PLUMBING LEGEND AND SYMBOLSSYMBOL ABBREVIATION DESCRIPTION
DETAIL REFERENCE
SECTION REFERENCE
PLUMBING STACK OR RISER REFERENCE
EQUIPMENT REFERENCE
FILTERED WATER
SOFTENED / CONDITIONED COLD WATER
COLD WATER
HOT WATER
HOT WATER RETURN
POP-OFF DRAIN LINE OR HIDDEN WATER LINE
SOIL or WASTE BELOW GRADE (or FLOOR)
SOIL or WASTE ABOVE GRADE (or FLOOR)
PLUMBING VENT
CONDENSATE DRAIN
GAS LOW PRESSURE
CIRCUIT SETTER
SHUT OFF VALVE
SHUT OFF VALVE OR GAS COCK ON RISER
SWING CHECK VALVE
PRESSURE REDUCING VALVE
PRESSURE-TEMPERATURE RELIEF VALVE
REDUCED PRESSURE BACKFLOW PREVENTER
PIPE DOWN
PIPE UP
TEE DOWN
TEE UP
PIPE RISER & PIPE DROP (UP AND DOWN)
FLOOR CLEANOUT
WALL CLEANOUT
CLEANOUT PLUG
YARD CLEANOUT or CLEANOUT TO GRADE
CAP ON END OF PIPE
HOSE BIBB WITH VACUUM BREAKER
WATER HAMMER ARRESTOR
BALL VALVE
GAS REGULATOR
GAS COCK (or GAS STOP)
GAS SOLENOID
POINT OF CONNECTION
POINT OF DEMOLITION
ACCESS PANEL
ABOVE
BELOW
AMERICAN GAS ASSOCIATION
CONNECTION
CONTINUATION
EXISTING
NEW
DOWN
HANDICAPPED
INVERT ELEVATION
TYPICAL
UNLESS OTHERWISE NOTED
VENT THROUGH ROOF
WITH
PLUMBING FIXTURE UNIT
SECONDARY CONDENSATE
DETAIL No.
SHEET No.
STACK/RISER
ID. No.
EQUIPMENT
ID. No.
FW
SCW
CW
HW
HWR
S or W
S or W
V
COND
G
CS
SOV
SOV or GC
CV
PRV
PTR
RPBFP
DN
UP
DN
UP
FCO
WCO
CO
COTG
HB
WHA & TP
BV
GR
GC
GS
P.O.C.
P.O.D.
A.P.
ABV.
BEL.
A.G.A.
CONN
CONT
(E)
(N)
DN
H.C.
IE
(TYP)
U.O.N.
VTR
W/
FU
SEC COND
COND
G
AP-1
SHEET INDEX
SCOPE OF WORK
1. THE TOTAL INSTALLATION SHALL COMPLY WITH ANY AND ALL REQUIREMENTS OF THE LEGALLY CONSTITUTED AUTHORITIES HAVING JURISDICTION INCLUDING 2010 CBC (CALIFORNIA BUILDING CODE) AND 2010 CMC/CPC (CALIFORNIA MECHANICAL AND PLUMBING CODE).
2. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND SHALL THOROUGHLY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS UNDERWHICH HE WILL BE REQUIRED TO WORK.
3. ALL INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY. BEFORE PROCEEDING WITH THE WORK THISCONTRACTOR SHALL CAREFULLY CHECK AND VERIFY ALL DIMENSIONS, SIZES, REQUIRED CLEARANCES AND SHALL ASSUME FULL RESPONSIBILITYFOR THE FITTING OF ALL EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK OF OTHER TRADES.
4. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT ALL OFFSETS, BENDS, SPECIAL FITTINGS AND LOCATIONS ARE NOTEXACTLY LOCATED.
5. IN THE PREPARATION OF THESE DOCUMENTS, CERTAIN ASSUMPTIONS ARE MADE REGARDING EXISTING CONDITIONS. SOME OF THESEASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING ADDITIONAL SUMS OF MONEY OR DESTROYING OTHERWISE ADEQUATE ORSERVICEABLE PORTIONS OF EXISTING BUILDINGS AND/OR EQUIPMENT. THEREFORE, THE ENGINEER SHALL NOT BE HELD RESPONSIBLE FOR ANYCHANGES OR ADDITIONAL COSTS INCURRED DUE TO EXISTING CONDITIONS.
6. ITEMS RELATED TO PLUMBING UTILITIES AND/OR OTHER SERVICE(S); MATERIALS, LABOR, PERMITS, FEES, ETC., SHALL BE VERIFIED WITH THERESPECTIVE SERVING UTILITY COMPANY PRIOR TO SUBMISSION OF A BID. THE ACT OF SUBMITTING A BID SHALL CONSTITUTE FULL RESPONSIBILITYOF THE CONTRACTOR TO INSTALL SERVICE(S) IN COMPLIANCE WITH THE REQUIREMENTS OF THE SERVING UTILITY COMPANY AND THE MECHANICALENGINEER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CHARGES LEVIED BY THE SERVING UTILITY COMPANY EXCEPTING THE FIRSTBILLING DEPOSIT.
7. THE CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING OUT HIS WORK AND EQUIPMENT. HE SHALL COORDINATE THEWORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND ALL JOB CONDITIONS.
8. THE INSTALLATION OF ACCESS PANELS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING, ADJUSTMENT, INSPECTION,REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY LOCATED WITH REFERENCE TO THE FINISHED BUILDING.
9. ALL EQUIPMENT AND FIXTURES INSTALLED UNDER THIS CONTRACT SHALL BE HUNG OR ANCHORED IN ACCORDANCE WITH TITLE 24,TABLE NO. 16 A-O.
10. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO CONSTRUCT THE PROJECT IN ACCORDANCE WITH TITLE 24, CALIFORNIA CODE OFREGULATIONS.
11. WHERE MATERIAL IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF THE SAME TYPE AND QUALITY AS EXISTING MATERIAL.
12. THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE ALL REQUIRED HYDRAULIC CALCULATIONS AND FIRE SPRINKLER HEAD LOCATION INACCORDANCE WITH NFPA 13 TO THE LOCAL FIRE DEPARTMENT FOR REVIEW AND APPROVAL OF THE FIRE PROTECTION SYSTEM.
13. TEST SYSTEM(S) IN ACCORDANCE WITH REQUIREMENTS OF THE GOVERNING AUTHORITIES.
14. ALL CLEANOUTS SHALL BE INSTALLED WHERE READILY ACCESSIBLE AND LOCATED AS PER CODE REQUIREMENTS THE CONTRACTOR SHALLCOORDINATE ALL CLEANOUT LOCATIONS WITH EQUIPMENT CABINETS, ETC. AND THE ARCHITECT PRIOR TO ANY INSTALLATION.
15. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING ALL PAVED AREAS WHICH ARE EXCAVATED AND/OR DAMAGED BY HISOPERATIONS. IN ADDITION, THE CONTRACTOR SHALL RESTORE TO THEIR ORIGINAL CONDITION ALL PLANTED AREAS DAMAGED BY HIS OPERATIONS.
16. ALL CONNECTIONS TO EXISTING SERVICES SHALL BE MADE SUCH THAT INTERRUPTION TIME WILL BE AS SHORT AS POSSIBLE. THE CONTRACTORSHALL GIVE THE OWNERS REPRESENTATIVE SUFFICIENT NOTICE OF SUCH INTERRUPTIONS AND THE ACTUAL SHUT-DOWN TIME SHALL BE AT A TIMEDESIGNATED BY THE OWNERS REPRESENTATIVE.
17. ALL EXTERIOR WATER SHUT-OFF VALVES BELOW GROUND SHALL BE INSTALLED IN YARD BOXES WITH COVERS CONSPICUOUSLY MARKED "WATERSHUT-OFF" RESPECTIVELY.
18. ALL REQUIRED CLEANOUTS SHALL BE INSTALLED AS PER SEC. 707.0 & 719.0 OF THE PLUMBING CODE.
19. EACH VENT SHALL RISE VERTICALLY TO A POINT NOT LESS THAN SIX (6) INCHES IN HEIGHT ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE BEFOREBEING CONNECTED TO ANY OTHER VENT.
20. NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE DISINFECTED PRIOR TO USE ACCORDING TO THE METHOD SET IN SECTION 609.9 OF THEPLUMBING CODE.
21. ALL PLUMBING FIXTURES AND FIXTURE FITTINGS SHALL MEET THE STANDARDS REFERENCE IN TABLE 5.503.6..
22. ALL EXPOSED GAS PIPING SHALL BE PROTECTED AGAINST CORROSION BY COATING OR WRAPPING WITH AN INERT MATERIAL APPROVED FOR SUCHAPPLICATIONS.
PLUMBING GENERAL NOTESFIXTURE SCHEDULE
WATER HEATER SCHEDULE
Schedule 40 ABS Solvent-Weld ABS
Copper L Tube Soldered Bronze N/A125
No-hub Cast Iron No-hub N/A N/AN/A
N/AN/A
PIPE MATERIAL SCHEDULE
SERVICE VALVE
COLD WATERABV. GROUND
COLD WATERBELOW GROUND BEYOND 5'-0"
HOT WATERABV. GROUND
FUEL GAS
VENT
WASTE & SOIL DRAINSBELOW GRADE
WASTE & SOIL DRAINSABOVE GRADE
CONDENSATE
COPPER L TUBE
SCHEDULE 80 PVC
COPPER L TUBE
STEEL 40, BLACK
NO-HUB CAST IRON
SCHEDULE 40 ABS
NO-HUB CAST IRON
COPPER M TUBE
SOLDERED
SOLVENT-WELD
SOLDERED
WELDED
NO-HUB
SALVENT-WELD
NO-HUB
SOLDERED
CAST BRONZE/WROUGHT COPPER 125
BALL
GATE
CHECK
PVC 125 GATE
CAST BRONZE/WROUGHT COPPER 125 CHECK
BALL
MALL. IRONSTEEL WELD
150
150
SQR HEAD COCK
N/A N/A N/A
N/A N/AABS
N/A N/A N/A
125 N/ABRONZE
PIPE MATERIAL
& WEIGHT
TYPE OF
JOINTS
PRESSURE
FITTING
MATERIAL
SHUT-OFF
RATINGS
PSI - SwP
GAS LOAD SCHEDULE
SYMBOL ITEM LOCATION DEMAND (IN CFH)
AC-1
AC-2
AC-3
AIR CONDITIONER
AIR CONDITIONER
AIR CONDITIONER
ROOF
ROOF
ROOF
136
56
75
TOTAL GAS LOAD 810 CFH
<400 FT.LONGEST DEVELOPED PIPE LENGTH (LOW PRESSURE GAS)
AC-4 AIR CONDITIONER ROOF 181
AC-5 AIR CONDITIONER ROOF 181
AC-6 AIR CONDITIONER ROOF 181
PLUMBING SIZING FORM
VELOCITY FOR HOT WATER PIPING LESS THAN 5 FT. PER SECOND
VELOCITY FOR COLD WATER PIPING LESS THAN 8 FT. PER SECOND
PIPE SIZE IS BASED ON CHART A-4 @ 3.0 P.S.I. / 100 FT.
FIXTURE UNITS ARE BASED ON TABLE A-2 FROM APPENDIX A
1171
691
47
158
380
13
24
5
1
1171
630 160
230
10
245
64
0
0
27
56
100
17
10
8.0
8.0
5.0
6.0
7.5
4.5
4.0
1
2
1
0
0 1.5
5
2.5
3.2 4
6
JS
U
S
3
4
1.5
107
3
8
1.5
L
WC
1
5
4
30
FIXTURE UNITS
3/4"
3"
4"
1-1/2"
2"
2-1/2"
1"
1-1/4"
SIZE
1/2"
F. TANK
TOTAL FIXTURE UNITS
PIPE SIZE SCHEDULE
F. VALVE GPM VELOCITY NUMBER TOTAL
FIXTURE UNITS
FIXTURE UNIT
-- - -
-- - -
-- - -
MAXIMUM SIZE FOR HOT WATER PIPING SHALL BE 1-1/2"
70TOTAL G.P.M.
