Hilti, Inc., 5400 South 122 nd East Avenue, Tulsa, OK 74121, (800) 879-8000 FIRESTOP SUBMITTAL PACKAGE Sprinkler Materials FS-ONE Intumescent Caulk Thermafiber Safing Includes: Technical and Installation Data UL Certificate of Compliance LEED information MSDS UL Details Concrete floor/wall C-AJ-1226 - Max. 30" steel, cast iron, Max 6" copper pipe C-AJ-2451 - Max. 2” FlowGuard Gold or max. 3” Blazemaster CPVC (c) Gypsum Wall assemblies W-L-1054 - Max. 30" steel, cast iron, Max. 6" copper pipe W-L-1408 - Multiple steel pipe, steel conduit or EMT, Max 4" W-L-1410 - Max. 3" steel pipe (membrane penetration) W-L-2377 - Max. 2" Blasemaster CPVC, Max. 2" Flowgaurd Gold
Transcript

Hilti, Inc., 5400 South 122nd East Avenue, Tulsa, OK 74121, (800) 879-8000

FIRESTOP SUBMITTAL PACKAGE

Sprinkler

Materials

FS-ONE Intumescent CaulkThermafiber Safing

Includes:Technical and Installation DataUL Certificate of Compliance

LEED informationMSDS

UL Details

Concrete floor/wall

C-AJ-1226 - Max. 30" steel, cast iron, Max 6" copper pipe C-AJ-2451 - Max. 2” FlowGuard Gold or max. 3” Blazemaster CPVC (c)

Gypsum Wall assemblies

W-L-1054 - Max. 30" steel, cast iron, Max. 6" copper pipe W-L-1408 - Multiple steel pipe, steel conduit or EMT, Max 4" W-L-1410 - Max. 3" steel pipe (membrane penetration) W-L-2377 - Max. 2" Blasemaster CPVC, Max. 2" Flowgaurd Gold

Product Information

Chap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

s

Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007

Hilti. Outperform. Outlast.

sodfm,ev iJdjfiwhriuh. NöoWE

Z8Z23awöp3i4eß0288u27 uze

4i5kirdwiloi4jtf-öx-.vbvbvh, ireiv

u9+ß12oeoo

tlke0´9^)&(/R 84tc )v 6453

FS-ONEHigh Performance Intumescent Firestop Sealant

FS-ONE Technical DataChemical basis Water-based intumescent acrylic

dispersionColor RedApplication temperature 40°F to 104°F (5°C to 40°C) Skin forming time Approx. 20-30 min.Curing time Approx. 2 mm / 3 daysMovement capability Approx. 5%Expansion rate Up to 3-5 times (unrestricted): original volumeTemperature resistance (cured) –40°F to 212°F (–40°C to 100°C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:108City of New York MEA 326-96-M Vol. IVTested in accordance with • UL 1479

• ASTM E 814• ASTM E 84

At 73°F (23°C) and 50% relative humidity

FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION

FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY

66Y7

FMAPPROVED

For Penetration Fire Stops. Consult the Factory Mutual Research Corporation Approval Guide.

R

C

LASSIFIED

FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY

UNDERWRITERS LABORATORIES, INC. FOR USE IN TROUGH-PENETRATION

FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY

66Y7

Product description• Intumescent (expands when exposed to fire) firestop sealant that

helps protect combustible and non-combustible penetrations forup to 4 hours fire rating

Product features• Smoke, gas and water resistant after material has cured

• Contains no halogen, solvents or asbestos

• High fire rating properties

• Water based, easy to clean

• Protects most typical firestop penetration applications

• Can be painted

• Single component systems available

• Meets LEED™ requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings

Areas of application• Steel, copper and EMT pipes

• Insulated steel and copper pipes

• Cable bundles

• Closed or vented plastic pipes

• HVAC penetrations

For use with• Concrete, masonry, drywall and wood floor assemblies

• Wall and floor assemblies rated up to 4 hours

Examples• Sealing around plastic pipe penetrations in fire rated construction

• Sealing around combustible and non-combustible penetrations infire rated construction

