Flint Water Press Conference December 2, 2016 1
Transcript
Page 1: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Flint WaterPress Conference

December 2, 2016

1

Page 2: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

2015: Flint River without Corrosion Control 2016: Detroit Water with Enhanced Corrosion Control

Flint Hospital 2015 vs. 2016

What a difference a year makes…..

Photographs: Zhu “Joyce” Ni, Min Tang, Pan Ji, Mariah Gnegy

Page 3: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

1) Fourth round of lead in water testing (led by Ms. LeeAnne Walters, Flint residents and funded by EPA)

2) A special study of Legionella and Shigella testing (led by William Rhoads and funded by the State of Michigan)

3) Fourth round of disinfection by-product testing (led by Dr. Susan D. Richardson, a team at the University of South Carolina and funded by the EPA)

Page 4: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Flint resident sampling:August 2015 - November 2016

Min Tang, Kelsey Pieper

and Marc Edwards

4

Page 5: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Sampling in November 2016Sampling organized by LeeAnne Walters and the Flint citizen science team

5

Page 6: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Sampling protocol

Collected water samples from a cold water tap that is used for drinking water

1 L

First draw

500 mL

1 min flush

125 mL

3 min flush

Flush for

2 minutes

6+ hour

stagnation

Flush for

45 seconds

6

Page 7: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Sampling protocol

1 L

First draw

500 mL

1 min flush

125 mL

3 min flush

Flush for

2 minutes

6+ hour

stagnation

Flush for

45 seconds

7

154 homes participated

in all 4 sampling efforts

Page 8: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Lead pipe

Water flow without corrosion inhibitors

April 2014: Flint discontinued corrosion control

8

Page 9: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Lead pipe

Water flow without corrosion inhibitors

Mobilization of corrosion rust layers

9

April 2014: Flint discontinued corrosion control

Page 10: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

First draw lead in August 2015

10

17%

0%

4%

8%

12%

16%

20%

Aug.15 Mar.16 Jul.16 Nov.16

Per

cen

t of

hom

e a

bo

ve

15

pp

b

1.7x EPA

standard

n=154

EPA standard

Page 11: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Lead pipe

Oct-Dec 2015: Connected to DWSD and added extra corrosion treatment

Water flow with corrosion inhibitors

Form new

corrosion scales

11

Page 12: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

First draw lead in March 2016

12

17%

15%

0%

4%

8%

12%

16%

20%

Aug.15 Mar.16 Jul.16 Nov.16

Per

cen

t of

hom

e a

bo

ve

15

pp

b

n=154

EPA standard

Page 13: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Lead pipe

May 2016: Promoted high-flow flushing to remove loose sediment

Water flow with corrosion inhibitors

Loose leaded

sediment

13

Page 14: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

First draw lead in July 2016

14

17%

15%

9.7%

0%

4%

8%

12%

16%

20%

Aug.15 Mar.16 Jul.16 Nov.16

Per

cen

t of

hom

e a

bo

ve

15

pp

b

n=154

EPA standard

Page 15: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

First draw lead in November 2016

15

17%

15%

9.7%

6%

0%

4%

8%

12%

16%

20%

Aug.15 Mar.16 Jul.16 Nov.16

Per

cen

t of

hom

e a

bo

ve

15

pp

b

EPA standard

n=154

Page 16: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

8%

36%

44%

57%

0%

10%

20%

30%

40%

50%

60%

70%

Aug.15 Mar.16 Jul.16 Nov.16

Non-detectable first draw leadP

erce

nt

of

ho

me

wit

h

no

n-d

etec

t le

ad

(<

1 p

pb

)

n=154

Page 17: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

First draw iron concentrations

17

Per

cen

t of

hom

e ab

ove

0.3

pp

m i

ron

14% 14%

9%

5%

0%

2%

4%

6%

8%

10%

12%

14%

16%

Aug.15 Mar.16 Jul.16 Nov.16n=154

Page 18: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

2015: Flint River without Corrosion Control 2016: Detroit Water with Enhanced Corrosion Control

Flint Hospital 2015 vs. 2016

What a difference a year makes…..