.51 DF .5
60- EXISTING 60
-- - -
-- - -
275 W. Hospitality Lane Suite #100San Bernardino, CA 92408
Phone: 909.890.3700Fax: 909.890.3770
email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTER
EDPR
OF
RE
ENI
GN
E
ESSIONAL
ETA
TS
FO FILACO
AI
NR
M
No. 33209
E CH A N I CAL
NHOJNEV
ET
S
M.
NO
S
EXP. 9-30-2013
J o b N u m b e r
D a t e
s h e e t n u m b e r
s h e e t t i t l e
p r o j e c t
a p p r o v a l s
c o n s u l t a n t
o w n e r
a r c h i t e c t
R e v i s i o n D a t e
R e v i s i o n D a t e
a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.
LIC
ENSEDA
RCHITECT
NO. C-28593
ST
A
T
EOFC
A
LIFOR
NIA
H
ERT G U
AA
S
R
EN. 10 -31- 13
2535 Commerce WayCommerce, CA 90040
R e v i s i o n D a t e
5655 JILLSONSTREET
COMMERCE, CA90040
P0.1
PLUMBINGLEGEND
SCHEDULES &NOTES
CC-CLR
CITY OFCOMMERCE
03/26/13
CITY OFCOMMERCE
CENTRALLIBRARY
RENOVATION
12-189
TAGTAG
MARK SPECIFICATION WASTE VENT TRAPCW
RISERHW
RISER
DF 1 Drinking Fountain: Haws model 1119.14 wall mtd., Hi-Lo dual bubbler drinking fountain, 14 GA. type 304 stainless steel with satin finish, polishedchrome plated vandal-resistant bubblers (5703M), front push button (PBA2), polished chrome plated vandal- resistant waste strainer (6462), vandalresistant bottom plates. ADA compliant
2" 1-1/2" INT. 1/2" -
FD 1 Floor Drain: Mifab #F1000, 5 inch round top, lacquered cast iron body with anchor fland and polished stainless steel strainer. Provide with trap primerconnection.
VARIES VARIES VARIES - -
JS 1 Service/Jan. Sink: Commercial Enameling Co. 871 white enameled cast iron floor mounted service sink with K-8940 rim guard. Chicago "897.COservice sink faucet w/ vacuum breaker, hose threaded outlet, pail hook & wall brace.
3" 1-1/2" 3" 3/4" 3/4"
L 1 Lavatory: American Standard "Ovalyn" 0496.221, white vitreous china, under counter mount w/ faucet holes on 4" centers. Chicago Faucets 3400-CPmetering faucet w/ 0.4 gpm aerator, provide ASSE 1070 approved TMV set to 120°,
2" 1-1/2" 1-1/4" 1/2" 1/2"
S 1 One Compartment Sink: Just Manufacturing "Stylist Group" SL-1921-A-GR, 21" X 19" X 6" stainless steel single bowl sink, 19 gauge, self rim, faucetholes on 4" centers. Chicago Faucet 201-RSGN2AE35VPXKABCP, provide ASSE 1070 approved TMV set to 120°, chrome basket strainers w/ 1-1/2"cast brass L.A. pattern P-trap with chrome finish, angle stops w/ rigid riser. (1.5 GPM aerator).
TP 1 Trap Primer: Mifab model number "MR-500", 1/2" inlet and outlet with removable filter screen. May be located as indicated on drawings or as requiredby code. UPC listed. For units serving (2) or more traps provide with Mifab distribution unit model "MI-DU-500". Provided with a 12" x 12" accesspanel.
- - - 1/2" -
U 1 Urinal: American Standard "Allbrook" 6541.511, (1/8) GPF, wall hung, white vitreous china. 3/4" top spud complete with Zurn ZEG6003EV-HW6sensor operated, hardwired flush valve.
2" 1-1/2" INT. 1" -
WC 1 Watercloset: American Standard "Madera" 2234.712, ADA compliant, 15" high rim, (1.28/1.1) GPF, floor mounted, siphon jet, white vitreous china,elongated bowl. 1-1/2" top spud with Sloan ROYAL 111-1.28, manual flush valve, Olsonite plastic seat model 95 ComfortCurve, elongated, openfront, stain & chemical resistant.
4" 2" INT. 1" -
WC 2 Watercloset: American Standard "Madera" 3043.712, ADA compliant, 17" high rim, (1.28/1.1) GPF, floor mounted, siphon jet, white vitreous china,elongated bowl. 1-1/2" top spud with Sloan ECOS 8111-1.6/1.1, sensor operated battery powered flush valve, Olsonite plastic seat model 95ComfortCurve, elongated, open front, stain & chemical resistant.
4" 2" INT. 1" -
WHA 1 Water Hammer Arrestor: Mifab "MWH" series, installed on all quick closing valves and all valves which close with the flow of fluid or on headersserving more than one fixture. Provided with a 12" x 12" access panel.
- - - VARIES -
Sheet # Sheet Name
P0.1 PLUMBING LEGEND SCHEDULES & NOTES
P1.1 PLUMBING DEMOLITION FLOOR PLAN
P2.1 PLUMBING REMODEL FLOOR PLAN
P2.2 PLUMBING GAS & CONDENSATE
P2.3 PLUMBING ROOF PLAN
P3.1 PLUMBING DETAILS
TYPE MARK MFR MODEL VOLUME RECOVERY
ELECTRICAL OPERATINGWEIGHT
(LBS.) ACCESSORIESWATTS VOLTAGE PHASE Hz
WH 1 A. O. Smith DEN-30 30.0 gal 30 gallon recover @ 80°temp. rise
4000 W 208 V 1 60 Hz 100
CALIFORNIA GREEN COMPLIANCE FORM
CALCULATIONS BASED ON CHAPTER 8 WORK SHEETS WS-1 & WS-2
KITCHEN FAUCET
LAV. FAUCET RES.
