+ All Categories
Home > Documents > For the heating specialist Operating and installation ... · PDF fileControl System THETA For...

For the heating specialist Operating and installation ... · PDF fileControl System THETA For...

Date post: 21-Feb-2018
Category:
Upload: phungphuc
View: 215 times
Download: 1 times
Share this document with a friend
36
Control System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit RS Boiler control panel
Transcript
Page 1: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

Control System THETAFor the heating specialist Operating and installation instructions

Standard unitRemote unit RSBoiler control panel

Page 2: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

2

Contents

General safety instructions ............................................................. 3

Safety measures for EMC - conform installation ........................... 3

Standard unit.................................................................................. 5Mounting ..............................................................................................................5Electrical installation ............................................................................................5Terminal assignment............................................................................................6

Boiler control panel ....................................................................... 7Mounting ..............................................................................................................7Electrical installation ............................................................................................7Terminal assignment............................................................................................8

Wall socket MS-K ........................................................................... 9Electrical installation .............................................................................................9Terminal assignment..........................................................................................10

Remote unit RS ............................................................................ 11Mounting location...............................................................................................11Mounting ............................................................................................................11Terminal assignment..........................................................................................12Electrical connections (control unit) ...................................................................12Data bus addressing ..........................................................................................12

Accessories.................................................................................. 14Outdoor sensor AF................................................................................................14Immersion sensor KVT..........................................................................................14Flow sensor VF.....................................................................................................15Resistance values of the sensor elements versus temperature ........................16

Starting up the control unit............................................................ 17Code-Input .........................................................................................................17

Automatic SET-Function ............................................................. 18

Malfunction messages................................................................. 19

Plant information.......................................................................... 20

Level synoptic .............................................................................. 24Synoptic of the specialist parameters and control options ...............................26

Page 3: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

3

General safety instructions All electrical connections and safetymeasures have to be carried out by aspecialist according to the valid normsand VDE-guidelines as well as the localinstructions.

The electrical connection must be fix (seeinstructions by VDE 0100).

The electrical connection has to be doneaccording to the wiring diagram of therespective boiler control panel.

Important! Switch off plant completely before opening boiler control panel. Do not plug or unplug electrical connectors under voltage. This may cause a defect to the control or a dangerous electrical shock.

Safety measures for EMC - conform installation 1. Cables with mains voltage must be

generally installed separately fromsensor and data bus cables. In thiscase a minimum distance of 2 cm mustbe observed. Crossing of lines ispermitted.

2. Controls with own mains connectionrequire a separate installation of mainsand sensor or data bus cable. Whenusing cable ducts such with internalseparators are recommended.

3. Installing control or remote units closeto other components with electromagnetic emission such as solid staterelays, motors, transformers, dimmers,micro wave ovens, TV-sets, loud-speakers, computers, radio telephonesetc. a minimum distance of 40 cmmust be observed.

4. Between remote units and standardunit a minimum distance of 40 cm hasto be observed. Several standard unitsmay be installed side by side.

5. The mains connection of the heatingplant (standard unit or boiler controlpanel) must be carried out as anindependent electric circuit. It is notpermitted to install fluorescent tubes orother machines that could produceinterferences to the same electricalcircuit.

Fig. 1: Minimum distance for cable installations

Mains 230 V~

Data bus cable 12 V~

2cm

Fuse 16 A

Emergency-switch

Install fluorescenttubes and plugs onseparated circuits.

Remote unit(s)

Heat generator

Fig. 3: Leading of electrical cables in the boiler room

40 cm

Fig. 2: Minimum distance to other electric supply

15 cm

Page 4: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

4

6. All data bus cables must be carried outin shielded version.Recommended cable:J-Y(St)Y 2 x 2 x 0.6

7. The shielding of the cable has to beconnected with earth potential, i.e. boilercovering, connecting terminals for earthpotential etc. Multiple grounding is notpermitted (humming loop).

In star shaped networks it is notpermitted to ground cables on bothsides. They should be grounded in thecentre.

8. The outside sensor may not beinstalled close to transmitter- orreceiver-equipment (on garage wallsclose to receivers for radio-controlledgarage door openers, ham operatorantennas, radio controlled alertsystems or close to big radiotransmission plants).

Cable dimensions and maximum cable length

For all 230V~ cables such as powersupply, burner, pumps, actuators: 1.5mm2

Maximum cable length:Unlimited cable length within houseinstallation

For all low voltage cables such assensors, extern selectors, bus andanalogue in- and outputs, heat requiringby means of extern contact, modemconnection cables, etc.: 0.5 mm2

Maximum cable length: 50 mLonger distances are possible butincrease the risk of interferences.

Data bus connections: 0.6 mm2

Recommended cable:J-Y(St)Y 2 x 2 x 0.6 mm2

Maximum cable length: 50 mLonger distances are possible butincrease the risk of interferences.

Fig. 5: Grounding in star shaped networks

Shielding

2-wire databus line

DistributionterminalDistribution box

Do not ground here!

Boiler

Fig. 4: Single grounding of shielding

Page 5: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

5

Standard unit

Mounting All standard units are designed exclusivelyas units for incorporation and will beinstalled from the front side into the boilerpanel after finishing the electrical wiring.The instrument is fastened by a quarterturn clockwise of the quick clampingdevices at the left and right side of thefront panel (1).Removal is done in opposite direction.

Electrical installation The electrical installation to the controlequipment is done at the back side of theinstrument via the four enclosedconnecting terminals X1, X2, X3 and X4corresponding to the identification on thecoloured-marked connection pads.

All blue marked connecting terminals (X1) work with safety low voltage and must not get into contact with the mains voltage. At non-observance the instrument will definitely be destroyed and any warranty gets lost.Red marked connecting terminals(X2...X4) principally may work with mainsvoltage according to the current operationconditions.For further information see documentationof the boiler manufacturer.

Electrical connection see next page.

Note:

Cables with mains voltage must beinstalled separate from low voltage cables(data bus, sensors etc.). It is strictlyprohibited to use one cable for bothvoltages. Sensor cables and data buscables may not be installed together withmains voltage cables supplying electricalappliance which are not suppressedaccording to EN 60555-2.

230 V~

11

Page 6: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

6

Terminal assignment

230 V~ Connections

1 – Floating exit for heat generator,output (stage 1)

2 – Floating exit for heat generator, input(stage 1)

3 – Pump for direct heating circuit4 – not connected, used for coding5 – Domestic hot water charging pump6 – L 1 / 230 V~7 – Mixing valve 1 OPEN8 – Mixing valve 1 CLOSED9 – Pump for mixed heating circuit 1

10 – Variable output 111 – Variable output 212 – L 1 / 230 V~13 – Mixing valve 2 OPEN14 – Mixing valve 2 CLOSED15 – Pump for mixed heating circuit 216 –17 – Floating exit for heat generator,

output (stage 2)18 – Floating exit for heat generator, input

(stage 2)19 – Operat. hours counter burner -

(stage 2)20 – Operat. hours counter burner -

(stage 1)21 – N / 230 V~22 – L 1 / 230 V~

Sensor and data bus connections

23 – Ground for data bus and sensors24 – Data bus signal A25 – Data bus signal B26 – Outdoor sensor27 – Sensor heat generator/boiler28 – Domestic hot water sensor29 – Flow sensor for mixed heating circuit 130 – Variable input 131 – Variable input 232 – Variable input 333 – Flow sensor for mixed heating circuit 234 – Solar panel flow sensor 1)

35 – Solar tank sensor36 – Pulse input37 – Heat generator-data bus A38 – Heat generator-data bus A

Mounting into boilersSee technical documentation of boilermanufacturer.

Wall mountingSee technical documentation »wallmounting set THETA WG«

1) Solar application only mains

Page 7: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

7

Boiler control panel

Mounting The boiler control panel is completelyprewired and will be mounted from thefront side into the panel cut-out of theboiler after finishing the electrical wiring.The panel is fastened with the fourenclosed screws.

Removal is done in opposite direction.

The sensor of the safety temperaturelimiter as well as the boiler sensor will beinserted into the sensor immersion pocketof the boiler.

