UP
FIRE SPRINKLER USAGE SCHEDULE
AREA TYPE(NOTE 1 & 6)
AREA HAZARD
SPRINKLER
MANUFACTURER & MODEL REMARKSSYMBOL
(NOTES 4 & 5)TYPE RESPONSE FINISH
TEMPERATURE°F
GENERAL SEE PLANS SPR-1 UPRIGHT QUICK ROUGH BRASS 175 VIKING VK, RELIABLE F1FR,TYCO TY-FRB, VICTAULIC V2704
NOTE 3
GENERAL SEE PLANS SPR-2 CONCEALED QUICK WHITE 175 VIKING VK, RELIABLE G4A,TYCO RFII, VICTAULIC V3802
NOTE 3
DETENTION SEE PLANS SPR-3 CONCEALED QUICK WHITE 165 VIKING QR , RELIABLE XL , TYCO RAVEN NOTES 3
NOTES:1. SEE FLOOR PLANS FOR ZONING REQUIREMENTS.
2. SPRINKLER SHALL HAVE COLOR CODED BULB THERMAL ELEMENT.
3. ALL SPRINKLERS SHALL BE UL LISTED.
4. CONTRACTOR TO VERIFY SPRINKLER REQUIREMENTS BASED ON ACTUAL INSTALLATION, USAGE, ARCHITECTURAL CEILING PLAN AND NFPA 13 REQUIREMENTS.5. SYMBOL IS PRIMARILY FOR INDENTIFYING SPRINKLERS IN SUBMITTALS. IT MAY OR MAY NOT BE FOUND ELSEWHERE ON THE DRAWINGS. CONTRACTOR TO SUBMIT ALL SPRINKLER TYPES TO BE USED.
6. AREAS ARE GENERAL IN NATURE. CONTRACTOR TO MATCH UNSCHEDULED AREAS TO SIMILAR SPACES.
SYMBOL: DESCRIPTION:
FIRE PROTECTIONFP
NO HATCH LIGHT HAZARD
ORDINARY GROUP 2
SPRINKLER
SPRINKLER
SPRINKLER
BFP BACKFLOW PREVENTER
FIRE PROTECTION SYMBOLS LIST
DIRECTION OF FLOW IN PIPE
CHECK VALVE
ELECTRICAL CONTRACTORE.C.
FLOOR DRAINFD
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
107 SF
PUBLIC LOBBY
101
326 SF
POST PROCESS
102
572 SF
PROCESS
103
283 SF
PRE-PROCESS
104
55 SF
WOMEN
106
218 SF
CBP OFFICE
108
115 SF
HOLDING
112
73 SF
SEARCH
11173 SF
INTERVIEW
110
121 SF
AG LAB
109
78 SF
ENTRY
107
971 SF
CONFERENCE
10555 SF
MEN
105
54 SF
SECURITY
116
81 SF
SUPPLY
114
119 SF
LAN
115
35 SF
ELECTRICAL
113
264 SF
WOMEN
129
161 SF
MEN
130
192 SF
MECH
117
188 SF
MAIN ELECTRICAL
118
389 SF
SPRINKLER/MECH
119
JJ HH GG FF EE DD CC
BB AA
11 SF
MECH
1205
/8"
/ 1
'-0
"
85 SF
STORAGE
121
1741 SF
CHARTER
122
SD
SD4
4
LOCATION OF FIREPROTECTIONCYLINDERS.
2
3
5
1
KEYNOTES:
1. NUMBER AND SIZE OF CYLINDERS TO BEPROVIDED BY THIS MANUFACTURER AND MAYVERY FROM WHAT IS SHOWN. SECURECYLINDERS AS REQUIRED BY NFPA.
2. AUDIO HORN/VISUAL DEVICE AND ALARM BELLFOR CLEAN AGENT SYSTEM.
3. MANUAL RELEASE STATION.4. SMOKE DETECTOR FOR CLEAN AGENT SYSTEM.5. CONTROL PANEL FOR CLEAN AGENT SYSTEM.6. REPLACE SPRINKLERS IN EXISTING AREA
UNDER BID ALTERNATE.7. REPLACE SPRINKLERS BETWEEN COLUMN
LINES FF AND JJ WITH NEW SPRINKLERS.BRANCH PIPING MAY REMAIN.
8. PROVIDE CLEAN AGENT SYSTEM IN LAN 115ROOM. SEAL ALL NEW AND EXISTINGPENETRATIONS INTO ROOM AIR TIGHT. REFERTO SPECIFICATIONS SECTION 21 22 00.
9. PROVIDE DETENTION STYLE SPRINKLER INSPACE.
#
ZONE
1
EXISTING AIR
COMPRESSOR
BID ALTERNATE
6
7
9
9
9
9
8
EXISTING FIRE
DEPARTMENT
CONNECTION
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
FP
1-1
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
FIR
ST
FLO
OR
PLA
N -
FIR
E P
RO
TE
CT
ION
NO R HT
1/8" = 1'-0"1FIRST FLOOR PLAN - FIRE PROTECTION
GENERAL SHEET NOTES1. REFER TO FPD1-10 FOR EXTENT OF
SPRINKLERS BEING REPLACED. CURRENTSYSTEM IS A DRY PIPE SPRINKLER SYSTEM.
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
JJ HH GG FF EE DD CC
BB AA
KEYNOTES:
1. REMOVE AND REPLACE SPRINKLER HEAD ANDBRANCH PIPING IN THIS AREA AS REQUIRED FORNEW ROOMS AND CEILING LAYOUT.
2. SPINKLER HEADS IN THIS AREA TO REMAIN.3. REMOVE AND REPLACE SPRINKLERS UNDER BID
ALTERNATE.
1 2
1
2
BID ALTERNATE
3
2 2
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
FP
D1-1
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
FIR
ST
FLO
OR
PLA
N -
FIR
E P
RO
TE
CT
ION
- D
EM
OLIT
ION
NO R HT
1/8" = 1'-0"1FIRST FLOOR PLAN - FIRE PROTECTION - DEMOLITION
GENERAL SHEET NOTES
1. SYSTEM IS CONNECTED TO DRY PIPE. NEW TOREMAIN ON DRY SYSTEM.
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
UP
T
T
T
T
T
T
T
T
T
T
TT
T
107 SF
PUBLIC LOBBY
101
326 SF
POST PROCESS
102
572 SF
PROCESS
103
283 SF
PRE-PROCESS
104
55 SF
WOMEN
106
218 SF
CBP OFFICE
108
115 SF
HOLDING
112
73 SF
SEARCH
11173 SF
INTERVIEW
110
121 SF
AG LAB
109
78 SF
ENTRY
107
971 SF
CONFERENCE
10555 SF
MEN
105
54 SF
SECURITY
116
81 SF
SUPPLY
114
119 SF
LAN
115
35 SF
ELECTRICAL
113
264 SF
WOMEN
129
161 SF
MEN
130
192 SF
MECH
117
188 SF
MAIN ELECTRICAL
118
389 SF
SPRINKLER/MECH
119
JJ HH GG FF EE DD CC
BB AA
11 SF
MECH
120
5/8
" / 1
'-0
"
85 SF
STORAGE
121
1741 SF
CHARTER
122
16x18
6x6
6x6
EG-1
6x6/70
8x8 EA UPTO EF-2
EG-3
8x8/100EG-3
6x6/75
12x10 EA UP TO EF-1FURNISH SECURITYBAR AT ROOF LEVEL.
FUME HOOD MODEL TO BEKEWAUNEE H05G5448-00 ,CONTRACTOR INSTALLED.BALANCE TO 810 CFM.
CU-1
CRU-1
SG-ESG-ESG-ESG-E
40x18
SB
REFER TO 2/M3-01 FORSECURITY BAR DETAIL.(TYP.)
NC
TG-E TG-E
TG-E
EF-E
TG-E
EG-E
10x10/270
(TYP.2)
EG-E
10x10/325
12x1412x14
SG-E
12x12/85
SG-E
10x10/140 12x12
CU-2
EF-EL-E
L-E18x30 UP TO OAH-1
SG-1
9x9/80
SG-1
9x9/160
8x88x8
TAB-114
SB
SG-1
6x6/75
SG-1
6x6/75
8x8 6x6
TAB-113
SG-2
8x8/100
TAB-106
SG-1
9x9/165
TAB-105
TAB-104
10x10
CD-1
10/250
LD-1
8/130(TYP.3)
12x12
10x8
TAB-101
14
x1
21
8x1
2
SG-2
8x8/200(TYP.2)
TAB-112
CD-1
8/250
TAB-107
20ø26x20
TAB-111
12x12
12
x1
2
16
ø
TAB-108
TAB-110
CUH-1
IDAC-3
RELOCATE IDAC-3TO THIS LOCATION.
IDAC-4
RELOCATE EXISTING OUTDOORCONDENSING UNIT TO THIS LOCATION.REROUTE PIPING TO IDAC-4. FURNISHNEW HOUSEKEEPING PAD
EF-E
KEEP TOP OF DUCT TIGHTTO BOTTOM OF BEAM.
KEEP TOP OF DUCT TIGHTTO BOTTOM OF BEAM.
CD-1
8/225
CD-1
8/225
ODAC-4
RELOCATE EXISTINGOUTDOORCONDENSING UNIT TOTHIS LOCATION.REROUTE PIPING TOIDAC-3. FURNISH NEWHOUSEKEEPING PAD.
EG-1
6x6/70
SB
SB SB
SB
1
KEYNOTES:
1. FURNISH EXHAUST AIR TEMPERATURE SENSORIN DUCT ABOVE ACCESSIBLE CEILING.
#
12x8 EA UP TO EF-3FURNISH SECURITYBAR AT ROOF WALL
12x8
EG-3
12x12/260 8x8
18x30 UP TO EAH-1
12ø
SG-2
10x6/200(TYP. 3)
SG-2
10x10/300(TYP. 2)
12ø
REFIGERANT PIPING SIZE ANDROUTE PER MANUFACTURER'SRECOMMENDATIONS
AHU-1
30x18 RA, PROVIDEBELLMOUTH OPENING.
PROVIDE GALVANIZEDSHEETMETAL ENCLOSURE.
14
ø
SG-2
12x10/325(TYP.3)
8x8
CD-1
6/100
20
x1
4
12x10
LD-1
8/125(TYP.2)
CD-1
10/300(TYP.4)
LD-1
8/135
20
x1
4
12x10
LD-1
8/130
LD-1
8/135
10x10
FURNISH NEWHOUSEKEEPING PAD
CUH-2
FURNISH NEWHOUSEKEEPING PAD
REFER TO 1/M3-00 FORELBOW CONSTRUCTIONDETAIL. (TYP.)
REFER TO 2/M3-00 FORBRANCH CONNECTIONDETAIL. (TYP.)
REFER TO 3/M3-00 FOR FLEXDUCT CONNECTION DETAIL.(TYP.)
REFER TO 5/M3-00 FORDIFFUSER CONNECTIONDETAIL. (TYP.)
REFER TO 4/M3-00 FORSLOT DIFFUSER MOUNTINGDETAIL. (TYP.)
REFER TO 3/M3-01 FOR AIRHANDLING UNIT DETAIL AND1/M3-01 FOR CONDENSATETRAP DETAIL.
EXISTING HEATER (TYP.)
