50LT3<width>

11.13CABLE SUPPORT SYSTEMS

FR50LT3 Fire Rated Laddertray (LT3)AS/NZ 3013:2005

FR50LT3 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement

Specications - Standard Length 3.0 metres. - Cable laying depth 40 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special nishes on request against rm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classication WS5X. It is designed and tested to achieve 2 hour re rating at 1050 deg. Centigrade. Fire rating only applies when used as a complete FR50LT3 arrangement.

Uniform load rating of 50 kg per metre.

Maximum support span of 1.0 metres.

Ordering Code FR50LT3 will include all required items in this arrangement

Cable Laying Widthmm

Pre-Galvanised Overall Widthmm 40 50

150300450600

LT3150GLT3300GLT3450GLT3600G

172322472622

Hot Dip Galvanised to AS/NZ 4680:2006

Page 19: Fire Rated Cable Support Systems - Burndy CSS

9.15FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR50LT3 Fire Rated Laddertray (LT3)AS/NZ 3013:2005

61.9 9.

3

41.33

WIDTH

43.3

49.0

11.0

17.0

5.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

61.9 9.

3

41.33

WIDTH

43.3

49.0

11.0

17.0

5.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

61.9 9.

3

41.33

WIDTH

43.3

49.0

11.0

17.0

5.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

Page 20: Fire Rated Cable Support Systems - Burndy CSS

9.16 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR12LT5 Fire Rated Laddertray (LT5)AS/NZ 3013:2005

FR12LT5 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement

Specifications - Standard Length 3.0 metres.

- Cable laying depth 75 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR12LT5 arrangement.

Uniform load rating of 13 kg per metre.

Maximum support span of 1.5 metres.

Cable Laying Width mm

Pre-GalvanisedOverall Width

mm150 LT5150G 172

300 LT5300G 322

Kit Ordering Code FR12LT5<width>

11.15CABLE SUPPORT SYSTEMS

FR12LT5 Fire Rated Laddertray (LT5)AS/NZ 3013:2005

FR12LT5 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement

Specications - Standard Length 3.0 metres. - Cable laying depth 75 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special nishes on request against rm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classication WS5X. It is designed and tested to achieve 2 hour re rating at 1050 deg. Centigrade. Fire rating only applies when used as a complete FR12LT5 arrangement.

Uniform load rating of 13 kg per metre.

Maximum support span of 1.5 metres.

Ordering Code FR12LT5 will include all required items in this arrangement

Cable Laying Widthmm

Pre-Galvanised Overall Widthmm

150300450600

LT5150GLT5300GLT5450GLT5600G

172322472622

75 85

Hot Dip Galvanised to AS/NZ 4680:2006

Page 21: Fire Rated Cable Support Systems - Burndy CSS

9.17FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR12LT5 Fire Rated Laddertray (LT5)AS/NZ 3013:2005

61.9 9.

3

41.3

3

78.6

WIDTH

5.7

11.0

17.00.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

61.9 9.

3

41.3

3

78.6

WIDTH

5.7

11.0

17.00.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

61.9 9.

3

41.3

3

78.6

WIDTH

5.7

11.0

17.00.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

Page 22: Fire Rated Cable Support Systems - Burndy CSS

9.18 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR20LT5 Fire Rated Laddertray (LT5)AS/NZ 3013:2005

FR20LT5 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement

Specifications - Standard Length 3.0 metres.

- Cable laying depth 75 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR20LT5 arrangement.

Uniform load rating of 19.6 kg per metre.

Maximum support span of 1.0 metres.

Cable Laying Width mm

Pre-GalvanisedOverall Width

mm150 LT5150G 172

300 LT5300G 322

Kit Ordering Code FR20LT5<width>

11.15CABLE SUPPORT SYSTEMS

FR12LT5 Fire Rated Laddertray (LT5)AS/NZ 3013:2005

FR12LT5 AS/NZ 3013:2005 Fire Rated Laddertray Arrangement

Specications - Standard Length 3.0 metres. - Cable laying depth 75 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special nishes on request against rm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classication WS5X. It is designed and tested to achieve 2 hour re rating at 1050 deg. Centigrade. Fire rating only applies when used as a complete FR12LT5 arrangement.

Uniform load rating of 13 kg per metre.

Maximum support span of 1.5 metres.

Ordering Code FR12LT5 will include all required items in this arrangement

Cable Laying Widthmm

Pre-Galvanised Overall Widthmm

150300450600

LT5150GLT5300GLT5450GLT5600G

172322472622

75 85

Hot Dip Galvanised to AS/NZ 4680:2006

Page 23: Fire Rated Cable Support Systems - Burndy CSS

9.19FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR20LT5 Fire Rated Laddertray (LT5)AS/NZ 3013:2005

61.9 9.

