UP FIRE SPRINKLER USAGE SCHEDULE AREA TYPE (NOTE 1 & 6) AREA HAZARD SPRINKLER MANUFACTURER & MODEL REMARKS SYMBOL (NOTES 4 & 5) TYPE RESPONSE FINISH TEMPERATURE °F GENERAL SEE PLANS SPR-1 UPRIGHT QUICK ROUGH BRASS 175 VIKING VK, RELIABLE F1FR, TYCO TY-FRB, VICTAULIC V2704 NOTE 3 GENERAL SEE PLANS SPR-2 CONCEALED QUICK WHITE 175 VIKING VK, RELIABLE G4A, TYCO RFII, VICTAULIC V3802 NOTE 3 DETENTION SEE PLANS SPR-3 CONCEALED QUICK WHITE 165 VIKING QR , RELIABLE XL , TYCO RAVEN NOTES 3 NOTES: 1. SEE FLOOR PLANS FOR ZONING REQUIREMENTS. 2. SPRINKLER SHALL HAVE COLOR CODED BULB THERMAL ELEMENT. 3. ALL SPRINKLERS SHALL BE UL LISTED. 4. CONTRACTOR TO VERIFY SPRINKLER REQUIREMENTS BASED ON ACTUAL INSTALLATION, USAGE, ARCHITECTURAL CEILING PLAN AND NFPA 13 REQUIREMENTS. 5. SYMBOL IS PRIMARILY FOR INDENTIFYING SPRINKLERS IN SUBMITTALS. IT MAY OR MAY NOT BE FOUND ELSEWHERE ON THE DRAWINGS. CONTRACTOR TO SUBMIT ALL SPRINKLER TYPES TO BE USED. 6. AREAS ARE GENERAL IN NATURE. CONTRACTOR TO MATCH UNSCHEDULED AREAS TO SIMILAR SPACES. SYMBOL: DESCRIPTION: FIRE PROTECTION FP NO HATCH LIGHT HAZARD ORDINARY GROUP 2 SPRINKLER SPRINKLER SPRINKLER BFP BACKFLOW PREVENTER FIRE PROTECTION SYMBOLS LIST DIRECTION OF FLOW IN PIPE CHECK VALVE ELECTRICAL CONTRACTOR E.C. FLOOR DRAIN FD FIRE PROTECTION CONTRACTOR F.P.C. PLUMBING CONTRACTOR P.C. 107 SF PUBLIC LOBBY 101 326 SF POST PROCESS 102 572 SF PROCESS 103 283 SF PRE-PROCESS 104 55 SF WOMEN 106 218 SF CBP OFFICE 108 115 SF HOLDING 112 73 SF SEARCH 111 73 SF INTERVIEW 110 121 SF AG LAB 109 78 SF ENTRY 107 971 SF CONFERENCE 105 55 SF MEN 105 54 SF SECURITY 116 81 SF SUPPLY 114 119 SF LAN 115 35 SF ELECTRICAL 113 264 SF WOMEN 129 161 SF MEN 130 192 SF MECH 117 188 SF MAIN ELECTRICAL 118 389 SF SPRINKLER/MECH 119 JJ HH GG FF EE DD CC BB AA 11 SF MECH 120 5/8" / 1'-0" 85 SF STORAGE 121 1741 SF CHARTER 122 SD SD 4 4 LOCATION OF FIRE PROTECTION CYLINDERS. 2 3 5 1 KEYNOTES: 1. NUMBER AND SIZE OF CYLINDERS TO BE PROVIDED BY THIS MANUFACTURER AND MAY VERY FROM WHAT IS SHOWN. SECURE CYLINDERS AS REQUIRED BY NFPA. 2. AUDIO HORN/VISUAL DEVICE AND ALARM BELL FOR CLEAN AGENT SYSTEM. 3. MANUAL RELEASE STATION. 4. SMOKE DETECTOR FOR CLEAN AGENT SYSTEM. 5. CONTROL PANEL FOR CLEAN AGENT SYSTEM. 6. REPLACE SPRINKLERS IN EXISTING AREA UNDER BID ALTERNATE. 7. REPLACE SPRINKLERS BETWEEN COLUMN LINES FF AND JJ WITH NEW SPRINKLERS. BRANCH PIPING MAY REMAIN. 8. PROVIDE CLEAN AGENT SYSTEM IN LAN 115 ROOM. SEAL ALL NEW AND EXISTING PENETRATIONS INTO ROOM AIR TIGHT. REFER TO SPECIFICATIONS SECTION 21 22 00. 9. PROVIDE DETENTION STYLE SPRINKLER IN SPACE. # ZONE 1 EXISTING AIR COMPRESSOR BID ALTERNATE 6 7 9 9 9 9 8 EXISTING FIRE DEPARTMENT CONNECTION SHEET NUMBER: PROJECT NUMBER: DATE: PROJECT DESCRIPTION: PROJECT ARCHITECT: DRAWN BY: CHECKED BY: THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES. COPYRIGHT 2015 © THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE AND SHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW 430 S. GLENSTONE AVE. SPRINGFIELD, MO 65802 PH: 417.885.0002 FAX: 417.868.0072 www.paragonarchitecture.com MISSOURI STATE CERTIFICATE OF AUTHORITY #2010011426 FP1-10 SGF Airport CBP/FIS 2300 N. AIRPORT BLVD. SPRINGFIELD, MO 65802 WADROS PARAGON ANDDEW 13-127 BID SET - 12/17/15 FIRST FLOOR PLAN - FIRE PROTECTION N O R H T 1/8" = 1'-0" 1 FIRST FLOOR PLAN - FIRE PROTECTION GENERAL SHEET NOTES 1. REFER TO FPD1-10 FOR EXTENT OF SPRINKLERS BEING REPLACED. CURRENT SYSTEM IS A DRY PIPE SPRINKLER SYSTEM. REFERENCE SCALE IN INCHES 0 1 2 3 ENGINEERING CONSULTANTS Missouri State Certificate of Authority #2003008820 309.788.0673 FAX: 309.786.5967 www.kjww.com 623 26TH AVENUE QUAD CITIES, ILLINOIS 61201 PROJECT # KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP. The FUTURE . Built SMARTER . ® 14.0259.01
Transcript

UP

FIRE SPRINKLER USAGE SCHEDULE

AREA TYPE(NOTE 1 & 6)

AREA HAZARD

SPRINKLER

MANUFACTURER & MODEL REMARKSSYMBOL

(NOTES 4 & 5)TYPE RESPONSE FINISH

TEMPERATURE°F

GENERAL SEE PLANS SPR-1 UPRIGHT QUICK ROUGH BRASS 175 VIKING VK, RELIABLE F1FR,TYCO TY-FRB, VICTAULIC V2704

NOTE 3

GENERAL SEE PLANS SPR-2 CONCEALED QUICK WHITE 175 VIKING VK, RELIABLE G4A,TYCO RFII, VICTAULIC V3802

NOTE 3

DETENTION SEE PLANS SPR-3 CONCEALED QUICK WHITE 165 VIKING QR , RELIABLE XL , TYCO RAVEN NOTES 3

NOTES:1. SEE FLOOR PLANS FOR ZONING REQUIREMENTS.

2. SPRINKLER SHALL HAVE COLOR CODED BULB THERMAL ELEMENT.

3. ALL SPRINKLERS SHALL BE UL LISTED.

4. CONTRACTOR TO VERIFY SPRINKLER REQUIREMENTS BASED ON ACTUAL INSTALLATION, USAGE, ARCHITECTURAL CEILING PLAN AND NFPA 13 REQUIREMENTS.5. SYMBOL IS PRIMARILY FOR INDENTIFYING SPRINKLERS IN SUBMITTALS. IT MAY OR MAY NOT BE FOUND ELSEWHERE ON THE DRAWINGS. CONTRACTOR TO SUBMIT ALL SPRINKLER TYPES TO BE USED.

6. AREAS ARE GENERAL IN NATURE. CONTRACTOR TO MATCH UNSCHEDULED AREAS TO SIMILAR SPACES.

SYMBOL: DESCRIPTION:

FIRE PROTECTIONFP

NO HATCH LIGHT HAZARD

ORDINARY GROUP 2

SPRINKLER

SPRINKLER

SPRINKLER

BFP BACKFLOW PREVENTER

FIRE PROTECTION SYMBOLS LIST

DIRECTION OF FLOW IN PIPE

CHECK VALVE

ELECTRICAL CONTRACTORE.C.

FLOOR DRAINFD

FIRE PROTECTION CONTRACTORF.P.C.

PLUMBING CONTRACTORP.C.

107 SF

PUBLIC LOBBY

101

326 SF

POST PROCESS

102

572 SF

PROCESS

103

283 SF

PRE-PROCESS

104

55 SF

WOMEN

106

218 SF

CBP OFFICE

108

115 SF

HOLDING

112

73 SF

SEARCH

11173 SF

INTERVIEW

110

121 SF

AG LAB

109

78 SF

ENTRY

107

971 SF

CONFERENCE

10555 SF

MEN

105

54 SF

SECURITY

116

81 SF

SUPPLY

114

119 SF

LAN

115

35 SF

ELECTRICAL

113

264 SF

WOMEN

129

161 SF

MEN

130

192 SF

MECH

117

188 SF

MAIN ELECTRICAL

118

389 SF

SPRINKLER/MECH

119

JJ HH GG FF EE DD CC

BB AA

11 SF

MECH

1205

/8"

/ 1

'-0

"

85 SF

STORAGE

121

1741 SF

CHARTER

122

SD

SD4

4

LOCATION OF FIREPROTECTIONCYLINDERS.

2

3

5

1

KEYNOTES:

1. NUMBER AND SIZE OF CYLINDERS TO BEPROVIDED BY THIS MANUFACTURER AND MAYVERY FROM WHAT IS SHOWN. SECURECYLINDERS AS REQUIRED BY NFPA.

2. AUDIO HORN/VISUAL DEVICE AND ALARM BELLFOR CLEAN AGENT SYSTEM.

3. MANUAL RELEASE STATION.4. SMOKE DETECTOR FOR CLEAN AGENT SYSTEM.5. CONTROL PANEL FOR CLEAN AGENT SYSTEM.6. REPLACE SPRINKLERS IN EXISTING AREA

UNDER BID ALTERNATE.7. REPLACE SPRINKLERS BETWEEN COLUMN

LINES FF AND JJ WITH NEW SPRINKLERS.BRANCH PIPING MAY REMAIN.

8. PROVIDE CLEAN AGENT SYSTEM IN LAN 115ROOM. SEAL ALL NEW AND EXISTINGPENETRATIONS INTO ROOM AIR TIGHT. REFERTO SPECIFICATIONS SECTION 21 22 00.

9. PROVIDE DETENTION STYLE SPRINKLER INSPACE.

#

ZONE

1

EXISTING AIR

COMPRESSOR

BID ALTERNATE

6

7

9

9

9

9

8

EXISTING FIRE

DEPARTMENT

CONNECTION

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

FP

1-1

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

FIR

ST

FLO

OR

PLA

N -

FIR

E P

RO

TE

CT

ION

NO R HT

1/8" = 1'-0"1FIRST FLOOR PLAN - FIRE PROTECTION

GENERAL SHEET NOTES1. REFER TO FPD1-10 FOR EXTENT OF

SPRINKLERS BEING REPLACED. CURRENTSYSTEM IS A DRY PIPE SPRINKLER SYSTEM.

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

JJ HH GG FF EE DD CC

BB AA

KEYNOTES:

1. REMOVE AND REPLACE SPRINKLER HEAD ANDBRANCH PIPING IN THIS AREA AS REQUIRED FORNEW ROOMS AND CEILING LAYOUT.

2. SPINKLER HEADS IN THIS AREA TO REMAIN.3. REMOVE AND REPLACE SPRINKLERS UNDER BID

ALTERNATE.