2.2
2.5
1.5
0.4
4 MIN
.25 MIN
FIXTURE TYPE DURATIONBASELINE FLOWRATE (GPM)
DESIGN FLOWRATE (GPM)
1
DAILY USES
200
200
OCCUPANTS
1760
330
BASELINE GAL.PER DAY
1200
60
DESIGN GAL.PER DAY
1.6 1.28 1 FLUSH 1 200 960 768FLUSH VALVEWATER CLOSET MALE
GRAVITY TANKWATER CLOSET FEMALE
URINAL 1.0 0.125 1 FLUSH 2 200 320 256
1.6 1.28 1 FLUSH 3 200 100 50
3770 2334TOTAL DAILY WATER USE (WU) =
3016 1867.2ALLOWABLE WATER USE =
1148.8TOTAL WATER CONSUMPTION REDUCTION =
38%TOTAL WATER CONSUMPTION REDUCTION SAVINGS =
1
COLD WATER SCHEDULE
fixture
PLUMBING SYSTEM FRICTION LOSS
Min. friction loss (psi) 25
15
LOW
200
4
6.45
29.55
5
9
(from plans, in feet)
(UPC Appendix A.1)
(from civil plans)
(25psi for flushvalve, 15 psi for tank type)
F.U.'s : 107
Dist. from St. to highest
(E) Backflow device loss (psi)
(E) PRV device loss (psi)
Friction loss available to
System static pressure loss (ft. hd.)
(E) 2" Meter pressure loss (psi)
Elev. above St. main (ft.)
280
10.55
(max. friction loss allowable)
system
Maximum velocity not to exceed 8fps.
Friction loss/100 ft.
79 (from local water district)Daily St. High pressure (psi)
25
15
HIGH
200
4
5
9
98
GPM : 70
A=
B=
D=
E=
G=
F=
C=
6.45
48.55
280
17.33
H=
I=
J=
K=
H = (B) (0.43)
I = C - A - E - F - G - H
J = (D) (1.4)
K = (I/J) (100)
Total developed length =
Dist. from St. to highest fixture
plus fitting loss
SCOPE OF WORK INTELS REMODEL OF EXISTING MENS & WOMENS RESTROOM OF LIBRARY ONLY. NEW GAS TO NEW UNITS & CONDENSATION TONEW UNITS. NO OTHER WORK TO BE DONE. EXISTING SITE UTILITIES TO REMAIN. NO SITE WORK TO BE DONE.
1 2
D
1
11
1 1
1
1
3
P.O.DP.O.D
1 2
2 P.O.D
275 W. Hospitality Lane Suite #100San Bernardino, CA 92408
Phone: 909.890.3700Fax: 909.890.3770
email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTER
EDPR
OF
RE
ENI
GN
E
ESSIONAL
ETA
TS
FO FILACO
AI
NR
M
No. 33209
E CH A N I CAL
NHOJNEV
ET
S
M.
NO
S
EXP. 9-30-2013
J o b N u m b e r
D a t e
s h e e t n u m b e r
s h e e t t i t l e
p r o j e c t
a p p r o v a l s
c o n s u l t a n t
o w n e r
a r c h i t e c t
R e v i s i o n D a t e
R e v i s i o n D a t e
a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.
LIC
ENSEDA
RCHITECT
NO. C-28593
ST
A
T
EOFC
A
LIFOR
NIA
H
ERT G U
AA
S
R
EN. 10 -31- 13
2535 Commerce WayCommerce, CA 90040
R e v i s i o n D a t e
GENERAL NOTES
5655 JILLSONSTREET
COMMERCE, CA90040
P1.1
PLUMBINGDEMOLITIONFLOOR PLAN
CC-CLR
CITY OFCOMMERCE
03/26/13
CITY OFCOMMERCE
CENTRALLIBRARY
RENOVATION
12-189
1/8" = 1'-0"PLUMBING DEMOLITION FLOOR PLAN 1
1/8" = 1'-0"PLUMBING DEMOLITION FLOOR PLAN - ATTIC AREA 2
1 EXISTING FIXTURE TO BE REMOVED. REMOVE ALL RELATED PIPING BACK AND CAPIN CEILING AND BELOW SLAB
EXISTING WATER HEATER TO BE REMOVED. REMOVE ALL RELATED PIPING BACK TOPOINT OF DEMOLITION
EXISTING 4" WASTE TO REMAIN
DEMOLITION NOTES
2
3
N
N
F.E
.C.
F.E
.C.