1. Clean opening. 2. Pack mineral wool.(If required)

3. Apply FS-ONE. 4. Smooth FS-ONE.

5. Leave completedseal undisturbed for 48hours.

6. Fasten identificationplate (if required).

1. Clean opening. 2. Pack mineral wool.(If required)

3. Apply FS-ONE. 4. Smooth FS-ONE.

5. Leave completedseal undisturbed for 48hours.

6. Fastenidentification plate (ifrequired).

Firestop System

Notice • Before handling, read Material Safety DataSheet and

product label for safe usage and health information.

• Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information

Opening 1. Clean the opening. Surfaces to which FS-ONE will be

applied should be cleaned of loose debris, dirt, oil,moisture, frost and wax. Structures supportingpenetrating items must be installed in compliancewith local building and electrical standards.

Application of firestop sealant 2. Install the prescribed backfilling material type and

depth to obtain the desired rating (if required). Leavesufficient depth for applying FS-ONE.

3. Application of firestop sealant: Apply FS-ONE to therequired depth in order to obtain the desired fire rating.Make sure FS-ONE contacts all surfaces to providemaximum adhesion. For application of FS-ONE use astandard caulking gun, foil pack gun, bulk loader andbulk gun. With FS-ONE buckets, Graco type sealantpumps may be used. (Contact pump manufacturer forproper selection).

4. Smoothing of firestop sealant: To complete the seal,tool immediately to give a smooth appearance.Excess sealant, prior to curing, can be cleanedaway from adjacent surfaces and tools with water.

5. Leave completed seal undisturbed for 48 hours.

6. For maintenance reasons, a penetration seal couldbe permanently marked with an identification plate.In such a case, mark the identification plate andfasten it in a visible position next to the seal.

Not for use • High movement expansion joints

• Underwater

• On materials where oil, plasticizers or solvents maybleed i.e. impregnated wood, oil based seals, greenor partially vulcanized rubber

• In any penetration other than those specificallydescribed in this manual or the test reports

Storage • Store only in the original packaging in a location

protected from moisture at temperatures between 40°F (5°C) and 86°F (30°C)

• Observe expiration date on the packaging

Installation instructions for FS-ONE

Firestop System

Firestop System

CA

BLE

PIP

E

Revision Date: 2/25/09 GREEN BUILDING MATERIALS CERTIFICATION FORM PROJECT NAME: __________________________ CONTRACTOR: ___________________________________________ SPEC SECTION(S): ______________________________________

CONTACT NAME: ___________________________________________ TEL. NO: ______________________________ SUBMITTAL NO: ______________________________________

Contains Recycled Content?

For wood products [Y/N]

Product Vendor or Manufacturer Total

Installed COST

Material COST

[excluding labor

+ equip.] % post con-

sumer 1

% post indus- trial 2

Manufacture Location 3

[City, State]

Raw Materials Origin 4

[City, State]

Contains Rapidly Renew- ables? 5 [note %]

FSC Certi- fied? 6

No added urea-

formalde-hyde?

VOC Content 7

[adhesives, sealants, paints,

coatings]