Important: Do not crease or damage thecapillary tubing of the safetytemperature limiter.

For further information see documentationof the boiler manufacturer.

Accessories on demand

For easier installation optional swing-outaids can be ordered. These aids will besnapped into both left and right sides ofthe panel and prevent that the panel fallsdown when opening.

Electrical installation The electrical installation is done at theback side of the boiler control panel viathe plugged-in connection terminalscorresponding to the identification on thecoloured-marked connection pads.

Low voltage connecting terminals:

All blue marked connecting terminals work with safety low voltage and must not get into contact with the mains voltage. At non-observance the instrument will definitely be destroyed and any warranty gets lost.

Electrical connection see next page.

Mains voltage connecting terminals:

Red marked connecting terminalsprincipally may work with mains voltageaccording to the current operationconditions.

Electrical connection see next page.

Note:

Cables with mains voltage must beinstalled separate from low voltage cables(data bus, sensors etc.). It is strictlyprohibited to use one cable for bothvoltages. Sensor cables and data buscables may not be installed together withmains voltage cables supplying electricalappliance which are not suppressedaccording to EN 60555-2.

230 V~

230 V~

Page 8: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

8

Terminal assignment

230 V~ Connections

1 – Mains 230V~ +6/-10%, 50 Hz2 – Safety circuit 13 – Safety circuit 24 – Burner 1 (single step boilers)5 – Burner 2 (double step boilers)6 – Pump for direct heating circuit7 – Domestic hot water charging pump8 – Pump for mixed heating circuit 19 – Actuator mixing valve 1

10 – Pump for mixed heating circuit 211 – Actuator mixing valve 212 – Variable output 1

depending of programmation(see level HYDRAULIC)

13 – Variable output 2depending of programmation(see level HYDRAULIC)

Sensor and data bus connections

14 – Outdoor sensor15 – Sensor heat generator/boiler16 – Domestic hot water sensor17 – Flow sensor for mixed heating circuit 118 – Flow sensor for mixed heating circuit 219 – Variable input 120 – Variable input 221 – Variable input 322 – Solar panel flow sensor 1)

23 – Solar tank sensor 1)

24 – Pulse input25 – Data bus T2B26 – Data bus RS 485 2)

1) Solar application only2) high efficiency condensing boilers only

14 15 16 17 19 25 18 22 23 24 5 4 3 2 1

20 21 26 11 10 9 8 6 7 12 13

Page 9: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

9

Wall socket MS-K

Application:

The wall socket MS-K is used for wallmounting application of all types ofstandard units.

TypeThe wall-mounted connection base isintended for the sole purpose of housingthe standard unit.After plugging the standard unit into thewall socket and after finishing theelectrical wiring ready for start up.Electrical installation 1- Break out the impressed cable inlets

due to the required number and seizeon top side or lower side of the wallsocket according to the position of thecable channel.Note:Cable strain relief is prescribed if nocable duct is used.

2- Turn locking screws (1) horizontallyand pull off terminal cover to the side.

3- Fix wall socket on a flat backgroundusing enclosed screws and plugs. Usedrill pattern the enclosed

4- Electrical installation has to be carriedout according to plant and connectivityas shown on next page.

The connecting terminals of terminal blocks X5 and X6 at the left side work with safety low voltage and must not get into contact with the mains voltage. At non-observance the instrument will

definitely be destroyed and any warranty gets lost.

The connecting terminals of terminalblocks X7 to X10 principally may workwith mains voltage according to thecurrent operation conditions.The wall socket is equippedcompletely with screwless terminals.Press lever before inserting strippedwire into terminal.

5- Attach and clamp the side terminal-covers.

6- Insert standard unit with evenlydistributed pressure. The electricalconnection is done by plugging theinstrument into the terminals at thesocket print. Lock standard unit withboth quick clamping devices left andright.

Note:

Cables with mains voltage must beinstalled separate from low voltage cables(data bus, sensors etc.). It is strictlyprohibited to use one cable for bothvoltages. Use cable ducts equipped withseparators, if necessary.

230 V~

Page 10: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

10

Terminal assignment

230 V~ Connections

Sensor and data bus connections Burner connectionsT1 Control terminal stage 1T2 Control terminal stage 1B4 Op. hours counter burner stage 1B5 Op. hours counter burner stage 2T6 Control terminal stage 2T7 Control terminal stage 2T8 Control terminal stage 2

L1 Mains 230 V~ (live)N Mains 230 V~ (neutre)

Pumps and actuators HC Pump for direct heating circuitDHW Domestic hot water charging pumpMC1 Pump for mixed heating circuit 1MC2 Pump for mixed heating circuit 21 m v actuator mix. valve 1 (OPEN)1 m b actuator mix. valve 1 (CLOSE)2 m v actuator mix. valve 2 (OPEN)2 m b actuator mix. valve 2 (CLOSE)LVO1 Variable output 1 (live)LVO2 Variable output 2 (live)

N

N

N

N

N

N

N

N

N

N

N

N

N

X7 X8 X9 X10

1

2

T2

M

M

1

2

3

4

5

6

7

8

9

10

11 MC2

vb

LVO2

LVO1

MC1

vb

DHW

HC

L1(mains)

B4

B5

T6

T8

T7

T1 1

2

3

4

5

6

7

8

9

10

N (mains)

1

2

3

4

5

6

7

8

9

10

11

12

Variable input 1

Variable input 2

Heat generator

Outdoor

Pulse input

X5 X6

Solar tank

Solar panel flow

Flow mixing circuit 2

Variable input 3

Flow mixing circuit 1

1

2

3

4

5

6

7

8

9

10

11

12

Boiler – Data busA B

B -Data bus signal- A

Domestic hot water

Page 11: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

11

Remote unit RS

Mounting location

a – for applications without room sensorWithout room sensor function theremote unit may be fixed at any placein the interior range.

b – for applications with room sensorThe remote unit should be fixed at aheight of approx.1.20 – 1.50 m at aplace most representative of all rooms.It is recommended to chose an interiorwall of the coolest day room (such asentrance halls). In order to ensuresufficient air circulation at the roomstation, it must be mounted to the wallwith a gap inbetween.

The remote unit must not be mounted

– at locations exposed to direct sunlight(seasonal variations should be takeninto account)

– close to heat-producing appliances(televisions, refrigerators, wall lamps,radiators etc.)

– onto walls heated by under plasterheating pipes or chimneys.

– onto outside walls

– in corners behind curtains or shelves(due to insufficient ventilation)

– close to doors of unheated rooms (dueto the influence of low temperature)

– on unsealed under-plaster wiringboxes (influence of external lowtemperatures due to the chimneyeffect of installation tubes)

– in rooms with radiators controlled bythermostatic valves (mutual influence).

Mounting After removing the front panel by pressingthe locating lug at the lower side thesocket can be mounted at the desiredlocation using the enclosed dowel pinsand screws. The cable for the busconnection has to be led through the lowercut-out of the socket.Recommended connecting cable:

J-Y(ST)Y 2 x 2 x 0.6mm2 (2 wires free)

Maximum length: 50 m

Note:

For new installations use a under-plasterwiring box for perfect wiring.

Locating lug

Page 12: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

12

Terminal assignment The wiring between remote unit andstandard unit or boiler control panel has tobe made by a shielded data bus cable atterminals A and B of both units. Theconnecting terminals may not be changed and have to be installedaccording to the labelling of the terminalsA/B in the wall socket. Changing theterminals causes no displaying.

Socket (unit removed)

After completing the electrical wiring hangremote unit conclusively on top sideaccording figure on page 11 and turndown until it clicks into the wall socket. Electrical connections (control unit) See installation instructions of control unit.

Data bus addressing In order to guarantee a selectivecommunication between remote units andcontrol units it is necessary to set everyremote unit in the bi-directional data bussystem to the corresponding data busaddress.

This concerns in the same way thecoupling of control units for extension ofheating circuits, which communicate onthe same data bus line.

By this reason control units and remoteunits are equipped with data bus addresses.

