+ All Categories
Home > Documents > Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns,...

Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns,...

Date post: 28-May-2020
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
89
Mark Terzigni Director of Engineering 2019 Fire, Smoke, & Radiation Dampers
Transcript
Page 1: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Mark TerzigniDirector of Engineering

2019

Fire, Smoke, & Radiation Dampers

Page 2: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Program

• Introduction• History• Code & Regulations

• Construction Types• Fire‐Rated• Smoke‐Rated• Other Duct and Air Transfer Openings

• Responsibilities• Testing & Rating• Damper Installation

Page 3: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

History

• Triangle Shirtwaist Factory Fire – 1911

•MGM Grand Fire – 1980

Page 4: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

History

Triangle Shirtwaist Factory Fire – 1911

• 146 Deaths = 44 from smoke and fire, 102 jumped or fell

• Exits were locked, Fire escape collapsed

• ASSE was founded

• NFPA ‐ Life Safety Code

Page 5: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

History

MGM Grand Fire – 1980• 85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped

• 650 treated at local hospital for smoke inhalation

• Fire on 1st floor ‐ 17 victims were located on the casino floor and 61 were on floors 16 - 26.

• Lead to nationwide reform fire safety codes

Page 6: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Codes and Regulations● NFPA 80  ‐ Standard for Fire Doors & Other Opening 

Protectives

● NFPA 90A  ‐ Standard for the Installation of Air‐Conditioning and Ventilation Systems

● NFPA 105  ‐ Standard for Smoke Door Assemblies & other Opening Protectives

● IBC  ‐ International Building Code

● IMC ‐ International Mechanical Code

● SMACNA ‐ Fire, Smoke, & Radiation Damper Guide

Page 7: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Who Establishes “Acceptable”?

The Damper Manufacturer• Anyone who requires or does any change not specifically shown or defined by the manufacturer is not in compliance with the “AS TESTED” UL safety label of that fire or smoke damper. 

Page 8: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated Construction

• Four Types of fire‐resistance rated walls• Fire Walls• Fire Barrier• Shaft Enclosures• Fire Partitions

Page 9: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionFire Walls

• A fire‐resistance rated wall having protected openings, which restricts the spread of fire and extends continuously from the foundation to or through the roof, with sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall. [IBC‐2015:202]

Page 10: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionFire Walls

• Usually structurally independent and are rated at 3 to 4 hours

• Duct or air transfer openings through a Fire Wall located on a property or lot line are NOT allowed *not even with a fire damper.

• Most restrictive of the 4 types of fire‐rated walls

Page 11: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionFire Walls

• Exceptions (2015 IBC sect. 706.11):• Not on lot line (i.e.. Fire Wall is located within a building)

• Penetration complies with 717.5.1

Page 12: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionFire Barriers

• A fire‐resistance‐rated wall assembly of materials designed to restrict the spread of fire in which continuity is maintained. [IBC‐2015:202]

• Typically used to subdivide floors• Can be used to sub‐divide portions of the building contained by a firewall

• Medium‐rating level of the four types of fire‐rated walls.

Page 13: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionFire Barriers

• Exceptions• ASTM E119 tested fire‐resistance rated assembly• Ducts used as part of an approved smoke control system• Walls penetrated with less than 1 hour rating & fully sprinkled. 

• constructed of minimum 26 gage and is continuous from equipment to the air outlet and inlet terminals.

Page 14: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionShaft Enclosures

• The walls or construction forming the boundaries of a shaft. [IBC‐2015:202]

• Shaft ‐ An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, or floors and roof.

• All permitted duct and air transfer openings must have a listed fire and smoke damper.

Page 15: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionShaft Enclosures

• Exceptions• Steel exhaust subducts at least 22 inch with continuous airflow upward to the outside

• ASTM E119 rated assembly• Ducts used as part of an approved smoke control system• The shaft (exhaust or supply)location is in a parking garage that is separated from other building shafts by 2‐hour fire‐resistance‐rated construction.

Page 16: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionFire Partition 

• A vertical assembly of materials designed to restrict the spread of fire in which openings are protected. [IBC‐2015:202]

• Can be used to sub‐divide portions of the building contained by a firewall

• Similar to Fire Barrier except generally less fire resistive materials than fire barriers

• Minimum‐rating level of the four types of fire‐rated walls.

Page 17: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire‐Rated ConstructionFire Partition 

• Exceptions• Tenant separation or corridor walls within fully sprinkled building

• Duct less than 100 sq. inches• Duct not having openings that communicate the corridor with adjacent spaces

• Walls penetrated with less than 1 hour rating & fully sprinkled. 

