CURBPAKAIR HANDLING UNITS
ENGINEERING GUIDE
OUTDOOR AIR HANDLING UNITS
FORM 100.10-EG2 (401)
00466VIP
2 YORK INTERNATIONAL
GENERAL DESCRIPTION ........................................ 3Unit Description .................................................... 3Outdoor Features ................................................. 3Structural Performance ........................................ 4Quality ................................................................... 4Flexibility ............................................................... 5Factory Installed Controls & Elec. Options ......... 7Variable Air Volume Applications ......................... 7Factory-Packaged Controls and Motor
Control Centers .............................................. 8Factory-mounted End Devices in the
AirPak Air-Handling Units .............................. 9Assurance of YORK Backing ............................... 10Segment Identification ......................................... 12Unit Nomenclature ............................................... 12Segment Availability ............................................. 13Economizer Damper Arrangement ..................... 13
QUICK SELECTION TABLES .................................... 15Coils ...................................................................... 15Dimensions & Weights ........................................ 16
ENGINEERING DATA ................................................ 18Forward Curved & Airfoil Fan & Motor Data ......... 18Plenum Supply/Return Fan & Motor Data ........... 20Plenum Return Fan & Motor Data ....................... 20Variable Inlet Vanes Operating Torques ............. 21Coil Data ............................................................... 23Integral Face & Bypass Coil Data ....................... 24Filter Data ............................................................. 25Blender Data ........................................................ 28Fan and Motor Heat .............................................. 28Air Unit Temperature Limitations ......................... 28Damper Sizes & Required Torque ...................... 29Humidifier Data .................................................... 33Sound Attenuator Data ......................................... 34Electric Heat ......................................................... 35Indirect Fired Gas Heater ..................................... 37Turndown Options and Guidelines ..................... 37Insurance Options and
Local Code Requirements ............................ 38Gas Pressure Requirements .............................. 38Gas Train .............................................................. 40
UNIT SELECTION ..................................................... 48Selecting a CurbPak Air Handling Unit ............... 48Reference Literature ............................................ 49
AIR PRESSURE DROP ............................................ 49Altitude/Temp. Conversion Factors ..................... 49Instructions for Using Tables .............................. 50Static Pressure Schematics ................................ 505/8" Cooling & Dehumidifying Table ................... 525/8" Heating & Sensible Cooling Table ............... 521/2" Cooling & Dehumidifying Table ................... 531/2" Heating & Sensible Cooling Table ............... 53Steam Distributing Coil Table ............................. 54Filter Table ............................................................ 54Diffuser Table ....................................................... 54Air Blender Table .................................................. 54
TABLE OF CONTENTS
Attenuator Table .................................................... 55Fan Velocity Table ................................................. 55Vertical Casing Pressure Table ........................... 55Electric Heat Table ............................................... 55Inlet Damper Pressure Drop Tables ................... 56
SEGMENT DIMENSIONS .......................................... 63Control Enclosure (CE) ........................................ 63Supply Fan (FS) .................................................... 64Plenum Supply Fan (FP) ...................................... 66Cooling Coil (SC, MC, LC) ................................... 68Heating Coil (HC) ................................................. 69Face & Bypass Damper (IB) ................................ 70Integral Face & Bypass Coil (IC) ......................... 71Filter (FF, AF, RF, BF, CF, HF) ............................... 72Mixing Box Inlet (MB) ............................................ 74Return Fan Segment EE / FR .............................. 76Economizer Segment EE / MB ............................. 77Economizer / Fan Plenum Segment EE / FP(V) .... 78
Economizer / Fan Plenum Segment EE / FP(H) ........ 80Exhaust Fan Segment EE / FE ............................ 81Access (MA, LA, XA) .............................................. 83Diffuser (DI) .......................................................... 84Sound Attenuator (AT) .......................................... 85Humidifier (HM) .................................................... 86Electric Heat (EH) ................................................. 87Indirect Fired Gas (IG) .......................................... 88Discharge Plenum (DP) ...................................... 89End Flange (SS & EF) .......................................... 90Air Blender (AB) .................................................... 91Non-Standard (NS) .............................................. 92
PHYSICAL DATA ........................................................ 93CurbPak Overall Dim. & Weight Calculations .... 93Segment Weights ................................................. 94Roof Curb Weights .............................................. 95Full and Reduced Face Coil Weights ................. 96Coil Connection Locations .................................. 101Water Coil Connection Locations ....................... 103Steam Coil Connection Locations ...................... 107Expansion Coil Connection Locations - Std ....... 108Expansion Coil Connection Locations - Tall ....... 109Pipe Chase Enclosure ........................................ 111Inlet Cone Dimensions ........................................ 112Unit & Coil Hand Selection .................................. 113Fan Segment Access Door Locations ................ 113Power Wiring Options .......................................... 114CurbPak Starter Wiring ........................................ 115CurbPak Lighting and Power Wiring ................... 116CurbPak AirMod Wiring ........................................ 117Typical Electric Heater Wiring Diagram .............. 118Sloped Curb ......................................................... 120Roof Curb ............................................................. 121Curb Detail ........................................................... 122Unit Base Rail Detail ........................................... 123Pipe Chase Detail ................................................ 124
GUIDE SPECIFICATIONS ......................................... 127
PAGE PAGE
Table of Contents
FORM 100.10-EG2
YORK INTERNATIONAL 3
General Description
UNIT DESCRIPTION
The YORK CurbPak is designed for rooftop applications.The design flexibility and quality construction of theCurbPak sets it apart from the competition.
OUTDOOR FEATURES
The CurbPak is specifically designed for outdoor appli-cations. The outdoor design features of the CurbPakallow it to withstand the most severe environments.
A rooftop unit is only as good as its roof. The CurbPakroof is sloped to eliminate standing water and its corro-sive effects. In addition, the roof panels are fastenedthrough standing seams and attached to the side walls.This eliminates the need for any screws through theskin of the roof, thus eliminating this as a possible sourceof leakage.
On the YORK CurbPak, the roof overhangs the side-walls and doors, allowing runoff water to drop freely,eliminating corrosive “streaming” down the sides of theunit.
The sidewalls are also free of exposed holes, and jointsare caulked and covered with U-shaped seamcaps toassure a tight, reliable seal. Internal stiffening assuresa high resistance to wind loads.
All outside air and exhaust air openings are protectedfrom the outside elements by rain hoods. The rain hoodsassure that no wind-blown moisture can penetrate theunit casing. The rain hood design features a full-length,drip lip that prevents moisture from being drawn in theoutside air intake.
ROOF w/SEAM CAP DETAIL
SIDE WALL PANELS SHOWING SEAM CAPS27195A
SIDE WALL AND ROOF DETAIL LD06028(7in)
00058VIP(27174 & 27194)
4 YORK INTERNATIONAL
FLOOR SUPPORT
FLOOR
2" INSULATIONBASE RAIL
OPTIONALCURB
DOUBLE WALL
2" DOUBLE WALL PANEL
VERTICAL FRAME
The CurbPak coil IAQ drain pan is sloped to minimizestanding condensate, and offers a full two inches of in-sulation to give the pan the thermal protection it requires.
STRUCTURAL PERFORMANCE
The CurbPak housing has been designed for maximumdeflections 1/200 of panel length. Design criteria sys-tem static pressure include snow loading of 30 pound/sq. ft. and wind load of 100 m.p.h.
QUALITY
CurbPak units are constructed entirely of double wallpanels – including the floor panels! Panels are insulatedwith a full two inches of insulation. Perforated lining isavailable in most segments to meet a variety of appli-cations.
The double wall design provides the highest quality ofunit construction, while preventing erosion of the insu-lation fibers into the air stream.
Access Doors
The CurbPak access doors are also double wall con-struction. The doors feature a full-length stainless steelpiano hinge. The use of positive action handles preventlocking if door is accidentally shut. These handles areused in unit sizes 65 through 400. For walk-in unit sizes460 through 1030, all door latches have a single handlewith multiple latch points.
General Description
28072A(D)
RAIN HOOD
LD06465SLOPED DRAIN PAN DETAIL
SIDE WALL & FLOOR DETAIL FOR UNIT SIZES CP65TO CP305
LD06464
SIDE WALL & FLOOR DETAIL FOR UNIT SIZES CP350TO CP1030
LD00010
DRAIN PAN
2" INSULATION
DOUBLE SLOPEDRAIN PAN
LINER
2" INSULATION1-1/4" DRAINMPT CONNECTION
FORM 100.10-EG2
YORK INTERNATIONAL 5
FLEXIBILITY
For maximum flexibility the CurbPak is based on a seg-mented design concept. The unit construction however,is unitized. Each unit is engineered and built as a singleassembly for greater unit integrity.
The segmental design concept permits the designer tooptimize and customize segments that will best meetthe application. The unit is then engineered and built asa single piece, not a collection of pre-designed and pre-built modules.
CurbPak units are designed and built to ship as a singlepiece except sizes 860 and 1030. This minimizes in-stallation time and cost. Units can however be shippedin multiple pieces to accommodate various shipping andjob site requirements.
Fans
Double-Width, Double-Inlet (DWDI) fans and SingleWidth, Single-Inlet (SWSI) plenum fans are availablefor supply and return air fans. The plenum fan segmentscan accommodate multiple duct outlets, thus reducingthe amount of field duct work and transitions.
All of the CurbPak fan assemblies are internally iso-lated. Seismic isolation is available as an option.
CURBPAK SEGMENTS EXPOSED
DWDI FAN w/VARIABLE INLET VANES25586B
25514A
SUPPLY FAN SEGMENTCOIL
SEGMENTFILTER
SEGMENTINLET/ECONOMIZER
SEGMENT WITHDWDI RETURN AIR FAN
STANDARD 2"WALL
2" INSULATION
STAINLESS STEELCONTINUOUS TYPE HINGE
VIEWPORT
ALUMINUM FRAME
20 GA. GALVANIZED STEEL LINER
18 GA. GALVANIZED STEEL OUTER PANEL
ACCESS DOOR DETAILLD06466
6 YORK INTERNATIONAL
INTEGRAL FACE & BYPASS (IFB) COIL
General Description
Coils
A variety of coils are available to meet every applica-tion. Both 1/2" and 5/8" coils are available for chilledwater, hot water and direct expansion applications. A1" inch outside diameter Steam Distributing Coil can beselected for heating applications.
For the maximum amount of freeze protection, theYORK CurbPak can be provided with an integral faceand bypass coil. YORK will furnish and factory installcoils manufactured by the L.J. WING Company (TM).L.J. WING has set the standard for freeze protectionwith unsurpassed quality and design. Wing Coils areavailable with horizontal (IFB) and vertical (VIFB) tubes,depending upon unit size.
Filters
CurbPak filter segments can be customized to meetany filtration requirement. Bag, Rigid and HEPA filterscan be provided to meet stringent filtration requirements.Carbon filters are available for applications involvingodor removal.
Economizer
Economizer segments are available to provide the maxi-mum benefits of free-cooling during off peak operation.All of the CurbPak Economizer Segments can accom-modate 100% outside air, exhaust air and return air.Return and exhaust fans are available to meet the needsof varying building pressurization requirements.
Additional Segments
A variety of other segments are available to match indi-vidual applications. The CurbPak is available with fac-tory installed air blenders, sound attenuators, electricheat, face and bypass, humidifiers, diffusers, dischargeplenums, access segments and indirect-fired gas burnersegments.
Other segments can be provided to accommodate spe-cial requirements.
STANDARD COIL w/PIPE CHASE & ACCESSPANEL (Piping by others) Optional pipe chasedepths are available.
THROWAWAY, PLEATED, BAG & HEPA FILTERS
27027A
27132A(D)
27029A
27028A
00498VIP
25536A
FORM 100.10-EG2
YORK INTERNATIONAL 7
FACTORY INSTALLED CONTROLS AND ELECTRICAL OPTIONS
YORK has the capability to furnish units with factory installed single-point power motor starter panels, disconnects, marine lights, sensors,actuators or complete unit automation. Factory installed wiring greatlyreduces installation time and cost.
Factory installed inverters, the YORK Air-Modulator, provide the mostefficient and cost effective VAV control in a complete factory package.Factory mounted inverters not only save field labor, but it also assuresproper fan balance for vibration free operation. While most fans arebalanced for a single speed, fans with inverters are factory balanced tooperate over the entire RPM range.
VARIABLE AIR VOLUME APPLICATIONS
Factory mounted variable frequency drives (YORK Air-Modulator) andvariable inlet vanes are available with the YORK CurbPak for VariableAir Volume Applications.
YORK Air-Modulator (AM):
YORK’s Variable Frequency Drive, the AM, offers the most efficientmeans of fan control for variable air volume systems. The Air-Modulatorvaries the speed of the fan to match the VAV load requirements.
The AM takes maximum advantage of the relation between fan speed andfan horsepower. With the AM, any reduction in fan speed results in acubic reduction in fan horsepower. For example, a 10% speed reductionresults in a 27% fan horsepower reduction!
The AM offers the following benefits over variable inlet vanes and dis-charge dampers: • Extended Equipment Life – soft start of motor and fan. • Quieter Fan Operation – fan operating at reduced speed and constant
line of efficiency. • Eliminates need for motor starter panels. • Improved system control and response – DDC controls with LED
digital display. • Proven reliability.
Variable Inlet Vanes
Variable inlet vanes are another method of energy efficient fan control.While the fan runs at a constant speed, the inlet vanes modulate the airentering the fan. This produces a reduced air volume resulting in loweroperating horsepowers.
INSIDE VIEW OF THE AM. AVAILABLEWITH TRANSFORM LIGHT/OUTLETBOX
AM LOCATED IN A NEMA 3R ENCLO-SURE TYPICALLY MOUNTED ON SUP-PLY/RETURN FAN SEGMENTS
00541vip
00542vip
8 YORK INTERNATIONAL
DUCT STATICPRESSURETRANSDUCER DISCHARGE AIR
TEMPERATURESENSOR
LOW LIMITCONTROL
MIXED AIRTEMPERATURESENSOR
FILTER DIFFERENTIALPRESSURE SWITCH
OPTIONAL (NEMA 3R)MOTOR CONTROL PANEL
*OPTIONAL (NEMA 3R)CONTROL ENCLOSURE
BUILDING STATICPRESSURETRANSDUCER
DAMPER ACTUATOR(R.A.)
MIXED AIRDIFFERENTIALPRESSURETRANSDUCER
RETURN AIRTEMP. SENSOR
OUTSIDE AIRTEMPERATURE SENSOR
DAMPERACTUATOR(O.A.)
*OPTIONAL MOUNTING LOCATIONS AVAILABLE
General Description
Factory EngineeredYORK Factory-Packaged Controls with Single-PointMotor Control Center assure you of getting a completefactory-engineered system – no surprise, no hassle, andno compromise. The control systems are designed witheach specific piece of equipment in mind. This assuresyou that the system will control, monitor and diagnoseonly those points that are necessary to maintain opti-mum performance.
Reduce CostsYORK Factory-Packaged End Devices wired to a MotorControl Center reduce costs by taking the guessworkout of control installation. Each device is mounted in thefactory as the equipment is being manufactured. Thereare no worries over job site locations or conditions. Fac-tory labor means faster assembly and lower first cost.
Quality ControlYORK Factory-Packaged End Devices wired to a MotorControl Center assure you of getting a higher quality con-trol system, right from the factory. The control system isdesigned and mounted following the same stringent qual-ity control standards by which the units are built.
Full Service SupportBecause YORK Factory-Packaged End Devices wiredto a Motor Control Center are an integral part of theequipment, who better to troubleshoot and service thesystem than a professional YORK Service technician.The YORK Service technician knows not only the equip-ment and the hardware, but also has a working knowl-edge of equipment application and operation. Every unitis backed by this kind of professional support.
FACTORY-PACKAGED CONTROLS AND MOTOR CONTROL CENTERS
TYPICAL CURBPAK w/FACTORY-PACKAGED CONTROLS or SINGLE POINT MOTOR CONTROL CENTER
LD06741
FORM 100.10-EG2
YORK INTERNATIONAL 9
END DEVICE FACTORY COMMISSIONING
Every end device that is Factory-mounted and wired willgo through a detailed automated commissioning processto ensure that every end device functions properly beforethe air-handling unit leaves the factory. As part of thiscommissioning process, a report will be generated andthis report will ship with the unit. The extensive commis-sioning the end devices go through at the factory wouldbe virtually impossible to duplicate in the field.
Through Cables on Shipping Splits – On all air-han-dling units with shipping splits, cables with field connec-tors will be supplied. The operator connects the auto-mated commissioning tester to the segment being testedand then connects test plugs to the through cables. Theautomated commissioning tester then performs a test toverify that there are no “open” or “shorts” in the throughcables and that all polarity is correct. On verification ofthis test, the automated commissioning tester recordsa pass condition.
Components Include:• 120VAC to 24VAC transformers (3)• Relays for fan start/stop & low-limit reset circuit• Circuit board for field & factory terminations• Low-limit reset button• Knockouts will be provided for customer wiring• Hinged front cover can be lifted off after opening 2"
CONTROL ENCLOSURE FOR FACTORY-MOUNTEDEND DEVICES
00547vip
FACTORY-MOUNTED END DEVICES IN THE CURBPAK AIR-HANDLING UNITS
FACTORY-MOUNTED END DEVICES OVERVIEW
The YORK Factory-mounted End Device Package con-sists of end devices that are pre-engineered; factory in-stalled, wired and commissioned to provide a higher levelof quality and consistency than can be achieved by in-stallation on the job site. All end devices are mounted inthe factory, on the assembly line, where there is com-plete access to all air-handling segments. No more try-ing to get inside of the unit, or taking it apart on the jobsite to install end devices. The end devices can be or-dered 2 ways; mounted with no wiring or mounted andwired to an external control enclosure on the air-han-dling unit. All units that have end devices mounted andwired will have E.T.L. rating.
CONTROL ENCLOSURE
On all units ordered with Factory-mounted End Devicesand wiring all end devices will be wired to a control en-closure that is mounted on the unit. On outdoor unitsthe enclosure will be a NEMA 3R enclosure. The enclo-sure will consist of secondary transformers sized tohandle all actuators, valves and end devices installed inthe air-handler, control relays, and a low-limit reset but-ton. On VAV air-handling units, a duct static pressuretransducer will be mounted inside the enclosure and thetubing for the low and high side of the transducer will bepiped to barbed fittings located on the outside of theenclosure. A terminal strip will be provided inside thecontrol enclosure for all low voltage field terminations.The control enclosure will be E.T.L. listed.
WIRING SCHEMATICS
On air-handling units that are ordered with Factory-mounted End Devices and wiring, a wiring schematicwill be attached to unit. This schematic will include thefollowing detail:
• A pictorial layout of the air-handling unit showing whatdevices are mounted in each segment.
• A wiring schematic showing all interlocking wiring tostarter, disconnects and VFDs. Wiring of all end de-vices back to the circuit board that is located insidethe control enclosure.
• A bill of material table that shows the YORK acronymand the corresponding part number.
These wiring schematics are available to customers inelectronic .dxf format.
10 YORK INTERNATIONAL
General Description
YORK FACTORY SERVICE
ASSURANCE OF YORK BACKING
With every CurbPak system, you get the support andresources that come from dealing with a worldwidemanufacturer – YORK. You are not tied to the limita-tions of a regional supplier. Instead, you get the flexibil-ity being able to design in one part of the country, andbuy and install in another location.
YORK carries the burden of single-source responsibilitysince YORK packages the total system, including cus-tom air handlers, chillers, controls, variable-air-volumeboxes and building automation systems. For added peaceof mind, YORK offers Inspection Only, Preventive Main-tenance and Inspection, or Total Service Contracts tomeet your financing and management requirements.YORK service can also provide certified techniciansavailable locally for factory start-up, drawing fromover 700 factory-trained service technicians in 100strategically-located offices nationwide – a capability notoffered by independent manufacturers.
FULL SERVICE SUPPORT
Because YORK Factory-mounted End Devices and Mo-tor Control Center are an integral part of the equipment,who better to troubleshoot and service the system thana professional YORK Service Technician. The YORKService technician knows not only the equipment andthe hardware, but also has a working knowledge of equip-ment application and operation. Every unit is backed bythis kind of professional support.
27598A
FORM 100.10-EG2
YORK INTERNATIONAL 11
This Page Intentionally Left Blank.
12 YORK INTERNATIONAL
General Description
Supply Fan Segments:• FS - Supply Fan
Fan Types: • Forward Curved Fan
• Standard • Class II
• Airfoil • Standard • Class II
• FP - SWSI Supply Plenum FanFan Types: • Airfoil
• Class II• Backward Inclined
• Standard
Coil Segments:• SC - Short Cooling Coil (13")• MC - Medium Cooling Coil (20")• LC - Long Cooling Coil (27-3/8")• HC - Heat Only, (8")• IC - Heat Only, Integral Face & Bypass Coil
Filter Segments:• FF - Flat Filter (2" & 4")• AF - Angle Filter (2")• RF - Rigid Filter (12")• BF - Bag Filter (21" & 30")• CF - Carbon Filter• HF - HEPA Filter
SEGMENT IDENTIFICATION
Inlet Segments:• MB - Inlet w/Dampers
(0%, 30% or 100% OA – 0% or 100% RA)• EE - Economizer w/Dampers
(100% OA/RA/EA)
Return Fan Segments:• FR - DWDI FC or AF Return Fan• FP - SWSI Horz./Vert. Plenum Return Fan• FE - DWDI FC Exhaust Fan
Accessory Segments:• MA, LA and XA - Access• AB - Air Blender• IB - Face & Bypass Damper• CE - Control Enclosure• SS - Shipping Split• DI - Diffuser• DP - Discharge Plenum• EF - End Flange• EH - Electric Heat• IG - Gas Heat• HM - Humidifier• NS - Non-Standard• AT - Sound Attenuator
UNIT NOMENCLATURE
CP 350 FC
UNIT TYPE FAN TYPE CurbPak DWDI *FC (Forward Curved)
DWDI *AF (Airfoil)UNIT SIZE SWSI **AF (Airfoil) 65 350 SWSI **BI (Backward Inclined) 85 400
105 460 125 530 170 680 *Double - Width, Double - Inlet 215 860 **Single - Width, Single - Inlet 250 1030 305
FORM 100.10-EG2
YORK INTERNATIONAL 13
SEGMENT AVAILABILITY
TOPVIEWS
SIDEVIEWS
EE1 EE 2EE 3 EE 4
MD
100% OA
MD
100% OA
100% EA
50% OA
50% OA
MD
100% OA
100% RA
USED WITHUSED WITHUSED WITHUSED WITH• EE-MB ALL UNIT SIZES• EE-FP(V) UNITS CP65 THROUGH CP305 ONLY
• EE-FR ALL UNIT SIZES• EE-FP(H) ALL UNIT SIZES
• EE-FE CP350 - 1030• EE-FP(V) CP350 - 1030
• EE-FE CP65 - 305
LD06263
LD06589
ECONOMIZER DAMPER ARRANGEMENTS
14 YORK INTERNATIONAL
This Page Intentionally Left Blank.
FORM 100.10-EG2
YORK INTERNATIONAL 15
CDW / CDX COILS (5/8" O.D.)
UNIT FACE VELOCITY – fpm COIL COIL FACE
SIZE 450 475 500 525 550 575 DIMENSIONS (in.) AREAcfm FH FL (sq. ft.)
65 2,745 2,898 3,050 3,203 3,355 3,508 24.25 36 6.185 3,645 3,848 4,050 4,253 4,455 4,658 24.25 48 8.1
105 4,545 4,798 5,050 5,303 5,555 5,808 24.25 60 10.1125 5,445 5,748 6,050 6,353 6,655 6,958 48.25 36 12.1170 7,245 7,648 8,050 8,453 8,855 9,258 48.25 48 16.1215 9,045 9,548 10,050 10,553 11,055 11,558 48.25 60 20.1250 10,845 11,448 12,050 12,653 13,255 13,858 48.25 72 24.1305 12,645 13,448 14,050 14,753 15,455 16,158 48.25 84 28.1350 15,638 16,506 17,375 18,244 19,113 19,981 69.50 72 34.8400 18,244 19,257 20,271 21,284 22,298 23,311 69.50 84 40.5460 20,363 21,494 22,625 23,756 24,888 26,019 90.50 72 45.3530 23,756 25,076 26,396 27,716 29,035 30,355 90.50 84 52.8680 30,544 32,241 33,938 35,634 37,331 39,028 90.50 108 67.9860 38,531 40,672 42,813 44,953 47,094 49,234 103.00 120 85.8
1030 46,238 48,806 51,375 53,944 56,513 59,081 103.00 144 103.0
BDW / BDX COILS (1/2" O.D.)