Data bus address (control unit)

Single control units must always have theaddress 10. In heating plants with severalcontrol units (maximum 5) the maincontroller that works on the burner getsthe data bus address 10, the remainingcontrollers have to be set to addresses 20,30, 40 and 50 one after the next.

Adjustment of data bus address of the control unit To adjust the data bus address in thecontrol unit the corresponding specialistcode must be entered in the data bus levelfirst (see starting up the control unit).

Adjustment of data bus address of the remote unit

The assignment between the data busaddresses of the control units and remoteunits is to a fixed factory preset scheme inaccordance with the following table:

Page 13: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

13

Control unit Remote unit

FunctionDatabusaddress Heating circuit

Databusaddress

Basic controlunit

10Direct circ.(HC)MC 1MC 2

111213

1. add-on unit 20Direct circ.(HC)MC 1MC 2

212223

2. add-on unit 30Direct circ.(HC)MC 1MC 2

313233

3. add-on unit 40Direct circ.(HC)MC 1MC 2

414243

4. add-on unit 50Direct circ.(HC)MC 1MC 2

515253

Adjustment of data bus address in the remote unit A- First start-up

After completing the electrical installationand starting up the plant the completesegment character appears in the displayof the remote unit.

Following this, the desired language canbe be selected in accordance with thecountry code (D; GB, F, I resp. NL) andactivated.

Onto that the device identification anddata bus address is displayed:

After setting the data bus address bymeans of the rotary knob and confirmingby pressing the same once the number ofthe corresponding control unit appearsautomatically:

Important:

Double reservation of data bus addressesare not permissible and do leadautomatically to troubles in the datatransfer and to faulty control characteristicof the heating system.

B – Changing data bus addresses

A data bus address can be changedsubsequently as follows:

1 - Disconnect remote unit from data busline (by loosening plug-in connector atthe lower end)

2 - Plug-in connector again while pressingthe rotary knob until the addressadjustment appears in the display.

3 - Adjust new data bus address bymeans of the rotary knob and confirmby pressing the same once.

°C KWh Min %

°C KWh Min %

0 2 4 6 8 10 12 14 16 18 20 22 24

Segment character

Device identification Type of controlSoftware dateSoftware-Version

Language

Address adjustment (See table to the left)

Data bus address Direct heating circuitBasic control unit (1)

Page 14: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

14

Accessories Outdoor sensor AF

Mounting location

The outdoor sensor should be installed onthe most exposed and coldest side of thebuilding (north or north-west) so that itdoes not collect any direct sun lightparticularly in the morning.

Note: Chose the corresponding side ofbuilding due to the direction ofthe preferential living area.

Never mount sensor onto external heatsources such as chimneys, hot air from airshafts, sunlight or black undergrounds etc.since this will falsify the measured valuesconsiderably. The cable outlet must bedirected downwards in order to avoid theintrusion of moisture.

Electrical installation

1– Install sensor cable to the sensorlocation

2– Loosen lid screws and remove top3– Mount open sensor case with enclosed

central fixing screw. Use sealing ring!Cable outlet must be directeddownwards!

4– Insert sensor cable. The cableinsulation must be encircled by thesealing lips of cable entry.

5– Set up electrical connection. For theelectrical installation preferably a 2-core cable with at least sectional viewof 1 mm2 is recommended.

The connection is made at the screwterminal block inside the sensor caseand may be changed.

6– Put on lid again an and screw it firmlywith the case. Pay attention to correctseat of sealing ring.

Immersion sensor KVT

Options:

KVT 20/2/6 2 m cable lengthApplication: Boiler sensor, hot water

sensor (for boiler integratedhot water tanks), return flowsensor

KVT 20/5/6 5 m cable lengthApplication: Hot water sensor (for add-on

tanks, buffer tanks, solar collectorreturn flowsensoretc.

Mounting location:

In the immersion sleeve of the respectiveapplication.

Mounting into boilers or other heat sources

Bend clutch spring to sensor top andinsert sensor together with the capillarysensors of boiler thermostat (KTR), safetytemperature limiter (SLT) and boilerthermometer (KTA) into the immersionsleeve. Use spring clip if necessary.

Mounting into hot water or buffer tanks

Bend clutch spring to sensor top andinsert sensor according to the instructionsof the manufacturer into the dry immersionsleeve of the respective hot water tank.

Terminal assignment

Connect sensors at the correspondingterminals of the respective control unit(see terminal diagram). The terminals maybe changed.

Outdoor sensor AF 200

Page 15: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

15

Flow sensor VF

Feeding sensor VF…

Options:

VF 202 2 m cable lengthApplication: Contact sensor for mixer

controlled heating circuits ontoflow- or return pipes

VF 204 4 m cable lengthApplication: see VF 202

Mounting location:

Behind the mixer pump for mixed heatingcircuit in the minimum distance of 50 cm.

In case of use as return flow sensors:

Controlled flow temperature additionby means of mixing valve

Bypass circuit by means of a bypass pumpBoiler bypass pump

Mounting

Clean flow pipe thoroughly and putthermal conduction paste to pipe surface.

Attach sensor on the contact place in aflush way to the tube surface by means ofthe enclosed clamping band.

Pay attention to firm seat!

Terminal assignment

Connect sensors at the correspondingterminals of the respective control unit(see terminal diagram). The terminals maybe changed.Flue gas sensor / solar panel flow sensor

Options:

PT1000/6 2.5 m cable length

Application: Flue gas temperatureCollector flow temperature

Mounting location: – In the flue gas tube in the minimum

distance of the double tube diameter

– In the immersion sleeve of the solarcollector.

Mounting in the flue gas tube

Mount sensor clamp according toillustration below. Determine immersiondepth into the core flow of the flue gas andfix sensor.

Terminal assignment

Connect sensors at the correspondingterminals of the respective control unit(see terminal diagram). The terminals maybe changed.

2 ∅D

Flue gas tube

∅8mm

Boiler

Immersion sensor PT 1000/6

Return flowsensor

Return flowsensor

Fixing srewSensor clamp

Flue gas sensor

Page 16: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

16

Resistance values of the sensor elements versus temperature

Heat generator/boiler sensor KVT 20Outdoor sensor AF 200 DHW tank sensor/buffer sensor KVT 20

Feeding sensor VF 202/204Boiler sensor (solid fuel) KVT 20

T (°C) R (kΩ) )

T (°C) R (kΩ) )

- 20- 18- 16- 14- 12- 10- 8- 6- 4- 2± 0

2468

1012141618202530

1,3831,4081,4341,4591,4851,5111,5371,5631,5901,6171,6441,6711,6991,7271,7551,7831,8121,8401,8691,8981,9282,0022,078

101214161820253035404550556065707580859095

100

1,7831,8121,8401,8691,8981,9282,0022,0782,1552,2342,3142,3952,4782,5632,6482,7352,8242,9143,0053,0983,1923,287

Flue gas sensor, solar panel sensor

T (°C) R (kΩ) )

T (°C) R (kΩ) )

405060708090

100110120130140

1,1551,1941,2321,2711,3091,3471,3851,4231,4611,4981,536

150160170180190200210220230240250

1,5731,6111,6481,6851,7221,7581,7951,8321,8681,9051,941

Page 17: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

17

Starting up the control unit

Display test and device identification During the first switch-on of the controlunit or at return of voltage after powerfailure all available display segments willtemporary appear:

The desired language (D, GB, F, I) can beselected.

Language

Onto that device identification follows:

Provided that there is not any errormessage, the basic display with date, timeand current boiler temperature will appearin the display.

An active summer switch-off isrepresented by a sunshade symbol ().

With acting frost protection function an icecrystal symbol appears in the display ().

Code-Input

Specialist code

After entering the specialist code theparameters which are certain for theheating specialist are released and can beprocessed according to the heating plantdesign. To enter the specialist code the buttons and have to be pressed simul-taneously for approx. 3 seconds until therequest to enter the code will bedisplayed.

+

Every flashing digit can be modified withthe rotary knob according to the codenumber and confirmed by pressing theknob once. The further digits are treated insame way.

