FIRE SAFETY PLANS ODETTE BUILDING 580 Sunset Ave Fire Safety Plan Prepared By: ___________________________ Customized Fire Safety Plan (CFSP) CONSULTANT ARC INC. 11 Willow Beach Amherstburg, ON Date Submitted: ________________________ Date Approved: ________________________ Approved Copy Name: _______________________ Date: _______________________
Transcript
Page 1: FIRE SAFETY PLANS

FIRE SAFETY PLANS

ODETTE BUILDING

580 Sunset Ave

Fire Safety Plan Prepared By: ___________________________ Customized Fire Safety Plan

(CFSP) CONSULTANT ARC INC. 11 Willow Beach Amherstburg, ON

Date Submitted: ________________________ Date Approved: ________________________

Approved Copy Name: _______________________ Date: _______________________

Page 2: FIRE SAFETY PLANS

TABLE OF CONTENTS

1 FIRE SAFETY PLAN ...................................................................... Error! Bookmark not defined. PURPOSE ............................................................................................................................................... 4 SCOPE .................................................................................................................................................... 4 DEFINITIONS .......................................................................................................................................... 4 OBJECTIVES .......................................................................................................................................... 5 DESCRIPTION OF BUILDING ................................................................................................................. 5

Building Access for Fire Department .................................................................................................... 6 Communications .................................................................................................................................. 6 Elevators .............................................................................................................................................. 6 Exit Routes .......................................................................................................................................... 6 Fire Plan Location ................................................................................................................................ 7 Keys ..................................................................................................................................................... 7 Operating Hours ................................................................................................................................... 7

UTILITIES & MAIN SHUTOFFS ............................................................................................................... 7 FIRE EMERGENCY EQUIPMENT ........................................................................................................... 8

Annunciator Panel ................................................................................................................................ 8 Emergency Lighting ............................................................................................................................. 9 Emergency Power ................................................................................................................................ 9 Fire Alarm ............................................................................................................................................ 9 Fire Alarm Pull Stations ........................................................................................................................ 9 Fire Blankets ........................................................................................................................................ 9 Fire Department Connections (FDC) .................................................................................................... 9 Fire Extinguishing Equipment ............................................................................................................... 9 Fire Hydrants ....................................................................................................................................... 9 Fire Pump .......................................................................................................................................... 10 Heat Detectors ................................................................................................................................... 10 Hose Cabinets ................................................................................................................................... 10 Smoke Detection Equipment (Smoke Detector, Duct Smoke Detector) .............................................. 10 Sprinkler System ................................................................................................................................ 10 Special Extinguishing System(s) ........................................................................................................ 10 Standpipe System .............................................................................................................................. 11 Smoke Control ................................................................................................................................... 11

FIRE HAZARDS..................................................................................................................................... 11 HAZARDOUS MATERIALS ................................................................................................................... 12 RADIOACTIVE MATERIALS.................................................................................................................. 12 SPILL RESPONSE PROCEDURES ...................................................................................................... 12 CAMPUS COMMUNITY POLICE ........................................................................................................... 12 FIRE EVACUATION DRILLS ................................................................................................................. 13 FIRE ALARM IMPAIRMENT .................................................................................................................. 15

Fire Watch Procedure ........................................................................................................................ 15 FIRE EMERGENCY PROCEDURES ..................................................................................................... 16

UWindsor Alert Emergency Notification System ................................................................................. 18 Persons Requiring Assistance in Evacuation ..................................................................................... 19

DUTIES & RESPONSIBILITIES ............................................................................................................. 20 Appointment of Staff ........................................................................................................................... 20 University of Windsor Duties & Responsibilities ................................................................................. 21 Fire Evacuation Committee Members ................................................................................................ 21 Building Fire Plan Manager Duties ..................................................................................................... 22 Fire Warden Duties ............................................................................................................................ 24 Traffic Officer Duties .......................................................................................................................... 25

Page 3: FIRE SAFETY PLANS

Monitor Duties .................................................................................................................................... 26 Instructor Duties ................................................................................................................................. 26 Event Organizer Duties ...................................................................................................................... 27

2 FLOOR PLANS ................................................................................. Error! Bookmark not defined. 3 FIRE PLAN APPENDICES ............................................................... Error! Bookmark not defined. Appendix I: ................................................................................................ Error! Bookmark not defined. Fire / Evacuation Forms & Postings .......................................................... Error! Bookmark not defined. Appendix II: ............................................................................................... Error! Bookmark not defined. Inspection of Fire Prevention and Protection Systems .............................. Error! Bookmark not defined. Appendix III: .............................................................................................. Error! Bookmark not defined. Fire Extinguisher Guidelines ..................................................................... Error! Bookmark not defined. Appendix IV: ............................................................................................. Error! Bookmark not defined. Emergency Contact Numbers ................................................................... Error! Bookmark not defined. Appendix V: .............................................................................................. Error! Bookmark not defined. Fire Plan Certification Page ...................................................................... Error! Bookmark not defined.

4 SPILL RESPONSE PLAN 5 EVACUATION COMMITTEE 6 FIRE EXTINGUISHER LISTING 7 DRILL REPORTS 8 FIRE DEPARTMENT COMMUNICATION

Page 4: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 4 of 28

PURPOSE

The Ontario Fire Code, Section 2.8 requires the implementation of a Fire Safety Plan for this building/occupancy. The plan is to be kept in the building in an approved location. The implementation of the Fire Safety Plan helps to ensure effective utilization of life safety features in a building to protect people from fire. The required Fire Safety Plan should be designed to suit the resources of each individual building or complex of buildings. It is the responsibility of the owner to ensure that the information contained within the Fire Safety Plan is accurate and complete. The Fire Protection and Prevention Act Part VII, Section 28, states that in the case of an offence for contravention of the fire code, a corporation is liable to a fine of not more than $100,000 and an individual is liable to a fine of not more than $50,000 or imprisonment for a term of not more than one year or both. The purpose of the Fire Safety Plan is to establish minimum requirements that will provide a reasonable degree of life safety from fire and similar emergencies in the University of Windsor buildings and structures. In the occurrence of a crisis, this plan should save lives and reduce personal injuries. Furthermore, it can prevent or minimize property damage, as well as decreasing the time of return to normal activities in the building. This official document is to be kept readily available at all times for use by staff and fire officials in the event of an emergency.

