Bray Controls Commercial Division 13788 West Road, Suite 200A Houston, Texas 77041 [email protected] Phone: 1-888-412-2729 Fax: 1-888-412-2720 COMMERCIAL www.braycommercialdivision.com ATT Series 1 Figure 1 Figure 2 The ATT inserts are for use with four different valve housings, either: B 1/2(15), 3/4(20), 1(25) B 1(25), 1-1/4(32) C 1/2(15), 3/4(20),1(25), 1 1/4(32) D 1(25), 1-1/4(32),1-1/2(40) Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, industry standards call for pressure interdependent control valves (PIC Valves) to be installed on the downstream side of the terminal unit. Especially for the C and D bodies with their isolation ball valve, it is recommended to ensure the isolation valve is downstream of the PIC valve. Note - valve selections should not be larger than pipe size. INSTALL THE VALVE HOUSING WITH THE FLOW DIRECTIONAL ARROW POINTING IN THE CORRECT DIRECTION. For all threaded connections please clear threads on both valve and piping of debris. Sealant such as pipe dope or teflon tape is recommended. WHEN USING HEMP AS PIPE SEALANT, ENSURE NO STRANDS ARE LEFT IN THE VALVE OR PIPING. The B valve body is similarly available with female-by-female threaded connections, i.e. figure 1. ATT valves ship standard with plugs already assembled. They can be ordered with Pressure Temperature ports assembled at the factory as well, just use the Connection/Port codes that end in “P” for pressure/ temperature plugs. The C and D valves are available with double union end connections, i.e. figure 2. Two types of end connections are available for use with the union nut: Threaded (male or female): The thread standard is NPT or BSP ISO 228 which is a straight metric thread (compatible with BS- 2779), depending on the end connections ordered. The threads on both the connection and piping should be cleaned carefully. As these models are union end connected, the union nuts and the end connections should be removed for installation. O-rings are supplied with the valve body and used to seal the connections. It is recommended to grease the o-rings with silicone grease before installation. IMPORTANT: Never use mineral oil or petrol based grease or oil on the o-rings. Please make sure the o-rings are in place in the o-ring grooves in the inlet and outlet of the valve body when installing the housing and REMEMBER TO TIGHTEN THE UNION NUTS TO ENSURE SEALING. Soldered End (sweat): REMOVE THE END CONNECTIONS FROM THE HOUSING BEFORE SOLDERING. THIS ENSURES THAT THE O-RINGS AND INTERNAL PARTS ARE NOT DAMAGED BY HEAT. Inserting the insert: ATT valves ship standard with your specified insert included. Inserts can be replaced keeping the valve in-line. Prior to installing the insert (supplied from factory in setting 5.0 due to calibration), the system should be properly flushed. A blank valve cover is available to be installed during flushing. It is recommended that the o-rings located around the ATT insert and at the headnut are lubricated with silicone grease, before the insert is installed into the valve body. IMPORTANT: Never use mineral oil or petrol based grease or oil on the o-rings. The desired flow rate is chosen by adjusting the flow control insert (turned from setting 1.0 and up), with a special adjustment key, i.e. figure 3 (page 2). The key is used to adjust the scale on the top of the insert; the large white are numbered 1 through 5 and the red are numbered 1 through 9. The insert can be installed in the valve body either before or after setting the required flow rate. Once the correct flow rate has been selected and the insert is fitted in the valve body, then the actuator is applied. Please see specific installation instruction for selected actuator. General. It is recommended flushing the system before installing the insert in the valve body. Suitable flushing caps are available. Water must always be suitable treated, clean and free of debris. It is recommended that a strainer be installed prior to the valve body to prevent damage or blockage due to debris. Ensure that the valve is not in the fully closed position when filling the system with water. Warranty obligation. Failure to abide by all recommendations as per this installation and operation instruction will void warranty. 1/2” – 1-1/2” Valve & Actuator Models FN.0.2, FN.0.4, FN.1.2 — Installation Instructions Valve Installation 6/29/15
Transcript
Page 1: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

