+ All Categories
Home > Documents > Fire Severity Design Notes (NRC)

Fire Severity Design Notes (NRC)

Date post: 06-Mar-2016
Category:
Upload: clubberlangpcf
View: 11 times
Download: 1 times
Share this document with a friend
Description:
Fire severity calculations

of 12

Transcript
  • 1Winter 2003 Fire Severity 1

    FIRE SEVERITY

    Winter 2003 Fire Severity 3-2

    OVERVIEW

    This section will: provide an overview of basic methods for designing

    structures for fire safety describe methods for quantifying the severity of post-

    flashover fires for comparison with fire resistance describe the standard fire used for fire resistance testing describe the concept of equivalent fire severity which is

    used to compare real fires with standard fires

    Winter 2003 Fire Severity 3-3

    FIRE SEVERITY AND FIRE RESISTANCE

    Verification Fire Exposure Models Design Combinations

    Winter 2003 Fire Severity 3-4

    Verification

    The fundamental step in designing structures for fire safety is to verify that the fire resistance of the structure is greater than the severity of the fire to which the structure is exposed, i.e.,

    Fire resistance Fire severity

    Fire resistance is the ability of the structure to resist collapse or fire spread during exposure to a fire of specified severity

    Winter 2003 Fire Severity 3-5

    Verification

    Fire severity is a measure of: the destructive impact of a fire, or the forces or temperatures that may cause collapse or

    fire spread as a result of a fire

    Below is a table showing methods for comparing fire severity with fire resistance

    Winter 2003 Fire Severity 3-6

    Verification

    Methods for comparing fire severity with fire resistance

    Domain Units Fire Resistance Fire SeverityTime minutes or hours Time to failure Fire duration as calculated or

    specified by codesTemperature C Temperature to cause

    failure Maximum temperature reachedduring the fire

    Strength kN or kN-m Load capacity at elevatedtemperature

    Applied load during the fire

  • 2Winter 2003 Fire Severity 3-7

    Verification

    The verification may be in the: time domain temperature domain strength domain

    Winter 2003 Fire Severity 3-8

    Verification - Time domain

    The most common verification is comparing fire severity and fire resistance in time domain, i.e.:

    tfail ts tfail is the time to failure of a building element,

    usually a fire-resistance rating ts is the fire duration or fire severity, usually a

    time of standard fire exposure or an equivalent time of standard fire exposure calculated for a real fire in a building

    Winter 2003 Fire Severity 3-9

    Verification - Temperature domain

    Sometimes, verification of design is in the temp. domain, i.e.:

    Tfail Tmax Tfail is the temp. which would cause failure of

    building elements (thermal or structural failure) Tmax is the maximum temp. reached in building

    elements during a fire or the temp. at a certain time specified by codes

    Winter 2003 Fire Severity 3-10

    Verification - Temperature domain

    Temperatures in elements can be calculated by thermal analyses of assemblies exposed to fire

    For barriers, failure temp. is the unexposed side temp. causing fire spread to other areas

    For structural elements, temp. causing collapse can be calculated based on loads on elements and elevated temp. effect on material properties

    Temperature domain is more suitable for barriers than structural elements

    Winter 2003 Fire Severity 3-11

    Verification - Strength domain

    Verifying strength domain is comparing applied loads at the time of fire with the load capacity of structural members throughout the fire, i.e.:

    Rf Uf Rf is the minimum load capacity reached during a

    fire or the load capacity at a certain time specified by codes

    Uf is the applied load at the time of a fire

    Winter 2003 Fire Severity 3-12

    Verification - Strength domain

    The load values may be expressed in units of: force and resistance for the whole building internal member actions such as axial force or bending

    moment in individual structural members Load capacity in a fire can be calculated using

    thermal and structural analyses at high temp., (limited structural tests available for full burnouts)

    Loads at the time of a fire can be calculated using load combinations from national building codes