1 2
D
WOMEN'S
5
MEN'S
6
CLASSROOM
2
LITERACY
CENTER
9
STORAGE
8
TEENS
10
COUNCIL
CHAMBERS
LOBBY
1
JANITOR'S
7
1 1/2"ø CW
1 1/2"ø CW
2"ø CW
2"ø CW
1
WC
1/2"ø TP
FD
1
3/4"ø CW
3/4"ø CW
3/4"ø CW
3/4"ø HW
3/4"ø CW
2"ø CW
2"ø CW1 1/2"ø CW
1 1/2"ø CW
1 1/2"ø CW
3/4"ø CW
1 1/2"ø CW
3/4"ø CW
1"ø HW
3/4"ø HW
3/4"ø HW
3/4"ø HW 3/4"ø HW
3/4"ø HW
3/4"ø HW
3/4"ø HW
3/4"ø HW
3/4"ø CW
3/4"ø CW
3/4"ø HW
1
WHA
1
TP
1/2"ø TP
1 1/2"ø CW
3/4"ø CW
3/4"ø CW
2
WC
(TYP. OF 3)
1
JS
1
U
(TYP. OF 2)
1
L
(TYP. OF 2)
1
WC
1
L
(TYP. OF 2)
1
S
1
WHA
1
WHA
FD
1
1
WH
1
1
2
3
1
4
4
6
1
DF
(E) 2" CW2"
2"
2"
7
1 2
D
TEENS
10
STORAGE
8
LITERACY
CENTER
9
COUNCIL
CHAMBERS
LOBBY
1
JANITOR'S
7
WOMEN'S
5
MEN'S
6
CLASSROOM
2
2"ø W4"ø W
3"ø W
1 1/2"ø V
1 1/2"ø V
2"ø V
2"ø V2"ø V
2"ø V 3"ø V2"ø V
2"ø V
4"ø W
1 1/2"ø V
4"ø W
4"ø W
4"ø W
4"ø W
2"ø W
4"ø W
4"ø W
2"ø W
4"ø W 4"ø W
4"ø W
4"ø W
2"ø W
2"ø W
4"ø W
4"ø W
4"ø W
2"ø W
4"ø W
1
U
1
L
1
L
1
WC
1
L
1
L
2"ø W
4"ø W
3"ø V
2"ø V
2"ø W2"ø W
2"ø W
4"ø W
2"ø V
2
WC
FD
1
FD
1
1
S
2"ø V
1
WC
2
WC
2
WC
2
WC
1
JS
1
DF
1
WH
(E)
P.O.C
P.O.C
P.O.C
P.O.C
5
6
(E)
(E)
WCO(TYP.)
(E) WCO
WCO
WCO
WCO
WCO
275 W. Hospitality Lane Suite #100San Bernardino, CA 92408
Phone: 909.890.3700Fax: 909.890.3770
email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTER
EDPR
OF
RE
ENI
GN
E
ESSIONAL
ETA
TS
FO FILACO
AI
NR
M
No. 33209
E CH A N I CAL
NHOJNEV
ET
S
M.
NO
S
EXP. 9-30-2013
J o b N u m b e r
D a t e
s h e e t n u m b e r
s h e e t t i t l e
p r o j e c t
a p p r o v a l s
c o n s u l t a n t
o w n e r
a r c h i t e c t
R e v i s i o n D a t e
R e v i s i o n D a t e
a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.
LIC
ENSEDA
RCHITECT
NO. C-28593
ST
A
T
EOFC
A
LIFOR
NIA
H
ERT G U
AA
S
R
EN. 10 -31- 13
2535 Commerce WayCommerce, CA 90040
R e v i s i o n D a t e
GENERAL NOTES
CONSTRUCTION NOTES
5655 JILLSONSTREET
COMMERCE, CA90040
P2.1
PLUMBINGREMODEL FLOOR
PLAN
CC-CLR
CITY OFCOMMERCE
03/26/13
CITY OFCOMMERCE
CENTRALLIBRARY
RENOVATION
12-189
1/4" = 1'-0"PLUMBING FLOOR PLAN - DOMESTIC COLD WATER & HOT WATER 2
1/4" = 1'-0"PLUMBING FLOOR PLAN - WASTE & VENT 1
FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON P0.1
FOR CONNECTION TO STRUCTURE & PIPE SUPPORT SEE DETAILS 1, 2, 4 & 5 ON SHEETP5.1
ALL VENTING SHALL HAVE A MIN. OF 10' CLEARANCE FROM ANY FORCED AIR INLET W/ AMIN. OF 3' CLEARANCE ABOVE & A MIN OF 4' CLEARANCE FROM ANY PROPERTY LINEEXCEPT A PUBLIC WAY PER CPC SEC. 906
SEE FIXTURE SCHEDULE ON P0.1 FOR ADA & STANDARD RIM HEIGHTS
1.
2.
3.
4.
1-1/2" CW DN IN WALL TO FULL SIZE HEADER
2" CW DN IN WALL TO FULL SIZE HEADER
3/4" CW & HW DN IN WALL TO FIXTURE
3/4" HW DN IN WALL TO FULL SIZE HEADER
3" VTR
1" HW & CW TO WATER HEATER, POP-OFF DRAIN LINE FULL SIZE OF UNITCONNECTION DN TO FLOOR SINK.
CONNECT NEW 2" CW LINE INTO EXISTING 2" CW LINE.
1
2
3
4
5
6
N
N
7
1 2 3 4 5 6 7 8
9
B
C
D
E
A
5
4
4
1
3
11
LITERACY
CLASSROOM
2
COUNCIL
CHAMBERS
LOBBY
1
LITERACY
CENTER
9
TUTORING
4
TUTORING
3
STORAGE
8
TEENS
10
CITADEL
25
REFERENCE
20
YOUTH
LIBRARY
22
STUDY
ROOM
21
MAIN
LIBRARY
26
YOUTH
CLASSROOM
23
WORKSTATION
17
MARKET
PLACE
14
ENTRY
13
LIVING
ROOM
16
COMPUTER
ROOM
L112
ELECTRICAL
ROOM
S151
PLAY
ROOM
24
QUIET
ROOM
12
QUIET
ROOM
11
ENTRY
13
MEN'S
6
WOMEN'S
5
6
6
6
7
8
913
14
15
15
19
18
20
21
22
1
3
2
275 W. Hospitality Lane Suite #100San Bernardino, CA 92408
Phone: 909.890.3700Fax: 909.890.3770
email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTER
EDPROF
RE
ENI
GN
E
ESSIONAL
ETA
TS
FO FILACO
AI
NR
M
No. 33209
E CH AN I CAL
NHOJNEV
ET
S
M.
NO
S
EXP. 9-30-2013
J o b N u m b e r
D a t e
s h e e t n u m b e r
s h e e t t i t l e
p r o j e c t
a p p r o v a l s
c o n s u l t a n t
o w n e r
a r c h i t e c t
R e v i s i o n D a t e
R e v i s i o n D a t e
a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.