Bray Controls Commercial Division13788 West Road, Suite 200AHouston, Texas [email protected]: 1-888-412-2729Fax: 1-888-412-2720

COMMERCIALwww.braycommercialdivision.com

ATT Series

1

Figure 1

Figure 2

The ATT inserts are for use with four different valve housings, either:

B 1/2(15), 3/4(20), 1(25)B 1(25), 1-1/4(32)C 1/2(15), 3/4(20),1(25), 1 1/4(32) D 1(25), 1-1/4(32),1-1/2(40)

Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, industry standards call for pressure interdependent control valves (PIC Valves) to be installed on the downstream side of the terminal unit. Especially for the C and D bodies with their isolation ball valve, it is recommended to ensure the isolation valve is downstream of the PIC valve.

Note - valve selections should not be larger than pipe size.

INSTALL THE VALVE HOUSING WITH THE FLOW DIRECTIONAL ARROW POINTING IN THE CORRECT DIRECTION.

For all threaded connections please clear threads on both valve and piping of debris. Sealant such as pipe dope or teflon tape is recommended.

WHEN USING HEMP AS PIPE SEALANT, ENSURE NO STRANDS ARE LEFT IN THE VALVE OR PIPING.

The B valve body is similarly available with female-by-female threaded connections, i.e. figure 1.

ATT valves ship standard with plugs already assembled. They can be ordered with Pressure Temperature ports assembled at the factory as well, just use the Connection/Port codes that end in “P” for pressure/ temperature plugs.

The C and D valves are available with double union end connections, i.e. figure 2.

Two types of end connections are available for use with the union nut:

Threaded (male or female):The thread standard is NPT or BSP ISO 228 which is a straight metric thread (compatible with BS- 2779), depending on the end connections ordered. The threads on both the connection and piping should be cleaned carefully. As these models are union end connected, the union nuts and the end connections should be removed for installation.

O-rings are supplied with the valve body and used to seal the connections. It is recommended to grease the o-rings with silicone grease before installation.

IMPORTANT: Never use mineral oil or petrol based grease or oil on the o-rings. Please make sure the o-rings are in place in the o-ring grooves in the inlet and outlet of the valve body when installing the housing and REMEMBER TO TIGHTEN THE UNION NUTS TO ENSURE SEALING.

Soldered End (sweat):REMOVE THE END CONNECTIONS FROM THE HOUSING BEFORE SOLDERING. THIS ENSURES THAT THE O-RINGS AND INTERNAL PARTS ARE NOT DAMAGED BY HEAT.

Inserting the insert:ATT valves ship standard with your specified insert included. Inserts can be replaced keeping the valve in-line. Prior to installing the insert (supplied from factory in setting 5.0 due to calibration), the system should be properly flushed. A blank valve cover is available to be installed during flushing. It is recommended that the o-rings located around the ATT insert and at the headnut are lubricated with silicone grease, before the insert is installed into the valve body. IMPORTANT: Never use mineral oil or petrol based grease or oil on the o-rings.

The desired flow rate is chosen by adjusting the flow control insert (turned from setting 1.0 and up), with a special adjustment key, i.e. figure 3 (page 2). The key is used to adjust the scale on the top of the insert; the large white are numbered 1 through 5 and the red are numbered 1 through 9.

The insert can be installed in the valve body either before or after setting the required flow rate. Once the correct flow rate has been selected and the insert is fitted in the valve body, then the actuator is applied.

Please see specific installation instruction for selected actuator.

General.It is recommended flushing the system before installing the insert in the valve body. Suitable flushing caps are available. Water must always be suitable treated, clean and free of debris. It is recommended that a strainer be installed prior to the valve body to prevent damage or blockage due to debris. Ensure that the valve is not in the fully closed position when filling the system with water.