1 2

1

2

BID ALTERNATE

3

2 2

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

FP

D1-1

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

FIR

ST

FLO

OR

PLA

N -

FIR

E P

RO

TE

CT

ION

- D

EM

OLIT

ION

NO R HT

1/8" = 1'-0"1FIRST FLOOR PLAN - FIRE PROTECTION - DEMOLITION

GENERAL SHEET NOTES

1. SYSTEM IS CONNECTED TO DRY PIPE. NEW TOREMAIN ON DRY SYSTEM.

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

UP

T

T

T

T

T

T

T

T

T

T

TT

T

107 SF

PUBLIC LOBBY

101

326 SF

POST PROCESS

102

572 SF

PROCESS

103

283 SF

PRE-PROCESS

104

55 SF

WOMEN

106

218 SF

CBP OFFICE

108

115 SF

HOLDING

112

73 SF

SEARCH

11173 SF

INTERVIEW

110

121 SF

AG LAB

109

78 SF

ENTRY

107

971 SF

CONFERENCE

10555 SF

MEN

105

54 SF

SECURITY

116

81 SF

SUPPLY

114

119 SF

LAN

115

35 SF

ELECTRICAL

113

264 SF

WOMEN

129

161 SF

MEN

130

192 SF

MECH

117

188 SF

MAIN ELECTRICAL

118

389 SF

SPRINKLER/MECH

119

JJ HH GG FF EE DD CC

BB AA

11 SF

MECH

120

5/8

" / 1

'-0

"

85 SF

STORAGE

121

1741 SF

CHARTER

122

16x18

6x6

6x6

EG-1

6x6/70

8x8 EA UPTO EF-2

EG-3

8x8/100EG-3

6x6/75

12x10 EA UP TO EF-1FURNISH SECURITYBAR AT ROOF LEVEL.

FUME HOOD MODEL TO BEKEWAUNEE H05G5448-00 ,CONTRACTOR INSTALLED.BALANCE TO 810 CFM.

CU-1

CRU-1

SG-ESG-ESG-ESG-E

40x18

SB

REFER TO 2/M3-01 FORSECURITY BAR DETAIL.(TYP.)

NC

TG-E TG-E

TG-E

EF-E

TG-E

EG-E

10x10/270

(TYP.2)

EG-E

10x10/325

12x1412x14

SG-E

12x12/85

SG-E

10x10/140 12x12

CU-2

EF-EL-E

L-E18x30 UP TO OAH-1

SG-1

9x9/80

SG-1

9x9/160

8x88x8

TAB-114

SB

SG-1

6x6/75

SG-1

6x6/75

8x8 6x6

TAB-113

SG-2

8x8/100

TAB-106

SG-1

9x9/165

TAB-105

TAB-104

10x10

CD-1

10/250

LD-1

8/130(TYP.3)

12x12

10x8

TAB-101

14

x1

21

8x1

2

SG-2

8x8/200(TYP.2)

TAB-112

CD-1

8/250

TAB-107

20ø26x20

TAB-111

12x12

12

x1

2

16

ø

TAB-108

TAB-110

CUH-1

IDAC-3

RELOCATE IDAC-3TO THIS LOCATION.

IDAC-4

RELOCATE EXISTING OUTDOORCONDENSING UNIT TO THIS LOCATION.REROUTE PIPING TO IDAC-4. FURNISHNEW HOUSEKEEPING PAD

EF-E

KEEP TOP OF DUCT TIGHTTO BOTTOM OF BEAM.

KEEP TOP OF DUCT TIGHTTO BOTTOM OF BEAM.

CD-1

8/225

CD-1

8/225

ODAC-4

RELOCATE EXISTINGOUTDOORCONDENSING UNIT TOTHIS LOCATION.REROUTE PIPING TOIDAC-3. FURNISH NEWHOUSEKEEPING PAD.

EG-1

6x6/70

SB

SB SB

SB

1

KEYNOTES:

1. FURNISH EXHAUST AIR TEMPERATURE SENSORIN DUCT ABOVE ACCESSIBLE CEILING.

#

12x8 EA UP TO EF-3FURNISH SECURITYBAR AT ROOF WALL

12x8

EG-3

12x12/260 8x8

18x30 UP TO EAH-1

12ø

SG-2

10x6/200(TYP. 3)

SG-2

10x10/300(TYP. 2)

12ø

REFIGERANT PIPING SIZE ANDROUTE PER MANUFACTURER'SRECOMMENDATIONS

AHU-1

30x18 RA, PROVIDEBELLMOUTH OPENING.

PROVIDE GALVANIZEDSHEETMETAL ENCLOSURE.

14

ø

SG-2

12x10/325(TYP.3)

8x8

CD-1

6/100

20

x1

4

12x10

LD-1

8/125(TYP.2)

CD-1

10/300(TYP.4)

LD-1

8/135

20

x1

4

12x10

LD-1

8/130

LD-1

8/135

10x10

FURNISH NEWHOUSEKEEPING PAD

CUH-2

FURNISH NEWHOUSEKEEPING PAD

REFER TO 1/M3-00 FORELBOW CONSTRUCTIONDETAIL. (TYP.)

REFER TO 2/M3-00 FORBRANCH CONNECTIONDETAIL. (TYP.)

REFER TO 3/M3-00 FOR FLEXDUCT CONNECTION DETAIL.(TYP.)

REFER TO 5/M3-00 FORDIFFUSER CONNECTIONDETAIL. (TYP.)

REFER TO 4/M3-00 FORSLOT DIFFUSER MOUNTINGDETAIL. (TYP.)

REFER TO 3/M3-01 FOR AIRHANDLING UNIT DETAIL AND1/M3-01 FOR CONDENSATETRAP DETAIL.

EXISTING HEATER (TYP.)

NEW DDC CONTROLPANELS

CD-1

10/310

CD-1

10/315

CD-1

10/310

CD-1

10/315

EXISTING DUCT TO REMAIN

EXISTING DUCT TO BE REMOVED

NEW DUCT

FABRIC DUCT CONNECTION

MANUAL VOLUME DAMPER

RISE IN DIRECTION OF AIR FLOWR

DROP IN DIRECTION OF AIR FLOWD

DUCT CAP

DUCT DOWN

DUCT UP

SUPPLY/OUTSIDE AIR DUCT SECTION

RETURN AIR DUCT SECTION

EXHAUST/RELIEF AIR DUCT SECTION

CD-16/115

AIR TERMINAL PROPERTIES SYMBOLNECK SIZE/CFM

THERMOSTAT/SENSORT

VENTILATION SYMBOLS LISTSYMBOL: DESCRIPTION:

SECURITY BARSB

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

M1-1

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

FIR

ST

FLO

OR

PLA

N -

VE

NT

ILA

TIO

N

NO R HT

1/8" = 1'-0"1FIRST FLOOR PLAN - VENTILATION

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

GENERAL NOTES :

1. COORDINATE ROOF PENETRATIONS WITHOWNER'S STANDING SEEM ROOFMANUFACTURER.

2. ALL EXPOSED DUCTWORK BETWEEN COLUMNLINE HH & FF SHALL BE "ARCHITECTURALLYEXPOSED" PER 23 31 00.

RECTANGULARMITERED ELBOW

WITH VANESTYPE RE2

RECTANGULARMITERED ELBOW

TYPE RE6

USE ONLY AS PART OF OFFSETSAND TRANSITIONS PER FIGURE4-7 TYPE 2 OR AS SHOWN ONDRAWINGS. OFFSETS ABOVE 30°SHALL BE TYPE RE1.

RECTANGULARRADIUS ELBOW

TYPE RE1

R/W = 1.0 (MINIMUM)R/W < 1.0 SHALL BE TYPE RE3

RECTANGULARRADIUS ELBOW WITH VANES

TYPE RE3

REFER TO SMACNA HVAC SYSTEMS DUCT DESIGN MANUAL, FOURTHEDITION, SECTION 5.14 "SPLITTER VANES" AND SMACNA HVAC DUCTCONSTRUCTION STANDARDS, THIRD EDITION, FIGURES 4-2 AND 4-9 ANDCHARTS 4-1 AND 4-1M. ELBOW SHALL HAVE THREE SPLITTER VANESAND r/W = 0.10 (R/W = 0.60) UNLESS NOTED OTHERWISE.

NOTES:

1. BEAD, CROSSBREAK, AND REINFORCE FLAT SURFACES AS IN STRAIGHT DUCT.2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.3. DEFAULT ELBOW SHALL BE TYPE "RE1".4. ELBOW TYPES SHALL BE INSTALLED AS SHOWN AND NOT BE SUBSTITUTED

WITHOUT PERMISSION. EXCEPTION: RE1 OR RE3 MAY BE SUBSTITUTED FORRE2.

RECTANGULARRADIUS ELBOW WITH

SQUARE THROAT

NOT ALLOWED

RECTANGULAR / OVAL / ROUNDMITERED ELBOWWITHOUT VANES

TYPE RE4

NOT ALLOWED

OVAL / ROUNDRADIUS ELBOW

SMOOTH OR 5 GORE (MINIMUM)

R/W = 1.5 (MINIMUM)

W W

R

R

W

r R1 R

2

R R3

W

W

30°

EX

CE

ED

NO

T T

O

W

W

90°

90°

W

W

SHEETMETAL ELBOW

NOTES:

1. TO ATTACH FLEX DUCT TO THE HARD DUCT, TAPE THE INNER LINERTO THE HARD DUCT THEN ATTACH WITH TWO NYLON TIE WRAPS;ONE FOR THE INNER LINER AND ONE FOR THE OUTER SHELL.FOLD THE OUTER SHELL INSIDE ITSELF SO IT HAS NEAT EDGESPRIOR TO TIE WRAPPING.

2. "SMARTFLOW" ELBOW (WWW.HARTANDCOOLEY.COM) AND"FLEXRIGHT" (WWW.TITUS-HVAC.COM) ARE ACCEPTABLEPRODUCTS FOR DURABLE ELBOW SUPPORT.

R = DUCT DIA.

FLEXIBLE DUCT

INSULATION

CEILING

STRUCTURE

DIFFUSER

D1>D2

45 DEGREE

BUTT FLANGESTRAIGHT TAP

ENTRY Θ 45°45 DEGREE CONICAL

CLINCH LOCK

CORNER FILLERPIECE OR USEGASKET (TYP.)

45 DEGREE LEAD IN

NOTES:

1. DO NOT USE CONNECTIONS WITH SCOOPS.2. FIT ALL CONNECTIONS TO AVOID VISIBLE OPENINGS AND

SECURE THEM SUITABLY FOR THE PRESSURE CLASS.3. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

DOVETAIL JOINT

LINED DUCT CONNECTION(NO EXPOSED LINER EDGES)

DUCT LINER

FLANGED

NOTE: STRAIGHT TAP WITH BUTTFLANGE FOR BRANCH AND TEECONNECTION IN RECTANGULAR DUCTSUNDER 1" PRESSURE CLASS ONLY.

ENTRY Θ 45°

D1

W

L

Θ

D2

(L = 4" OR W/4; WHICHEVER IS LARGER)

3"

NYLON TIE WRAP, TWO REQUIREDFOR EACH END OF FLEXIBLEDUCT (TOTAL 2). INSTALL ONE TIEWRAP TO SECURE THE INNERLINER AND ONE TO SECURE THEOUTER SHELL. (TYP.)

SPOT WELD EXTENSIONS TOINSIDE OF CONNECTOR.

1 1/2" 28 GAUGE GALVANIZEDEXTENSIONS WITH 1 1/2" DEEPNOTCHES. (LOOKS LIKE THISBEFORE BENDING TABS DOWN.)

BEND TABS DOWN CLAMPINGCONNECTORS SECURELY TODUCT LINER.

CUT INSIDE CARRIER DUCTAT THIS POINT

26 GAUGE GALVANIZEDSHEET METAL DUCT.SAME DIAMETER ASFLEX DUCT.

NOTES:

1. THIS DETAIL APPLIES ONLY TO TAPS OFF LINED DUCTS.2. TAP DOES NOT NEED TO BE CONICAL IF THE TAP IS NOT LOCATED

BETWEEN FANS AND TERMINAL AIR BOXES, DUCT IS NOT OVER 2"PRESSURE CLASS, AND ROUND DUCT IS NOT OVER 12" DIAMETER.