UNIT FACE VELOCITY – fpm COIL COIL FACE
SIZE 450 475 500 525 550 575 DIMENSIONS (in.) AREAcfm FH FL (sq. ft.)
65 2,835 2,993 3,150 3,308 3,465 3,623 25.00 36 6.385 3,735 3,943 4,150 4,358 4,565 4,773 25.00 48 8.3
105 4,680 4,940 5,200 5,460 5,720 5,980 25.00 60 10.4125 5,625 5,938 6,250 6,563 6,875 7,188 50.00 36 12.5170 7,515 7,933 8,350 8,768 9,185 9,603 50.00 48 16.7215 9,360 9,880 10,400 10,920 11,440 11,960 50.00 60 20.8250 11,250 11,875 12,500 13,125 13,750 14,375 50.00 72 25.0305 13,140 13,870 14,600 15,330 16,060 16,790 50.00 84 29.2350 15,188 16,031 16,875 17,719 18,563 19,406 67.50 72 33.8400 17,719 18,703 19,688 20,672 21,656 22,641 67.50 84 39.4460 20,250 21,375 22,500 23,625 24,750 25,875 90.00 72 45.0530 23,625 24,938 26,250 27,563 28,875 30,188 90.00 84 52.5680 30,375 32,063 33,750 35,438 37,125 38,813 90.00 108 67.5860 38,438 40,573 42,708 44,844 46,979 49,115 102.50 120 85.4
1030 46,125 48,688 51,250 53,813 56,375 58,938 102.50 144 102.5
Quick Selection Tables
16 YORK INTERNATIONAL
DIMENSIONS AND WEIGHTS
Quick Selection Tables (continued)
UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
HEIGHT 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122WIDTH 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151
SEGMENT L = LENGTH OF SEGMENT IN THE DIRECTION OF AIRFLOW (IN.)
FS3 SUPPLY FAN L 45 45 48 51 54 63 66 75 87 87 93 99 99 102 111W/AF bs. 637 727 910 928 1139 1421 1728 2164 2404 2734 2998 3376 4429 5637 7137SUPPLY FAN L 45 45 48 51 54 63 66 75 87 87 93 99 99 102 111W/FC lbs. 609 699 859 906 1118 1400 1689 2006 2283 2567 2736 3200 4182 5355 5653
FP3 PLENUM SUPPLY L 63 63 66 69 72 81 84 99 111 111 117 123 123 138 147FAN lbs. 987 1097 1262 1492 1817 2260 2658 3025 4057 4466 4641 5737 7217 9365 9924
MA 18" ACCESS L 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18lbs. 209 228 246 258 275 293 312 331 354 390 399 439 528 721 798
LA 24" ACCESS L 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24lbs. 251 273 295 309 330 352 374 414 442 487 499 549 660 901 998
XA 30" ACCESS L 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30lbs. 301 328 354 371 396 422 449 517 553 609 616 686 825 1126 1248
SC SHORT COIL (13") L 21 21 21 24 24 24 24 24 24 24 24 24 24 30 30(6 Row/8 FPI BDW FF Coil) lbs. 298 350 406 501 584 672 761 854 1018 1144 1257 1419 1740 2314 2646
MC MEDIUM COIL (20") L 30 30 30 33 33 33 33 33 33 33 33 33 33 48 48(8 Row/8 FPI BDW FF Coil) lbs. 400 468 544 653 764 881 999 1124 1336 1502 1646 1861 2290 3041 3480
LC LONG COIL (27-3/8") L 36 36 36 39 39 39 39 39 39 39 39 39 39 60 60(2 & 4 Row/8FPI/BDW FF Coil) lbs. 506 593 688 829 967 1115 1264 1417 1692 1898 2089 2360 2899 3864 4417
HC HEATING COIL L 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15(1 Row/8 FPI BDW FF Coil) lbs. 157 181 205 231 260 290 322 334 410 449 484 533 630 866 971
IC (2 Row IFB Wing Coil) L N/A 33 33 N/A 33 33 33 33 33 33 N/A N/A N/A N/A N/AWING lbs. 673 756 1057 1237 1328 1388 1748 1821COILS (4 Row IFB Wing Coil) L N/A 48 48 N/A 48 48 48 48 48 48 N/A N/A N/A N/A N/A
lbs. 367 417 476 474 530 596 662 734 805 890 901 1008 1221 1665 1845(1 Row VIFB Wing Coil) L N/A N/A N/A 42 42 42 42 42 42 42 42 42 42 42 42
lbs. 940 1045 1165 1300 1426 1666 1826 2035 2238 2745 3471 3888
(2 Row VIFB Wing Coil) L N/A N/A N/A 42 42 42 42 42 42 42 42 42 42 42 42lbs. 967 1081 1210 1301 1526 1729 1904 2161 2395 2954 3694 4147
(3 Row VIFB Wing Coil) L N/A N/A N/A 42 42 42 42 42 42 42 42 42 42 42 42lbs. 997 1121 1260 1362 1576 1799 1991 2257 2506 3114 3869 4338
EH ELECTRIC HEAT L 24 24 24 24 24 24 24 24 24 24 24 24 24 24 2424" lbs. 301 342 389 386 432 483 536 591 646 712 715 793 948 1293 1433ELECTRIC HEAT L 30 30 30 30 30 30 30 30 30 30 30 30 30 30 3030" lbs. 367 417 476 474 530 596 662 734 805 890 901 1008 1221 1665 1845ELECTRIC HEAT L 42 42 42 42 42 42 42 42 42 42 42 42 42 42 4242" lbs. 479 543 619 619 692 777 862 954 1048 1157 1174 1306 1570 2038 2258
IG INDIRECT L N/A N/A N/A N/A 63 66 75 78 78 81 84 99 102 105 120FIRED GAS HEAT lbs. 1757 2055 2793 3241 3301 3748 3821 5475 6490 7977 12022
HM HUMIDIFIER L 30 30 30 33 33 33 33 33 33 33 33 33 33 48 48lbs. 188 215 245 275 309 348 388 433 480 535 553 623 761 1038 1150
FF FLAT FILTER (2", 4") L 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9lbs. 65 75 85 89 99 111 123 138 155 172 184 206 250 340 378
AF ANGLE FILTER (2") L 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30lbs. 237 267 304 301 337 376 416 459 499 549 549 608 727 991 1099
RF RIGID FILTER L 21 21 21 21 21 21 21 21 21 21 21 21 21 21 21lbs. 150 171 194 194 217 242 267 295 325 355 361 400 481 655 726
BF BAG FILTER (21") L 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30lbs. 216 244 278 276 309 345 383 422 461 508 510 567 678 924 1024
BAG FILTER (32") L 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42lbs. 329 375 427 425 476 536 596 662 727 805 817 915 1111 1515 1679
CF CARBON FILTER L 39 39 39 39 39 39 39 39 39 39 39 39 39 39 39lbs. 486 656 761 931 1111 1175 1555 1694 2380 2694 3000 3379 4220 5754 6378
HF HEPA FILTER L 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18lbs. 110 129 199 231 273 331 433 587 636 784 817 1015 1269 1730 1918
MB INLET L 30 30 30 36 36 36 36 36 42 42 48 48 48 63 63(30% OA & 100% RA) lbs. 438 527 625 594 700 816 933 1051 1180 1321 1389 1558 1893 2581 2861
MB INLET L 30 30 30 36 36 36 36 36 42 42 48 48 48 63 63(100% OA & 100% RA) lbs. 438 527 625 653 734 892 991 1136 1297 1441 1580 1767 2143 2923 3239
MB INLET L 30 30 30 30 30 30 30 30 30 30 30 30 30 36 36(100% OA & 0% RA) lbs. 438 527 625 612 680 825 904 1040 1112 1235 1297 1451 1758 2398 2656
MB INLET L 30 30 30 36 36 36 36 36 42 42 48 48 48 63 63(0% OA & 100% RA) lbs. 352 420 493 507 592 684 782 870 1029 1141 1218 1359 1639 2235 2453
FORM 100.10-EG2
YORK INTERNATIONAL 17
NOTES:1. Weights are shipping weights not operating weights.2. For coil segments, the dimensions in (") represents the coil space available.3. Weights include the largest available motor and largest Class II fans.4. Certain items (e.g. coil connections, door handles, mounting feet, etc.) may extend beyond the cabinet dimensions.5. MB and EE / FR, FP, FE weights include rain hood.
DIMENSIONS AND WEIGHTSUNIT SIZE
65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
HEIGHT 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122WIDTH 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151
SEGMENT L = LENGTH OF SEGMENT IN THE DIRECTION OF AIRFLOW (IN.)
AB AIR BLENDER L 33 33 36 36 36 36 36 36 54 54 87 93 72 54 60lbs. 383 519 634 603 812 827 810 986 1691 1922 2738 3134 3519 4923 5319
AT SOUND ATTENUATOR L 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36(3FT) lbs. 458 536 641 699 820 987 1114 1302 1515 1755 1874 2188 2732 3726 4130SOUND ATTENUATOR L 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60(5FT) lbs. 769 901 1079 1177 1382 1665 1881 2200 2561 2968 3172 3705 4629 6313 6996SOUND ATTENUATOR L 84 84 84 84 84 84 84 84 84 84 84 84 84 84 84(7FT) lbs. 1078 1264 1514 1651 1939 2338 2641 3089 3597 4168 4457 5204 6503 8868 9829
DIF DIFFUSER L 18 18 21 21 24 27 30 30 36 36 42 45 48 51 57lbs. 161 183 235 237 294 361 436 480 604 660 736 853 1086 1480 1641
DP DISCHARGE L 30 30 30 36 36 36 36 36 42 42 48 48 48 63 63PLENUM lbs. 240 272 307 355 394 438 481 526 647 701 758 822 952 1298 1438
EF END FLANGE L 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6lbs. 56 64 72 73 81 90 100 110 122 134 136 150 175 238 264
IB FACE & BYPASS L 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24DAMPER lbs. 94 115 137 149 186 223 260 298 363 417 459 527 664 869 1022
CE CONTROL CABINET L 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24lbs. 407 462 471 526 587 658 728 827 884 975 986 1098 1320 1801 1995
SS SHIPPING L 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6SPLIT lbs. 56 64 72 73 81 90 100 110 122 134 136 150 175 238 264
EE-FR INLET/ECONOMIZER L 102 108 120 108 117 135 144 150 153 165 165 171 189 192 213W/ RETURN FAN lbs. 1357 1561 2040 1948 2352 2864 3457 4001 4580 5242 5677 6335 7789 10119 13847
EE-MB INLET/ECONOMIZER L 75 75 75 81 84 90 90 102 102 105 111 114 117 135 135NO FAN lbs. 1031 1179 1333 1469 1680 1985 2204 2724 3014 3362 3632 4154 5025 6250 6770
EE-FP(V) INLET/ECONOMIZER L N/A 102 102 102 108 117 117 132 105 111 117 117 129 141 141VERTICAL PLENUM FAN lbs. N/A 1549 1669 1929 2201 2610 2819 3428 3342 3956 4099 5264 6646 8421 9858
EE-FP (H) INLET/ECONOMIZER L 132 138 150 144 153 171 180 195 207 213 219 231 237 261 282HORZ. PLENUM FAN lbs. 1581 1853 2247 2231 2726 3405 3982 4453 5309 6067 6459 7316 9316 11880 14740
EE-FE INLET/ECONOMIZER L 102 108 120 108 117 135 144 150 105 111 111 123 129 141 141FC EXHAUST FAN lbs. 1253 1457 1811 1758 2146 2810 3332 3728 3768 4305 4611 5335 6595 8486 8924
LC PIPE CHASE lbs. 177 177 177 272 272 272 272 272 375 375 498 498 498 680 753MC PIPE CHASE lbs. 158 158 158 248 248 248 248 248 354 354 462 462 462 630 699SC PIPE CHASE lbs. 140 140 140 231 231 231 231 231 323 323 437 437 437 595 66012" NS lbs. 101 115 130 132 147 164 182 200 221 243 248 271 317 475 528HC PIPE CHASE lbs. 112 112 112 162 162 162 162 162 194 194 218 218 218 298 329
18 YORK INTERNATIONAL
Engineering DataFORWARD CURVED / AIRFOIL FAN AND MOTOR DATA
UNIT FAN VIV MAX. MAX. FAN OUTLET
SIZE TYPE SIZE OPTIONMOTOR MOTOR AREA
HP FRAME (sq. ft)
65 FC 10 X 10 N/A 7.5 213T 1.03AF 12 N/A 7.5 213T 1.45
85 FC 10 X 10 N/A 7.5 213T 1.03AF 12 N/A 7.5 213T 1.45FC 10 X 10 N/A 7.5 213T 1.03
105 FC 12 X 12 N/A 10 215T 1.45FC 12 X 12 (L) YES 10 215T 1.45AF 15 YES 15 254T 2.04FC 12 X 12 N/A 10 215T 1.45FC 12 X 12 (L) YES 10 215T 1.45
125 FC 15 X 15 N/A 10 215T 2.04AF 12 N/A 10 215T 1.45AF 15 YES 15 254T 2.04FC 15 X 15 N/A 10 215T 2.04FC 15 X 15 (L) YES 15 254T 2.05
170 FC 18 X 18 N/A 15 254T 2.86FC 18 X 18 (L) YES 20 256T 2.86AF 15 YES 15 254T 2.04AF 18 YES 20 256T 2.86FC 18 X 18 N/A 15 254T 2.86
215 FC 18 X 18 (L) YES 20 256T 2.86AF 15 YES 15 254T 2.04AF 18 YES 20 256T 2.86FC 20 X 20 N/A 25 284T 4.38
250 FC 20 X 20 (L) YES 30 286T 4.25AF 18 YES 20 256T 2.86AF 20 YES 25 284T 4.38FC 20 X 20 N/A 25 284T 4.38
305 FC 20 X 20 (L) YES 30 286T 3.25AF 20 YES 25 284T 4.38AF 22 YES 30 286T 5.50FC 22 X 22 N/A 40 324T 5.50
350 FC 22 X 22 (L) YES 40 324T 5.20AF 22 YES 30 286T 5.50AF 25 YES 40 324T 6.90FC 25 X 25 N/A 50 326T 6.90
400 FC 25 X 25 (L) YES 50 326T 6.80AF 25 YES 40 324T 6.90AF 28 YES 40 324T 8.70FC 25 X 25 N/A 50 326T 6.90
460FC 27 X 27 (L) YES 50 326T 8.10FC 28 X 28 N/A 50 326T 8.10AF 28 YES 40 324T 8.67AF 32 YES 50 326T 10.91FC 28 X 28 N/A 50 326T 8.67
530FC 30 X 30 (L) YES 60 364T 9.40FC 32 X 32 N/A 60 364T 10.91AF 28 YES 50 326T 8.67AF 32 YES 60 364T 10.91
FORM 100.10-EG2
YORK INTERNATIONAL 19
FORWARD CURVED / AIRFOIL FAN AND MOTOR DATA
UNIT FAN VIV MAX. MAX. FAN OUTLET
SIZE TYPE SIZE OPTION MOTOR MOTOR AREAHP FRAME (sq. ft)
FC 28 X 28 N/A 50 326T 8.67FC 30 X 30 (L) YES 60 364T 9.40FC 32 X 32 N/A 60 364T 10.91680AF 32 YES 60 364T 10.91AF 36 YES 75 365T 13.74FC 30 X 30 (L) YES 60 364T 9.40
860
FC 32 X 32 N/A 60 364T 10.91FC 33 X 33 (L) YES 60 364T 11.90FC 36 X 36 N/A 60 364T 13.74AF 36 YES 75 365T 13.74AF 40 YES 100 404T 17.27FC 36 X 36 N/A 60 364T 13.74FC 36 X 36 (L) YES 60 364T 12.70
1030 FC 40 X 40 N/A 60 364T 17.27AF 40 YES 100 404T 17.27AF 44M YES 100 404T 20.50AF 49M YES 100 404T 24.90
FORWARD CURVE EXHAUST FAN AND MOTOR DATA – FE
UNIT FAN MAX. MAX. FAN OUTLET
SIZE TYPE SIZE MOTOR MOTOR AREAHP FRAME (sq. ft)
350 FC 22 X 22 40 324T 5.50400 FC 25 X 25 50 326T 6.90460 FC 28 X 28 50 326T 8.67530 FC 28 X 28 50 326T 8.67680 FC 28 X 28 50 326T 8.67860 FC 32 X 32 60 364T 10.91
1030 FC 32 X 32 60 364T 10.91
20 YORK INTERNATIONAL
PLENUM RETURN FAN AND MOTOR DATA – FP(V)
NOTE: 1. Units with SWSI fans are not within the scope of ARI Certification(Standard 430).
PLENUM SUPPLY / RETURN FAN AND MOTOR DATA – FP(S) & FP(H)
NOTES: 1. Units with SWSI fans are not within the scope of ARI Certification(Standard 430).
2. All SWSI fans are CL2.
SWSI (AF) PLENUM FANSUNIT FAN MAX MAX MOTORSIZE TYPE SIZE MOTOR HP FRAME65 N/A N/A N/A N/A85 BI 15 3 182T
105 BI 15 5 184T125 AF 18 5 184T170 AF 20 7.5 213T215 AF 24 10 215T250 AF 27 10 215T305 AF 30 15 254T350 AF 33 15 254T400 AF 36 15 254T460 AF 36 20 256T530 AF 40 20 256T680 AF 49 30 286T860 AF 49 40 324T
1030 AF 49 50 326T
SWSI (AF) PLENUM FANSUNIT FAN MAX MAX MOTORSIZE TYPE SIZE MOTOR HP FRAME65 BI 13 7.5 213T
85 BI 13 7.5 213TBI 15 10 215T
105 BI 15 10 215T
125 BI 16 15 254TAF 18 15 254TAF 18 15 254T
170 AF 20 20 256TAF 22 20 256TAF 22 20 256T
215 AF 24 20 256TAF 27 25 284TAF 24 20 256T
250 AF 27 25 284TAF 30 30 286TAF 24 20 256T
305 AF 27 25 284TAF 30 30 286TAF 30 30 286T
350 AF 33 40 324TAF 36 50 326TAF 40 60 364TAF 33 40 324T
400 AF 36 50 326TAF 40 60 364TAF 44 75 365TAF 36 50 326T
460 AF 40 60 364TAF 44 75 365TAF 36 50 326T
530 AF 40 60 364TAF 44 75 365TAF 49 100 404TAF 44 75 365T
680 AF 49 100 404TAF 54 100 404T
860 AF 49 75 365TAF 54 100 404TAF 49 75 365T
1030 AF 54 100 404TAF 60 100 404T
Engineering Data
FORM 100.10-EG2
YORK INTERNATIONAL 21
RPM FAN SIZES12 15 18 20 22 25 28 32 36 40 44 49
400 20 20 20 20 20 20 20 26 39 57 86 127600 20 20 20 20 20 20 26 58 87 129 193 280800 20 20 20 20 21 32 47 104 155 229 343 499
1000 20 20 20 22 33 49 73 162 243 357 536 7831200 20 20 22 32 48 71 105 234 350 5141400 20 20 29 43 65 97 142 318 4761600 20 20 38 56 85 126 186 4151800 20 22 49 71 108 160 2361900 20 25 54 79 120 178 2622000 20 28 60 88 133 197 2912100 20 31 66 97 147 2172200 22 34 73 106 161 2392300 24 37 79 116 176 2612400 26 40 86 126 1912500 28 43 94 137 2082600 31 47 101 1482700 33 50 109 1602800 36 54 1182900 38 58 1263000 41 62 1353100 44 67 1443200 47 713300 49 753400 53 803500 56 853600 59 903700 62 953800 66 1003900 694000 734100 764200 884300440045004600
VARIABLE INLET VANES OPERATING TORQUES
AIRFOIL (DWDI) (IN. LBS.)
NOTE: Shaded area indicates an area where the fan exceeds the Class II limits.
FORWARD CURVED (IN. LBS.)
NOTE: Shaded area indicates an area where the RPM is below minimum or exceeds the Class II limits.
RPM FAN SIZES12 x 12 15 x 15 18 x 18 20 x 20 22 x 22 25 x 25 27 x 27 30 x 30 33 x 33 36 x 36
300 37 48 58 67400 35 40 45 73 88 90500 35 35 40 48 71 100 123 140600 35 35 44 48 61 88 133 160 169700 35 38 53 60 75 110 165 200 215800 35 35 43 64 72 90 135 200 235900 35 35 49 75 83 108 160 225
1000 35 42 55 85 95 1251100 35 45 63 95 108 1371200 35 50 70 108 1201300 38 55 78 1201400 43 61 851500 45 68 901600 50 731700 52 781800 581900 602000 652100 692200 74
22 YORK INTERNATIONAL
VARIABLE INLET VANES OPERATING TORQUES
Engineering Data
RPM FAN SIZE13 15 16 18 20 22 24 27 30 33 36 40 44 49 54 60
400 20 20 20 20 20 20 20 20 20 20 20 26 39 57 84 128600 20 20 20 20 20 20 20 20 20 26 40 58 87 129 190 289800 20 20 20 20 20 20 20 21 32 47 70 103 155 228 337 514
1000 20 20 20 20 20 20 22 33 50 73 110 162 243 357 5271200 20 20 20 20 20 22 32 47 72 106 158 233 3501400 20 20 20 20 20 29 44 64 98 144 2151500 20 20 20 20 22 34 50 74 113 1651600 20 20 20 20 25 39 57 84 128 1881700 20 20 20 20 29 43 64 95 1451800 20 20 20 22 32 49 72 107 1631900 20 20 20 25 36 54 81 1192000 20 20 20 27 40 60 89 1322100 20 20 20 30 44 66 982200 20 20 22 33 48 73 1082300 20 20 24 36 52 802400 20 20 26 39 57 872500 20 20 29 42 622600 20 21 31 46 672700 20 23 33 502800 20 25 36 532900 20 26 39 573000 20 28 413100 20 30 443200 21 32 473300 22 34 503400 24 363500 25 383600 27 413700 283800 303900 314000 3341004200
NOTE: 1. Shaded area indicates an area where the fan exceeds the Class II limits.
PLENUM FAN (IN. LBS.)
FORM 100.10-EG2
YORK INTERNATIONAL 23
NOTE: 1. (Quantity) = Connections per Unit
(1) = 1 set of connections (1 supply, 1 return)
(2) = 2 set of connections (2 supply, 2 return)
(3) = 3 set of connections (3 supply, 3 return)
FH x FL = Finned Height (Inches) x Finned Length (Inches)
Engineering Data – Coils
COIL DATAFREE FLOW COILS TURBOFIN COILS NON-FREEZE COILS
UNIT 1/2" DIA. TUBES 5/8" DIA. TUBES 1" DIA. TUBES (SDC TYPES)SIZE Full Face Reduced Face Full Face Reduced Face Full Face Reduced Face
1(Quantity) Area 1(Quantity) Area 1(Quantity) Area 1(Quantity) Area 1(Quantity) Area1 (Quantity) AreaFH x FL (sq.ft.) FH x FL (sq.ft.) FH x FL (sq.ft.) FH x FL (sq.ft.) FH x FL (sq.ft.) FH x FL (sq.ft.)
