Heat Transfer To a Fluid in a CSTR University Of Illinois
Heat Transfer to a Fluid in a CSTR
Lab Prep ReportUnit Operations Lab 1
January 25, 2011Group 3
Russel CabralJay Gulotta
Scott MorganBrian MottelMrunal PatelFrank Perez
Sukhjinder Singh
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
1
Heat Transfer To a Fluid in a CSTR University Of Illinois
1. Introduction
Stirred tanks are used for many different processes in the chemical industry, which can
include mixing of solutions, leaching, and chemical reactions. An impeller will be used
to continuously stir the tank and perfect mixing can be assumed. Baffles are also in
place to enhance the mixing. This particular lab will allow one to study a range of heat
transfer processes. The focus will the measurement of the heat transfer coefficient
between the fluid and the inside vessel wall.
The values of the heat transfer coefficients are functions of the fluid flow field
and the molecular transport properties of the fluid [1]. Analyzing the parameters will
include the dependence of the heat transfer coefficient on fluid properties, impeller
speed, and the use of the baffles. Once these values are obtained, they can be
compared to results from other labs or investigators. Theoretical analysis has shown
that the heat transfer coefficient between a fluid and a surface can be related in terms
of dimensionless groups. Convective flow can be used as an example, which only needs
Reynolds number, Prandtl number, and geometric factors to correlate heat transfer data
over a broad range of conditions.
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
2
Heat Transfer To a Fluid in a CSTR University Of Illinois
2. Literature Review/ Theory
In this experiment, three heat transfer cases can be considered;
1) Heat transfer condensing steam to the tank wall2) Heat transfer across the internal fluid to the wall of the stirred tank3) Heat transfer across the tank wall
In all three cases the heat transfer operation may be written as:
Q=U i A∆T Q=UA ∆T (1)
where
Q – heat transferred [=] J / sec Ui – overall heat transfer [=]
Wm2 K
A - area available for the flow of heat [=] m2
∆T - difference in temperature [=] K
From equation (1) it can be seen that the relationship between Q and ∆T is linear and U
is constant, (Wikipedia). However in practice, U is not a constant and is influenced by
both the temperature difference and the absolute value of the temperatures. Therefore,
determination of the overall heat transfer coefficient a requirement in any heat transfer
operation.
Thusly, U will depend on the mechanism by which heat is transferred, (Perrys,
section 8). This can be due to the properties of the material and the geometry of the fluid
paths. In case 1, heat from steam is transferred solely by convection. In case 2, heat is
transferred through the metal by conduction and in case 3; the liquid also transmits heat
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
3
Heat Transfer To a Fluid in a CSTR University Of Illinois
readily by conduction, although convection transfer is considerably greater than the
transfer by conduction.
The flow of heat by conduction in a solid is a result of the transfer of vibrational
energy from one molecule to another and in fluids it occurs as a result of the transfer of
kinetic energy. Heat transfer by convection arises from the mixing of elements of fluid. It
is important to note that convection requires mixing of fluid elements and is not governed
by temperature alone is in the case of conduction.
Consider the simplest case where a solid wall is separating two fluids at two
different temperatures.
Figure (1). Direction of heat flow as a function of time.
At steady state Q, the heat transferred, is the same for any point in the dQ’s direction or
there will be a heat accumulation will result which implies steady state has not been
reached. Therefore dQ is zero and the heat capacity on the solid wall is assumed to be
constant.
A temperature profile at steady state for the above situation is shown below;
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
4
Heat Transfer To a Fluid in a CSTR University Of Illinois
Figure (2). Temperature profile at S.S.
From equation (1), Q is then;
Q=hi A (T ❑2−T 3 )=ho A (T 1−T 2 )=U i A (T 1−T 3)(2)
Q – heat transferred [=] J / sec Ui – overall heat transfer [=]
Wm2 K
hi - the wall heat transfer coefficient at the inner surface [=] W
m2 K
ho - the wall heat transfer coefficient at the outer surface [=] W
m2 KT1 - temperature of the hot fluid [=] KT2 - temperature of the outer and inner wall [=] KT3 - temperature of the cold fluid [=] K
When the solid wall is covered with scale the equation above will change to take
into account scaling of the wall. In this experiment, the apparatus is assumed to be free
of scale.