WRAP INSULATION (REFER TOSPECIFICATION SECTION 15890)(SECTION 23 31 00 - DUCTWORK)

INSULATED FLEX DUCT

GALVANIZED SHEET METAL DUCT

NYLON TIE WRAP

6" (MIN.)

D D+

2"

FLEXIBLE DUCT

2 LAYERS OFDUCT TAPE

ROUND INLET(OVAL IS NOTACCEPTABLE)

NYLON TIE WRAPSECURE TO INLET

ACOUSTICTILE BY G.C.

TEES FURNISHEDWITH DIFFUSER.

LIGHT FIXTUREBY E.C.

TEES 24" O.C.BY G.C. (TYP.)

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

M3-0

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

ME

CH

AN

ICA

L D

ET

AIL

S

NO SCALE1ELBOW CONSTRUCTION

NO SCALE5DIFFUSER CONNECTION DETAIL

NO SCALE2BRANCH CONNECTIONS

NO SCALE3FLEX DUCT CONNECTION (CONICAL/LINED)

NO SCALE4SLOT DIFFUSER MOUNTING DETAIL

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

NOTES:

1. ANCHORAGE TO CONCRETE WALL OR SOLID BRICK, USEEXPANSION ANCHORS 3/8"ø (MIN.)

2. ANCHORAGE TO HOLLOW CONCRETE BLOCK, USETOGGLE BOLT (CARBON STEEL) 5/8"ø (MIN.)

3. ANCHORAGE TO METAL STUDS AND GYP. BOARD WALLS,USE CARBON STEEL THROUGH BOLT, 3/8"ø (MIN.)

REFER TO SPECIFICATION SECTION 23 33 00FOR SECRUTY BAR REQUIREMENTS.

WRAP INSULATION ALL AROUNDDUCT AND SLEEVE ON BOTH SIDESOF WALL. (REFER TO SPEC SECTION23 31 00 FOR REQUIREMENTS)

3" x 2 1/2" x 3/16" ANGLE FRAME CONTINUALLYWELDED AT CORNERS AND SEAMS. SECUREANGLES @ 100mm O.C. MIN. ANGLES MUSTLAP STRUCTURAL OPENING 75mm MINIMUM

3/16" STEEL SLEEVE CONTINUALLYWELDED AT CORNERS OR SEAMS.EXTEND 3" EACH SIDE FROM WALL

SECURE DUCT TO SLEEVE, INSTALLTAPE ALONG ENTIRE PERIMETEROF THE DUCT SEAM TO SLEEVE.

PLAN VIEW

ELEVATION VIEW

DX

CO

OL

ING

CO

IL S

EC

TIO

N

AC

CE

SS

SE

CT

ION

SA - 4,800 CFM(2,200 CFM MIN.)

OA - 1,400 CFM EA - VARIES RA - 3,600 CFM(1,000 CFM MIN.)

SUPPLY FAN RETURN FAN

RELIEF AIRSECTION

MIXINGAIR &

FILTERSECTION

ELECTRICHEAT

AC

CE

SS

SE

CT

ION

SUPPLY FAN RETURN FANRELIEF AIRSECTION

MIXING AIR &FILTER SECTION

CONTROLLER

DX

CO

OLIN

G C

OIL

EL

EC

TR

IC H

EA

T

18'-0" MAX.

6'-0

" M

AX

.

3”

CLEANOUT PLUG (TYP.)

ROUTE TO WITHIN TENFEET OF ROOF DRAIN (IFROOFTOP UNIT). OR TOFLOOR DRAIN IF UNIT ISLOCATED INSIDE.

FULL SIZE CONDENSATEDRAIN, CONNECT TO DRAINPAN AS RECOMMENDED BYMANUFACTURER.

1.5

"

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

M3-0

1S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

ME

CH

AN

ICA

L D

ET

AIL

S

NO SCALE2SECURITY BAR DETAIL

1/2" = 1'-0"3AIR HANDLING UNIT AHU-1

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

NO SCALE1CONDENSATE TRAP DETAIL (DRAW-THROUGH)

COMPUTER ROOM UNIT SCHEDULE - DIRECT EXPANSION

SYMBOL SERVICE CFMEXT. S.P.IN. W.C.

REFRIGERANT COOLING COIL FILTERS ELECTRICAL

MANUFACTURER MODEL REMARKSCOIL TYPE &REFRIGERANT

# OFCIRCUITS

EAT MBHTYPE HP

VOLT-PHASE

FLA/RLA

MCAMOCPAMPS

DISCONNECT CONTROLLER/STARTER

°FDB °FWB TOTAL SENSIBLE BY (NOTE A) BY (NOTE A) SCCR

CRU-1 SECURITY/LAN 750 0.3 R-407C 1 80 62.8 19,300 19,300 MERV 8 0.2 208-1 1.4 1.8 15.0 MFR MFR 3.6 LIEBERT MINI-MATE 2

NOTES:

1. CRU-1 CONTROLS TO BE PROVIDED WITH UNIT. FMCS TO MONITOR SPACE TEMPERATURE AND TO SEND ALARM UPON OCCURRENCE OF ANY OF THE FOLLOWING CONDITIONS:LOSS OF POWER TO CRU, HIGH TEMPERATURE, LOW TEMPERATURE, HIGH HUMIDITY OR LOW HUMIDITY.

HOOD & LOUVERED PENTHOUSE SCHEDULE

SYMBOL SERVICE CFMTHROAT

SIZE (IN)

STATICPRESSURE

(IN W.C.)

FREEAREA(FT2)

TYPE

MAX. HEIGHT(TOP OF CURB

TO TOP OFEQUIPMENT)

DAMPERTYPE

CURB(NOTE G)

MANUFACTURER MODEL REMARKS

OAH-1 AHU-1 6,000 18x42 0.15 10.6 ROOF HOOD 16" ELECTRIC MFR COOK GI NOTE 1 & 2

EAH-1 AHU-1 6,000 18x42 0.10 6.8 ROOF HOOD 13" ELECTRIC MFR COOK GR NOTE 1 & 2

NOTES:

1. ELECTRIC DAMPER TO HAVE 24V ACTUATOR.

2. MINIMUM 12" ROOF CURB.

CONDENSING UNIT SCHEDULE

SYMBOL SERVICENOMINALDESIGNTONS

REFRIGERANTSATURATEDSUCTION °F

AMBIENTTEMP. °F

MINIMUMAMBIENTTEMP. °F

NUMBER OFCOMPRESSORS

NUMBEROF

STAGES

NUMBEROF

CIRCUITS

NUMBEROF

FANS

ELECTRICAL

MANUFACTURER MODEL REMARKSVOLT-PHASE RLA

MCAMOCPAMPS

DISCONNECT

BY (NOTE A) TYPE (NOTE B)

CU-1 SECURITY/LAN 1.5 R-407C 95 -20 1 1 1 1 208-1 12.1 14.8 25.0 MFR NF LIEBERT PFH

CU-2 AHU-1 20 R-410A 45 95 0 2 1 2 2 460-3 37.2 46.9 60.0 MFR NF TRANE TTA240 NOTE 1

NOTES:

1. PROVIDE ADIABATIC PROPORTIONING REFRIGERATION (APR) CONTROL TO MODULATE REFRIGERATION CAPACITY. EACH COMPRESSOR CIRCUIT SHALL HAVE APR CONTROL, PROVIDE RAWAL MODEL APR-410-6 OR EQUAL (WWW.RAWAL.COM).

GRILLES REGISTERS & DIFFUSERS SCHEDULE

SYMBOL MAT'L TYPE MARGIN(NOTE 1)

INLETSIZE

(INCH)

FACESIZE

(INCH)

VOLUMEDAMPER

REQ'DFINISH MANUFACTURER MODEL REMARKS

CD-1 STEEL PANEL FACE LAY-IN SEE DWG. 24x24 NO WHITE TITUS OMNI FLUSH FACE PANEL

RG-1 STEELPERFORATED

FACELAY-IN N/A 24x24 NO WHITE TITUS PXP FACE ONLY - NON DUCTED

SG-1 STEELPERFORATED

FACE 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS SG-PR MAXUMUM SECURITY GRILLE

SG-2 STEELSINGLE

DEFLECTION 1 1/4' SEE DWG. INLET +2 YES WHITE TITUS 301R BLADES VERTICAL UNLESS NOTED OTHERWISE

EG-1 STEEL 35° DEFLECTION 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS 350R

EG-2 STEEL PANEL FACE 1 1/4" SEE DWG. 24x24 YES WHITE TITUS PXP

EG-3 STEELPERFORATED

FACE 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS SG-PR MAXUMUM SECURITY GRILLE

NOTES:

1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.

2. ALL RUN OUT DUCTWORK TO DIFFUSERS SHALL BE NECK SIZE UNLESS OTHERWISE NOTED.

FAN SCHEDULE

SYMBOL SERVICE CFMS.P.IN.

W.C.

WHEELDIA.

INCHES

FANRPM

(NOTE F)DRIVE

MAX.AMCASONES

BACKDRAFTDAMPER

CURBTYPE

(NOTE G)

ELECTRICAL

MANUFACTURER MODEL REMARKSBHP(NOTE E)

MHP(NOTE E)

VOLT-PHASE

DISCONNECT CONTROLLER/STARTER

BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)

EF-1 AG LAB 810 .35 12.0 1,028 DIRECT 5.4 ELECTRIC MFR 0.078 0.167 115-1 EC NF MFR VSC COOK ACED NOTES 1 & 2

EF-2 RESTROOMS 140 0.5 9.0 1,300 DIRECT 7 ELECTRIC MFR 92(W) 1/8 115-1 EC NF MFR FV COOK ACED NOTES 2 & 3

EF-3 INTERVIEW 435 0.5 9.0 1,450 DIRECT 7 ELECTRIC MFR 92(W) 1/8 115-1 EC NF MFR FV COOK ACED NOTES 2 & 3

NOTES:

1. REFER TO DETAIL 1/M6-01 FOR FAN CONTROL DIAGRAM.

2. FURNISH FAN SPEED CONTROLLER

3. REFER TO DETAIL 2/M6-01 FOR FAN CONTROL DIAGRAM.

SCHEDULE GENERAL NOTES:A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND

INSTALLED BY:

MFR = MANUFACTURER

EC = ELECTRICAL CONTRACTOR.

MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED

BY ELECTRICAL CONTRACTOR

MFR/EC = FURNISHED LOOSE BY MANUFACTURER

INSTALLED BY ELECTRICAL CONTRACTOR

ATC = AUTOMATIC TEMPERATURE CONTROL CONTRACTOR

B. DISCONNECT TYPE:

F = FUSED

NF = NON-FUSED

C. CONTROLLER STARTER TYPE:

FV = FULL VOLTAGE

WYE = WYE-DELTA

SS = SOLID STATE (SOFT START)

MS = MANUAL STARTER

VFD = VARIABLE FREQUENCY DRIVE

VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS

VSC = VARIABLE SPEED CONTROLLER

D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE,

WITH THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS

FANS FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.

E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR

NAME PLATE RATING.

F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.

G. CURB TYPE:

MFR = STANDARD CURB BY MANUFACTURER

GC = BY GENERAL CONTRACTOR

SAC = SOUND ATTENUATOR CURB

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

M5-0

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

ME

CH

AN

ICA

L S

CH

ED

ULE

S

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

AIR HANDLING UNITSCHEDULE - ELECTRIC

SYMBOL AHU-1

SERVICEFLIGHT PASSENGER

PROCESSING

SUPPLY FAN

CFM 4,800

MINIMUM CFM 2,200

EXTERNAL STATIC PRESSURE 1.50

TYPE FC

FAN RPM (NOTE D) 1,800

BHP (NOTE E) 5.62

MHP (NOTE E) 7.5

RETURN FAN

CFM 3,600

MINIMUM CFM 1,400

EXTERNAL STATIC PRESSURE 1.00

TYPE FC

FAN RPM (NOTE D) 1,800

BHP (NOTE E) 1.53

MHP (NOTE E) 2

MINIMUM OUTSIDE AIR CFM 1,400

HEATING - ELECTRICAL

EAT °F DB 52

MAX. LAT °F DB 65

MINIMUM OUTPUT KW 20

STAGES SCR

COOLING COIL - DX

EAT °F DB 82.5

EAT °F WB 68

MAX. LAT °F DB 55

LAT °F WB 53.8

TOTAL MBH 212

AMBIENT TEMPERATURE °F 95

MAX. A.P.D. IN. W.C. 0.32

REFRIGERANT R410A

FILTER

TYPE 2" MERV 8

VELOCITY 360 FPM

VIBRATION ISOLATION

TYPE M3

DEFLECTION 0.75"

ELECTRICAL

VOLT-PHASE 460-3

MANUFACTURER TRANE

MODEL NUMBER CSSA 12

REMARKS NOTES 1 & 2

NOTES:

1. LAT LISTED IS AT LEAVING SIDE OF COOLING COIL.

2.PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTORSPECIFICATION 23 05 13.