Photographs: Zhu “Joyce” Ni, Min Tang, Pan Ji, Mariah Gnegy

Page 19: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Conclusions

1. It is likely that Flint is meeting the lead action level• However, this is not an approved LCR sampling pool

2. Lead and iron levels have continued to decrease since July 2016

3. Residents should use lead filters or bottled water until further notice from the State or EPA

19

Page 20: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Water Heater Study: Update

William Rhoads, Taylor Bradley, Amy Pruden and Marc Edwards

20

Page 21: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Legionella bacteria is the cause of Legionnaires’ disease and Pontiac fever

Flint Water

SwitchDetroit Water

Switch

Page 22: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Legionella bacteria is the cause of Legionnaires’ disease and Pontiac fever

Flint Water

SwitchDetroit Water

Switch

Page 23: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Legionella bacteria is the cause of Legionnaires’ disease and Pontiac fever

Page 24: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

L. pneumophila serogroup 1 – identified in 85% of clinical isolates

Legionella bacteria is the cause of Legionnaires’ disease and Pontiac fever

Page 25: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

L. pneumophila serogroup 1 – identified in 85% of clinical isolates

• Monoclonal Antibodies (MAb)

Legionella bacteria is the cause of Legionnaires’ disease and Pontiac fever

Page 26: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

L. pneumophila serogroup 1 – identified in 85% of clinical isolates

• Monoclonal Antibodies (MAb)L. pneumophila serogroup 1 MAb2 –observed in 94% of outbreak cases

Legionella bacteria is the cause of Legionnaires’ disease and Pontiac fever

Page 27: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Water Quality Testing in HomesJune 2016 – 30 Homes

Sacrificial Anode

Rod

Sediment Accumulation

Fe tank corrosion

Iron, Lead, Aluminum

[Cl2]

Page 28: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Water Quality Testing in HomesJune 2016 – 30 Homes

• Tested water

• Metals (Pb, Fe, Al, Cu)

• Chemistry (Cl2, pH, temperature)

• Legionella

Sacrificial Anode

Rod

Sediment Accumulation

Fe tank corrosion

Iron, Lead, Aluminum

[Cl2]

Page 29: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Water Quality Testing in HomesJune 2016 – 30 Homes

• Tested water

• Metals (Pb, Fe, Al, Cu)

• Chemistry (Cl2, pH, temperature)

• Legionella

• Extensive tank cleaning

• Flush, drain, scour out sediment

Sacrificial Anode

Rod

Sediment Accumulation

Fe tank corrosion

Iron, Lead, Aluminum

[Cl2]

Page 30: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Water Quality Testing in HomesJune 2016 – 30 Homes

• Tested water

• Metals (Pb, Fe, Al, Cu)

• Chemistry (Cl2, pH, temperature)

• Legionella

• Extensive tank cleaning

• Flush, drain, scour out sediment

• Re-tested water

Sacrificial Anode

Rod

Sediment Accumulation

Fe tank corrosion

Iron, Lead, Aluminum

[Cl2]

Page 31: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Key Conclusions Regarding Legionella

• Legionella colonization rates were very low relative to levels of concern

• 2 of 30 homes had culturable L. pneumophila serogroup 1, that was MAb 2 positive

• Chlorine levels reaching homes were relatively high

Page 32: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Follow-Up Sampling in One of the Homes

Culture L. pneumophila serogroup 1, MAb2 positive?Kitchen Tap: June Nov.Cold Water Yes NoHot Water Yes No

BQL = “Below quantification limit” (i.e., present, but in very low concentration)BD = “Below detection” (i.e., none detected)

Page 33: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Follow-Up Sampling in One of the Homes

Culture L. pneumophila serogroup 1, MAb2 positive?Kitchen Tap: June Nov.Cold Water Yes NoHot Water Yes No

BQL = “Below quantification limit” (i.e., present, but in very low concentration)BD = “Below detection” (i.e., none detected)

Page 34: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Follow-Up Sampling in One of the Homes

Culture L. pneumophila serogroup 1, MAb2 positive?Kitchen Tap: June Nov.Cold Water Yes NoHot Water Yes No

L. pneumophila concentration (gene copies/mL)Kitchen Tap: June Nov.Cold Water BQL BDHot Water 323 BD

BQL = “Below quantification limit” (i.e., present, but in very low concentration)BD = “Below detection” (i.e., none detected)

Page 35: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Follow-Up Sampling in One of the Homes

Culture L. pneumophila serogroup 1, MAb2 positive?Kitchen Tap: June Nov.Cold Water Yes NoHot Water Yes No

L. pneumophila concentration (gene copies/mL)Kitchen Tap: June Nov.Cold Water BQL BDHot Water 323 BD

BQL = “Below quantification limit” (i.e., present, but in very low concentration)BD = “Below detection” (i.e., none detected)

Page 36: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Follow-Up Sampling in One of the Homes

Culture L. pneumophila serogroup 1, MAb2 positive?Hose Bib: June Nov.

“Distribution System Water” Yes No

L. pneumophila concentration (gene copies/mL)Hose Bib: June Nov.

“Distribution System Water” 1121 BD

BQL = “Below quantification limit” (i.e., present, but in very low concentration)BD = “Below detection” (i.e., none detected)

Page 37: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Follow-Up Sampling in One of the Homes

Culture L. pneumophila serogroup 1, MAb2 positive?Hose Bib: June Nov.