For this experiment, calculations for the overall heat transfer coefficients will be
based on the scenario shown below:
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
Ui
5
Heat Transfer To a Fluid in a CSTR University Of Illinois
Figure (3). Cstr Heat transfer arrangement
Assumptions are as follows;
1) No scale 2) Negligible resistance to heat transfer by the solid wall. 3) The wall thickness is small compare to the tank diameter. 4) The fluid inside the vessel is well mixed and thus at a uniform temperature. 5) There is no heat loss from the system to the surrounding.
here
T1 - steam temperature in the jacket [=] KelvinT2 - temperature of vessel wall [=] KelvinT3 - bulk average temperature of the fluid inside the tank [=] KelvinT4 - cooling water (tap water) temperature [=] KelvinAi and Ao - heat transfer area of inner and outer vessel wall respectively [=] m2
h o,wall ,h i,wall , h o,coil - heat transferred coefficients [=] W
m2 K
Uwall - overall heat transfer coefficient of the vessel wall [=] W
m2 K
Q13, Q34 - heat transferred [=] J
sec
At steady state, the heat transferred through the vessel follows from equation (2).
Rearrangement of the equations to a form of T a−T b=Qh A
(T 1−T 2 )=Q13
ho Ao(3)
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
6
Heat Transfer To a Fluid in a CSTR University Of Illinois
(T 2−T 3 )=Q13
hi A i(4)
and t adding equations (3) and (4) produces
(T 1−T 3 )=Q13
{ho Ao+hi A i }(5)
When Ao = Ai = A this equation becomes:
Q13=1
1hi
+ 1ho
A(T 1−T 3) (6)
By comparing with equation (1), the overall wall heat transfer coefficient Uwall is
therefore defined as
Uwall=1
1hi
+ 1ho
(7)
Uwall depends on the material of the vessel and is also listed in many literature sources,
(Perry, section8).
The reasons why the above equations, (3) through (7), are only concerned with
the heat transferred, Q, across the vessel wall is because Q is the same everywhere in the
x direction and heat transfer by conduction has less input variables. Heat transfer by
conduction only depends on the temperature, which is much easier to model than the heat
transfer taking place in the vessel.
To measure the heat transferred to the vessel from the steam, Q13, can be
determined from an energy balance around the agitated vessel. Here the heat in is Q13
while the heat out is Qcoil, Qhx, and Qsurrounding.
The Qcoil , heat transferred to the cooling coil, can be calculated by the following:
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
7
Heat Transfer To a Fluid in a CSTR University Of Illinois
Qcoil=mcw C p (T out−T ¿ )(8)
where
Qcoil - heat transferred to the cooling coil [=] J / sec
mcw - mass flow rate of the cooling water [=] kgsec
Cp - heat capacity of the cooling water [=] J
kg K Tout - outlet temperature of the cooling water [=] Kelvin Tin - inlet temperature of the cooling water [=] Kelvin
A countercurrent heat exchanger is used to cool the re-circulating fluid inside the vessel.
The heat exchanger can be modeled as follow:
Figure (4). Counter-current Heat Exchanger
The apparatus does not measure T3 and T4; however an energy balance can be obtained
by the equation (9) below.
Qh x=mhxC p(T t−T r) (9)
where;
Qhx - heat transfer in the heat exchanger [=] J
sec
Cp - heat capacity of the cooling water [=] J
kg K
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
8
Heat Transfer To a Fluid in a CSTR University Of Illinois
mhx - mass flow rate of the recycle water [=] kgsec
Tt - water temperature inside the vessel [=] Kelvin Tr - recycle water temperature leaving the heat exchanger [=] Kelvin
An overall energy balance around the vessel is defined as:
Q13=Q=Qhx+Qcoil+Qsurrounding(10)
Setting Qsurrounding to zero and substituting equations (8) and (9) into equation (10) to give:
Uwall A (T 1−T3 )=mhx Cp (T t−T r )+mcw C p (T out−T¿ )(11)
For an unsteady case where the recirculation pump and the cooling coil are not used, the
accumulation of heat causes the temperature of the fluid in the vessel to increase.
Heat in – Heat out = Accumulation of heat in the fluid or
AU (T 1−T3 )−0=mvC p
d T3
dt (12)
Where
mv - mass if fluid in the vessel [=] kgdT 3
dt - the change of the bulk average temperature of the fluid in the vessel with
respect to time [=] Kelvinsec
Cp - heat capacity of the fluid in the vessel [=]J
kg KA - heat transfer area vessel wall [=] m2
U - overall heat transfer coefficient of the vessel wall [=]W
m2 KT1 - temperature of the steam [=] KelvinT3 - bulk average temperature of the fluid in the vessel [=] Kelvin
To obtain theoretical values for this experiment one can use the following equations.