LINEAR DIFFUSER SCHEDULE

SYMBOL MATERIALSLOT

WIDTHNO.

SLOTSBAR

WIDTHBAR

SPACINGWIDTHINCHES

LENGTHFEET

PLENUMREQUIRED

PLENUMINSULATION

PLENUMINLET SIZE

PATTERNCONTROLREQUIRED

BALANCINGDAMPER

REQUIREDFINISH MANUFACTURER MODEL REMARKS

LD-1 ALUMINUM 1" 2 N/A N/A 4 7/16 4 YES LINED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2 & 3

NOTES:

1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.

2. PROVIDE WITH CONCEALED FASTENERS.

3. DIFFUSERS WITH MULTIPLE SLOTS SHALL HAVE THE INNER MOST SLOT DIRECTED TOWARDS THE INTERIOR OF THE BUILDING, THE REMAINING SHALL BE DIRECTED TOWARDS THE EXTERIOR UNLESS NOTED OTHERWISE.

CABINET UNIT HEATER SCHEDULE - ELECTRIC

SYMBOL SERVICE TYPE CFM STAGES

ELECTRICAL

TSTAT LOCATION MANUFACTURER MODEL REMARKSFAN HP KW

VOLT/PHASE

FLA/RLA

DISCONNECT CONTROLLER/STARTER

BY (NOTE A) TYPE (NOTE B) BY (NOTE A)

CUH-1 ENTRY CEILING 285 3 0.1 5.0 277-1 18.0 MFR. NF MFR WALL BERKO FFCH NOTE 1 & 2

CUH-2 TOILET WALL 100 1 0.1 1.5 110-1 12.5 MFR. NF MFR INTEGRAL BERKO FRC

NOTES:

1. RECESSED WITH BOTTOM INLET AND OUTLET

2. REFER TO 6/M6-01 FOR CONTROL SEQUENCE.

TERMINAL AIR BOX SCHEDULE - SINGLE DUCT ELECTRIC REHEATSYMBOL

AREA SERVED

CFM HEATING COILMIN.

INLETSIZE(IN.)

CONTROLTYPE

(NOTE 3)

SENSORTYPE

(NOTE 4)MANUFACTURER MODEL REMARKS

###COOLING

MAX.HEATING

MAX.MIN.

EAT°F

LAT°F

KWVOLT/

PHASE/WIRE

DISCONNECTNO. OFSTEPSBY

(NOTE A)TYPE

(NOTE B)

101 117 MECH 400 400 150 55 95 5.0 277-1 MFR NF NOTE 5 8 A 2 TRANE VCEF NOTE 1 & 2

104 108 CBP OFFICE 640 640 240 55 95 7.5 277-1 MFR NF NOTE 5 8 A 4 TRANE VCEF NOTE 1 & 2

105 109 AG LAB 165 50 50 55 95 0.5 277-1 MFR NF NOTE 5 6 A 4 TRANE VCEF NOTE 1 & 2

106 113 ELECTRICAL 100 - - - - - 277-1 MFR NF NOTE 5 6 C 2 TRANE VCEF NOTE 1 & 2

107 102 POST PROCESS 600 600 200 55 95 7.5 277-1 MFR NF NOTE 5 8 A 1 TRANE VCEF NOTE 1 & 2

108 103 PROCESS 975 400 235 55 95 5.0 277-1 MFR NF NOTE 5 10 A 1 TRANE VCEF NOTE 1 & 2

110 104 PRE-PROCESS 600 600 200 55 95 7.5 277-1 MFR NF NOTE 5 8 A 1 TRANE VCEF NOTE 1 & 2

111 130 MEN 675 675 675 55 95 10.0 277-1 MFR NF NOTE 5 8 B 1 TRANE VCEF NOTE 1 & 2

112 101 LOBBY 250 250 100 55 95 3.0 277-1 MFR NF NOTE 5 6 A 1 TRANE VCEF NOTE 1 & 2

113 111 SEARCH 150 150 150 55 95 2.5 277-1 MFR NF NOTE 5 6 B 1 TRANE VCEF NOTE 1 & 2

114 112 HOLDING 240 240 240 55 95 3.0 277-1 MFR NF NOTE 5 6 B 1 TRANE VCEF NOTE 1 & 2

NOTES:

1. NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER AHRI STANDARD 885-2008 USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE.

2. TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC.

3. SEE SPECIFICATION SECTION 23 09 003 FOR DESCRIPTION OF CONTROL TYPE.

4. SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE.

5. PROVIDE TAB WITH SCR HEATING

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

M5-0

1S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

ME

CH

AN

ICA

L S

CH

ED

ULE

S

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

AIAI

AI

AODI

DO

DI

AOAI

AOAI

AO AI

AI

AI

DI AI

AODI

DO

DI

DI

AI AI

AIAI

TH

FM

VFD

FM

T

FM

VFD

H T

T

SP

RETURNAIR

DUCT MOUNTEDTEMPERATURE &HUMIDITYSENSORS

RETURN DUCTMOUNTED LOWSTATIC SWITCH

RETURNAIRFLOW

RETURNFAN

COMMUNICATION LINKBETWEEN VFD GATEWAY &FMCS (TYPICAL EACH VFD)

MODALRM

START/STOP

CS

FANSTATUS

ACT

N.C.

DMPRMOD.

DMPRFDBK RELIEF

AIR

RELIEFAIR

DAMPER

ACT

ACT

OUTSIDEAIRFLOW

N.C.

O.A.

DMPRMOD.

DMPRFDBK

SP

MIXED AIRLOW STATIC

SWITCH

DMPRFDBK

DMPRMOD.

DP

FILTERSTATUS

ELECTRICPRE HEAT

COIL

SP

RETURNAIR

DAMPER

N.O.

OUTSIDEAIR

DAMPER

M.A.TEMP

PRE-FILTER(30%)

SUC

LIQ

DIFF. PRESS. SWITCH(0-1" W.G. SCALE)(TYP.2)

DX COOLINGCOIL

MOUNT FLOWMETER DISPLAY WITHINSERVICE VESTIBULE OF EACH RTU OR ONEXTERIOR OF AHU FOR INDOOR UNITS. (TYP.)

MODALRM

CS

FANSTATUS

DP

FILTERSTATUS

HIGH STATICSWITCH

DUCT MOUNTEDTEMPERATURE &HUMIDITY SENSORS

MOUNT IN DISCHARGEPLENUM OF AHU.

SP

SUPPLYAIR

STATICPRESS.TRANS.

UNLESS LOCATED ELSEWHEREON FLOOR PLANS, LOCATE 2/3DOWN LONGEST MEDIUMPRESSURE DUCT MAIN.

AHU REPORT GENERATION:DDC FMCS SHALL MONITOR THE FOLLOWING POINTS ON 10 MINUTE (ADJ.) INTERVALS WITHIN ASINGLE TREND. THE TREND SHALL RUN FOR A 100-DAY (ADJ.) DURATION AT WHICH POINT THENEWEST VALUES SHALL AUTOMATICALLY OVERWRITE THE OLDEST VALUES:

• DATE• TIME• GLOBAL OUTSIDE AIR TEMP [°F]• GLOBAL OUTSIDE AIR DEWPOINT [°F]• GLOBAL OUTSIDE AIR HUMIDITY [%RH]• SUPPLY AIRFLOW [CFM]• SUPPLY AIR TEMP (SAT) [°F]• SUPPLY AIR TEMP SETPOINT [°F]• SUPPLY AIR RELATIVE HUMIDITY [%]• SUPPLY AIR DEWPOINT [°F]• SUPPLY AIR DEWPOINT SETPOINT [°F]• RETURN AIRFLOW [CFM]• RETURN AIR TEMP (RAT) [°F]• RETURN AIR RELATIVE HUMIDITY [%]• OUTSIDE AIRFLOW [CFM]• MIXED AIR TEMP [°F]• PREHEAT COIL DISCHARGE AIR TEMP [°F]• PRE-FILTER LOADING (30% FILTER) [INCHES W.G.]• SUPPLY DUCT STATIC PRESSURE SETPOINT [INCHES W.G.]• SUPPLY DUCT STATIC PRESSURE [INCHES W.G.]• SUPPLY FAN VFD OUTPUT [% FULL SPEED]• RETURN FAN VFD OUTPUT [% FULL SPEED]• OUTSIDE AIR DAMPER POSITION [% OPEN]• RETURN AIR DAMPER POSITION [% OPEN]• RELIEF AIR DAMPER POSITION [% OPEN]

THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN GRAPHICAL FORM ON THE FMCS OPERATORWORKSTATION.

ONCE PER MONTH, THE DDC FMCS SHALL RECORD THE LARGEST AHU AIRFLOW WHICH OCCUREDDURING THAT MONTH. THE DATE, TIME, OUTSIDE AIR TEMP (AND ALL OTHER VALUES LISTED ABOVE)THAT COINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS INFORMATION SHALL BESTORED TO A MEMORY LOCATION ON THE FMCS OPERATOR WORKSTATION THAT IS MAINTAINED(NOT AUTOMATICALLY OVERWRITTEN).

SEQUENCE OF OPERATION:

WHEN AHU/RTU IS INDEXED TO RUN, THE FOLLOWING SHALL OCCUR:• SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS SHALL OPEN.• AFTER A 30 SECOND DELAY (ADJ.) TO ALLOW FOR OPENING OF SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS. SUPPLY FAN SHALL BE ENABLED TO RUN.• WHEN THE SUPPLY FAN HAS STARTED THE RETURN FAN AND INTERLOCKED EXHAUST FANS SHALL START AS SHOWN IN THE FAN INTERLOCK SCHEDULE.

SUPPLY FAN OPERATION:FMCS SHALL MODULATE SIGNAL TO SUPPLY FAN VFD AS REQUIRED TO MAINTAIN DUCT STATIC PRESSURE AS MEASURED BY STATIC PRESSURE TRANSMITTER. FMCS SHALL RESET SUPPLY DUCT STATICPRESSURE SETPOINT AS REQUIRED TO MAINTAIN AT LEAST ONE SUPPLY TAB DAMPER 95% (ADJ.) OPEN. FMCS SHALL UTILIZE COMMAND TO ALL SUPPLY TERMINAL AIR BOX POSITIONS TO RESET THESUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.

RETURN FAN OPERATION:RETURN FAN SHALL BE INDEXED TO RUN WHENEVER THE SUPPLY FAN IS INDEXED TO RUN. FMCS SHALL MODULATE SIGNAL TO RETURN FAN VFD AS REQUIRED TO MAINTAIN THE AIRFLOW OFFSET ASINDICATED IN THE RETURN FAN AIRFLOW SCHEDULE.

DISCHARGE AIR TEMPERATURE SET POINT:DISCHARGE AIR SET POINT SHALL BE 55ºF (ADJ.).