LIC
ENSEDA
RCHITECT
NO. C-28593
ST
A
T
EOFC
A
LIFOR
NIA
H
ERT G U
AA
S
R
EN. 10-31- 13
2535 Commerce WayCommerce, CA 90040
R e v i s i o n D a t e
GENERAL NOTES
CONSTRUCTION NOTES
1 ADDENDUM #1 - 06/05/2013
5655 JILLSONSTREET
COMMERCE, CA90040
P2.2
PLUMBING GAS &CONDENSATE
CC-CLR
CITY OFCOMMERCE
06/05/13
CITY OFCOMMERCE
CENTRALLIBRARY
RENOVATION
12-189
3/32" = 1'-0"PLUMBING FLOOR PLAN - GAS & CONDENSATE 1
3/4" COND
1-1/4" COND UP TO ROOF
1-1/4" COND
3/4" COND DN IN WALL TO FITTING IN TAILPIECE OF SINKSEE DETAIL
1-1/4" CONDENSATE DN TO JAN. SINK W/ 1" AIR BREAK ABOVE RIMSEE DETAIL
3/4" COND DN FROM AC UNIT ON ROOF
1-1/4" GAS UP TO A/C 1 ON ROOF (136 CFH)
1" GAS UP TO A/C 3 ON ROOF (75 CFH)
1" GAS UP TO A/C 2 ON ROOF (56 CFH)
NOT USED
NOT USED
NOT USED
1-1/4" GAS (136 CFH)
1-1/2" GAS (211 CFH)
1-1/2" GAS (267 CFH)
NOT USED
NOT USED
2" GAS (543 CFH) UP TO ROOF
2-1/2" GAS (810 CFH)
OWNER TO MAKE APPLICATION & PAY ALL FEES TO LOCAL GAS CO. FOR NEW GASMETER ASSEMBLY. (810 CFH), PROVIDE SEISMIC VALVE SEE DETAIL
2" GAS RISER W/ S.O.V
3/4" CONDENSATE TO TAIL PIECE OF EXISTING LAVATORY
1
2
3
4
5
6
9
P2.1
8
P2.1
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON P0.1.
FOR CONNECTION TO STRUCTURE & PIPE SUPPORT SEE DETAILS 1, 2, 4 & 5 ONSHEET P3.1
ALL VENTING SHALL HAVE A MIN. OF 10' CLEARANCE FROM ANY FORCED AIRINLET W/ A MIN. OF 3' CLEARANCE ABOVE & A MIN OF 4' CLEARANCE FROM ANYPROPERTY LINE EXCEPT A PUBLIC WAY PER CPC SEC. 906.
1.
2.
3.
N
22
1
1
1
1
1 2 3 4 5 6 7 8
9
B
C
D
E
A
AC-6AC-5AC-4
AC-3AC-2
AC-1
1
1
11 10 1
1
3
5
4
4
6 7
8
9
12
13
275 W. Hospitality Lane Suite #100San Bernardino, CA 92408
Phone: 909.890.3700Fax: 909.890.3770
email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTER
EDPROF
RE
ENI
GN
E
ESSIONAL
ETA
TS
FO FILACO
AI
NR
M
No. 33209
E CH AN I CAL
NHOJNEV
ET
S
M.
NO
S
EXP. 9-30-2013
J o b N u m b e r
D a t e
s h e e t n u m b e r
s h e e t t i t l e
p r o j e c t
a p p r o v a l s
c o n s u l t a n t
o w n e r
a r c h i t e c t
R e v i s i o n D a t e
R e v i s i o n D a t e
a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.
LIC
ENSEDA
RCHITECT
NO. C-28593
ST
A
T
EOFC
A
LIFOR
NIA
H
ERT G U
AA
S
R
EN. 10-31- 13
2535 Commerce WayCommerce, CA 90040
R e v i s i o n D a t e
GENERAL NOTES
CONSTRUCTION NOTES
1 ADDENDUM #1 - 06/05/2013
5655 JILLSONSTREET
COMMERCE, CA90040
P2.3
PLUMBING ROOFPLAN
CC-CLR
CITY OFCOMMERCE
06/05/13
CITY OFCOMMERCE
CENTRALLIBRARY
RENOVATION
12-189
3/32" = 1'-0"PLUMBING REMODEL ROOF PLAN 1
3/4" COND DN TO BELOW
1-1/4" GAS DN TO BELOW (181 CFH)
1" GAS DN TO BELOW (56 CFH)
1-1/4" GAS DN TO BELOW (136 CFH)
1" GAS DN TO BELOW (75 CFH)
1-1/4" GAS (181 CFH)
2" GAS (362 CFH)
2" GAS (543 CFH)
2" GAS DN TO BELOW (543 CFH)
3/4" COND
1" COND
1-1/4" COND
1-1/4" COND DN TO BELOW
1
2
3
FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON P0.1.
ALL VENTING SHALL HAVE A MIN. OF 10' CLEARANCE FROM ANY FORCED AIR INLET W/ AMIN. OF 3' CLEARANCE ABOVE & A MIN OF 4' CLEARANCE FROM ANY PROPERTY LINEEXCEPT A PUBLIC WAY PER CPC SEC. 906.
PROVIDE APPROVED SUPPORT BLOCKS FOR GAS & CONDENSATE LINES ON ROOF.
1.
2.
N
4
5
3.
6
7
8
9
10
11
12
13
1
1
1
1 1/2" LONG "TEK"SCREW
DIAGONAL BRACE
STRUCTURE
1" MIN.
1" MIN.1 1/2" LONG"TEK" SCREW
1/2"ø HANGER ROD(TYP.) 2 1/2"x2 1/2"x16 GA ANGLE
BRACE (TYP.)