65(1)
6.3(1)
3.8(1)
6.1(1)
3.8(1)
5.3(1)
3.725.0 x 36.0 15.0 x 36.0 24.25 x 36.0 15.25 x 36.0 21.0 x 36.0 15.0 x 36.0
85(1)
8.3(1)
5.0(1)
8.1(1)
5.1(1)
7.0(1)
5.025.0 x 48.0 15.0 x 48.0 24.25 x 48.0 15.25 x 48.0 21.0 x 48.0 15.0 x 48.0
105(1)
10.4(1)
6.3(1)
10.1(1)
6.4(1)
8.8(1)
6.225.0 x 60.0 15.0 x 60.0 24.25 x 60.0 15.25 x 60.0 21.0 x 60.0 15.0 x 60.0
125(1)
12.5(1)
8.1(1)
12.1(1)
8.3(1)
11.3(1)
8.250.0 x 36.0 32.5 x 36.0 48.25 x 36.0 33.25 x 36.0 45.0 x 36.0 33.0 x 36.0
170(1)
16.7(1)
10.8(1)
16.1(1)
11.1(1)
15.0(1)
11.050.0 x 48.0 32.5 x 48.0 48.25 x 48.0 33.25 x 48.0 45.0 x 48.0 33.0 x 48.0
215(1)
20.8(1)
13.5(1)
20.1(1)
13.9(1)
18.8(1)
13.750.0 x 60.0 32.5 x 60.0 48.25 x 60.0 33.25 x 60.0 45.0 x 60.0 33.0 x 60.0
250(1)
25.0(1)
16.3(1)
24.1(1)
16.6(1)
22.5(1)
16.550.0 x 72.0 32.5 x 72.0 48.25 x 72.0 33.25 x 72.0 45.0 x 72.0 33.0 x 72.0
305(1)
29.2(1)
19.0(1)
28.1(1)
19.4(1)
26.3(1)
19.250.0 x 84.0 32.5 x 84.0 48.25 x 84.0 33.25 x 84.0 45.0 x 84.0 33.0 x 84.0
350(2)
33.8(1)
23.8(2)
34.8(2)
25.8(2)
33.0(1)
24.067.5 x 72.0 47.5 x 72.0 69.5 x 72.0 51.5 x 72.0 69.0 x 72.0 48.0 x 72.0
400(2)
39.4(1)
27.7(2)
40.5(2)
30.0(2)
38.5(1)
28.067.5 x 84.0 47.5 x 84.0 69.5 x 84.0 51.5 x 84.0 69.0 x 84.0 48.0 x 84.0
460(2)
45.0(2)
33.8(2)
45.3(2)
34.8(2)
45.0(2)
34.590.0 x 72.0 67.5 x 72.0 90.5 x 72.0 69.5 x 72.0 90.0 x 72.0 69.0 x 72.0
530(2)
52.5(2)
39.4(2)
52.8(2)
40.5(2)
52.5(2)
40.390.0 x 84.0 67.5 x 84.0 90.5 x 84.0 69.5 x 84.0 90.0 x 84.0 69.0 x 84.0
680(2)
67.5(2)
50.6(2)
67.9(2)
52.1(2)
67.5(2)
51.890.0 x 108.0 67.5 x 108.0 90.5 x 108.0 69.5 x 108.0 90.0 x 108.0 69.0 x 108.0
860(2)
85.4(2)
60.4(2)
85.8(2)
60.4(3)
85.0(2)
60.0102.5 x 120.0 72.5 x 120.0 103.0 x 120.0 72.5 x 120.0 102.0 x 120.0 72.0 x 120.0
1030(2)
102.5(2)
72.5(2)
103.0(2)
72.5(3)
102.0(2)
72.0102.5 x 144.0 72.5 x 144.0 103.0 x 144.0 72.5 x 144.0 102.0 x 144.0 72.0 x 144.0
BDW CDW SDC
24 YORK INTERNATIONAL
UNITHORIZONTAL TUBE COILS (IFB)
SIZE MAX. OUTLET L.J. WINGcfm AREA MODEL
65 N/A N/A N/A85 4,080 5.1 lFB-A-42105 5,488 6.9 lFB-A-54125 N/A N/A N/A170 8,240 10.3 IFB-C-42215 13,740 17.2 lFB-D-54250 15,390 19.2 lFB-D-60305 15,390 19.2 lFB-D-60350 21,600 27.0 IFB-F-60400 21,600 27.0 IFB-F-60460 N/A N/A N/A530 N/A N/A N/A680 N/A N/A N/A860 N/A N/A N/A1030 N/A N/A N/A
UNIT VERTICAL TUBE COILS (VIFB)
SIZE MAXIMUM OUTLET L.J. WINGcfm AREA MODEL
65 N/A N/A N/A85 N/A N/A N/A105 N/A N/A N/A125 4,851 5.4 VA-3170 6,435 7.2 VA-4215 8,046 8.9 VA-5250 9,630 10.7 VA-6305 11,250 12.6 VA-7350 19,260 21.4 VC-6400 22,500 25.0 VC-7460 31,320 34.8 VE-6530 36,540 40.6 VE-7680 52,240 58.1 VE-10860 57,420 63.8 VE-111030 62,640 69.6 VE-12
INTEGRAL FACE AND BYPASS COIL DATA
NOTE: 1. All coil information used w/permis-sion from L.J. Wing
2. Model numbers indicated are for two(2) row coils, 1 section.
3. All IFB coils have side coil connec-tions.
4. Maximum cfm is based on 800 fpm xoutlet area.
NOTE: 1. All coil information used w/permis-sion from L.J. Wing
2. Model numbers indicated are for one(1) row coils.
3. All VIFB coils have center coil con-nections.
4. Maximum cfm is based on 900 fpm xoutlet area.
Engineering Data – Coils
FORM 100.10-EG2
YORK INTERNATIONAL 25
Engineering Data
FLAT FILTER (FF), RIGID FILTER (RF), BAG FILTER (BF) & HEPA FILTER (HF) SEGMENTS
FILTER SIZES AND QUANTITIES PER UNIT SIZE
FILTER DATA
NOTES: 1. See the filter configurations below for specific filter arrangements.2. Filters are side-loaded, except when in blow through arrangement they are either front or rear loaded. HEPA will always be
front loaded.3. The number in ( ) defines how many rows high with that particular filter pattern.
UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
Area (sq.ft.) 6 8 10 12 16 20 24 28 36 42 48 56 72 90 108Filter 12 x 24 1 – 1 2 – 2 – 2 – 3 – 4 4 5 6Size 24 x 24 1 2 2 2 4 4 6 6 9 9 12 12 16 20 24
LD06264
26 YORK INTERNATIONAL
ANGLE FILTER SEGMENTS (AF)
FILTER SIZES AND QUANTITIES PER UNIT SIZE
FILTER DATA
NOTES: 1. See the filter configurations below for specific filter arrangements.2. Filters are side-loaded.3. The number in ( ) defines how many rows high with that particular filter pattern.
UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
Area (sq.ft.) 12 16 20 24 32 40 48 56 72 84 96 112 144 180 216Filter 12 x 24 2 – 2 4 – 4 – 4 – 6 – 8 8 – –Size 24 x 24 2 4 4 4 8 8 12 12 18 18 24 24 32 45 54
LD06265
Engineering Data
FORM 100.10-EG2
YORK INTERNATIONAL 27
FILTER DATA
NOTES: 1. See the filter configurations below for specific filter arrangements.2. Filters are side-loaded.
UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
Area (sq.ft.) 72 96 120 144 192 240 288 336 432 504 576 672 864 960 1152Filter 12 x 24 12 – 12 24 – 24 – 24 – 36 – 48 48 – –Size 24 x 24 12 24 24 24 48 48 72 72 108 108 144 144 192 240 288Lbs Carbon 155 213 261 309 426 522 639 735 959 1103 1278 1470 1896 2130 2556
3. Avoid placing carbon filters in high humidity areas.4. Optional 4" flat filters are available upstream.5. The number in ( ) defines how many rows high
with that particular filter pattern.
1" CARBON TRAY FILTER SEGMENTS (CF)FILTER SIZES AND QUANTITIES PER UNIT SIZE
LD06266
28 YORK INTERNATIONAL
UNIT TOTAL AREASIZE (sq. ft.)
65 2.885 3.3105 3.9125 5.5170 6.6215 6.6250 13.2305 13.2350 14.8400 14.8460 19.2530 22.0680 26.3860 28.31030 34.9
BLENDER DATA
HP FAN MOTOR FAN FAN ANDFAN MOTOR
5 2.8 12.7 15.57-1/2 3.6 19.1 22.7
10 4.4 24.5 29.915 6.2 38.2 44.420 7.5 51.0 58.525 8.7 63.6 72.330 9.4 76.3 85.740 13.0 102.0 115.050 16.0 127.0 143.060 19.0 153.0 172.075 21.0 191.0 212.0
100 25.0 254.0 279.0
FAN AND MOTOR HEAT (MBH)
AIR UNIT TEMPERATURE LIMITATIONS
Motors with Class F Insulation – 140°FMotors with Class B Insulation – 104°FPower Wiring – 140°FControls & Control Wiring - 140°FPrefilters – 150°F
High Efficiency Filters – 200°FFan Bearings – 120°F (FC),
180°F (AF)Gasketing – 200°F
DAMPER ULL* DAMPER ULL* DAMPER LOW LEAK DAMPERWIDTH LEAKAGE cfm/SQ. FT. LEAKAGE cfm/SQ. FT. LEAKAGE cfm/SQ. FT.INCHES @ 1" W.G. @ 4" W.G. @ 1" W.G.
12 5.0 10.5 7.024 4.5 9.5 4.836 4.0 8.4 3.748 3.0 6.3 3.760 3.0 6.3 3.7
NOTE: All damper banks are made up from maximum 48" wide sections. * Ultra-low leak
DAMPER LEAKAGE
EXAMPLE:CP–350 EE/FR Outside Air Damper Standard Construction
HEIGHT 68.0WIDTH 43.0AREA 20.3
Leakage 20.3 sq. ft. x 3.7 cfm / sq. ft. = 75.1 cfm
Engineering Data
FORM 100.10-EG2
YORK INTERNATIONAL 29
100% OA IndividualUnit Damper Actual Dimensions Damper
Size Width Height Area Torque65 34.75 12 2.90 2085 46.75 12 3.90 27
105 58.75 12 4.90 34125 34.75 24 5.80 41170 46.75 24 7.80 55215 58.75 24 9.80 69250 70.75 24 11.80 83305 82.75 24 13.80 97350 70.75 20.75 10.19 71400 82.75 20.75 11.12 84460 70.75 26.75 13.14 92530 82.75 26.75 15.37 108680 106.75 26.75 19.83 139860 118.75 45.75 37.73 264
1030 142.75 45.75 45.35 318
NOTES:1. Torque required to achieve maximum leakage performance.2. Torques are based on 1 inch wg pressure differential.3. Damper performance is based on AMCA 500 test setup 5.4/5.5.4. Maximum damper face velocity is 2000 fpm.5. Torques are configured for ULL dampers. To achieve LL dampers: Area of damper multiplied by 5.
DAMPER SIZES AND REQUIRED TORQUE
MB Segment100% Return Air (RA) 30% Outside Air (OA)
100% RA Individual 30% OA IndividualUnit Damper Actual Dimensions Damper Damper Actual Dimensions DamperSize Width Height Area Torque Width Height Area Torque65 24 15 2.50 18 34.75 9.75 2.35 1785 36 15 3.75 26 46.75 9.75 3.17 22
105 48 15 5.00 35 58.75 9.75 3.98 28125 27 24 4.50 32 34.75 9.75 2.35 17170 36 24 6.00 42 46.75 9.75 3.17 22215 48 24 8.00 56 58.75 9.75 3.98 28250 60 24 10.00 70 70.75 9.75 4.79 34305 72 24 12.00 84 82.75 9.75 5.60 39350 60 27 11.25 79 70.75 8.75 4.30 30400 72 27 13.50 95 82.75 8.75 5.03 35460 60 33 13.75 96 70.75 14.75 7.25 51530 72 33 16.50 116 82.75 14.75 8.48 59680 96 33 22.00 154 106.75 14.75 10.93 77860 108 48 36.00 252 118.75 14.75 12.16 85
1030 132 48 44.00 308 142.75 14.75 14.62 102
NOTE:1. 4-20mA control signal can be easily installed in the field with
a resistor and simple wiring.
ACTUATOR DESCRIPTION
ELECTRIC24VAC, 0-10VDC CONTROL, DIR. COUP., 266
(*) 24VAC, 0-10VDC CONTROL, DIR. COUP., 133PNEUMATIC 8-13 PSIG SPRING RANGE
30 YORK INTERNATIONAL
Engineering Data
EE2 - FR SEGMENT ECONOMIZER WITH RETURN FAN EE2 - FP(H) ECONOMIZER WITH HORIZONTAL RETURN PLENUM FAN
100% EXHAUST AIR (EA) 100% OUTSIDE AIR (OA) 100% RETURN AIR (RA)100% EA Individual 100% OA Individual 100% Mixing Damper Individ.Unit Damper Actual Dim. Damper Damper Actual Dim. Damper Damper Actual Dim. DamperSize Width Height Area Torque Width Height Area Torque Width Height Area Torque
65 20.75 20 2.88 20 20.75 20 2.88 20 20.75 20 2.88 2085 26.75 20 3.72 26 26.75 20 3.72 26 26.75 20 3.72 26105 35.75 20 4.97 35 35.75 20 4.97 35 35.75 20 4.97 35125 20.75 40 5.76 40 20.75 40 5.76 40 20.75 40 5.76 40170 26.75 40 7.43 52 26.75 40 7.43 52 26.75 40 7.43 52215 35.75 40 9.93 70 35.75 40 9.93 70 35.75 40 9.93 70250 41.75 40 11.60 81 41.75 40 11.60 81 41.75 40 11.60 81305 47.75 40 13.26 93 47.75 40 13.26 93 47.75 40 13.26 93350 41.75 *25 14.50 102 41.75 *25 14.50 102 41.75 50 14.50 102400 47.75 *25 16.58 116 47.75 *25 16.58 116 47.75 50 16.58 116460 41.75 *36 20.88 146 41.75 *36 20.88 146 41.75 72 20.88 147530 47.75 *36 23.88 167 47.75 *36 23.88 167 47.75 72 23.88 167680 53.75 *36 26.88 188 53.75 *36 26.88 188 53.75 72 26.88 188860 47.75 **33 32.83 216 47.75 **33 32.83 216 47.75 99 32.88 230
1030 59.75 **33 41.08 270 59.75 **33 41.08 270 59.75 99 41.08 288
NOTES: See notes on page 29.* 2 Dampers Stacked
** 3 Dampers Stacked
EE1 - MB SEGMENT ECONOMIZER WITHOUT RETURN FAN 100% EXHAUST AIR (EA) 100% OUTSIDE AIR (OA) 100% RETURN AIR (RA)
100% EA Individual 50% OA (Each Side) Individual 100% Mixing Damper Individ.Unit Damper Actual Dim. Damper Damper Actual Dim. Damper Damper Actual Dim. DamperSize Width Height Area Torque Width Height Area Torque Width Height Area Torque65 34.75 12 2.90 20 12 22 1.83 13 20.75 20 2.88 2085 46.75 12 3.90 27 12 22 1.83 13 26.75 20 3.72 26105 58.75 12 4.90 34 12 22 1.83 13 35.75 20 4.97 35125 34.75 24 5.80 41 12 32 2.67 19 20.75 40 5.76 40170 46.75 24 7.80 55 15 32 3.33 23 26.75 40 7.43 52215 58.75 24 9.80 69 21 32 4.67 33 35.75 40 9.93 70250 70.75 24 11.80 83 21 32 4.67 33 41.75 40 11.60 81305 82.75 24 13.80 97 32 32 7.11 50 47.75 40 13.26 93350 70.75 20.75 10.19 71 32 50 11.11 78 41.75 50 14.50 102400 82.75 20.75 11.12 84 28 50 9.72 68 47.75 50 16.58 116460 70.75 26.75 13.14 92 28 58 11.28 79 41.75 72 20.88 147530 82.75 26.75 15.37 108 33 58 13.29 93 47.75 72 23.88 167680 106.75 26.75 19.83 139 36 68 17.00 119 53.75 72 26.88 188910 118.75 45.75 37.73 264 39 104 28.17 197 47.75 99 32.88 230
1030 142.75 45.75 45.35 318 39 104 28.17 197 59.75 99 41.08 288
EE1 - MB
EE2 - FR, EE2 - FP(H)
NOTE:1. 4-20mA control signal can be easily installed in the field with
a resistor and simple wiring.
ACTUATOR DESCRIPTION
ELECTRIC24VAC, 0-10VDC CONTROL, DIR. COUP., 266
(*) 24VAC, 0-10VDC CONTROL, DIR. COUP., 133PNEUMATIC 8-13 PSIG SPRING RANGE
FORM 100.10-EG2
YORK INTERNATIONAL 31
NOTE: FP (V) and EA is same as OA and RA.
EE1, EE3 - FP(V) ECONOMIZER WITH VERTICAL RETURN PLENUM FAN 100% RETURN AIR (RA) 50% OUTSIDE AIR (OA) 100% EXHAUST AIR (EA)
100% RA Damper Individual 50% OA Individual 100% EA Individ.Unit Damper Actual Dim. Damper Damper Actual Dim. Damper Damper Actual Dim. DamperSizeWidth Height Area Torque Width Height Area Torque Width Height Area Torque
EE1- FP (V)65 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A85 26.75 20 3.72 26 12 22 1.83 13 46.75 12 3.90 27
105 35.75 20 4.97 35 12 22 1.83 13 58.75 12 4.90 34125 20.75 40 5.76 40 12 32 2.67 19 34.75 24 5.80 41170 26.75 40 7.43 52 15 32 3.33 23 46.75 24 7.80 55215 35.75 40 9.93 70 21 32 4.67 33 58.75 24 9.80 69250 41.75 40 11.60 81 21 32 4.67 33 70.75 24 11.80 83305 47.75 40 13.26 93 32 32 7.11 50 82.75 24 13.80 97
EE3 - FP (V)350 70.75 26.75 13.14 92 70.75 26.75 13.14 92 70.75 26.75 13.14 92400 82.75 26.75 15.37 108 82.75 26.75 15.37 108 82.75 26.75 15.37 108460 70.75 38.75 19.04 133 70.75 38.75 19.04 133 70.75 38.75 19.04 133530 82.75 38.75 22.27 156 82.75 38.75 22.27 156 82.75 38.75 22.27 156680 106.75 38.75 28.73 201 106.75 38.75 28.73 201 106.75 38.75 28.73 201860 118.75 45.75 37.73 264 118.75 45.75 37.73 264 118.75 45.75 37.73 264
1030 142.75 45.75 45.35 318 142.75 45.75 45.35 318 142.75 45.75 45.35 318
EE4, EE3 - FE ECONOMIZER WITH EXHAUST FAN 100% RETURN AIR (RA) 100% OUTSIDE AIR (OA) 100% EXHAUST AIR (EA)
100% RA Individual 100% OA Damper Individual 100% EA Individ.Unit Damper Actual Dim. Damper Damper Actual Dim. Damper Damper Actual Dim. DamperSizeWidth Height Area Torque Width Height Area Torque Width Height Area Torque
EE4 - FE65 15 24 2.50 18 21 20 2.92 21 18.0 21.5 2.69 N/A85 15 36 3.75 27 27 20 3.75 27 18.0 21.5 2.69 N/A
105 15 48 5.00 36 36 20 5.00 36 22.5 21.5 3.36 N/A125 24 27 4.50 32 21 40 5.83 41 25.5 21.5 3.81 N/A170 24 36 6.00 44 27 40 7.50 49 33.5 21.5 5.00 N/A215 24 48 8.00 61 36 40 10.00 69 27.5 33.5 6.40 N/A250 24 60 10.00 74 42 40 11.67 82 37.5 33.5 8.72 N/A305 24 72 12.00 84 48 40 13.33 95 37.5 33.5 8.72 N/A
EE3 - FE350 70.75 26.75 13.14 92 70.75 26.75 13.14 92 37.5 45.5 11.88 N/A400 82.75 26.75 15.37 108 82.75 26.75 15.37 108 47.5 45.5 15.00 N/A460 70.75 38.75 19.04 133 70.75 38.75 19.04 133 47.5 45.5 15.00 N/A530 82.75 38.75 22.27 156 82.75 38.75 22.27 156 57.5 57.5 22.96 N/A680 106.75 38.75 28.73 201 106.75 38.75 28.73 201 57.5 57.5 22.96 N/A860 118.75 45.75 37.73 264 118.75 45.75 37.73 264 71.5 57.5 28.55 N/A
1030 142.75 45.75 45.35 318 142.75 45.75 45.35 318 85.5 57.5 34.14 N/A
See notes on page 29.
EE1 and EE3 - FP(V)
EE4 and EE3 - FE
NOTE: EA is Barometric; no actuator required.
NOTE:1. 4-20mA control signal can be easily installed in the field with
a resistor and simple wiring.
ACTUATOR DESCRIPTION
ELECTRIC24VAC, 0-10VDC CONTROL, DIR. COUP., 266
(*) 24VAC, 0-10VDC CONTROL, DIR. COUP., 133PNEUMATIC 8-13 PSIG SPRING RANGE
32 YORK INTERNATIONAL
INLET VANES ACTUATORS WING COIL DAMPER ACTUATORSCP DWDI DWDI PLENUM
SIZE FC AF AF65 *(1) *(1) *(1)85 *(1) *(1) *(1)
105 *(1) *(1) *(1)125 *(1) *(1) *(1)170 *(1) *(1) *(1)215 (1) (1) (1)250 (1) (1) (1)305 (1) (1) (1)350 (1) (1) (1)400 (1) (1) (1)460 (2) (1) (1)530 (2) (2) (1)680 (2) (2) (2)860 (2) (2) (3)
1030 (2) (2) (4)
CP WING COILSIZE VERT / HORIZ.65 *(1)85 *(1)105 *(1)125 *(1)170 *(1)215 *(1)250 (1)305 (1)350 (1)400 (1)460 (2)530 (2)680 (2)860 N/A1030 N/A
Engineering Data
IB SEGMENTFace Damper Individual Bypass Damper IndividualUnit Damper Actual Dimensions Damper Damper Actual Dimensions DamperSize Width Height Area Torque Width Height Area Torque
65 35 16 3.89 27 35 5 1.22 985 47 16 5.22 37 47 5 1.63 11
105 59 16 6.56 46 59 5 2.05 14125 35 34 8.26 58 35 11 2.67 19170 47 34 11.10 78 47 11 3.59 25215 59 34 13.93 98 59 11 4.51 32250 71 34 16.76 117 71 11 5.42 38305 83 34 19.60 137 83 11 6.34 44350 71 52 25.64 179 71 17 8.38 59400 83 52 29.97 210 83 17 9.80 69460 71 70 34.51 242 71 23 11.34 79530 83 70 40.35 282 83 23 13.26 93680 107 70 52.01 364 107 23 17.09 120860 119 73 60.33 422 119 32 26.44 185
1030 143 73 72.49 507 143 32 31.78 222 See notes on page 29.
NOTE:1. 4-20mA control signal can be easily installed in the field with
a resistor and simple wiring.
ACTUATOR DESCRIPTION
ELECTRIC24VAC, 0-10VDC CONTROL, DIR. COUP., 266
(*) 24VAC, 0-10VDC CONTROL, DIR. COUP., 133PNEUMATIC 8-13 PSIG SPRING RANGE
FORM 100.10-EG2
YORK INTERNATIONAL 33
HUMIDIFIER DATA
PSIGUNIT SIZE
65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
2 0.40 0.44 0.42 0.43 0.59 0.43 0.46 0.40 0.41 0.33 0.33 0.44 0.42 0.40 0.435 0.69 0.68 0.65 0.67 0.70 0.75 0.74 0.72 0.68 0.64 0.64 0.68 0.68 0.63 0.69
10 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.0012 1.13 1.12 1.11 1.13 1.11 1.09 1.12 1.05 1.09 1.13 1.13 1.12 1.09 1.03 1.1315 1.25 1.26 1.27 1.30 1.29 1.23 1.25 1.20 1.24 1.28 1.28 1.38 1.31 1.19 1.2620 1.49 1.44 1.49 1.55 1.53 1.46 1.48 1.40 1.50 1.55 1.55 1.58 1.50 1.43 1.5525 1.65 1.68 1.73 1.76 1.79 1.65 1.68 1.58 1.67 1.81 1.81 1.77 1.72 1.65 1.8030 1.85 1.84 2.02 1.97 2.00 1.84 1.88 1.77 1.87 2.02 2.02 2.00 1.94 1.81 2.03
CAPACITY CORRECTION FACTORS (For steam pressures other than 10 PSIG)
SIZE SEPARATOR CAPACITY P.S.I. ORIFICE MANIFOLD OR DISPERSION TUBEMODEL LBS / HR SIZE QUANTITY MODEL LENGTH
65 91 51 10 .25 2 91 3 ft.85 91 68 10 .31 2 91 4 ft.105 91 85 10 .34 2 91 5 ft.125 92 108 10 .37 3 91 3 ft.170 92 145 10 .50 3 91 4 ft.215 93 181 10 .47 3 91 5 ft.250 93 217 10 .50 3 91 6 ft.305 93 253 10 .56 3 91 7 ft.350 93 307 10 .62 4 91 6 ft.400 93 372 10 .75 4 91 7 ft.460 93 409 10 .75 5 91 6 ft.530 94 508 10 .87 5 92 7 ft.680 94 652 10 1.00 5 92 9 ft.860 94 688 10 1.12 4 92 10 ft.1030 94 900 10 1.50 4 92 12 ft.