NEW DDC CONTROLPANELS
CD-1
10/310
CD-1
10/315
CD-1
10/310
CD-1
10/315
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE REMOVED
NEW DUCT
FABRIC DUCT CONNECTION
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DROP IN DIRECTION OF AIR FLOWD
DUCT CAP
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
CD-16/115
AIR TERMINAL PROPERTIES SYMBOLNECK SIZE/CFM
THERMOSTAT/SENSORT
VENTILATION SYMBOLS LISTSYMBOL: DESCRIPTION:
SECURITY BARSB
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
M1-1
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
FIR
ST
FLO
OR
PLA
N -
VE
NT
ILA
TIO
N
NO R HT
1/8" = 1'-0"1FIRST FLOOR PLAN - VENTILATION
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
GENERAL NOTES :
1. COORDINATE ROOF PENETRATIONS WITHOWNER'S STANDING SEEM ROOFMANUFACTURER.
2. ALL EXPOSED DUCTWORK BETWEEN COLUMNLINE HH & FF SHALL BE "ARCHITECTURALLYEXPOSED" PER 23 31 00.
RECTANGULARMITERED ELBOW
WITH VANESTYPE RE2
RECTANGULARMITERED ELBOW
TYPE RE6
USE ONLY AS PART OF OFFSETSAND TRANSITIONS PER FIGURE4-7 TYPE 2 OR AS SHOWN ONDRAWINGS. OFFSETS ABOVE 30°SHALL BE TYPE RE1.
RECTANGULARRADIUS ELBOW
TYPE RE1
R/W = 1.0 (MINIMUM)R/W < 1.0 SHALL BE TYPE RE3
RECTANGULARRADIUS ELBOW WITH VANES
TYPE RE3
REFER TO SMACNA HVAC SYSTEMS DUCT DESIGN MANUAL, FOURTHEDITION, SECTION 5.14 "SPLITTER VANES" AND SMACNA HVAC DUCTCONSTRUCTION STANDARDS, THIRD EDITION, FIGURES 4-2 AND 4-9 ANDCHARTS 4-1 AND 4-1M. ELBOW SHALL HAVE THREE SPLITTER VANESAND r/W = 0.10 (R/W = 0.60) UNLESS NOTED OTHERWISE.
NOTES:
1. BEAD, CROSSBREAK, AND REINFORCE FLAT SURFACES AS IN STRAIGHT DUCT.2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.3. DEFAULT ELBOW SHALL BE TYPE "RE1".4. ELBOW TYPES SHALL BE INSTALLED AS SHOWN AND NOT BE SUBSTITUTED
WITHOUT PERMISSION. EXCEPTION: RE1 OR RE3 MAY BE SUBSTITUTED FORRE2.
RECTANGULARRADIUS ELBOW WITH
SQUARE THROAT
NOT ALLOWED
RECTANGULAR / OVAL / ROUNDMITERED ELBOWWITHOUT VANES
TYPE RE4
NOT ALLOWED
OVAL / ROUNDRADIUS ELBOW
SMOOTH OR 5 GORE (MINIMUM)
R/W = 1.5 (MINIMUM)
W W
R
R
W
r R1 R
2
R R3
W
W
30°
EX
CE
ED
NO
T T
O
W
W
90°
90°
W
W
SHEETMETAL ELBOW
NOTES:
1. TO ATTACH FLEX DUCT TO THE HARD DUCT, TAPE THE INNER LINERTO THE HARD DUCT THEN ATTACH WITH TWO NYLON TIE WRAPS;ONE FOR THE INNER LINER AND ONE FOR THE OUTER SHELL.FOLD THE OUTER SHELL INSIDE ITSELF SO IT HAS NEAT EDGESPRIOR TO TIE WRAPPING.
2. "SMARTFLOW" ELBOW (WWW.HARTANDCOOLEY.COM) AND"FLEXRIGHT" (WWW.TITUS-HVAC.COM) ARE ACCEPTABLEPRODUCTS FOR DURABLE ELBOW SUPPORT.
R = DUCT DIA.
FLEXIBLE DUCT
INSULATION
CEILING
STRUCTURE
DIFFUSER
D1>D2
45 DEGREE
BUTT FLANGESTRAIGHT TAP
ENTRY Θ 45°45 DEGREE CONICAL
CLINCH LOCK
CORNER FILLERPIECE OR USEGASKET (TYP.)
45 DEGREE LEAD IN
NOTES:
1. DO NOT USE CONNECTIONS WITH SCOOPS.2. FIT ALL CONNECTIONS TO AVOID VISIBLE OPENINGS AND
SECURE THEM SUITABLY FOR THE PRESSURE CLASS.3. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DOVETAIL JOINT
LINED DUCT CONNECTION(NO EXPOSED LINER EDGES)
DUCT LINER
FLANGED
NOTE: STRAIGHT TAP WITH BUTTFLANGE FOR BRANCH AND TEECONNECTION IN RECTANGULAR DUCTSUNDER 1" PRESSURE CLASS ONLY.
ENTRY Θ 45°
D1
W
L
Θ
D2
(L = 4" OR W/4; WHICHEVER IS LARGER)
3"
NYLON TIE WRAP, TWO REQUIREDFOR EACH END OF FLEXIBLEDUCT (TOTAL 2). INSTALL ONE TIEWRAP TO SECURE THE INNERLINER AND ONE TO SECURE THEOUTER SHELL. (TYP.)
SPOT WELD EXTENSIONS TOINSIDE OF CONNECTOR.
1 1/2" 28 GAUGE GALVANIZEDEXTENSIONS WITH 1 1/2" DEEPNOTCHES. (LOOKS LIKE THISBEFORE BENDING TABS DOWN.)
BEND TABS DOWN CLAMPINGCONNECTORS SECURELY TODUCT LINER.
CUT INSIDE CARRIER DUCTAT THIS POINT
26 GAUGE GALVANIZEDSHEET METAL DUCT.SAME DIAMETER ASFLEX DUCT.
NOTES:
1. THIS DETAIL APPLIES ONLY TO TAPS OFF LINED DUCTS.2. TAP DOES NOT NEED TO BE CONICAL IF THE TAP IS NOT LOCATED
BETWEEN FANS AND TERMINAL AIR BOXES, DUCT IS NOT OVER 2"PRESSURE CLASS, AND ROUND DUCT IS NOT OVER 12" DIAMETER.
WRAP INSULATION (REFER TOSPECIFICATION SECTION 15890)(SECTION 23 31 00 - DUCTWORK)
INSULATED FLEX DUCT
GALVANIZED SHEET METAL DUCT
NYLON TIE WRAP
6" (MIN.)
D D+
2"
FLEXIBLE DUCT
2 LAYERS OFDUCT TAPE
ROUND INLET(OVAL IS NOTACCEPTABLE)
NYLON TIE WRAPSECURE TO INLET
ACOUSTICTILE BY G.C.
TEES FURNISHEDWITH DIFFUSER.
LIGHT FIXTUREBY E.C.
TEES 24" O.C.BY G.C. (TYP.)
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
M3-0
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
ME
CH
AN
ICA
L D
ET
AIL
S
NO SCALE1ELBOW CONSTRUCTION
NO SCALE5DIFFUSER CONNECTION DETAIL
NO SCALE2BRANCH CONNECTIONS
NO SCALE3FLEX DUCT CONNECTION (CONICAL/LINED)
NO SCALE4SLOT DIFFUSER MOUNTING DETAIL
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
NOTES:
1. ANCHORAGE TO CONCRETE WALL OR SOLID BRICK, USEEXPANSION ANCHORS 3/8"ø (MIN.)
2. ANCHORAGE TO HOLLOW CONCRETE BLOCK, USETOGGLE BOLT (CARBON STEEL) 5/8"ø (MIN.)
3. ANCHORAGE TO METAL STUDS AND GYP. BOARD WALLS,USE CARBON STEEL THROUGH BOLT, 3/8"ø (MIN.)
REFER TO SPECIFICATION SECTION 23 33 00FOR SECRUTY BAR REQUIREMENTS.
WRAP INSULATION ALL AROUNDDUCT AND SLEEVE ON BOTH SIDESOF WALL. (REFER TO SPEC SECTION23 31 00 FOR REQUIREMENTS)
3" x 2 1/2" x 3/16" ANGLE FRAME CONTINUALLYWELDED AT CORNERS AND SEAMS. SECUREANGLES @ 100mm O.C. MIN. ANGLES MUSTLAP STRUCTURAL OPENING 75mm MINIMUM
3/16" STEEL SLEEVE CONTINUALLYWELDED AT CORNERS OR SEAMS.EXTEND 3" EACH SIDE FROM WALL
SECURE DUCT TO SLEEVE, INSTALLTAPE ALONG ENTIRE PERIMETEROF THE DUCT SEAM TO SLEEVE.
PLAN VIEW
ELEVATION VIEW
DX
CO
OL
ING
CO
IL S
EC
TIO
N
AC
CE
SS
SE
CT
ION
SA - 4,800 CFM(2,200 CFM MIN.)
OA - 1,400 CFM EA - VARIES RA - 3,600 CFM(1,000 CFM MIN.)
SUPPLY FAN RETURN FAN
RELIEF AIRSECTION
MIXINGAIR &
FILTERSECTION
ELECTRICHEAT
AC
CE
SS
SE
CT
ION
SUPPLY FAN RETURN FANRELIEF AIRSECTION
MIXING AIR &FILTER SECTION
CONTROLLER
DX
CO
OLIN
G C
OIL
EL
EC
TR
IC H
EA
T
18'-0" MAX.
6'-0
" M
AX
.
3”
CLEANOUT PLUG (TYP.)
ROUTE TO WITHIN TENFEET OF ROOF DRAIN (IFROOFTOP UNIT). OR TOFLOOR DRAIN IF UNIT ISLOCATED INSIDE.
FULL SIZE CONDENSATEDRAIN, CONNECT TO DRAINPAN AS RECOMMENDED BYMANUFACTURER.
1.5
"
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
M3-0
1S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
ME
CH
AN
ICA
L D
ET
AIL
S
NO SCALE2SECURITY BAR DETAIL
1/2" = 1'-0"3AIR HANDLING UNIT AHU-1
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
NO SCALE1CONDENSATE TRAP DETAIL (DRAW-THROUGH)
COMPUTER ROOM UNIT SCHEDULE - DIRECT EXPANSION
SYMBOL SERVICE CFMEXT. S.P.IN. W.C.
REFRIGERANT COOLING COIL FILTERS ELECTRICAL
MANUFACTURER MODEL REMARKSCOIL TYPE &REFRIGERANT
# OFCIRCUITS
EAT MBHTYPE HP
VOLT-PHASE
FLA/RLA
MCAMOCPAMPS
DISCONNECT CONTROLLER/STARTER
°FDB °FWB TOTAL SENSIBLE BY (NOTE A) BY (NOTE A) SCCR
CRU-1 SECURITY/LAN 750 0.3 R-407C 1 80 62.8 19,300 19,300 MERV 8 0.2 208-1 1.4 1.8 15.0 MFR MFR 3.6 LIEBERT MINI-MATE 2
NOTES:
1. CRU-1 CONTROLS TO BE PROVIDED WITH UNIT. FMCS TO MONITOR SPACE TEMPERATURE AND TO SEND ALARM UPON OCCURRENCE OF ANY OF THE FOLLOWING CONDITIONS:LOSS OF POWER TO CRU, HIGH TEMPERATURE, LOW TEMPERATURE, HIGH HUMIDITY OR LOW HUMIDITY.