3

41.3

3

78.6

WIDTH

5.7

11.0

17.00.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

61.9 9.

3

41.3

3

78.6

WIDTH

5.7

11.0

17.00.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

161

.9 9.3

41.3

3

78.6

WIDTH

5.7

11.0

17.00.7

NOTES:1. ALL SHARP EDGES AND BURRS TO BE REMOVED.2. ALL LINEAR TOLERANCE TO BE +/-1.0mm, ALL ANGULAR TO BE +/-1.0 DEGREE U.N.O.3. ALL PRE GALVANISED PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1397.4. ALL HDG PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS/NZ1365, AS1594, AS/NZS46805. ALL STAINLESS STEEL PRODUCT TO BE FABRICATED IN ACCORDANCE WITH AS1449 & AS2837

TECHNICAL INFORMATION

LADDER TYPE NEMA 1 LADDER NON-FR LADDER WIDTH 600mm

TIER QUANTITY 2 MAX SPAN 3m

DESIGN LIFE 25 YEARS LADDER LOAD CAPACITY 150kg/m/TIER

FIRE RATED NO FIRE TEST REPORT No NOT REQUIRED

EXPOSURE CLASS C4

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

Drawing No.

Drawn RevisionInitiated: Approved:

Date :Finish

Material

GradeDESCRIPTION DATE APP'D

REVISIONS

DO NOT SCALE

161 Jackson Road,Sunnybank Hills,QLD 4109

Ph: 3219 6108Fax: 3219 6208

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV FD ZD

A ISSUED FOR INTERNAL REVIEW 04/11/2018

LT5 LADDER TRAY ASSEMBLY

FD

AS PER B.O.M. FD

28.06.18 29.06.18 A28.06.18

LT5

LT5

GENERAL ARRANGEMENT

DRAWN

ZD AS PER B.O.M.

AS PER B.O.M.

A A

B B

C C

D D

6

6

5

5

4

4

3

3

2

2

1

1

Page 24: Fire Rated Cable Support Systems - Burndy CSS

9.20 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR7BCM Fire Rated Cable MeshAS/NZ 3013:2005

FR7BCM AS/NZ 3013:2005 Fire Rated Cable Mesh Arrangement

Specifications - Standard Length 3.0 metres.

- Cable laying depth 50 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR7BCM arrangement.

Uniform load rating of 7 kg per metre.

Maximum support span of 1.0 metres.

Ordering Code Height mm Width mm

BCM150PG 50 150

BCM300PG 50 300

Kit Ordering Code FR7BCM<width>

11.19CABLE SUPPORT SYSTEMS

FR7BCM Fire Rated Cable MeshAS/NZ 3013:2005

FR7BCM AS/NZ 3013:2005 Fire Rated Cable Mesh Arrangement

Specications - Standard Length 3.0 metres. - Cable laying depth 50 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special nishes on request against rm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classication WS5X. It is designed and tested to achieve 2 hour re rating at 1050 deg. Centigrade. Fire rating only applies when used as a complete FR7BCM arrangement.

Uniform load rating of 7 kg per metre.

Maximum support span of 1.0 metres.

Ordering Code FR7BCM will include all required items in this arrangement

Ordering Code

BCM150PGBCM300PGBCM450PGBCM600PG

50505050

150300450600

25

50 50 50

50

o20

width

Heightmm

Widthmm

Hot Dip Galvanised to AS/NZ 4680:2006

Page 25: Fire Rated Cable Support Systems - Burndy CSS

9.21FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR7BCM Fire Rated Cable MeshAS/NZ 3013:2005

41.3

41.3

WIDTH

54.5

4.5

G.W. M.C.

11.5.179.5.17

MESH 300W PRE GAL

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

A4Drawing No.

Drawn

11

Burndy Cable Support Systems

/SheetRevision

Initiated

DD

CC

BB

AA

6

6

5

5

4

4

3

3

2

2

1

1

Approved

Date :Finish

Material

Grade

UNLESS OTHERWISE SPECIFIED ALL

TOLERANCESLINEAR =+/- 1.0ANGULAR =+/- 1.0 Degree

DIMENSIONS ARE IN MILLIMETRES

REMOVE ALL SHARP EDGES AND BURRS

DESCRIPTION DATE APP'D

REVISIONS

NOTES:

161Jackson Road,Sunnybank Hills,Qld 4109

Ph: 3219 6108Fax: 3219 6208

THIRD ANGLE PROJECTION

By : By : By :

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV

41.3

41.3

WIDTH

54.5

4.5

G.W. M.C.

11.5.179.5.17

MESH 300W PRE GAL

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

A4Drawing No.