DISCHARGE AIR TEMPERATURE RESET:RESET DISCHARGE AIR TEMPERATURE BASED ON THE ZONE WITH THE GREATEST CALL FOR COOLING. RESET THE TEMPERATURE AS FOLLOWS:• WHEN WORST CASE TAB IS OPEN ABOVE 90% (ADJ.) FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL RAISE BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL AHU MAXIMUM

DISCHARGE AIR TEMPERATURE OF 60ºF (ADJ.) IS ACHIEVED.• WHEN WORST CASE TAB IS OPEN BELOW 80% (ADJ.) FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL DROP BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL AHU MINIMUM

DISCHARGE AIR TEMPERATURE OF 55ºF (ADJ.) IS ACHIEVED.• THE MAXIMUM RETURN AIR HUMIDITY SETPOINT SHALL BE 60% (ADJ.) IF RETURN AIR HUMIDITY IS GREATER THAN SETPOINT, RESET DISCHARGE AIR TEMPERATURE TO 55°F UNTIL RETURN AIR

HUMIDITY IS 5% LESS THAN MAXIMUM SETPOINT.

USER TOGGLE - STATIC PRESSURE AND DISCHARGE AIR TEMPERATURE RESETS:PROVIDE USER WITH OPTION TO USE EITHER STATIC PRESSURE RESET OR DISCHARGE AIR TEMPERATURE RESET. ONLY ONE CONTROL OPTION SHALL BE USED AT A TIME. GRAPHIC ON AHU SCREENSHALL ALLOW USER TO TOGGLE FROM EITHER TEMPERATURE OR STATIC PRESSURE RESET.

VENTILATION AIR CONTROL:WHENEVER THE AIR HANDLING UNIT IS IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER SHALL BE FULLY OPEN. THE RETURN AIR AND RELIEF AIR DAMPER SHALL MODULATE IN OPPOSITION TO MAINTAINTHE MINIMUM OUTSIDE AIR FLOW RATE, OR TO SATISFY THE ECONOMIZER DISCHARGE AIR SEQUENCE.

DX COOLING COIL OPERATION:WHEN IN MINIMUM OUTSIDE AIR MODE, FMCS SHALL CONTROL CONDENSING UNIT (CU-1) AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.

WHEN IN ECONOMIZER MODE, FMCS SHALL NOT MODULATE COOLING CONTROL VALVE UNLESS RETURN AIR DAMPER IS 5% (ADJ.) OPEN AND RELIEF AIR DAMPER IS 95% (ADJ.) OPEN.

PREHEAT COIL OPERATION:PREHEAT COIL CONTROLS SHALL BE ENABLED WHEN OUTSIDE AIR TEMP DROPS BELOW 50°F (ADJ.). PREHEAT COIL CONTROLS SHALL BE DISABLED WHEN OUTSIDE AIR TEMP RISES ABOVE 54°F (ADJ.).

FMCS SHALL MODULATE ELECTRIC HEATING COIL AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.

ECONOMIZER OPERATION:WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS LESS THAN THE RETURN AIR DRY BULB TEMPERATURE THE FMCS SHALL ENABLE ECONOMIZER CONTROLS. WHEN OUTSIDE AIR DRY BULBTEMPERATURE IS GREATER THAN THE RETURN AIR DRY BULB TEMPERATURE FOR 10 MINUTES THE FMCS SHALL DISABLE ECONOMIZER CONTROLS AND SHALL RETURN THE UNIT TO MINIMUM OUTSIDEAIR MODE. ONCE ECONOMIZER CONTROLS HAVE BEEN ENABLED OR DISABLED, THE UNIT SHALL CONTINUE TO OPERATE IN THAT MODE FOR A MINIMUM OF 10 MINUTES (ADJ.) BEFORE BEING ALLOWEDTO SWITCH BACK (TO PREVENT SHORT CYCLING).

IN ECONOMIZER MODE THE FMCS SHALL MODULATE THE RETURN AND RELIEF DAMPERS AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT.

ALARMS, INTERLOCKS, AND SAFETIES:WHEN FIRE ALARM CONTROL PANEL INDICATES AN ALARM CONDITION, AHU SHALL BE SHUTDOWN.

THE FOLLOWING CONDITIONS SHALL SHUTDOWN THE AHU AND SHALL INDICATE AN ALARM CONDITION AT THE FMCS WORKSTATION:• LOW STATIC PRESSURE SWITCH INDICATES RETURN DUCT PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS.• LOW STATIC PRESSURE SWITCH INDICATES MIXED AIR PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS OF THE OUTSIDE AIR DUCTWORK.• HIGH STATIC PRESSURE SWITCH INDICATES SUPPLY DUCT STATIC PRESSURE GREATER THAN THE SPECIFIED DUCT PRESSURE CLASS.

THE FOLLOWING CONDITIONS SHALL INDICATE AN ALARM AT THE FMCS, HOWEVER AHU SHALL CONTINUE TO OPERATE:• AN ALARM IS INDICATED AT ANY SUPPLY FAN VFD OR RETURN FAN VFD.• DIFFERENTIAL PRESSURE SWITCH ACROSS PRE-FILTER (30%) BANK EXCEEDS 0.6 INCHES W.G. (ADJ.)• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 5°F (ADJ.) ABOVE OR BELOW SETPOINT.

IN THE EVENT SUPPLY FAN IS NOT RUNNING (AS INDICATED BY THE CURRENT SENSING RELAYS) RETURN AIR FAN SHALL BE DE-ENERGIZED.

WHENEVER AHU IS SHUTDOWN THE FOLLOWING SHALL OCCUR:• THE OUTSIDE AIR DAMPER AND RELIEF AIR DAMPER SHALL FULLY CLOSE.• RETURN AIR DAMPER SHALL FULLY OPEN.• ALL SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS SHALL FULLY CLOSE.• SUPPLY FAN AND RETURN FAN VFDS SHALL BE DE-ENERGIZED.• INTERLOCKED EXHAUST FANS SHALL BE DE-ENERGIZED WITH THE EXCEPTION OF EF-1 (AG LAB) & EF-3 (SEARCH/INTERVIEW).

UNOCCUPIED MODE:PROVIDE TIME OF DAY SCHEDULE TO ALLOW AHU TO ENTER UNOCCUPIED MODE PER SCHEDULE. COORDINATE SCHEDULE WITH OWNER.

• THE SUPPLY AND RETURN FANS SHALL CONTINUE RUNNING. WHEN USING CONSTANT VOLUME OFFSET FOR RETURN AIR FAN CONTROL, THE OFFSET SHALL GO TO ZERO AND THE SUPPLY FAN SHALLBE LIMITED TO THE MAXIMUM RETURN FAN AIRFLOW.

• THE OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN. ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER DAMPER POSITION.• ALL SPACE TEMPERATURES SHALL BE ALLOWED TO VARY +/- 10°F (ADJ.) FROM OCCUPIED SETPOINT.

HEATING OPTIMUM START-UP:• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC SYSTEM

SHALL DETERMINE THE MINIMUM RUNTIME TO WARM THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURESHALL BE MAINTAINED AT A SETPOINT OF 85ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES EXCEED A SETPOINT OF 68ºF (ADJ.). AT THAT TIME,THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.

COOLING OPTIMUM START-UP:• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC SYSTEM

SHALL DETERMINE THE MINIMUM RUNTIME TO COOL THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURESHALL BE MAINTAINED AT A SETPOINT OF 55ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES ARE LESS THAN A SETPOINT OF 75ºF (ADJ.). AT THATTIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.

GRAPHICAL DISPLAY:DISPLAY THE GLOBAL OUTSIDE AIR TEMPERATURE AND HUMIDITY ON AHU GRAPHIC PAGE.

A

B

C

D

E

F

R

A

B

C

D

E

F

AUX CONTACT TOFMCS TO INITIATECONTROL

TERMINALSTRIP SPEED

CONTROLSIGNALRETURN FAN

VFD SECTION

SPEEDCONTROLSIGNALSUPPLY FAN

VFD SECTION

TERMINALSTRIP

AUX CONTACT TOFMCS TO INITIATECONTROL

SAFETYCIRCUITS

NH

FIR

E A

LA

RM

SY

ST

EM

DU

CT

HIG

H S

TA

TIC

DU

CT

LO

W S

TA

TIC

LO

W L

IMIT

TE

MP

SW

ITC

H

SUPPLY & RETURN FAN VFD CONTROL

RETURN FAN AIRFLOW SCHEDULE

SYSTEM SUPPLY CFM EXHAUST FANS PRESSURIZATIONCFM

REMARKS

AHU-1 6,000EF-1, 2, & 3

0 NOTES 1,2,3

NOTES:1. RETURN FAN AIRFLOW SETPOINT SHALL BE THE SUPPLY FAN AIRFLOW (AS MEASURED BY THE

AFMS) MINUS THE SUM OF THE EXHAUST FAN AIRFLOWS MINUS THE PRESSURIZATION CFM

2. FMCS SHALL DETERMINE THE OPERATIONAL STATUS OF EACH EXHAUST FAN VIA THE CURRENTSENSING RELAY TO DETERMINE WHETHER THE CFM ASSOCIATED WITH THAT FAN SHOULD BEINCLUDED IN THE RETURN FAN AIRFLOW CALCULATION.

3. EXHAUST FAN AIRFLOWS SHALL NOT BE THE CFM INDICATED ON THE FAN SCHEDULE, BUTSHALL BE THE AIRFLOW INDICATED IN THE FINAL TAB REPORT.

FAN INTERLOCK SCHEDULE

SYSTEM INTERLOCKED EXHAUST FANS REMARKS

AHU-1 EF- 2 & 3 NOTE 1

NOTES:1. INTERLOCK EXHAUST FAN OPERATION THROUGH THE FMCS WITH RESPECTIVE

AHU IN ACCORDANCE WITH AHU SEQUENCE OF OPERATION.

P.H.TEMP

CU-1

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

M6-0

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

ME

CH

AN

ICA

L C

ON

TR

OL D

IAG

RA

MS

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

NO SCALE1AIR HANDLING UNIT CONTROL - AHU-1

DO

DI

DO

DI AI

AIAO

AI

AO

T

T

AIAO

AIAO

AI

T

T

AI

AO

AI

T

AI

AO

DO

T

FANSTATUS

HM

START/STOP

EXHAUSTAIR

ACT

SEQUENCE OF OPERATION:EXHAUST FAN SHALL BE INTERLOCKED TO RUN CONTINUOUSLY WHENRESPECTIVE AHU IS OPERATING.

2-POSITION DAMPER SHALL FULLY OPEN WHEN FAN IS ENERGIZED. WHEN FAN ISDE-ENERGIZED, 2-POSITION DAMPER SHALL FULLY CLOSE.

ALARMS, INTERLOCKS AND SAFETIES:AN ALARM SHALL BE GENERATED AT THE FMCS OPERATOR WORKSTATION IN THEEVENT THE FMCS COMMANDS THE EXHAUST FAN TO OPERATE AND THE CURRENTSENSING RELAY DETECTS INSUFFICIENT CURRENT DRAW.

FANSTATUS

CS

START/STOP

EXHAUSTAIR

ACT

SWALL MOUNTEDSWITCH ORTWIST TIMER

SEQUENCE OF OPERATION::FAN SHALL BE CONTROLLED BY MANUAL MOTOR STARTER (WALLSWITCH OR TWIST TIMER) PROVIDED BY OTHERS.

2-POSITION DAMPER SHALL FULLY OPEN WHEN FAN IS ENERGIZED.WHEN FAN IS DE-ENERGIZED, 2-POSITION DAMPER SHALL FULLY CLOSE.

GREEN LED LIGHT SHALL BE INSTALLED NEXT TO SWITCH AND INDICATEFAN-ON STATUS.

ALARMS, INTERLOCKS AND SAFETIES:AN ALARM SHALL BE GENERATED AT THE FMCS OPERATORWORKSTATION IN THE EVENT THE SWITCH POSITION DOES NOT MATCHFAN STATUS ACCORDING TO CURRENT SENSING RELAY.

N.T.S. #1 WALL MTDTEMP SENSOR

PRIMARY AIR FROM ZONECONDITIONING AHU

SUPPLYAIR

ACTVELOCITY ANDSTATIC SENSOR

PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)

SUPPLYAIR TEMP

DAMPER ACTUATORDAMPERMOD.

TABAIRFLOW

SEQUENCE OF OPERATION:

• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND TAB ELECTRIC REHEAT COILCONTROL VALVE TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJ.) WITH 2°F (ADJ.) DEAD BANDBASED ON A SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR. SEE DRAWINGS FORTEMPERATURE SENSOR REQUIREMENTS. SPACES WITH ADJUSTABLE THERMOSTATS WILL ALLOW A+/- 3°F (ADJ.) OFFSET FROM THE DDC SETPOINT.

• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL SHALLBE DE-ENERGIZED.

• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED UNTIL SPACE SETPOINTIS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED CFM POSITION PER THE TABSCHEDULE. THE REHEAT COIL SHALL REMAIN DE-ENERGIZED.

• UPON A FURTHER FALL IN SPACE TEMPERATURE, THE ELECTRIC REHEAT COIL AND TAB SHALLMODULATE OPEN IN UNISON TO MAINTAIN SPACE SETPOINT UNTIL TAB AIR FLOW REACHES ITSMAXIMUM HEATING SETTING.

ALARMS, INTERLOCKS & SAFETIES:

• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN10°F (ADJ.) ABOVE OR BELOW SETPOINT.

• IF THE HIGH TEMPERATURE SAFETY DEVICE EXCEEDS MANUFACTURER'S SETPOINT, AN ALARMSHALL BE SENT TO THE OPERATOR INTERFACE.

WALL MTDTEMP SENSOR

PRIMARY AIR FROM ZONECONDITIONING AHU

SUPPLYAIR

ACTVELOCITY ANDSTATIC SENSOR

PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)

SUPPLYAIR TEMP

DAMPER ACTUATORDAMPERMOD.

TABAIRFLOW

SEQUENCE OF OPERATION:

• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER TO MAINTAIN CONSTANT SUPPLYAIRFLOW TO THE ROOM.

• FMCS TAB CONTROLLER SHALL MODULATE TAB ELECTIC REHEAT COIL TO MAINTAIN SPACETEMPERATURE OF 72°F (ADJ.) WITH 2°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALLMOUNTED TEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.SPACES WITH ADJUSTABLE THERMOSTATS WILL ALLOW A +/- 3°F (ADJ.) OFFSET FROM THE DDCSETPOINT.

ALARMS, INTERLOCKS & SAFETIES:

• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN10°F (ADJ.) ABOVE OR BELOW SETPOINT.

• IF THE HIGH TEMPERATURE SAFETY DEVICE EXCEEDS MANUFACTURER'S SETPOINT, AN ALARMSHALL BE SENT TO THE OPERATOR INTERFACE.

WALL MTDTEMP SENSOR

PRIMARY AIR FROM ZONECONDITIONING AHU

SUPPLYAIR

ACTVELOCITY ANDSTATIC SENSOR

PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)

DAMPER ACTUATORDAMPERMOD.

TABAIRFLOW

SEQUENCE OF OPERATION:

• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER TO MAINTAIN SPACE TEMPERATUREOF 72°F (ADJ.) WITH 2°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTEDTEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS. SPACESWITH ADJUSTABLE THERMOSTATS WILL ALLOW A +/- 3°F (ADJ.) OFFSET FROM THE DDC SETPOINT.

• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION.• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED UNTIL SPACE SETPOINT

IS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED CFM POSITION PER THE TABSCHEDULE.

ALARMS, INTERLOCKS & SAFETIES:

SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN 10°F(ADJ.) ABOVE OR BELOW SETPOINT.

WALL MTDTEMP SENSOR

SUPPLYAIR

RETURNAIR

PRE-FILTER START /

STOP

SUPPLYFAN

HEATINGCOIL

SEQUENCE OF OPERATION:

THE CABINET HEATER SHALL BE FURNISHED WITH A UNIT MOUNTED FAN SPEED SELECTOR SWITCH(OFF-HIGH-MED-LOW). THE UNIT SHALL MAINTAIN A SPACE TEMPERATURE OF NO MORE THAN 60°F.

WHEN THE OUTDOOR AIR TEMPERATURE IS ABOVE 45°F, HEATING SHALL BE DISABLED.

WHEN THE OUTDOOR AIR TEMPERATURE IS BELOW 45°F, HEATING SHALL BE ENABLED AND THE FANSHALL RUN CONTINUOUSLY.

ALARMS, INTERLOCKS & SAFETIES:

• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF SPACE TEMPERATURE FALLS 10°F (ADJ.)BELOW SETPOINT.

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

M6.0

1S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

ME

CH

AN

ICA

L C

ON

TR

OL D

IAG

RA

MS

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

NO SCALE1EXHAUST FAN CONTROL - AHU INTERLOCK - FAN-A

NO SCALE2EXHAUST FAN CONTROL - WALL SWITCH - FAN-B

NO SCALE3TAB CONTROL W/ ELECTRIC REHEAT - TAB-A

NO SCALE4TAB CONTROL CONSTANT VOLUME W/ ELECTRIC REHEAT - TAB-B

NO SCALE5TAB CONTROL W/ COOLING ONLY - TAB-C

NO SCALE6CABINET HEATER CONTROL - ELECTRIC

JJ HH GG FF EE DD CC

BB AA

IDAC-4IDAC-3

ODAC-3 TO BE RELOCATED. REFER TOM1-10 FOR NEW LOCATION.

ODAC-4 TO BE RELOCATED.REFER TO SHEET M1-10FOR NEW LOCATION.

EF-11

EF-9

10x10

24x8

24x8

24x8

24

x8

36

x1

4

22ø

TG-E TG-E

TG-E

EF-E

16x18

40x18

SG-E

10x10/225

SG-E

10x10/225SG-E

24x12/750

SG-E

24x12/750

TG-E

14

x1

2

14x12

14

x1

2

14x12

14x1214x12

12x12

EG-E12x12/200(TYP.2)

SG-E24x12/495(TYP.4)

SG-E10x10/225(TYP.2)

EG-E

10x10/270

(TYP.2)

EG-E

10x10/32530x20

20x30

SL

OP

E D

N. SLOPE DN.

SLOPE DN.

12x1412x14

SG-E

12x12/85

SG-E

10x10/140 12x12

RELOCATE DDCCONTROLS TOROOM 119UNDER BIDALTERNATE.24x8

SLOPE DN.

24

x8

IDAC-3 TO BE RELOCATED. REFERTO M1-10 FOR NEW LOCATION.

5

4

EXISTING LINEARDIFFUSER (TYP.)

2

1

3

KEYNOTES:

1. REMOVE EXISTING AIR HANDLER ANDASSOCIATED PIPING AND DUCTWORK. REMOVEEXISTING HOUSEKEEPING PAD.

2. REMOVE EXISTING EXHAUST FAN ANDASSOCIATED DUCT. PATCH EXISTING EXTERIORLOUVER.

3. REMOVE EXISTING OUTDOOR CONDENSINGUNIT.

4. PATCH EXISTING EXTERIOR LOUVER.5. REMOVE EXISTING DUCTWORK AND DIFFUSERS

FOR FURNACE UNDER BID ALTERNATE ONLY.

#

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

MD

1-1

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

FIR

ST

FLO

OR

PLA

N -

VE

NT

ILA

TIO

N -

DE

MO

LIT

ION

NO R HT

1/8" = 1'-0"1FIRST FLOOR PLAN - VENTILATION - DEMOLITION

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

UP

107 SF

PUBLIC LOBBY

101

326 SF

POST PROCESS

102

572 SF

PROCESS

103

283 SF

PRE-PROCESS

104

55 SF

WOMEN

106

218 SF

CBP OFFICE

108

115 SF

HOLDING

112

73 SF

SEARCH

11173 SF

INTERVIEW

110

121 SF

AG LAB

109

78 SF

ENTRY

107

971 SF

CONFERENCE

10555 SF

MEN

105

54 SF

SECURITY

116

81 SF

SUPPLY

114

119 SF

LAN

115

35 SF

ELECTRICAL

113

264 SF

WOMEN

129

161 SF

MEN

130

192 SF

MECH

117

188 SF

MAIN ELECTRICAL

118

389 SF

SPRINKLER/MECH

119

JJ HH GG FF EE DD CC

BB AA

11 SF

MECH

120

5/8

" / 1

'-0

"

85 SF

STORAGE

121

1741 SF

CHARTER

1224" WASTE LINE

BELOW SLAB

FCO

WC WC WC WC

LAV

WC

UR UR LAV LAV FCO

FD

FD

FD

FCO

FCO

FCO

FD

2" V UP

CF

FCO

4"SAN

FCO

SK(2)

4"SAN

4"SAN

2" V UP

WCLAV

EWCFD

4"SAN

4"SAN

4"SAN

LAV

2" V UP

WC

SK

FD

FD

SK

3"SAN

1 1/2" V

4"S

AN

EWC

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW CONNECTION

PLUMBING SYMBOLS LISTSYMBOL: DESCRIPTION:

COLD WATER - POTABLECW

HOT WATER - POTABLEHW

HOT WATER CIRCULATING - POTABLEHWC

SANITARY DRAINAGESAN

VENTV

PIPE CAP

PIPE DOWN

PIPE UP OR UP/DOWN

PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD

PITCH PIPE IN DIRECTION

DIRECTION OF FLOW IN PIPE

SHUTOFF VALVE NORMALLY OPEN

SHUTOFF VALVE NORMALLY CLOSED

BALANCING VALVE (NO. INDICATES GPM)0.5

CHECK VALVE

BFP BACKFLOW PREVENTER

CO CLEANOUT

FLOOR CLEANOUTFCO

FLOOR DRAINFD

LAVATORYLAV

NC NEW CONNECTION

SINKSK

URINALUR

WATER CLOSETWC

WALL CLEANOUTWCO

ELECTRIC WATER COOLEREWC

VENT THROUGH ROOFVTR

NC

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

P0-1

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

UN

DE

RF

LO

OR

PLA

N -

PLU

MB

ING

- W

AS

TE

NO R HT

1/8" = 1'-0"1UNDERFLOOR PLAN - PLUMBING - WASTE

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

UP

107 SF

PUBLIC LOBBY

101

326 SF

POST PROCESS

102

572 SF

PROCESS

103

283 SF

PRE-PROCESS

104

55 SF

WOMEN

106

218 SF

CBP OFFICE

108

115 SF

HOLDING

112

73 SF

SEARCH

11173 SF

INTERVIEW

110

121 SF

AG LAB

109

78 SF

ENTRY

107

971 SF

CONFERENCE

10555 SF

MEN

105

54 SF

SECURITY

116

81 SF

SUPPLY

114

119 SF

LAN

115

35 SF

ELECTRICAL

113

264 SF

WOMEN

129

161 SF

MEN

130

192 SF

MECH

117

188 SF

MAIN ELECTRICAL

118

389 SF

SPRINKLER/MECH

119

JJ HH GG FF EE DD CC

BB AA

11 SF

MECH

120

5/8

" / 1

'-0

"85 SF

STORAGE

121

1741 SF

CHARTER

122

WC-E WC-E WC-EL-E L-E L-E

WC-E

UR-E UR-E

L-E L-E

3" C.W. LINE

OVERHEAD

3/4" C.W. LINE

OVERHEAD

3" C.W. UP

1" H.W. LINE

3/4" REC. LINE

UP FROM END

OF H.W. LINE

2" C.W.

DOWN

ABOVE CLG.

3/4" C.W.

DOWN

1" H.W.

DOWN

3" C.W. LINE BELOW GRADE.

SEE SITE PLAN FOR

CONTINUATION 115 G.P.M.

1"

P-E

P-E P-E

HB-E

SK-1

SK-1

WC-1

WC-1L-1

L-1

EWC-1

2"C

W

2"CW

3/4"HW

1"H

W

2"CW

3/4"HW

2"CW

1 1/2"CW 3/4"HW

3/4"HWC

2"CW

3/4"HWC

WC-EWC-E

FD-E FD-EFD-E

FD-1

FD-1

GD-1

PUSH BUTTONFLUSH FOR CF-1

CF-1

FD-E

FD-E

FCO-E

0.5

0.5

0.5

REFER TO 1/P5-00FOR GARBAGEDISPOSAL DETAIL.

FD-1

2" V TO3" VTR.

2"V

2"V

2" V TO3" VTR.