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
9
Heat Transfer To a Fluid in a CSTR University Of Illinois
Experiment data for heating of an unbaffled vessel containing a Newtonian fluid have the
following correlation, (BSL);
hi DT
k=0.36( D I
2 n ρμ )
23 (Cp μ
k )13 (13)
Where
hi – convection heat transfer coefficient at the inner surface of the tank [=] W
m2 KDT – tank diameter [=] meters
μ - viscosity of the fluid [=] kg
m−secDI - impeller diameter [=] meters
Cp - specific heat of the fluid [=] J
kg K
k - thermal conductivity of the fluid [=] WmK
ρ - density of the fluid [=] kgm3
n - speed of rotation of the impeller [=] revolutions
minute
Equation (13) can be simplified further into three dimensionless groups:
N uT=0.36 (Re imp)23 ( Pr )
13 (14 )
where
hi DT
k=N uT = tank Nusselt number [=] dimensionless
DI2n ρμ
=ℜimp = impeller Reynols number [=] dimensionless
Cp μk
= Pr = fluid Prandtl number [=] dimensionless
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
10
Heat Transfer To a Fluid in a CSTR University Of Illinois
In equations (13) and (14), the only unknown variable is hi, wall ; therefore it can
easily be solved. Take caution to verify that each dimensionless group is in fact
dimensionless. Each dimensionless group can be calculated in different measuring
systems (SI or English unit).
The goal of this experiment is to determine the experiment value of hi, wall (UIC)
and compare it with the theoretical value from equations (13) and (14).
3. Experimental
3.1.1 Apparatus
The apparatus used while conducting the “Heat Transfer in a Stirred Tank”
lab procedure consists of constantly stirred tank, which is equipped with a cooling
coil, and lined with a steam jacket. Once the tank is filled with water, a pump
located underneath the tank continuously pumps water out of the tank and through
the shell side of a heat exchanger where heat is removed via cooling water. The
cooled tank water then flows through a rotameter to determine the flow rate and re-
enters the tank. Dial thermometers are located at the inlet and outlet of the heat
exchanger. The cooling coils within the tank are fed cold tap water. The flow rate of
the cooling water is set using a rotameter. The temperature of the cooling water is
displayed on dial thermometers located near the inlet and outlet of the cooling coils.
Steam is fed into the steam jacket of the tank to allow heat transfer into the system.
Steam condensate exits the steam jacket and enters a condenser, which has cooling
water flowing through it. The impeller, which stirs the water in the tank, is
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
11
Heat Transfer To a Fluid in a CSTR University Of Illinois
controlled using a variable power supply. A strabotec is used to measure and
display the speed of the impeller.
Figure (3.1) Upper front of the apparatus
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
12
Heat Transfer To a Fluid in a CSTR University Of Illinois
Figure (3.2) lower half of the apparatus
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
13
Heat Transfer To a Fluid in a CSTR University Of Illinois
Figure(3.3) Side view of the apparatus
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
14
Heat Transfer To a Fluid in a CSTR University Of Illinois
Description of labeled aspects of the apparatus:
LabelNumber
Description Use
1 Strabotec Display rotational speed (RPM) of motor which drives impeller
2 Electric Motor Powers the impeller
3 Variable Power Supply Controls the speed of the electric motor
4 Cooling Coil Inlet Rotameter Displays the flowrate of the cooling coil water
5 Cooling Water Inlet Valve Controls the flowrate of the cooling coil water
6 Recycle Water Rotameter Displays the flowrate of the recycle water
7 Recycle Water Thermometer Displays the temperature of the recycle water
8 Cooling Water Inlet Thermometer
Displays the temperature of the cooling coil water at the inlet
9 Tank Thermometer Displays the temperature of the fluid in the tank
10 Tank Contains the fluids, as well as the impeller and steam jacket
11 Tank Outlet Thermometer Displays the temperature of the condensate exiting the steam jacket before it enters the condenser
12 Condenser Cools the steam condensate
13 Pump Continually re-circulates water through the tank
14 Condenser Thermometer Displays the temperature of the cooling water entering the condenser
15 Recycle thermometer Displays the temperature of the water that exited the tank before it enters the heat exchanger
16 Heat Exchanger Cools the recycled water before it re-enters the tank
17 Pump Power Switch Turns on the pump
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
15
Heat Transfer To a Fluid in a CSTR University Of Illinois
3.2 Materials and Supplies
Item Description
Stir Tank with Impeller Holds water as well as mixes.