• constructed of minimum 26 gage and is continuous from equipment to the air outlet and inlet terminals.

Page 18: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated Construction

• Three Types of fire‐resistance rated walls• Corridors• Smoke Barrier• Smoke Partitions

Page 19: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionCorridor

• An enclosed exit access component that defines and provides a path of egress travel. [IBC‐2015:202]

Page 20: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionCorridor

• Corridors shall be protected with dampers as follows:• A corridor damper constructed as required for the corridor walls

• A ceiling radiation damper shall be provided where the ceiling membrane of a fire‐resistance‐rated floor‐ceiling or roof‐ceiling assembly

• A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a corridor

Page 21: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionCorridor

• Exceptions:• The building is equipped throughout with an approved smoke control system.

• The duct is constructed of steel not less than 26 ga and there are no openings serving the corridor. 

Page 22: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionSmoke Barrier 

• A continuous membrane, either vertical or horizontal, such as a wall, floor or ceiling assembly, that is designed and constructed to restrict the movement of smoke. [IBC‐2015:202]

• Smoke barriers are also automatically one‐hour fire partitions.

Page 23: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionSmoke Barrier 

• Smoke Barriers shall be protected with dampers as follows:

• A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates the smoke barrier

• Leakage Rating either Class I or Class II with a minimum elevated temperature rating of 250°F

Page 24: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionSmoke Barrier 

• Exceptions:• Opening in duct are limited to a single smoke compartmentand the ducts are constructed of steel.

• Constructed per IMC and Building is equipped throughout with an automatic sprinkler system

Page 25: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionSmoke Partition

• A continuous membrane that is designed to form a barrier to limit the transfer of smoke [NFPA 101‐2015:3.3.256 (SAF‐MEA)]

• Typically used in Corridor walls in Group I‐2(IBC only) and  Sprinkler protected hazardous areas – NFPA

Page 26: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionSmoke Partition

• Smoke Partitions shall be protected with dampers as follows:

• A listed smoke damper designed to resist the passage of smoke shall be provided at each point that an air transfer opening penetrates a smoke partition.

• Leakage Rating either Class I or Class II with an minimum elevated temperature rating of 250°F

Page 27: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke‐Rated ConstructionSmoke Partition

• Exceptions:• If the smoke damper will interfere with a smoke control system.

Page 28: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Other  Duct and Air Transfer OpeningsHorizontal Assemblies

• A fire resistance rated floor or roof assembly of materials designed to restrict the spread of fire in which continuity is maintained.

Page 29: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Other  Duct and Air Transfer OpeningsHorizontal Assemblies

• Penetrations of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected by a shaft enclosure.

• Penetrations that are considered Horizontal Assemblies• Through Penetrations• Membrane Penetrations

Page 30: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Other  Duct and Air Transfer OpeningsHorizontal Assemblies ‐ Through

• A duct that penetrates a fire‐resistance‐rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection, provided a listed fire damper is installed at the floor line or the duct is protected

Page 31: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Other  Duct and Air Transfer OpeningsHorizontal Assemblies ‐ Through

• Exceptions:• Duct is permitted to penetrate three floors or less without a fire damper if it meets all of the following:

• 26ga minimum and located within the cavity of the wall

• Opens into one unit and is continuous from unit to exterior of building

• Duct cross area shall not exceed 100 sq. inches

• Annular space must be protected per ASTM E119

• Grille openings in fire rated locations must be listed ceiling radiation dampers 

Page 32: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Other  Duct and Air Transfer OpeningsHorizontal Assemblies ‐ Membrane

• A breach in one side of a floor‐ceiling, roof‐ceiling or wall assembly to accommodate an item installed into or passing through the breach.

• Must be protected with one of the following:• A shaft enclosure• A listed ceiling radiation damper

• Duct or transfer air opening

Page 33: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Other  Duct and Air Transfer OpeningsGrease Duct

• Grease Duct Enclosures• Fire Dampers/Smoke Dampers are prohibited

• 2015 IMC

• Type I Hood Grease Duct 

Page 34: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Plans/Specifications/Responsibilities

Architect/Designer –

Clearly identify all fire‐resistant assemblies and their hourly ratings on the drawings

Page 35: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Plans/Specifications/Responsibilities

Engineer –Clearly identify on the project's drawings all duct penetrations of fire‐resistive assemblies and the details and methods required to maintain the fire‐resistive integrity of those assemblies

Page 36: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Plans/Specifications/Responsibilities

Code Official –Mandatory that the plans and specifications completely identify all fire‐resistant assemblies, and the details of how those penetrations are to be protected