HOOD & LOUVERED PENTHOUSE SCHEDULE
SYMBOL SERVICE CFMTHROAT
SIZE (IN)
STATICPRESSURE
(IN W.C.)
FREEAREA(FT2)
TYPE
MAX. HEIGHT(TOP OF CURB
TO TOP OFEQUIPMENT)
DAMPERTYPE
CURB(NOTE G)
MANUFACTURER MODEL REMARKS
OAH-1 AHU-1 6,000 18x42 0.15 10.6 ROOF HOOD 16" ELECTRIC MFR COOK GI NOTE 1 & 2
EAH-1 AHU-1 6,000 18x42 0.10 6.8 ROOF HOOD 13" ELECTRIC MFR COOK GR NOTE 1 & 2
NOTES:
1. ELECTRIC DAMPER TO HAVE 24V ACTUATOR.
2. MINIMUM 12" ROOF CURB.
CONDENSING UNIT SCHEDULE
SYMBOL SERVICENOMINALDESIGNTONS
REFRIGERANTSATURATEDSUCTION °F
AMBIENTTEMP. °F
MINIMUMAMBIENTTEMP. °F
NUMBER OFCOMPRESSORS
NUMBEROF
STAGES
NUMBEROF
CIRCUITS
NUMBEROF
FANS
ELECTRICAL
MANUFACTURER MODEL REMARKSVOLT-PHASE RLA
MCAMOCPAMPS
DISCONNECT
BY (NOTE A) TYPE (NOTE B)
CU-1 SECURITY/LAN 1.5 R-407C 95 -20 1 1 1 1 208-1 12.1 14.8 25.0 MFR NF LIEBERT PFH
CU-2 AHU-1 20 R-410A 45 95 0 2 1 2 2 460-3 37.2 46.9 60.0 MFR NF TRANE TTA240 NOTE 1
NOTES:
1. PROVIDE ADIABATIC PROPORTIONING REFRIGERATION (APR) CONTROL TO MODULATE REFRIGERATION CAPACITY. EACH COMPRESSOR CIRCUIT SHALL HAVE APR CONTROL, PROVIDE RAWAL MODEL APR-410-6 OR EQUAL (WWW.RAWAL.COM).
GRILLES REGISTERS & DIFFUSERS SCHEDULE
SYMBOL MAT'L TYPE MARGIN(NOTE 1)
INLETSIZE
(INCH)
FACESIZE
(INCH)
VOLUMEDAMPER
REQ'DFINISH MANUFACTURER MODEL REMARKS
CD-1 STEEL PANEL FACE LAY-IN SEE DWG. 24x24 NO WHITE TITUS OMNI FLUSH FACE PANEL
RG-1 STEELPERFORATED
FACELAY-IN N/A 24x24 NO WHITE TITUS PXP FACE ONLY - NON DUCTED
SG-1 STEELPERFORATED
FACE 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS SG-PR MAXUMUM SECURITY GRILLE
SG-2 STEELSINGLE
DEFLECTION 1 1/4' SEE DWG. INLET +2 YES WHITE TITUS 301R BLADES VERTICAL UNLESS NOTED OTHERWISE
EG-1 STEEL 35° DEFLECTION 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS 350R
EG-2 STEEL PANEL FACE 1 1/4" SEE DWG. 24x24 YES WHITE TITUS PXP
EG-3 STEELPERFORATED
FACE 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS SG-PR MAXUMUM SECURITY GRILLE
NOTES:
1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.
2. ALL RUN OUT DUCTWORK TO DIFFUSERS SHALL BE NECK SIZE UNLESS OTHERWISE NOTED.
FAN SCHEDULE
SYMBOL SERVICE CFMS.P.IN.
W.C.
WHEELDIA.
INCHES
FANRPM
(NOTE F)DRIVE
MAX.AMCASONES
BACKDRAFTDAMPER
CURBTYPE
(NOTE G)
ELECTRICAL
MANUFACTURER MODEL REMARKSBHP(NOTE E)
MHP(NOTE E)
VOLT-PHASE
DISCONNECT CONTROLLER/STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)
EF-1 AG LAB 810 .35 12.0 1,028 DIRECT 5.4 ELECTRIC MFR 0.078 0.167 115-1 EC NF MFR VSC COOK ACED NOTES 1 & 2
EF-2 RESTROOMS 140 0.5 9.0 1,300 DIRECT 7 ELECTRIC MFR 92(W) 1/8 115-1 EC NF MFR FV COOK ACED NOTES 2 & 3
EF-3 INTERVIEW 435 0.5 9.0 1,450 DIRECT 7 ELECTRIC MFR 92(W) 1/8 115-1 EC NF MFR FV COOK ACED NOTES 2 & 3
NOTES:
1. REFER TO DETAIL 1/M6-01 FOR FAN CONTROL DIAGRAM.
2. FURNISH FAN SPEED CONTROLLER
3. REFER TO DETAIL 2/M6-01 FOR FAN CONTROL DIAGRAM.
SCHEDULE GENERAL NOTES:A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND
INSTALLED BY:
MFR = MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED
BY ELECTRICAL CONTRACTOR
MFR/EC = FURNISHED LOOSE BY MANUFACTURER
INSTALLED BY ELECTRICAL CONTRACTOR
ATC = AUTOMATIC TEMPERATURE CONTROL CONTRACTOR
B. DISCONNECT TYPE:
F = FUSED
NF = NON-FUSED
C. CONTROLLER STARTER TYPE:
FV = FULL VOLTAGE
WYE = WYE-DELTA
SS = SOLID STATE (SOFT START)
MS = MANUAL STARTER
VFD = VARIABLE FREQUENCY DRIVE
VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
VSC = VARIABLE SPEED CONTROLLER
D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE,
WITH THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS
FANS FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR
NAME PLATE RATING.
F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
G. CURB TYPE:
MFR = STANDARD CURB BY MANUFACTURER
GC = BY GENERAL CONTRACTOR
SAC = SOUND ATTENUATOR CURB
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
M5-0
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
ME
CH
AN
ICA
L S
CH
ED
ULE
S
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
AIR HANDLING UNITSCHEDULE - ELECTRIC
SYMBOL AHU-1
SERVICEFLIGHT PASSENGER
PROCESSING
SUPPLY FAN
CFM 4,800
MINIMUM CFM 2,200
EXTERNAL STATIC PRESSURE 1.50
TYPE FC
FAN RPM (NOTE D) 1,800
BHP (NOTE E) 5.62
MHP (NOTE E) 7.5
RETURN FAN
CFM 3,600
MINIMUM CFM 1,400
EXTERNAL STATIC PRESSURE 1.00
TYPE FC
FAN RPM (NOTE D) 1,800
BHP (NOTE E) 1.53
MHP (NOTE E) 2
MINIMUM OUTSIDE AIR CFM 1,400
HEATING - ELECTRICAL
EAT °F DB 52
MAX. LAT °F DB 65
MINIMUM OUTPUT KW 20
STAGES SCR
COOLING COIL - DX
EAT °F DB 82.5
EAT °F WB 68
MAX. LAT °F DB 55
LAT °F WB 53.8
TOTAL MBH 212
AMBIENT TEMPERATURE °F 95
MAX. A.P.D. IN. W.C. 0.32
REFRIGERANT R410A
FILTER
TYPE 2" MERV 8
VELOCITY 360 FPM
VIBRATION ISOLATION
TYPE M3
DEFLECTION 0.75"
ELECTRICAL
VOLT-PHASE 460-3
MANUFACTURER TRANE
MODEL NUMBER CSSA 12
REMARKS NOTES 1 & 2
NOTES:
1. LAT LISTED IS AT LEAVING SIDE OF COOLING COIL.
2.PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTORSPECIFICATION 23 05 13.
LINEAR DIFFUSER SCHEDULE
SYMBOL MATERIALSLOT
WIDTHNO.
SLOTSBAR
WIDTHBAR
SPACINGWIDTHINCHES
LENGTHFEET
PLENUMREQUIRED
PLENUMINSULATION
PLENUMINLET SIZE
PATTERNCONTROLREQUIRED
BALANCINGDAMPER
REQUIREDFINISH MANUFACTURER MODEL REMARKS
LD-1 ALUMINUM 1" 2 N/A N/A 4 7/16 4 YES LINED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2 & 3
NOTES:
1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.
2. PROVIDE WITH CONCEALED FASTENERS.
3. DIFFUSERS WITH MULTIPLE SLOTS SHALL HAVE THE INNER MOST SLOT DIRECTED TOWARDS THE INTERIOR OF THE BUILDING, THE REMAINING SHALL BE DIRECTED TOWARDS THE EXTERIOR UNLESS NOTED OTHERWISE.
CABINET UNIT HEATER SCHEDULE - ELECTRIC
SYMBOL SERVICE TYPE CFM STAGES
ELECTRICAL
TSTAT LOCATION MANUFACTURER MODEL REMARKSFAN HP KW
VOLT/PHASE
FLA/RLA
DISCONNECT CONTROLLER/STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A)
CUH-1 ENTRY CEILING 285 3 0.1 5.0 277-1 18.0 MFR. NF MFR WALL BERKO FFCH NOTE 1 & 2
CUH-2 TOILET WALL 100 1 0.1 1.5 110-1 12.5 MFR. NF MFR INTEGRAL BERKO FRC
NOTES:
1. RECESSED WITH BOTTOM INLET AND OUTLET
2. REFER TO 6/M6-01 FOR CONTROL SEQUENCE.
TERMINAL AIR BOX SCHEDULE - SINGLE DUCT ELECTRIC REHEATSYMBOL
AREA SERVED
CFM HEATING COILMIN.
INLETSIZE(IN.)
CONTROLTYPE
(NOTE 3)
SENSORTYPE
(NOTE 4)MANUFACTURER MODEL REMARKS
###COOLING
MAX.HEATING
MAX.MIN.
EAT°F
LAT°F
KWVOLT/
PHASE/WIRE
DISCONNECTNO. OFSTEPSBY
(NOTE A)TYPE
(NOTE B)
101 117 MECH 400 400 150 55 95 5.0 277-1 MFR NF NOTE 5 8 A 2 TRANE VCEF NOTE 1 & 2
104 108 CBP OFFICE 640 640 240 55 95 7.5 277-1 MFR NF NOTE 5 8 A 4 TRANE VCEF NOTE 1 & 2
105 109 AG LAB 165 50 50 55 95 0.5 277-1 MFR NF NOTE 5 6 A 4 TRANE VCEF NOTE 1 & 2
106 113 ELECTRICAL 100 - - - - - 277-1 MFR NF NOTE 5 6 C 2 TRANE VCEF NOTE 1 & 2
107 102 POST PROCESS 600 600 200 55 95 7.5 277-1 MFR NF NOTE 5 8 A 1 TRANE VCEF NOTE 1 & 2
108 103 PROCESS 975 400 235 55 95 5.0 277-1 MFR NF NOTE 5 10 A 1 TRANE VCEF NOTE 1 & 2
110 104 PRE-PROCESS 600 600 200 55 95 7.5 277-1 MFR NF NOTE 5 8 A 1 TRANE VCEF NOTE 1 & 2
111 130 MEN 675 675 675 55 95 10.0 277-1 MFR NF NOTE 5 8 B 1 TRANE VCEF NOTE 1 & 2
112 101 LOBBY 250 250 100 55 95 3.0 277-1 MFR NF NOTE 5 6 A 1 TRANE VCEF NOTE 1 & 2
113 111 SEARCH 150 150 150 55 95 2.5 277-1 MFR NF NOTE 5 6 B 1 TRANE VCEF NOTE 1 & 2
114 112 HOLDING 240 240 240 55 95 3.0 277-1 MFR NF NOTE 5 6 B 1 TRANE VCEF NOTE 1 & 2
NOTES:
1. NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER AHRI STANDARD 885-2008 USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE.
2. TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC.
3. SEE SPECIFICATION SECTION 23 09 003 FOR DESCRIPTION OF CONTROL TYPE.
4. SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE.
5. PROVIDE TAB WITH SCR HEATING
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
M5-0
1S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
ME
CH
AN
ICA
L S
CH
ED
ULE
S
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
AIAI
AI
AODI
DO
DI
AOAI
AOAI
AO AI
AI
AI
DI AI
AODI
DO
DI
DI
AI AI
AIAI
TH
FM
VFD
FM
T
FM
VFD
H T
T
SP
RETURNAIR
DUCT MOUNTEDTEMPERATURE &HUMIDITYSENSORS
RETURN DUCTMOUNTED LOWSTATIC SWITCH
RETURNAIRFLOW
RETURNFAN
COMMUNICATION LINKBETWEEN VFD GATEWAY &FMCS (TYPICAL EACH VFD)
MODALRM
START/STOP
CS
FANSTATUS
ACT
N.C.
DMPRMOD.
DMPRFDBK RELIEF
AIR
RELIEFAIR
DAMPER
ACT
ACT
OUTSIDEAIRFLOW
N.C.
O.A.
DMPRMOD.
DMPRFDBK
SP
MIXED AIRLOW STATIC
SWITCH
DMPRFDBK
DMPRMOD.
DP
FILTERSTATUS
ELECTRICPRE HEAT
COIL
SP
RETURNAIR
DAMPER
N.O.
OUTSIDEAIR
DAMPER
M.A.TEMP
PRE-FILTER(30%)
SUC
LIQ
DIFF. PRESS. SWITCH(0-1" W.G. SCALE)(TYP.2)
DX COOLINGCOIL
MOUNT FLOWMETER DISPLAY WITHINSERVICE VESTIBULE OF EACH RTU OR ONEXTERIOR OF AHU FOR INDOOR UNITS. (TYP.)
MODALRM
CS
FANSTATUS
DP
FILTERSTATUS
HIGH STATICSWITCH
DUCT MOUNTEDTEMPERATURE &HUMIDITY SENSORS
MOUNT IN DISCHARGEPLENUM OF AHU.
SP
SUPPLYAIR
STATICPRESS.TRANS.
UNLESS LOCATED ELSEWHEREON FLOOR PLANS, LOCATE 2/3DOWN LONGEST MEDIUMPRESSURE DUCT MAIN.
AHU REPORT GENERATION:DDC FMCS SHALL MONITOR THE FOLLOWING POINTS ON 10 MINUTE (ADJ.) INTERVALS WITHIN ASINGLE TREND. THE TREND SHALL RUN FOR A 100-DAY (ADJ.) DURATION AT WHICH POINT THENEWEST VALUES SHALL AUTOMATICALLY OVERWRITE THE OLDEST VALUES:
• DATE• TIME• GLOBAL OUTSIDE AIR TEMP [°F]• GLOBAL OUTSIDE AIR DEWPOINT [°F]• GLOBAL OUTSIDE AIR HUMIDITY [%RH]• SUPPLY AIRFLOW [CFM]• SUPPLY AIR TEMP (SAT) [°F]• SUPPLY AIR TEMP SETPOINT [°F]• SUPPLY AIR RELATIVE HUMIDITY [%]• SUPPLY AIR DEWPOINT [°F]• SUPPLY AIR DEWPOINT SETPOINT [°F]• RETURN AIRFLOW [CFM]• RETURN AIR TEMP (RAT) [°F]• RETURN AIR RELATIVE HUMIDITY [%]• OUTSIDE AIRFLOW [CFM]• MIXED AIR TEMP [°F]• PREHEAT COIL DISCHARGE AIR TEMP [°F]• PRE-FILTER LOADING (30% FILTER) [INCHES W.G.]• SUPPLY DUCT STATIC PRESSURE SETPOINT [INCHES W.G.]• SUPPLY DUCT STATIC PRESSURE [INCHES W.G.]• SUPPLY FAN VFD OUTPUT [% FULL SPEED]• RETURN FAN VFD OUTPUT [% FULL SPEED]• OUTSIDE AIR DAMPER POSITION [% OPEN]• RETURN AIR DAMPER POSITION [% OPEN]• RELIEF AIR DAMPER POSITION [% OPEN]
THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN GRAPHICAL FORM ON THE FMCS OPERATORWORKSTATION.
ONCE PER MONTH, THE DDC FMCS SHALL RECORD THE LARGEST AHU AIRFLOW WHICH OCCUREDDURING THAT MONTH. THE DATE, TIME, OUTSIDE AIR TEMP (AND ALL OTHER VALUES LISTED ABOVE)THAT COINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS INFORMATION SHALL BESTORED TO A MEMORY LOCATION ON THE FMCS OPERATOR WORKSTATION THAT IS MAINTAINED(NOT AUTOMATICALLY OVERWRITTEN).
SEQUENCE OF OPERATION:
WHEN AHU/RTU IS INDEXED TO RUN, THE FOLLOWING SHALL OCCUR:• SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS SHALL OPEN.• AFTER A 30 SECOND DELAY (ADJ.) TO ALLOW FOR OPENING OF SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS. SUPPLY FAN SHALL BE ENABLED TO RUN.• WHEN THE SUPPLY FAN HAS STARTED THE RETURN FAN AND INTERLOCKED EXHAUST FANS SHALL START AS SHOWN IN THE FAN INTERLOCK SCHEDULE.
SUPPLY FAN OPERATION:FMCS SHALL MODULATE SIGNAL TO SUPPLY FAN VFD AS REQUIRED TO MAINTAIN DUCT STATIC PRESSURE AS MEASURED BY STATIC PRESSURE TRANSMITTER. FMCS SHALL RESET SUPPLY DUCT STATICPRESSURE SETPOINT AS REQUIRED TO MAINTAIN AT LEAST ONE SUPPLY TAB DAMPER 95% (ADJ.) OPEN. FMCS SHALL UTILIZE COMMAND TO ALL SUPPLY TERMINAL AIR BOX POSITIONS TO RESET THESUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
RETURN FAN OPERATION:RETURN FAN SHALL BE INDEXED TO RUN WHENEVER THE SUPPLY FAN IS INDEXED TO RUN. FMCS SHALL MODULATE SIGNAL TO RETURN FAN VFD AS REQUIRED TO MAINTAIN THE AIRFLOW OFFSET ASINDICATED IN THE RETURN FAN AIRFLOW SCHEDULE.
DISCHARGE AIR TEMPERATURE SET POINT:DISCHARGE AIR SET POINT SHALL BE 55ºF (ADJ.).
DISCHARGE AIR TEMPERATURE RESET:RESET DISCHARGE AIR TEMPERATURE BASED ON THE ZONE WITH THE GREATEST CALL FOR COOLING. RESET THE TEMPERATURE AS FOLLOWS:• WHEN WORST CASE TAB IS OPEN ABOVE 90% (ADJ.) FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL RAISE BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL AHU MAXIMUM
DISCHARGE AIR TEMPERATURE OF 60ºF (ADJ.) IS ACHIEVED.• WHEN WORST CASE TAB IS OPEN BELOW 80% (ADJ.) FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL DROP BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL AHU MINIMUM
DISCHARGE AIR TEMPERATURE OF 55ºF (ADJ.) IS ACHIEVED.• THE MAXIMUM RETURN AIR HUMIDITY SETPOINT SHALL BE 60% (ADJ.) IF RETURN AIR HUMIDITY IS GREATER THAN SETPOINT, RESET DISCHARGE AIR TEMPERATURE TO 55°F UNTIL RETURN AIR
HUMIDITY IS 5% LESS THAN MAXIMUM SETPOINT.
USER TOGGLE - STATIC PRESSURE AND DISCHARGE AIR TEMPERATURE RESETS:PROVIDE USER WITH OPTION TO USE EITHER STATIC PRESSURE RESET OR DISCHARGE AIR TEMPERATURE RESET. ONLY ONE CONTROL OPTION SHALL BE USED AT A TIME. GRAPHIC ON AHU SCREENSHALL ALLOW USER TO TOGGLE FROM EITHER TEMPERATURE OR STATIC PRESSURE RESET.
VENTILATION AIR CONTROL:WHENEVER THE AIR HANDLING UNIT IS IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER SHALL BE FULLY OPEN. THE RETURN AIR AND RELIEF AIR DAMPER SHALL MODULATE IN OPPOSITION TO MAINTAINTHE MINIMUM OUTSIDE AIR FLOW RATE, OR TO SATISFY THE ECONOMIZER DISCHARGE AIR SEQUENCE.
DX COOLING COIL OPERATION:WHEN IN MINIMUM OUTSIDE AIR MODE, FMCS SHALL CONTROL CONDENSING UNIT (CU-1) AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.
WHEN IN ECONOMIZER MODE, FMCS SHALL NOT MODULATE COOLING CONTROL VALVE UNLESS RETURN AIR DAMPER IS 5% (ADJ.) OPEN AND RELIEF AIR DAMPER IS 95% (ADJ.) OPEN.
PREHEAT COIL OPERATION:PREHEAT COIL CONTROLS SHALL BE ENABLED WHEN OUTSIDE AIR TEMP DROPS BELOW 50°F (ADJ.). PREHEAT COIL CONTROLS SHALL BE DISABLED WHEN OUTSIDE AIR TEMP RISES ABOVE 54°F (ADJ.).
FMCS SHALL MODULATE ELECTRIC HEATING COIL AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.
ECONOMIZER OPERATION:WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS LESS THAN THE RETURN AIR DRY BULB TEMPERATURE THE FMCS SHALL ENABLE ECONOMIZER CONTROLS. WHEN OUTSIDE AIR DRY BULBTEMPERATURE IS GREATER THAN THE RETURN AIR DRY BULB TEMPERATURE FOR 10 MINUTES THE FMCS SHALL DISABLE ECONOMIZER CONTROLS AND SHALL RETURN THE UNIT TO MINIMUM OUTSIDEAIR MODE. ONCE ECONOMIZER CONTROLS HAVE BEEN ENABLED OR DISABLED, THE UNIT SHALL CONTINUE TO OPERATE IN THAT MODE FOR A MINIMUM OF 10 MINUTES (ADJ.) BEFORE BEING ALLOWEDTO SWITCH BACK (TO PREVENT SHORT CYCLING).
IN ECONOMIZER MODE THE FMCS SHALL MODULATE THE RETURN AND RELIEF DAMPERS AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT.
ALARMS, INTERLOCKS, AND SAFETIES:WHEN FIRE ALARM CONTROL PANEL INDICATES AN ALARM CONDITION, AHU SHALL BE SHUTDOWN.
THE FOLLOWING CONDITIONS SHALL SHUTDOWN THE AHU AND SHALL INDICATE AN ALARM CONDITION AT THE FMCS WORKSTATION:• LOW STATIC PRESSURE SWITCH INDICATES RETURN DUCT PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS.• LOW STATIC PRESSURE SWITCH INDICATES MIXED AIR PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS OF THE OUTSIDE AIR DUCTWORK.• HIGH STATIC PRESSURE SWITCH INDICATES SUPPLY DUCT STATIC PRESSURE GREATER THAN THE SPECIFIED DUCT PRESSURE CLASS.