SCOPE

This Fire Safety Plan will include:

location, description, and operation of fire suppression equipment present in the building.

procedures for building occupants during a fire crisis.

duties & responsibilities of key personnel during an emergency evacuation.

regulations for frequency of emergency equipment inspections, as well as fire drills.

DEFINITIONS

B.F.P.M. - Building Fire Plan Manager

Check- visual observation to ensure the device or system is in place and is not obviously damaged or obstructed. Exit - refers to that part of a means of egress that leads from the floor area it serves, including any doorway leading directly from a floor area, to an open public concourse or an exterior open space protected from exposure from the building and having access to a public thoroughfare. FDC – Fire Department Connection (Siamese Connection) Fire Emergency - means a fire situation caused by the forces of nature or an accident or an intentional act or otherwise that constitutes a danger of major proportions to life or property. Fire Safety Plan - is a detailed procedural plan combining the elements of contingency planning and emergency response designed to reduce the effects of an abnormal and unexpected event.

Page 5: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 5 of 28

Incident Commander – First arriving Fire Dept. company officer (ie: Captain, District Chief)

Inspect- physical examination to determine that the device or system will apparently perform in accordance with its intended function. OBC-Ontario Building Code OFC – The Ontario Fire Code (O. Reg. 213/07) as amended Person Requiring Assistance (Mobility Impaired) - a person who is unable to leave a building unassisted under emergency conditions. This may include persons with temporary or permanent mobility disabilities (e.g. use of crutches, walkers, wheelchairs), with hearing or vision disabilities, as well as persons who may be immobilized due to distress.

Supervisory staff - means those occupants of a building who have some delegated responsibility for the fire safety of other occupants under the fire safety plan and may include the fire department where the fire department agrees to accept these responsibilities.

Test- to operate a device or system to ensure that it will perform in accordance with its intended operation or function. WF&RS – Windsor Fire & Rescue Services

OBJECTIVES

The objectives of the fire plan are:

Fire Prevention: To prevent the incident of fire by the control of fire hazards in the building and the maintenance of the building facilities provided for the safety of the occupants. Emergency Evacuation: To establish a systematic method of safe and orderly evacuation of an area or building, by and of its occupants, in case of fire or other emergency. Regulatory Requirements: To establish standards which are in compliance with the Ontario Fire Code.

DESCRIPTION OF BUILDING

The Odette building has different sections of up to 6 stories with a basement. It is immediately north of Wyandotte Street West, west of California Avenue, and east of Sunset Avenue. The building is primarily used for research, teaching, and storage, and houses the University Bookstore (Group A Division 2, Group D). The main floor consists of classrooms, offices, storage rooms and maintenance rooms. There is also a food service area located between the Odette School of Business and the Bookstore. The remaining floors are offices, classrooms and book storage areas.

Page 6: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 6 of 28

The Odette School of Business is considered as a noncombustible construction building. It is constructed of steel framing with concrete panels and face brick. The floor is cast-in-place concrete with metal decking and steel joists. The roof is comprised of single-ply rubber membrane with metal decking and steel joists. The original building opened in 1991 and has had no major renovations. There are approximately 100 employees in this building. The number of students, employees and visitors within the building can vary depending upon the time of year or the time of day. There is no accounting system in place to know how many students are in the building at any one time. Visitors are not required to sign-in or report to Campus Police before entering.

Building Access for Fire Department

This building can be accessed using the south (main) entrance located on the north side of Wyandotte Street West. The Environmental Services division of Facility Services is responsible for maintaining fire access routes.

Communications

There is no Public Address (PA) system within the building. Communication under fire emergency conditions is executed by telephone, or through the UWindsor Alert mass notification system as initiated by the University’s Emergency Response Plan.

Elevators

YES NO There are two (2) elevators in this building. They are located in the main lobby, and at the east entrance of the bookstore. These elevators are equipped with the Fireman recall feature. The elevator is currently serviced by Thyssen Krupp Elevators.

Exit Routes

Basement

There are three (3) exits that lead to the outside, situated at the east (2) and west (1) ends of the floor. First Floor

There are nine (9) exits leading directly outside. They can be found at the east (4), southeast (3), and northwest (2) ends of the building. Second Floor

There are five (5) stairwells that lead directly outside. They can be found at the east (3), and west (2) ends of the building. Exit Signs are posted on each floor of the building. Roof

The roof can be accessed through a door in the penthouse mechanical room and from stairwell # 5 (in the east end of the building, Bookstore end). During power failure, exit signs will be illuminated.

Page 7: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 7 of 28

Fire Plan Location

A hard copy of the fire plan is located in a secure Fire Safety Plan box near the annunciator panel (main entrance on south side of building). An electronic copy of this Fire Plan can be obtained online at: www.uwindsor.ca/safety/fireplans. Please note that online editions of the plan do not include emergency contact numbers.

Keys

During off hours: when the alarm becomes activated, Campus Police will meet Windsor Fire & Rescue Services outside the annunciator panel entrance (main entrance on south side of building) and provide appropriate keys for access into the building as well as pertinent rooms.

Operating Hours

The Odette Building normal hours of operation are 8:30 am-4:30 p.m., Monday through Friday. However, the building is accessible 24 hours a day, 7 days a week through controlled entry.

UTILITIES & MAIN SHUTOFFS

Electricity

All building substation transformers are “dry-type”. The University’s main substation (outdoor) has oil-filled transformers; PCB free. Shut-Off Electrical Isolation 5KV Feeder, M3 Main Sub, M3M4-5 in the Computer Centre. For the Bookstore, 600V Sub feeder from Odette Electrical Sub feeder in room MB-01C. During an emergency, Campus Police will contact Facility Services to shut off electricity. Electrical services can be isolated in sections of the University campus. Annually, Health & Safety will forward an updated copy of the Electrical Distribution Building Power Sources to Windsor Fire & Rescue Services and Campus Community Police.

Heating, Ventilation, and Air Conditioning (HVAC)

There are four (4) HVAC systems located in this building. They are located as follows: HVAC System Room/Location

AHU01 MB01

AHU02 MB01

AHU03 MB03

AHU04 M302

The HVAC system in this building stays shut down on activation of the Fire Alarm System. During an emergency, Campus Police will contact Facility Services to shut down HVAC systems through Maintenance Dispatch at ext. 2850 (after hours: ECC control room at ext. 7027).