NOTES: 1. Pipe chase is required for humidifier control location.2. Unit section: 30" in direction of airflow (CP65 - 105).
Unit section: 33" in direction of airflow (CP125 - 680).Unit section: 48" in direction of airflow (CP860 - 1030).
HM – HUMIDIFIER SEGMENT
34 YORK INTERNATIONAL
AT – SOUND ATTENUATOR
Sound Attenuators are rated for two flow conditions,FORWARD and REVERSE. Forward flow occurs whenair and sound-waves travel in the same direction, as ina supply air duct or fan discharge. Reverse flow occurswhen sound-waves and air travel in opposing directions,as in a typical return-air system.
Because Attenuation values are generally higher in thefirst five octave bands in the reverse flow mode, com-pared to the forward flow mode, more economical si-lencer selections can often be made on the return-airsystems. These phenomena are illustrated below.
Under FORWARD FLOW conditions, high-frequencysound is refracted into the duct-silencer walls.
Under REVERSE FLOW conditions, sound is refracted awayfrom the walls and toward the center of the duct-silencer.
SELF-NOISE POWER LEVELS
ATTENUATOR ATTENUATOR FACE VEL. FLOWMINIMUM OUTLET SOUND PRESSURE (dB)
LENGTH TYPE (fpm) 1 2 3 4 5 6 7 8
3, 5 & 7 Feet STANDARD 1000 Forward 55 49 49 47 46 49 42 321000 Reverse 54 51 50 51 54 56 52 40
ATTENUATOR ATTENUATOR FACE VEL. FLOWDYNAMIC INSERTION LOSS (dB) PER OCTAVE BAND
LENGTH TYPE (fpm) 1 2 3 4 5 6 7 8
3 Feet STANDARD 1000 Forward 7 12 16 28 35 35 28 171000 Reverse 7 13 17 30 36 33 26 13
5 Feet STANDARD 1000 Forward 8 18 24 40 45 46 41 261000 Reverse 11 21 25 43 47 44 39 22
7 Feet STANDARD 1000 Forward 10 20 35 45 50 48 45 241000 Reverse 12 23 37 46 51 48 44 30
DYNAMIC INSERTION LOSS RATING
LD0005
ATTENUATOR SIZES AND QUANTITIES PER AHU SIZE
NOTE: Mylar liners are not supplied with sound attenuator, as may be required for certain hospital applications.
UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
Area (sq.ft.) 6 8 10 12 16 20 24 28 36 42 48 56 72 90 108Actuator 12 x 24 1 – 1 2 – 2 – 2 – 3 – 4 4 5 6
Size 24 x 24 1 2 2 2 4 4 6 6 9 9 12 12 16 20 24
Engineering Data
FORM 100.10-EG2
YORK INTERNATIONAL 35
DESCRIPTION
Electric heaters are of “open coil” construction, with 80%nickel, 20% chromium coil elements machine crimpedto stainless steel terminals and amply supported on ce-ramic bushing isolators. All internal wiring of controls,contactors, etc., is complete including a 120V, 60 Hzcontrol circuit transformer. Field wiring input terminalblocks are provided for code sized (125%) copper (only)conductors. Largest terminals are for 500 MCM copperconductors, so heaters requiring over 304 amps/phasewill have two or more parallel terminals per phase.
Standard electric heaters include terminals for field con-nection of 120V control circuit transformer, and fusesper N.E.C. and U.L. (on heaters exceeding 48 amps).Field wiring diagram is mounted on inside of terminalbox cover. The terminals are clearly marked and knock-outs are provided per the latest N.E.C.
Heater Segments have disc automatic thermal cut-outsand a load carrying disc manual reset cut-out for eachcircuit. A differential pressure air flow switch with veloc-ity pick-up tube can be field set to sense minimum airflow.
MINIMUM AIR FLOWS
Electric heaters differ from steam or hot water coils inthat the heat output is constant as long as the heater isenergized. Therefore, sufficient air flow must be pro-vided to prevent overheating and nuisance tripping ofthe thermal cutouts. The minimum required velocity isdetermined from the graph on the basis of entering airtemperature and watts per square foot of cross seg-mental heating coil area.
EXAMPLE: Determine whether the minimum air veloc-ity requirement is met for a 108 kW heater installed witha CP400 Air Handling Unit. The unit is operating at 18,000cfm at a maximum inlet temperature of 65°F.
1. Heating Coil Area = 33 sq. ft.NOTE: Heating Coil Areas are found on page 38.
2. kW per sq ft. = 108 kW = 3.3 kW / sq. ft. 33 sq. ft.
3. Use top curve (below 80°F inlet air). Find 3.3 kW persquare foot on the vertical axis. Read the minimumface velocity required, which in this case is 205 feetper minute (fpm).
4. Air Handling Unit Face Velocity =
18,000 cfm = 545 fpm
33 sq. ft.
Since 545 FPM exceeds the minimum velocity require-ment of 205 FPM, this installation is satisfactory forheater operation.
APPLICATION / SELECTION
Equations:
EQUATION 1: MBH = kW x 3.412
EQUATION 2: ∆ T = kW x 3160
Scfm
EQUATION 3: Actual kW = Rated kW x V actual
V rated
EQUATION 4: Load Amps = kW x 1000 V x √ 3
EH – ELECTRIC HEAT
LD02453
36 YORK INTERNATIONAL
EH – ELECTRIC HEAT
UNIT MINIMUM MAXIMUM kW COIL FACESIZE kW @ 208/240V @ 480V AREA (Ft2)65 8 30 60 3.285 12 40 80 4.9105 16 50 100 6.6125 20 60 120 7.0170 25 80 165 10.8215 25 100 200 13.8250 40 140 280 18.0305 40 140 280 21.0350 65 160 320 28.0400 65 160 320 33.0460 65 160 320 39.0530 85 160 320 46.4680 85 160 320 60.3860 95 180 360 66.11030 115 210 425 79.4
ELECTRIC HEAT CAPACITY
208 VOLTS 240 VOLTS 480 VOLTSUNIT 1-2 3-6 7-8 1-2 3-6 7-8 1 2-6 7-8SIZE (# STAGES/ (# STAGES/ (# STAGES/ (# STAGES/ (# STAGES/ (# STAGES/ (# STAGES/ (# STAGES/ (# STAGES/
CIRCUIT) CIRCUIT) CIRCUIT) CIRCUIT) CIRCUIT) CIRCUIT) CIRCUIT) CIRCUIT) CIRCUIT)65 24 42 42 24 42 42 24 42 4285 24 42 42 24 42 42 24 42 42105 24 42 42 24 42 42 24 42 42125 24 30 30 24 30 30 24 30 30170 24 30 30 24 30 30 24 30 30215 24 30 30 24 30 30 24 30 30250 24 30 30 24 30 30 24 30 30305 24 30 30 24 30 30 24 30 30350 24 30 30 24 30 30 24 30 30400 24 30 30 24 30 30 24 30 30460 24 30 30 24 30 30 24 30 30530 24 30 30 24 30 30 24 30 30680 24 30 30 24 30 30 24 30 30860 24 30 30 24 30 30 24 30 301030 24 30 30 24 30 30 24 30 30
SEGMENT LENGTH BY VOLTAGE AND NUMBER OF STAGES CIRCUITS (in.)
NOTES: 1. When step controller, SCR controller or disconnect is required, the EH42 segment must be used.2. Segment size may change depending on kW of heat or SCR controller selected.
Engineering Data
TO DETERMINE CIRCUITS:
# Circuits =kW x 1000
V x 3 x 48
Always Round Up To Next Whole Number
√√√√√
FORM 100.10-EG2
YORK INTERNATIONAL 37
IG – INDIRECT FIRED GAS HEATER
DESCRIPTION
Indirect Fired Gas Heater section consists of the stain-less steel primary and secondary heat exchanger withthe power burner design. The basic design allows thepower burner to inject the correct ratio of air and gas intothe primary heat exchanger where the main combustionoccurs. The heated products of combustion then passthrough the multiple secondary tubes heating each tubefor maximum heat transfer. The products of combustionthen pass to the inducer draft fan and through the flue.The air is heated by passing around the primary andsecondary tubes for optimal heat transfer. The heater isdesigned for 80% efficiency.
The furnace is U.L. approved but not the unit and comeswired with all necessary safety controls and valves in-stalled. The controls vary based on the BTU level and
Insurance Requirements selected. These units are de-signed to handle Natural Gas as a standard and can beselected to operate on LP Gas. The gas pressure avail-able at the unit of either type needs to be consideredwhen ordering the equipment.
APPLICATION / SELECTION
The nomenclature indicating the size of the heater refersto 10,000 BTUs. Example: the Size 25 that can be se-lected in a CP-44 refers to 250,000 BTU output.
Equations:
BTU Output Required =cfm x 1.08 x Temperature Rise Required
BTU Input = BTU Output ÷ .80
TURNDOWN OPTIONS AND GUIDELINES
The CurbPak furnaces are available with the followingburner firing arrangements.
ON/OFF FIRING: The burner in the on position firesat full rating
TWO-STAGE: The burner fires at 50% capacityon Low fire and 100% capacity onHigh fire
3-1 MODULATION: The burner will modulate for 100%- 33% of full fire
10-1 MODULATION: The burner will modulate from100% - 10% of full fire
When choosing the proper turn down three issues shouldbe considered.1. Greater modulation provides improved temperature
control. If the furnace is modulated to its minimumfire position, and controls determine there is too muchfurnace capacity, then the furnace is staged on andoff, on carefully chosen time delays, to satisfy thelight load heating requirements. The 3-1 option is gen-erally sufficient particularly if design temperature risedoes not exceed 30-40 degrees.
2. The greater the range of modulation the greater thecost.
3. Experience requires that a furnace should not turndown to a temperature rise less than 5-8 degrees.
Greater modulation decreases the flue stack tempera-ture at low fire, increases the amount of condensa-tion, and can decrease the life of the heat exchangereven though all CP furnaces utilizes a 430 stainlesssteel primary and 409 stainless steel secondary heatexchanger tubes along with condensate drains. Thesegrades of stainless steel have been selected for theideal combination of thermal and corrosion protection.The condensate line must be adequately sized,trapped, along with drainage of the condensate perlocal code.
TEMPERATURE RISE VERSUS FIRING RATECONSIDERATIONS
1. Furnace design temperature rise is less than 25 de-grees: Only Single or Two-Stage furnaces are recom-mended.
2. Furnace design temperature rise is 15-49 degrees:The 3:1 option is the only modulation option availableand modulates down to 5-16 degrees temperature rise.
3. Furnace temperature rise is 50-70 degrees: The 3:1burner is strongly recommended instead of the 10-1furnace.
4. Furnace temperature rise is 70-100 degrees: Both 3:1and 10:1 Modulation can be considered.
38 YORK INTERNATIONAL
INSURANCE OPTIONS & LOCAL CODE REQUIREMENTS
There are two types of pipe trains available on powerduct furnaces. The insurance options for these pipe trainsare as follows:
a. IRI – Industrial Risk Insurersb. FM – Factory Mutual
GAS PRESSURE REQUIREMENTS
The CurbPak furnaces are designed to handle a widerange of inlet gas pressures as listed below. Exact val-ues depend on the required options and capacity of thefurnace. These limits must be adhered to in order to ob-tain safe and reliable performance. Please allow this tosupersede all previous data.
If the gas pressure exceeds the furnace maximum thenthe field must provide a pressure regulator to reduce theinlet pressure to acceptable levels.
Engineering Data
All IRI gas trains are provided with atmospheric vents onthe vent valve piped to the exterior of the unit. Local codesand project requirements vary. For this reason, salesmust carefully review the requirements that apply to thearea where the equipment is to be installed.
If the inlet pressures fall short of the furnace minimumthe field must provide a booster pump to increase inletpressure to acceptable levels.
The YORK pressure range is competitive, however, notethat the extra turn down, associated with a 10-1 burnerrequires a greater inlet pressure.
BURNER INLET GAS PRESSURE REQUIREMENTSBTU ON/OFF, 2-STAGE,3:1 MODULATION 10:1 MODULATIONPER MINIMUM MAXIMUM MINIMUM MAXIMUM10,000 U.L./FM IRI U.L. FM/IRI U.L. FM/IRI U.L. FM/IRI25 5" 5" 14" 13" 20"30 5" 5" 14" 13" 20"35 5" 6" 14" 13" 20"40 5" 6" 14" 13" 20"45 5" 6" 14" 13" 20"50 5" 6" 14" 13" 20"60 5" 6" 14" 13" 20"75 5" 6" 14" 13" 1 PSI85 5" 7" 14" 13" 1 PSI100 6.5" 9" 14" 18" 1 PSI125 6" 7" 14" 18" 1 PSI150 6" 8" 14" 13" 1 PSI175 7.5" 11" 14" 13" 2 PSI200 9.5" 13" 14" 13" 2 PSI225 7" 9" 14" 13" 2 PSI250 7.9" 9.2" 14" 13" 2 PSI275 9.9" 10.5" 14" 20" 2 PSI300 11.0" 12.5" 14" 20" 2 PSI
FORM 100.10-EG2
YORK INTERNATIONAL 39
FURNACE MBH AVAILABILITY (OUTPUT)UNIT SIZE
MBH 170 215 250 305 350 400 460 530 680 860 1030150 - 250300 - 400450 - 500600 - 750850 - 10001250 - 15001750 - 20002250 - 3000
INPUT MIN. MAX. A.P.D. @ A.P.D.@HTG OUTPUT (CFH) AIRFLOW AIRFLOW GAS CONN. MINIMUM MAXIMUMMODEL (MBH) (NPT) AIRFLOW AIRFLOW(1) (CFM) (CFM) (IN. W.G.) (IN. W.G.)
15 150 188 1736 4500 3/4 0.23 1.4720 200 250 2315 4500 3/4 0.40 1.4725 250 313 2894 4500 3/4 0.61 1.4730 300 375 3472 7000 1 0.31 1.4535 350 438 4051 7111 1 0.43 1.4540 400 500 4630 7000 1 0.58 1.4545 450 563 5208 9000 1 0.51 1.3850 500 625 5787 9000 1 0.61 1.3860 600 750 6944 12000 1 0.59 1.7075 750 938 8681 12000 1 0.92 1.7085 850 1063 9838 18000 1 0.62 2.00100 1000 1250 11574 18000 1-1/4 0.84 2.00125 1250 1563 14468 25000 1-1/4 0.62 1.75150 1500 1875 17361 25000 1-1/4 0.86 1.80175 1750 2188 20255 34000 1-1/2 0.65 1.80200 2000 2500 23148 34000 1-1/2 0.83 1.80225 2250 2813 26042 54000 2 0.40 1.71250 2500 3125 28935 54000 2 0.49 1.71275 2750 3438 31829 54000 2 0.60 1.71300 3000 3750 34722 54000 2 0.71 1.71
NOTES:(1) Based on 1,000 BTU/CU Ft. natural gas.Furnace includes a 430 series stainless steel primary and 409 series stainless steel secondary heat exchangers, condensate drain,combustion air blower / motor, air-proving switch, flame safeguard control, spark ignited pilot, electric main gas valve, main and pilot gas cocks.
POWER BURNER FURNACES
40 YORK INTERNATIONAL
Engineering Data
ITEM DF-15, 20 & 25U.L. (STD) U.L.C. FM IRI
1. TEST CONN., GAS PRESSURE2. BUTTERFLY VALVE, OPTIONAL MODULATED BURNERS ONLY3. FIRING VALVE, MANUAL OPT. OPT. OPT. OPT.4. MAIN AUTO. GAS VALVE* SOL. SOL. SOL. SOL.5. AUX. GAS VALVE6. MAIN PRESSURE REGULATOR*7. MAIN LINE SHUT-OFF VALVE8. PILOT SOLENOID VALVE9. PILOT PRESSURE REGULATOR
10. PILOT SHUT-OFF VALVE11. HIGH GAS PRESSURE SWITCH OPT. OPT. OPT. OPT.12. LOW GAS PRESSURE SWITCH OPT. OPT. OPT. OPT.NOTES:*Items 4 & 6 may be combined in one assembly.OPT. denotes Optional ItemsU.L. Listed burners firing less than 400,000 BTU comply with FM & IRI requirements.
GAS TRAIN – DF-15, 20 & 25
BURNER
1 21 1
11
PILOT
3
4 1 5
12
S S
S
6
GAS INLET
8 9 10
LD06770
FORM 100.10-EG2
YORK INTERNATIONAL 41
ITEM DF-30, 35 & 40U.L. (STD) U.L.C. FM IRI
1. TEST CONN., GAS PRESSURE2. BUTTERFLY VALVE, OPTIONAL MODULATED BURNERS ONLY3. FIRING VALVE, MANUAL 35 & 40 – 35 & 40 35 & 404. MAIN AUTO. GAS VALVE* SOL. SOL. SOL. SOL.5. AUX. GAS VALVE** **6. MAIN PRESSURE REGULATOR*7. MAIN LINE SHUT-OFF VALVE8. PILOT SOLENOID VALVE9. PILOT PRESSURE REGULATOR
10. PILOT SHUT-OFF VALVE11. HIGH GAS PRESSURE SWITCH OPT. OPT. OPT.12. LOW GAS PRESSURE SWITCH OPT. OPT. OPT.NOTES:*Items 4 & 6 may be combined in one assembly.**Items 4 & 5 can be replaced by one Motorized valve with Proof-of-Closure (POC) switch.OPT. denotes Optional ItemsU.L. Listed burners firing less than 400,000 BTU comply with FM & IRI requirements.
GAS TRAIN – DF-30, 35 & 40
LD06771
BURNER
1 21 1
11
PILOT
3
4 1 5
12
S S
S
6
GAS INLET
8 9 101
42 YORK INTERNATIONAL
Engineering Data
GAS TRAIN – DF-45 & 50
NOTES:*Items 4 & 6 may be combined in one assembly.**Items 4 & 5 can be replaced by one Motorized valve with Proof-of-Enclosure (POC) switch.OPT. denotes Optional Items
LD06772
BURNER
1 21 1
11
PILOT
3
4 1 5
12
S S
S
6
GAS INLET
8 9 101
ITEM DF-45 & 50U.L. (STD) U.L.C. FM IRI
1. TEST CONN., GAS PRESSURE2. BUTTERFLY VALVE, OPTIONAL MODULATED BURNERS ONLY3. FIRING VALVE, MANUAL4. MAIN AUTO. GAS VALVE* SOL. SOL. SOL. MOT.5. AUX. GAS VALVE** **6. MAIN PRESSURE REGULATOR*7. MAIN LINE SHUT-OFF VALVE8. PILOT SOLENOID VALVE9. PILOT PRESSURE REGULATOR
10. PILOT SHUT-OFF VALVE11. HIGH GAS PRESSURE SWITCH OPT. OPT. OPT.12. LOW GAS PRESSURE SWITCH OPT. OPT. OPT.
FORM 100.10-EG2
YORK INTERNATIONAL 43
GAS TRAIN – DF-60 & 75
LD06773
BURNER
1 21 1
11
PILOT
3
4 1 5
12
S S
S
6
GAS INLET
8 9 101
ITEM DF-60 & 75U.L. (STD) U.L.C. FM IRI
1. TEST CONN., GAS PRESSURE2. BUTTERFLY VALVE, OPTIONAL MODULATED BURNERS ONLY3. FIRING VALVE, MANUAL4. MAIN AUTO. GAS VALVE* SOL. SOL. SOL. MOT.5. AUX. GAS VALVE** **6. MAIN PRESSURE REGULATOR*7. MAIN LINE SHUT-OFF VALVE8. PILOT SOLENOID VALVE9. PILOT PRESSURE REGULATOR
10. PILOT SHUT-OFF VALVE11. HIGH GAS PRESSURE SWITCH OPT. OPT. OPT.12. LOW GAS PRESSURE SWITCH OPT. OPT. OPT.NOTES:*Items 4 & 6 may be combined in one assembly.**Items 4 & 5 can be replaced by one Motorized valve with Proof-of-Closure (POC) switch.OPT. denotes Optional Items
44 YORK INTERNATIONAL
Engineering DataEngineering Data
GAS TRAIN – DF-85 & 100
ITEM DF-85 & 100U.L. (STD) U.L.C. FM IRI
1. TEST CONN., GAS PRESSURE2. BUTTERFLY VALVE, OPTIONAL MODULATED BURNERS ONLY3. FIRING VALVE, MANUAL – – –4. MAIN AUTO. GAS VALVE* SOL. SOL. SOL. MOT.5. AUX. GAS VALVE** **6. MAIN PRESSURE REGULATOR*7. MAIN LINE SHUT-OFF VALVE8. PILOT SOLENOID VALVE9. PILOT PRESSURE REGULATOR
10. PILOT SHUT-OFF VALVE11. HIGH GAS PRESSURE SWITCH OPT. OPT. OPT.12. LOW GAS PRESSURE SWITCH OPT. OPT. OPT.13. N.O. VENT VALVE – – –
NOTES:*Items 4 & 6 may be combined in one assembly.**Items 4 & 5 can be replaced by one Motorized valve with Proof-of-Enclosure (POC) switch.OPT. denotes Optional Items
LD06774
BURNER
1 21 1
11
PILOT
3
4 1 5
12
M S
S
6
GAS INLET
8 9 101
S
FORM 100.10-EG2
YORK INTERNATIONAL 45
GAS TRAIN – DF-125 & 150
ITEM DF-125 & 150U.L. (STD) U.L.C. FM IRI
1. TEST CONN., GAS PRESSURE2. BUTTERFLY VALVE, OPTIONAL MODULATED BURNERS ONLY3. FIRING VALVE, MANUAL – – –4. MAIN AUTO. GAS VALVE* SOL. SOL. SOL. MOT.5. AUX. GAS VALVE** **6. MAIN PRESSURE REGULATOR*7. MAIN LINE SHUT-OFF VALVE8. PILOT SOLENOID VALVE9. PILOT PRESSURE REGULATOR
10. PILOT SHUT-OFF VALVE11. HIGH GAS PRESSURE SWITCH OPT. OPT. OPT.12. LOW GAS PRESSURE SWITCH OPT. OPT. OPT.13. N.O. VENT VALVE – – –
NOTES:*Items 4 & 6 may be combined in one assembly.**Items 4 & 5 can be replaced by one Motorized valve with Proof-of-Closure (POC) switch.OPT. denotes Optional ItemsU.L. Listed burners comply with FM requirements.
LD06775
BURNER
1 21 1
11
PILOT
3
4 1 5
12
M S
S
6
GAS INLET
8 9 101
S
46 YORK INTERNATIONAL
Engineering DataEngineering Data
GAS TRAIN – DF-175 & 200
NOTES:*Items 4 & 6 may be combined in one assembly.**Items 4 & 5 can be replaced by one Motorized valve with Proof-of-Enclosure (POC) switch.OPT. denotes Optional ItemsU.L. Listed burners comply with FM requirements.
ITEM DF-175 & 200U.L. (STD) U.L.C. FM IRI
1. TEST CONN., GAS PRESSURE2. BUTTERFLY VALVE, OPTIONAL MODULATED BURNERS ONLY3. FIRING VALVE, MANUAL – – –4. MAIN AUTO. GAS VALVE* SOL. SOL. SOL. MOT.5. AUX. GAS VALVE** **6. MAIN PRESSURE REGULATOR*7. MAIN LINE SHUT-OFF VALVE8. PILOT SOLENOID VALVE9. PILOT PRESSURE REGULATOR
10. PILOT SHUT-OFF VALVE11. HIGH GAS PRESSURE SWITCH OPT. OPT. OPT.12. LOW GAS PRESSURE SWITCH OPT. OPT. OPT.13. N.O. VENT VALVE – – –
LD06776
BURNER
1 21 1
11
PILOT
3
4 1 5
12
M S
S
6
GAS INLET
8 9 101
S
FORM 100.10-EG2
YORK INTERNATIONAL 47
GAS TRAIN – DF-225, 250, 275 & 300
ITEM DF-225, 250, 275 & 300U.L. (STD) U.L.C. FM IRI
1. TEST CONN., GAS PRESSURE2. BUTTERFLY VALVE, OPTIONAL MODULATED BURNERS ONLY3. FIRING VALVE, MANUAL – – –4. MAIN AUTO. GAS VALVE* SOL. 2-SOL. SOL. SOL.5. AUX. GAS VALVE6. MAIN PRESSURE REGULATOR*7. MAIN LINE SHUT-OFF VALVE8. PILOT SOLENOID VALVE9. PILOT PRESSURE REGULATOR
10. PILOT SHUT-OFF VALVE11. HIGH GAS PRESSURE SWITCH – OPT. – –12. LOW GAS PRESSURE SWITCH – OPT. – –NOTES:*Items 4 & 6 may be combined in one assembly.OPT. denotes Optional Items
LD06777
BURNER
1 21 1
11
PILOT
3
4 1 5
12
M S
S
6
GAS INLET
8 9 101
S
48 YORK INTERNATIONAL
Unit SelectionSELECTING A CURBPAK AIR HANDLING UNITCurbPak air handling units permit selection of compo-nents to meet individual job requirements. The wide se-lection of basic segments, optional components, coils,and accessories, enables the design engineer to obtainoptimum performance and temperature control.