Warranty obligation.Failure to abide by all recommendations as per this installation and operation instruction will void warranty.

1/2” – 1-1/2” Valve & Actuator Models FN.0.2, FN.0.4, FN.1.2 — Installation Instructions

Valve Installation

6/29/15

Page 2: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

2

(L) Cartridge (M) Cartridge (H) Cartridge2.3-58 psid (.16-4 bar)*

High Flow(Black O-Ring)

2.3-29 psid (.16-2 bar)Low Flow

(Green O-Ring)

4.4-58 psid (.30-4 bar)Medium Flow(Black O-Ring)

SETTING GPM l/hr GPM l/hr GPM l/hr1 0.1 32.0 0.3 64 3.8 865

1.1 0.3 75.8 0.6 142 4.5 10101.2 0.5 116 0.9 209 5.1 11601.3 0.7 153 1.2 268 5.7 13001.4 0.8 188 1.4 319 6.3 14301.5 1.0 220 1.6 366 6.9 15701.6 1.1 250 1.8 408 7.5 17001.7 1.2 278 2.0 446 8.0 18201.8 1.3 304 2.1 482 8.6 19401.9 1.5 329 2.3 516 9.1 20602.0 1.6 352 2.4 549 9.6 21802.1 1.7 374 2.6 580 10.1 22902.2 1.7 396 2.7 611 10.6 24002.3 1.8 416 2.8 641 11.0 25102.4 1.9 435 3.0 671 11.5 26102.5 2.0 453 3.1 700 11.9 27102.6 2.1 471 3.2 728 12.4 28102.7 2.2 488 3.3 756 12.8 29002.8 2.2 504 3.5 783 13.2 30002.9 2.3 520 3.6 810 13.6 30903.0 2.4 535 3.7 835 14.0 31803.1 2.4 549 3.8 860 14.4 32603.2 2.5 563 3.9 883 14.7 33503.3 2.5 577 4.0 906 15.1 34303.4 2.6 590 4.1 927 15.5 35103.5 2.7 602 4.2 946 15.8 35903.6 2.7 614 4.3 965 16.1 36703.7 2.8 626 4.3 982 16.5 37403.8 2.8 637 4.4 998 16.8 38203.9 2.9 649 4.5 1010 17.1 38904.0 2.9 659 4.5 1020 17.4 39604.1 3.0 670 4.6 1040 17.7 40304.2 3.0 681 4.6 1050 18.1 41004.3 3.0 691 4.7 1060 18.4 41704.4 3.1 701 4.7 1070 18.7 42404.5 3.1 711 4.7 1080 19.0 43004.6 3.2 721 4.8 1080 19.2 43704.7 3.2 730 4.8 1090 19.5 44404.8 3.3 740 4.8 1100 19.8 45004.9 3.3 749 4.9 1100 20.1 45705.0 3.3 757 4.9 1110 20.4 4630

Accuracy: Greatest of either +/- 10% of controlled flow rate or +/- 5% of maximum flow rate.* At setting 2.6

Figure 3

1/2” – 1-1/2” - Valve & Actuator Models FN.0.2, FN.0.4, FN.1.2 — Installation Instructions

Page 3: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

3

Figure 4

B

C

Fa

A

DN25/32/40

F

D1 D2

C

EE

Assembly DrawingA: Valve housingB: InsertC: Adjustment keysD1: P/t plug (2 pcs.)D2: Plug and gasket (2 of each)E: Union end connectionsF: Actuator (FN.0.X-type)Fa: Valve adaptor.

1/2” – 1-1/2” - Valve & Actuator Models FN.0.2, FN.0.4, FN.1.2 — Installation Instructions

Page 4: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

4

Figure 1

Figure 2

Max 90º Max 90º

Figure 4

Figure 3

The actuator type Bray FN.0.2 is anelectrical modulating actuator supplied with a valve adaptor for easy installation.