Page 37: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Plans/Specifications/Responsibilities

• NFPA 90A‐2015  Section 5.4.6• 2015 IBC Section 107.2.1• 2015 IMC Section 106.3.1• 2015 UMC Section 104.3.1

Page 38: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

UL555 Fire Dampers

• UL test included but are not limited to:• Fire Endurance and Hose Stream Test• Operational Reliability Cycle Test• Salt Spray Test• Dynamic Closure Test

Combination Fire /Smoke DampersTested to UL555 and UL555S

Page 39: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

UL555S Smoke Dampers

• UL test included but are not limited to:• Cycling• Temperature Degradation• Operation• Leakage• Long Term Holding Test

Combination Fire /Smoke DampersTested to UL555 and UL555S

Page 40: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 41: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 42: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 43: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 44: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 45: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Fire Damper Ratings

• 1½‐hour and 3‐hour ratings:• 1½‐Hour Fire Damper – 1‐hour or 2‐hour walls

• 3‐Hour Fire Damper – 3‐hour or 4‐hour walls

• Static or Dynamic• Static – Usually gravity only.  Fan shuts off

• Dynamic –Spring driven. Fan can be on or off

Page 46: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Smoke Damper Ratings

• Minimum operational rating is 2000 fpm @ 4" w.g. (1.0 kPa) and 250ºF.

• Leakage Classifications per UL555S

• Combination fire/smoke dampers or stand‐alone smoke dampers are leakage –rated devices

Leakage Classification Leakage, cfm/ft2 at Standard Conditions

4.5 in.wg. 8.5 in.wg. 12.5 in.wg.

I 8 11 14

II 20 28 35

III 80 112 140

Page 47: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Table 5‐1 Required Fire Damper Installation Instructions

Page 48: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐1 Basic Fire Damper Installations

Page 49: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

A. Retaining Angles

1. Minimum 1½ ×1 ½ ×16 ga (40×40×1.6mm)a. Retaining angles must overlap structure opening 1 inch 

minimum and cover corners of openings.b. 16 gage is the most commonly used thickness for the 

retaining angles. However manufacturers may allow lighter gage angles on some smaller dampers and may require heavier gage angles on larger dampers. Consult the manufacturer’s installation instructions for specifics.

Page 50: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐1 Basic Fire Damper Installations

Page 51: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

B. Expansion Space

1. Fire Damper Sleeve Clearance within Wall/ Floor Opening

a. Minimum ⅛ inch per linear foot (10mm per linear meter) of damper — both dimensions. (¼” (6 mm) minimum)

b. Clearance requirements for damper sleeves within a wall opening are based on ⅛ inch per foot (10 mm per meter) of width (or height) unless otherwise stated in the listing of the assembly. The sleeve may rest on the bottom of the opening, and need not be centered. (Fractional dimensions shall be taken as the next largest whole foot.)

Page 52: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐1 Basic Fire Damper Installations

Page 53: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

1. Steel Sleeve, see Table 5‐2 for details.

C. Damper Sleeve

Page 54: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐1 Basic Fire Damper Installations

Page 55: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

E. Retaining Angles Fastened to Sleeve

1. Secure Retaining Angels to Sleeve ONLY on 8” centers (203mm) with:

a. ½" (12 mm) long welds

b. ¼" (6 mm) bolts and nuts

c. No. 10 Sheet Metal Screws

d. Minimum  ⁄ " (5 mm) steel rivets

e. Note: The size and spacing requirements may differ by damper manufacturer. Consult manufacturer’s installation instructions for specifics.

Page 56: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐1 Basic Fire Damper Installations

Page 57: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

F. Damper Attachment to Sleeve1. Secure Damper to Sleeve on 8” centers (203mm) with:

a. ½" (12 mm) long weldsb. ¼" (6 mm) bolts and nutsc. No. 10 Sheet Metal Screws

d. Minimum  " (5 mm) steel rivets

See note in Item E aboveNote: The size and spacing requirements may differ by damper manufacturer. Consult manufacturer’s installation instructions for specifics.

Page 58: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐1 Basic Fire Damper Installations

Page 59: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

G. Connection to Duct

• Connect Duct to Sleeve as shown in Table 5‐2 and as indicated in Figure 5‐2.