Selection of the optimum system for each individual ap-plication requires only the following simple steps:Step 1 - Select Unit Size Based on Coil Face Velocity.Step 2 - Choose the Segments Required for the System.Step 3 - Select Coils from the YORK Computer Selection Program.Step 4 - Calculate the Total Static Pressure (TSP) of the Unit.Step 5 - Select Fan & Determine Fan Brake Horsepower (BHP) &RPM.
STEP 1SELECT UNIT SIZE
Minimum Coil Area = cfm Maximum Coil Face Velocity
Select the unit size that has the minimum coil area avail-able. Cooling coils are typically selected at 500 fpm, whileheating coils are typically selected at 700-800 fpm.
The Quick Selection Tables on page 13 should be usedto determine unit size.
STEP 2CHOOSE THE SEGMENTS
Select the various segments required to satisfy the sys-tem. This includes fan, coil, filter, inlet and any other seg-ment required for the particular application.
STEP 3SELECT COILS
Select the heating and/or cooling coils by using theYorkWorks Coil Selection Program.
STEP 4CALCULATE THE TOTAL STATIC PRESSURE
Utilizing the schematic diagrams on pages 42-43, de-fine the items that must be included to calculate thestatic pressure for the supply and/or return air fan. TheInternal Static Pressure (ISP) is the sum of the air pres-sure drops for the internal components.Determine the face velocity of all the components.
Face Velocity = cfm Area
The Air Pressure Drop tables on pages 41-55 should beused to determine the static pressure of each componentbased on component face velocity.NOTE: The listed filter pressure drops are for clean fil-
ters. The approximate pressure drop of dirty fil-
ters is twice the air pressure drop of clean fil-ters. The best estimate is an average of the two(2) values.
The TSP equals the sum of all the internal static pres-sures and the external static pressure (TSP = ISP + ESP).
STEP 5SELECT FAN
The Fan and Motor Data tables on pages 18-20 showsthe available fan sizes in each unit size. Based on the fansize, cfm and TSP, enter the appropriate fan curve andread BHP and RPM.Account for belt and drive losses by adding 3-6% to thefan BHP. Select the appropriate motor size to accommo-date the fan BHP.
SELECTION EXAMPLE: Specified Conditions:
UNIT DESIGN: 17,000 cfm1.25" ESP
COOLING COIL 500 fpm maximum face velocityDESIGN: 80°F/67°F entering air temperature
55°F/54°F leaving air temperature44°F entering water temperature 65 GPM
HEATING COIL 40°F entering air temperatureDESIGN: 90°F leaving air temperature
10 PSIG steam
COMPONENT Draw-throughREQUIREMENTS: Constant volume
Airfoil fan wheel, down discharge5/8" OD cooling coil1" OD steam distributing coil2" pleated filters (angle configuration)Mixing box (100% OA/RA)Low leak dampers
SELECTION:
1. Minimum coil area = 17,000 cfm = 34 square feet 500 fpm
Select a size CP350 (34.8 square feet).
2. Choose unit segments based on Component RequirementsFS - SC - HC - AF - MB
3. YorkWorks Coil Selection Program OutputCooling Coil: 6 row/10 fpi; 0.80" APDHeating Coil: 1 row/12 fpi: 0.18" APD
4. Calculate Unit TSP1.25" ESP (given)0.80" Cooling Coil (YORK Coil Selection Program)0.18" Heating Coil (YORK Coil Selection Program)0.20" 2" Pleated Filter - Average of Clean & Dirty APD0.26" (Where Clean APD = 0.13" & Dirty APD = 0.26")
Filter fpm = 17,000 cfm = 236 fpm 72 sq. ft.
0.32" OA / RA DamperDamper fpm = 17,000 cfm = 1511 fpm
11.25 sq. ft.2.75" = TSP
5. From the CurbPak Fan Curve the fan BHP is 12.2 and the RPMis 1620. Include 6% for est. drive losses, BHP = 12.93. A 15 HPmotor is selected.
FORM 100.10-EG2
YORK INTERNATIONAL 49
Air Pressure Drop
SYSTEM EFFECT FACTOR (SEF)
The performance of fans is determined with a straightduct on the fan outlet. This duct configuration was usedin testing to develop the fan performance curves. There-fore, when the fan is applied without sufficient outletduct, the SEF must be accounted for to use the FanTables, Form 100.10-EG1.1. This does not apply toducted outlet fans with a minimum length of straightduct that measures three times the fan diameter. Thefan velocity APD table on page 49 contains values forsystem effect at various velocities.
The air pressure drop tables are presented to accountfor the difference between the return and the supply air.This is almost always the case since air is exhaustedfrom kitchens, rest rooms, etc.
REFERENCE LITERATUREFAN PERFORMANCE CURVES AND TABLES ....................................................................... 100.10-EG1.1DRAINABLE WATER (DW) AND DIRECT EXPANSION (DX) 5/8" O.D. TUBES ..................... 105.17-EG1DRAINABLE WATER (DW) DIRECT EXPANSION (DX) 1/2" O.D. TUBES .............................. 105.18-EG1NON-FREEZE STEAM COILS (SDC) 1" O.D. TUBES ............................................................ 105.26-EG2AIR-MODULATOR .................................................................................................................... 100.40-EG1
AIR PRESSURE DROP
STATIC PRESSURE CALCULATIONS
Use examples and schematic diagrams on pages 42and 43 as a guide to calculating the Total Static Pres-sure for use with the fan curves. Modify the examples tosuit the actual application.
VELOCITY PRESSURE DROP
AMCA Standard 201 is the basis of all static calcula-tions and fan applications in the CurbPak. This stan-dard details the velocity pressure drop that occurs withunducted DWDI fans (return air fans). AMCA fan rat-ings are done with an outlet duct of 3 fan diameters inlength.
The velocity pressure drop is based on fan outlet veloc-ity and must be taken into consideration with return fanapplications and supply fans that are not followed bythe minimum AMCA recommended length of straightduct.
ALTITUDE/TEMPERATURE CONVERSION FACTORS
AIR ALTITUDE (FEET)TEMP. °F 0 1000 2000 3000 4000 5000 6000 7000 8000
-20 1.20 1.16 1.12 1.08 1.04 1.00 .97 .93 .890 1.15 1.10 1.06 1.02 .99 .95 .92 .88 .85
20 1.11 1.06 1.02 .98 .95 .92 .88 .85 .8240 1.06 1.02 .98 .94 .91 .88 .84 .81 .7860 1.02 .98 .94 .91 .88 .85 .81 .79 .7670 1.00 .96 .93 .89 .86 .83 .80 .77 .7480 .98 .94 .91 .88 .84 .81 .78 .75 .72
100 .94 .91 .88 .84 .81 .78 .75 .72 .70120 .92 .88 .85 .81 .78 .76 .72 .70 .67140 .89 .85 .82 .79 .76 .73 .70 .68 .65160 .85 .82 .79 .76 .74 .70 .68 .65 .63200 .80 .77 .75 .72 .69 .67 .64 .62 .60250 .75 .72 .69 .67 .65 .62 .60 .58 .56
50 YORK INTERNATIONAL
Air Pressure Drop
The Air Pressure Drop Tables (Pages 44 thru 55) are tobe used to determine the unit internal resistance. Theinternal resistance, along with the supply duct pressuredrops, return duct pressure drops and external staticpressures should be used to select supply, return and/
INSTRUCTIONS FOR USING AIR PRESSURE DROP TABLESor exhaust fans from the fan performance curves andTables, Form 100.10-EG1.1. The Engineering Data Ta-bles, provide the necessary data (face areas) to de-velop the face velocity required to use the appropriateAir Pressure Drop Tables.
STATIC PRESSURESCHEMATIC
LD06030
LD06003
Example 1: An air handler is being selected for 13,000 cfm. The application is at sea level, with a design of 70°F.
Example 2: An air handler is being selected for 20,000 cfm. The application is at 5000 ft. above sea level, with adesign of 60°F.
STATIC PRESSURESCHEMATIC
SUPPLY (In. W.G.) RETURN (In. W.G.)Specified External 1.50 .5Internal: Economizer (EE / FR) Mixing Damper Pressure Drop .09
Mixing Damper Opening Pressure Drop .12Mixing Plenum Pressure Drop –.10Return Air Opening Pressure Drop .26Exhaust Plenum Pressure Drop .10
Flat Filter (FF) Throwaway Media .23 Electric Heat (EH) .19 Medium Coil Segment (MC) 4-Row, 12 FPI cooling coil .42
2-Row, 12 FPI heating coil .14 Velocity Pressure Drop .32
TOTAL STATIC PRESSURE: 2.59 1.18 ALTITUDE/TEMPERATURE CORRECTION FACTOR: X 1.0
Corrected Total Static Pressure: 2.59 1.18
SUPPLY (In. W.G.) RETURN (In. W.G.)Specified External 1.50 .5Internal: Economizer (EE / FE) Mixing Damper Pressure Drop .06
Mixing Damper Opening Pressure Drop .09Exhaust Air Damper Pressure Drop .39Return Air Opening Pressure Drop .27 .37Return Air Grating Pressure Drop .08 .12
Angle Filter (AF) Throwaway Media .08 Short Coil Segment (SC) 4-Row, 12 FPI cooling coil .63 Indirect-fired Gas (IG) .61 Velocity Pressure Drop .34
TOTAL STATIC PRESSURE: 3.66 1.38 ALTITUDE/TEMPERATURE CORRECTION FACTOR: x 0.85
Corrected Total Static Pressure: 3.11 1.17
FORM 100.10-EG2
YORK INTERNATIONAL 51
LD06031
Example 3: An air handler is being selected for 40,000 cfm. The application is at 1000 ft. above sea level, with adesign of 80°F.
STATIC PRESSURE SCHEMATIC
SUPPLY (In. W.G.) RETURN (In. W.G.)Specified External 1.50 .5Internal: Economizer (EE / FP) Mixing Damper Pressure Drop .12
Mixing Damper Opening Pressure Drop .21Mixing Plenum Pressure Drop –.10Return Air Opening Pressure Drop .21Exhaust Plenum Pressure Drop .10
Flat Filter (FF) Throwaway Media .22 Integral Face & Bypass (IC) .37 Short Coil Segment (SC) 4-Row, 12 FPI cooling coil .39 Plenum Fan Segment (FP) Rigid Filter (RF) Rear Load High Efficiency – 60-65% .34 Discharge Plenum (DP) Opening Pressure Drop .21
Grating Pressure Drop .07
TOTAL STATIC PRESSURE: 3.33 .81 ALTITUDE CORRECTION FACTOR: x 0.94
Corrected Total Static Pressure: 3.12 .76
52 YORK INTERNATIONAL
Air Pressure Drop5/8 INCH (CDW or CDX) FOR COOLING AND DEHUMIDIFYING (IN. W.G.)WET COIL For Standard Air
ROWS FPI AIR VELOCITY (fpm)400 425 450 475 500 525 550 575 600
8 0.35 0.38 0.42 0.45 0.48 0.52 0.56 0.59 0.63
4 10 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.69 0.7312 0.45 0.50 0.55 0.59 0.64 0.70 0.75 N/A N/A14 0.50 0.56 0.52 N/A N/A N/A N/A N/A N/A8 0.53 0.58 0.63 0.68 0.73 0.78 0.83 0.89 0.9
6 10 0.60 0.66 0.72 0.78 0.84 0.90 0.97 1.03 1.1012 0.68 0.75 0.82 0.89 0.97 1.04 1.12 N/A N/A14 0.76 0.84 0.92 N/A N/A N/A N/A N/A N/A8 0.70 0.77 0.83 0.90 0.97 1.04 1.11 1.18 1.25
8 10 0.80 0.88 0.95 1.03 1.12 1.20 1.29 1.37 1.4612 0.91 1.00 1.09 1.19 1.29 1.39 1.50 N/A N/A14 1.02 1.12 1.23 N/A N/A N/A N/A N/A N/A8 0.87 0.95 1.04 1.12 1.20 1.29 1.38 1.47 1.56
10 10 0.99 1.09 1.18 1.28 1.39 1.49 1.60 1.71 1.8212 1.12 1.24 1.35 1.47 1.60 1.72 1.86 N/A N/A14 1.25 1.39 1.52 N/A N/A N/A N/A N/A N/A8 1.05 1.14 1.24 1.34 1.44 1.55 1.65 1.76 1.87
12 10 1.19 1.30 1.42 1.54 1.66 1.79 1.92 2.04 2.1812 1.35 1.48 1.62 1.77 1.91 2.07 2.23 N/A N/A14 1.51 1.66 1.82 N/A N/A N/A N/A N/A N/A
NOTE: Shaded area available for standard coils only. No tall or stacked coils.
5/8 INCH (CDW) FOR HEATING AND (CDW or CDX) FOR SENSIBLE COOLING (IN. W.G.)DRY COIL For Standard Air
ROWS FPI AIR VELOCITY (fpm)400 450 500 550 600 700 800 900* 1000*
8 0.07 0.09 0.10 0.12 0.14 0.19 0.23 0.29 0.34
1 10 0.08 0.10 0.12 0.14 0.16 0.21 0.26 0.32 0.3812 0.09 0.11 0.13 0.15 0.18 0.23 0.29 0.35 0.4214 0.10 0.12 0.14 0.17 0.20 0.25 0.32 0.38 0.468 0.14 0.17 0.21 0.25 0.28 0.37 0.47 0.57 0.68
2 10 0.16 0.20 0.23 0.27 0.32 0.41 0.52 0.63 0.7612 0.18 0.22 0.26 0.31 0.36 0.46 0.58 0.70 0.8414 0.20 0.24 0.29 0.35 0.40 0.51 0.64 0.77 0.948 0.28 0.35 0.42 0.49 0.57 0.74 0.93 1.14 1.37
4 10 0.32 0.39 0.47 0.55 0.64 0.83 1.04 1.26 1.5112 0.36 0.44 0.52 0.61 0.71 0.92 1.15 1.40 1.6714 0.40 0.49 0.57 0.67 0.78 1.01 1.26 1.54 1.838 0.73 0.52 0.62 0.73 0.85 1.11 N/A N/A N/A
6 10 0.48 0.59 0.70 0.82 0.95 1.24 N/A N/A N/A12 0.54 0.66 0.79 0.92 1.07 1.38 N/A N/A N/A14 0.60 0.73 0.88 1.02 1.19 1.52 N/A N/A N/A8 0.57 0.69 0.83 0.98 1.14 1.48 N/A N/A N/A
8 10 0.64 0.78 0.93 1.10 1.27 1.64 N/A N/A N/A12 0.72 0.88 1.05 1.23 1.42 1.84 N/A N/A N/A14 0.80 0.98 1.17 1.36 1.57 2.03 N/A N/A N/A8 0.71 0.87 1.04 1.22 1.42 1.85 N/A N/A N/A
10 10 0.80 0.98 1.14 1.37 1.59 2.06 N/A N/A N/A12 0.90 1.10 1.31 1.54 1.78 2.30 N/A N/A N/A14 1.00 1.22 1.45 1.71 1.97 N/A N/A N/A N/A8 0.85 1.04 1.25 1.47 1.70 2.22 N/A N/A N/A
12 10 0.96 1.17 1.40 1.64 1.91 2.48 N/A N/A N/A12 1.08 1.32 1.57 1.84 2.13 2.76 N/A N/A N/A14 1.20 1.47 1.74 2.04 2.35 N/A N/A N/A N/A
NOTE: * Beyond the scope of ARI certification for heating applications.
FORM 100.10-EG2
YORK INTERNATIONAL 53
1/2 INCH (BDW OR BDX) COIL FOR COOLING AND DEHUMIDIFYING (IN. W.G.)WET COIL For Standard Air
1/2 INCH (BDW) COIL FOR HEATING AND (BDW OR BDX) FOR SENSIBLE COOLING (IN. W.G.)DRY COIL For Standard Air
ROWS FPI AIR VELOCITY (fpm)
300 325 350 375 400 425 450 475 500 525 550 6008 0.06 0.08 0.09 0.10 0.10 0.12 0.13 0.14 0.15 0.16 0.18 0.23
2 10 0.08 0.09 0.10 0.12 0.13 0.14 0.15 0.17 0.18 0.20 0.21 0.2712 0.10 0.11 0.12 0.14 0.16 0.17 0.18 0.20 0.21 0.23 0.25 N/A14 0.12 0.13 0.14 0.16 0.18 0.19 0.20 0.22 0.23 0.25 0.27 N/A8 0.13 0.15 0.17 0.19 0.21 0.23 0.26 0.28 0.30 0.33 0.35 0.45
4 10 0.17 0.19 0.21 0.23 0.26 0.28 0.31 0.34 0.36 0.39 0.42 0.5312 0.20 0.22 0.25 0.28 0.31 0.34 0.37 0.40 0.43 0.46 0.49 N/A14 0.23 0.25 0.29 0.33 0.30 0.40 0.43 0.46 0.49 0.51 0.56 N/A8 0.20 0.23 0.26 0.29 0.32 0.35 0.38 0.42 0.45 0.49 0.53 0.67
6 10 0.25 0.28 0.31 0.35 0.39 0.42 0.46 0.50 0.55 0.59 0.63 0.8012 0.30 0.34 0.38 0.42 0.46 0.50 0.55 0.60 0.64 0.69 0.74 N/A14 0.35 0.40 0.45 0.49 0.53 0.58 0.64 0.70 0.73 0.76 0.85 N/A8 0.27 0.31 0.34 0.38 0.42 0.47 0.51 0.56 0.61 0.65 0.71 0.89
8 10 0.33 0.37 0.42 0.47 0.52 0.57 0.62 0.67 0.73 0.78 0.84 1.0612 0.40 0.45 0.50 0.56 0.61 0.67 0.73 0.79 0.86 0.92 0.99 N/A14 0.47 0.53 0.58 0.65 0.70 0.77 0.84 0.91 0.99 1.06 1.14 N/A8 0.34 0.39 0.42 0.47 0.52 0.58 0.65 0.72 0.79 0.88 0.93 1.11
10 10 0.43 0.47 0.54 0.61 0.68 0.75 0.83 0.90 0.97 1.05 1.12 1.3312 0.51 0.56 0.62 0.70 0.78 0.86 0.94 1.03 1.11 1.20 1.29 N/A14 0.59 0.65 0.70 0.79 0.88 0.97 1.05 1.16 1.25 1.35 1.46 N/A8 0.42 0.48 0.54 0.60 0.66 0.73 0.81 0.89 0.99 1.10 N/A 1.33
12 10 0.52 0.60 0.68 0.78 0.88 0.98 1.08 1.13 1.28 1.38 1.48 1.5912 0.63 0.73 0.83 0.93 1.03 1.13 1.23 1.34 1.46 1.58 1.70 N/A14 0.74 0.86 0.98 1.08 1.18 1.28 1.38 1.55 1.64 1.78 1.92 N/A
NOTE: * Beyond the scope of ARI certification for heating applications.
ROWS FPIAIR VELOCITY (fpm)
400 450 500 550 600 650 700 800 900* 1000*8 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.14 0.17
1 10 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.13 0.16 0.2012 0.05 0.06 0.07 0.08 0.10 0.11 0.12 0.15 0.19 0.2214 0.06 0.06 0.08 0.09 0.12 0.13 0.14 0.17 0.21 0.248 0.07 0.09 0.10 0.12 0.14 0.16 0.18 0.23 0.28 0.33
2 10 0.08 0.10 0.12 0.14 0.17 0.19 0.21 0.27 0.33 0.3912 0.10 0.12 0.14 0.16 0.19 0.22 0.25 0.31 0.38 0.4514 0.12 0.14 0.16 0.18 0.21 0.25 0.29 0.35 0.43 0.518 0.14 0.17 0.21 0.24 0.28 0.32 0.37 0.46 0.56 0.67
4 10 0.17 0.20 0.24 0.29 0.33 0.38 0.43 0.54 0.65 0.7812 0.19 0.23 0.28 0.33 0.38 0.43 0.49 0.62 0.75 0.9014 0.21 0.26 0.32 0.37 0.43 0.48 0.55 0.70 0.85 1.028 0.21 0.26 0.31 0.36 0.42 0.48 0.55 N/A N/A N/A
6 10 0.25 0.31 0.36 0.43 0.50 0.57 0.60 N/A N/A N/A12 0.29 0.35 0.42 0.49 0.57 0.65 0.74 N/A N/A N/A14 0.33 0.39 0.48 0.55 0.64 0.73 0.88 N/A N/A N/A8 0.28 0.35 0.41 0.49 0.56 0.64 0.73 N/A N/A N/A
8 10 0.33 0.41 0.49 0.57 0.66 0.76 0.86 N/A N/A N/A12 0.38 0.47 0.56 0.66 0.76 0.87 0.98 N/A N/A N/A14 0.43 0.53 0.63 0.75 0.86 0.98 1.10 N/A N/A N/A8 0.37 0.44 0.50 0.58 0.65 0.73 0.82 N/A N/A N/A
10 10 0.43 0.51 0.59 0.67 0.76 0.86 0.96 N/A N/A N/A12 0.49 0.58 0.67 0.76 0.87 0.98 1.09 N/A N/A N/A14 0.55 0.65 0.75 0.85 0.98 1.10 1.22 N/A N/A N/A8 0.48 0.55 0.61 0.69 0.76 0.84 0.93 N/A N/A N/A
12 10 0.55 0.63 0.71 0.79 0.88 0.98 1.08 N/A N/A N/A12 0.62 0.71 0.80 0.89 1.00 1.11 1.22 N/A N/A N/A14 0.69 0.79 0.89 0.99 1.12 1.24 1.36 N/A N/A N/A
NOTE: Shaded area available for standard coils only. No tall or stacked coils.
54 YORK INTERNATIONAL
Air Pressure Drop
FILTER APD (IN. W.G.)
TYPE FILTER MEDIAFILTER VELOCITY (fpm)
200 250 300 350 400 450 500 550 6002" – Throwaway 0.08 0.10 0.12 0.15 0.18 0.21 0.25 0.30 0.352" – Pleated 0.08 0.10 0.12 0.16 0.19 0.23 0.28 0.32 0.362" – Cleanable 0.02 0.03 0.04 0.05 0.07 0.09 0.10 0.11 0.131" – Carbon Tray 0.06 0.13 0.20 0.26 0.34 0.40 0.48 N/A N/A4" – Pleated 0.06 0.08 0.10 0.13 0.16 0.19 0.23 0.27 0.3160 – 65% Efficient 0.15 0.17 0.20 0.23 0.28 0.32 0.38 0.44 0.5180 – 85% Efficient 0.17 0.21 0.25 0.31 0.37 0.45 0.53 0.62 0.7290 – 95% Efficient 0.20 0.24 0.28 0.34 0.41 0.49 0.58 0.67 0.7660 – 65% Efficient 0.07 0.09 0.11 0.13 0.16 0.19 0.22 0.26 N/A80 – 85% Efficient 0.15 0.19 0.23 0.27 0.31 0.35 0.40 0.44 N/A90 – 95% Efficient 0.19 0.23 0.27 0.31 0.36 0.42 0.48 0.56 N/A60 – 65% Efficient 0.09 0.10 0.13 0.16 0.19 0.23 0.27 0.31 0.3580 – 85% Efficient 0.09 0.12 0.15 0.19 0.23 0.28 0.32 0.37 0.4390 – 95% Efficient 0.15 0.21 0.27 0.33 0.39 0.45 0.52 0.58 0.65
99.97% Efficient 0.44 0.60 0.76 0.92 1.08 1.24 1.40 N/A N/A99.99% Efficient 0.44 0.60 0.76 0.92 1.08 1.24 1.40 N/A N/A
NOTE: 1. Filter velocity is based upon gross filter area.2. Filter pressure drop is through clean filters.