2" V DN

2" V DN

2"V

FCO-1

FCO-1

FCO-1

FCO-1

SK-2

L-2

MB-1

FD-1

L-2

FD-1

CONNECT TOEXISTING SAN,VENT, & WATER

FCO-1

FURNISH NEWCONNECTION TOEXISTING HOSEBIBB.

1 1/2" V

EWC-2

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

P1-1

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

FIR

ST

FLO

OR

PLA

N -

PLU

MB

ING

1/8" = 1'-0"1FIRST FLOOR PLAN - PLUMBING

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

GENERAL NOTES :

1. COORDINATE ROOF PENETRATIONS WITHOWNER'S STANDING SEAM ROOFMANUFACTURER.

PLUMBING FIXTURE ROUGH-IN SCHEDULE

FIXTURE DESCRIPTIONDOMESTIC

C.W.(NOTE 3)

DOMESTICH.W.

(NOTE 3)

SANITARY(NOTE 3)

VENT(NOTE 3)

REMARKS

WATER CLOSET 1" - 4" 2" (FLUSH VALVE)

LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2

SINK 1/2" 1/2" 1 1/2" 1 1/2" NOTE 1 & 2 (KITCHEN TYPE SINK)

MOP BASIN 3/4" 3/4" 3" 1 1/2" -

ELECTRIC WATER COOLER 1/2" - 1 1/2" 1 11/4" NOTE 1 & 2

WASHING MACH. FIXTURE 3/4" 3/4" 2" 1 1/4" -

FLOOR DRAIN/FLOOR SINK - - 2" 1 1/2" -

NOTES:

1. SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINIMUM OF 2".2. 1/2" CW AND HW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE. BRANCH PIPING TO VERTICAL

RISE-DROP SHALL BE A MINIMUM OF 3/4" INCH UNLESS NOTED OTHERWISE.

3. SIZES SHOWN ARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED IN THE SCHEDULESHALL DICTATE THE ROUGH-IN SIZE.

PLUMBING MATERIAL LISTTAG DESCRIPTION ACCEPTABLE MANUFACTURERS

CF-1

COMBINATION FIXTURE - CORRECTION STYLE COMBINATIONLAVATORY/TOILET, FRONT ACCESSIBLE, A.D.A - 36" WIDE , 14 GAUGE TYPE 304STAINLESS STEEL, FULLY WELDED SEAMS, SATIN FINISH. ELONGATED BOWLWITH CONTOURED SEAT, BLOWOUT TYPE, INTEGRAL DRAIN WITH AIR VENT,SELF DRAINING SOAP DISH, FLOOR MOUNTED, FLOOR TOILET WASTECONNECTION, REMOTE BUTTON FLUSH VALVE PENAL BUBBLES, DUALTEMPRATURE TRIM WATER SAVING, FLUSH VALVE AND ELBOW WASTETHROUGH THE WALL, P-TRAP AND CLEANOUT, OVERFLOW PREVERNTER, 1.6GALLONS PER FLUSH AND INTEGRAL TISSUE HOLDER.

COMBINATION FIXTURE -WILLOUGHBY ECF-3936-L/R

EWC-1

ELECTRIC WATER COOLER - WALL HUNG, 18 GAUGE STAINLESS STEEL

CABINET AND NON-SPLASH BASIN WITH STAINLESS STEEL FINISH, STREAM

PROJECTOR WITH PROTECTIVE HOOD, PUSH BAR OR LEVER OPERATING

CONTROLS ON FRONT AND SIDES, BUILT-IN FLOW REGULATOR, DRAIN & TRAP

ASSEMBLY, ADJUSTABLE THERMOSTAT, MOUNTING ACCESSORIES, TANKDRAIN AND ANGLE STOPS, HERMETIC COMPRESSOR TO OPERATE ON HFC-134a

REFRIGERANT. COMPLIANT TO LATEST ANSI A117.1 AND ADA STANDARDS.

UNIT SHALL COMPLY WITH FEDERAL ACT S.3874.

UNIT SHALL PROVIDE 8.0 GPH OF WATER FROM 80°F TO 50°F AT 90°F AMBIENT.WATER SYSTEM SHALL BE OF LEAD FREE CONSTRUCTION. TANK SHALL BE

TESTED TO 125 PSIG.

ORIFICE SHALL BE AT 36" (MAXIMUM) ABOVE FINISHED FLOOR. BOTTOM OF

APRON SHALL BE AT 27" ABOVE FINISHED FLOOR IN COMPLIANCE WITHLATEST ADA STANDARDS.

ELECTRICAL REQUIREMENTS - 115V-1 PHASE, CORD AND PLUG, 1/5 HP MOTOR

ELKAY (LZS8), HALSEY-TAYLER(HTHB-HAC8WF), ACORN (A111)

FCO-1

FLOOR CLEANOUT - ADJUSTABLE, CAST IRON HOUSING, ANCHOR FLANGE,

TAPERED THREAD PLUG, SECURED NICKEL BRONZE TOP. TOP STYLE SHALL

MATCH FLOOR FINISH AS FOLLOWS:

UNFINISHED FLOOR - ROUND SOLID SCORIATED TOP

TILE OR TERRAZZO - SQUARE RECESSED TOP

ZURN (Z1400), JOSAM (55000),MIFAB (C1100), SMITH (4000),WADE (6000), WATTS (CO-200)

FD-1FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZE ADJUSTABLE TOP, 6"ROUND, 2" BOTTOM OUTLET, FLASHING COLLAR, DEEP SEAL TRAP.

FLOOR DRAIN - ZURN (Z-415),

SMITH (2005), WADE (1100),

JOSAM (30000), WATTS (FD-100),MIFAB (F1100)

FD-2FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZE ADJUSTABLE TOP, 6"ROUND, 3" BOTTOM OUTLET, FLASHING COLLAR, DEEP SEAL TRAP.

FLOOR DRAIN - ZURN (Z-415),

SMITH (2005), WADE (1100),JOSAM (30000), WATTS (FD-100),

MIFAB (F1100)

GD-1

GARBAGE DISPOSAL - CONTINUOUS FEED UNIT, CORROSION RESISTANT GRIND

CHAMBER, CONTROL CENTER WITH AUTOMATIC REVERSING ACTION, MANUALRESET OVERLOAD PROTECTION, DISPOSER MOUNTING ASSEMBLY, SOLENOID

VALVE, SYPHON BREAKER, FLOW CONTROL VALVE, 1/2" WATER CONNECTION,

SUPPORT LEGS, SERVICE WRENCH, FULL 1 YEAR WARRANTY.

ELECTRICAL REQUIREMENTS - 480V-3 PHASE, HARD-WIRED, 5 HP MOTOR, 11.6AMPS.

IN-SINK-ERATOR (SS-500)

L-1

LAVATORY - COUNTER TOP MOUNTED, OVAL, SELF-RIMMING, WHITE VITREOUS

CHINA, 20"x17", SINGLE FAUCET HOLE.

LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED ,

BRASS CONSTRUCTION, CHROME-PLATED FINISH, RIGID GOOSENECK SPOUT

WITH MINIMUM 5" REACH AND AERATOR, SINGLE HOLE, PERFORATED GRID

STRAINER WITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH

BUILT-IN FILTER, SOLID BRASS THERMOSTATIC MIXING VALVE MEETING ASSE1070 REQUIREMENTS WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND

INTEGRAL CHECK VALVES, WATERPROOF CONNECTORS AND CABLE

MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT

ENCLOSURE BELOW LAVATORY.

MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF

2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH

FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOUNT

MIXING VALVE UNDER COUNTER/LAVATORY. MIXING VALVE SHALL NOT BEWYE PATTERN STYLE.

INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES, AND

SUPPLY LINES.

ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE

SUPPLY LOOSE KEY STOPS, CHROME PLATED SOFT COPPER SUPPLY LINES,

1-1/4" 20 GAUGE CAST BRASS P-TRAP.

ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OF INSULATION KIT.

LAVATORY -

AMERICAN STANDARD (0475.047),GERBER (12-841), KOHLER

(K-2196-1), SLOAN (SS-3102),

TOTO (LT501), ZURN (Z5111)

LAVATORY TRIM - DELTA

(3001T3), AMERICAN STANDARD

(6055.163), CHICAGO FAUCET

(116.203.AB.1), HYDROTEK(HB-6000C-LR), MOEN (8303),

SLOAN (EBF-750), SPEAKMAN

(S-9100), SYMMONS (S-6095),

ZURN (Z6920-XL)

INSULATION KIT - TRUEBRO

(LAV-GUARD), BROCAR

PRODUCTS (TRAP WRAP),

MCGUIRE (PROWRAP),

PLUMBEREX (PRO-EXTREME)

SK-2

SINK - SELF-RIMMING SINGLE COMPARTMENT WITH FAUCET DECK, 18 GAUGE

TYPE 304 STAINLESS STEEL, COMPLETELY UNDERCOATED, 19" (SIDE-TO-SIDE)x 19" (FRONT-TO-BACK) OVERALL SIZE, EACH COMPARTMENT 16" x 13" x 7.5"

DEEP, 3-1/2" DIAMETER DRAIN OUTLET LOCATION IN BOWL.

SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION,

CHROME-PLATED FINISH, GOOSENECK SWING SPOUT, NOMINAL 6" REACH,AERATOR 4" WRISTBLADE HANDLES AT 8" CENTERS, 1/4-TURN OPERATION

CERAMIC DISC CARTRIDGE.

MAXIMUM FLOW TO BE 2.2 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF

2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITHFEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON

PLATE AS REQUIRED.

ACCESSORIES - 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE AND

P-TRAP, QUARTER-TURN BALL VALVE TYPE 3/8" CHROME-PLATED BRASSANGLE SUPPLIES WITH LOOSE KEY STOPS, CHROME-PLATED SOFT COPPER

SUPPLY LINES.

INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES, AND

SUPPLY LINES.

SINK - ELKAY (LR/LK18B), JUST

(SL-J-35 SSF), FRANKE (LBS)

INSULATION KIT - MCGUIRE(PROWRAP), JUST (J-ADA),

PLUMBEREX (PRO-EXTREME),

TRUEBRO (LAV-GUARD2)

SINK TRIM - CHICAGO FAUCET(786), AMERICAN STANDARD(6450), SPEAKMAN (SC-3000SERIES), ZURN (Z831-XL)

PLUMBING MATERIAL LISTTAG DESCRIPTION ACCEPTABLE MANUFACTURERS

SK-1

SINK - SELF-RIMMING DOUBLE COMPARTMENT WITH FAUCET DECK , 18 GAUGE

TYPE 304 STAINLESS STEEL, COMPLETELY UNDERCOATED, 20" (SIDE-TO-SIDE)

x 18 " (FRONT-TO-BACK) OVERALL SIZE, EACH COMPARTMENT 12" x 12" x 7 1/2"DEEP, 3-1/2" DIAMETER DRAIN OUTLET LOCATION CENTERED EACH BOWL,

REMOVABLE TYPE 304 BASKET STRAINERS WITH NEOPRENE STOPPERS.

SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION,

CHROME-PLATED FINISH, CONVENTIONAL SWING SPOUT, NOMINAL 8" REACH,AERATOR FLOW OUTLET, LEVER BLADE HANDLES AT 8" CENTERS, 1/4-TURN

OPERATION CERAMIC DISC CARTRIDGE.

MAXIMUM FLOW TO BE 2.2 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF

2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH

FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEONPLATE AS REQUIRED.

ACCESSORIES - OFFSET 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE

AND P-TRAP, QUARTER-TURN BALL VALVE TYPE 3/8" CHROME-PLATED BRASS

ANGLE SUPPLIES WITH LOOSE KEY STOPS, CHROME-PLATED SOFT COPPERSUPPLY LINES.

INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES, AND

SUPPLY LINES.

SINK -

ELKAY(LR/LK18B), JUST

(DL/J-35-SSF), FRANKE LBD

SINK TRIM -

DELTA (27C2), AMERICAN

STANDARD (7270.000), CHICAGO

FAUCET (786), KOHLER (K-7761),

SYMMONS (S-254), ZURN (Z831-XL)

[INSULATION KIT - MCGUIRE

(PROWRAP), JUST (J-ADA),

PLUMBEREX (PRO-EXTREME),

TRUEBRO (LAV-GUARD2)]

WC-1

WATER CLOSET - ACCESSIBLE, FLOOR MOUNTED, FLUSH VALVE TYPE, WHITE

VITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-1/2" TOP

SPUD, BOLT CAPS.