  • 3Winter 2003 Fire Severity 3-13

    Verification - Example

    Behaviour of a steel beam in fire(a) temperature increase (b) loss of strength

    Winter 2003 Fire Severity 3-14

    Verification - Example

    Figure (a) shows the time-temperature of a steel beam during fire exposure

    Calculations indicate the beam failing at time tfailwhen the steel temperature reaches Tfail

    The code requires a fire resistance or required fire severity of tcode for the beam

    Winter 2003 Fire Severity 3-15

    Verification - Example

    Verifying time domain (check 1 - Figure (a)):time to failure tfail fire severity tcode

    Verifying temp. domain (check 2 - Figure (a)):steel temperature causing failure Tfail Tcodetemperature reached in the beam at time tcode

    Checks 1 & 2 give the same results since they are based on the same process

    Winter 2003 Fire Severity 3-16

    Verification - Example

    Figure (b) shows the load capacity of the same steel beam during the fire

    Applied load at the time of the fire is Uf Load capacity before the fire is Rcold, which

    decreases during the fire Load capacity of the beam reduces to Rcode at

    tcode Verifying strength domain (check 3 - Figure (b)):

    Rcode Uf at time tcode

    Winter 2003 Fire Severity 3-17

    Fire Exposure ModelsFire models and structural response models

    Winter 2003 Fire Severity 3-18

    Fire Exposure Models

    The Figure shows a range of design situations The first column shows three fire exposure

    models representing three different design fires Fire exposure H1 (most common) represents a

    standard test fire exposure for a specified period of time, tcode given by a prescriptive code

    Prescriptive codes specify required fire resistance (30 min to 4 hrs), no reference to the fire severity

  • 4Winter 2003 Fire Severity 3-19

    Fire Exposure Models

    Fire exposure H2 represents a modified duration of exposure to the standard test fire

    The equivalent time, te is the exposure time to the standard test fire considered to be equivalent to a complete burnout of a real fire in the same room (equivalent fire severity)

    Performance-based codes allow the use of time equivalent formulae to improve on simple prescriptive fire-resistance requirements

    Winter 2003 Fire Severity 3-20

    Fire Exposure Models

    Fire exposure H3 represents a realistic fire that occurs in a room with complete burnout and no fire suppression - for example Swedish curves

    The figure also shows that the fire resistance may be assessed considering a single element, a sub-assembly or a whole structure

    For each category, the method of assessment is indicated - testing or calculation

    Winter 2003 Fire Severity 3-21

    Design Combinations

    Many design combinations are possible and therefore it is essential for designers to specify clearly the combination that will be used

    The Table below illustrates the most common combinations

    In very general terms, both the accuracy of the prediction and the amount of calculation effort increase downwards in the table

    Winter 2003 Fire Severity 3-22

    Design Combinations

    Design combinations for verifying fire resistance

    Combination Fire exposure model Assessment of fireresistance

    Verificationdomain

    1 Prescriptive code(H1)

    Listed rating orcalculation

    Time

    2 Time-equivalent formula(H2)

    Listed rating orcalculation

    Time

    3 Predicted real fire(H3)

    Calculation Temperature orstrength

    Winter 2003 Fire Severity 3-23

    FIRE SEVERITY

    Fire severity is a measure of the destructive potential of a fire

    Fire severity is usually defined as the period of exposure to the standard test fire, but this is not appropriate for real fires which are different

    In prescriptive codes, the design of fire severity is usually prescribed

    In performance-based codes, the design fire severity is usually a complete burnout fire or the equivalent time of a complete burnout fire

    Winter 2003 Fire Severity 3-24

    FIRE SEVERITY

    The equivalent time of a complete burnout is the time of exposure to a standard test fire that results in an equivalent impact on an element

    Damage to a structure is mainly dependent on the heat absorbed by the structural elements

    The severity of a fire is mainly dependent on the level and duration of the high temperatures

  • 5Winter 2003 Fire Severity 3-25

    STANDARD FIRE

    Fire performance of building elements is assessed using full-size fire resistance tests

    Time-temperature curves used in fire resistance tests is called the 'standard fire'