Drawn

11

Burndy Cable Support Systems

/SheetRevision

Initiated

DD

CC

BB

AA

6

6

5

5

4

4

3

3

2

2

1

1

Approved

Date :Finish

Material

Grade

UNLESS OTHERWISE SPECIFIED ALL

TOLERANCESLINEAR =+/- 1.0ANGULAR =+/- 1.0 Degree

DIMENSIONS ARE IN MILLIMETRES

REMOVE ALL SHARP EDGES AND BURRS

DESCRIPTION DATE APP'D

REVISIONS

NOTES:

161Jackson Road,Sunnybank Hills,Qld 4109

Ph: 3219 6108Fax: 3219 6208

THIRD ANGLE PROJECTION

By : By : By :

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV

41.3

41.3

WIDTH

54.5

4.5

G.W. M.C.

11.5.179.5.17

MESH 300W PRE GAL

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

A4Drawing No.

Drawn

11

Burndy Cable Support Systems

/SheetRevision

Initiated

DD

CC

BB

AA

6

6

5

5

4

4

3

3

2

2

1

1

Approved

Date :Finish

Material

Grade

UNLESS OTHERWISE SPECIFIED ALL

TOLERANCESLINEAR =+/- 1.0ANGULAR =+/- 1.0 Degree

DIMENSIONS ARE IN MILLIMETRES

REMOVE ALL SHARP EDGES AND BURRS

DESCRIPTION DATE APP'D

REVISIONS

NOTES:

161Jackson Road,Sunnybank Hills,Qld 4109

Ph: 3219 6108Fax: 3219 6208

THIRD ANGLE PROJECTION

By : By : By :

Date : Date :

PRODUCT DESCRIPTION

PART NUMBER

REV

41.3

41.3

WIDTH

54.5

4.5

G.W.M.C.

11.5.17 9.5.17

MESH 300W PRE GAL

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF PHOENIX STEEL SALES PTY LTD.

A4Drawing No.

Drawn

1 1

Burndy Cable Support Systems

/Sheet Revision

Initiated

D D

C C

B B

A A

6

6

5

5

4

4

3

3

2

2

1

1

Approved

Date : Finish

Material

Grade

UNLESS OTHERWISE SPECIFIED ALL

TOLERANCESLINEAR =+/- 1.0ANGULAR =+/- 1.0 Degree

DIMENSIONS ARE IN MILLIMETRES

REMOVE ALL SHARP EDGES AND BURRS

DESCRIPTIONDATEAPP'D

REVISIONS

NOTES:

161Jackson Road,Sunnybank Hills,Qld 4109

Ph: 3219 6108Fax: 3219 6208

THIRD ANGLE PROJECTION

By :By :By :

Date :Date :

PRODUCT DESCRIPTION

PART NUMBER

REV

Page 26: Fire Rated Cable Support Systems - Burndy CSS

9.22 FIRE RATED CABLE SUPPORT SYSTEMS

INFORMATION

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

FR5C Fire Rated Cable ChannelAS/NZ 3013:2005

FR5C AS/NZ 3013:2005 Fire Rated Cable Channel Arrangement

Specifications - Standard Length 6.0 metres.

- Cable laying depth 45 mm

Surface Finish Available Finish

Pre Galvanised to AS1397

Hot Dip Galvanised to AS/NZ 4680:2006

Note - The Burndy Fire Rated Systems requires no on-site welding to cut and rejoin.

- Powder coating and special finishes on request against firm orders only and are non returnable.

The Fire Rated System complies with Australian and New Zealand Standard AS/NZ 3013:2005 Classification WS5X. It is designed and tested to achieve 2 hour fire rating at 1050 degrees Celsius.

Fire rating only applies when used as a complete FR5C arrangement.

Uniform load rating of 5 kg per metre.

Maximum support span of 1.5 metres.

Ordering Code Height mm Width mm

FR5C 62 42

Kit Ordering Code FR5C

Page 27: Fire Rated Cable Support Systems - Burndy CSS

9.23FIRE RATED CABLE SUPPORT SYSTEMS

ARRANGEMENTFR5C Fire Rated Cable ChannelAS/NZ 3013:2005

1500 1500 1500

HS1020ZHS1020Z HN10Z

HN10Z

FW10Z

FW10ZB1008Z B1008Z

TR10Z

B5500G 6000L 30kg/m

B1047H

THIS DRAWING IS ISSUED IN STRICT CONFIDENCE AND SHALL NOT BE REPRODUCED WITHOUT THE PERMISSION OF BURNDY ELECTRICAL PRODUCTS

A4Drawing No.