After entering all digits correctly andconfirming the last digit the specialist codeis accepted by displaying INSTALLER OK,with wrong entry the message CODE ERROR will appear.

The factory preset code for the specialistis

Note: Contact boiler manufacturer ifthe factory preset specialistcode is not accepted!

Important: Released parameters arelocked again if for the durationof no further service occurs. Inthis case the specialist codemust be entered again.

Segment character

Device type

Type code and versionnumber

Basic Display Date: Mon. Aug. 22, 2005Time: 16.32Temp. 40.5°C

Summer switch-off active

Frost protection active

°C

°C

0 2 4 6 8 10 12 14 16 18 20 22 24

°C KWh Min %

°C KWh Min %

0 2 4 6 8 10 12 14 16 18 20 22 24

°C

1 2 3 4

Page 18: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

18

Automatic SET-Function This function allows to remove heating orhot water circuits from operation.

The control circuits are registratedautomatically, if their correspondingsensors are connected and provideacceptable measuring values. Controlcircuits without the corresponding sensorsremain automatically withoutconsideration.

The automatic set function will beactivated after every switch-on.

Automatical activation

Provided that the auto-set function isturned on (see SYSTEM-Level –parameter 14) and the initial start-up datewas not yet stored, connected ordisconnected sensors will be registeredautomatically at every switch-on of thecontrol unit. During this time errormessages of sensors (short circuit orinterruption) will be suppressed.

After the initial start-up date was stored, amodified sensor configuration can only betaken over by manual activation.

Manual activation

The auto-set function can be activated tooat any time manually by keeping the rotaryknob pressed when switching the unit on,until the auto set function is accepted inthe display.

The auto set function registers thefollowing sensors:– Outdoor sensor– Flow sensor 1– Flow sensor 2– Hot water tank sensor– Heat generator /boiler sensor

Furthermore the auto set function iscarried out only, if the control circuitswhich are assigned to the correspondingsensors were parameterised in therespective levels.

For the hot water sensor: HYDRAULIC Level

Parameter 2 - Function DHW charging pumpSetting range OFF or 1 (DHW chargingpump)

For the supply sensor 1: HYDRAULIC Level

Parameter 3 - Function mix. heating circuit 1Setting range OFF or 3 (mix. heatingcircuit)

For the supply sensor 2: HYDRAULIC Level

Parameter 4 - Function mix. heating circuit 2Setting range OFF or 3 (mix. heatingcircuit)

For the boiler sensor: Level HEAT GENERATOR Parameter 1 – Type of heat generatorSetting range OFF or 1 (1-stage-burner)

With that a programmed parameterisationwill not be changed again, the currentvalues will be checked before. Amodification is carried out only if one ofthe adjustments listed above is given. Inthis way the auto set function for examplenever can cancel a return flow increase ofmixer heating circuit 2, or can function it toa mixer heating circuit.

Basic Display

Page 19: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

19

Malfunction messages In order to set up a precise diagnosis inthe case of malfunction the control systemis equipped with an extensive malfunctionmessage system. An occurring error isalways announced in the display of thecorresponding basic control and stored.

There are five different categories ofmalfunction messages:

1 - Sensor alarm messages Sensor values which are not in theirrespective measuring range will either besensor breaks or sensor short circuits.They appear with an error messageaccording to their use.

2 - Boiler alarm messages This messages depend on the actualswitching conditions. They appear with thecorresponding error message, dependingon the version and allocation.

3 - Logical alarm messages These messages will react on the actualcontrol result. They appear with thecorresponding error message, dependingon the version and allocation.

4 - Bus alarm messages These messages display addressproblems such as double addresses or notrecognizing addresses within the data bussystem. They appear with thecorresponding error message, dependingon the version and allocation.

5 - Alarm messages from boiler control (high efficiency condensing boilers)These fault messages come of the boilercontrol and are divided into permanentfaults (permanent lock) with error code E-XX (MCBA-code) or temporary faults (selfcancelling lock) with error code B-XX(MCBA-code).

The displaying characters and furtherprocessing of the logical faults can beenabled or suppressed by acorresponding parameterization (seeSYSTEM level-parameter 13 (logical errormessage).

Further processing in case of malfunction messages: – Alarms will be indicated in the basic display

of the control unit

– System errors appear in the informationlevel beside the corresponding information

– Malfunction messages are loaded into amalfunction message log (see descriptionbelow)

– Malfunction messages activate in case ofcorresponding parameterisation an alarmoutput for optical or audible signallers.

– Malfunction messages are transmitted viadata bus to corresponding gateways.

Table of malfunction messages:

Sensors and variable inputs:

Designation Alarm cause Code

Outdoor sensor break 10-0Outdoor sensor short circuit 10-1Boiler sensor break 11-0

Boiler sensor short circuit 11-1Flow sensor 1 break 12-0Flow sensor 1 short circuit 12-1

DHW sensor break 13-0DHW sensor short circuit 13-1Variable input 2 break 14-0

Variable input 2 short circuit 14-1Variable input 2 alarm 14-7Variable input 3 break 15-0

Variable input 3 short circuit 15-1Variable input 3 alarm 15-7Variable input 1 break 16-0

Variable input 1 short circuit 16-1Variable input 1 alarm 16-7Sol.panel/buffer break 17-0

Sol.panel/buffer short circuit 17-1

Page 20: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

20

Designation Alarm cause Code

Flow sensor 2 break 18-0Flow sensor 2 short circuit 18-1Solar panel sensor break 19-0

Solar panel sensor short circuit 19-1

Heat generator: Burner 1 not OFF 30-2

Burner 1 not ON 30-3Burner 2 not OFF 31-2Burner 2 not ON 31-3Heat quantitymeter

no impulse 32-3

Flue gas exceeded 33-5Flue gas STL triggered 33-8

Temperatures: Heat generator not reached 50-4

Heat generator exceeded 50-5DHW not reached 51-4Flow mixer circuit 1 not reached 52-4

Flow mixer circuit 2 not reached 53-4

Room HC not reached 54-4

Room-mix. circuit 1 not reached 55-4Room-mix. circuit 2 not reached 56-4

Data bus errors Address case of collision 70-0

Activity no T2B-signal 70-1EEPROM 71-0EEPROM defect 71-1

Condensing boiler control error (MCBA) Malfunction locking EnX

Malfunction blocking BnX

Malfunction log

The control unit has a malfunction log inwhich a maximum of five malfunctionmessages can be saved. The malfunctionmessages are displayed with date, timeand malfunction type (error number). Thequery is carried out in the sequence of theentered malfunction messages in the levelALARM.

The last (= most recent) malfunctionmessage is in first position (No. 01); theprevious malfunction messages areshifted down by a position upon each newmalfunction message. The fifthmalfunction message is deleted when anew message appears.

Malfunction messages from condensing boiler controls (MCBA) represent a specialfeature. They will not be stored into theinternal malfunction log because they areexternal errors.

Plant information Plant and system temperatures

After entering of the information level bymeans of the information key a queryof all available plant and systemtemperatures can be made using therotary pushbutton.

Provided that in the following table underthe column Display Value a nominalvalue is listed, it will appear when pressingthe rotary push-button.

The following information appear onlyunder the indicated display conditions.Some displays are not available and areskipped according to the respective typeof control.

Page 21: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

21

Information Displayed value Remarks Application

Outdoor temp. (1) Average value /current value

Outside sensor connected

Outdoor temp. (1) Min-max-valuefrom 0.00 to 24.00 h) Outside sensor connected

Outdoor temp. 2 Average value /current value Outdoor sensor 2 at var. input

Outdoor temp. 2 Min-max-valuefrom 0.00 to 24.00 h) Outdoor sensor 2 at var. input

Heat generator (1) Nominal/actual value Only if heat generator is defined (..2..)

Heat generator 2 Nominal/actual value Sensor BS 2 at variable input (..2..)

Return flow(b. contr.) Actual value Return flow sensor connected at

boiler control (..C..)

Flue gas (b. contr.) Actual value Flue gas sensor connceted atboiler control (..C..)