    The most widely used test specifications are: ASTM E 119 and CAN/ULC-S101-M89 (North America) ISO 834 (International) British Standard BS 476 Parts 20-23 Australian Standard AS 1530 Part 4

    Winter 2003 Fire Severity 3-26

    Time-temperature CurvesStandard time-temperature curves

    Winter 2003 Fire Severity 3-27

    Time-temperature Curves

    The figure shows standard time-temperature curves for ASTM E 119 (ULC-S101), ISO 834, Eurocode (EC1)

    ASTM E 119 and ISO 834 curves are similar (this is true for most international standards curves)

    ISO 834 specifies the temperature T (C) as:T = 345 log10 (8t+1) + To

    t is the time (min), To is the ambient temp. (C)

    Winter 2003 Fire Severity 3-28

    Time-temperature Curves

    ASTM E 119 curve is defined by a number of discrete points

    The following is an approximate equation of the ASTM E119 curve for temperature T (C) as:

    T = 750[1 - e-3.79553 t] + 170.41 t + To t is the time (hours), To is the ambient temp. (C)

    Winter 2003 Fire Severity 3-29

    Time-temperature Curves

    The following table shows temperature values for ASTM E119 and ISO 834

    Time(minutes)

    ASTM EI19Temperature (C)

    ISO 834Temperature (C)

    0 20 205 538 57610 704 67830 843 84260 927 945120 1010 1049240 1093 1153480 1260 1257

    Winter 2003 Fire Severity 3-30

    Time-temperature Curves

    The Eurocode hydrocarbon fire curve is intended for use where a structural member is engulfed in flames from a large pool fire

    The temperature T (C) in the hydrocarbon fire curve is given by:

    T = 1080(1 - 0.325e-0.167t - 0.675e-2.5t)+ To t is the time (min), To is the ambient temp. (C)

  • 6Winter 2003 Fire Severity 3-31

    Time-temperature Curves

    The other Eurocode curve (lower temperatures) is intended for designing external structural members located outside a burning compartment

    The temperature T (C) for this fire is given by: T = 660(1 - 0.687e-0.32t - 0.313e-3.8t) + To

    t is the time (min), To is the ambient temp. (C)

    Winter 2003 Fire Severity 3-32

    Furnace Parameters

    Fire severity depends on the testing furnace characteristics

    Two similarly-operated furnaces may not impact test specimens with the same fire severity

    Temperatures are not always uniform throughout the furnace (may severely impact test specimens)

    Even with similar curves, tests can be considered to give only roughly equivalent thermal exposure

    Winter 2003 Fire Severity 3-33

    Furnace Parameters

    Thermocouple measurements may be different from one furnace to another

    Temp. differences are most significant during the first 5 minutes of the tests

    Significant differences may exist between heating conditions in various furnaces, depending on the furnace size, fuel type and furnace lining material

    These differences affect the heat transfer to the furnace walls and to the test specimens

    Winter 2003 Fire Severity 3-34

    Furnace Parameters

    Most common wall lining materials are fire bricks or ceramic fibre blankets, which have different thermal properties, hence different rates of heat transfer to the test specimens

    Temperatures increase less rapidly in furnaces lined with bricks

    Winter 2003 Fire Severity 3-35

    EQUIVALENT FIRE SEVERITY

    Real Fire Exposure Equal Area Concept Maximum Temperature Concept Minimum Load Capacity Concept Time-equivalent formulae

    Winter 2003 Fire Severity 3-36

    Real Fire Exposure

    The equivalent fire severity is a concept used to relate the severity of an expected real fire to the standard test fire

    This relation is important for designers who want to use published fire-resistance ratings from standard tests with estimates of real fire exposure

    Below is a description of the methods comparing real fires to the standard test fire

  • 7Winter 2003 Fire Severity 3-37

    Equal Area Concept

    Ingberg (1928) introduced the equivalency concept by stating that two fires have equivalent severity if areas under each time-temp. curve are equal