“Distribution System Water” Yes No

L. pneumophila concentration (gene copies/mL)Hose Bib: June Nov.

“Distribution System Water” 1121 BD

BQL = “Below quantification limit” (i.e., present, but in very low concentration)BD = “Below detection” (i.e., none detected)

Page 38: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Possible Explanations for Improved Water Quality with Respect to Legionella

• Amount of time back on Detroit water

• Generally improved water quality stability

• Chlorine residuals throughout system

• Reduced iron

Page 39: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Possible Explanations for Improved Water Quality with Respect to Legionella

• Amount of time back on Detroit water

• Generally improved water quality stability

• Chlorine residuals throughout system

• Reduced iron

• Seasonality

• Cooler weather = cooler water in mains

Page 40: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Possible Explanations for Improved Water Quality with Respect to Legionella

• Amount of time back on Detroit water

• Generally improved water quality stability

• Chlorine residuals throughout system

• Reduced iron

• Seasonality

• Cooler weather = cooler water in mains

• Increased water heater temperature

• Hot water temperature = 53.7 °C in August 2016

Page 41: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Possible Explanations for Improved Water Quality with Respect to Legionella

• Amount of time back on Detroit water

• Generally improved water quality stability

• Chlorine residuals throughout system

• Reduced iron

• Seasonality

• Cooler weather = cooler water in mains

• Increased water heater temperature

• Hot water temperature = 53.7 °C in August 2016

Reflects high quality distribution system

operations overseen by EPA and MDEQ

Page 42: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

The Saginaw & Genesee County Shigella Outbreak

Owen Strom, William Rhoads, Emily Garner, Amy Pruden, and Marc Edwards

Page 43: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

2016 Outbreak of Shigella

• Saginaw & Genesee counties

• Starting March 1, 2016

• 180 cases as of November 14th

• Public concern that drinking water could be the source of the outbreak.

• MDHHS and CDC investigating

htt

p:/

/ww

w.m

ich

igan

.go

v/im

ages

/md

hh

s/Sh

igel

laO

utb

reak

Gra

ph

_54

191

7_7

.jpg

3/5

/20

16

4/2

/20

16

5/7

/20

16

6/4

/20

16

6/1

8/2

01

6

7/2

/20

16

8/6

/20

16

9/3

/20

16

10

/1/2

01

6

10

/29

/20

16

Page 44: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Shigella

• Infected through ingestion of contaminated fecal matter

• Touching a contaminated surface then touching mouth or food

• Consuming contaminated food and drinking water

http://www.cdc.gov/shigella/index.html

• Bacteria

• Symptoms • Severe Diarrhea• Abdominal pain• Fever

Page 45: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Detection in Water

• Samples from June 2016

• 30 houses across town

• 5 types of samples

• 1 Liter

• Hot, cold, stagnant, flushed, main

• Kitchen faucet, shower head, and hose bib

• Total of 150 samples tested

Page 46: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

6/1

8/2

01

6

7/2

/20

16

Page 47: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Results

• Tested Presence/Absence of DNA from common pathogenic Shigella

• Endpoint polymerase chain reaction (PCR) • Identifies DNA from once living or dead Shigella

• Sensitive to the four pathogenic Shigella species

• All 150 samples negative

*Matrix spike to confirm inhibition was not present.

Environmental Samples

Lad

der

Neg

ativ

e C

on

tro

l

Posi

tive

Co

ntr

ol

Page 48: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

CDC and MDHHS Investigation• Initial Conclusion 1

• “Shigella does NOT appear to be spreading through a drinking water system”

• 90% of sick individuals drank only bottled water • 65% use only bottled water to brush teeth• No common drinking water source among infected

• multiple water system with 15% on private wells

• Initial Conclusion 2• “Shigella bacteria appear to be spreading in the community

from person to person”• 51% of sick were 9 years old or younger• 59% of sick “wore diapers, changed diapers, or came in contact with a

person wearing diapers in the week before they became ill.”

“Update on the Shigella outbreak Investigation in Saginaw & Genesee Counties November 17, 2016”

Page 49: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Is There a Disinfection By-Product Problem in Flint?

Joshua M. Allen

Amy A. Cuthbertson, Susana Y. Kimura, Hannah K.

Liberatore,

Meghan E. Franco, Susan D. Richardson

1

Page 50: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

• Key Question: Are there

chemicals/DBPs present at levels

that could be causing skin

rashes?

2

Page 51: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Strategy

• Compare Flint hot and cold water to water of other cities Anything unusual?