• Table 5‐2 Recommended Minimum Sleeve Thickness for Fire Dampers*

• Figure 5‐2 UL Duct‐Sleeve Connections (BREAKAWAY CONNECTIONS)

Page 60: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Table 5‐2 Recommended Minimum Sleeve Thickness for Fire Dampers

Page 61: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐1 Basic Fire Damper Installations

Page 62: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐2 UL Duct‐Sleeve Connections (BREAKAWAY CONNECTIONS)

Page 5.5

Page 63: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐2 UL Duct‐Sleeve Connections (BREAKAWAY CONNECTIONS)Formed on Flange Style Connections

Page 64: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐2 UL Duct‐Sleeve Connections (BREAKAWAY CONNECTIONS)

Page 65: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

BREAKAWAY CONNECTIONS Mfg. Installation requirements

Page 66: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

BREAKAWAY CONNECTIONS Mfg.. Installation requirements

Page 67: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

BREAKAWAY CONNECTIONS Mfg. Installation requirements

Page 68: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

BREAKAWAY CONNECTIONS Mfg. Installation requirements

Page 69: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 70: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 71: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 72: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire
Page 73: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐3 Improper Fire Damper Installations

Item 1 ‐ Sealing of the fire damper. • In no case should the retaining angles be sealed with any product not approved by the damper manufacturers

Item 2 ‐ Introduction of any materials • Such as mineral wool, ceramic fiber or sealants of any kind has not been tested, approved, or permitted by damper manufacturers.

Page 74: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐5 Fire Damper Out Of Wall

The use of this method requires the approval of the local authority.

Page 75: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐6 Combination Fire/Smoke Damper Out Of Wall Installation

Note: Several damper manufacturers have available UL tested and listed fire/combination fire‐smoke dampers for mounting out of the fire barrier. Contact damper manufacturers for information.

Page 76: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Insulation Requirements

• Coverings, linings, adhesives must meet flame spread requirements

• Duct covering shall not penetrate fire‐resistive rated assemblies or those that require fire blocking

• Nosings are required on the downstream side of liner interruption 

Page 77: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐8 Duct Liner Interruption

Page 78: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Metal NosingHVAC Duct Construction Standards

Metal nosing shall be used on leading edges of each piece of lined duct when the velocity exceeds 4000 fpm otherwise, it shall be used on the leading edge of any lined duct section that is preceded by unlined duct.

Like the downstream side of a fire damper preceded by lined duct!

Page 79: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 7‐11 Phenolic Duct InterruptionPhenolic Duct Construction Standards

Page 80: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 5‐9 Fibrous Glass Duct Installation

Page 81: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Figure 12‐1 SubductsPage 12.1

Page 82: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Inspection, Testing & Maintenance

• Fire & Smoke Dampers

• Smoke Control Systems

Page 83: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Inspection, Testing & MaintenanceFire & Smoke Dampers

• Fire Dampers (NFPA 80 Chapter 19)

• Smoke Dampers (NFPA 105 Chapter 7)

• Fire dampers fusible link shall be removed for testing (fan off for safety)

• Fire/Smoke dampers or Smoke Dampers without fusible links ‐ position indicator or visually verify 

Page 84: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Inspection, Testing & MaintenanceFire & Smoke Dampers

• Dampers to be tested and inspected 1 year after installation

• Test & inspection frequency shall be every 4 years, except in hospitals where frequency is every 6 years

• Operational test after installation for dynamic fire dampers and combination fire smoke dampers

Page 85: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Inspection, Testing & MaintenanceSmoke Control Systems

• NFPA 92 covers engineered smoke control systems• Periodic Testing

• Dedicated Smoke Control Systems shall be tested semi‐annually

• Non‐dedicated Smoke Control Systems shall be tested annually

• (This includes cycling all Smoke and Combination Fire Smoke Dampers)

• Conducted under normal airflow conditions!

Page 86: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Inspection, Testing & MaintenanceSmoke Control Systems

• High‐Rise, Hotels, Atriums, Underground Bldgs., etc.• Analysis & Design Factors‐Stack Effect‐Temperature Effect of Fire‐Wind Effect/Climate‐HVAC Systems‐Duration of Operation

Page 87: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Who Establishes “Acceptable”?

THE DAMPER MANUFACTURER• Anyone who requires or does any change not specifically shown or defined by the manufacturer is not in compliance with the “AS TESTED” UL safety label of that fire or smoke damper. 

PERIOD.

Page 88: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Who Approves?

• Code Official• What does the code official need for inspection and approval?

• Clearly drawn, detailed plans• Damper manufacturer installation instructions

• Codes are supposed to be about safety and protecting life.  This inspection can save the lives of occupants and fire fighters.

Page 89: Fire, Smoke, & Radiation Dampers · MGM Grand Fire –1980 •85 Deaths = 79 smoke & CO2, 4 burns, 1 heart attack, 1 jumped •650 treated at local hospital for smoke inhalation •Fire

Questions?www.smacna.org


Recommended