    The figure below shows the concept The concept is not theoretically sound Although inadequate, the concept was used as a

    crude method of comparing fires

    Winter 2003 Fire Severity 3-38

    Equal Area Concept

    Equivalent fire severity on equal area basis

    Winter 2003 Fire Severity 3-39

    Equal Area Concept The equal area concept is used to correct results

    of standard fire-resistance tests if the standard curve is not exactly followed within tolerances

    A problem with the equal area concept is that it can give a poor comparison of heat transfer for fires with different shaped time-temp. curves

    Babrauskas and Williamson (1978) commented that there could be a big difference between a short hot fire and a longer cool fire

    Winter 2003 Fire Severity 3-40

    Maximum Temperature Concept

    This is a more realistic concept, developed by Law (1971), Pettersson et al. (1976) and others

    The concept defines the equivalent fire severity as the time of exposure to the standard fire that would result in the same maximum temperature in a protected steel member as would occur in a complete burnout of the fire compartment

    The following figure shows the concept

    Winter 2003 Fire Severity 3-41

    Maximum Temperature Concept

    Equivalent fire severity on temperature basis

    Winter 2003 Fire Severity 3-42

    Maximum Temperature Concept

    The figure compares temp. in a protected steel beam exposed to a standard fire with those when the same beam is exposed to a particular real fire

    This concept is applicable to insulating elements when the temp. on the unexposed

    face is used instead of the steel temp. materials which have a limiting temp. such as the 300C

    temperature of charring onset of wood

  • 8Winter 2003 Fire Severity 3-43

    Maximum Temperature Concept

    The maximum temp. concept is commonly used The concept may be misleading when maximum

    temp. used in the derivation of a time-equivalent formula are: greater than those causing failure in a building lower than those causing failure in a building

    Winter 2003 Fire Severity 3-44

    Minimum Load Capacity Concept

    The minimum load capacity concept is similar to the maximum temperature concept

    In this concept, the equivalent fire severity is the time of exposure to a standard fire resulting in the same load bearing capacity as the minimum that would occur in a complete burnout of a compartment

    The following figure shows the concept

    Winter 2003 Fire Severity 3-45

    Minimum Load Capacity Concept

    Equivalent fire severity on load capacity basis

    Winter 2003 Fire Severity 3-46

    Minimum Load Capacity Concept

    The Figure shows the load bearing capacity of a structural member exposed to a standard fire decreases continuously

    The strength of the same member exposed to a real fire increases after the fire enters the decay period and the steel temperatures decrease

    Winter 2003 Fire Severity 3-47

    Minimum Load Capacity Concept

    The concept is the most realistic time equivalent concept for the design of load bearing members

    However, the concept is difficult to apply for a material which does not show a well defined minimum load capacity

    For example, wood members where charring can continue after fire temperatures start to decrease

    Winter 2003 Fire Severity 3-48

    Time-equivalent formulae

    Based on the maximum temp. concept, many empirical time-equivalent formulae have been developed

    These formulae are based on maximum temp. of protected steel members exposed to real fires and include: CIB formula Law formula Eurocode formula

  • 9Winter 2003 Fire Severity 3-49

    Time-equivalent formulae -CIB formula

    Widely used time equivalent formula (published by CIB W14 group (CIB, 1986)

    Formula derived by Pettersson (1973) based on the ventilation parameters of the compartment and the fuel load

    Winter 2003 Fire Severity 3-50

    Time-equivalent formulae -CIB formula

    The equivalent time of exposure to an ISO 834 fire test te (min) is given by:

    te = kc w ef ef is the fuel load (MJ/m2 of floor area) kc is a parameter to account for different linings

    of the compartment

    Winter 2003 Fire Severity 3-51

    Time-equivalent formulae -CIB formula

    w is the ventilation factor (m-0.25) given by: w = Af / Av At Hv

    Af is the floor area of the compartment (m2) Av is the total area of openings in the walls (m2) At is the total area of the internal bounding

    surfaces of the compartment (m2) Hv is the height of the windows (m)