FLAT
12"
RIG
ID21
" BAG
30" B
AGHE
PA
STEAM DISTRIBUTING (SDC) APD (IN. W.G. )ROW FIN AIR VELOCITY (fpm)
COIL DEPTH SERIES 200 300 400 500 600 700 800 900 1000 1100 12006 .02 .04 .07 .10 .14 .18 .22 .28 .34 .40 .468 .03 .05 .09 .13 .17 .22 .28 .34 .41 .48 .55
SDC 1 10 .03 .06 .10 .15 .21 .27 .33 .40 .48 .56 .6611 .03 .07 .11 .16 .22 .29 .36 .44 .52 .61 .7012 .04 .07 .12 .18 .24 .31 .38 .47 .56 .65 .7513 .04 .08 .13 .19 .25 .33 .41 .50 .59 .70 .8114 .04 .08 .14 .20 .27 .35 .44 .53 .63 .74 .86
NOTE: Ratings for more than one row deep are obtained with multiple segments of one-row coils. All unit coils are rated and certified inaccordance with ARI Standard 410.
AIR BLENDER APD (IN. W.G.)
NOTE: Variable air volume applications with blender velocities below 1000 fpm should be reviewed to ensure blender performance.
BLENDER FACE VELOCITY 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000PRESSURE DROP 0.07 0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29
DIFFUSER APD (IN. W.G.)FAN OUTLET VELOCITY
1600 1800 2000 2200 2400 2600 2800 3000
DIFFUSER (DIF) 0.09 0.11 0.14 0.17 0.20 0.24 0.27 0.32
FORM 100.10-EG2
YORK INTERNATIONAL 55
ATTENUATOR APD (IN. W.G.)AIR VELOCITY (fpm)
300 400 500 600 700 800 900 10003' Standard 0.03 0.06 0.09 0.13 0.18 0.23 0.30 0.375' Standard 0.04 0.07 0.11 0.15 0.20 0.26 0.33 0.407' Standard 0.04 0.07 0.11 0.16 0.22 0.28 0.35 0.433' Hospital 0.03 0.06 0.09 0.13 0.18 0.23 0.30 0.375' Hospital 0.04 0.07 0.11 0.15 0.20 0.26 0.33 0.407' Hospital 0.04 0.07 0.11 0.16 0.22 0.28 0.35 0.433' Low Frequency 0.05 0.09 0.14 0.21 0.28 0.37 0.46 0.575' Low Frequency 0.05 0.10 0.16 0.23 0.31 0.41 0.51 0.637' Low Frequency 0.06 0.08 0.14 0.22 0.32 0.43 0.53 0.63
FAN OUTLET VELOCITY1600 1800 2000 2200 2400 2600 2800 3000
FC 0.32 0.40 0.50 0.60 0.71 0.84 0.97 1.12AF 0.09 0.11 0.13 0.16 0.19 0.23 0.26 0.30
FAN VELOCITY APD* (IN. W.G.)
NOTE: * Applies to supply fans without the proper length of discharge duct.
VERTICAL CASING PRESSURE LOSS APD (IN. W.G.)COIL FACE VELOCITY
350 400 450 500 550 600
CASING LOSS 0.14 0.18 0.23 0.29 0.36 0.41
ELECTRIC HEATAIR VELOCITY (fpm)
350 400 450 500 550 600 650OPEN-FACE ELEMENT 0.06 0.08 0.10 0.13 0.15 0.18 0.21
GAS HEATSee data listed withEngineering data on page 37.
56 YORK INTERNATIONAL
Air Pressure Drop
(2) 50% OUTSIDE AIR DAMPER
EE1 - MB SEGMENT – LOW LEAK APD (IN W.G.)Economizer without Return Fan
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 1.83 0.04 0.06 0.08 0.11 0.13 0.16 0.19 0.23 0.27 0.31 0.35 0.4085 1.83 0.04 0.06 0.08 0.11 0.13 0.16 0.19 0.23 0.27 0.31 0.35 0.40
105 1.83 0.04 0.06 0.08 0.11 0.13 0.16 0.19 0.23 0.27 0.31 0.35 0.40125 2.67 0.03 0.04 0.06 0.08 0.10 0.12 0.14 0.17 0.19 0.22 0.26 0.29170 3.33 0.03 0.04 0.06 0.07 0.09 0.12 0.14 0.16 0.19 0.22 0.25 0.28215 4.67 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.16 0.18 0.21 0.24 0.27250 4.67 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.16 0.18 0.21 0.24 0.27305 7.11 0.03 0.04 0.05 0.07 0.09 0.10 0.13 0.15 0.17 0.20 0.23 0.26350 11.11 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.14 0.16 0.18400 9.72 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.14 0.16 0.18460 11.28 0.02 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.12 0.14 0.16530 13.29 0.02 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.12 0.14 0.16680 17.00 0.01 0.02 0.03 0.04 0.04 0.06 0.07 0.08 0.09 0.11 0.12 0.14860 28.17 0.01 0.01 0.02 0.02 0.03 0.04 0.05 0.05 0.06 0.07 0.08 0.09
1030 28.17 0.01 0.01 0.02 0.02 0.03 0.04 0.05 0.05 0.06 0.07 0.08 0.09
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 2.90 0.06 0.06 0.08 0.11 0.13 0.16 0.19 0.23 0.27 0.31 0.35 0.4085 3.90 0.05 0.08 0.10 0.13 0.16 0.20 0.24 0.28 0.33 0.38 0.44 0.50
105 4.90 0.05 0.07 0.10 0.12 0.15 0.19 0.23 0.27 0.31 0.36 0.41 0.47125 5.79 0.03 0.05 0.06 0.08 0.11 0.13 0.15 0.18 0.21 0.25 0.28 0.32170 7.79 0.03 0.05 0.06 0.08 0.10 0.12 0.15 0.17 0.20 0.23 0.26 0.30215 9.79 0.03 0.04 0.06 0.08 0.09 0.12 0.14 0.16 0.19 0.22 0.25 0.28250 11.79 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.16 0.18 0.21 0.24 0.27305 13.79 0.03 0.04 0.05 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.26350 10.19 0.03 0.05 0.06 0.08 0.10 0.12 0.15 0.17 0.20 0.23 0.27 0.30400 11.92 0.03 0.04 0.06 0.08 0.10 0.12 0.14 0.17 0.20 0.23 0.26 0.29460 13.14 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.17 0.19 0.22 0.25530 15.37 0.03 0.04 0.05 0.06 0.08 0.10 0.12 0.14 0.16 0.19 0.21 0.24680 19.83 0.02 0.03 0.05 0.06 0.08 0.09 0.11 0.13 0.15 0.18 0.20 0.23860 37.73 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15
1030 45.35 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.14
USE ON ALL OPENING VELOCITY (FPM) UNIT SIZES 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
0.04 0.06 0.08 0.11 0.14 0.17 0.20 0.24 0.28 0.33 0.38 0.43
100% RETURN AIR OPENING SIDE OR BOTTOM
100% RETURN AIR (MIXING DAMPER) UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 2.88 0.04 0.06 0.08 0.11 0.13 0.16 0.19 0.23 0.27 0.31 0.35 0.4085 3.72 0.04 0.06 0.08 0.10 0.13 0.16 0.19 0.22 0.26 0.30 0.34 0.38
105 4.97 0.04 0.06 0.07 0.10 0.12 0.15 0.18 0.21 0.24 0.28 0.32 0.36125 5.76 0.02 0.03 0.05 0.06 0.08 0.09 0.11 0.13 0.15 0.18 0.20 0.23170 7.43 0.02 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.19 0.22215 9.93 0.02 0.03 0.04 0.06 0.07 0.09 0.10 0.12 0.14 0.16 0.19 0.21250 11.60 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.18 0.21305 13.26 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.18 0.20350 14.50 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.13 0.15 0.17400 16.58 0.02 0.03 0.03 0.04 0.06 0.07 0.08 0.10 0.11 0.13 0.15 0.17460 20.88 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.11 0.13530 23.88 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13680 26.88 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.12860 32.83 0.01 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08 0.10
1030 41.08 0.01 0.01 0.02 0.02 0.03 0.04 0.05 0.05 0.06 0.07 0.08 0.09
100% EXHAUST AIR
FORM 100.10-EG2
YORK INTERNATIONAL 57
(2) 50% OUTSIDE AIR DAMPER
100% RETURN AIR (MIXING DAMPER)
EE1 - MB SEGMENT – ULTRA LOW LEAK APD (IN W.G.)Economizer without Return Fan
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 1.83 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.2685 1.83 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.26
105 1.83 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.26125 2.67 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.11 0.13 0.15 0.17 0.19170 3.33 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.13 0.14 0.16 0.18215 4.67 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.12 0.14 0.16 0.18250 4.67 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.12 0.14 0.16 0.18305 7.11 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.15 0.17350 11.11 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.12400 9.72 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.12460 11.28 0.01 0.02 0.02 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.10530 13.29 0.01 0.02 0.02 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.10680 17.00 0.01 0.01 0.02 0.03 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09860 28.17 0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.04 0.05 0.05 0.06
1030 28.17 0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.04 0.05 0.05 0.06
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 2.88 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.2685 3.72 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.20 0.22 0.25
105 4.97 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.21 0.24125 5.76 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15170 7.43 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.14215 9.93 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.12 0.14250 11.60 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.12 0.13305 13.26 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.12 0.13350 14.50 0.01 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11400 16.58 0.01 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11460 20.88 0.01 0.01 0.02 0.02 0.03 0.04 0.04 0.05 0.06 0.06 0.07 0.08530 23.88 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08680 26.88 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08860 32.83 0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.04 0.05 0.06 0.06
1030 41.08 0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.04 0.05 0.05 0.06
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 2.90 0.04 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.2685 3.90 0.04 0.05 0.07 0.09 0.11 0.14 0.16 0.19 0.22 0.25 0.29 0.32
105 4.90 0.04 0.05 0.07 0.09 0.11 0.13 0.15 0.18 0.21 0.24 0.27 0.30125 5.79 0.02 0.03 0.05 0.06 0.07 0.09 0.10 0.12 0.14 0.16 0.18 0.21170 7.79 0.02 0.03 0.04 0.06 0.07 0.08 0.10 0.12 0.13 0.15 0.17 0.19215 9.79 0.02 0.03 0.04 0.05 0.07 0.08 0.09 0.11 0.13 0.15 0.16 0.19250 11.79 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.12 0.14 0.16 0.18305 13.79 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15 0.17350 10.19 0.02 0.03 0.04 0.06 0.07 0.08 0.10 0.12 0.14 0.15 0.18 0.20400 11.92 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.11 0.13 0.15 0.17 0.19460 13.14 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.15 0.16530 15.37 0.02 0.03 0.04 0.04 0.06 0.07 0.08 0.09 0.11 0.12 0.14 0.16680 19.83 0.02 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.10 0.12 0.13 0.15860 37.73 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10
1030 45.35 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08 0.09
100% EXHAUST AIR
58 YORK INTERNATIONAL
Air Pressure DropEE2 - FR SEGMENT – LOW LEAK APD (IN W.G.)Economizer with Return Fan
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 2.88 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.2685 3.72 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.20 0.22 0.25
105 4.97 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.21 0.24125 5.76 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15170 7.43 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.14215 9.93 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.12 0.14250 11.60 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.12 0.13305 13.26 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.12 0.13350 14.50 0.01 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11400 16.58 0.01 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11460 20.88 0.01 0.01 0.02 0.02 0.03 0.04 0.04 0.05 0.06 0.06 0.07 0.08530 23.88 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08680 26.88 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08860 32.83 0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.04 0.05 0.06 0.06
1030 41.08 0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.04 0.05 0.05 0.06
100% OUTSIDE AIR, RETURN AIR AND EXHAUST AIR
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 2.88 0.04 0.06 0.08 0.11 0.13 0.16 0.20 0.23 0.27 0.31 0.35 0.4085 3.72 0.04 0.06 0.08 0.10 0.13 0.16 0.19 0.22 0.26 0.30 0.34 0.38
105 4.97 0.04 0.06 0.07 0.10 0.12 0.15 0.18 0.21 0.24 0.28 0.32 0.36125 5.76 0.02 0.03 0.05 0.06 0.08 0.09 0.11 0.13 0.15 0.18 0.20 0.23170 7.43 0.02 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.19 0.22215 9.93 0.02 0.03 0.04 0.06 0.07 0.09 0.10 0.12 0.14 0.16 0.19 0.21250 11.60 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.18 0.21305 13.26 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.18 0.20350 14.50 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.13 0.15 0.17400 16.58 0.02 0.03 0.03 0.04 0.06 0.07 0.08 0.10 0.11 0.13 0.15 0.17460 20.88 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.11 0.13530 23.88 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13680 26.88 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.12860 32.83 0.01 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08 0.10
1030 41.08 0.01 0.01 0.02 0.02 0.03 0.04 0.05 0.05 0.06 0.07 0.08 0.09
EE2 - FP(H) SEGMENT – ULTRA LOW LEAK APD (IN W.G.)Economizer with Return Horizontal Plenum Fan
100% OUTSIDE AIR, RETURN AIR AND EXHAUST AIR
FORM 100.10-EG2
YORK INTERNATIONAL 59
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 N/A Not Available85 1.83 0.04 0.06 0.08 0.11 0.13 0.16 0.19 0.23 0.27 0.31 0.35 0.40105 1.83 0.04 0.06 0.08 0.11 0.13 0.16 0.19 0.23 0.27 0.31 0.35 0.40125 2.67 0.03 0.04 0.06 0.08 0.10 0.12 0.14 0.17 0.19 0.22 0.26 0.29170 3.33 0.03 0.04 0.06 0.07 0.09 0.12 0.14 0.16 0.19 0.22 0.25 0.28215 4.67 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.16 0.18 0.21 0.24 0.27250 4.67 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.16 0.18 0.21 0.24 0.27305 7.11 0.03 0.04 0.05 0.07 0.09 0.10 0.13 0.15 0.17 0.20 0.23 0.26
(2) 50% OUTSIDE AIR DAMPER, (1) 100% EA & RA – UNIT SIZES 65-305
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
350 10.35 0.03 0.05 0.06 0.08 0.10 0.12 0.15 0.17 0.20 0.23 0.26 0.30400 12.10 0.03 0.04 0.06 0.08 0.10 0.12 0.14 0.17 0.19 0.22 0.25 0.29460 13.31 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.17 0.19 0.22 0.25530 15.56 0.03 0.04 0.05 0.06 0.08 0.10 0.12 0.14 0.16 0.19 0.21 0.24680 20.06 0.02 0.03 0.05 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23860 38.01 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15
1030 45.68 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.14
100% OUTSIDE AIR, RETURN AIR AND EXHAUST AIR DAMPERS – UNIT SIZES 350 - 1030
EE1 - FP(V) SEGMENT – LOW LEAK APD (IN W.G.)Economizer with Vertical Plenum Return Fan
EE3 - FP(V) SEGMENT – LOW LEAK APD (IN W.G.)Economizer with Vertical Plenum Return Fan
USE ON ALL OPENING VELOCITY (FPM) UNIT SIZES 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
0.04 0.06 0.08 0.11 0.14 0.17 0.20 0.24 0.28 0.33 0.38 0.43
100% OUTSIDE AIR OPENING
60 YORK INTERNATIONAL
Air Pressure Drop
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 N/A Not Available85 1.83 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.26
105 1.83 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.26125 2.67 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.11 0.13 0.15 0.17 0.19170 3.33 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.13 0.14 0.16 0.18215 4.67 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.12 0.14 0.16 0.18250 4.67 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.12 0.14 0.16 0.18305 7.11 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.15 0.17
(2) 50% OUTSIDE AIR DAMPER – UNIT SIZES 65-305
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
350 10.35 0.02 0.03 0.04 0.06 0.07 0.08 0.10 0.12 0.13 0.15 0.17 0.20400 12.10 0.02 0.03 0.04 0.05 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.19460 13.31 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.14 0.16530 15.56 0.02 0.03 0.03 0.04 0.06 0.07 0.08 0.09 0.11 0.12 0.14 0.16680 20.06 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15860 38.01 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.101030 45.68 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08 0.09
100% OUTSIDE AIR, RETURN AIR AND EXHAUST AIR DAMPERS – UNIT SIZES 350 - 1030
EE1 - FP(V) SEGMENT – ULTRA LOW LEAK APD (IN W.G.)Economizer with Vertical Plenum Return Fan
EE3 - FP(V) SEGMENT – ULTRA LOW LEAK APD (IN W.G.)Economizer with Vertical Plenum Return Fan
USE ON ALL OPENING VELOCITY (FPM) UNIT SIZES 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
0.04 0.06 0.08 0.11 0.14 0.17 0.20 0.24 0.28 0.33 0.38 0.43
100% OUTSIDE AIR OPENING
FORM 100.10-EG2
YORK INTERNATIONAL 61
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 2.88 0.04 0.06 0.08 0.11 0.13 0.16 0.20 0.23 0.27 0.31 0.35 0.4085 3.72 0.04 0.06 0.08 0.10 0.13 0.16 0.19 0.22 0.26 0.30 0.34 0.38105 4.97 0.04 0.06 0.07 0.10 0.12 0.15 0.18 0.21 0.24 0.28 0.32 0.36125 5.76 0.02 0.03 0.05 0.06 0.08 0.09 0.11 0.13 0.15 0.18 0.20 0.23170 7.43 0.02 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.19 0.22215 9.93 0.02 0.03 0.04 0.06 0.07 0.09 0.10 0.12 0.14 0.16 0.19 0.21250 11.60 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.18 0.21305 13.26 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.18 0.20
100% OUTSIDE AIR AND RETURN AIR (MIXING DAMPER) – UNIT SIZES 65-305
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
350 10.35 0.03 0.05 0.06 0.08 0.10 0.12 0.15 0.17 0.20 0.23 0.26 0.30400 12.10 0.03 0.04 0.06 0.08 0.10 0.12 0.14 0.17 0.19 0.22 0.25 0.29460 13.31 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.17 0.19 0.22 0.25530 15.56 0.03 0.04 0.05 0.06 0.08 0.10 0.12 0.14 0.16 0.19 0.21 0.24680 20.06 0.02 0.03 0.05 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23860 38.01 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15
1030 45.68 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.14
100% OUTSIDE AIR AND RETURN AIR (MIXING DAMPER) – UNIT SIZES 350 - 1030
EE4 - FE SEGMENT – LOW LEAK APD (IN W.G.)Economizer with Exhaust Fan
EE3 - FE SEGMENT – LOW LEAK APD (IN W.G.)Economizer with Exhaust Fan
USE ON ALL OPENING VELOCITY (FPM) UNIT SIZES 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
0.15 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 0.26
100% EXHAUST AIR DAMPERS
USE ON ALL OPENING VELOCITY (FPM) UNIT SIZES 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
0.04 0.06 0.08 0.11 0.14 0.17 0.20 0.24 0.28 0.33 0.38 0.43
100% OUTSIDE AIR OPENING
62 YORK INTERNATIONAL
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
65 2.88 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.18 0.20 0.23 0.2685 3.72 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.20 0.22 0.25
105 4.97 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.21 0.24125 5.76 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15170 7.43 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.14215 9.93 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.12 0.14250 11.60 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.12 0.13305 13.26 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.12 0.13
100% OUTSIDE AIR AND RETURN AIR (MIXING DAMPER) – UNIT SIZES 65-305
UNIT DAMPER DAMPER VELOCITY (FPM) SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
350 10.35 0.02 0.03 0.04 0.06 0.07 0.08 0.10 0.12 0.13 0.15 0.17 0.20400 12.10 0.02 0.03 0.04 0.05 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.19460 13.31 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.14 0.16530 15.56 0.02 0.03 0.03 0.04 0.06 0.07 0.08 0.09 0.11 0.12 0.14 0.16680 20.06 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.15860 38.01 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10
1030 45.68 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.06 0.07 0.08 0.09
100% OUTSIDE AIR AND RETURN AIR (MIXING DAMPER) – UNIT SIZES 350 - 1030
EE4 - FE SEGMENT – ULTRA LOW LEAK APD (IN W.G.)Economizer with Exhaust Fan
EE3 - FE SEGMENT – ULTRA LOW LEAK APD (IN W.G.)Economizer with Exhaust Fan
USE ON ALL OPENING VELOCITY (FPM) UNIT SIZES 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
0.15 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 0.26
100% EXHAUST AIR DAMPERS
USE ON ALL OPENING VELOCITY (FPM) UNIT SIZES 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
0.04 0.06 0.08 0.11 0.14 0.17 0.20 0.24 0.28 0.33 0.38 0.43
100% OUTSIDE AIR OPENING
Air Pressure Drop
FORM 100.10-EG2
YORK INTERNATIONAL 63
Segment Dimensions
CE – CONTROL ENCLOSURE
Dimensions are in inches.NOTE: 1. Double doors are furnished only on units 105, 215 and larger.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
CONTROL ENCLOSURE DIMENSIONS
TO BE USED FOR FIELD INSTALLED DEVICES.
LD06047
All dimensions are approximate andnot certified for construction.
64 YORK INTERNATIONAL
Segment Dimensions
FS – SUPPLY FAN (DWDI)
SUPPLY FAN SEGMENT DIMENSIONS
Dimensions are in inches.NOTES: 1. Motor/drive will be located on the same side of the unit as the specified coil hand (right or left).
2. An access door is supplied as standard on the coil header side of the unit.3. Access doors (opposite coil header side of the unit), access doors (both sides of the unit), window in door and perforated
liners are all optional.4. FS bottom down discharge has a 1" flange that extends below the bottom of floor panel.5. FSR and FSRI has a 1" flange on exterior of unit.6. FST and FSTI has a 2" flange on exterior of unit.* See page 56.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W * 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 45 45 48 51 54 63 66 75 87 87 93 99 99 102 111
LD00016
All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 65
FS – SUPPLY FAN (DWDI) DISCHARGE
LD04273
Dimensions are in inches.
NOTES: 1. Access door is supplied as standard on the coil header side of the unit.2. Discharge opening dimensions shown above are for the largest listed fan per unit size.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
D 14.9 20.9 25.6 12.1 16.4 21.1 25.8 31.8 23.8 28.3 21.1 27.1 39.1 43.6 54.1E 19.1 19.1 16.0 21.4 23.4 24.1 25.1 25.1 26.3 28.1 29.6 29.6 29.6 27.4 27.4F 13.3 13.3 15.8 18.8 22.2 24.9 28.4 28.4 31.8 35.6 35.6 39.8 39.8 44.7 50.1G 11.5 11.5 13.6 16.1 19.1 24.9 28.4 28.4 31.8 35.6 35.6 42.9 42.9 44.7 50.1
FORWARD CURVED (FC) FAN DIMENSIONS
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
D 13.1 19.1 24.1 11.3 16.3 21.1 26.0 30.4 22.8 27.2 19.2 23.1 32.8 36.3 42.5E 16.6 16.6 16.2 25.5 26.1 27.5 28.9 30.7 32.5 34.5 36.9 39.2 42.0 44.6 51.5F 15.8 15.8 18.8 18.8 22.2 22.2 25.4 28.4 31.8 35.6 39.8 39.8 44.7 50.1 66.1G 13.6 13.6 16.1 16.1 19.1 19.1 25.4 28.4 31.8 35.6 42.9 42.9 44.7 50.1 54.6
AIRFOIL (AF) FAN DIMENSIONS
All dimensions are approximate andnot certified for construction.
66 YORK INTERNATIONAL
Segment Dimensions
FP – PLENUM SUPPLY FAN (SWSI)
Dimensions are in inches.
NOTES: 1. Access doors are supplied as standard on the coil header side of the unit only.2. Perforated liners are an option.3. Units CP65, 85, 105 & 125 have outward swinging doors as standard.4. Access segment required upstream for fan inlet.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 45 45 48 51 54 63 66 75 87 87 93 99 99 102 111
PLENUM SUPPLY FAN DIMENSIONS
LD06032
All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 67
FP – PLENUM SUPPLY FAN (SWSI)
Dimensions are in inches.P = HIGH SIDE DIMENSIONP1 = LOW SIDE DIMENSION
LD06285
NOTE: Bottom duct mounting surface is flush with bottom of floor.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
J 24 36 48 24 36 48 60 72 60 72 60 72 96 108 132K 15 15 15 21 21 21 21 21 27 27 33 33 33 48 48N 15 21 21 21 21 21 21 21 27 33 33 33 33 48 48M 24 24 24 24 36 48 48 48 60 60 60 72 72 105 105C 11.5 11.5 11.5 20.5 20.5 20.5 20.5 20.5 29.5 29.5 38.5 38.5 38.5 37 37P 8.2 8.2 8.2 20.2 14.2 8.2 8.2 8.2 14.2 14.2 26.7 20.7 20.7 10.2 10.2P1 7.2 7.2 7.2 19.2 13.2 7.2 7.2 7.2 13.2 13.2 25.2 19.2 19.2 8.7 8.7
OUTLET DIMENSIONS
All dimensions are approximate andnot certified for construction.