1. FS One Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 75g/l

2. CP 604 Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 53g/l

3. CP 606 Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 71g/l

4. CP 672 Hilti NK NK Tampa, Florida

Tampa, Florida No NA NA 0g/l

5. CP 672 FC Hilti NK NK Tampa, Florida

Tampa, Florida No NA NA 24.7g/l

6. CP 601S Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 3g/l

7. CP 620 Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 15g/l

8. CP 637 Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 0g/l

9. CP 657 Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 3.9g/l

10. CP 136 Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 0g/l

11. CP 617/619T Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 5.2g/l

12. CP 618 Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 14.5g/l

13. CP 658T Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 3.9g/l

14. CP 643/4 Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 7.6g/l

15. CP 648-S/E Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 7.6g/l

16. CP 777/767 Hilti NK NK Waubash, Indiana

Waubash, Indiana No NA NA 0g/l

NK = Not Known N/A = Not Applicable

NOTES / DEFINITIONS: 1. Post-Consumer Recycled Content: Portion of material or product derived from discarded consumer waste that has been recovered for use as a raw material [e.g., plastic bottles, newspaper] 2. Post-Industrial Recycled Content: Portion of material or product derived from recovered industrial and mfg. materials that are diverted from municipal solid waste for use in a different mfg.

process, prior to use by a consumer [e.g., fly-ash in concrete or synthetic gypsum board, both of which are by-products of coal-burning power plants]. Spills and scraps from the original manufacturing process that are combined with other constituents after a minimal amount of reprocessing for use in further production of the same product do not qualify.

3. Manufactured: Final assembly of components into building product that is furnished and installed by trades [e.g., if the hardware comes from Dallas, TX, the lumber from Keene, NH, and the joist is assembled in Kent, WA; then the location of final assembly is Kent, WA]. www.gpsvisualizer.com/calculators can be used to calculate straight-line distance between project site / New York, NY and location of manufacture and raw material source. Note: location noted on material data sheets is often corporate location; need manufacturer to verify actual manufacture location.

4. Raw Materials: Virgin or recovered resources from which the product’s components are made [i.e., before processing or manufacturing]. 5. Rapidly Renewable: Materials and products made from raw materials that are harvested within a 10-year cycle [e.g., bamboo, cork, linoleum, fast-growing poplar, wheatboard, wool carpet]. 6. FSC Certified: Wood-based products that are certified by the Forest Stewardship Council and carry a Chain-of-Custody certificate number from the vendor or manufacturer. 7. VOC Content: The quantity of volatile organic compounds contained in products such as adhesives, sealants and architectural coatings. VOC content is to be reported in grams/liter or lbs/gallon,

less water and any exempt compounds/solvents.

CONTRACTOR CERTIFICATION: I, ________________________________________ a duly authorized representative of______________________________________________ hereby certify that the information contained herein accurately represents the listed “green building” characteristics of the materials to be provided by our company as components of the building construction. Furthermore, I understand that any change in such “green building” material characteristics during the purchasing and/or installation period will require prior written approval from the Construction Manager and Owner.

SIGNATURE OF AUTHORIZED REPRESENTATIVE: _____________________________________________ DATE: ______________________ VOC Requirements for Building Products 2/25/09 LEED1 EPA2 SCAQMD3 BAAQMD4 Green Seal5

Adhesive & Sealant

250 g/l SCAQMD RULE 1168

Not specified

250 g/l RULE 1168

250 g/l RULE 51

Not specified

Paints 150 g/l - non flat 50 g/l - flat

380 g/l -non flat 250 g/l - flat

50 g/ -non flat 50 g/l – flat

RULE 1113

150 g/ -non flat 100 g/l - flat

100 g/ -non flat 50 g/l - flat

Fire Retardant / Resistive Coatings

Not specified

450 g/l (opaque)

350 g/l (pigmented)

RULE 1113

350 g/l RULE 3

Not specified

1 LEED – Leadership in Energy & Environmental Design – Green Building Rating System for New Construction & Major Renovations (LEED-NC) Version 2.1 2 EPA 40CFR Part 59 National Volatile Organic Compound Emission Standards for Architectural Coatings 3 South Coast Air Quality Management District – State EPA / Southern California 4 Bay Area Air Quality Management District – State EPA / San Francisco Area 5 Green Seal - Green Seal is an independent, non-profit organization that strives to achieve a healthier and cleaner environment by identifying and promoting products and services that cause less toxic pollution and waste, conserve resources and habitats, and minimize global warming and ozone depletion. Based in Washington, D.C.