    Winter 2003 Fire Severity 3-52

    Time-equivalent formulae -Law formula

    Similar to CIB formula, Law developed a formula based on tests in small-scale and large-scale compartments

    The formula is given by:

    te = Af ef / Hc Av (At Av) Hc is the calorific value of the fuel (MJ/kg)

    Winter 2003 Fire Severity 3-53

    Time-equivalent formulae -CIB/Law formulae

    CIB and Law formulae are only valid for compartments with vertical openings in the walls

    CIB and Law formulae cannot be applied to rooms with openings in the roof

    CIB and Law formulae give, in general, similar results (Law formula predicts slightly larger values)

    Winter 2003 Fire Severity 3-54

    Time-equivalent formulae -Eurocode formula

    Eurocode (1994) formula is a modification of CIB and Law formulae

    The formula give te (minutes) as: te = kb w ef

    kb replaces kc in CIB formula and the ventilation factor w is altered to allow for horizontal roof openings

  • 10

    Winter 2003 Fire Severity 3-55

    Time-equivalent formulae -Eurocode formula

    The ventilation factor is given by:w = (6.0/Hr)0.3[0.62+90(0.4-v)4/(1+bv h)] > 0.5

    v = Av / Af (0.05 v 0.25)h = Ah / Af (h 0.20)bv = 12.5 (1 + 10v - v2)

    Winter 2003 Fire Severity 3-56

    Time-equivalent formulae -Eurocode formula

    Hr is the compartment ceiling height (m) Af is the floor area of the compartment (m2) Av is the area of vertical openings in walls (m2) Ah is the area of horizontal openings in roofs (m2)

    Winter 2003 Fire Severity 3-57

    Time-equivalent formulae -CIB/Eurocode formulae

    The Eurocode formula comes from an empirical analysis of calculated steel temperatures in a large number of fires

    An important difference from the CIB formula is that the Eurocode equivalent time is independent of opening height, but depends on the ceiling height of the compartment

    Winter 2003 Fire Severity 3-58

    Time-equivalent formulae -CIB/Eurocode formulae

    The two formulae can give different results for the same room geometry

    The two formulae give similar results for small compartments with tall windows

    The Eurocode formula gives much lower fire severity values for large compartments with tall ceilings and low window heights

    Winter 2003 Fire Severity 3-59

    Time-equivalent formulae -CIB/Eurocode formulae

    Values of kc and kb are given in the table below Values of kc and kb depend on materials of the

    compartment The general case is used for compartments with

    unknown materials kc and kb have slightly different values and units

    because of the different ventilation factors in the respective formulae

    Winter 2003 Fire Severity 3-60

    Time-equivalent formulae

    The table below gives values of kc or kb in the time equivalent formulae

    k is thermal conductivity (W/m-K), is density (kg/m3), cp is specific heat (J/kg-K)

    b = ( k cp)High Medium Low

    Formula Term Units > 2500 720-2500 < 720 GeneralCIB WI4 kc min m2.25/MJ 0.05 0.07 0.09 0.10Eurocode kb min m2/MJ 0.04 0.055 0.07 0.07Large compartments kb min m2/MJ 0.05 0.07 0.09 0.09

  • 11

    Winter 2003 Fire Severity 3-61

    WORKED EXAMPLE 1

    Calculate the equivalent fire severity using the Eurocode formula for a room 4.0 m x 6.0 m in area, 3.0 m high, with one window 3.0 m wide and 2.0 m high. The fire load is 800 MJ/m2 floor area. The room is constructed from concrete.