Page 8: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 8 of 28

Natural Gas

Shut-off

The natural gas/meter line enters north of Stair 1 on the west side of the building. The shut-off is also located here. Water

Shut-off

The 8” diameter domestic water supply shut-off is located in the NE corner of the basement level in mechanical room MB-02.

Natural Gas

The underground natural gas line enters the building at one (1) location on the west side of the building, north of the main entrance. Shut-off

The natural gas shut-off is located on the west side of the building, towards the north corner.

During an emergency, Campus Police will contact Facility Services to shut off natural gas.

Steam

Shut-off / Isolation

Steam Isolation: If required in an emergency, steam line isolation can be arranged by contacting Facility Services at ext. 2850, or Campus Community Police after hours at ext. 9-1-1.

Compressed Air

Compressed Air Lines: Shut-off / Isolation

If required in an emergency, compressed air isolation can be arranged by contacting Facility Services at ext. 2850, or Campus Community Police after hours at ext. 9-1-1.

Air Compressors

There are no air compressors in this building.

FIRE EMERGENCY EQUIPMENT

Annunciator Panel

YES NO The fire alarm system indicates the specific zone of the alarm at the Fire Alarm Annunciator Panel. This panel is located at the south (main) entrance, on the southwest wall of the lobby.

Page 9: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 9 of 28

Emergency Lighting

During power failure, designated lighting fixtures will be activated to ensure lamination of required means to exit the building. Battery powered Emergency lighting units and remote heads are located in the basement level mechanical areas (MB-01, MB—01B, MB-01C) Emergency Power

YES NO A Kohler Fast Response II emergency natural gas generator is located in maintenance room MB-01B. Fire Alarm

YES NO This building is equipped with a fire alarm system (Edwards 6500 II Single Stage Fire Alarm System) which has been installed in conformance with CAN/ULC S524-M, “Standard for the Installation of Fire Alarm Systems”. Activation of fire alarm can be triggered by manual pull-stations, smoke detectors, smoke duct detectors, sprinkler head activation, and electronically supervised valves for the sprinkler & standpipe systems. This fire alarm is connected to A.P.I. Alarm Inc. (1-800-268-6870) by the University’s Central Monitoring System located in Chrysler Hall. Windsor Fire & Rescue Services will be notified by A.P.I.

Fire Alarm Pull Stations

Manual pull stations as required have been installed at all required exits, and access to exits. Refer to the Floor Plans tab in this Fire Plan binder for the locations of the fire alarm pull stations.

Fire Blankets

There are no fire blankets in this building. Fire Department Connections (FDC)

YES NO The FDC(s) for this building are located on the east side of the building on California Ave., south of the NE Exit (Stair 4). Fire Extinguishing Equipment

Fire Extinguishers as required by code have been installed on the floor levels and in the mechanical/electrical rooms. Please refer to the Fire Extinguisher tab in this Fire Plan binder for a complete list of fire extinguishers and locations. See Appendix III for information on the use of fire extinguishers.

Fire Hydrants

A fire hydrant with a blue bonnet is located approximately 105’ NE of the FDC on the east building face (NE exit, Stair 4-1). A second hydrant (Blue bonnet) (Private # 25147) is located NW of Exit 104-C. A third hydrant is located on the SW corner of the intersection of Wyandotte Street West and California Avenue. These hydrants have been colour coded to the NFPA 291 standard requirement that indicates the available water flow is 1500+ gpm at 20psi.

Page 10: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 10 of 28

Fire Pump

YES NO Darling vertical in line Fire Pump 1-1/2-LA-54152-3F rated at 100gpm, located in the NE corner of the basement level in room MB-02. Heat Detectors

No heat detectors have been installed in the Odette building (See annual Fire Alarm Inspection Report) Two types are used: (1) Fixed, and (2) Fixed/Rate of Rise.

(1) Fixed detectors trigger the fire alarm when a specific temperature is reached (57oC or 92oC).

(2) Fixed/Rate of Rise detectors will activate the fire alarm upon the occurrence of two (2) factors. First, the ambient air temperature has to rise at a rate of 9.4 oC per minute or the temperature reaching 57oC or 92oC.

Hose Cabinets

YES NO

Fire hose cabinets with 100’ of hose and an adjustable nozzle are located in the building. There are six

Level No. of Hose Cabinets Location

Basement 6 MB-01, B-00, Stair 3, Stair 4, CB-01, Stair 6

1 5 106, 112, C-113, Stair 6-1

2 4 Lobby 200, 206, Stair 4-2, Stair 6-2

3 2 Stair 1-3, 324

4 2 401, 446

5 2 502, 509

6 1 M-601

Smoke Detection Equipment (Smoke Detector, Duct Smoke Detector)

Smoke detectors as required are installed in the elevator lobbies, and at the top pf the stairwells. Smoke detectors are also located on the 2nd floor (rooms 208 and 210) Refer to the Floor Plans tab in this Fire Plan binder for the locations of the smoke detection equipment. Sprinkler System

YES NO

A sprinkler system has been installed in this building. It has been installed to meet the requirements of NFPA 13, “Standard for the Installation of Sprinkler Systems”, all areas of the building are protected with this system. The sprinkler control room is located in the NE corner of the basement level in meter room MB-02). The hose cabinets in this system are supplied water via a 6” riser. Special Extinguishing System(s)

YES NO Computer labs on the second-floor level (rooms 208 and 214) are protected with a wet pre-action sprinkler system (single interlock, tripping devices smoke detectors, and manual pull stations).

Page 11: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 11 of 28

The Electrical Transformer room MB-01C located in the NW corner area of the basement level is protected with a ANSUL CO2 system (8-CO2 tanks mounted on the east exterior wall of the room)

Standpipe System

YES NO

The standpipe system has been installed in conformance with NFPA 14, “Standard for the Installation of Standpipe and Hose System”. The standpipe control room is located in the NE corner of the basement level in meter room MB-02). The hose cabinets in this system are supplied water via a 4” riser.

Smoke Control

Upon activation of the Fire Alarm System the Air Handling Units for the Odette Building will shut down.

Doors:

Fire rated doors as required are located throughout the building, rated doors as required shall not be held open by any means unless approved.

Note: closing of doors in the event of a fire is the most important precaution to take as this will prevent/minimize the vertical and horizontal spread of smoke and fire from one area to another (zone to zone).