THE FOLLOWING CONDITIONS SHALL INDICATE AN ALARM AT THE FMCS, HOWEVER AHU SHALL CONTINUE TO OPERATE:• AN ALARM IS INDICATED AT ANY SUPPLY FAN VFD OR RETURN FAN VFD.• DIFFERENTIAL PRESSURE SWITCH ACROSS PRE-FILTER (30%) BANK EXCEEDS 0.6 INCHES W.G. (ADJ.)• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 5°F (ADJ.) ABOVE OR BELOW SETPOINT.
IN THE EVENT SUPPLY FAN IS NOT RUNNING (AS INDICATED BY THE CURRENT SENSING RELAYS) RETURN AIR FAN SHALL BE DE-ENERGIZED.
WHENEVER AHU IS SHUTDOWN THE FOLLOWING SHALL OCCUR:• THE OUTSIDE AIR DAMPER AND RELIEF AIR DAMPER SHALL FULLY CLOSE.• RETURN AIR DAMPER SHALL FULLY OPEN.• ALL SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS SHALL FULLY CLOSE.• SUPPLY FAN AND RETURN FAN VFDS SHALL BE DE-ENERGIZED.• INTERLOCKED EXHAUST FANS SHALL BE DE-ENERGIZED WITH THE EXCEPTION OF EF-1 (AG LAB) & EF-3 (SEARCH/INTERVIEW).
UNOCCUPIED MODE:PROVIDE TIME OF DAY SCHEDULE TO ALLOW AHU TO ENTER UNOCCUPIED MODE PER SCHEDULE. COORDINATE SCHEDULE WITH OWNER.
• THE SUPPLY AND RETURN FANS SHALL CONTINUE RUNNING. WHEN USING CONSTANT VOLUME OFFSET FOR RETURN AIR FAN CONTROL, THE OFFSET SHALL GO TO ZERO AND THE SUPPLY FAN SHALLBE LIMITED TO THE MAXIMUM RETURN FAN AIRFLOW.
• THE OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN. ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER DAMPER POSITION.• ALL SPACE TEMPERATURES SHALL BE ALLOWED TO VARY +/- 10°F (ADJ.) FROM OCCUPIED SETPOINT.
HEATING OPTIMUM START-UP:• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC SYSTEM
SHALL DETERMINE THE MINIMUM RUNTIME TO WARM THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURESHALL BE MAINTAINED AT A SETPOINT OF 85ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES EXCEED A SETPOINT OF 68ºF (ADJ.). AT THAT TIME,THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.
COOLING OPTIMUM START-UP:• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC SYSTEM
SHALL DETERMINE THE MINIMUM RUNTIME TO COOL THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURESHALL BE MAINTAINED AT A SETPOINT OF 55ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES ARE LESS THAN A SETPOINT OF 75ºF (ADJ.). AT THATTIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.
GRAPHICAL DISPLAY:DISPLAY THE GLOBAL OUTSIDE AIR TEMPERATURE AND HUMIDITY ON AHU GRAPHIC PAGE.
A
B
C
D
E
F
R
A
B
C
D
E
F
AUX CONTACT TOFMCS TO INITIATECONTROL
TERMINALSTRIP SPEED
CONTROLSIGNALRETURN FAN
VFD SECTION
SPEEDCONTROLSIGNALSUPPLY FAN
VFD SECTION
TERMINALSTRIP
AUX CONTACT TOFMCS TO INITIATECONTROL
SAFETYCIRCUITS
NH
FIR
E A
LA
RM
SY
ST
EM
DU
CT
HIG
H S
TA
TIC
DU
CT
LO
W S
TA
TIC
LO
W L
IMIT
TE
MP
SW
ITC
H
SUPPLY & RETURN FAN VFD CONTROL
RETURN FAN AIRFLOW SCHEDULE
SYSTEM SUPPLY CFM EXHAUST FANS PRESSURIZATIONCFM
REMARKS
AHU-1 6,000EF-1, 2, & 3
0 NOTES 1,2,3
NOTES:1. RETURN FAN AIRFLOW SETPOINT SHALL BE THE SUPPLY FAN AIRFLOW (AS MEASURED BY THE
AFMS) MINUS THE SUM OF THE EXHAUST FAN AIRFLOWS MINUS THE PRESSURIZATION CFM
2. FMCS SHALL DETERMINE THE OPERATIONAL STATUS OF EACH EXHAUST FAN VIA THE CURRENTSENSING RELAY TO DETERMINE WHETHER THE CFM ASSOCIATED WITH THAT FAN SHOULD BEINCLUDED IN THE RETURN FAN AIRFLOW CALCULATION.
3. EXHAUST FAN AIRFLOWS SHALL NOT BE THE CFM INDICATED ON THE FAN SCHEDULE, BUTSHALL BE THE AIRFLOW INDICATED IN THE FINAL TAB REPORT.
FAN INTERLOCK SCHEDULE
SYSTEM INTERLOCKED EXHAUST FANS REMARKS
AHU-1 EF- 2 & 3 NOTE 1
NOTES:1. INTERLOCK EXHAUST FAN OPERATION THROUGH THE FMCS WITH RESPECTIVE
AHU IN ACCORDANCE WITH AHU SEQUENCE OF OPERATION.
P.H.TEMP
CU-1
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
M6-0
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
ME
CH
AN
ICA
L C
ON
TR
OL D
IAG
RA
MS
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
NO SCALE1AIR HANDLING UNIT CONTROL - AHU-1
DO
DI
DO
DI AI
AIAO
AI
AO
T
T
AIAO
AIAO
AI
T
T
AI
AO
AI
T
AI
AO
DO
T
FANSTATUS
HM
START/STOP
EXHAUSTAIR
ACT
SEQUENCE OF OPERATION:EXHAUST FAN SHALL BE INTERLOCKED TO RUN CONTINUOUSLY WHENRESPECTIVE AHU IS OPERATING.
2-POSITION DAMPER SHALL FULLY OPEN WHEN FAN IS ENERGIZED. WHEN FAN ISDE-ENERGIZED, 2-POSITION DAMPER SHALL FULLY CLOSE.
ALARMS, INTERLOCKS AND SAFETIES:AN ALARM SHALL BE GENERATED AT THE FMCS OPERATOR WORKSTATION IN THEEVENT THE FMCS COMMANDS THE EXHAUST FAN TO OPERATE AND THE CURRENTSENSING RELAY DETECTS INSUFFICIENT CURRENT DRAW.
FANSTATUS
CS
START/STOP
EXHAUSTAIR
ACT
SWALL MOUNTEDSWITCH ORTWIST TIMER
SEQUENCE OF OPERATION::FAN SHALL BE CONTROLLED BY MANUAL MOTOR STARTER (WALLSWITCH OR TWIST TIMER) PROVIDED BY OTHERS.
2-POSITION DAMPER SHALL FULLY OPEN WHEN FAN IS ENERGIZED.WHEN FAN IS DE-ENERGIZED, 2-POSITION DAMPER SHALL FULLY CLOSE.
GREEN LED LIGHT SHALL BE INSTALLED NEXT TO SWITCH AND INDICATEFAN-ON STATUS.
ALARMS, INTERLOCKS AND SAFETIES:AN ALARM SHALL BE GENERATED AT THE FMCS OPERATORWORKSTATION IN THE EVENT THE SWITCH POSITION DOES NOT MATCHFAN STATUS ACCORDING TO CURRENT SENSING RELAY.
N.T.S. #1 WALL MTDTEMP SENSOR
PRIMARY AIR FROM ZONECONDITIONING AHU
SUPPLYAIR
ACTVELOCITY ANDSTATIC SENSOR
PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)
SUPPLYAIR TEMP
DAMPER ACTUATORDAMPERMOD.
TABAIRFLOW
SEQUENCE OF OPERATION:
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND TAB ELECTRIC REHEAT COILCONTROL VALVE TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJ.) WITH 2°F (ADJ.) DEAD BANDBASED ON A SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR. SEE DRAWINGS FORTEMPERATURE SENSOR REQUIREMENTS. SPACES WITH ADJUSTABLE THERMOSTATS WILL ALLOW A+/- 3°F (ADJ.) OFFSET FROM THE DDC SETPOINT.
• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL SHALLBE DE-ENERGIZED.
• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED UNTIL SPACE SETPOINTIS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED CFM POSITION PER THE TABSCHEDULE. THE REHEAT COIL SHALL REMAIN DE-ENERGIZED.
• UPON A FURTHER FALL IN SPACE TEMPERATURE, THE ELECTRIC REHEAT COIL AND TAB SHALLMODULATE OPEN IN UNISON TO MAINTAIN SPACE SETPOINT UNTIL TAB AIR FLOW REACHES ITSMAXIMUM HEATING SETTING.
ALARMS, INTERLOCKS & SAFETIES:
• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN10°F (ADJ.) ABOVE OR BELOW SETPOINT.
• IF THE HIGH TEMPERATURE SAFETY DEVICE EXCEEDS MANUFACTURER'S SETPOINT, AN ALARMSHALL BE SENT TO THE OPERATOR INTERFACE.
WALL MTDTEMP SENSOR
PRIMARY AIR FROM ZONECONDITIONING AHU
SUPPLYAIR
ACTVELOCITY ANDSTATIC SENSOR
PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)
SUPPLYAIR TEMP
DAMPER ACTUATORDAMPERMOD.
TABAIRFLOW
SEQUENCE OF OPERATION:
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER TO MAINTAIN CONSTANT SUPPLYAIRFLOW TO THE ROOM.
• FMCS TAB CONTROLLER SHALL MODULATE TAB ELECTIC REHEAT COIL TO MAINTAIN SPACETEMPERATURE OF 72°F (ADJ.) WITH 2°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALLMOUNTED TEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.SPACES WITH ADJUSTABLE THERMOSTATS WILL ALLOW A +/- 3°F (ADJ.) OFFSET FROM THE DDCSETPOINT.
ALARMS, INTERLOCKS & SAFETIES:
• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN10°F (ADJ.) ABOVE OR BELOW SETPOINT.
• IF THE HIGH TEMPERATURE SAFETY DEVICE EXCEEDS MANUFACTURER'S SETPOINT, AN ALARMSHALL BE SENT TO THE OPERATOR INTERFACE.
WALL MTDTEMP SENSOR
PRIMARY AIR FROM ZONECONDITIONING AHU
SUPPLYAIR
ACTVELOCITY ANDSTATIC SENSOR
PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)
DAMPER ACTUATORDAMPERMOD.
TABAIRFLOW
SEQUENCE OF OPERATION:
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER TO MAINTAIN SPACE TEMPERATUREOF 72°F (ADJ.) WITH 2°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTEDTEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS. SPACESWITH ADJUSTABLE THERMOSTATS WILL ALLOW A +/- 3°F (ADJ.) OFFSET FROM THE DDC SETPOINT.
• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION.• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED UNTIL SPACE SETPOINT
IS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED CFM POSITION PER THE TABSCHEDULE.
ALARMS, INTERLOCKS & SAFETIES:
SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN 10°F(ADJ.) ABOVE OR BELOW SETPOINT.