17. CP 680’s & access. Hilti NK NK Kaufering, Germany

Kaufering, Germany No NA NA 7.6g/l

Sheet Drawing No.HILTI, Inc.

Tulsa, Oklahoma USA (918) 252-6000Date

Scale

FRONT VIEWA

A

SECTION A-A

NOTES : 1. MAXIMUM DIAMETER OF OPENING : A. 32-1/4" FOR STEEL STUD WALLS. B. 14-1/2" FOR WOOD STUD WALLS.

2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 2-1/4". 3. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT OF CONTACT. 4. PIPE MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45°

FROM PERPENDICULAR.

1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U300 OR U400 SERIES) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2-1/2" WIDE.

3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING : A. MAXIMUM 30" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER). B. MAXIMUM 30" DIAMETER CAST IRON PIPE. C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE. D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT. E. MAXIMUM 4" NOMINAL DIAMETER EMT.

4. MINIMUM 5/8" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT. 5. MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT.

WL1054q

1 of 1

7/32" = 1"

Nov. 6, 2002

UL/cUL SYSTEM NO. W-L-1054

F-RATING = 1-HR. OR 2-HR. T-RATING = 0-HR.

L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ. FT. L-RATING AT 400°F = 4 CFM/SQ. FT.

WL1

054q

.1106

02

1

3

2

4

5

THERMAFIBER® Safing Insulation is a mineral-wool-type insulation that resists temperatures up to 2,000 °F (1,093 °C), thus offering superior fire protection in a wide variety of fire-rated applications. It isa UL- and OPL-labeled product especially intended for tested UL and OPL Designs, as well as many otherfire- and smoke-tested assemblies. This product is noncombustible per Standard NFPA 220 when testedin accordance with ASTM E 136, and moisture-resistant, noncorrosive, nondeteriorating, mildew-proofand vermin-proof. It permits dry construction for all-year-round work. Also, THERMAFIBER SafingInsulation is available plain, or with scrim-reinforced foil facing (FSP) that serves as a vapor retarderand/or smoke barrier.

THERMAFIBER Safing Insulation is compatible with both THERMAFIBER® Curtain Wall CW Insulations andTHERMAFIBER FIRESPAN™ Insulations.

THERMAFIBER Safing Insulation is a key element in a wide variety of fire-tested construction assemblies.It is used with THERMAFIBER Curtain Wall and FIRESPAN Insulations in applications to contain both fireand smoke to the area of origin. Especially for mid- and high-rise buildings, where fire and smoke mustbe prevented from spreading to the next floor. Since the floor assembly is typically fire-rated, one routefor the fire spread is through and up the exterior curtain wall system. THERMAFIBER Safing Insulation isalso used in conjunction with various sealants and caulks, in wall and floor penetration (poke-through)applications, head-of-wall construction joints, and other construction joints.

It is important to note that one of the most valuable yet misunderstood applications of THERMAFIBER Safing Insulation is its use in exterior curtain wall assemblies to safe-off the openingbetween concrete floor slabs and the curtain wall assemblies. Many people still believe the myth that allthermal insulations are the same when used in the curtain wall spandrel panels as long as THERMAFIBER Safing Insulation is used in the assembly. This is simply not true. Actual fire tests haveproven that low-melt-point insulations, such as glass fiber types, will disintegrate quickly once exposedto fire, leaving the curtain wall unprotected. Then, as the now-unprotected curtain wall disintegrates orfalls away, the safing insulation will no longer be supported, and the fire will spread to the floor(s) above.Effective perimeter fire containment can only be achieved when a fire-compatible product with the abilityto resist high temperatures (such as THERMAFIBER Curtain Wall Insulations or THERMAFIBERFIRESPAN Insulations) is used in conjunction with the THERMAFIBER Safing Insulation, acting together asa system. (See TF685, TF686 and TF871 for additional information).