FIRE HAZARDS

Common Hazards:

a) Combustible waste shall not be allowed to accumulate in quantities or locations that will constitute a fire hazard.

b) All means of egress (corridors, stairways, fire escapes… etc.) shall be kept free of combustible materials and obstructions

c) Smoking is only permitted in designated areas, and smoking materials shall be disposed of in approved containers.

d) Fire doors and smoke barriers shall not be wedged or blocked open. e) Fire separations** shall be inspected regularly to ensure that the integrity of the fire separation is

maintained. f) For staff who work normal business hours, at the end of the day check all electrical equipment, i.e.

coffee machines, heaters, computers, etc. to ensure they are turned off. g) All fire hazards or conditions that pose a threat to the occupants are to be reported to the Facility

Services in writing so they can be rectified. h) Identified fire routes shall be kept clear of parked vehicles and when found will be moved or towed. i) Snow and ice shall not be allowed to accumulate in such quantities that would obstruct exit doors,

evacuation routes, fire routes, fire department Siamese connections and natural gas meters. Facility Services

Special Hazards

a) Flammable liquids will not be used for cleaning purposes. b) Flammable and combustible liquids will be stored in the original manufacturers’ containers of

containers that are listed and labeled for such use.

Page 12: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 12 of 28

c) Approved containers used to store flammable liquids shall be stored in approved cabinets and

labeled “Flammable”. d) All greasy or oily rags or materials subject to spontaneous heating will be deposited in listed and

labeled approved metal receptacle. e) Open flames shall be securely supported in non-combustible holders or protected to prevent

accidental contact with combustible materials.

Electrical Hazards:

All electrical equipment must be CSA or ULC approved (Canadian Standards Association, Underwriters Laboratories of Canada) Extension cords must be for temporary use only (2.4.6.1. OFC) **Fire Separation means a construction assembly that acts as a barrier against the spread of fire and may or may not have a fire-resistance rating or a fire-protection rating.

HAZARDOUS MATERIALS

A detailed inventory of hazardous materials ordered through the Chemical Control Centre is available by contacting the Chemical Control Centre (ext. 3523 / 3524), the Manager of Environmental Health and Safety (ext. 2055), or Campus Community Police (ext. 9-1-1 for emergencies). Hazardous materials NOT obtained through Chemical Control are as follows: None.

Asbestos within building infrastructure: YES NO *Please refer to the online asbestos inventory for current asbestos inventory.

RADIOACTIVE MATERIALS

A detailed inventory, including locations of radioactive materials can be obtained by contacting the Chemical Control Centre (ext. 3523 / 3524), or the Manager of Environmental Health and Safety (ext. 2055). Annually, Health & Safety will forward an inventory of radioactive materials to Windsor Fire & Rescue Services.

SPILL RESPONSE PROCEDURES

For a complete copy of the University’s spill control procedures, please refer to the ‘Spill Procedure’ tab in this binder or reference the Spill Response Guide online at www.uwindsor.ca/ccc.

CAMPUS COMMUNITY POLICE

During a fire emergency, Campus Community Police will meet the Chief Fire Official (and Building Fire Plan Manager during business hours) outside the annunciator panel entrance of the Biology Building

Page 13: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 13 of 28

(main entrance on the west side of the building). Campus Community Police carry the necessary keys to access the building, as well as any pertinent rooms the fire department requires to enter.

FIRE EVACUATION DRILLS

General The purpose of the fire drill is to ensure that the staff and building occupants are fully familiar with emergency evacuation procedures as detailed in the Fire Safety Plan. This will result in an orderly evacuation with efficient use of exit facilities in the event of a fire emergency. Conducting effective Fire Drills will help the owner, on site property manager and designated supervisory staff as well as any other personnel that have responsibilities for fire safety in the building to:

Assess the effectiveness of the emergency procedures under various fire scenario conditions

Determine if supervisory personnel can respond and carry out their duties as outlined in the Fire Safety Plan

Determine if Supervisory personnel respond in a timely manner

Comply with the Fire Code requirements for conducting Fire Drills Fire drills are to be held once every twelve (12) months, and at intervals not greater than six (6) months for buildings with laboratories as required under the Ontario Fire Code (2.8.3).

Fire Drill Planning The conducting of fire evacuation drills is arranged and supervised by Health & Safety in co-operation with the B.F.P.M., the Facility Services maintenance department, and the Fire Prevention Division of Windsor Fire & Rescue Services. All occupants in the building are expected to participate in the fire drills. Facility Services is responsible for notifying the fire alarm monitoring company before and after the drill. Health & Safety shall forward a completed copy of the “Evacuation Drill Report” (OHS-4.7.1a, see Appendix I) to the Building Fire Plan Manager after the completion of each drill or incident. Records of a fire drill shall be kept for twelve (12) months after the fire drill. Fire Drills will be scheduled and announced in advance of the date and time to all tenants. The Fire Department and monitoring agency will be notified prior to a Comprehensive Fire Drill.

Types of Fire Drills Fire Drills that comply with the Code Requirements may be Comprehensive, Silent or table Talk drills.

Comprehensive Fire Drill:

Contact the Fire Department (Windsor Fire Dispatch 519-255-6478, Emergency 9-1-1) and the monitoring agency if applicable and notify them of the date and time of the Drill.

Page 14: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 14 of 28

Activate the Fire Alarm System ( ie: pull manual pull station) if applicable

Verify that emergency systems operate as required (ie: voice communication system, elevators, smoke control etc.)

Manager and supervisory staff carry out their assigned duties (ie: evacuating endangered/mobility impaired personnel, call 911 etc.)

Document outcomes, concerns and corrective measures

Determine degree of participation of the building occupants. Silent Drills:

Fire Alarm System is not activated (simulation only) if applicable

Manager and supervisory staff monitor individual response in the floor area of the Fire scenario

Staff/occupants in the floor area respond as per their evacuation procedures

Personnel in the area of the exercise will be notified prior to the Drill in order to avoid accidental activation of the Fire Alarm System if applicable

Document outcomes, identified concerns and corrective measures to be implemented

Table Talk Drills:

Table Talk Drills do not involve physical demonstration/simulation of the emergency response

Discussion on the Fire scenario and actions to be taken

Manager and supervisory staff and alternates facilitate discussion and monitor response of participating individuals to emergency Fire scenario(s)

Participants must describe their proposed response, these responses are assessed for adequacy and where necessary, use the opportunity to reinforce correct response expectations of Supervisory Staff

Note:

Fire Incidents and Accidental Fire Alarm System activation may be considered as a Fire Drill if permitted by the Authority Having Jurisdiction provided that a thorough analysis of the event occurs and that the responses by Supervisory Staff are assessed, outcomes are documented and corrective measures are implemented.