WALL MTDTEMP SENSOR
SUPPLYAIR
RETURNAIR
PRE-FILTER START /
STOP
SUPPLYFAN
HEATINGCOIL
SEQUENCE OF OPERATION:
THE CABINET HEATER SHALL BE FURNISHED WITH A UNIT MOUNTED FAN SPEED SELECTOR SWITCH(OFF-HIGH-MED-LOW). THE UNIT SHALL MAINTAIN A SPACE TEMPERATURE OF NO MORE THAN 60°F.
WHEN THE OUTDOOR AIR TEMPERATURE IS ABOVE 45°F, HEATING SHALL BE DISABLED.
WHEN THE OUTDOOR AIR TEMPERATURE IS BELOW 45°F, HEATING SHALL BE ENABLED AND THE FANSHALL RUN CONTINUOUSLY.
ALARMS, INTERLOCKS & SAFETIES:
• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF SPACE TEMPERATURE FALLS 10°F (ADJ.)BELOW SETPOINT.
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
M6.0
1S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
ME
CH
AN
ICA
L C
ON
TR
OL D
IAG
RA
MS
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
NO SCALE1EXHAUST FAN CONTROL - AHU INTERLOCK - FAN-A
NO SCALE2EXHAUST FAN CONTROL - WALL SWITCH - FAN-B
NO SCALE3TAB CONTROL W/ ELECTRIC REHEAT - TAB-A
NO SCALE4TAB CONTROL CONSTANT VOLUME W/ ELECTRIC REHEAT - TAB-B
NO SCALE5TAB CONTROL W/ COOLING ONLY - TAB-C
NO SCALE6CABINET HEATER CONTROL - ELECTRIC
JJ HH GG FF EE DD CC
BB AA
IDAC-4IDAC-3
ODAC-3 TO BE RELOCATED. REFER TOM1-10 FOR NEW LOCATION.
ODAC-4 TO BE RELOCATED.REFER TO SHEET M1-10FOR NEW LOCATION.
EF-11
EF-9
10x10
24x8
24x8
24x8
24
x8
36
x1
4
22ø
TG-E TG-E
TG-E
EF-E
16x18
40x18
SG-E
10x10/225
SG-E
10x10/225SG-E
24x12/750
SG-E
24x12/750
TG-E
14
x1
2
14x12
14
x1
2
14x12
14x1214x12
12x12
EG-E12x12/200(TYP.2)
SG-E24x12/495(TYP.4)
SG-E10x10/225(TYP.2)
EG-E
10x10/270
(TYP.2)
EG-E
10x10/32530x20
20x30
SL
OP
E D
N. SLOPE DN.
SLOPE DN.
12x1412x14
SG-E
12x12/85
SG-E
10x10/140 12x12
RELOCATE DDCCONTROLS TOROOM 119UNDER BIDALTERNATE.24x8
SLOPE DN.
24
x8
IDAC-3 TO BE RELOCATED. REFERTO M1-10 FOR NEW LOCATION.
5
4
EXISTING LINEARDIFFUSER (TYP.)
2
1
3
KEYNOTES:
1. REMOVE EXISTING AIR HANDLER ANDASSOCIATED PIPING AND DUCTWORK. REMOVEEXISTING HOUSEKEEPING PAD.
2. REMOVE EXISTING EXHAUST FAN ANDASSOCIATED DUCT. PATCH EXISTING EXTERIORLOUVER.
3. REMOVE EXISTING OUTDOOR CONDENSINGUNIT.
4. PATCH EXISTING EXTERIOR LOUVER.5. REMOVE EXISTING DUCTWORK AND DIFFUSERS
FOR FURNACE UNDER BID ALTERNATE ONLY.
#
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
MD
1-1
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
FIR
ST
FLO
OR
PLA
N -
VE
NT
ILA
TIO
N -
DE
MO
LIT
ION
NO R HT
1/8" = 1'-0"1FIRST FLOOR PLAN - VENTILATION - DEMOLITION
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
UP
107 SF
PUBLIC LOBBY
101
326 SF
POST PROCESS
102
572 SF
PROCESS
103
283 SF
PRE-PROCESS
104
55 SF
WOMEN
106
218 SF
CBP OFFICE
108
115 SF
HOLDING
112
73 SF
SEARCH
11173 SF
INTERVIEW
110
121 SF
AG LAB
109
78 SF
ENTRY
107
971 SF
CONFERENCE
10555 SF
MEN
105
54 SF
SECURITY
116
81 SF
SUPPLY
114
119 SF
LAN
115
35 SF
ELECTRICAL
113
264 SF
WOMEN
129
161 SF
MEN
130
192 SF
MECH
117
188 SF
MAIN ELECTRICAL
118
389 SF
SPRINKLER/MECH
119
JJ HH GG FF EE DD CC
BB AA
11 SF
MECH
120
5/8
" / 1
'-0
"
85 SF
STORAGE
121
1741 SF
CHARTER
1224" WASTE LINE
BELOW SLAB
FCO
WC WC WC WC
LAV
WC
UR UR LAV LAV FCO
FD
FD
FD
FCO
FCO
FCO
FD
2" V UP
CF
FCO
4"SAN
FCO
SK(2)
4"SAN
4"SAN
2" V UP
WCLAV
EWCFD
4"SAN
4"SAN
4"SAN
LAV
2" V UP
WC
SK
FD
FD
SK
3"SAN
1 1/2" V
4"S
AN
EWC
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW CONNECTION
PLUMBING SYMBOLS LISTSYMBOL: DESCRIPTION:
COLD WATER - POTABLECW
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
SANITARY DRAINAGESAN
VENTV
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
BALANCING VALVE (NO. INDICATES GPM)0.5
CHECK VALVE
BFP BACKFLOW PREVENTER
CO CLEANOUT
FLOOR CLEANOUTFCO
FLOOR DRAINFD
LAVATORYLAV
NC NEW CONNECTION
SINKSK
URINALUR
WATER CLOSETWC
WALL CLEANOUTWCO
ELECTRIC WATER COOLEREWC
VENT THROUGH ROOFVTR
NC
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
P0-1
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
UN
DE
RF
LO
OR
PLA
N -
PLU
MB
ING
- W
AS
TE
NO R HT
1/8" = 1'-0"1UNDERFLOOR PLAN - PLUMBING - WASTE
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
UP
107 SF
PUBLIC LOBBY
101
326 SF
POST PROCESS
102
572 SF
PROCESS
103
283 SF
PRE-PROCESS
104
55 SF
WOMEN
106
218 SF
CBP OFFICE
108
115 SF
HOLDING
112
73 SF
SEARCH
11173 SF
INTERVIEW
110
121 SF
AG LAB
109
78 SF
ENTRY
107
971 SF
CONFERENCE
10555 SF
MEN
105
54 SF
SECURITY
116
81 SF
SUPPLY
114
119 SF
LAN
115
35 SF
ELECTRICAL
113
264 SF
WOMEN
129
161 SF
MEN
130
192 SF
MECH
117
188 SF
MAIN ELECTRICAL
118
389 SF
SPRINKLER/MECH
119
JJ HH GG FF EE DD CC
BB AA
11 SF
MECH
120
5/8
" / 1
'-0
"85 SF
STORAGE
121
1741 SF
CHARTER
122
WC-E WC-E WC-EL-E L-E L-E
WC-E
UR-E UR-E
L-E L-E
3" C.W. LINE
OVERHEAD
3/4" C.W. LINE
OVERHEAD
3" C.W. UP
1" H.W. LINE
3/4" REC. LINE
UP FROM END
OF H.W. LINE
2" C.W.
DOWN
ABOVE CLG.
3/4" C.W.
DOWN
1" H.W.
DOWN
3" C.W. LINE BELOW GRADE.
SEE SITE PLAN FOR
CONTINUATION 115 G.P.M.
1"
P-E
P-E P-E
HB-E
SK-1
SK-1
WC-1
WC-1L-1
L-1
EWC-1
2"C
W
2"CW
3/4"HW
1"H
W
2"CW
3/4"HW
2"CW
1 1/2"CW 3/4"HW
3/4"HWC
2"CW
3/4"HWC
WC-EWC-E
FD-E FD-EFD-E
FD-1
FD-1
GD-1
PUSH BUTTONFLUSH FOR CF-1
CF-1
FD-E
FD-E
FCO-E
0.5
0.5
0.5
REFER TO 1/P5-00FOR GARBAGEDISPOSAL DETAIL.
FD-1
2" V TO3" VTR.
2"V
2"V
2" V TO3" VTR.
2" V DN
2" V DN
2"V
FCO-1
FCO-1
FCO-1
FCO-1
SK-2
L-2
MB-1
FD-1
L-2
FD-1
CONNECT TOEXISTING SAN,VENT, & WATER
FCO-1
FURNISH NEWCONNECTION TOEXISTING HOSEBIBB.
1 1/2" V
EWC-2
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
P1-1
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
FIR
ST
FLO
OR
PLA
N -
PLU
MB
ING
1/8" = 1'-0"1FIRST FLOOR PLAN - PLUMBING
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
GENERAL NOTES :
1. COORDINATE ROOF PENETRATIONS WITHOWNER'S STANDING SEAM ROOFMANUFACTURER.
PLUMBING FIXTURE ROUGH-IN SCHEDULE
FIXTURE DESCRIPTIONDOMESTIC
C.W.(NOTE 3)
DOMESTICH.W.
(NOTE 3)
SANITARY(NOTE 3)
VENT(NOTE 3)
REMARKS
WATER CLOSET 1" - 4" 2" (FLUSH VALVE)
LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2
SINK 1/2" 1/2" 1 1/2" 1 1/2" NOTE 1 & 2 (KITCHEN TYPE SINK)
MOP BASIN 3/4" 3/4" 3" 1 1/2" -
ELECTRIC WATER COOLER 1/2" - 1 1/2" 1 11/4" NOTE 1 & 2
WASHING MACH. FIXTURE 3/4" 3/4" 2" 1 1/4" -
FLOOR DRAIN/FLOOR SINK - - 2" 1 1/2" -
NOTES:
1. SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINIMUM OF 2".2. 1/2" CW AND HW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE. BRANCH PIPING TO VERTICAL
RISE-DROP SHALL BE A MINIMUM OF 3/4" INCH UNLESS NOTED OTHERWISE.
3. SIZES SHOWN ARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED IN THE SCHEDULESHALL DICTATE THE ROUGH-IN SIZE.
PLUMBING MATERIAL LISTTAG DESCRIPTION ACCEPTABLE MANUFACTURERS
CF-1
COMBINATION FIXTURE - CORRECTION STYLE COMBINATIONLAVATORY/TOILET, FRONT ACCESSIBLE, A.D.A - 36" WIDE , 14 GAUGE TYPE 304STAINLESS STEEL, FULLY WELDED SEAMS, SATIN FINISH. ELONGATED BOWLWITH CONTOURED SEAT, BLOWOUT TYPE, INTEGRAL DRAIN WITH AIR VENT,SELF DRAINING SOAP DISH, FLOOR MOUNTED, FLOOR TOILET WASTECONNECTION, REMOTE BUTTON FLUSH VALVE PENAL BUBBLES, DUALTEMPRATURE TRIM WATER SAVING, FLUSH VALVE AND ELBOW WASTETHROUGH THE WALL, P-TRAP AND CLEANOUT, OVERFLOW PREVERNTER, 1.6GALLONS PER FLUSH AND INTEGRAL TISSUE HOLDER.