STRUCTURE
THREADED HANGARROD. FOR SIZE ANDSPACING SEE
5
-
ADD VERTICAL ANGLESTIFFNER IF LENGTH ISGREATER THAN MAX.LENGTH SHOWN ON PIPESUPPORT SCHEDLE
NUT & WASHERTOP & BOTTOM
"B-LINE" - B3690ADJUSTABLE "J" HANGAR
PIPING. SEE PLANS FOR SIZEAND LOCATION
"B-LINE" B3162 PIPE SADDLE
TRANSVERSE ANGLE BRACE.ALTERNATIVE SIDES EVERY BRACE
FOR CONNECTION TOSTRUCTURE SEE
1
-
INSULATION WHEREAPPILES - SEEAPECIFICATIONS
ADD VERTICAL ANGLESTIFFNER IF LENGTH ISGREATER THAN MAX. LENGTHSHOWN ON PIPE SUPPORTSCHEDULE
HANGAR ROD - SEESCHEDULE FOR SIZE
TRANSVERSE ANGLEBRACE. ALTERNATIVE SIDESEVERY BRACE.
PIPE SLEEVE WITH I.D. 1/4"LARGER THAN O.D. OF BOLT
"B-LINE" B3100 CLEVISHANGAR - SEE SCHEDULEFOR SPACING
"B-LINE" B3162PIPE SADDLE
NOTE:
1. DETAIL APPLIES TO PIPES 2-1/2" I.D. AND LARGER.
TYPICAL PIPE - SEE PLANFOR SIZE AND LOCATION
INSULATION - SEESPECIFICATIONS
"B-LINE" B327SHORT ANGLE
ATTACH BOLT -SEE SCHEDULEFOR SIZE
LONGITUDINAL DIAGONALANGLE (SLOPE 1 TO 1).FOR SIZE AND SPACING 0SEE SCHEDULE. ALT.SIDES EACH BRACE.
FOR CONNECTIONTO STRUCTURESEE
5
-
5
-
5
-
1
-
(TYP.)
F
E
D
C
B
A
2"
1 1/2"
1 1/4"
1"
155-330
114-154
61-113
33-60
3/4"
1/2"
12-32
1-11
BALLVALVE
STAINLESS STEELACCESS PANEL
WATTER HAMMERARRESTOR
REFER TO PLANSFOR SIZE & LOCATION
PIPE SIZING ANDSELECTION TABLE
PPPSIZE
FIXTUREUNITS
CROSSREF. PDI
SCHEDULE 40 PVC & ABS DWV
STEEL PIPE FOR GAS
REFER TO SMACNA GUIDELINES IN SCHEDULE BELOW
SUPPORT EVERY JOINT. SUPPORT SHALL BE WITHIN 18 INCHES OF JOINT ON BOTH SIDES. (SUPPORT ALSO REQUIRED AT EACHHORIZONTAL JOINT CONNECTION.)
CAST IRON HUBLESS (NO HUB)
ALL PIPING 2-1/2" AND LARGER PER THE FOLLOWING SMACNA GUIDELINES
BRACING MAY BE OMITTED WHERE TOP OF PIPE IS 12" OR LESS FROM BOTTOM OF HANGER SUPPORT CONNECTED TO STRUCTURE
VERTICAL ANGLE ONLY REQUIRED WHEN ROD MAXIMUM LENGTH IS EXCEEDED.
COPPER TUBE & PIPE
37"1- & 2 15'-0" 3/8"
5/8"
ALLOW FOR EXPANSION EVERY 30'-0".3
NOTES:
2
1
6 10'-0" 10'-0" 37"
10'-0"10'-0"2-1/2
4
5
3
10'-0"10'-0"
10'-0" 10'-0"
10'-0" 10'-0"
A
3 thru 6 A
25"1/2"
5/8"
5/8"
1/2"
31"
31"
25"
1 thru 2 10'-0"4'-0"
A
4'-0" 10'-0"
1
1- thru 2
8'-0"8'-0"
10'-0" 10'-0"
6'-0" 6'-0"
3/8"
3/8"
37"
37"
3/8"
3/8"
3/8"
37"
37"
37"
BETWEEN SUPPORT
1 THRU 1/2
2
1_2
&3_4
10'-0"6'-0"
10'-0" 10'-0"
6'-0" 10'-0"
PIPE SIZEIN INCHES
MAXIMUM SPAN
HANGERS O.C.
HORIZ. VERT.
3/8"
3/8"
3/8"
37"
37"
37"
HANGER RODDIAMETER SIZE
MAX. LENGTHFOR RODS
3/8"1-1/2 x 1-1/2 x 18
ga @ 40'-0" O.C.1-1/2 x 1-1/2 x 18
ga @ 80'-0" O.C.1 x 1 x 18ga
1/2"
1/2"
1/2"
3/8"
3/8"
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
2 x 2 x 16ga
2 x 2 x 16ga
2 x 2 x 16ga
2 x 2 x 16ga
2 x 2 x 16ga2-1/2 x 2-1/2 x 16
ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
BOLTSIZE
1 x 1 x 18ga
1 x 1 x 18ga
1 x 1 x 18ga
1 x 1 x 18ga
1 x 1 x 18ga
3
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
1 x 1 x 18ga
1 x 1 x 18ga
(STIFFNER)
VERTICALHANGER ANGLE
1 x 1 x 18ga
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
LONGITUDINALANGLE BRACE
2
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
TRANSVERSEANGLE BRACE
1 2
1_2
&3_4
1_2
&3_4
1/2" CW
4
2
3
DU-2
1
NO. OFDRAINS
N/A
STRAIGHT
STRAIGHT
STRAIGHT
5 OZ.
2 OZ.
5 OZ.
4 OPENING
3 OPENING
2 OPENING
STRAIGHT
PIPE STYLEUSE STAND
FLOOR DRAIN TRAP PRIMER
DEL. ON 15SEC. PRESS.
MAX. WATER
2 OZ.
DROP.