Training:

Supervisory Staff Management, supervisory staff and designated personnel must be instructed in the Fire Emergency Procedures as detailed in the Fire Safety Plan. Copies of duties and responsibilities will be given to the personnel.

Evacuation of mobility impaired and persons in need of assistance

Initiating smoke control measures and other life safety systems until the arrival of the Fire Department

Assist the Fire Department with access to the building and fire location

Assist with instruction of Supervisory staff and Fire Department for operation of Life Safety Systems (ie: HVAC, EVAC, elevators etc.)

Procedures to affect orderly evacuation of all customers

Resetting the Fire Alarm System when instructed to if applicable

Page 15: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 15 of 28

All personnel with specific duties/responsibilities will attend a debriefing meeting after every Fire Drill to review the procedures and reactions of participants.

Fire Drill Analysis

Responses and Outcomes:

Discovery of the Fire

Sounding the Fire Alarm (if applicable)

Notifying the Fire Department

Establishing provisions for access for Fire Fighting

Responding to the Fire Alarm (if applicable)

Evacuating mobility impaired/endangered customers

Confining, controlling and/or extinguishing the fire

Shut down of designated equipment ( ie: HVAC)

Resetting of the Fire Alarm System (if applicable)

Fire Drill Record Fire drills will be held at least once every twelve (12) months, and at intervals not greater than six (6) months for buildings with laboratories to ensure efficient execution of the Fire Safety Plan. Fire drill records are to be retained for a period of one year. The documentation should identify the date and time of the drill, persons participating, type of drill, fire drill scenario and a summary analysis of the outcome of the drill.

FIRE ALARM IMPAIRMENT

When the fire alarm system is shut off, precautions must be taken to protect all occupants in the building.

Notifications along with instructions must be posted throughout the building so individuals are aware of procedures to follow in the event of a fire. During testing, the fire alarm signals will sound intermittently. In case of a fire emergency, the fire alarm signals will sound continuously. Fire alarm impairment records are maintained electronically by Facility Services. Fire Watch Procedure

If the fire alarm system is placed out of service, Facility Services will contact the appropriate agencies, as well as Campus Community Police. A member of the Fire Evacuation Committee (or designate) will be responsible for performing a fire watch by patrolling all floors of the building. The fire watch procedure is as follows:

patrol the entire building hourly (at a minimum), on all floors

during the patrol, look for fire, smoke, and other possible fire hazards (i.e. blocked fire doors, means of egress, or extinguishers)

log the time of each patrol and sign the Fire Watch Log (OHS-4.7.1e)

SHOULD YOU DISCOVER SMOKE OR FIRE, EVACUATE THE BUILDING, NOTIFYING OCCUPANTS BY SHOUTING “FIRE, FIRE, FIRE” AND CALL CAMPUS COMMUNITY

Page 16: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 16 of 28

POLICE AT EXT. 9-1-1 FROM A SAFE LOCATION.

send completed Fire Watch Log sheets to the Building Fire Plan Manager for filing in the Fire Plan binder.

Fire Watch during regular operating hours (8:30 am – 4:30 pm)

The B.F.P.M. or designate(s) shall perform Fire Watch duties. Fire Watch Procedure (after hours)

Campus Community Police or designate(s) shall perform Fire Watch duties.

Note: Fire Watch procedures shall be implemented when any of the fire related Life Safety Systems are not in service, and signage indicating which system is out of service will be posted in the affected areas.

FIRE EMERGENCY PROCEDURES

Upon Discovering a Fire:

1. Vacate the fire area, closing doors and windows on the way out (if safe to do so).

2. Shout “FIRE, FIRE, FIRE” and activate the fire alarm pull station box, located at all building exits.

3. EXTINGUISHING THE FIRE - FIRE FIGHTING IS A VOLUNTARY ACT

In the event that the fire you discover cannot be extinguished with the use of a fire extinguisher, or smoke presents a hazard to the operator, close the door to the area to confine or contain the fire and leave the fire area per the Evacuation Process below. DO NOT attempt to extinguish fires that cannot be easily handled. Firefighting is the responsibility of the Fire Department.

Fire extinguishers may be used to extinguish small fires if it is safe to do so. Make sure to have a safe way out of the fire area, and close the door as you leave. If safe to do so, extinguish the fire following instructions on the proper use of fire extinguishers (see Appendix III). Remember the acronym “PASS” to help you extinguish the fire:

P pull the pin

A aim low at base of flame

S squeeze the lever

S sweep from side to side

If you put out a fire with a fire extinguisher, never walk on the area that you extinguished in case the fire reignites. Once the fire is extinguished, evacuate the fire area, closing doors behind you if safe to do so, and then evacuate the building per the Evacuation Process below. Ensure that information regarding the fire, no matter how small, is reported to the fire department and/or Campus Community Police at ext. 911.

Page 17: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 17 of 28

If the fire is too large to use a fire extinguisher, DO NOT fight the fire! Leave the fire area immediately, and follow steps below. Upon Hearing the Fire Alarm – Evacuation Process:

1. Stop all work and remain calm. If safe, turn off any equipment you are using if you have authority to do so.

2. The Instructor, Supervisor, or Event Organizer will take charge of the classroom / space and ensure everyone evacuates safely from their respective area.

3. Close doors and windows behind you if safe to do so. Follow directions from the Fire Wardens (wearing orange vests), as they will assume a lead role in building evacuation.

4. Evacuate the building via the nearest exit. DO NOT use elevators to evacuate the building. If you encounter smoke in a stairwell or corridor, use an alternate route. Only authorized persons (Windsor Fire & Rescue Services) shall be permitted to use the elevators during fire emergencies.

5. Move to a safe area away from the building. Wait for further instruction from Windsor Fire, Campus Community Police, and/or the Building Fire Plan Manager.