68 YORK INTERNATIONAL
Segment Dimensions
SC, MC, LC – COOLING COIL
Dimensions are in inches.
NOTES: 1. All cooling coil segments have a double sloped drain pan with a condensate connection on the opposite side of the coil header.2. All coils located in the same coil segment must have the same coil hand.3. Full and reduced face coils can not be used in the same or adjacent segments.4. Solid lining (only) available in the cooling coil segment.5. Header cover standard; pipe chase optional, see page XX for installation.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 30 30 30 33 33 33 33 33 33 33 33 33 33 48 48
MC – MEDIUM COIL SEGMENT (20" AVAILABLE COIL SPACE)
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 36 36 36 39 39 39 39 39 39 39 39 39 39 60 60
LC – LONG COIL SEGMENT (27-3/8" AVAILABLE COIL SPACE)
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 21 21 21 24 24 24 24 24 24 24 24 24 24 30 30
SC – SHORT COIL SEGMENT (13" AVAILABLE COIL SPACE)
LD06034
TOP VIEW SIDE VIEW
All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 69
HC – HEATING COIL
Dimensions are in inches.
NOTES: 1. All cooling coil segments have a double sloped drain pan with a condensate connection on the opposite side of the coil header.2. All coils located in the same coil segment must have the same coil hand.3. Full and reduced face coils can not be used in the same or adjacent segments.4. Solid lining (only) available in the cooling coil segment.5. Header cover standard; pipe chase optional, see page XX for installation.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
HEAT ONLY (7-3/8") DIMENSIONS
LD06035
TOP VIEW SIDE VIEW
All dimensions are approximate andnot certified for construction.
70 YORK INTERNATIONAL
Segment Dimensions
IB – FACE & BYPASS DAMPER
Dimensions are in inches.NOTES: 1. The IB Segment must be located immediately upstream of a reduced face coil.
2. When a full face coil is required downstream of the reduced face coil, access segment(s) must be included between the coils.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
W1 35 47 59 35 47 59 71 83 71 83 71 83 107 119 143H1 7 7 7 13 13 13 13 13 19 19 25 25 25 37 37H2 18 18 18 36 36 36 36 36 54 54 72 72 72 72 72
FACE AND BYPASS DAMPER DIMENSIONS
LD06036All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 71
IC – INTEGRAL FACE & BYPASS COIL
LD06037
IC – HEAT ONLY - INTEGRAL FACE & BYPASS COIL DIMENSIONS
Dimensions are in inches.NOTES: 1. A pipe chase is provided on the header side of the unit to accommodate steam or hot water piping and actuator.
2. lFB Coils (horizontal tube) have side coil connections.3. VIFB Coils (vertical tube) have center coil connections.4. All piping by others in field.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
2 Row IFB Coil N/A 33 33 N/A 33 33 33 33 33 33 N/A N/A N/A N/A N/A4 Row IFB Coil N/A 48 48 N/A 48 48 48 48 48 48 N/A N/A N/A N/A N/A
L 1 Row VIFB Coil N/A N/A N/A 42 42 42 42 42 42 42 42 42 42 42 422 Row VIFB Coil N/A N/A N/A 42 42 42 42 42 42 42 42 42 42 42 42
3 Row VIFB Coil N/A N/A N/A 42 42 42 42 42 42 42 42 42 42 42 42H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151
All dimensions are approximate andnot certified for construction.
72 YORK INTERNATIONAL
Segment Dimensions
S = Access door standardO = Access door optional
FILTERS
Dimensions are in inches.NOTES: 1. All filters are standard side-loading, except blow through units. All blow through units will be front or rear loaded.
2. An access door is supplied as standard on the coil header side of the unit, except in a blow through.3. Front or rear load filters are optional.4. The RF Segment is available with 2" prefilters, except when rear loaded filters are used.5. FF Segments’ access door will be combined with the upstream or downstream segments’ access door where possible.6. Filters are accessible from header side of unit only.
FILTER UNIT SIZESIZE DESCRIPTION 65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
FF 2" L 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 4" L 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9
AF 2" L 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30RF 12" L 21 21 21 21 21 21 21 21 21 21 21 21 21 21 21
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151 H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
FILTER DIMENSIONS
LD00024 LD05927 LD05928
FF - FLAT FILTER (2" & 4") AF - ANGLE FILTER (2") RF - RIGID FILTER (12")
All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 73
FILTERS
Dimensions are in inches.NOTES: 1. All filters are side-loading, except blow through units. All blow through units will be front or rear loaded.
2. An access door is supplied as standard on the coil header side of the unit.3. Access door (opposite coil header side of the unit) is not available on carbon filter. Opposite side door on BF is optional but does
not allow filter access.4. The CF Segment is available with 2" prefilters.5. Prefilters for the HEPA Filters (HF) must be located in another segment.6. Perforated liner not available.
FILTER DIMENSIONSFILTER UNIT SIZE
SIZE DESCRIPTION 65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
BF 21" L 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 32" L 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42
CF 1" L 39 39 39 39 39 39 39 39 39 39 39 39 39 39 39HF 12" L 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151 H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
S = Access Door StandardO = Access Door Optional
LD05929 LD05930 LD06267
BF - BAG FILTER (21" & 32") CF - CARBON FILTER HF - HEPA FILTER
All dimensions are approximate andnot certified for construction.
74 YORK INTERNATIONAL
Segment DimensionsMB – MIXING BOX INLET
0%, 30% OR 100% OUTSIDE AIR, 0% OR 100% RETURN AIR
W
L
5.75"
5.75"
W
RA
OA
RA
RA
H
30%-100%
K
J
V
U
N
M
P
T
Z
E
4"
14"
F
RA
SIDELOCATION
ONLY
RA
IN H
OO
D
11"
TOP LOCATION
BOTTOM LOCATION
FRONT LOCATION
FRONT LOCATION
X
T
SIDE VIEWEND VIEW
TOP VIEW
3.63"
LD06467
All dimensions are approximate andnot certified for construction.
MB – MIXING BOX INLET DIMENSIONS - UNIT SIZES 65-305Unit Size H J K L * L M N P P1 W
65 37 24 15 30 30 24 15 7.2 8.2 4385 37 36 15 30 30 24 21 7.2 8.2 67105 37 48 15 30 30 24 21 7.2 8.2 67125 61 27 24 36 30 24 21 19.2 20.2 43170 61 36 24 36 30 36 21 13.2 14.2 55215 61 48 24 36 30 48 21 7.2 8.2 67250 61 60 24 36 30 48 21 7.2 8.2 79305 61 72 24 36 30 48 21 7.2 8.2 91
FORM 100.10-EG2
YORK INTERNATIONAL 75
30% Outside Air Damper Opening Hood DimensionUnit Size F T U V X Z
65 4.13 22 34.75 9.75 36 1885 4.13 22 46.75 9.75 48 18105 4.13 22 58.75 9.75 60 18125 4.13 46 34.75 9.75 36 24170 4.13 46 46.75 9.75 48 24215 4.13 46 58.75 9.75 60 24250 4.13 46 70.75 9.75 72 24305 4.13 46 82.75 9.75 84 24350 4.13 70 70.75 8.75 72 24400 4.13 70 82.75 8.75 84 24460 4.13 88 70.75 14.75 72 24530 4.13 88 82.75 14.75 84 24680 4.13 88 106.75 14.75 108 24860 4.13 95.3 118.75 14.75 120 241030 4.13 95.3 142.75 14.75 144 24
Note:P = Low Side of Unit
P1 = High Side of the Unit
Locating Openings in theFront Panel
F & T = 30% OAF1 & T1 = 100% OAF2 & T2 = 100% RA
Front Panel can haveany of the Following
U & V = 30% OAU1 & V1 = 100% OAU2 & V2 = 100% RA
* Damper/Openings horizontally located on front panel - no other openings allowed.
NOTES: 1. An access door is supplied as standard on the coil header side of the unit.2. Access doors (opposite coil header side of the unit), access doors (both sides of the unit), and perforated liners are available.3. An expanded metal screen over the return air damper is optional, standard if a damper is not ordered.4. All hoods shipped attached to unit, unless unit length is prohibitive for shipment.5. The MB Segment must be the first segment in direction of airflow.6. Bottom inlet duct mounting surface is flush with bottom of floor.7. Dimension “T” is the location from the bottom of the unit to the bottom of the hood.8. Bird screen mesh is 16-gauge aluminum flattened expanded metal with a 3/4" hole size.9. Add 6" to Segment length “L” when side opening is selected.
MB – MIXING BOX INLET0%, 30% OR 100% OUTSIDE AIR, 0% OR 100% RETURN AIR
Unit Size H J K L * L M N P P1 W350 85 60 27 42 30 60 27 13.2 14.2 79400 85 72 27 42 30 60 33 13.2 14.2 91460 110 60 33 48 30 60 33 25.2 26.7 79530 110 72 33 48 30 72 33 19.2 20.7 91680 110 96 33 48 30 72 33 19.2 20.7 115860 122 108 48 63 36 105 48 8.7 10.2 1271030 122 132 48 63 36 105 48 8.7 10.2 151
MB – MIXING BOX INLET DIMENSIONS - UNIT SIZES 350-1030
100% Outside Air Damper Opening Hood DimensionUnit Size F1 T1 U1 V1 X Z
65 4.13 19.5 34.75 12.00 36 1885 4.13 19.5 46.75 12.00 48 18105 4.13 19.5 58.75 12.00 60 18125 4.13 31.5 34.75 24.00 36 33170 4.13 31.5 46.75 24.00 48 33215 4.13 31.5 58.75 24.00 60 33250 4.13 31.5 70.75 24.00 72 33305 4.13 31.5 82.75 24.00 84 33350 4.13 58.0 70.75 20.75 72 48400 4.13 58.0 82.75 20.75 84 48460 4.13 76.0 70.75 26.75 72 60530 4.13 76.0 82.75 26.75 84 60680 4.13 76.0 106.75 26.75 108 60860 4.13 67.3 118.75 45.75 120 691030 4.13 67.3 142.75 45.75 144 69
100% Return Air Damper Opening Unit Size F2 T2 U2 V2
65 9.5 11.5 24 1585 9.5 11.5 36 15105 9.5 11.5 48 15125 8.0 19.0 27 24170 9.5 19.0 36 24215 9.5 19.0 48 24250 9.5 19.0 60 24305 9.5 19.0 72 24350 9.5 29.5 60 27400 9.5 29.5 72 27460 9.5 38.5 60 33530 9.5 38.5 72 33680 9.5 38.5 96 33860 9.5 37.0 108 481030 9.5 37.0 132 48
76 YORK INTERNATIONAL
Segment DimensionsECONOMIZER / RETURN FAN
LD06272
*Dimension includes 2" end wall.
EA & OA Hoods are standard on all unit sizes.
Bird screen placed on bottom of allhoods as standard.
S = Standard Access DoorO = Optional Access Door
DIMENSIONUNIT SIZE
65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
L (TOTAL) 102 108 120 108 117 135 144 150 153 165 165 171 189 192 213 L1 EE 57 63 72 57 63 72 78 84 78 84 78 84 90 84 96 L2 FR 45 45 48 51 54 63 66 66 75 81 87 87 99 108 117 100% RETURN AIR OPENING (BOTTOM OR FRONT)
C 11.5 11.5 11.5 19 19 19 19 19 29.5 29.5 38.5 38.5 38.5 37 37J 24 36 48 27 36 48 60 72 60 72 60 72 96 108 132K 15 15 15 24 24 24 24 24 27 27 33 33 33 48 48
100% MIXING, OUTSIDE & EXHAUST AIR DAMPER OPENINGA 21 27 36 21 27 36 42 48 42 48 42 48 54 48 60B 20 20 20 40 40 40 40 40 50 50 72 72 72 93 93
100% EXHAUST & OUTSIDE AIR HOOD DIMENSIONSG 25.5 31.5 40.5 25.5 31.5 40.5 46.5 52.5 45.3 51.3 45.3 51.3 57.3 51.3 63.3F 24 24 24 36 36 36 42 42 30 30 39 42 42 45 45
NOTES: 1. An access door is supplied as standard on the coil header side of the unit. Dimensions are in inches.2. Access doors (both sides of the unit), and perforated liners are all optional.3. An expanded metal screen over the bottom return air opening is standard.4. Bottom inlet duct mounting surface is flush with bottom of floor.5. Front opening has 2" flange hook-up.6. CP860 & CP1030 length includes shipping split.
EE2 / FR – w/DWDI FC OR AF RETURN FAN
All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 77
ECONOMIZER / INLET SEGMENT
*Dimension includes end wall.
Dimensions are in inches.NOTES: 1. An access door is supplied as standard on the coil header side of the unit.
2. Access doors (both sides of the unit), and perforated liners are all optional.3. An expanded metal screen over the bottom return air opening is standard.4. Bottom inlet duct mounting surface is flush with bottom of floor.5. CP860 & CP1030 length includes shipping split.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
L (TOTAL) 75 75 75 81 84 90 90 102 102 105 111 114 117 135 135L1 EE 45 45 45 45 48 54 54 66 60 63 63 66 69 72 72L2 MB 30 30 30 36 36 36 36 36 42 42 48 48 48 63 63
100% RETURN AIR OPENING – NOTE: Add 6" unit sizes 85, 105 and 400 when side RA is chosen.J 24 36 48 27 36 48 60 72 60 72 60 72 96 108 132
K 15 15 15 24 24 24 24 24 27 27 33 33 33 48 48 M 24 24 24 24 36 48 48 48 60 60 60 72 72 105 105 N 15 21 21 21 21 21 21 21 27 33 33 33 33 48 48(2) 50% OUTSIDE AIR OPENING
A 12 12 12 12 15 21 21 32 22 28 28 33 36 39 39 B 22 22 22 32 32 32 32 32 50 50 58 58 68 104 104(2) 50% OUTSIDE AIR HOOD F 33 33 33 42 42 42 42 42 36 36 36 36 40 40 40 G 12 12 12 12 15 21 21 32 22 28 28 33 36 39 39100% MIXING AIR OPENING R 21 27 36 21 27 36 42 48 42 48 42 48 54 48 60 D 20 20 20 40 40 40 40 40 50 50 72 72 72 99 99100% EXHAUST AIR OPENING U 35 47 59 35 47 59 71 83 71 83 71 83 107 119 143 V 12 12 12 24 24 24 24 24 21 21 27 27 27 46 46100% EXHAUST AIR HOOD Z 18 18 18 24 24 24 24 24 24 24 24 24 24 24 24 X 36 48 60 36 48 60 72 84 72 84 72 84 108 120 144
S S
O O
W
50% OA HOOD
50% OA HOOD
TOP VIEW
F K
J U
MIX
ING
DA
MP
ER
X
G
HB
A
L2L1
L (TOTAL)
N 14"
MR
5.75"
SIDE VIEW
Z4"
VEAHOOD
RA
RAD
EE1 MB
LD06468
EE1 / MB – BOTTOM RETURN w/o RETURN FAN
All dimensions are approximate andnot certified for construction.
78 YORK INTERNATIONAL
Segment DimensionsECONOMIZER / FAN PLENUM – VERTICAL RETURN – CP85 - 305
* Dimension includes 2" end wall.OA Hoods are standard.
S = Standard Access DoorO = Optional Access Door
LD06274
4. Access is required below the unit to service the lower fan bearing.5. Bottom inlet duct mounting surface is flush with bottom of floor.6. Fan opening is centered on floor.7. This segment not available for CP65.8. Motor on end (shown dotted) for unit sizes CP85, 125 & 170.
Dimensions are in inches.NOTES: 1. An access door is supplied as standard on the coil header sideof the unit.
2. Access doors (opposite coil header side of the unit), ac-cess doors (both sides of the unit), and perforated linersare all optional.
3. The EE, FP Segment must be the first segment indirection of airflow.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305
W N/A 55 67 43 55 67 79 91H N/A 37 37 61 61 61 61 61
L(TOTAL) N/A 102 102 102 108 117 117 132 L1 EE N/A 45 45 45 48 54 54 66 L2 FP(V) N/A 57 57 57 60 63 63 66 100% RETURN AIR OPENING (BOTTOM)
K N/A 19 19 22 25 30 34 37J N/A 19 19 22 25 30 34 37
100% EXHAUST AIR DAMPERSU N/A 47 59 35 47 59 71 83V N/A 12 12 24 24 24 24 24
100% EXHAUST AIR HOODZ N/A 18 18 24 24 24 24 24X N/A 48 60 36 48 60 72 84
(2) 50% OUTSIDE AIR OPENINGA N/A 12 12 12 15 21 21 32B N/A 22 22 32 32 32 32 32
(2) 50% OUTSIDE AIR HOODF N/A 33 33 33 42 42 42 42G N/A 12 12 12 15 21 21 32
EE1 / FP(V) – w/SWSI (FAN PLENUM – VERTICAL RETURN)
All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 79
OA
RA
IN H
OO
D
5.75"
RA
RA
H
50% OARAINHOOD
RAINHOOD
L2
L1
H
K
W J
EA
50% OA
V
V
U
G
X
F
Z
A
B**
L (TOTAL)
RA
K
17"
V
ACCESS PANEL
11"
S S
O S
TOPVIEW
SIDEVIEW
EE3 FP(V)
5. Bottom inlet duct mounting surface is flush with bottom of floor.6. Fan opening is centered on floor.7. Access door standard on opposite side on fan segment
for CP 350-1030.8. Motor on end (shown dotted) for unit sizes CP350, 460 & 530.
Dimensions are in inches.NOTES:1. An access door is supplied as standard on the coil header side of the unit.2. Access doors (opposite coil header side of the unit), access doors (both sides of
the unit), and perforated liners are all optional.3. The EE, FP Segment must be the first segment in direction of airflow.4. Access is required below the unit to service the lower fan bearing.
ECONOMIZER / FAN PLENUM – VERTICAL RETURN – CP350 - 1030
* Dimension includes 2" end wall.
**50% Outside Air opening, Nodamper, both sides.
S = Standard Access DoorO = Optional Access Door
LD06469
DIMENSIONUNIT SIZE
350 400 460 530 680 860 1030W 79 91 79 91 115 127 151H 85 85 110 110 110 122 122
L (TOTAL) 105 111 111 123 129 141 141 L1 E E 30 30 30 30 30 36 36 L2 FP(V) 75 81 81 93 99 105 105 100% RETURN AIR OPENING (BOTTOM)
K 41 46 46 50 63 63 63J 41 46 46 50 63 63 63
(2) 50% OUTSIDE AIR OPENINGA 51 57 63 75 81 87 87B 24 24 30 30 30 39 39
100% RETURN, OUTSIDE, EXHAUST AIR DAMPERSU 71 83 71 83 107 119 143V 21 21 27 27 27 46 46
100% EXHAUST AIR HOODZ 24 24 24 24 24 24 24X 72 84 72 84 108 120 144
(2) 50% OUTSIDE AIR HOODF 36 36 36 36 36 48 48G 51 57 63 75 81 87 87
EE3 / FP(V) – w/SWSI (FAN PLENUM VERTICAL RETURN)
All dimensions are approximate andnot certified for construction.
80 YORK INTERNATIONAL
Segment Dimensions
Dimensions are in inches.NOTES: 1. An access door is supplied as standard on the coil header side of the unit.
2. Access doors (both sides of the unit), and perforated liners are all optional.3. Bottom inlet duct mounting surface is flush with bottom of floor.4. CP860 & CP1030 length includes shipping split steel.
LD06276
* Dimension includes 2" end wall.
S = Standard Access DoorO = Optional Access Door
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
L (TOTAL) 132 138 150 144 153 171 180 195 207 213 219 231 237 261 282 L1 EE 57 63 72 57 63 72 78 84 78 84 78 84 90 84 96 L2 FP(H) 75 75 78 87 90 99 102 111 129 129 141 147 147 177 186 100% RETURN AIR OPENING (BOTTOM OR FRONT)
C 11.5 11.5 11.5 19.0 19.0 19.0 19.0 19.0 29.5 29.5 38.5 38.5 38.5 37 37J 24 36 48 27 36 48 60 72 60 72 60 72 96 108 132K 15 15 15 24 24 24 24 24 27 27 33 33 33 48 48
100% MIXING, EXHAUST, OUTSIDE AIR OPENINGSA 21 27 36 21 27 36 42 48 42 48 42 48 54 48 60B 20 20 20 40 40 40 40 40 50 50 72 72 72 93 93
100% EXHAUST AND OUTSIDE AIR HOODSF 24 24 24 36 36 36 42 42 30 30 39 42 42 45 45G 25.5 31.5 40.5 25.5 31.5 40.5 46.5 52.5 45.3 51.3 45.3 51.3 57.3 51.3 63.3
EE2 / FP(H) – (FAN PLENUM – HORIZONTAL RETURN)
All dimensions are approximate andnot certified for construction.
ECONOMIZER / FAN PLENUM – HORIZONTAL RETURN
FORM 100.10-EG2
YORK INTERNATIONAL 81
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305
W 43 55 67 43 55 67 79 91H 37 37 37 61 61 61 61 61
L (TOTAL) 102 108 120 108 117 135 144 150 L1 E E 57 63 72 57 63 72 78 84 L2 F E 45 45 48 51 54 63 66 66 100% RETURN AIR OPENINGS (BOTTOM)
C 23 23 26 23 26 35 38 38J 24 36 48 27 36 48 60 72K 15 15 15 24 24 24 24 24
100% EXHAUST AIR HOOD DIMENSIONSX 20.4 20.4 24.9 28 36 30 40 40Z 24 24 24 24 24 36 36 36
100% MIXING & OUTSIDE AIR DAMPER OPENINGSA 21 27 36 21 27 36 42 48B 20 20 20 40 40 40 40 40
100% OUTSIDE AIR HOODF 24 24 24 36 36 36 42 42G 21 27 36 21 27 36 42 48
EE4 / FE – ECONOMIZER / FC EXHAUST FAN
Dimensions are in inches. NOTES: 1. An access door is supplied as standard on the coil header side of the unit.
2. Access doors (opposite coil header side of the unit), access doors (both sides of the unit), and perforated liners are all optional.3. An expanded metal screen over the return air opening is standard.4. FE Segment must be the first segment in direction of airflow.5. Forward curved fans (only) are available as exhaust air fans.6. Exhaust air damper is barometric type, no actuator(s) required.7. CP860 & CP1030 length includes shipping split.
ECONOMIZER / EXHAUST FAN – CP65 - 305
LD06277
* Dimension includes 2" end wall.
S = Standard Access DoorO = Optional Access Door
All dimensions are approximate andnot certified for construction.
82 YORK INTERNATIONAL
Segment Dimensions
DIMENSION UNIT SIZE350 400 460 530 680 860 1030
W 79 91 79 91 115 127 151H 85 85 110 110 110 122 122
L (TOTAL) 105 111 111 123 129 141 141 L1 E E 30 30 30 30 30 36 36 L2 F E 75 81 81 93 99 105 105 100% RETURN AIR OPENING (BOTTOM)
C 41 47 41 47 59 50 50J 60 72 60 72 96 108 132K 27 27 33 33 33 48 48
(2) 50% OUTSIDE AIR OPENINGA 51 57 63 75 81 87 87B 24 24 30 30 30 39 39
100% RETURN AIR & OUTSIDE AIR DAMPER OPENINGSU 71 83 71 83 107 119 143V 21 21 27 27 27 46 46
100% EXHAUST AIR HOODX 40 50 50 60 60 74 88Z 48 48 48 60 60 60 60
50% OUTSIDE HOODF 36 36 36 36 36 48 48G 51 57 63 75 81 87 87
ECONOMIZER / EXHAUST FAN – CP350-1030
NOTES:
1. An access door is supplied as standard on the coil headerside of the unit.
2. Access doors (opposite coil header side of the unit), accessdoors (both sides of the unit), and perforated liners are all optional.
3. An expanded metal screen over the return air opening isstandard.
OA
5.75"
RA
H
RAINHOOD
K
RAINHOOD
L2
L1
K
W J
F
EA
50% OA
50% OA
V
V
U
G
X
F
Z
A
B**
L (TOTAL)
C
ACCESS PANEL
S S
O S
BAROMETRICDAMPER
HR
AIN
HO
OD
EE3FE
LD06474
**50% Outside Air opening,No damper
S = Standard Access DoorO = Optional Access Door
All dimensions are approximate andnot certified for construction.
