    FLAME SCANNERSFLAME SCANNERS

  • 7/31/2019 Flame Scanners1

    2/24

    INTRODUCTION

    PRINCIPLE PURPOSE OF FLAME SAFEGUARDSUPERVISIORY SYSTEM IS TO ENSURE THAT ITIS SAFE TO LIGHT THE BOILER AND CONTINUEBOILER OPERATION.

    IT IS ALSO USED FOR BOILER SHUTDOWN. ACCURATE DETECTION OF A FIRE IS ONE OF

    THE MOST IMPORTANT TASKS OF FSSS.

    FOR THIS PURPOSE THERMOCOUPLES , FLAME

    RODS OR FLAME SCANNERS ARE INSTALLED. UV, IR AND MULTIPLE FREQUENCY SENSING

    ARE THE DIFFERENT TYPES OF FLAMESCANNERS.

  • 7/31/2019 Flame Scanners1

    3/24

  • 7/31/2019 Flame Scanners1

    4/24

  • 7/31/2019 Flame Scanners1

    5/24

    MECHANICAL COMPONENTSMECHANICAL COMPONENTS

    Comprises of a stationary part called theflame scanner guide assembly and a removablepart called the flame scanner assembly.

    FLAME SCANER GUIDE ASSEMBLY:- SCANNER HEAD HOUSING

    FLEXIBLE METAL HOSE :- Adapts scanner to tilting ofwind box nozzles.

    RIGID GUIDE PIPE SECTION:- Fixed to the wind boxand serves as a protective cover/packing gland.

    COOLING AIR MANIFOLD:- is screwed onto theguide pipe

    COVER PLATE: closes the wind box opening when

    scanner is removed for maintenance.

  • 7/31/2019 Flame Scanners1

    6/24

    MECHANICAL COMPONENTSMECHANICAL COMPONENTS

    FLAME SCANNER ASSEMBLY:-

    SCANNER HEAD ASSEMBLY:- Comprises of ascanner head body with the collimator tube, shield,

    collimating lens, barrel, mounting plate,compression spring, one end of fiber optic cableand a plug.

    FLEXIBLE METAL HOSE:- Houses the fiber opticcable

    RIGID PIPE:- Houses the fiber optic cable SCANNER HOUSING ASSEMBLY:- houses the

    scanner head electronics card which convertsvisible light signal to equivalent electrical signal.

  • 7/31/2019 Flame Scanners1

    7/24

    FLAME SCANNER ASSEMBLY:-

    FLEXIBLE

    METAL

    HOSERIGID PIPE

    SCANNER

    HOUSING

    SCANNER HEAD

    ASSEMBLY

  • 7/31/2019 Flame Scanners1

    8/24

    FLAME SCANNER ASSEMBLY:-

    COMPRESSION SPRING FIBER OPTIC CABLE

    PLUG

    SCANNER HEAD BODYLENSSPACER

  • 7/31/2019 Flame Scanners1

    9/24

    ELECTRICAL COMPONENETSELECTRICAL COMPONENETS

    LOCAL:- SCANNER HOUSING ELECTRONICS

    REMOTE :- POWER SUPPLY MODULE:-

    INTENSITY & FAULT DETECTION CARD:-

    FREQUENCY DETECTION CARD:-

    LAMP & METER CARD:-

    LAMP DRIVER CARD:-

    2/4 FLAME INDICATION & FAULT ALARM:-

  • 7/31/2019 Flame Scanners1

    10/24

    ELECTRICAL COMPONENTSELECTRICAL COMPONENTS

    SCANNER HOUSING ELECTRONICSSCANNER HOUSING ELECTRONICS :- Flame signal (light) transmitted via the fiber

    optic cable strikes a photodiode.

    Light signal is converted into an small current

    signal by the photodiode. Current signal is converted to a voltage signal.

    (1.5v for intense brightness and 6.4 v for nolight)

    Voltage signal is amplified by an amplifier ofgain 1/3.

    Voltage signal is the converted into a currentsignal and sent to remote electronics.