In curtain wall fire-containment applications, THERMAFIBER Safing Insulation fills the void between theslab edge and the curtain wall insulation to contain fire. Foil-faced insulation impedes the passage ofsmoke and noxious gases. Install THERMAFIBER Safing Insulation, of proper width (2" to 8" max. opening), compression fit in safe-off area (foil side up, if required) between THERMAFIBER FIRESPAN orCW Curtain Wall Insulation and floor slabs, on safing "Z" clips spaced as required in the design (24" or12" o.c. maximum), leaving no voids. Compression fitting the safing insulation is critical to assuring atight seal. See specific test description for proper installation details. Install proper topping material,such as THERMAFIBER SMOKE SEAL Compound, or other approved smoke sealants as indicated in the spe-cific test description or architectural specification.

THERMAFIBER Safing Insulation provides a noncombustible, fire-resistant forming/packing material formany types of penetrations in walls and floor/ceilings. In all poke-through penetrations, clean substrateof dirt, dust, grease, oil, efflorescence, loose material or other matter. With a serrated knife, cut THERMAFIBER Safing Insulation slightly wider than the opening. Compress and tightly fit the minimumthickness and density of insulation required (per system specification) completely around penetrant. Forfloor slab openings, compress or install THERMAFIBER Safing Insulation according to details indicated inthe specific test description or architectural specification to seal completely around cables, ducts, pipingor other utilities.

THERMAFIBER Safing Insulation is also used as a forming material in head-of-wall, floor to floor, floor towall, and wall to wall construction joints. It is compressed and slid into joint openings to completely fillthe gap between the intersection of the walls, floor, etc.

THERMAFIBER® Safing Insulation

UL- and OPL-labeled* safing insulation for firestops and fire-containment systems • Firestop product for curtain wall fire and smoke containment systems, floor and wall penetrations,

head-of-wall, and other construction joint systems. • Fire resistant and noncombustible. • Economical; installs quickly and easily. • Aids sound control in many assemblies. • Available in unfaced felt (plain) or with a tough scrim-reinforced foil facing (FSP). • Durable; nondeteriorating and noncorrosive.

Description

Perimeter Fire Containment,Penetrations and Construction Joints

Installation Perimeter Installation

Penetration Application

Construction JointApplication

* UL is an abbreviation for Underwriters Laboratories Inc.; OPL is an abbreviation for Omega Point Laboratories, Inc.

Submittal Sheet07840

Trademarks THERMAFIBER, FIRESPAN and THENAME IN MINERAL WOOL are trade-marks of Thermafiber Inc. SMOKESEAL is a trademark of United StatesGypsum Company.

NoteProducts described here may not beavailable in all geographic markets.Consult your local sales office or rep-resentative for information.

Notice THERMAFIBER INC. shall not beliable for incidental and consequentialdamages, directly or indirectlysustained, nor for any loss caused byapplication of these goods not inaccordance with current printedinstructions or for other than theintended use. THERMAFIBER’Sliability is expressly limited toreplacement of defective goods. Anyclaim shall be deemed waived unlessmade in writing within thirty (30)days from date it was or reasonablyshould have been discovered.

Safety First!Follow good safety and industrialhygiene practices while handling andinstalling products and systems.Take necessary precautions and wearthe appropriate personal protectiveequipment as needed. Read materialsafety data sheets and related litera-ture on products before specificationand/or installation.

Health AspectsInformation about health aspects ofusing THERMAFIBER® Curtain WallInsulation products are thoroughlyexplained in North AmericanInsulation ManufacturersAssociation’s (NAIMA) Health andSafety facts for rock and slag woolinsulation document #63. ContactThermafiber, Inc. for more details.

Product Designation Flame Spread Smoke Developed Safing, Regular (Unfaced) 0 0 Safing (Foil-Faced) 25 0 Products have a class A interior finish rating per NFPA 101, life safety code.