Water Main component at which measurements will be taken from
Condenser Condenses steam.
Heat Exchanger Transfers heat from water.
Graduated Cylinder Used to measure amount of water from the condenser.
Thermometer Measures temperature.
Pump Forces water through apparatus.
Baffles Creates inconsistency in stir tank.
Mop Used to clean up any spillage.
Stop Watch Time the amount of fluid dispelled from condenser.
3.3 Experimental Procedure
Experiment I. Steady State Procedure Using No Baffles
1. Fill the tank (10) with water to a level about two inches from the top of the tank
by opening the yellow water inlet valve (3rd from left). Measure how far down the
water is in the tank to find the volume of the tank. All yellow valves on the back
wall should always open except for the 3rd from the left. That one is only used to
fill the tank and then closed.
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
16
Heat Transfer To a Fluid in a CSTR University Of Illinois
2. Open recycle valve and heat exchanger water valve, which are located right next
to the respective piece of equipment.
3. Turn on the pump (13) by flipping the pump switch (17).
4. Adjust the recycle flowrate to a chosen rate displayed on the recycle rotameter
(6).
5. Open the cooling water valve (5) and adjust the flowrate to a chosen rate
displayed on the cooling water rotameter (4).
6. Open heat exchanger water valve to allow the flow of cooling water.
7. Open condenser water valve to allow cooling water to run through steam
condenser.
8. Open steam inlet valve located behind the tank and not how many turns used
while opening the valve.
9. Turn on the agitator (2) by flipping the mixer switch (3).
10. Adjust the black dial (3) to set the impeller speed to a low rpm value (between
125 and 150 rpm).
11. Record the impeller speed once the system is at steady state.
12. Obtain steady state by adjusting the water heat exchanger and cooling coil
flowrates such that the tank temperature is maintained at 65°C.
13. Allow system to reach steady state by letting system stay for 10-15 minutes.
14. Record steady state temperature readings of all 7 thermometers and flowrates of
cooling water and recycle.
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
17
Heat Transfer To a Fluid in a CSTR University Of Illinois
15. Obtain mass flowrate of steam by measuring the amount of condensate collected
from the steam condenser, located at the bottom of the front of the system, over a
certain time interval.
16. Repeat steps 11-15 for measurements at two additional higher impeller speeds.
17. Repeat steps 11-15 for measurements for two different heat exchanger flowrates
so that two different vessel temperatures are obtained, using the second impeller
speed settings.
18. To safely shut down turn off the impeller, electric pump, and open the valve at the
bottom of the tank, to allow the tank to drain.
Experiment II. Steady State Procedure with Baffles
1. Repeat experiment I, but this time put baffles inside of the tank
2. There is no difference in the procedure between this part of the experiment and
experiment I.
Experiment II. Unsteady State Procedure Without Baffles in the Tank
1. Fill the tank (10) with cold water (< 40°C) to a level about two inches from the
top of the tank by opening the yellow water inlet valve. Measure with a ruler and
record how far down the water level is to obtain the volume of the tank and water
in the tank.
2. Make sure recycle and heat exchanger valves and the cooling water dial are
closed.
3. Turn on cooling water flow to the steam condenser.
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
18
Heat Transfer To a Fluid in a CSTR University Of Illinois
4. Turn on the agitator (2) by flipping the mixer switch (3).
5. Begin steam flow through insulated jacket by slightly opening the steam valve.
Only turn the steam valve a couple turns at most.
6. Carefully record the fluid temperature as a function of time by recording the
temperature from the tank temperature gauge at even time intervals. Record data
until a temperature of about 85°C is reached. The more data points that can be
recorded the more accurate the final data will be.
7. Obtain a second set of measurements.
8. Repeat the experiment using two additional impeller speeds.
9. To safely shut down apparatus, turn off mixer switch and turn impeller speed
knob (3) to zero. Close all valves. Drain tank (10) by opening drain valve to
allow all water to drain from vessel.
