FloorLineInstallationInstructions

GB

1

2

3

4a4b

5

5

7

8

9

6

10

11

11

12

13

14

17

15

15

8

16

17

2 Maj2007

FloorLine Panels - overview

1. Floorgrating(aluminium) 2. Mouldingstrip(Santoprene) 3. Guideprofile(aluminium) 4a. Finnedpipe,flow(copper) 4b. Finnedpipe,return(copper) 5. Velcrotape 6. Flexiblepipes 7. Motor 8. Fan(aluminium)

9. Bearingblock(aluminium/brass) 10. Fancoupling(plastic) 11. Pipefixture(aluminium) 12. Installationprofile(aluminium) 13. Panelend(aluminium) 14. CHMmotorcontrolprint 15. Motorconnection 16. Connectioncableandterminals 17. Adjustmentblocks(aluminium)

Maj2007 3

FloorLinePanel-overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page2

Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page3

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page4

Unpackingthepanel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page5

Positioningofinstallationfittings. . . . . . . . . . . . . . . . . . . . . . . . . . . page6

Installingthepanel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page6

Checkingthejoints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page8

Powerconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page8

Adjustingthepanel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page9

Openingtheguideprofile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page9

Connectingseveralpanelsinseries. . . . . . . . . . . . . . . . . . . . . . . . . page11

Diagram:ControlwithTWWroomthermostat . . . . . . . . . . . . . . page13

Diagram:ControlviaexternalCTSsignal. . . . . . . . . . . . . . . . . . . . page14

Operatingconditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page15

Contents

ReadtheseinstallationinstructionscarefullybeforeinstallingtheConvecFloorLinepanel.

TheinstallationofFloorLinepanelsisdividedintopre-installationandfinalinstallation.

Pre-installationcomprisesinstallationoffittingsandanyshut-offvalvesconnectedtotheheatingsystemaswellaselectricwiring.

Finalinstallationcomprisesthepanelitself,whichshouldbeinstalledaslateinthebuildingprocessaspossibletoprovidethebestprotectionofmechanicalpartsagainstdustandpaintresidue,aswellasshocks,impactsandotherdamage.

Installation ductThepanelsaresuppliedwithself-jointingrubberstrips,which“absorb”smallinaccuraciesintheinstallationduct.

Toachievethevisuallybestresult,itisnecessarytoobservethemeasurementsoftheinstallationductaspreciselyaspossible,particularlytheductwidthof139mm(seepage6).

AdjustmentsTheFloorLinepanelsareequippedwithintegratedadjustmentscrews,whichenableaccurateadjustmentofthepanelheighttoalignwiththefloorlevel.

Pleaseensurethatalladjustmentscrewsarerestingonthebasetoachievemaxi-mumstability.

4 Maj2007

NB!Allelectricalandplumbingworkmustbecarriedoutbyauthorisedelectriciansandplumbers.

Introduction

Before installationBeforeinstallationofthepanelthefol-lowingshouldbecompleted:

Systempipes,flowandreturn

ExternalwiringforCHR/BMSand powersupply

Check!Measurementsoftheinstal- lationductandleveloffinalfloor

Check!Panelnumber

Maj2007 5

Unpacking the panel 1/3

Checkthepanelnumberonthebox.

Breakthesealonthebox.

Unpacking the panel 2/3

Openthebox.

Liftthegratingsoffthepanelandplacethemontheopenedpartofthebox.

NB!Avoidmixinggratingsfromdifferentpanelsastheyarecuttoindividualdimensions.

Removethepanelfromthebox.

Unpacking the panel 3/3

Underthepanelisaprotectivesheetofstrongcardboard.Usethistoprotectthepanelagainstdust,impacts,etc.

6 Maj2007

Positioning of installation fittings 1/2

139 ± 1 mm

63 - 73 mm

Checkthattheinstallationductmeetsthespecifieddimensions.Iftheductisdeeperthan73mm,astablesupportmustbecre-atedforthepanel.

Ductlengthcanbecalculatedasfollows:•Panelsshorterthan6000mm:thelengthequalstotalpanellength+5mm.•Panelslongerthan6000mm:theductisextendedfurther1mmpermeterpanel.

Positioning of installation fittings 2/2 65 mm

½“

Fixtheenclosedinstallationfittingtothebaseoftheinstallationduct.

Connectthesystempipes.

NB!Checkthattheflowandreturnpipesarecorrectlypositioned.

Installing the panel 1/4

1.Flow2.Return3.Flexiblepipes4.Terminal5.Motor

Maj2007 7

Installing the panel 2/4

LowertheFloorLinepanelintotheinstallationduct.

Installing the panel 3/4

Attachtheflexiblepipestotheinstallationfittings.