Return flow Nominal/actual value Return flow sensor at var. input andreturn temp. increasing activated

External blocking Block modeON, OFF

Ext. blocking at variable input

Flue gas Limit value/actual value

Flue gas sensor at variable input (..2..)

Hot water tank (1) Nominal/actual value Only with hot water tank (..B..)

Hot water tank 2 Nominal/actual value Hot water sensor 2 at var. input (..B..)

Hot waterthermostat

Charging statusON/OFF Instead of an electronic sensor (..B..)

Heat requirementvia contact (VI-1)

RequirementON/OFF

Switching contact at variableinput

Heat requirementvia contact (VI-2)

RequirementON/OFF

Switching contact at variableinput

Heat requirementvia contact (VI-3)

RequirementON/OFF

Switching contact at variableinput

FlowMixed circuit 1

Nominal/actual value Flow sensor mix. heating circuit1 connected

(..3..)

FlowMixed circuit 2 Nominal/actual value Flow sensor mix. heating circuit

2 connected (..33..)

Ambient temper.Direct heat. circuit Nominal/actual value Remote control necessary (..2..)

Ambient temper.Mix. heat. circuit 1 Nominal/actual value Remote control necessary (..3..)

Page 22: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

22

Ambient temper.Mix. heat. circuit 2 Nominal/actual value Remote control necessary (..33..)

Thermostat functionDirect heat. circuit THERMOSTAT DC Room thermostat function activated

OFF = no room temperature limit (..2..)

Thermostat functionMixed circuit 1 THERMOSTAT MC1 Room thermostat function activated

OFF = no room temperature limit (..3..)

Thermostat functionMixed circuit 2 THERMOSTAT MC2 Room thermostat function activated

OFF = no room temperature limit (..33..)

Solid fuel boilerupper buffer sensor

Actual valueNominal/actual value

Solid fuel charging pump at var. outputBuffer charging pump at var. output

(Type ..VV..)(Type ..VV..)

Lower buffer sensorSolar panel sensor

Nominal/actual valueActual value

Buffer sensor 2 at variable inputSolar pump at variable output

(Type ..VV..)(Type ..VV..)

Solar tank Actual value Solar pump at variable output (Type ..VV..)

Solar panel returnflow sensor Actual value Solar pump at variable output

Return flow sensor at var. input (Type ..VV..)

Operating states

After entering the information level bymeans of the information key allavailable operating states and usage datasuch as counter readings, specified

performance data etc. can be requestedafter each other by turning the rotarypush-button anti-clockwise.

Information Display (Example) Function Application

Statusdirect circuit

AUTO-P1 ECO HC ON

Operating mode / 3-program/modestatus of heating pump

(..2..)

StatusMixed circuit 1

AUTO-P1 ECO MC1 ON

Operating mode / 3-program/modestatus of heating pump

(..3..)

Status actuatorMix. valve-1

MIX. VALVE-1 OPEN

Display of directionOPEN-STOP-CLOSE

(..3..)

StatusMixed circuit 2

AUTO-P1 ECO MC2 ON

Operating mode / 3-program/modestatus of heating pump

(..33..)

Status actuatorMix. valve-2

MIX. VALVE-2 STOP

Display of directionOPEN-STOP-CLOSE (..33..)

Status heat gener.stage 1

HEAT GENER. ON

Switching state of heat generatorSingle stage or stage 1 (2-stage) (..2..)

Status heat gener.stage 2

HEAT GENER. ST-2 OFF

Switching state of heat generatorStage 2 (..22..)

Status modulatingheat gener.

MODULATION 57% 60%

Modulating single stage heat gene-rator, nominal and actual value (Type ..VV..)

StatusDHW circuit

AUTO-P1 ECO DHW ON

Operating mode / 3-program/modestatus of DHW charging pump

(..B..)

Function & statusDirect circuit pump

OUTPUT HC-P EO ON

Information about the assignedfunction and switching state of pump (..2..)

Page 23: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

23

Function & statusVariable output 1

OUTPUT VO-1 SOP OFF

Informationabout theassigned functionandswitchingstateofvar.output1 (Type ..VV..)

Function & statusVariable output 2

OUTPUT VO-2 SOP OFF

Informationabout theassigned functionandswitchingstateofvar.output1 (Type ..VV..)

Activationsheat generator (St.1)

NR OF STARTS 1234 (ST-1)

Accumulated number of startsSingle stage or stage 1 (2-stage)

(..2..,..22..)

Operating hoursheat generator (St.1)

OPER. HOURS 246

Accumulated operating hoursSingle stage or stage 1 (2-stage) (..3..)

Activationsheat generator St. 2

NR OF STARTS 268

Accumulated number of startsStage 2 (..3..)

Operating hoursheat generator St. 2

OPER. HOURS 45 ST-2

Accumulated operating hoursStage 2 (..33..)

Test temp. sensorfor test purpose

INFO-TEMP. 50°C

Ext. sensor for test purpose atvariable input (..33..)

Operating modeext. modem control

MODEM AUTO

Actual operating mode of externalmodem at variable input (..2..)

Actual solar power HEAT POWER 43 KW SOL

Act. power of the solar systemin kW

(Type ..VV..)

Solar energybalance

HEAT CONS. 2468 KWh SOL

Accumulated thermal capacityof the solar system in kWh (Type ..VV..)

Activationssolar panel pump

NR OF STARTS 296 SOL

Accumulated number of starts ofthe solar panel pump (Type ..VV..)

Operating hourssolar panel pump

OPER. HOURS 478 SOL

Accumulated operating hoursof the solar panel pump (Type ..VV..)

Application:

(..2..) 1-stage heat generator(..22..) 2-stage heat generator(..3..) with 1 mixing circuit(..33..) with 2 mixing circuits(..B..) DHW circuit(..VV..) with 2 variable outputs(C, OT) high efficiency condensing boilers

Page 24: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

24

Level synoptic Entry into the level selection: Hold rotary push-button pressed for approx. 3 seconds - automatic call of time programs

Select required level via rotary push-button and confirm, enter code if necessary Programming Configuration Parameterization (Heating circuits, controlled systems)

Par

amet

er N

r.

Tim

e-D

ate

Tim

e p

rog

ram

s

Hyd

rau

lic

Sys

tem

-p

aram

eter

s

DH

W

(..B

..)

Unm

ixed

circ

. H

C

(..2

..)

Mix

ed c

ircui

t 1

MC

1 (.

.3..)

Mix

ed c

ircui

t 2

MC

2 (.

.33.

)

Hea

t g

ener

ato

r (.

.2..,

..22

..)

1Time

(Min/hrs)Hydraulicdiagram Language

ECO DHWtemperature Reduced mode Reduced mode Reduced mode Type H-Gen

2 Year Output SOL-PEnable timeprograms

Legion.prot.(day)

Heating system(exponent)

Heating system(exponent)

Heating system(exponent)

Start-upprotection

3Day-

MonthOutput MC1 Control mode

Legion.prot.(time)

Enable roominfluence

Enable roominfluence

Enable roominfluence

Heat generatormini.temp.limit

4Change

Su-Wi-time Output MC1Summerswitch-off

Legion.prot.(temp.) Room factor Room factor Room factor

Maximumtemp. limit

5 Output HCSystem frostprotection

DHW sensortype

Adaptationheat. charact.

Adaptationheat. charact.

Adaptationheat. charact.