6. DO NOT re-enter the building until Windsor Fire has given the all-clear to Campus Community Police and/or the Building Fire Plan Manager.

7. The designated shelter area in the event of an extended and/or after-hours evacuation is the CAW Student Centre, which is open 24 hours.

8. Persons requiring assistance in evacuation shall implement their Personal Exit Plan. Please reference the Emergency Procedures for Persons Requiring Assistance in Evacuation at www.uwindsor.ca/safety/firesafety.

9. If you are unable to evacuate the building, move to a safe area if possible. This can include stairwells and Areas of Refuge per the building’s fire safety plan. Contact Campus Community Police to report your location and circumstance at extension 911, or extension 4444 from a mobile phone. Keep doors and windows closed, and attempt to seal vents and cracks with available materials to keep smoke out. If smoke enters the room, stay low as heat and gas tend to rise.

After-Hours Evacuation – Critical Reminders:

1. Fire wardens may not be present in the building after-hours. Therefore, when using the building after-hours it is important that building occupants are able to self-evacuate, and have access to a phone. Reference the Persons Requiring Assistance in Evacuation section below.

2. Working Alone-When working alone on campus after-hours, members of the campus community are encouraged to use the Work Alone Service offered by Campus Community Police. In the event of an emergency, Campus Community Police will be able to contact you and advise you of appropriate procedures to follow. For more information on the Work Alone Service, please visit the Campus Community Police website at: www.uwindsor.ca/campuspolice/workalone-service

Page 18: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 18 of 28

UWindsor Alert Emergency Notification System

The University’s campus emergency notification system, called UWindsorAlert, enables fast and efficient distribution of critical information to members of the University community during a major emergency. The system sends messages simultaneously through email, text, voicemail, and other registered devices. Campus Community Police encourages all members of the campus community to register with UWindsor Alert at www.uwindsor.ca/alert in order to receive these emergency notifications.

Page 19: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 19 of 28

Persons Requiring Assistance in Evacuation

Person(s) Requiring Assistance is defined as:

a person who is unable to leave a building unassisted under emergency conditions. This may include persons with temporary or permanent mobility disabilities (e.g. use of crutches, walkers, wheelchairs), with hearing or vision disabilities, as well as persons who may be immobilized due to distress. University students and staff who require assistance to evacuate a building shall discuss a Personal Exit Plan with their Supervisor or Instructor. Monitors may be assigned to assist with evacuation (see Monitors responsibilities section below). University guests who may require assistance in evacuation are responsible to check-in with appropriate building staff. For more information, please reference the Emergency Procedures for Persons Requiring Assistance in Evacuation page at www.uwindsor.ca/safety/firesafety.

Emergency Procedures for Persons Requiring Assistance in Evacuation When a Fire Alarm Sounds:

Ground Level:

Evacuate the building and move to a safe area away from the building to await further instruction from emergency responders.

Above or Below Ground Floor:

Evacuate as per the Personal Exit Plan, or seek a safe area. This can include stairwells and Areas of Refuge. Reference the building’s Fire Safety Plan for information on the building’s safe areas.

During business hours:

The building’s Fire Wardens perform sweeps of each floor and stairwell upon evacuation. If they are not able to assist you to evacuate, they will note your location, floor and stairwell and will notify emergency responders of your need for assistance.

After-hours:

Fire Wardens may not be present in the building after-hours. Therefore, when using the building after-hours it is important that you are able to self-evacuate and have access to a phone.

If you are not able to self-evacuate:

1. Contact Campus Community Police (ext. 911 from a University phone, or 519-253-3000 ext. 4444

from a mobile phone) Dialing 911 from a mobile phone will connect to the external 911 service.

2. Notify dispatcher of your building location, circumstance and intentions. Provide the dispatcher

with your phone number to receive updates.

3. Campus Community Police have radio contact with emergency responders at the scene and will

provide you with updates on the situation where possible. In the event your safety could be

compromised, firefighters will assist in your safe evacuation.

Notify building staff and/or emergency responders once you have evacuated the building. The actions to be taken by occupants in emergency situations will be posted at each required exit. An example is provided.

Page 20: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 20 of 28

2.8.2.5.(1) At least one copy of the fire emergency procedures shall be prominently posted and maintained on each floor area.

o Vacate the fire area and close doors on the way out

o Pull the closest fire alarm (located at all exits) and shout “FIRE, FIRE, FIRE”

o Do not attempt to extinguish a fire unless you are sure it is safe to do so

o Dial ext. 9-1-1 from a safe location

o If safe to do so, turn off any equipment you are using, close doors and windows

o Evacuate the building in an orderly manner by walking to the nearest exit

o DO NOT USE ELEVATORS

o Move away from the exits once outside. Do not re-enter the building until the

all clear has been given by the Building Fire Plan Manager.

o If you are unable to leave due to fire conditions or a disability, call ext.

9-1-1 and give your location. Keep doors and windows closed, and

attempt to seal vents and cracks with available materials to keep

smoke out.

DUTIES & RESPONSIBILITIES

Appointment of Staff

The University of Windsor and/or their representatives have designated the Fire Evacuation Committee to act as the responder in the event of a Fire Emergency and to carry out all required duties as outlined in the Fire Safety Plan. 1

CAMPUS EMERGENCIES EXT. 9-1-1

UPON HEARING FIRE ALARM:

IF YOU DISCOVER FIRE OR SMOKE:

OHS-4.7.1c Emergency Evacuation Posting Rev: 5/23/14

Page 21: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 21 of 28

The University of Windsor and/or their representatives shall arrange for annual training of designated staff2 in their duties and responsibilities under the Fire Safety Plan and each shall receive a copy of their responsibilities and duties3. In addition, designated staff shall be trained in the operation of all emergency systems in the building. The University of Windsor and/or their representatives shall arrange for training for all new designates, prior to giving them any responsibility for Fire Safety as well as ensuring the fire safety plan is kept up to date. University of Windsor Duties & Responsibilities

The University of Windsor and/or their representative are responsible for the building and operations as well as being responsible for:

a) Ensuring a fire safety plan is developed, approved and fully implemented.

b) Maintaining control and currency of the fire safety plan once approved.

c) Posting emergency procedures in each floor area.

d) Ensuring that a detailed list of specific responsibilities is provided to staff.

e) Maintaining a list of mobility impaired (See: “Persons Requiring Assistance in Evacuation”) 5.

f) Providing assistance as required to mobility impaired occupants.

g) Ensuring that fire drills involving all staff / occupants are held annually (Every 12 months) 4.

h) Providing training for staff on the Fire Safety equipment on site (use of portable extinguishers).

i) Maintaining adequate records of fire drills for future reference.

j) Ensuring the fire department has been called on activation of the fire alarm system.

k) Ensuring that arriving fire fighters have access, and are provided with keys to the building.

l) Controlling of fire hazards in the building.

m) Maintenance of building facilities provided for safety of the occupants.

n) Provisions of alternate measures for safety of occupants during shut down of fire protection

equipment.

o) Assuring that checks, tests and inspections as required by the Ontario Fire Code are completed

on schedule and that records of tests are retained for (2) years.

p) Notification of the Chief Fire Official regarding changes in the fire safety plan.