COMBINATION FIXTURE -WILLOUGHBY ECF-3936-L/R
EWC-1
ELECTRIC WATER COOLER - WALL HUNG, 18 GAUGE STAINLESS STEEL
CABINET AND NON-SPLASH BASIN WITH STAINLESS STEEL FINISH, STREAM
PROJECTOR WITH PROTECTIVE HOOD, PUSH BAR OR LEVER OPERATING
CONTROLS ON FRONT AND SIDES, BUILT-IN FLOW REGULATOR, DRAIN & TRAP
ASSEMBLY, ADJUSTABLE THERMOSTAT, MOUNTING ACCESSORIES, TANKDRAIN AND ANGLE STOPS, HERMETIC COMPRESSOR TO OPERATE ON HFC-134a
REFRIGERANT. COMPLIANT TO LATEST ANSI A117.1 AND ADA STANDARDS.
UNIT SHALL COMPLY WITH FEDERAL ACT S.3874.
UNIT SHALL PROVIDE 8.0 GPH OF WATER FROM 80°F TO 50°F AT 90°F AMBIENT.WATER SYSTEM SHALL BE OF LEAD FREE CONSTRUCTION. TANK SHALL BE
TESTED TO 125 PSIG.
ORIFICE SHALL BE AT 36" (MAXIMUM) ABOVE FINISHED FLOOR. BOTTOM OF
APRON SHALL BE AT 27" ABOVE FINISHED FLOOR IN COMPLIANCE WITHLATEST ADA STANDARDS.
ELECTRICAL REQUIREMENTS - 115V-1 PHASE, CORD AND PLUG, 1/5 HP MOTOR
ELKAY (LZS8), HALSEY-TAYLER(HTHB-HAC8WF), ACORN (A111)
FCO-1
FLOOR CLEANOUT - ADJUSTABLE, CAST IRON HOUSING, ANCHOR FLANGE,
TAPERED THREAD PLUG, SECURED NICKEL BRONZE TOP. TOP STYLE SHALL
MATCH FLOOR FINISH AS FOLLOWS:
UNFINISHED FLOOR - ROUND SOLID SCORIATED TOP
TILE OR TERRAZZO - SQUARE RECESSED TOP
ZURN (Z1400), JOSAM (55000),MIFAB (C1100), SMITH (4000),WADE (6000), WATTS (CO-200)
FD-1FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZE ADJUSTABLE TOP, 6"ROUND, 2" BOTTOM OUTLET, FLASHING COLLAR, DEEP SEAL TRAP.
FLOOR DRAIN - ZURN (Z-415),
SMITH (2005), WADE (1100),
JOSAM (30000), WATTS (FD-100),MIFAB (F1100)
FD-2FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZE ADJUSTABLE TOP, 6"ROUND, 3" BOTTOM OUTLET, FLASHING COLLAR, DEEP SEAL TRAP.
FLOOR DRAIN - ZURN (Z-415),
SMITH (2005), WADE (1100),JOSAM (30000), WATTS (FD-100),
MIFAB (F1100)
GD-1
GARBAGE DISPOSAL - CONTINUOUS FEED UNIT, CORROSION RESISTANT GRIND
CHAMBER, CONTROL CENTER WITH AUTOMATIC REVERSING ACTION, MANUALRESET OVERLOAD PROTECTION, DISPOSER MOUNTING ASSEMBLY, SOLENOID
VALVE, SYPHON BREAKER, FLOW CONTROL VALVE, 1/2" WATER CONNECTION,
SUPPORT LEGS, SERVICE WRENCH, FULL 1 YEAR WARRANTY.
ELECTRICAL REQUIREMENTS - 480V-3 PHASE, HARD-WIRED, 5 HP MOTOR, 11.6AMPS.
IN-SINK-ERATOR (SS-500)
L-1
LAVATORY - COUNTER TOP MOUNTED, OVAL, SELF-RIMMING, WHITE VITREOUS
CHINA, 20"x17", SINGLE FAUCET HOLE.
LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED ,
BRASS CONSTRUCTION, CHROME-PLATED FINISH, RIGID GOOSENECK SPOUT
WITH MINIMUM 5" REACH AND AERATOR, SINGLE HOLE, PERFORATED GRID
STRAINER WITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH
BUILT-IN FILTER, SOLID BRASS THERMOSTATIC MIXING VALVE MEETING ASSE1070 REQUIREMENTS WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND
INTEGRAL CHECK VALVES, WATERPROOF CONNECTORS AND CABLE
MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT
ENCLOSURE BELOW LAVATORY.
MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF
2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH
FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOUNT
MIXING VALVE UNDER COUNTER/LAVATORY. MIXING VALVE SHALL NOT BEWYE PATTERN STYLE.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES, AND
SUPPLY LINES.
ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE
SUPPLY LOOSE KEY STOPS, CHROME PLATED SOFT COPPER SUPPLY LINES,
1-1/4" 20 GAUGE CAST BRASS P-TRAP.
ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OF INSULATION KIT.
LAVATORY -
AMERICAN STANDARD (0475.047),GERBER (12-841), KOHLER
(K-2196-1), SLOAN (SS-3102),
TOTO (LT501), ZURN (Z5111)
LAVATORY TRIM - DELTA
(3001T3), AMERICAN STANDARD
(6055.163), CHICAGO FAUCET
(116.203.AB.1), HYDROTEK(HB-6000C-LR), MOEN (8303),
SLOAN (EBF-750), SPEAKMAN
(S-9100), SYMMONS (S-6095),
ZURN (Z6920-XL)
INSULATION KIT - TRUEBRO
(LAV-GUARD), BROCAR
PRODUCTS (TRAP WRAP),
MCGUIRE (PROWRAP),
PLUMBEREX (PRO-EXTREME)
SK-2
SINK - SELF-RIMMING SINGLE COMPARTMENT WITH FAUCET DECK, 18 GAUGE
TYPE 304 STAINLESS STEEL, COMPLETELY UNDERCOATED, 19" (SIDE-TO-SIDE)x 19" (FRONT-TO-BACK) OVERALL SIZE, EACH COMPARTMENT 16" x 13" x 7.5"
DEEP, 3-1/2" DIAMETER DRAIN OUTLET LOCATION IN BOWL.
SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION,
CHROME-PLATED FINISH, GOOSENECK SWING SPOUT, NOMINAL 6" REACH,AERATOR 4" WRISTBLADE HANDLES AT 8" CENTERS, 1/4-TURN OPERATION
CERAMIC DISC CARTRIDGE.
MAXIMUM FLOW TO BE 2.2 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF
2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITHFEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON
PLATE AS REQUIRED.
ACCESSORIES - 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE AND
P-TRAP, QUARTER-TURN BALL VALVE TYPE 3/8" CHROME-PLATED BRASSANGLE SUPPLIES WITH LOOSE KEY STOPS, CHROME-PLATED SOFT COPPER
SUPPLY LINES.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES, AND
SUPPLY LINES.
SINK - ELKAY (LR/LK18B), JUST
(SL-J-35 SSF), FRANKE (LBS)
INSULATION KIT - MCGUIRE(PROWRAP), JUST (J-ADA),
PLUMBEREX (PRO-EXTREME),
TRUEBRO (LAV-GUARD2)
SINK TRIM - CHICAGO FAUCET(786), AMERICAN STANDARD(6450), SPEAKMAN (SC-3000SERIES), ZURN (Z831-XL)
PLUMBING MATERIAL LISTTAG DESCRIPTION ACCEPTABLE MANUFACTURERS
SK-1
SINK - SELF-RIMMING DOUBLE COMPARTMENT WITH FAUCET DECK , 18 GAUGE
TYPE 304 STAINLESS STEEL, COMPLETELY UNDERCOATED, 20" (SIDE-TO-SIDE)
x 18 " (FRONT-TO-BACK) OVERALL SIZE, EACH COMPARTMENT 12" x 12" x 7 1/2"DEEP, 3-1/2" DIAMETER DRAIN OUTLET LOCATION CENTERED EACH BOWL,
REMOVABLE TYPE 304 BASKET STRAINERS WITH NEOPRENE STOPPERS.
SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION,
CHROME-PLATED FINISH, CONVENTIONAL SWING SPOUT, NOMINAL 8" REACH,AERATOR FLOW OUTLET, LEVER BLADE HANDLES AT 8" CENTERS, 1/4-TURN
OPERATION CERAMIC DISC CARTRIDGE.
MAXIMUM FLOW TO BE 2.2 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF
2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH
FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEONPLATE AS REQUIRED.
ACCESSORIES - OFFSET 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE
AND P-TRAP, QUARTER-TURN BALL VALVE TYPE 3/8" CHROME-PLATED BRASS
ANGLE SUPPLIES WITH LOOSE KEY STOPS, CHROME-PLATED SOFT COPPERSUPPLY LINES.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES, AND
SUPPLY LINES.
SINK -
ELKAY(LR/LK18B), JUST
(DL/J-35-SSF), FRANKE LBD
SINK TRIM -
DELTA (27C2), AMERICAN
STANDARD (7270.000), CHICAGO
FAUCET (786), KOHLER (K-7761),
SYMMONS (S-254), ZURN (Z831-XL)
[INSULATION KIT - MCGUIRE
(PROWRAP), JUST (J-ADA),
PLUMBEREX (PRO-EXTREME),
TRUEBRO (LAV-GUARD2)]
WC-1
WATER CLOSET - ACCESSIBLE, FLOOR MOUNTED, FLUSH VALVE TYPE, WHITE
VITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-1/2" TOP
SPUD, BOLT CAPS.
FLUSH VALVE - FLUSH VALVE - EXPOSED, SENSOR OPERATION, BATTERY
POWERED, 1.6 GALLONS PER FLUSH, 11-1/2" ROUGH-IN, CHROME PLATED, 1"
I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDAL RESISTANT CAP, HIGH
BACK PRESSURE VACUUM BREAKER, ADJUSTABLE TAILPIECE, SPUD
COUPLING AND FLANGE, WALL FLANGE WITH SET SCREW, MECHANICALOVER-RIDE BUTTON, CHLORAMINE RESISTANT MATERIALS, ADA COMPLIANT, 3
YEAR WARRANTY.
SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTION MOLDED SOLID
PLASTIC, SELF-SUSTAINING HINGE, STAINLESS STEEL OR PLATED STEELPOSTS AND NUTS.
CONTRACTOR OPTION: COMBINATION WATER CLOSET/FLUSH VALVE
PACKAGED SYSTEM BY AMERICAN STANDARD, KOHLER, SLOAN, OR ZURN
TOP OF SEAT SHALL BE AT 17"-19" ABOVE FINISHED FLOOR. FLUSH HANDLE
SHALL BE LOCATED ON THE WIDE SIDE OF THE TOILET STALL AND BE 12"
(MAXIMUM) ABOVE BOWL RIM AND OPERATE WITH NO GREATER THAN 5 LB
FORCE IN COMPLIANCE WITH LATEST ADA STANDARDS. VERIFY EQUIPMENT
REQUIREMENTS AND ROUGH-IN LOCATIONS.
WATER CLOSET -
AMERICAN STANDARD (3043.001),
CRANE (3H701), GERBER (25-730),
KOHLER (K-4368), SLOAN
(ST-2023), ZURN (Z5660)
FLUSH VALVE - ZURN
(ZER6000AV), SLOAN (8111),
AMERICAN STANDARD (6065.161),
HYDROTEK (HB-8000C), MOEN
(8310), KOHLER (K-10957-SV-CP)
SEAT -
BEMIS (1655C), CHURCH (9500C),
BENEKE (533), KOHLER(K-4666-C), OLSONITE (95), SAME
AS WATER CLOSET
MANUFACTURER
L-2
LAVATORY - ACCESSIBLE WALL MOUNTED, WHITE VITREOUS CHINA, 20"x18", 4"HIGH CONTOURED BACKSPLASH, SINGLE FAUCET HOLE, DRILLED FOR
CONCEALED ARM CARRIER.
LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED ,
BRASS CONSTRUCTION, CHROME-PLATED FINISH, RIGID GOOSENECK SPOUTWITH MINIMUM 5" REACH AND AERATOR, SINGLE HOLE, PERFORATED GRID
STRAINER WITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH
BUILT-IN FILTER, SOLID BRASS THERMOSTATIC MIXING VALVE MEETING ASSE
1070 REQUIREMENTS WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND
INTEGRAL CHECK VALVES, WATERPROOF CONNECTORS AND CABLE
MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT
ENCLOSURE BELOW LAVATORY.
MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH
FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOUNT
MIXING VALVE UNDER COUNTER/LAVATORY. MIXING VALVE SHALL NOT BE
WYE PATTERN STYLE.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND
SUPPLY LINES.
ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE
SUPPLY LOOSE KEY STOPS, CHROME PLATED SOFT COPPER SUPPLY LINES,DRAIN AND OFFSET TAILPIECE, 1-1/4" 20 GAUGE CAST BRASS P-TRAP,
SUPPORT CARRIER.
MOUNT LAVATORY WITH SUPPORT CARRIER BOLTED SECURELY TO FLOOR.
TOP OF RIM SHALL BE AT 34" ABOVE FLOOR IN COMPLIANCE WITH LATEST ADASTANDARD. ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OF
INSULATION KIT.
LAVATORY -
AMERICAN STANDARD (0356.421),
KOHLER (K-2007), SLOAN
(SS-3103), TOTO (LT307), ZURN(Z5361)
LAVATORY TRIM - DELTA(3001T3), AMERICAN STANDARD
(6055.163), CHICAGO FAUCET
(116.203.AB.1), HYDROTEK
(HB-6000C-LR), MOEN (8303),
SLOAN (EBF-750), SPEAKMAN(S-9100), SYMMONS (S-6095),
ZURN (Z6920-XL)
INSULATION KIT - TRUEBRO
(LAV-GUARD), BROCAR
PRODUCTS (TRAP WRAP),MCGUIRE (PROWRAP),
PLUMBEREX (PRO-EXTREME)
WHA-1WATER HAMMER ARRESTER - BELLOWS TYPE, PRE-CHARGED, ALL LEADFREE STAINLESS STEEL CONSTRUCTION, ASSE 1010 APPROVED, PDICERTIFIED, RATED FOR 1-11 FIXTURE UNIT.
ZURN (Z1700), JR SMITH(5005-5050), WADE (W5-100),JOSAM (75000 SERIES),WATTS (SS), MIFAB (WHB)
MB-1
MOP BASIN - PRECAST TERRAZZO, 36"x24"x12", STAINLESS STEEL INTEGRALDRAIN WITH REMOVABLE STRAINER, 3" OUTLET, CONTINUOUS STAINLESS
STEEL CAP ON ALL EDGES.
TRIM - EXPOSED TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION,
CHROME-PLATED FINISH, SINGLE WING HANDLES, 1/4 TURN CERAMIC DISCCARTRIDGE, 3/4" HOSE THREAD SPOUT WITH ASSE 1053 RATED INTEGRAL
VACUUM BREAKER, WALL BRACE, PAIL HOOK, CHECK STOPS OR INLINE
CHECK VALVES TO PREVENT THERMAL CROSSOVER. FAUCET SHALL
COMPLY WITH FEDERAL ACT S.3874.
ACCESSORIES - MOP HANGER, HOSE AND HOSE BRACKET, DEEP SEAL TRAP
MOP BASIN - FIAT (TSB), ACORN(TSH), CREATIVE INDUSTRIES
(MC), WILLIAMS (SB)
TRIM - DELTA (28C2383),
AMERICAN STANDARD (8344.012),MOEN (8124), SPEAKMAN
(SC-5812), SYMMONS (S-2490),
ZURN (Z841M1-XL)
VACUUM BREAKER - WATTS (8A),OR APPROVED EQUAL
EWC-2
ELECTRIC WATER COOLER - WALL HUNG, 18 GAUGE STAINLESS STEEL
CABINET AND NON-SPLASH BASIN WITH STAINLESS STEEL FINISH, STREAM
PROJECTOR WITH PROTECTIVE HOOD, PUSH BAR OR LEVER OPERATING
CONTROLS ON FRONT AND SIDES, BUILT-IN FLOW REGULATOR, DRAIN & TRAPASSEMBLY, ADJUSTABLE THERMOSTAT, MOUNTING ACCESSORIES, TANK
DRAIN AND ANGLE STOPS, HERMETIC COMPRESSOR TO OPERATE ON HFC-134a
REFRIGERANT. COMPLIANT TO LATEST ANSI A117.1 AND ADA STANDARDS.
UNIT SHALL COMPLY WITH FEDERAL ACT S.3874.
BOTTLE FILLING STATION - UNIT MOUNTED, STAINLESS STEEL CONSTRUCTION
AND FINISH, INTEGRAL DRAIN, SENSOR OPERATED WITH AUTOMATIC SHUTOFF,
BOTTLE COUNTER.
UNIT SHALL PROVIDE 8.0 GPH OF WATER FROM 80°F TO 50°F AT 90°F AMBIENT.WATER SYSTEM SHALL BE OF LEAD FREE CONSTRUCTION. TANK SHALL BE
TESTED TO 125 PSIG.
ORIFICE SHALL BE AT 36" (MAXIMUM) ABOVE FINISHED FLOOR. BOTTOM OF
APRON SHALL BE AT 27" ABOVE FINISHED FLOOR IN COMPLIANCE WITHLATEST ADA STANDARDS.
ELECTRICAL REQUIREMENTS - 115V-1 PHASE, CORD AND PLUG, 1/5 HP MOTOR
ELKAY (EZS8), HALSEY-TAYLER(HTHB-HAC8), ACORN (A111)
VACUUM BREAKER W/ANGLE FLANGES
FLOW CONTROL VALVE 8GPM
SOLENOID VALVE
1/2" CW
1-1/4" CW
1/2" HW
WHA-1
1/2"
2" SAN
DISPOSER
BODY WATER INLET @SINK APPLICATIONS
MIXING VALVEWITH INTEGRALCHECK VALVES
SINK BOWL
NOTES:
1. INSTALL VACUUM BREAKER ON WALL MINIMUM 12" ABOVE FLOODRIM OF SINK.
2. ALL EXPOSED PIPING TO BE CHROME PLATED.
THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLYOPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THECONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FORCOMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONSBEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THECATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLESTATE, LOCAL AND GOVERNING AUTHORITIES.
ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874
PLUMBING FIXTURE SCHEDULE GENERAL NOTES
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
P5-0
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AD
DE
W
13-1
27
BID
SE
T -
12/1
7/1
5
PLU
MB
ING
MA
TE
RIA
L L
IST
NO SCALE1GARBAGE DISPOSER GD-1 PIPING DETAIL
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01
JJ HH GG FF EE DD CC
BB AA
3/4" C.W. LINE
OVERHEAD
1" H.W. LINE
3" C.W. LINE BELOW GRADE.
SEE SITE PLAN FOR
CONTINUATION 115 G.P.M.
1"
WC-E WC-E
FD-E
WC-E WC-EL-E L-E L-E WC-E
UR-E UR-E
L-E L-E
FCO-E
3" C.W. LINE
OVERHEAD
3" C.W. UP
3/4" REC. LINE
UP FROM END
OF H.W. LINE
2" C.W.
DOWN
ABOVE CLG.
3/4" C.W.
DOWN
1" H.W.
DOWN
P-E
P-E P-E
P-E
WC-E
FD-E
FD-E
FD-E
REMOVE EXISTINGFLOOR DRAIN ANDREPLACE WITH FCO-1.
REMOVE EXISTINGPIPE DOWN TOEXISTING HOSE BIBB.RECONNECT IN NEWWALL.
SH
EET N
UM
BER:
PRO
JECT N
UM
BER:
DATE:
PRO
JECT D
ESCRIP
TIO
N:
PRO
JECT A
RCH
ITECT:
DRAW
N B
Y:
CH
ECKED
BY:
THIS WORK IS PROTECTED UNDER U.S. COPYRIGHT LAW AND THE ARCHITECTURAL WORKS COPYRIGHT PROTECTION ACT OF 1990. FAILURE TO COMPENSATE PARAGON ARCHITECTURE FOR THE USE OF THESE DRAWINGS AS GOVERNED BY THE TERMS OF THE CLIENT-ARCHITECT AGREEMENT (CONTRACT ON FILE), OR 5% OF THE COST OF CONSTRUCTION MINIMUM IF CONTRACT IS IMPLIED (USE OF THESE DOCUMENTS CREATES AN IMPLIED CONTRACT), SHALL BE CONSIDERED SUBSTANTIAL NON-PERFORMANCE AND CONSTITUTES A BREACH OF CONTRACT AND RESULTS IN THE LOSS OF PERMISSION TO USE THESE DOCUMENTS FOR ANY PURPOSE, BY ANYONE. USE OF THESE DOCUMENTS AFTER FAILURE TO COMPENSATE THE ARCHITECT CONSTITUTES COPYRIGHT INFRINGEMENT. A SERVICE FEE OF 1.5% WILL BE CHARGED PER MONTH ON THE UNPAID BALANCE. THE USER OF THESE DRAWINGS SHALL PAY ALL COSTS OF COLLECTION, INCLUDING ATTORNEY'S FEES.
COPYRIGHT 2015 ©
THESE PRINTS ARE THE PROPERTY OF PARAGON ARCHITECTURE ANDSHALL BE USED ONLY FOR THE PROJECT REFERENCE BELOW
430 S
. G
LE
NS
TO
NE
AV
E. S
PR
ING
FIE
LD
, M
O 6
5802
PH
: 417.8
85.0
002 F
AX
: 417.8
68.0
072
ww
w.p
ara
gonarc
hitectu
re.c
om
MIS
SO
URI
STATE C
ERTIF
ICATE O
F A
UTH
ORIT
Y #
2010011426
PD
1-1
0S
GF
Airport
CB
P/F
IS
23
00
N. A
IRP
OR
T B
LV
D.
SP
RIN
GF
IEL
D, M
O 6
58
02
WA
DR
OS
PA
RA
GO
N
AN
DD
EW
13-1
27
BID
SE
T -
12/1
7/1
5
FIR
ST
FLO
OR
PLA
N -
PLU
MB
ING
- D
EM
OLIT
ION
NO R HT
1/8" = 1'-0"1FIRST FLOOR PLAN - PLUMBING - DEMOLITION
REFERENCE SCALE IN INCHES
0 1 2 3
ENGINEERINGCONSULTANTS
Missouri State Certificate of Authority #2003008820
309.788.0673 FAX: 309.786.5967www.kjww.com
623 26TH AVENUEQUAD CITIES, ILLINOIS 61201
PROJECT #
KJWW ENGINEERING RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATAARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING AND SHALL NOT BE USEDOR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTENAPPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2015 KJWW CORP.
The FUTURE.Built SMARTER.
®
14.0259.01