Minimum temp.limiting mode

6

seeprogramming

of time-programs

Output VO-1Heat requiringcontact VI-1

DHW max.temp. limit

Switch-onoptimization

Switch-onoptimization

Switch-onoptimization

Heat generatorsensor mode

7 Output VO-2Heat requiringcontact VI-2

DHW operat.mode Heating limit Heating limit Heating limit

Minimumburner run time

8 Input VI-1Heat requiringcontact VI-3

Dischargeprotection

Roomfrostprotection limit

Roomfrostprotection limit

Roomfrostprotection limit

Burner switch.differential I

9 Input VI-2 Climate zoneTemperatureparallel shift

Roomthermostatfunction

Roomthermostatfunction

Roomthermostatfunction

Burner switch.differential II

10 Input VI-3Type ofbuilding

DHW switchingdifferential

Outdoor sensorassignment

Outdoor sensorassignment

Outdoor sensorassignment

Time delaystage II

11Indirect raisingof return flow

Time forautom. exit

Ext. run timeSOL-P

Constant temp.setpoint

Constant temp.setpoint

Constant temp.setpoint

Enablingmode stage II

12Anti blocking

protectionTime program

CIR.Minim. temp.

limit HCMinim. temp.

limit HCMinim. temp.

limit HCDHW chargingmode stage II

13 Logical alarmsEcon. intervalCIR. (break)

Maxim. temp.limit HC

Maxim. temp.limit HC

Maxim. temp.limit HC

Pre-run timeboilerpump

14Automatic Set -

FunctionEcon. interval

CIR. (period)Heat generator

parallel shiftHeat generator

parallel shiftHeat generator

parallel shiftExtendedrun

timeboilerpump

15Extended

pump run timeExtended

pump run timeExtended

pump run timeExt. run timefeed pump

16Compos. floordrying function

Compos. floordrying function

Compos. floordrying function

Flue gas temp.monitoring

17Return flowmax.

temp. limitReturn flowmax.

temp. limitFlue gas

temp. limit

18Release cycle

temp.

19Frost protection

mode

20

21

22

23Locking codefor user level

Room controlP-range

Room controlP-range

Room controlP-range

24Scaling accord.to Fahrenheit

RoomcontrolAdaptation time

RoomcontrolAdaptation time

RoomcontrolAdaptation time

25Outdoor temp.locking stage II

26Basic load

parallel shift

27HC mini temp.

limit

28Diff. Min. lim.

HC

29H-GEN forced

discharge

36Resetstage I

37Reset to

factory presetResetstage II

Page 25: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

25

Parameters without background colour: accessible to the userParameters with grey background: Installer parameter, only accessible with correct installer code.

Parameterization Communic. Service

Ret

urn

flo

w

tem

per

atu

re

rais

ing

So

lar

(Typ

e ..V

V..)

So

lid f

uel

(

Typ

e ..V

V..)

Bu

ffer

(

Typ

e ..V

V..)

Cas

cad

e co

ntr

ol

Dat

a b

us

Rel

ay t

est

Mal

fun

ctio

n

Sen

sor

calib

rati

on

Par

amet

er

Nr.

Return temp.setpoint

Switch-on differ.collector-buffer

Minimumtemp. limit

Minimumtemp. limit

Switchingdifferential

Bus addressBasic unit

Heatgenerator.

Malfunctionmessage 1

Type 1

Switch-offdifferential

Switch-off differ.collector-buffer

Maximumtemp. limit

Maximumtemp. limit

Time delayascend. seq.

Bus accessRS HC

Heat. pump(HC)

Malfunctionmessage 2

Outdoorsensor

2

Extendedpump run time

Min. run timesolar pump

Switch-on differ.boiler-buffer

Heat generatorparallel shift

Time delaydescend. seq.

Bus accessRS MC1

Heat. pumpMC 1

Malfunctionmessage 3 Boiler sensor 3

Max. solarpanel temp.

Switch-off diff.boiler-buffer

Switchingdifferential

Sequentialswitch-over pwr.

Bus accessRS MC2

ActuatorMix.valve 1

Malfunctionmessage 4

DHW tanksensor

4

Max. buffertemperature

Inhibition heatgenerator

Forced heatdissipation

Reverse boilersequence

Heat. pumpMC 2

Malfunctionmessage 5

Flow sensorMC1

5

Solar operatingmode

Drain functionSwitch-on differ. Leading stage

ActuatorMix.valve 2

Flow sensorMC2 6

Inhibition heatgenerator

Drain functionSwitch-off differ.

Peak loadboiler

DHWcharging pump

Solar panelsensor 7

Change priority/parallel mode

Buffer start-upprotection

changeover Output VO-1 Buffer sensor 8

Solar energybalance

Buffer dischargeprotection

Output VO-2 Senosr VI-1 9

Reset sol.energy balance

Buffer operatingmode

Senosr VI-2 10

Volume flowsolar fluid

Sensor VI-3 11

Fluid density 12

Fluid heatcapacity

13

Final switch-offtemperature 14

Test cyclesol.load.sw. 15

Change overtemperature 16

17

18

19

20

21

22

23

24

25

26

27

28

29

36

37

Page 26: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

26

Synoptic of the specialist parameters and control options

HYDRAULIC Level The parameters of this level refer to the general hydraulic system of the heating plant aswell as to the functionality and configuration of the programmable inputs and outputs forthe corresponding plant components.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

01 Hydraulic diagram 0000, .... 9999 0

02 DHW charging pump output(Type ..B..)

OFF No function1 DHW charging pump4 DHW circulation pump5 DHW electrical heating element

1

03 Mixing circuit 1 (MC1) output(Type ..3..)

OFF No function2 Direct circuit (outdoor temp. contr.)3 Mixing circuit (outdoor temp. contr.)6 Constant temp. contr.7 Fixed value contr.8 Raising return temp.

3

04 Mixing circuit 2 (MC1) output(Type ..33..) Setting range and assignment see parameter 03 3

05 Direct circuit 1 (HC) output

OFF No function2 Direct circuit pump4 DHW circulation pump5 DHW electrical heating element6 Constant temperature control10 Feed pump11 Boiler circuit pump 112 Boiler circuit pump 213 Alarm output14 Timer15 Solar charging pump (Type ..VV..)21 Parall. H-GEN-clearance (..VV..)27 Hydraulic buffer release (..VV..)

2

06 Variable output 1(Type ..VV..)

OFF No function4 DHW circulation pump5 DHW electrical heating element9 Boiler bypass pump10 Feed pump11 Boiler circuit pump 112 Boiler circuit pump 213 Alarm output15 Solar charging pump16 Buffer charging pump17 Solid fuel boiler pump19 Solar change over charging valve20 Solar forced heat removal21 Parall. H-GEN-clearance (..VV..)26 Primary pump27 Hydraulic buffer release (..VV..)

OFF

07 Variable output 2(Type ..VV..)

Setting range and assignment see parameter06 OFF

08 Variable input 1

OFF No function1 Outdoor sensor 22 Boiler sensor 23 DHW tank sensor 24 Buffer sensor 25 Heat requirement contact6 External alarm input7 Return flow max. temp. limit (MC1)8 Return flow max. temp. limit (MC2)9 Return sensor (bypass pump)10 External blocking (heat generator)11 External switching modem

Page 27: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

27

08 Variable input 1

12 External information13 Common flow sensor14 Solar panel return sensor16 Flue gas sensor17 Boiler sensor (solid fuel)18 Solid fuel buffer sensor19 Buffer sensor 127 Minimum value intrusion

OFF

09Variable input 2(Type ..VV..)

Setting range and assignment see parameter08 without parameter 16 (flue gas sensor) OFF

10Variable input 3(Type ..VV..)