Product Actual Density Minimum ApplicationDesignation Density Tolerance-pcf(1) Thickness MethodSafing 4.0 -0.5 +1.0 1" safing clips and/or compression fitSafing 6.0 -0.75 +2.0 1-1/2" safing clips and/or compression fit Safing 8.0 -1.0 +2.0 1" safing clips and/or compression fit(1) On packaging weight basis.

THERMAFIBER Safing Insulation meets the following:

ASTM C 665 - Federal Specification HH-I-521F–Safing insulation as Types I and III, Class A, Category 1.

ASTM C 612-00 - Federal Specification HH-I-558B–Safing insulation as Types IA, IB and II.

ASTM E 136 - Rated noncombustible as defined by NFPA Standard 220 when tested according to ASTM E 136.

ASTM E 814 or UL 1479 - Safing insulation used in conjunction with SMOKE SEAL Compound, or other approved material in through - penetration firestop systems.

UL 2079 - Safing insulation used in conjunction with various sealants and caulks in construction jointsystems.

ASTM C 553 - THERMAFIBER Insulations absorb less than 1% moisture by weight and volume.

Safing insulation products are approved by: New York City Board of Standards & Appeals– 39-74-SM &MEA 209-82-M, Vol. II.

THERMAFIBER blankets are a mineral fiber material manufactured from blast furnace slag, a by-product ofiron ore reduction, and naturally occurring rock. THERMAFIBER blankets contain greater than 80% post-industrial recycle content. This product contains No Asbestos.

System performance following substitution of materials or compromise in assembly design cannot becertified and may result in failure of fire performance under certain conditions. Products and systemsprovided by Thermafiber Inc. are warranted to be free from defects in material workmanship. ContactThermafiber Inc. for complete warranty details.

Store in a cool, dry place.

Surface BurningCharacteristics (According to ASTM E 84)

Product Density

Standards Compliance

Composition andMaterials

Warranty

Storage

Submittal Approvals:

Product Data

Job Name

Contractor Date

INC

3711 West Mill Street Wabash, IN 46992-8687 1-888-TFIBER1 (834-2371)www.thermafiber.com

TF612/Rev 11/06Copyright 2004, Thermafiber Inc. Printed in U.S.A.

Technical Data

MMAADDEE IINN UUSSAATTHHEERRMMAAFFIIBBEERR MMAADDEE FFRROOMM

RREECCYYCCLLEEDD MMAATTEERRIIAALLSS

For the most up-to-date technical data, please refer to our website at www.thermafiber.com

Material Safety Data Sheet

MSDS No.: 270Revision No.: 003Revision Date: 06/18/03Page: 1 of 2

Product name: Mineral woolDescription: Synthetic vitreous fiber

Supplier: Hilti, Inc. P.O. Box 21148, Tulsa, OK 74121

Emergency # (Chem-Trec.): 1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)

INGREDIENTS AND EXPOSURE LIMITS

Ingredients: CAS Number: P EL: TLV: STEL:

Slag wool fiber 65997-17-3 NE 1 fiber / cc NE

Phenolic resin 09003-35-4 NE NE NE

Polyvinyl alcohol 09002-89-5 NE NE NE

Abbreviations: PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. STEL = Short Term Exposure Limit. NE = None Established.NA = Not Applicable.

PHYSICAL DATA

Appearance: 2’ x 4’ x 4” sheets. Odor: Negligible.

Boiling Point: Not applicable. Vapor Pressure: Not applicable.

Melting Point: Approx. 2400° F VOC Content: Not applicable.

Evaporation Rate: Not applicable. Solubility in Water: Insoluble.

pH: Not applicable. Specific Gravity: Not determined.

FIRE AND EXPLOSION HAZARD DATA

Flash Point: Not applicable. Flammable Limits: Not applicable.

Extinguishing Media: As appropriate for surrounding fire; material does not burn.

Special Fire Fighting Procedures: Soak cartons to help prevent the spread of fire. Use a self-contained breathing apparatus when fighting firesinvolving chemicals.

