Design and Application for Hygienic Outcomes AS/NZS 3666.1 Reflection Craig Johnson Business Development Manager Baltimore Aircoil Australia Pty Ltd
Transcript
Page 1: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Design and Application

for Hygienic Outcomes

AS/NZS 3666.1

Reflection

Craig JohnsonBusiness Development Manager

Baltimore Aircoil Australia Pty Ltd

Page 2: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and
Page 3: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Baltimore Aircoil support and promote the

responsible, effective use of evaporative

cooling equipment . . .

Evaporative cooling is the most economical,

environmentally sustainable, scalable and

flexible cooling method available . . .

Page 4: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Legionella Primary &

Point Sources

Potable WaterPrimary Source

Aerosol Point Sources

Aspirated Point Sources

Spa Baths

Fountains

Supermarket Misters

Towers

Hybrid Mists

Warm WaterServices

Water Supply

Un-HygienicLow Flow Pipes

Showers

Dentist Drill

Page 5: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Equipment shall be constructed from non corrosive materials

Pultruded Composite Components provide up to 5 times the glass (strength) of conventional hand laid LRTM G235

GalvanisedSteel

304/316StainlessSteel

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 6: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

All internal corners and edges to facilitate cleaning and shall be smooth faced

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 7: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Provision for quick draining and refilling

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 8: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Basins and sumps should be water tight and graded to a (min 50mm dia) drain outlet

AS/NZS 3666.1 DESIGN REQUIREMENT

BEST PRACTICE

Stainless steelfully welded, coldwater basin option

Page 9: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Corrosion resistant Louvres included to prevent debrisand splash out, and exclude direct sunlight

AS/NZS 3666.1 DESIGN REQUIREMENT

Combined Inlet Shields (CIS) / louvresare fitted to all BAC evaporative units

Page 10: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Hot water box covers for cross-flow configurations

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 11: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Maximum drift loss shall not exceed 0.002% max design circulation (AS/NZS 4180)

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 12: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Maximum drift loss shall not exceed 0.002% max design circulation (AS/NZS 4180)

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 13: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Ease of maintenance access

AS/NZS 3666.1 DESIGN REQUIREMENT

Counter-flow Configurations

Page 14: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Ease of maintenance access

AS/NZS 3666.1 DESIGN REQUIREMENT

Counter-flow Configuration's

Page 15: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Ease of maintenance, particularly for . . . water distribution system

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 16: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Ease of maintenance, particularly for . . . cleaning eliminators

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 17: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Fill should be designed for in-situ or withdrawn cleaning without damage

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 18: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Fill should be designed for in-situ or withdrawn cleaning without damage

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 19: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Ease of maintenance, particularly for . . . cleaning basin and sumps

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 20: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

AS/NZS 3666.1 DESIGN REQUIREMENT

BEST PRACTICE

Ease of maintenance, particularly for . . . cleaning basin and sumps

Observation of towers with small cold water basinsSmall water retention volumes = harder to manage water chemistry

= risk

Evaporation, bleed, drift, leakage, overflow

Make up WaterWater treatment

Potential for remote sumps to avoid dry running of pump at start up and water + chemical overflow at shut down

Page 21: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

BEST PRACTICE

Access to equipment for maintenance and cleaningNon-Corrosive Pultruded Materials

“Easy and safe access for cleaning, inspection and maintenance shall be to and about all plant, equipment and components covered in this (standard).”

Page 22: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

BEST PRACTICE

Access to equipment for maintenance and cleaningNon-Corrosive Pultruded Materials

Page 23: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

BEST PRACTICEAccess to equipment for maintenance and cleaning

Page 24: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

BEST PRACTICE

Access to equipment for maintenance and cleaning

Page 25: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Automatic bleed off to limit the build-up of dissolved and undissolved

solids, minimize scale, corrosion and fouling

AS/NZS 3666.1 DESIGN REQUIREMENT

“Cooling water systems shall be provided with suitable, automatically controlled water treatment systems for effective management of corrosion, scaling, fouling and micro-biological growth including water treatment when the water is first introduced into the system during the construction phase.”

Page 26: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

BEST PRACTICE

Basin design should compliment use of sump sweeper piping and nozzles

Sump sweeper piping / nozzles and side stream filtration enhance system hygiene.

Page 27: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Orientation – avoid contamination from exhaust discharges of kitchens and other towers (8m)

AS/NZS 3666.1 DESIGN REQUIREMENT

Refer to AS/NZS1668.2 Mechanical Ventilation specifically

Page 28: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Orientation/Placement – direct sunlight is minimized from wetted areas

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 29: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Discharge away from occupied areas pedestrians and thoroughfares air intakes, building openings, traffic areas

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 30: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Enclosures not to interfere with tower airflow

AS/NZS 3666.1 DESIGN REQUIREMENT

Unit Configurations Adjacent to a Solid Wall or Building

Maximum acceptable envelope air velocity ≤ 1.5 m/sec *

Where Envelope Velocity (m/sec) = Unit Airflow (m3/sec) Envelope area (m2)

Single Side EntryFour Side Entry

Double Side Entry

and ① = Unit Inlet

Page 31: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Enclosures not to interfere with tower airflow

AS/NZS 3666.1 DESIGN REQUIREMENT

Unit Configurations in a Well Installation

Maximum acceptable envelope air velocity ≤ 2.0 m/sec *

Where Envelope Velocity (m/sec) = Unit Airflow (m3/sec) Envelope area (m2)

Single Side EntryFour Side EntryDouble Side Entry

and ① = Useable Louvre

Page 32: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Enclosures not to interfere with tower airflow

AS/NZS 3666.1 DESIGN REQUIREMENT

Unit Configurations in a Louvered Well Installation

Maximum acceptable envelope air velocity ≤ 2.5 m/sec *

Where Envelope Velocity (m/sec) = Unit Airflow (m3/sec) Envelope area (m2)

Single Side EntryFour Side Entry

Double Side Entry

and ① = Unit Inlet

Page 33: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Enclosures not to interfere with tower airflow

AS/NZS 3666.1 DESIGN REQUIREMENT

BEST PRACTICEDesign Exceptions to the Rule – Raised Louvres

Page 34: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

Not to recirculate discharge air

AS/NZS 3666.1 DESIGN REQUIREMENT

Page 35: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

AS/NZS 3666.1 DESIGN REQUIREMENTPlease note :

AS/NZS 3666.1: Clause 4.1.5

“Cooling towers that undergo retrofit of components such as fill, basins or eliminators or any upgrade for performance shall be required to meet all requirements associated with cooling towers, of this standard”

Page 36: Fire safety in tall buildings - AIRAH · Baltimore Aircoil Australia Pty Ltd. Baltimore Aircoil support and promote the ... All internal corners and edges to facilitate cleaning and

THANK YOU