Setting range and assignment see parameter08 without parameter 16 (flue gas sensor) OFF

11 Indirect raising of returntemperature via mixing valve

OFF, ON (only Type ..3.., ..33..) OFF

SYSTEM Level The parameters in this level refer to the general limiting parameters and setting values inthe heating system to be used.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

LANGUAGE Language selection

D GermanGB EnglishF FrenchI Italian

D

TIMEPROGRAM

Number of enabled timeprograms

P1 Only one time program enabledP1-P3 Three time programs enabled P1

CONTROLMODE

Enabling of separate controlmode setting (room temp.specific. and operat. modes)

1 Common setting for all heatingcircuits

2 Individual setting for every heatingcircuit

1

SUMMER OFF no function10-30 °C switch-off at set value

20 °C

05 System frost protectiontemperature

OFF no function-20...+10 °C frost protection at set value 3 °C

06 Heat requiring contact at VI-1

1 Direct circuit (HC)2 Mixed circuit 13 Mixed circuit 24 DHWALL All circuits

1

07 Heat requiring contact at VI-2(Type .. (Type ..VV..) Settings see parameter 06 1

08 Heat requiring contact at VI-2(Type .. (Type ..VV..) Settings see parameter 06 1

09 Climate zone -20…0 °C -12 °C

10 Type of building1 light construction2 medium construction3 heavy construction

2

11 Time for automatic exit(return to basic display)

OFF No automatic return0.5…5 min Automatic return to the basic

display according to the set time2 Min

12Pump and mix valve forcedoperation (Anti-blockingprotection)

ON activeOFF not active ON

13 Logical malfunctionmessages

OFF no displayON Display active OFF

14 Automatic SET-Function OFF automat. sensor recognition deactivatedON automat. sensor recognition activated OFF

Page 28: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

28

18 Release cycle temperature OFF cycle temperatures blockedON cycle temperatures released ON

19 Frost protection mode

OFF permafrost protection according toadjustment in parameter 05- plantfrost protection

0.5...60 min cyclic operation

OFF

23 Anti-blocking for protection OFF (0000) no blockON (0001...9999) block OFF

24 Temperature display in°Fahrenheit

OFF display in °C and KON display in °F OFF

RESET Reset to factory preset in dependence on access code only toreleased parameters

DOMESTIC HOT WATER (Type ..B..) Level This level comprises all parameters which are necessary to program the DHW circuit withthe exception of the operating time programs.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

DHW NIGHT Hot water economytemperature 10 °C ... Hot water temperature 40 °C

LEGION.PROT. DAY Day for legionella protection

OFF No legionella protectionMo...Su Legionella protection on the

specified dayALL Legionella protection every weekday

OFF

03 Time for legionella protection 00:00...23:50 hour 02:00

04 Temperature for legionellaprotection 10 °C ... DHW maximum temperature 65 °C

05Type of DHW temperaturemeasurement

1 electronic temperature sensor2 mechanical thermostat

1

06 DHW- temperature limit 20 °C ... maximum boiler temperature 65 °C

07 DHW operating mode

1 parallel mode2 Priority mode3 Conditional priority4 Weather responsive parallel mode5 Priority mode with intermediate

heating6 Priority-separation circuit7 External operation

2

08 DHW tank dischargeprotection

OFF No discharge protectionON Discharge protection activated

ON

09 Boiler parallel shift duringDHW charging

0 ... 50 K;Difference between the DHW chargingtemperature and DHW setpoint

15 K

10 DHW switching differential2 ... 20 K;Amount of DHW switching differential,symmetrical to the DHW setpoint

5 K

11 DHW charging pumpExtended running time

0 ... 60 Min 5 Min

12 Time programm circulationpump

AUTO - Active DHW time program1 - P1, direct heating circuit2 - P2, direct heating circuit3 - P3, direct heating circuit4 - P1, mixing circuit 15 - P2, mixing circuit 1

AUTO

Page 29: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

29

12 Time programm circulationpump

6 - P3, mixing circuit 17 - P1, mixing circuit 28 - P2, mixing circuit 29 - P3, mixing circuit 210 - P1, DHW circuit11 - P2, DHW circuit12 - P3, DHW circuit

AUTO

13 Economy intervall - cir. pump(no pulse period)

0 Min ... setpoint of parameter 14;time of circulation pump stop

5 Min

14Economy intervall - cir. pump(Period duration)

10... 60 MinDuration = shutdown time + operating time

20 Min

Level DIRECT CIRCUIT (2.., 22..) MIXING CIRCUIT 1 (..3.. ) MIXING CIRCUIT 2 (..33..) This level contains all necessary parameters for the programming of the direct (unmixed)and/or the mixed heating circuits with the exception of the operating times programs.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

RED.HEATING Type of reduced mode ECO - Switch-off mode (frost protection)

ABS - Reduced modeECO

HEAT.SYSTEM Heating system (exponent) 1,00 ... 10,00

HC =1,30 MC =1,10

03Room influence (with roomunit )

OFF Room sensor deactivated1 Room sensor enabled2 Room sensor enabled, operation

of room control unit blocked3 only display mode (room temp.)

OFF

04 Room factor OFF, 10 ... 500 %, RC (only room control) OFF

05 Adaptation heating curve OFF, ON OFF

06 Optimmization (start) OFF, 1 ... 8 h OFF

07 Heating limit OFF, 0.5 … 40 K OFF

08 Room frost protection limit 5 ... 30 °C 10 °C

09 Room thermostat function OFF, 0,5 ... 5 K OFF

10 Outdoor sensor assignment(only if VI n = out.sensor 2)

0 Control to mean value of OS 1 + OS 21 Control to OS 1 only2 Control to OS 2 only

0

11 Constant temperaturesetpoint

10... 95 °C only if output is set at constantcontrol (CC) 20 °C

12Minimum flow temperaturelimit

10 °C ... Maximum temperature limit(Parameter 13) 20 °C

13 Maximum temperature limit Minimum temperature limit(Parameter 12) ... 95 °C 75 °C

14 Heating circuit parallel shift -5 ... 20 K HC=0 MC=4

15 Heating pump (MC1, MC2)extended running time 0 ... 60 Min 5 Min

Page 30: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

30

16Screed function (profile drying)(only if the circuit is enabledexclusively)

OFF Function switched off1 Function heating2 Occupation suitable heating3 Function and occupation suitable

heating

OFF

HEAT GENERATOR LEVEL (2..., 22...) The parameters in this level refer to the type of the relevant heat generator and to thecorresponding specific control functions.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

01 Heat generator type

OFF without heat generator1 Oil/Gas 1 stage (..2..)2 Oil/Gas 2 stage (..22..)3 Oil/Gas 2 x 1 stage (..22..)4 variable burner5 High efficiency condensing boiler

(..C../..OT..)

1

02 Start-up protection

OFF no start-up protection1 Start-up protection on minim. temp.

limit2 Start-up protection on outdoor

reference3 Start up protection separated

1

03 Heat generator minimumtemperature limit 5 °C ... Maximum temperature limit 38 °C

04 Heat generator maximumtemperature limit

Minimum temperature limit ... Set limitmaximum temperature limit H-GEN 80 °C

05 Heat generator minimumtemperature limiting mode

1 Minimum temperature limit at heatrequirement

2 Restricted minimum temp. limit3 Permanent minimum temp. limit

1

06 Heat generator sensor mode

1 Burner switch off in case of defect2 External Burner switch off3 Burner enabling in case of defect

!!! !!!Consider warnings!!!

1

07 Minimum burner run time 0 ... 20 Min 2 Min

08 Burner switching differential I(SD I)

1-stage: 2 ... 30 K2-stage: 2 ... (SDII - 0,5K) 6 K

09 Burner switching differential II(SD II) (..22..) (SD I + 0,5 K) ... 30 K 8 K

10 Time delay stage 2 (..22..) 0 ... 60 min (0 = 10 Sec) 0

11 Enabling mode stage II (..22..)1 Unlimited enabling during start-up

release2 Time out during start-up release

2

12 DHW charging mode stage1/2 (..22..)

1 DHW charging with delayedenabling of stage 2

2 unlimited DHW charging stage 23 DHW charging with stage 1 only

1

13 Pre-run time boiler circ. pump/parall. het gener. release

0 ... 10 Min 2 Min

14 Extended run time boiler circuitpump 0 ... 60 Min 2 Min

15 Extended run time feed pumpor primary pump 0 ... 60 Min 2 Min

Page 31: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

31

16 Flue gas temperaturemonitoring

OFF displays only flue gas temperature0 … 60 min Heat generator blockage in case

of exceeding limit for the set timeSLT Heat generator blockage in case

of exceeding limit

OFF

17 Flue gas temperature limit 50 ... 500 °C 200°C

25 Outdoor temp. locking OFF, -20…+30 °C OFF

26Basic load parallel shift (only

when used incascade mode)

0…60 K 10 K

27 Heat circuits minimumtemperature limit

5 °C...KTmin (only if start up release isseparated - Parameter 02 = 3)

36 °C

28Switching differentialHeat circuits minimumtemperature limit

2 K...20 K (only if start up release isseparated - Parameter 02 = 3)

4 K

29 H-GEN forced discharge

OFF no function1 Into DHW tank

2 Into heating circuits3 Discharge in buffer tank

OFF

RESETST-1

Resetoper. hours / starts stage 1 SET -

RESETST-2

Resetoper. hours / starts stage 2 SET -

RAISING RETURN TEMPERATURE Level The parameters in this level refer to the special settings to increase the return temperatureof heat generators. Enabling occurs only following activation in the HYDRAULIC level

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

01 Return flow limiting setpoint 10 ... 95 °C 20 °C 02 Switch-off differential 1 ... 20 K 2 K

03 Extended run time (pump) 0 ... 60 Min 1 Min

SOLAR Level (..VV..) The parameters in this level refer to the special settings for solar energy application.Enabling occurs only following activation in the HYDRAULIC level.