4. Anticipated Results
This experiment is divided into three sections; the first of the three sections consists
of three trials and is meant to find the heat transfer coefficient of the wall of the tank
between the steam and the water. The first trial will determine the heat transfer
coefficient of the wall and will have a fixed value. The second trial will determine the
heat transfer coefficient as a function of impeller speed. It is believed that from
equation 3 if the initial conditions are used to find the value for Q13, then equation 4
was then used with the new area since the impeller speed increases the amount of
water in contact with the wall of the tank. Also as equation 4 shows, with a constant
Q13 and the same change in temperature the value for the heat transfer coefficient
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
19
Heat Transfer To a Fluid in a CSTR University Of Illinois
should decrease. The third trial will determine the heat transfer coefficient as a
function of temperature. It is believed that as the change in temperature increases
then the heat transfer coefficient should decrease due to the inverse proportionality
between the two.
The second section of the lab repeats the process of the first with the addition of
baffles in the tank. The baffles will increase the surface area and if we assume the
change in temperature and the heat added are constant the heat transfer coefficient
should decrease going off of equations 3 and 4.
In the last section of the lab a steady state will be reached without the steam then
the steam valve will be opened and the change in temperature will be recorded as a
function of time. By doing so the heat added to the system will increase, thus
increasing the heat transfer coefficient due to the direct relationship between heat
and heat transfer coefficient.
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
20
Heat Transfer To a Fluid in a CSTR University Of Illinois
5. References
1. Bird, R. B., Warren E. Stewart, and Edwin N. Lightfoot. Transport Phenomena. 2nd ed. New York, NY: Jonh Wiley & Sons, Inc., 2002
2. "Heat Transfer Coefficient." Wikipedia. 19 Jay. 2011
3. Perry, Robert H., and Don W. Green. Perry's Chemical Engineers' Handbook. New York: McGraw-Hill Professional, 2007.
4. University of Illinois at Chicago - UIC. Web. 13 Sept. 2010. <http://www.uic.edu/depts/chme/UnitOps/entry.html>.
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
21
Heat Transfer To a Fluid in a CSTR University Of Illinois
Appendix I: Job Safety Analysis (formerly called WP &C)
What is the purpose of this experiment?
The purpose of this experiment is to study the heat transfer in a constantly stirred
tank, by measuring the heat transfer coefficients associated with the system.
Experiments are carried out under varying conditions; for example steady state,
unsteady state, with and without baffles, different impeller speeds and steam flow
rates.
What are the hazards associated with the experiment?
A hazard associated with this experiment is overfilling the tank and causing it to
spill. Other hazards include accidently burning yourself with the pipe carrying the
incoming steam as well as pressurized components. In addition the impeller motor
is a moving part of machinery and is easily capable of injuring someone.
How will the experiment be conducted in a safe manner?
The tank will be filled with the lid off so that the water level can be easily monitored.
The pump will be turned on after the tank has reached the desired water level to
avoid spilling water. In addition the pump will not be run dry and the impeller will
only be ran at appropriate speeds and monitored via the digital output. Also
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
22
Heat Transfer To a Fluid in a CSTR University Of Illinois
because of moving parts hands will be kept away from the area where injury will
occur.
What safety controls are in place?
The tank drain valve is present and will be used if the water level is too high. In case
of a water spill napkins or a mop will be used, depending on the size of the puddle,
to clean up the spill.
Describe safe and unsafe ranges of operations.
The pump should never be run without having water in the tank. The impeller speed
should be kept at a safe range (100-400 rpm) but higher speeds should be avoided
(above 1000 rpm). In addition the steam flow rate should not go past 50% of the
maximum operating capacity.
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
23
Heat Transfer To a Fluid in a CSTR University Of Illinois
I have read relevant background material for the Unit Operations Laboratory
entitled: “ Heat transfer to a Fluid in a CSTR” and understand the hazards associated
with conducting this experiment. I have planned out my experimental work in
accordance to standards and acceptable safety practices and will conduct all of my
experimental work in a careful and safe manner. I will also be aware of my
surroundings, my group members, and other lab students, and will look out for their
safety as well.
Signatures: First & Last Name 1____electronic_signature___________
Jay Gulotta __ ________________________________________________
Mrunal Patel _ ______________________________________________
Brian Mottel________________________________________________
Frank Perez_________________________________________________
Sukhjinder Singh________________________________
Russell Cabral________________________________________________
Scott Morgan_________________________________________________
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
24
Heat Transfer To a Fluid in a CSTR University Of Illinois
Unit Operations CHE-381 Group No. 3 Spring 2011 01/25/2011Cabral, Gulotta, Morgan, Mottel, Patel, Perez, Singh
25