In the event of a fire emergency or a hazardous chemical release / spill, the University of Windsor shall activate the University of Windsor’s Emergency Response Plan.

To prevent fires, the University of Windsor shall conduct the following general duties:

a) Ensure the Fire Safety Plans are kept current, including annual updates.

b) Ensure that the members of the Fire Evacuation Committee are knowledgeable in the conducting of their duties as detailed in the University’s Fire Safety Plans.

Fire Evacuation Committee Members

The Fire Evacuation Committee, in conjunction with Health & Safety, shall meet at least once annually to review:

the building fire safety plan;

roles and responsibilities of the Fire Evacuation Committee; and

Page 22: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 22 of 28

any evacuation equipment and/or devices that are found within the building.

The Fire Evacuation Committee Meeting/Training form can be used to document this annual review.

The building’s Fire Evacuation Committee is comprised of the following members:

Building Fire Plan Manager (B.F.P.M.)

Fire Warden(s)

Traffic Officer(s)

Monitors (if applicable)

The current member listing of the Fire Evacuation Committee for this building can be found under the “Evacuation Plans” tab of the Fire Plan binder and online at: www.uwindsor.ca/safety/firecommittees.

The roles and responsibilities of each Fire Evacuation Committee member are defined below. Duties are also outlined for the evacuation of classrooms and special events.

Building Fire Plan Manager Duties

The Building Fire Plan Manager is in charge of overseeing the emergency evacuation from the point where the alarm is activated until emergency services arrive.

When the Fire Alarm Sounds:

a) proceed to the fire alarm annunciator panel at the main floor entrance wearing the orange vest;

b) ensure that evacuation of building has commenced;

c) ensure that appropriate emergency services have been notified;

d) gather and record all incoming information from the Fire Wardens on the progress of the evacuation, the location of injured or trapped occupants and of evacuees needing assistance;

e) gather and record all incoming information on the location and extent of the fire.

When the Windsor FIRE & RESCUE SERVICES Arrives:

a) liaise with the Fire Department upon their arrival;

b) explain nature of the emergency, the location and extent of the fire;

c) explain the progress of the evacuation, the location of injured or trapped occupants and of evacuees needing assistance;

d) provide any other information as requested by Windsor Fire & Rescue Services

General Responsibilities:

a) be familiar with the Emergency Evacuation Procedures and promote fire safety awareness among the building occupants;

Page 23: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 23 of 28

b) assist with instructing Fire Wardens in Emergency Evacuation Procedures before they are given

any responsibility for fire safety.

c) when advised, ensure Fire Wardens keep records of persons requiring assistance in the building and the designated persons (monitors) responsible for their evacuation.

d) be aware of:

fire safety procedures and practices;

fire and safety notices and information bulletins;

the location of pull stations and fire extinguishing equipment within the building.

e) attend applicable training sessions or meetings as required

f) ensure any incorrect information in the building fire plans is forwarded to Health & Safety.

g) Health and Safety will forward a completed copy of “Evacuation Drill Report” (See Appendix I) to the B.F.P.M. after the completion of each drill or incident.

Page 24: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 24 of 28

Fire Warden Duties

Fire Wardens are responsible for the evacuation of individual workplaces or areas of a workplace. The role of fire wardens is to ensure the safety of occupants and their orderly evacuation from the building, NOT TO combat fire and emergencies.

When the Fire Alarm Sounds:

a) in pre-assigned area: shout “FIRE, FIRE, FIRE” and instruct all persons to leave building;

b) wearing the orange vest, check the exit stairwells to see that they are clear for evacuation, and choose an alternate route should egress be blocked by fire or smoke;

c) direct the flow of people to the nearest and safest exit;

d) advise the evacuees NOT TO use the elevators;

e) ensure the Personal Exit Plan for persons requiring assistance is executed;

f) knock on any closed doors in your area after checking for warmth or smoke, and attempt to open the door to ensure proper evacuation of all personnel. Check washrooms, lunch, mail, and copy rooms last, and advise occupants in these areas to leave immediately;

g) Do not remain or argue with persons refusing to leave. Note the person’s name and location and report the matter to the Building Fire Plan Manager;

h) close all doors, if safe to do so;

i) when possible, assist all injured evacuees to ground level exits if safe to do so;

j) ensure all persons have evacuated the building(s); and

k) report to the assigned Building Fire Plan Manager:

the progress of the evacuation;

the location of injured or trapped occupants and of the evacuees needing assistance;

the location and extent of the fire; and

the names and/or room numbers of individuals who caused any problems.

when possible, report any further information and/or comments to the Building Fire Plan Manager, Campus Community Police, or Windsor Fire & Rescue Services.

General Responsibilities:

a) be familiar with the Emergency Evacuation Procedures and promote fire safety awareness among the building occupants;

b) participate in training on Emergency Evacuation Procedures by the B.F.P.M. or Health & Safety before being given any responsibility for fire safety;

c) be aware of:

fire and safety notices and information bulletins;

Page 25: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 25 of 28

the location of pull stations and fire extinguishing equipment within the building;

fire safety procedures and practices on a day-to-day basis, such as:

o accumulation of combustible material, rubbish or flammable liquids

o dangerous ignition sources, i.e. worn extension cords, oily rags, overheating equipment

o exit lights in good order and adequate lighting in public corridors and stairwells

o fire and exit doors and their self-closing hardware in good operating condition (doors should not be wedged under any conditions.)

o fire hose and portable extinguishers not obstructed, in good order and ready to use

o exit routes are unobstructed

d) advise the Building Fire Plan Manager or Health & Safety of any potential fire hazards;

e) attend applicable training sessions or meetings as required

Traffic Officer Duties

Traffic Officers are in charge of guarding re-entrance into the building during emergencies.