Fitting andorientation of the actuator.Separate valve adaptor from actuator (figure 2) by pressing the green release button and turning the top part of the actuator 30° counter clockwise. Then remove the top part of the actuator from the valve adaptor.

Rotate the black knob on the valve adaptor counter clockwise (figure 3) so that the valve adaptor stem and the green indicators are in top position. Mount the valve adaptor on the insert (which must already be installed inthe valve body) and finger tighten the connec-tion union. Do not use additional tools.Never install the valve adaptor in closed position as this may damage the insert.

The piping network can now be tested if necessary by manually adjusting the valve adaptor knob.

WARNING: Do not force the knob in either direction and never adjust the black knob on the valve adaptor with a higher torque than 1 Nm.

Then place the actuator on the valve adap-tor and turn clockwise 30°, until a “click” is heard.Please do not mount the actuator more than 90° from vertical (figure 4).

Bray Controls Commercial Division13788 West Road, Suite 200AHouston, Texas [email protected]: 1-888-412-2729Fax: 1-888-412-2720

COMMERCIALwww.braycommercialdivision.com

FN.0.2 Series - Electric Actuators

1/2” – 1-1/2” - Actuator Models FN.0.2 — Installation Instructions

Page 5: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

5

Figure 6: Dip switch factory settings (ON-OFF-ON).

Blac

k

Power 24V AC/DC

Ground/common

Gre

en

Whi

te

Feedback signal0(2)-10V DCInput signal

0(2)-10V DC

Red

FN.0.2 / 1.2 / 5.2 / 6.2 Actuator

Figure 5

FN.0.2 Actuator

Actuator wiring.The wiring diagram for Bray FN.0.2 is shown in figure 5.

Dip switch settings.Lift the silicone cap on the back of the actua-tor to get access to the dip switches (figure 6).

Dip switch no. 1- Rotation direction:OFF - Normally open.ON - Normally closed.

Dip switch no. 2 - Auto stroke:OFF - Deactivated.ON - Activated.

Dip switch no. 3 - Analog control and feed-back signal:OFF - 2-10V DC.ON - 0-10V DC.

Auto stroke option.With the auto stroke option activated, the ac-tuator will make one full cycle every 24 hour,if the actuator constantly has been in fullyopen or fully closed position during the previous24 hours.This operation will clear up any possibleimpurities accumulated in the valve, andre-calculate the end positions

Please note that during auto stroke cycle, the actuator will not respond to the control signal.

Start-Up Sequence.When power is applied, the actuator will calibrate itself: • The actuator is calibrated by first opening fully and then closing to find the valve’s closing point. This can take up to 165 sec. The LED will be constantly turned on during calibration. • The actuator will proceed to normal operation (according to the control signal). The LED will blink in a loop of 1 sec. on, 9 sec. off while in normal operation.During operation the actuator will self-adjust according to the closing point of the valve.

Removing actuator / Manual override operation.To disengage the actuator or perform manual override, please turn off the power supply and press the release button while turning thetop part of the actuator counter clockwise 30°(figure 2, previous page).

The piping network can now be tested if necessary by manually adjusting the valve adaptor knob.

IMPORTANT:The Bray FN.0.2 actuator and the FN.0.2 valve adaptor are not custom made as a pair from the supplier, which means that a FN.0.2 actuator can be used with any FN valve adaptor. Using other models of valve adaptors may cause valve damage.

Warranty obligation.Failure to abide by all recommendations as per this installation and operation instruction will void warranty.

1/2” – 1-1/2” - Actuator Models FN.0.2 — Installation Instructions, continued

factory default is Normally Closed

Page 6: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

6

Figure 1

Figure 2

Max 90º Max 90º

Figure 4

Figure 3

The actuator type Bray FN.0.4 is anelectrical On/Off actuator supplied with a valve adaptor for easy installation.