  • 7/31/2019 Flame Scanners1

    11/24

    SCANNER HOUSING ELECTRONICSSCANNER HOUSING ELECTRONICS

    PHOTOCOUPLER

    ASSEMBLY

    TRIMMING POTS

  • 7/31/2019 Flame Scanners1

    12/24

    ELECTRICAL COMPONENTSELECTRICAL COMPONENTS

    POWER SUPPLY CARD :-

    I/P voltage and frequency:- 110V 50 Hz

    O/P voltage:- +15v, -15VDC

  • 7/31/2019 Flame Scanners1

    13/24

    POWER SUPPLY CARDPOWER SUPPLY CARD:-

    P/S SWITCH

  • 7/31/2019 Flame Scanners1

    14/24

    ELECTRICAL COMPONENTSELECTRICAL COMPONENTS

    INTENSITY AND FAULT DETECTION CARDINTENSITY AND FAULT DETECTION CARD :-

    - Current Signal Converted To Equivalent millivoltsignal.

    - Intensity slope is inverted and multiplied by factor

    3.

    - This active flame signal consists of intensity andfrequency components. The active flame signal istransmitted to the frequency detection cards aswell as the intensity circuitry.

    - The ac component is eliminated to obtain anintensity only flame signal.

  • 7/31/2019 Flame Scanners1

    15/24

  • 7/31/2019 Flame Scanners1

    16/24

    INTENSITY AND FAULT DETECTION CARDINTENSITY AND FAULT DETECTION CARD

    INTENSITY

    INDICATOR

    DROP OUT

    SWITCH

    DROP OUT

    POT

    PULL IN POT

    PULL OUT

    SWITCH

  • 7/31/2019 Flame Scanners1

    17/24

    ELECTRICAL COMPONENTSELECTRICAL COMPONENTS

    FREQUENCY DETECTION CARDFREQUENCY DETECTION CARD :-

    - Two types of frequency detection cards used. Oneis tuned to frequency 3hz to determine existencefireball flame frequency in the active flame signal

    and the other is tuned to 29hz and is used fordetermining oil gun flame frequency.

    - Active flame signal from intensity and faultdetection card is ac coupled to block intensityinformation.

    - Ac signal is compared with set frequency. A matchgenerates a logic one.

    - Delay of 2 secs is provided during frequencypermissive drop out.

  • 7/31/2019 Flame Scanners1

    18/24

    FREQUENCY DETECTION CARDFREQUENCY DETECTION CARD

    FILTER

    SWITCH FREQUENCY LED

    YELLOW TRIM

  • 7/31/2019 Flame Scanners1

    19/24

    ELECTRICAL COMPONENTSELECTRICAL COMPONENTS

    LAMP AND METER CARDLAMP AND METER CARD :-

    - Oil guns flame/no flame and visual intensityFAULT warnings are generated.

    - Flame intensity signal is indicated on Flameintensity mA Meter.

    - Power supply of +/-15Vdc is provided to thescanner housing electronics.

  • 7/31/2019 Flame Scanners1

    20/24

    LAMP AND METER CARDLAMP AND METER CARD

    FAULT LED

    INTENSITY METER

    FLAME LED

  • 7/31/2019 Flame Scanners1

    21/24

    ELECTRICAL COMPONENTSELECTRICAL COMPONENTS

    2/4 FAULT INDICATION AND FAULT2/4 FAULT INDICATION AND FAULTALARMALARM:-

    - Provides contact closure of relay when at least

    2 out of 4 scanners are detecting fireballflame.

    - Provides contact closure of relay when fault isdetected on any scanner cable or scannerhead electronics.

    - These contact are further used in DCS:

    - Fault signal is used to alert operator ofexisting fault is system.

    - 2/4 flame scanner in service is used in Boiler

    tripping logic.

  • 7/31/2019 Flame Scanners1

    22/24

    2/4 FAULT INDICATION AND FAULT ALARM2/4 FAULT INDICATION AND FAULT ALARM:-

    RELAYS

    2/4 FLAME

    FAULT

  • 7/31/2019 Flame Scanners1

    23/24

  • 7/31/2019 Flame Scanners1

    24/24