Parameter Designation Setting range / Setting values

Fact

ory

pres

et

Ind

ivid

ual

se

ttin

g

01 Switch-on differential (Switch-off differential +3 K) ... 30 K 10 K

02 Switch-off differential 2 K ... (Switch-on differential -3 K) 5 K

03 Minimum run time of solarpanel pump

0 ... 60 Min 3 Min

04 Maximum temperature limitof solar panel

90 ... 250 °C 120 °C

05 Maximum temperature limitsolar buffer

50 ... 110 °C 75 °C

06 Solar operating mode1 Priority mode2 parallel mode

2

Page 32: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

32

07 Inhibition heat generator OFF, 0,5 … 24 h(Only in priority mode - Parameter 6 = 1)

OFF

08 Change priority/parallelmode

OFF, 1 … 40 K(only in priority mode and act. cyclic block)

OFF

09 Solar energy balanceOFF No accounting1 Accounting via flow calculation2 Accounting via pulse processing

OFF

RESET SOLAR Reset solar energy balanceReset: SET by pushing the rotary push-

button(only if solar heat balance is enabled)

-

11 Volume flow 0,0 ... 30 l/Min or liter/impulse(only if solar heat balance is enabled)

0,0 l/Min

12 Fluid density 0,8 ... 1,2 kg/l(only if solar heat balance is enabled)

1,05 kg/l

13 Fluid heat capacity 2,0 ... 5,0 KJ/kgK (only if solar heat balanceis enabled)

3,6 KJ/kgK

14 Final switch-off temperature OFF, 90… 210 °C 150°C

15 Test cycle solar load switch 1 … 60 Min 10 Min

16 Switch-over temperature 50…0.110°C 75°C

SOLID FUEL Level (..VV..) The parameters in this level refer to the special settings for solid fuel application. Enablingoccurs only following activation in the HYDRAULIC level.

Parameter Designation Setting range / Setting values

Fact

ory

pres

et

Ind

ivid

ual

se

ttin

g

01 Minimum temperature 20 ... 80 °C 60 °C

02 Maximum temperature 30 ... 100 °C 90 °C

03 Switch-on differential (Switch-off differential +3K) ... 20 K 10 K

04 Switch-off differential 2 K ... (Switch-on differential - 3K) 5 K

05 Inhibition heat generator OFF, 2…180 min OFF

BUFFER Level (..VV..) The parameters in this level refer to the special settings regarding buffer charging.Enabling occurs only following activation in the HYDRAULIC level.

Parameter Designation Setting range / Setting values

Fact

ory

pres

et

Ind

ivid

ual

se

ttin

g

01 Minimum temperature buffer 5 °C ... Maximum temperature buffer 20 °C

02 Maximum temperature buffer Minimum temperature buffer ... 95 °C 80 °C

03 Temperature excess H-GEN -10 ... 50 K 8 K

04 Switching differential 1 ... 20 K 2 K

Page 33: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

33

05 Forced heat dissipationOFF1 Into DHW tank2 Into heating circuits

OFF

06 Drain functionSwitch-on differential (Switch-off differential + 2 K) ... 30 K 10 K

07 Drain functionSwitch-off differential 1 K ... (Switch-on differential -2 K) 5 K

08 Buffer start-up protectionOFF no start-up protectionON start-up protection active

ON

09 Buffer discharge protectionOFF no discharge protectionON discharge protection active

ON

10 Buffer operating mode

1 Charging control (heating and DHW)2 Charging control (heating only)3 Discharging control (heating and DHW)4 Discharging control (heating only)5 Charging control (change over to DHW)6 Discharging control (to heat generator)

1

CASCADE CONTROL Level The parameters in this level refer to cascaded heat generators and are only accessible inthe first basic unit with data bus address 10.

This level is only available if several heat generators communicate with each other in adata bus connection.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

01 Switching differential 30 K 8 K

02 Switching on delay 0…60 min 0 Min

03 Switching off delay 0…60 min 0 Min

04 Sequential switch-over powerstage sequence

10...100% 65%

05 Reverse boiler sequence OFF, 1 … 24 h OFF

06 Leading stage 1…n (stages) 1

07 Peak load boiler from adress...OFF

3...(max.stages) all heat generators incascade numbered

OFF

08 Changeover basis power atgroup formation

OFF no changeoverON changeover OFF

Page 34: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

34

DATA BUS Level The parameters in this level refer exclusively to the parameters related to the data bus andthey control the access rights to each remote station.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

01 Bus address basic unit 10, 20, 30, 40, 50 10

02 Bus access room unit HC 1 Advanced access (Owner status)2 Simple access (Tenant status)

2

03 Bus access room unit MC1 1 Advanced access (Owner status)2 Simple access (Tenant status) 2

04 Bus access room unit MC1 1 Advanced access (Owner status)2 Simple access (Tenant status)

2

RELAY TEST Level This level allows the check off all relays the controller contains. The relays can be selectedwith the rotary push-button.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

01 Heat generator test Different relay sequence according to type ofboiler (one or tow level)

OFF

02 Direct heating circuit pumptest OFF-ON-OFF -... OFF

03 Mixing circuit pump 1 test OFF-ON-OFF -... OFF

04 Mixer actuator 1 test STOP-OPEN-STOP-CLOSE-STOP… STOP

05 Mixing circuit pump 2 test OFF-ON-OFF -... OFF

06 Mixer actuator 2 test STOP-OPEN-STOP-CLOSE-STOP… STOP

07 DHW charging pump test OFF-ON-OFF -... OFF

08 Variable output 1 test OFF-ON-OFF -... OFF

09 Variable output 2 test OFF-ON-OFF -... OFF

Page 35: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

35

MALFUNCTION MESSAGE Level In this level every malfunction message that may appear is saved into a message memorystack (max. 5 values)

Parameter Designation Setting range / Setting values

Fact

ory

pres

et

Indi

vidu

al

sett

ing

01 Malfunction message #1 Last malfunction message

02 Malfunction message #2 Next to last malfunction message

03 Malfunction message #3 Third to last malfunction message

04 Malfunction message #4 Fourth to last malfunction message

05 Malfunction message #5 Fifth to last malfunction message

SENSOR CALIBRATION Level

In this level all the sensors connected to the control unit can be corrected by ± 5 Kcompared to the factory calibration value.

Parameter Designation Setting range / Setting values

Fac

tory

p

rese

t

Ind

ivid

ual

se

ttin

g

02 Outdoor sensor - 5 K ... + 5 K

03 Heat generator sensor - 5 K ... + 5 K

04 Domestic hot water sensor - 5 K ... + 5 K

05 Flow sensor mixing circuit 1 - 5 K ... + 5 K

06 Flow sensor mixing circuit 2 - 5 K ... + 5 K

07 Solar panel sensor - 5 K ... + 5 K

08 Solar buffer sensor - 5 K ... + 5 K

09 Variable input 1 (VI 3) - 5 K ... + 5 K

10 Variable input 2 (VI 3) - 5 K ... + 5 K

11 Variable input 3 (VI 3) - 5 K ... + 5 K

Page 36: For the heating specialist Operating and installation ... · PDF fileControl System THETA For the heating specialist Operating and installation instructions Standard unit Remote unit

36

Notes

Subject to change Art. 0450017004 - 0548-23


Recommended