When the Fire Alarm Sounds:

a) proceed directly to designated area, outside of building, wearing the orange vest.

b) direct occupants away to ensure the entrance is free of people and to facilitate fire department operations.

c) DO NOT allow anyone to go back in the building under any circumstances until Windsor Fire, Campus Community Police, or the Building Fire Plan Manager has given permission to do so.

General Responsibilities:

a) be familiar with the Emergency Evacuation Procedures and promote fire safety awareness among the building occupants;

b) participate in training on Emergency Evacuation Procedures by the B.F.P.M. or Health & Safety before being given any responsibility for fire safety;

c) be aware of:

fire safety procedures and practices;

fire and safety notices and information bulletins;

the location of pull stations and fire extinguishing equipment within the building;

Page 26: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 26 of 28

d) advise the Building Fire Plan Manager or Health & Safety of any potential fire hazards.

e) attend applicable training sessions or meetings as required

Monitor Duties

Monitors are pre-assigned to aid persons requiring assistance to safety during an emergency.

When the fire alarm sounds:

a) help persons requiring assistance to evacuate the building per their Personal Exit Plan.

b) if physically unable to evacuate the person requiring assistance, notify emergency response personnel of the person’s location. DO NOT use the elevator.

c) Unless imminent life-threatening conditions exist in the area occupied by a person requiring assistance, relocation of the individual should be limited to a safe area on the same floor, in proximity to an evacuation stairwell.

General Responsibilities:

a) be familiar with the Emergency Evacuation Procedures and promote fire safety awareness among the building occupants;

b) participate in training on Emergency Evacuation Procedures by the B.F.P.M. or Health & Safety before being given any responsibility for fire safety;

c) be aware of:

fire safety procedures and practices;

fire and safety notices and information bulletins;

the location of pull stations and fire extinguishing equipment within the building;

d) advise the Building Fire Plan Manager or Health & Safety of any potential fire hazards.

e) attend applicable training sessions or meetings as required

More information can be found at www.uwindsor.ca/safety/firesafety, including the reference document “Emergency Procedures for Persons Requiring Assistance in Evacuation”.

Instructor Duties

Instructors are responsible to evacuate the classroom and have students exit the building as quickly and safely as possible.

General Responsibilities:

At the beginning of each new semester, Instructors shall:

review evacuation routes from your classroom and the location of stairwells;

Page 27: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 27 of 28

ensure that all aisle ways and exits are kept clear during lectures;

advise students that:

o copies of evacuation instructions are available at www.uwindsor.ca/emergency.

o classroom evacuation instructions are posted inside the classrooms.

Any questions regarding Personal Exit Plans for students requiring assistance in evacuation can be referred to the Emergency Response Coordinator or Student Success Centre - Disability Services. Please refer to the Emergency Procedures for Persons Requiring Assistance in Evacuation document at: www.uwindsor.ca/safety/firesafety

When the fire alarm sounds:

a) Direct students to vacate the building in a calm, orderly fashion leaving through the nearest exit and to assemble away from the building;

b) Should a student within your class require assistance please attempt to recruit volunteer help. If

this is not possible, please notify emergency personnel of the location of the student(s) through:

Building Fire Evacuation Committee members identified in orange vests (if present)

extension 9-1-1 (internal Campus Community Police dispatch via campus phone) or 911

from a mobile phone (external service);

c) Ensure classroom occupants have moved to safe area away from the building;

d) During an alarm after-hours, ensure appropriate emergency services have been notified (Campus

Community Police at ext. 911 or Windsor Fire at 9-1-1 from a mobile phone). Provide the location

of fire, your name and answer any questions asked by the dispatcher.

When emergency services arrive:

Provide any known information on the evacuation status, nature of the emergency, any injured occupants or persons requiring assistance, or location of anyone in the building who refused to evacuate.

Wait for further instruction from Windsor Fire & Rescue Services and/or Campus Community Police

DO NOT let classroom occupants back into the building until Windsor Fire and/or Campus Community Police declares it safe to do so.

The designated meeting area in the event of an extended and/or after-hours evacuation is the CAW Student Centre, which is open 24 hours.

Event Organizer Duties

An Event Organizer is defined as the person who schedules and plans a special event on campus,

including conferences, meetings, activities, functions, and other social events.

Event Organizers are responsible:

Page 28: FIRE SAFETY PLANS

Odette School of Business Fire Safety Plan

580 Sunset Avenue

Effective: Feb. 05,2017 Revision: Issued by: Health & Safety Page 28 of 28

to be familiar with Emergency Evacuation Procedures, including the posted evacuation routes;

during the special event, to evacuate the event space and have event patrons exit the building as

quickly and safely as possible

When planning a special event:

The Event Organizer shall assign an appropriate number of event staff/volunteers to assist with evacuation and patrons requiring assistance to evacuate the building. All staff/volunteers assigned to assist with evacuation must be trained in their roles and responsibilities in the event of a fire alarm. For large events, or when an event is being held in a space not intended for continuous occupancy (ie. part of an egress route or corridor), a plan must be submitted to Health and Safety in advance of the event for approval from Windsor Fire Department. Please contact Health and Safety for more information on this process, or visit www.uwindsor.ca/safety/fspspecialevents.

When the fire alarm sounds:

The Event Organizer will take charge of the classroom / event space, and ensure:

Event patrons evacuate safely;

Event patrons have moved to a safe area away from the building;

During an alarm after-hours, that appropriate emergency services have been notified (Campus Community Police at ext. 911 or Windsor Fire at 9-1-1 from a mobile phone). Provide the location of fire, your name and answer any questions asked by the dispatcher.

When emergency services arrive:

Wait for further instruction from Windsor Fire & Rescue Services and/or Campus Community Police.

Provide any known information on the evacuation status, nature of the emergency, any injured occupants or persons requiring assistance, or location of anyone in the building who refused to evacuate.

DO NOT let event patrons back into the building until Windsor Fire and/or Campus Community Police declares it safe to do so.

The designated meeting area in the event of an extended and/or after-hours evacuation is the CAW Student Centre, which is open 24 hours.


Recommended