DISTRIBUTION CHART
NOT REQUIRED
UNIT ISDISTRIBUTION
FLOOR DRAIN TRAPTO FLOOR SINK OR
WHERE REQUIREDDISTRIBUTION UNIT
FOR SIZE AND LOCATION
1/2" CW (TYP)
REFER TO PLANS
BALL VALVE
PRECISION PLUMBING PRODUCTSPRIME-RITE TRAP PRIMER VALVEMODEL #PR-500
UNIT MODELDISTRIBUTION
DU-3
DU-4
3"
FLOOR
OR
ACCESS
PANEL
PRIMER
TRAP
BALL VALVE
1/2" CW
SUPPLY
NOTE:
ACCESS PANEL SHALL NOT BE INSTALLED
BEHIND GRAB BARS.
FS
1
FD
1
TP
1
JANITOR SINKOR FLOOR SINK
MIN. 1" AIR BREAK
ESCUTCHEON
COND. FROM AC UNIT
COND. LINE, SEE FLOORPLANS FOR SIZE & LOCATION
PLUMBING CONTRACTOR TOCOORDINATE WITH MECHANICALCONTRACTOR TO VERIFY-EQ. TO STATIC PRESSURE OFUNIT IN " W.G.
VENT FULL SIZE OF COND. LINE. LOCATEON DOWNSTREAM SIDE OF COND. LINE
CONDENSATE DRAIN FROM AC UNIT.SEE PLANS FOR SIZE & LOCATION
INSTALL PER CPC (SEC. 814.0 - 814.3)
MECHANICALEQUIPMENT
MIN. 1% SLOPE
PLUMBING CONTRACTOR TOCOORDINATE WITH MECHANICALCONTRACTOR TO VERIFY-EQ. TO STATIC PRESSURE OFUNIT IN " W.G.
VENT FULL SIZE OF COND. LINE. LOCATEON DOWNSTREAM SIDE OF COND. LINE
CONDENSATE DRAIN FROM AC UNIT.SEE PLANS FOR SIZE & LOCATION
INSTALL PER CPC (SEC. 814.0 - 814.3)
MECHANICALEQUIPMENT
MIN. 1% SLOPE
COND. SLOPE TO DRAIN
ESCUTCHEON
OR
COND. CONN. TO TAIL PCS. WITH SLIPJOINT FITTING BELOW SINK.SEE FLOOR PLANS FOR LOCATIONS
S
1
L
1
VENT
FINISH FLOOR
WASTE
WCO
WALL
2% SLOPE1% SLOPE
FINISHFLOOR ORSIDEWALK
FCO OR COTG
WASTE
COVER PLATE
COVER PLATE
PIPE CLAMP (TYP)
INSTALL PER CPC (SEC. 707.0 & 719.0)
INSIDEOUTSIDE
TURNED FLASHING DNINTO VENT PIPE
1" MIN.
ROOFING OVER BASE
6 LB. SOFT LEADFLASHING
VENT PIPE THRU. ROOFSEE PLUMBING ROOFPLANS FOR SIZE & LOC.
8" MIN.
SEE ARCHITECHURALDWGS. FOR ROOFCONSTRUCTION
AIR GAP
3/4" CW
SINK
3/4" HW
2" WASTE
WCO
1-1/2" VENT
1-1/2" TRAP
PROVIDE (2) 1/2"CAPPED TEES &(1) 1/2" S.O.V.FOR FUTUREREVERSE OSMOSISSYSTEM
GARBAGE DISPOSER
FAUCET
WH
1
BALL VALVE (TYP)
UNION
3/4" CW3/4" HW
CHECK VALVE
POP-OFF DRAIN LINE FULLSIZE OF UNIT CONNECTION,PER SEC. 608.5
VACUUM RELIEF VALVEINSTALL PER LOCAL CODES
1.5 GAL. THERMALEXPANSION TANK
ASME RATED PRESS.RELIEF VALVE
FLOOR
SECURE W/H TO WALLWITH 1" WIDE - MIN. 20GA. SHT. MTL. STRAP &(2) 1/4" LAG BOLTS∅
EACH END. PER CPCSEC. 508.0 - 508.2
MIN. 1" AIR BREAK
JANITOR SINKOR FLOOR SINK
ESCUTCHEON
POP-OFF DRAIN LINE
275 W. Hospitality Lane Suite #100San Bernardino, CA 92408
Phone: 909.890.3700Fax: 909.890.3770
email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTER
EDPR
OF
RE
ENI
GN
E
ESSIONAL
ETA
TS
FO FILACO
AI
NR
M
No. 33209
E CH A N I CAL
NHOJNEV
ET
S
M.
NO
S
EXP. 9-30-2013
J o b N u m b e r
D a t e
s h e e t n u m b e r
s h e e t t i t l e
p r o j e c t
a p p r o v a l s
c o n s u l t a n t
o w n e r
a r c h i t e c t
R e v i s i o n D a t e
R e v i s i o n D a t e
a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.a
d
r
i
a
n
g
a
u
s
a
r
c
h
i
t
e
c
t
s
,
i
n
c
.
LIC
ENSEDA
RCHITECT
NO. C-28593
ST
A
T
EOFC
A
LIFOR
NIA
H
ERT G U
AA
S
R
EN. 10 -31- 13
2535 Commerce WayCommerce, CA 90040
R e v i s i o n D a t e
5655 JILLSONSTREET
COMMERCE, CA90040
P3.1
PLUMBINGDETAILS
CC-CLR
CITY OFCOMMERCE
03/26/13
CITY OFCOMMERCE
CENTRALLIBRARY
RENOVATION
12-189
CTS - RAFTER 1
PIPE SUPPORT 2
PIPE SUPPORT 4PIPE SIZING & SELECTION TABLE 7
PIPING SUPPORT SCHEDULE 5
TRAP PRIMER 8
CONDENSATE CONNECTION - 02 10
CONDENSATE CONNECTION - 03 11
CLEAN OUT - 02 9
VENT THRU ROOF - SLOPE 3
SINK CONNECTION 12 WATER HEATER CONNECTION 6