Fitting andorientation of the actuator.Separate valve adaptor from actuator (figure 2) by pressing the green release button and turning the top part of the actuator 30° coun-ter clockwise. Then remove the top part of the actuator from the valve adaptor.

Rotate the black knob on the valve adaptor counter clockwise (figure 3) so that the valve adaptor stem and the green indicators are in top position. Mount the valve adaptor on the insert (which must already be installed inthe valve body) and finger tighten the connec-tion union. Do not use additional tools.Never install the valve adaptor in closed position as this may damage the insert.

The piping network can now be tested if necessary by manually adjusting the valve adaptor knob.

WARNING: Do not force the knob in either direction and never adjust the black knob on the valve adaptor with a higher torque than 1 Nm.

Then place the actuator on the valve adap-tor and turn clockwise 30°, until a “click” is heard.Please do not mount the actuator more than 90° from vertical (figure 4).

Bray Controls Commercial Division13788 West Road, Suite 200AHouston, Texas [email protected]: 1-888-412-2729Fax: 1-888-412-2720

COMMERCIALwww.braycommercialdivision.com

FN.0.4 Series - Electric Actuators

1/2” – 1-1/2” - Actuator Models FN.0.4 — Installation Instructions

Page 7: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

Blac

k

Power 24V AC/DC

Ground/common

Whi

te

Red

2-position, NC

Open

FN.0.4 / 5.4 Actuator

Close

Figure 5

FN.0.4 Actuator2-Position, Normally Closed

Blac

k

Power 24V AC/DC

Ground/common

Whi

te

Red

2-position, NO

Open

FN.0.4 / 5.4 Actuator

Close

Figure 6

FN.0.4 Actuator2-Position, Normally Open

Blac

k

Power 24V AC/DC

Ground/common

Whi

te

Red

3-point-floating, NC

OpenStop

FN.0.4 / 5.4 Actuator

Close

Figure 7

FN.0.4 Actuator3-Point-Floating, Normally Closed

Blac

k

Power 24V AC/DC

Ground/common

Whi

te

Red

3-point-floating, NC

OpenStop

FN.0.4 / 5.4 Actuator

Close

Figure 8

FN.0.4 Actuator3-Point-Floating, Normally Open

Figure 9: Dip switch factory settings (ON-OFF).

7

Actuator wiring.The wiring diagram for Bray FN.0.4 is shown in figure 5-8.

Removing actuator / Manual override operation.To disengage the actuator or perform manual override, please turn off the power supply and press the release button while turning thetop part of the actuator counter clockwise 30°(figure 2, previous page).

The piping network can now be tested if necessary by manually adjusting the valve adaptor knob.

IMPORTANT:The Bray FN.0.4 actuator and the FN.0.4 valve adaptor are not custom made as a pair from the supplier, which means that a FN.0.4 actuator can be used with any FN valve adaptor. Using other models of valve adaptors may cause valve damage.

Warranty obligation.Failure to abide by all recommendations as per this installation and operation instruction will void warranty.

Dip switch settings.Lift the silicone cap on the back of the actua-tor to get access to the dip switches (figure 9).

Dip switch no. 1- Rotation direction:OFF - Normally open.ON - Normally closed.

Dip switch no. 2 - NA:This dip switch is not in use.

1/2” – 1-1/2” - Actuator Models FN.0.4 — Installation Instructions, continued

factory default is Normally Closed

Page 8: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

8

Figure 1

Figure 2

Max 90º Max 90º

Figure 4

Figure 3

The actuator type Bray FN.1.2 is anelectrical modulating actuator with failsafe sup-plied with a valve adaptor for easy installation.

Fitting andorientation of the actuator.Separate valve adaptor from actuator (figure 2) by pressing the green release button and turning the top part of the actuator 30° coun-ter clockwise. Then remove the top part of the actuator from the valve adaptor.