• Other cities:

Detroit (uses chlorine and same source water [Lake Huron] as Flint)

Grovetown, GA (surface water system using chlorine)

Lyons, GA (groundwater system using chlorine)

3

Page 52: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Quantitative MethodsIodo-Trihalomethanes

Haloacetonitriles

Haloketones

Tri-Haloaldehydes

Mono, di-Halonitromethanes

Liquid-liquid extraction

(LLE) with 2 mL MTBE

Selected Ion Monitoring (SIM) GC-MS

VOCs

(including THM4)

GC-MS

Purge and Trap

Mono, di-Haloaldehydes

PFBHA

derivatizatio

n

LLE with 10 mL hexane

times 3 and concentrated

under N2

GC/HRT-MS

Iodoacetic acids (IAAs)

Haloacetamides (HAms)

Tribromoacetonitrile (TBAN)

Trihalonitromethanes (THNMs)

GC-MS/MS

IAA

sHAms

TBAN

THNMsDiazomethane

derivatization

SIM GC-MS

LLE with 5 mL MTBE

times 3 and

concentrated under N2

14

Page 53: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Ethyl acetate layer dried with Na2SO4 and concentrated to 1

mL

XAD Resin Extraction

30 mL XAD-2

30 mL DAX-8

Eluted with 200 mL ethyl acetate

• Agilent 5977 GC-MS• LECO GC-HRT-MS (25,000

resolution)

10 Liter Hot and Cold Water Samples acidified to ~ pH 1

GC-MS

Comprehensive Analysis15

Page 54: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Trichloroacetaldehyde

was the only

haloaldehyde

detected > 1.0 µg/L in

Flint waters. This is

normal.

Results Summary

Most

haloacetonitriles

were detected at

low to trace levels.

Detroit 2 Flint 2

cold hot hot cold hot hot cold hot cold hot

Haloacetonitriles

Chloroacetonitrile 0.1 <0.1 <0.1 <0.1 NM <0.1 <0.1 <0.1 <0.1 ND ND

Dichloroacetonitrile 0.1 1.5 2.1 1.9 X 0.4 <0.1 3.3 3.6 <0.1 X

Bromochloroacetonitrile 0.1 0.3 0.2 0.2 X <0.1 X 0.4 0.3 <0.1 <0.1

Dibromoacetonitrile 0.1 <0.1 <0.1 <0.1 X <0.1 <0.1 <0.1 <0.1 <0.1 <0.1

Trichloroacetonitrile 0.1 <0.1 ND <0.1 NM ND ND <0.1 <0.1 ND ND

LOQ

(µg/L)

Detroit 1 Flint 1 LyonsGrovetown

DBP

Detroit 2 Flint 2

cold hot hot cold hot hot cold hot cold hot

Haloacetonitriles

Chloroacetonitrile 0.1 <0.1 <0.1 <0.1 NM <0.1 <0.1 <0.1 <0.1 ND ND

Dichloroacetonitrile 0.1 1.5 2.1 1.9 X 0.4 <0.1 3.3 3.6 <0.1 X

Bromochloroacetonitrile 0.1 0.3 0.2 0.2 X <0.1 X 0.4 0.3 <0.1 <0.1

Dibromoacetonitrile 0.1 <0.1 <0.1 <0.1 X <0.1 <0.1 <0.1 <0.1 <0.1 <0.1

Trichloroacetonitrile 0.1 <0.1 ND <0.1 NM ND ND <0.1 <0.1 ND ND

LOQ

(µg/L)

Detroit 1 Flint 1 LyonsGrovetown

DBP

Key: X = detected in XAD extract; NM = not measured; ND = not detected; LOQ = limit of quantification

18

Page 55: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

Detroit 1 HotDetroit 2 Hot Flint 1 Hot Flint 2 Hot GrovetownHot

Concentr

ation (

µg/L

)

Chlorine Iodine

DBP Speciation in Unregulated DBPs 20

Page 56: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

= THMs

• Increased THM levels from cold to

hot water seen in all cases, but

below the 80 µg/L regulatory limit.

• Unregulated DBPs detected were

found at low to trace levels.

• Comprehensive analyses results

showed Detroit and Flint water is

very similar in composition.

• Preliminary data shows all iodo-

acids to be < 10 ng/L in Flint and

Detroit.

Conclusions

Flint appears to have no DBP issues when compared to other cities

21

Page 57: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Acknowledgments

Collaborators

Dr. Marc Edwards, Virginia Tech University

Richardson Group

Amy Cuthbertson

Hannah Liberatore

Dr. Susana Kimura-Hara

Meghan Franco

22

Page 58: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

58

Dennis Walters, Matt Smith, Tracy Hacker, Tonya Williams, Kaylie Mosteller, Carrie Nelson, Claire McClinton, Keri Webber, Tony Palladeno Jr., Leah Palladeno, Jessica Owens

Page 59: Flint Water Press Conferenceflintwaterstudy.org/wp-content/uploads/2016/12/VT_Edwards_12.2.pdf · Kitchen Tap: June Nov. Cold Water Yes No Hot Water Yes No L. pneumophila concentration

Thank you!