NB! Theenclosedgasketsmustbeused.

Installing the panel 4/4

Tightenthejointswithamoderatetorque.

YouarerecommendedtouseanNV24openringspanner(orderno.088H4821).

8 Maj2007

Checking the joints 1/1

Aftertightening,pressurisethesystemandcheckforpossibleleaks.

Power connection 1/2

ConnectcablesfromtheCHRroomthermostat(orBMSsystem)andfromthe24Vpowersupply.

Power connection 2/2

Wiringmustbecarriedoutaccordingtotheelectricalcurcuitdiagramsonpage13-14.

Maj2007 9

Adjusting the panel 1/2

Adaptthepaneltothefloorheightusingtheintegratedadjustingscrewslocatedatsuitableintervalsalongthefulllengthofthepanel.

Usea2.5mmAllenkey.

NB!Onaccountofthepanel’sloadstrength,itisimportantforalladjustingscrewstobeadjustedcorrectly.

Adjusting the panel 2/2

Putthefloorgratinginplaceandcheckthatitisalignedwiththefloorsurface.

Opening the guide profile 1/4

Removethefloorgratingfromthepanel.

10 Maj2007

Opening the guide profile 2/4

Releasetheguideprofilefromthepipefixturebypullingsightly.

Repeatthisalongthefulllengthofthepanel.

Opening the guide profile 3/4

Theguideprofilecannowbeliftedtogiveaccesstothebaseofthepanel.

Opening the guide profile 4/4

Whentheguideprofileisclosed,secureitwithlightpressureontheVelcropads.

Maj2007 11

Connecting several panels in series 1/5 A

Pushthepanelstogether.Thejointblocks(A)ensureprecisepaneljointing.

Extendtheflexiblepipestoreachthefittingsonthenextpanel.

Connecting several panels in series 2/5

Togiveroomforthermalexpansion,pullthepanels2mmapart.

Connecting several panels in series 3/5

1

1

2

2

Insertgasketsbetweentheflexiblepipesandthefittingsbeforefastening.

12 Maj2007

Connecting several panelsin series 4/5

TightentheflexiblepipeswithanNV24ringspanner.

NB!Alwaysholdthepipeinplaceinthepanelwithmultigrippliers.

Connecting several panelsin series 5/5

Aftertightening,pressurisethesystemandcheckforleaks.

24Vdc0Vdc24Vdc0VdcHeat/CoolRPM(0-10V)H.valve+H.valve-

CHR

24Vdcmax.1.1A

Powersupply(22-28Vdc)

Panels in series

Stand-alone (ST) panel

1

2

3

4

5

6

7

8

9

10

1 2 3 4 5 6

24 Vdc

GND

24 Vdc

GND

H/C

RPM

HV +

HV -

CV +

CV -

Maj2007 13

System with CHR room thermostat

ACHRcancontrolupto10Convecpan-elsinthesameroom.AConvecpanelcanbesuppliedwithavalvetocontrolflowthroughthepanel.

Wiring

SuppliedfromfactoryTDMpowersupply

CHRroomthermostat

CHMmotorcontrolCHR

roomthermostat

TDMpowersupply

TDMpowersupply

CHRroom

thermostat

NB!CHRroomthermostatsandCHMmotorcontrolhaveacommon“0”.

1

2

3

4

5

6

7

8

9

10

24 Vdc

GND

24 Vdc

GND

H/C

RPM

HV +

HV -

CV +

CV -

0-10V0

14 Maj2007

System with BMS controlAConvecpanelcanbecontrolleddirectlyfromaBMSsystembya0-10Vsignal.Controlofmin.andmax.fanspeedisperformedbytheBMSsystem.However,theCHMmotorcontrolwillcontinueto

Wiring

SuppliedfromfactoryTDM

powersupply

BMSsystem

CHMmotorcontrol

BMSsystem

TDMpowersupply

TDMpowersupply

performthepanelcontrol,e.g.stoppingthemotorifblockedorthecontrolofanydecentralizedvalves.NB! Watersupplyvalvesareconnectedtocoolingoutputs9and10.

24Vdc0Vdc24Vdc0VdcHeat/CoolRPM(0-10V)

C.valve+C.valve-

BMSsystem

24Vdcmax.1.1A

Powersupply(22-28Vdc)

Panels in series

Stand-alone (ST) panel

Maj2007 15

Operating conditions

Operatingpressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10bar

Testpressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13bar

Storagetemperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -10-60°C

Watertemperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-85°C

Waterquality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .VDI2035

16 Maj2007

Forfurtherinformationpleasecontact:

MEINERTZA/SSverigesvej11DK-8660SkanderborgPhone+4586521811Fax+4586521515www.meinertz.com