Rotate the black knob on the valve adaptor counter clockwise (figure 3) so that the valve adaptor stem and the green indicators are in top position. Mount the valve adaptor on the insert (which must already be installed inthe valve body) and finger tighten the connec-tion union. Do not use additional tools.Never install the valve adaptor in closed position as this may damage the insert.

The piping network can now be tested if necessary by manually adjusting the valve adaptor knob.

WARNING: Do not force the knob in either direction and never adjust the black knob on the valve adaptor with a higher torque than 1 Nm.

Then place the actuator on the valve adap-tor and turn clockwise 30°, until a “click” is heard.Please do not mount the actuator more than 90° from vertical (figure 4).

Bray Controls Commercial Division13788 West Road, Suite 200AHouston, Texas [email protected]: 1-888-412-2729Fax: 1-888-412-2720

COMMERCIALwww.braycommercialdivision.com

FN.1.2 Series - Electric Actuators

1/2” – 1-1/2” - Actuator Models FN.1.2 — Installation Instructions

Page 9: FlowCon Green Instruction… · Install the selected valve housing as called for in the design drawings. Although the performance of the valve is not affected either way, is re industry

9

Figure 6: Dip switch factory settings (ON-OFF-ON-ON).

Blac

k

Power 24V AC/DC

Ground/common

Gre

en

Whi

te

Feedback signal0(2)-10V DCInput signal

0(2)-10V DC

Red

FN.0.2 / 1.2 / 5.2 / 6.2 Actuator

Figure 5

FN.1.2 Actuator

Actuator wiring.The wiring diagram for Bray FN.1.2 is shown in figure 5.

Dip switch settings.Lift the silicone cap on the back of the actuator to get access to the dip switches (figure 6).

Dip switch no. 1- Rotation direction:OFF - Normally open.ON - Normally closed.

Dip switch no. 2 - Auto stroke:OFF - Deactivated.ON - Activated.

Dip switch no. 3 - Analog control and feedback signal:OFF - 2-10V DC.ON - 0-10V DC.

Dip switch no. 4 - Failsafe direction:OFF - Open.ON - Close.

Auto stroke option.With the auto stroke option activated, the actuator will make one full cycle every 24 hour, if the actuator constantly has been in fully open or fully closed position during the previous 24 hours.This operation will clear up any possibleimpurities accumulated in the valve, and re-calculate the end positions

Please note that during auto stroke cycle, the actuator will not respond to the control signal.

Start-Up Sequence.When power is applied, the actuator will charge the capacitor and calibrate itself: • The capacitor is charged. This can take up to 140 sec. (normally about 20 sec). The LED will blink once every 2 sec. while charging. • The actuator is calibrated by first opening fully and then closing to find the valve’s closing point. This can take up to 165 sec. The LED will be constantly turned on during calibration. • The actuator will proceed to normal operation (according to the control signal). The LED will blink in a loop of 1 sec. on, 9 sec. off while in normal operation.

Failsafe Sequence.When power is lost, the actuator will go into failsafe mode after a few seconds: • The actuator will perform the failsafe action (open or close). The LED will blink once every 2 sec. while in failsafe mode. • The LED will blink in failsafe mode for about 7 minutes after the failsafe action is completed and then the actuator will shut off.

Removing actuator / Manual override operation.To disengage the actuator or perform manual override,please turn off the power supply and press the release button while turning the top part of the actuator counter clockwise 30° (figure 2, page 1).

The piping network can now be tested if necessary by manually adjusting the valve adaptor knob.

Important: Bray FN.1.2 actuator and FN.1.2 valve adaptor are not custom made as a pair from the supplier, which means that a FN.1.2 actuator can be used with any FN valve adaptor with green indicators. Using other models of valve adaptors may cause valve damage.

Warranty obligation.Failure to abide by all recommendations as per this installation and operation instruction will void warranty.

1/2” – 1-1/2” - Actuator Models FN.1.2 — Installation Instructions, continued

factory default is Normally Closed


Recommended