FLUSH VALVE - FLUSH VALVE - EXPOSED, SENSOR OPERATION, BATTERY

POWERED, 1.6 GALLONS PER FLUSH, 11-1/2" ROUGH-IN, CHROME PLATED, 1"

I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDAL RESISTANT CAP, HIGH

BACK PRESSURE VACUUM BREAKER, ADJUSTABLE TAILPIECE, SPUD

COUPLING AND FLANGE, WALL FLANGE WITH SET SCREW, MECHANICALOVER-RIDE BUTTON, CHLORAMINE RESISTANT MATERIALS, ADA COMPLIANT, 3

YEAR WARRANTY.

SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTION MOLDED SOLID

PLASTIC, SELF-SUSTAINING HINGE, STAINLESS STEEL OR PLATED STEELPOSTS AND NUTS.

CONTRACTOR OPTION: COMBINATION WATER CLOSET/FLUSH VALVE

PACKAGED SYSTEM BY AMERICAN STANDARD, KOHLER, SLOAN, OR ZURN

TOP OF SEAT SHALL BE AT 17"-19" ABOVE FINISHED FLOOR. FLUSH HANDLE

SHALL BE LOCATED ON THE WIDE SIDE OF THE TOILET STALL AND BE 12"

(MAXIMUM) ABOVE BOWL RIM AND OPERATE WITH NO GREATER THAN 5 LB

FORCE IN COMPLIANCE WITH LATEST ADA STANDARDS. VERIFY EQUIPMENT

REQUIREMENTS AND ROUGH-IN LOCATIONS.

WATER CLOSET -

AMERICAN STANDARD (3043.001),

CRANE (3H701), GERBER (25-730),

KOHLER (K-4368), SLOAN

(ST-2023), ZURN (Z5660)

FLUSH VALVE - ZURN

(ZER6000AV), SLOAN (8111),

AMERICAN STANDARD (6065.161),

HYDROTEK (HB-8000C), MOEN

(8310), KOHLER (K-10957-SV-CP)

SEAT -

BEMIS (1655C), CHURCH (9500C),

BENEKE (533), KOHLER(K-4666-C), OLSONITE (95), SAME

AS WATER CLOSET

MANUFACTURER

L-2

LAVATORY - ACCESSIBLE WALL MOUNTED, WHITE VITREOUS CHINA, 20"x18", 4"HIGH CONTOURED BACKSPLASH, SINGLE FAUCET HOLE, DRILLED FOR

CONCEALED ARM CARRIER.

LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED ,

BRASS CONSTRUCTION, CHROME-PLATED FINISH, RIGID GOOSENECK SPOUTWITH MINIMUM 5" REACH AND AERATOR, SINGLE HOLE, PERFORATED GRID

STRAINER WITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH

BUILT-IN FILTER, SOLID BRASS THERMOSTATIC MIXING VALVE MEETING ASSE

1070 REQUIREMENTS WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND

INTEGRAL CHECK VALVES, WATERPROOF CONNECTORS AND CABLE

MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT

ENCLOSURE BELOW LAVATORY.

MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH

FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOUNT

MIXING VALVE UNDER COUNTER/LAVATORY. MIXING VALVE SHALL NOT BE

WYE PATTERN STYLE.

INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND

SUPPLY LINES.

ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE

SUPPLY LOOSE KEY STOPS, CHROME PLATED SOFT COPPER SUPPLY LINES,DRAIN AND OFFSET TAILPIECE, 1-1/4" 20 GAUGE CAST BRASS P-TRAP,

SUPPORT CARRIER.

MOUNT LAVATORY WITH SUPPORT CARRIER BOLTED SECURELY TO FLOOR.

TOP OF RIM SHALL BE AT 34" ABOVE FLOOR IN COMPLIANCE WITH LATEST ADASTANDARD. ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OF

INSULATION KIT.

LAVATORY -

AMERICAN STANDARD (0356.421),

KOHLER (K-2007), SLOAN

(SS-3103), TOTO (LT307), ZURN(Z5361)

LAVATORY TRIM - DELTA(3001T3), AMERICAN STANDARD

(6055.163), CHICAGO FAUCET

(116.203.AB.1), HYDROTEK

(HB-6000C-LR), MOEN (8303),

SLOAN (EBF-750), SPEAKMAN(S-9100), SYMMONS (S-6095),

ZURN (Z6920-XL)

INSULATION KIT - TRUEBRO

(LAV-GUARD), BROCAR

PRODUCTS (TRAP WRAP),MCGUIRE (PROWRAP),

PLUMBEREX (PRO-EXTREME)

WHA-1WATER HAMMER ARRESTER - BELLOWS TYPE, PRE-CHARGED, ALL LEADFREE STAINLESS STEEL CONSTRUCTION, ASSE 1010 APPROVED, PDICERTIFIED, RATED FOR 1-11 FIXTURE UNIT.

ZURN (Z1700), JR SMITH(5005-5050), WADE (W5-100),JOSAM (75000 SERIES),WATTS (SS), MIFAB (WHB)

MB-1

MOP BASIN - PRECAST TERRAZZO, 36"x24"x12", STAINLESS STEEL INTEGRALDRAIN WITH REMOVABLE STRAINER, 3" OUTLET, CONTINUOUS STAINLESS

STEEL CAP ON ALL EDGES.

TRIM - EXPOSED TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION,

CHROME-PLATED FINISH, SINGLE WING HANDLES, 1/4 TURN CERAMIC DISCCARTRIDGE, 3/4" HOSE THREAD SPOUT WITH ASSE 1053 RATED INTEGRAL

VACUUM BREAKER, WALL BRACE, PAIL HOOK, CHECK STOPS OR INLINE

CHECK VALVES TO PREVENT THERMAL CROSSOVER. FAUCET SHALL

COMPLY WITH FEDERAL ACT S.3874.

ACCESSORIES - MOP HANGER, HOSE AND HOSE BRACKET, DEEP SEAL TRAP

MOP BASIN - FIAT (TSB), ACORN(TSH), CREATIVE INDUSTRIES

(MC), WILLIAMS (SB)

TRIM - DELTA (28C2383),

AMERICAN STANDARD (8344.012),MOEN (8124), SPEAKMAN

(SC-5812), SYMMONS (S-2490),

ZURN (Z841M1-XL)

VACUUM BREAKER - WATTS (8A),OR APPROVED EQUAL

EWC-2

ELECTRIC WATER COOLER - WALL HUNG, 18 GAUGE STAINLESS STEEL

CABINET AND NON-SPLASH BASIN WITH STAINLESS STEEL FINISH, STREAM

PROJECTOR WITH PROTECTIVE HOOD, PUSH BAR OR LEVER OPERATING

CONTROLS ON FRONT AND SIDES, BUILT-IN FLOW REGULATOR, DRAIN & TRAPASSEMBLY, ADJUSTABLE THERMOSTAT, MOUNTING ACCESSORIES, TANK

DRAIN AND ANGLE STOPS, HERMETIC COMPRESSOR TO OPERATE ON HFC-134a

REFRIGERANT. COMPLIANT TO LATEST ANSI A117.1 AND ADA STANDARDS.

UNIT SHALL COMPLY WITH FEDERAL ACT S.3874.

BOTTLE FILLING STATION - UNIT MOUNTED, STAINLESS STEEL CONSTRUCTION

AND FINISH, INTEGRAL DRAIN, SENSOR OPERATED WITH AUTOMATIC SHUTOFF,

BOTTLE COUNTER.

UNIT SHALL PROVIDE 8.0 GPH OF WATER FROM 80°F TO 50°F AT 90°F AMBIENT.WATER SYSTEM SHALL BE OF LEAD FREE CONSTRUCTION. TANK SHALL BE

TESTED TO 125 PSIG.

ORIFICE SHALL BE AT 36" (MAXIMUM) ABOVE FINISHED FLOOR. BOTTOM OF

APRON SHALL BE AT 27" ABOVE FINISHED FLOOR IN COMPLIANCE WITHLATEST ADA STANDARDS.

ELECTRICAL REQUIREMENTS - 115V-1 PHASE, CORD AND PLUG, 1/5 HP MOTOR

ELKAY (EZS8), HALSEY-TAYLER(HTHB-HAC8), ACORN (A111)

VACUUM BREAKER W/ANGLE FLANGES

FLOW CONTROL VALVE 8GPM

SOLENOID VALVE

1/2" CW

1-1/4" CW

1/2" HW

WHA-1

1/2"

2" SAN

DISPOSER

BODY WATER INLET @SINK APPLICATIONS

MIXING VALVEWITH INTEGRALCHECK VALVES

SINK BOWL

NOTES:

1. INSTALL VACUUM BREAKER ON WALL MINIMUM 12" ABOVE FLOODRIM OF SINK.

2. ALL EXPOSED PIPING TO BE CHROME PLATED.

THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLYOPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.

CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THECONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FORCOMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONSBEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THECATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLESTATE, LOCAL AND GOVERNING AUTHORITIES.

ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874

PLUMBING FIXTURE SCHEDULE GENERAL NOTES

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

P5-0

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AD

DE

W

13-1

27

BID

SE

T -

12/1

7/1

5

PLU

MB

ING

MA

TE

RIA

L L

IST

NO SCALE1GARBAGE DISPOSER GD-1 PIPING DETAIL

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01

JJ HH GG FF EE DD CC

BB AA

3/4" C.W. LINE

OVERHEAD

1" H.W. LINE

3" C.W. LINE BELOW GRADE.

SEE SITE PLAN FOR

CONTINUATION 115 G.P.M.

1"

WC-E WC-E

FD-E

WC-E WC-EL-E L-E L-E WC-E

UR-E UR-E

L-E L-E

FCO-E

3" C.W. LINE

OVERHEAD

3" C.W. UP

3/4" REC. LINE

UP FROM END

OF H.W. LINE

2" C.W.

DOWN

ABOVE CLG.

3/4" C.W.

DOWN

1" H.W.

DOWN

P-E

P-E P-E

P-E

WC-E

FD-E

FD-E

FD-E

REMOVE EXISTINGFLOOR DRAIN ANDREPLACE WITH FCO-1.

REMOVE EXISTINGPIPE DOWN TOEXISTING HOSE BIBB.RECONNECT IN NEWWALL.

SH

EET N

UM

BER:

PRO

JECT N

UM

BER:

DATE:

PRO

JECT D

ESCRIP

TIO

N:

PRO

JECT A

RCH

ITECT:

DRAW

N B

Y:

CH

ECKED

BY:

THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.

COPYRIGHT 2015 ©

THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW

430 S

. G

LE

NS

TO

NE

AV

E. S

PR

ING

FIE

LD

, M

O 6

5802

PH

: 417.8

85.0

002 F

AX

: 417.8

68.0

072

ww

w.p

ara

gonarc

hitectu

re.c

om

MIS

SO

URI

STATE C

ERTIF

ICATE O

F A

UTH

ORIT

Y #

2010011426

PD

1-1

0S

GF

Airport

CB

P/F

IS

23

00

N. A

IRP

OR

T B

LV

D.

SP

RIN

GF

IEL

D, M

O 6

58

02

WA

DR

OS

PA

RA

GO

N

AN

DD

EW

13-1

27

BID

SE

T -

12/1

7/1

5

FIR

ST

FLO

OR

PLA

N -

PLU

MB

ING

- D

EM

OLIT

ION

NO R HT

1/8" = 1'-0"1FIRST FLOOR PLAN - PLUMBING - DEMOLITION

REFERENCE SCALE IN INCHES

0 1 2 3

ENGINEERINGCONSULTANTS

Missouri State Certificate of Authority #2003008820

309.788.0673 FAX: 309.786.5967www.kjww.com

623 26TH AVENUEQUAD CITIES, ILLINOIS 61201

PROJECT #

KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.

The FUTURE.Built SMARTER.

®

14.0259.01