Unusual Fire and Explosion Hazards: None known.

REACTIVITY DATA

Stability: Stable. Hazardous Polymerization: Will not occur.

Incompatibility: Strong acids.

Hazardous Decomposition Products: Thermal decomposition products can be formed at temperatures exceeding 2000° F. Thermal decompositioncan yield CO and CO2.

Conditions to Avoid: None known.

HEALTH HAZARD DATA

Known Hazards: Acute: Eye, skin and respiratory irritation. Chronic: Respiratory impairment.

Routes of Exposure: Inhalation, Dermal.

Signs and Symptoms of Exposure: Eyes: Mechanical irritation. Skin: Itching, irritation. Inhalation: Nose, throat and upper respiratory tractirritation.

Carcinogenicity: Slag wool has been classified by the IARC as Group 3 – Unclassifiable as to Carcinogenicity in Humans.

Medical Conditions Eye, skin, and respiratory conditions.Aggravated by Exposure:

INTR

ODUC

TION

APPL

ICAT

IONS

/ PR

ODUC

TSSY

STEM

DET

AILS

ESTI

MAT

ING

TABL

ES /

TEC

H DA

TA

Saving Lives through innovation & education ❘ Hilti Firestop Guide 2005–2006 ❘ 1-800-879-8000 ❘ www.us.hilti.com480

W3321_12_TablesTech_TP_70.qxd 3/23/05 7:56 AM Page 480

Material Safety Data SheetINTRODUCTION

APPLICATIONS / PRODUCTSSYSTEM

DETAILSESTIM

ATING TABLES / TECH DATA

Saving Lives through innovation & education ❘ Hilti Firestop Guide 2005–2006 ❘ 1-800-879-8000 ❘ www.us.hilti.com 481

MSDS No.: 270Revision No.: 003Revision Date: 06/18/03Page: 2 of 2

EMERGENCY AND FIRST AID PROCEDURES

Eyes: Flush with plenty of water while holding eyelids apart. Avoid rubbing the eyes as mechanical abrasions canoccur. Call a physician if symptoms persist.

Skin: Wash with soap and water. Launder clothing before reuse.

Inhalation: Move to fresh air.

Ingestion: No ill effects expected.

Other: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.

CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT

Ventilation: General (natural or mechanically induced fresh air movements).

Eye Protection: Safety goggles recommended to prevent particulates from irritating the eyes.

Skin Protection: Cloth gloves and long sleeves to protect skin from irritating fibers.

Respiratory Protection: Use local exhaust and/or a NIOSH-approved dust respirator when air movement is inadequate to control dusts / fibers below recommended exposure levels.

PRECAUTIONS FOR SAFE HANDLING AND USE

Handling and Storing Precautions: Avoid generating dusts. Local exhaust may be required to control dusts if power tools are used for cutting /trimming. Wear appropriate personal protective equipment. Store away from moisture; keep dry.

Spill Procedures: Not applicable.

REGULATORY INFORMATION

Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication Standard 29 CFR1910.1200.

HMIS Codes: Health 1, Flammability 0, Reactivity 0, PPE B (Gloves, Goggles)

DOT Shipping Name: Not regulated.

IATA / ICAO Shipping Name: Not regulated.

TSCA Inventory Status: Chemical components listed on TSCA inventory.

SARA Title III, Section 313: This product does not contain any toxic chemicals which are subject to reporting under Section 313 of SARATitle III (40 CFR Part 372).

EPA Waste Code(s): Not regulated by EPA as a hazardous waste.

Waste Disposal Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that comply with local,state, and federal safety, health and environmental regulations.

CONTACTS

Customer Service: 1 800 879 8000 Technical Service: 1 800 879 8000

Health / Safety: 1 800 879 6000 Jerry Metcalf (x6704)

Emergency # (Chem-Trec): 1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or warranty of any kindexpressed or implied is made with respect to the information provided.