Title

Approved By

PHONE - (07) 3219 6108FAX - (07) 3219 6208

161 Jackson RoadSunnybank HillsQueensland 4109

11

Burndy Electrical/

SheetRevision

DateDrawn By

DD

CC

BB

AA

6

6

5

5

4

4

3

3

2

2

1

1

AQ FERNANDO DIFAZIO 17/06/2015

SD 8 of 10 B5500G 1.5m SPAN 30kg/m

BURNDY-150617-3

Page 28: Fire Rated Cable Support Systems - Burndy CSS

9.24 FIRE RATED CABLE SUPPORT SYSTEMS

Fire Rated Accessories

Fire Rated Swivel Bracket Heavy Duty

Fire Rated Swivel Bracket Medium Duty

Fire Rated Beam Clamp

Ordering Code BFRSBHDH

Ordering Code BFRSBMDH

Ordering Code FRMDSBBC

Page 29: Fire Rated Cable Support Systems - Burndy CSS

9.25FIRE RATED CABLE SUPPORT SYSTEMS

Fire Rated Accessories

FIRE RATED

AS / N Z 3 0 1 3 : 2

0 05

Fire Rated Cantilever Bracket

Ordering Code Length Load Capacity kg

CLB335FRH 335 100

CLB485FRH 485 100

CLB635FRH 635 100

CLB335FRH CLB485FRH CLB635FRH

Page 30: Fire Rated Cable Support Systems - Burndy CSS

9.26 FIRE RATED CABLE SUPPORT SYSTEMS

Fire Rated Summary Chart

Fire Rated Options

Page Kit Code Product Load

RatingSupport Included

Cable Laying Depth

Cable Laying Width

LengthsSupport

SpanOrientation

9.2 FR50LNema 2 Cable Ladder

50kg metre

Trapeze / Cantilever

45mm

150mm 300mm 450mm 600mm

3m 6m

1.5m Horizontal

9.4 FR50VLNema 2 Cable Ladder

50kg metre

45mm

150mm 300mm 450mm 600mm

3m 6m

1m Vertical

9.6 FR60LNema 3 Cable Ladder

60kg metre

Trapeze / Cantilever

84mm

150mm 300mm 450mm 600mm

3m 6m

1.5m Horizontal

9.8 FR70LNema 4 Cable Ladder

70kg metre

Trapeze / Cantilever

102mm

150mm 300mm 450mm 600mm

3m 6m

1.5m Horizontal

9.10 FR100LNema 4 Cable Ladder

100kg metre

Trapeze / Cantilever

102mm 900mm3m 6m

1m Horizontal

9.12 FR150LNema 4 Cable Ladder

150kg metre

Trapeze / Cantilever

102mm

150mm 300mm 450mm 600mm

3m 6m

1m Horizontal

9.14 FR50LT3LT3 Laddertray

50kg metre

Trapeze / Cantilever

40mm

150mm 300mm 450mm 600mm

3m 1m Horizontal

9.16 FR12LT5LT5 Laddertray

13kg metre

Trapeze / Cantilever

75mm150mm 300mm

3m 1.5m Horizontal

9.18 FR20LT5LT5 Laddertray

19.6kg metre

Trapeze / Cantilever

75mm150mm 300mm

3m 1m Horizontal

9.20 FR7BCM Cable Mesh7kg

metreTrapeze / Cantilever

50mm150mm 300mm

3m 1m Horizontal

9.22 FR5C Channel5kg

metreThreaded Rod

45mm 42mm 6m 1.5m Horizontal

Kit components include

- Cantilever or Trapeze

- Splice plate & fasteners (ladder only)

- Hold down (tray only)

- Channel nuts, screws, bolts & fasteners to complete the assembly

Page 31: Fire Rated Cable Support Systems - Burndy CSS
Page 32: Fire Rated Cable Support Systems - Burndy CSS

www.burndycss.com.auFebruary 2019

Head Office

Western Australia91 - 93 McDowell Street, WelshpoolWestern Australia, 6106Phone 08 9458 1188Fax 08 9458 1182email [email protected]

New South Wales11 Sunblest Crescent, Mt DruittNew South Wales, 2770Phone 02 9832 3377Fax 02 9832 0733email [email protected]

TasmaniaGordon Wood & Co

31 Sunderland Street, MoonahTasmania, 7009Phone 03 6273 4455Fax 03 6273 4734email [email protected]

Queensland

Brisbane Branch161 Jackson Road, Sunnybank HillsQueensland, 4109Phone 07 3219 6108Fax 07 3219 6208email [email protected]

Townsville Branch75 - 81 Toll Street, Mount St JohnQueensland, 4818Phone 1300 287 639Fax 1300 329 669email [email protected]

8029

1 aco

rnde

sign

.com

.au

FIRST CHOICE FOR • TRAY • LADDER • STRUT • HYGROUND • CABLE MESH


Recommended