    Length of room: l1 = 6.0 m Width of room: l2 = 4.0 m Floor area: Af = l1 x l2 = 6.0 x 4.0 = 24.0 m2

    Winter 2003 Fire Severity 3-62

    WORKED EXAMPLE 1

    Height of room: Hr = 3.0 m Fuel load energy density: ef = 800 MJ/m2

    For concrete Thermal conductivity: k = 1.6 W/m-K Density: = 2200 kg/m3 Specific heat: cp = 880 J/kg-K Thermal inertia: kcp = 1760 Ws0.5/m2K (medium)

    Winter 2003 Fire Severity 3-63

    WORKED EXAMPLE 1 Conversion factor: kb = 0.055 Window height: Hv = 2.0 m Window width: B = 3.0 m Window area: Av = Hv B = 2.0 x 3.0 = 6.0 m2

    Horizontal vent area:Ah = 0 (no ceiling opening) v = Av / Af = 6.0/24.0 = 0.25 h = Ah / Af = 0 bv = 12.5(1 + 10v - v2) = 43.0

    Winter 2003 Fire Severity 3-64

    WORKED EXAMPLE 1

    Ventilation factor:w = (6.0/3.0)0.3 [0.62+90(0.4-0.25)4/(1+43.0x0)]

    = 0.820 m-0.3

    Equivalent fire severity:te = ef kb w = 800 x 0.055 x 0.820 = 36.1 min

    Winter 2003 Fire Severity 3-65

    WORKED EXAMPLE 2 Repeat Worked Example 1 with an additional

    ceiling opening of 3.0 m2.

    Ceiling opening area:Ah = 3.0 m2; h = Ah / Af = 3.0/24.0 = 0.125

    Ventilation factor:w = (6.0/3.0)0.3[0.62+90(0.4-0.25)4/(1+43x0.125)]

    = 0.772 m-0.3 Equivalent fire severity:

    te = ef kb w = 800 x 0.055 x 0.772 = 34.0 minWinter 2003 Fire Severity 3-66

    WORKED EXAMPLE 3 Repeat Worked Example 1 using the CIB

    formula and the Law formula.

    CIB formula Length of room: l1 = 6.0 m Width of room: l2 = 4.0 m Floor area: Af = l1 x l2 = 6.0 x 4.0 = 24.0 m2

    Height of room: Hr = 3.0 m

  • 12

    Winter 2003 Fire Severity 3-67

    WORKED EXAMPLE 3

    Fuel load energy density: ef = 800 MJ/m2

    Total area of the internal surface:At = 2(l1l2 + l1Hr + l2Hr) = (6x4+6x3+4x3) = 108 m2

    For concrete Thermal conductivity: k = 1.0 W/m-K Density: = 2200 kg/m3 Specific heat: cp = 880 J/kg-K

    Winter 2003 Fire Severity 3-68

    WORKED EXAMPLE 3

    Thermal inertia: kcp = 1391 Ws0.5/m2K (medium) Conversion factor: kc = 0.07 min-m2.25/MJ Window height: Hv = 2.0 m Window width: B = 3.0 m Window area: Av = Hv B = 2.0 x 3.0 = 6.0 m2

    Winter 2003 Fire Severity 3-69

    WORKED EXAMPLE 3 Ventilation factor

    w = Af /(Av At Hv0.5)0.5 = 24/(6x108x20.5)0.5

    = 0.793 m-0.25

    Equivalent fire severity:te = ef kc w = 800 x 0.07 x 0.793 = 44.4 min

    Winter 2003 Fire Severity 3-70

    WORKED EXAMPLE 3

    Law formula Net calorific value of wood: Hc = 16 MJ/kg Equivalent fire severity:

    te = ef Af / [Hc (Av (At - Av))0.5]= 800x24/[16x(6(108-6))0.5] = 48.6 min

    Winter 2003 Fire Severity 3-71

    Time-equivalent formulae -Validity

    Time-equivalent formulae are empirical and have been derived by calculation using: a particular set of design fires small rooms maximum temp. concept for protected steel members

    with various thickness of insulation Formulae are crude, may not be applicable to:

    other shapes of time-temperature curve larger rooms other types of protection other structural materials

    Winter 2003 Fire Severity 3-72

    Time-equivalent formulae -Validity

    Time equivalent formulae are applicable to protected steel and reinforced concrete members

    Time equivalent formulae are not intended for unprotected steel or for timber construction

    It is more accurate to carry out designs using first principles to estimate post-flashover fire temp.


Recommended