4. The FE Segment must be the first segment in direction of airflow.5. Forward curved fans (only) are available as exhaust air fans.6. Exhaust air damper is barometric type, no actuators required.7. CP860 & CP1030 length includes shipping split.
8. Access door standard on opposite side on fan segment forCP350 - 1030.
Dimensions are in inches.
EE3 / FE – ECONOMIZER / FC EXHAUST FAN
FORM 100.10-EG2
YORK INTERNATIONAL 83
ACCESS SEGMENT
Dimensions are in inches.NOTES: 1. An access door is supplied as standard on the coil header side of the unit.
2. Access doors (both sides of the unit), and perforated liners are all optional.3. Access Segments may be used at any point in the unit configuration.4. LA or XA must be used with inward opening doors downstream of supply fan.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
MA, LA AND XA – ACCESS SEGMENT DIMENSIONS
LD06007
All dimensions are approximate andnot certified for construction.
S = Standard Access DoorO = Optional Access Door
84 YORK INTERNATIONAL
Segment Dimensions
DI – DIFFUSER
Dimensions are in inches.
NOTES: 1. Access doors must be placed in adjacent segments.2. Perforated liner is optional.3. The Diffuser Segment must be placed immediately downstream of a rear-discharge, rear fan segment when filters, attenuators,
humidifiers and/or coils are downstream.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 18 18 21 21 24 27 30 30 36 36 42 45 48 51 57
DIFFUSER DIMENSIONS
LD00041
All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 85
SOUND ATTENUATORSTANDARD (HP), HOSPITAL (LHP), OR LOW FREQUENCY (SPC)
AT3 – SOUND ATTENUATOR (3')AT5 – SOUND ATTENUATOR (5')AT7 – SOUND ATTENUATOR (7')
Dimensions are in inches.NOTES: 1. Access doors must be placed in adjacent segments.
2. Solid lining (only) available in the Sound Attenuator Segments.3. Sound attenuator segment cannot be adjacent to coil, filters, humidifiers and DWDI fan segments.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122 AT 3 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
L AT 5 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 AT 7 84 84 84 84 84 84 84 84 84 84 84 84 84 84 84
SOUND ATTENUATOR DIMENSIONS
LD00042
All dimensions are approximate andnot certified for construction.
86 YORK INTERNATIONAL
Segment Dimensions
HM – HUMIDIFIER
Dimensions are in inches.
NOTES: 1. Humidifier Segments have a double sloped drain pan with a condensate connection opposite of the coil header side of the unit.2. Solid lining (only) available in the Humidifier Segment.3. A pipe chase is provided on the header side of the unit to accommodate steam separator, strainers and piping.4. Segment must be accessible from upstream or downstream segments, otherwise optional opposite side access door is required.5. Steam separators, strainers and traps will be shipped loose for field installation.6. Dispersion tubes are Factory-mounted. All piping in field by others.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 30 30 30 33 33 33 33 33 33 33 33 33 33 48 48
HM – HUMIDIFIER DIMENSIONS
LD05988
All dimensions are approximate andnot certified for construction.
PIPECHASE
FORM 100.10-EG2
YORK INTERNATIONAL 87
EH – ELECTRIC HEAT
Dimensions are in inches.NOTES: 1. Reference page 44 for electric heat capacity and selection.
2. An access door is supplied as standard on the coil header side of the unit.3. Additional access doors are not available.4. When a step controller or disconnect is required, the EH42 segment is required.5. Electric heat segment complete w/internal terminal box.6. EH30 required for more than 2 steps.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24
EH30 – ELECTRIC HEAT DIMENSIONS
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
EH42 – ELECTRIC HEAT DIMENSIONS
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42
EH24 – ELECTRIC HEAT DIMENSIONS
LD06839Refer to Electric Heat Wiring Diagramon page 105.
All dimensions are approximate andnot certified for construction.
88 YORK INTERNATIONAL
Segment Dimensions
IG – INDIRECT FIRED GAS CONFIGURATIONS
GAS HEAT DIMENSIONS DIMENSION UNIT SIZE
170 215 250 305 350 400 460 530 680 860 1030 H 61 61 61 61 85 85 110 110 110 122 122 J* 51 51 60 60 60 60 60 72 72 72 81 K 36 36 36 36 36 36 36 36 36 36 48 L 63 66 75 78 78 81 84 99 102 105 120 W 55 67 79 91 79 91 79 91 115 127 151
Dimensions are in inches.NOTE: *With largest available burner.
LD06778
L
H
5.75
L
W
K
INDUCER FAN
J
TOP VIEW SIDE VIEW
All dimensions are approximate andnot certified for construction.
FORM 100.10-EG2
YORK INTERNATIONAL 89
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 30 30 30 36 36 36 36 36 42 42 48 48 48 63 63*L 30 30 30 30 30 30 30 30 30 30 30 30 30 36 36
* When rear discharge is selected only.
SIDE OPENINGN 15 21 21 21 21 21 21 21 27 33 33 33 33 48 48M 24 24 24 24 36 48 48 48 60 60 60 72 72 105 105
DP – DISCHARGE PLENUM
Dimensions are in inches.NOTES: 1. The DPR / DPB / DPT Segment must be the last segment in direction of airflow except when using the CE segment.
2. An access door is supplied as standard, on drive side of unit.3. Access doors (both sides of the unit), window in door and perforated liners are all optional.4. An expanded metal screen is standard in the DP(B) Segment.
DISCHARGE OPENING DIMENSIONSUNIT D C J KSIZE
65 9.5 11.5 24 1585 9.5 11.5 36 15
105 9.5 11.5 48 15125 9.5 20.5 24 21170 9.5 20.5 36 21215 9.5 20.5 48 21250 9.5 20.5 60 21305 9.5 20.5 72 21350 9.5 29.5 60 27400 9.5 29.5 72 27460 9.5 38.5 60 33530 9.5 38.5 72 33680 9.5 38.5 96 33860 9.5 37.0 108 48
1030 9.5 37.0 132 48Dimensions are in inches.
LD05943
LD06279
DISCHARGE PLENUM DIMENSIONS
*Bottom Discharge Flushwith Floor
**Dimension included end wall.
S = Standard Access DoorO = Optional Access Door
All dimensions are approximate andnot certified for construction.
90 YORK INTERNATIONAL
AB – AIR BLENDER
Dimensions are in inches.NOTES: 1. Air blender should be applied immediately downstream of the Inlet Segments.
2. Access doors must be placed in adjacent segments.3. Perforated liner is optional.4. For Variable Air Volume applications, contact the local YORK representative.
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122L 33 33 36 36 36 36 36 36 54 54 87 93 72 54 60
AIR BLENDER DIMENSIONS
LD00030
All dimensions are approximate andnot certified for construction.
Segment Dimensions
FORM 100.10-EG2
YORK INTERNATIONAL 91
EF – END FLANGE
Dimensions are in inches.
NOTES: 1. An End Flange Segment must be used when the first segment in direction of airflow is not an Inlet Segment (MB, FR, FE, FP).or the last segment in direction or airflow is not a Discharge Plenum Segment (DP) or a Fan Segment (FS / FP).
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122X 36 48 60 36 48 60 72 84 72 84 72 84 108 120 144Y 24 24 24 48 48 48 48 48 72 72 96 96 96 108 108
END FLANGE DIMENSIONS
LD05942
All dimensions are approximate andnot certified for construction.
92 YORK INTERNATIONAL
NS – NON-STANDARD
Dimensions are in inches.NOTES: 1. Perforated liner is optional.
2. Non-Standard Segments may be used at any point in the unit configuration between the entering-air and leaving-airsegments.
3. Non-Standard Segments must be ordered in 3" increments of length up to ____?
DIMENSION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
W 43 55 67 43 55 67 79 91 79 91 79 91 115 127 151H 37 37 37 61 61 61 61 61 85 85 110 110 110 122 122
NONSTANDARD DIMENSIONS
LD05989
All dimensions are approximate andnot certified for construction.
Segment Dimensions
FORM 100.10-EG2
YORK INTERNATIONAL 93
Physical Data
NOTES: 1. Motor weight must be added to the Fan Segment weight for TOTAL Segment weight. See page 94 for motor weights.2. Coil weight(s) must be added to the Coil Segment weight for TOTAL Segment weight. See pages 89-93 for specific coil weights.3. Air-Modulator weight must be added to the Control Enclosure Segment (CE).
CURBPAK SEGMENT OVERALL DIMENSIONS AND WEIGHT CALCULATIONSCURBPAK AHU LENGTH & WEIGHT CALCULATIONS
SEGMENT SEGMENT LENGTH SEGMENT WEIGHTMA - AccessLA - AccessXA - AccessAB - Air BlenderIB - Face & Bypass DamperCE - Control EnclosureSC - Short CoilMC - Medium CoilLC - Long CoilSS - DemountDI - DiffuserDP - Discharge PlenumEF - End FlangeEH - Electric HeatFF - Flat Filter (2" & 4")AF - Angle Filter (2")RF - Rigid Filter 12")BF - Bag Filter (21" & 32")CF - Carbon FilterHF - HEPA FilterHC - Heat-CoilIC - Heat-Integral Face & Bypass CoilHM - HumidifierIG - Indirect Gas HeatNS - Non-StandardMB - Mixing BoxEE / FR - lnlet/Economizer w/DWDI Return Fan (100% OA/EA/RA)EE / MB - Front Return Inlet/Economizer w/o Return Fan (100% OA/EA/RA)EE / FP - Inlet/Economizer w/SWSI Plenum Return Fan (100% OA/EA/RA)EE / FE - Inlet/Economizer w/FC Exhaust Fan (100% OA/EA/RA)AT- Sound AttenuatorFS - Supply FanFP - SWSI Plenum Supply Fan
UNIT TOTALS TOTAL LENGTH = TOTAL WEIGHT =TOTAL WIDTH =TOTAL HEIGHT =
94 YORK INTERNATIONAL
Physical Data
MA 209 228 246 258 275 293 312 331 354 390 399 439 528 721 798 LA 251 273 295 309 330 352 374 414 442 487 499 549 660 901 998 XA 301 328 354 371 396 422 449 517 553 609 616 686 825 1126 1248BLENDER SEGMENT AB 383 519 634 603 812 827 810 986 1691 1922 2738 3134 3519 4923 5319COIL SEGMENT SC (13") 188 215 245 275 309 348 388 433 480 535 553 623 761 1038 1151 MC (20") 260 295 338 365 411 464 518 579 639 712 733 826 1013 1381 1531 LC (27-3/8") 309 352 403 430 484 548 614 684 758 845 871 987 1217 1659 1839 HC (7-3/8") 111 127 143 145 162 180 200 200 243 267 273 303 361 493 545 IC - IFB, 2 ROW 418 453 496 N/A 659 712 766 826 993 1066 N/A N/A N/A N/A N/A IC - IFB, 4 ROW 486 529 580 N/A 756 820 886 956 1133 1220 N/A N/A N/A N/A N/A IC - VIFB,2 N/A N/A N/A 613 659 712 766 826 993 1066 1195 1288 1475 2011 2230COIL SEGMENT PIPE CHASE ENCLOSURE SC 140 140 140 231 231 231 231 231 323 323 437 437 437 595 660 MC 158 158 158 248 248 248 248 248 354 354 462 462 462 630 699 LC 177 177 177 272 272 272 272 272 375 375 498 498 498 680 753 HC 112 112 112 162 162 162 162 162 194 194 218 218 218 298 329CONTROL ENCLOSURE SEGMENT CE 407 462 471 526 587 658 728 827 884 975 986 1098 1320 1801 1995DIFFUSER SEGMENT DI 161 183 235 237 294 361 436 480 604 660 736 853 1086 1480 1641DISCHARGE PLENUM SEGMENT DPB - DPR - DPT 240 272 307 355 394 438 481 526 647 701 758 822 952 1298 1438ELECTRIC HEAT SEGMENT EH24 - 24" 301 342 389 386 432 483 536 591 646 712 715 793 948 1293 1433 EH30 - 30" 367 417 476 474 530 596 662 734 805 890 901 1008 1221 1665 1845 EH42 - 42" 479 543 619 619 692 777 862 954 1048 1157 1174 1306 1570 2038 2258FIRED GAS HEAT IG 1757 2055 2793 3241 3301 3748 3821 5475 6490 7977 12022END FLANGE & DEMOUNT SEGMENT EF & SS 56 64 72 73 81 90 100 110 122 134 136 150 175 238 264FACE AND BYPASS DAMPER SEGMENT IB 161 199 243 239 304 343 383 425 512 568 625 682 795 1085 1203FAN SEGMENT FS - FC1 609 699 859 906 1118 1419 1698 2140 2381 2696 2909 3380 4242 5710 5878 FS - AF1 621 711 903 923 1137 1523 1843 2160 2386 2740 2993 3371 4421 5782 7137 FP 798 908 1073 1211 1497 1894 2229 2596 3207 3566 3741 4337 5817 7965 8524FILTER SEGMENT
FLAT FF - 2" / 4" 65 75 85 89 99 111 123 138 155 172 184 206 250 340 378ANGLE 2" 237 267 304 301 337 376 416 459 499 549 549 608 727 991 1099RIGID 12" 150 171 194 194 217 242 267 295 325 355 361 400 481 655 726BAG 21" 216 244 278 276 309 345 383 422 461 508 510 567 678 924 1024
30" 329 375 427 425 476 536 596 662 727 805 817 915 1111 1515 1679CARBON 1" 486 656 761 931 1111 1175 1555 1694 2380 2694 3000 3379 4220 5754 6378
HEPA 12" 361 397 494 540 603 683 807 1001 1078 1271 1316 1564 1929 2631 2916HUMIDIFIER SEGMENT HM 188 215 245 275 309 348 388 433 480 535 553 623 761 1038 1150INLET / ECONOMIZER SEGMENTS
MB OA 30%, RA 100% 438 527 625 594 700 816 933 1051 1180 1321 1389 1558 1893 2581 2861OA, RA 100% 438 527 625 653 734 892 991 1136 1297 1441 1580 1767 2143 2923 3239OA 100% 438 527 625 612 680 825 904 1040 1112 1235 1297 1451 1758 2398 2656RA 100% 352 420 493 507 592 684 782 870 1029 1141 1218 1359 1639 2235 2453
EE/FR FC1 1193 1397 1737 1676 2049 2679 3178 3561 3901 4587 4902 5549 6762 8742 11138AF1 1205 1409 1783 1693 2063 2575 3033 3541 3896 4543 4986 5540 6941 8814 12397
EE/MB NO RETURN FAN 901 1096 1342 1282 1531 1852 2129 2429 2724 3076 3159 3582 4426 6077 6709EE/FP VERTICAL 1397 1549 1669 1929 2201 2610 2819 3428 3909 4582 4761 6036 7576 9343 10714
HORIZONTAL 1581 1853 2247 2231 2726 3405 3982 4453 5309 6067 6459 7316 9316 11880 14740EE/FE3 EXHAUST FAN 1253 1457 1811 1758 2146 2810 3332 3728 4133 4857 5214 5889 7163 9113 11509
NON-STANDARD SEGMENT NS - 3" 28 32 36 36 41 45 51 55 61 67 68 75 87 119 133SOUND ATTENUATOR SEGMENT AT3 458 536 641 699 820 987 1114 1302 1515 1755 1874 2188 2732 3726 4130 AT5 769 901 1079 1177 1382 1665 1881 2200 2561 2968 3172 3705 4629 6313 6996 AT7 1078 1264 1514 1651 1939 2338 2641 3089 3597 4168 4457 5204 6503 8868 9829
1 Does not include motor, drive, or fan weights. 2 IC Weight does not include coils, weight includes pipe chase. 3 MB, EE / FE weight includes rainhood.
SEGMENT WEIGHTSDESCRIPTION
UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
ACCESS SEGMENT
FORM 100.10-EG2
YORK INTERNATIONAL 95
DESCRIPTION UNIT SIZE65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
ACCESS SEGMENT MA 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 LA 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 XA 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40BLENDER SEGMENT AB 44 44 52 44 47 47 47 47 72 72 116 123 96 72 79COIL SEGMENT SC 77 77 77 84 84 84 84 84 84 84 84 84 84 96 96 MC 96 96 96 101 101 101 101 101 101 101 101 101 101 131 131 LC 107 107 107 113 113 113 113 113 113 113 113 113 113 155 155 HC 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 IC - IFB 2 ROW N/A 101 101 N/A 101 101 101 101 101 N/A N/A N/A N/A N/A N/A IC - IFB 4 ROW N/A 131 131 N/A 131 131 131 131 131 N/A N/A N/A N/A N/A N/A IC - VIFB N/A N/A N/A 119 119 119 119 119 119 119 119 119 119 119 119CONTROL ENCLOSURE SEGMENT CE 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32DIFFUSER SEGMENT DI 24 24 28 28 32 35 40 40 47 47 55 59 64 67 75DISCHARGE PLENUM SEGMENT DP 68 76 84 76 84 91 100 108 108 116 116 123 140 147 163ELECTRIC HEAT SEGMENT EH24 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 EH30 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 EH42 55 55 55 55 55 55 55 55 55 55 55 55 55 55 55END FLANGE & DEMOUNT SEGMENT EF & SS 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8FACE AND BYPASS DAMPER SEGMENT IB 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32FAN SEGMENT FS 88 96 108 96 108 128 140 160 167 175 175 191 207 219 246 FP 112 120 132 120 132 152 163 191 199 207 207 222 239 266 294FILTER SEGMENT FLAT 2" / 4" 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 ANGLE 2" 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 RIGID 12" 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 BAG 21" 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
30" 55 55 55 55 55 55 55 55 55 55 55 55 55 55 55 CARBON 1" 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 HEPA 12" 55 55 55 55 55 55 55 55 55 55 55 55 55 55 55HUMIDIFIER SEGMENT HM 40 40 40 44 44 44 44 44 44 44 44 44 44 52 52INLET / ECONOMIZER SEGMENTS MB OA 30% 68 76 84 76 84 91 100 108 108 116 116 123 140 167 183
RA 100% 68 76 84 76 84 91 100 108 108 116 116 123 140 167 183OA, RA 100% 68 76 84 68 76 84 91 100 91 100 91 100 116 132 147OA 100% 68 76 84 76 84 91 100 108 108 116 116 123 140 167 183RA 100% 163 179 202 172 191 222 242 259 254 278 271 286 326 353 402
EE/FR RETURN FAN 143 160 179 152 167 187 202 219 211 227 219 234 259 286 333 EE/MB NO RETURN FAN 112 128 147 112 128 147 163 179 163 179 163 179 207 227 266 EE/FP VERTICAL 155 172 179 160 175 199 207 234 227 251 242 271 298 318 333
HORIZONTAL 202 219 242 219 239 271 290 318 326 342 342 365 389 417 461 EE/FE EXHAUST FAN 163 179 202 172 191 222 242 259 254 278 271 286 326 385 402 NS (3") 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
SOUND ATTENUATOR SEGMENT AT3 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 AT5 79 79 79 79 79 79 79 79 79 79 79 79 79 79 79 AT7 111 111 111 111 111 111 111 111 111 111 111 111 111 111 111
ROOF CURB WEIGHTS
NOTE: Weights are for 14" high standard curb including nailer.
96 YORK INTERNATIONAL
Physical DataFULL FACE COILSCOIL WEIGHTS – 1/2" (BDW/BDX) (Ibs) (DRY WEIGHT)
ROWS FPI UNIT WEIGHT65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
8 46 54 62 86 98 110 122 134 167 182 211 230 269 373 426
1 10 47 55 64 89 102 115 128 141 175 192 222 243 285 394 45012 48 57 66 91 105 119 133 147 183 201 233 256 301 415 47514 49 59 68 94 109 124 138 153 191 211 244 269 318 435 5008 57 68 79 111 130 150 169 188 237 263 305 338 405 545 629
2 10 59 71 83 117 138 159 180 201 253 282 326 363 438 586 67912 62 75 87 122 145 168 191 213 269 301 348 389 470 627 72914 64 78 92 128 152 177 202 226 286 320 370 414 503 669 7788 74 90 106 145 173 200 228 255 321 359 415 464 561 751 873
3 10 78 95 112 154 184 214 244 274 346 388 447 502 610 813 94712 82 100 118 162 195 228 260 293 370 417 480 540 659 875 102214 85 105 124 170 206 241 277 312 395 445 513 578 708 937 10968 88 107 125 175 210 245 279 314 398 447 517 581 707 933 1087
4 10 93 113 133 186 225 263 301 339 431 485 561 631 772 1016 118712 98 120 141 197 239 281 323 365 464 523 605 682 838 1099 128614 102 126 150 208 254 299 345 390 496 562 648 733 903 1181 13858 99 121 143 201 242 284 326 368 468 528 611 688 843 1104 1291
5 10 105 129 153 214 261 307 353 399 509 576 665 752 925 1208 141512 111 137 163 228 279 330 380 431 550 623 720 815 1006 1311 153914 117 145 173 242 297 352 408 463 591 671 774 879 1088 1415 16648 110 135 161 226 275 324 373 421 538 609 704 796 979 1276 1495
6 10 118 145 173 242 297 351 405 460 587 666 770 872 1077 1400 164412 125 155 185 259 318 378 438 498 637 723 835 948 1175 1524 179314 132 164 197 275 340 405 471 536 686 780 900 1025 1273 1648 19428 140 173 206 288 353 417 481 545 697 790 913 1035 1277 1660 1949
8 10 150 186 222 310 382 453 525 596 763 866 1001 1136 1408 1825 214712 160 199 238 332 411 489 568 647 828 943 1088 1238 1539 1991 234614 170 212 254 354 440 526 612 698 893 1019 1175 1340 1670 2156 25458 171 211 252 350 430 510 590 670 856 971 1121 1273 1575 2047 2407
10 10 183 228 272 377 466 555 645 734 937 1067 1230 1400 1739 2254 265512 195 244 292 404 503 601 699 797 1019 1162 1339 1527 1902 2461 290314 207 260 312 432 539 646 754 861 1101 1257 1448 1654 2066 2668 31518 194 240 287 401 495 589 683 778 996 1133 1308 1488 1848 2390 2814
12 10 208 260 311 433 539 644 749 854 1094 1247 1439 1640 2044 2638 311212 223 279 335 466 582 698 814 930 1192 1362 1570 1793 2240 2886 341014 237 298 360 499 626 753 880 1007 1290 1476 1700 1946 2436 3134 3708
NOTE: Approximate Water Weight = # of Rows x Face Area x 0.9
FORM 100.10-EG2
YORK INTERNATIONAL 97
REDUCED FACE COILSCOIL WEIGHTS – 1/2" (BDW/BDX) (Ibs) (DRY WEIGHT)
ROWS FPI UNIT WEIGHT65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
8 37 45 52 67 77 87 97 107 127 140 167 182 214 242 275
1 10 38 46 53 69 80 91 101 112 133 146 175 192 226 257 29312 39 47 55 71 82 94 105 117 139 153 183 201 238 271 31014 40 48 56 73 85 97 109 121 144 160 191 211 250 286 3288 46 55 65 85 101 116 131 146 176 196 237 263 316 363 419
2 10 47 58 68 89 106 122 139 156 188 210 253 282 340 393 45412 49 60 71 93 111 129 147 165 199 223 269 301 365 422 48914 51 63 74 97 116 136 155 174 211 237 286 320 389 451 5258 60 73 86 111 133 154 176 197 238 267 321 359 436 504 585
3 10 63 77 91 117 141 164 188 211 255 287 346 388 473 548 63812 65 80 95 123 149 174 200 225 273 307 370 417 509 592 69114 68 84 100 129 156 184 211 239 290 327 395 445 546 636 7438 70 86 101 133 160 186 213 240 292 329 398 447 545 633 737
4 10 74 90 107 141 170 199 229 258 315 355 431 485 594 691 80712 77 95 113 149 181 213 245 276 338 382 464 523 643 750 87714 81 100 119 157 191 226 260 295 361 409 496 562 692 809 9488 78 96 114 151 183 215 247 279 342 385 468 528 647 754 881
5 10 83 102 122 161 196 231 266 302 370 419 509 576 708 827 96912 87 108 129 171 209 248 286 324 399 453 550 623 770 900 105714 92 115 137 181 222 264 306 347 428 486 591 671 831 974 11458 87 107 128 170 207 243 280 317 391 442 538 609 749 875 1025
6 10 92 114 137 181 222 263 304 345 426 483 587 666 823 963 113112 98 122 146 193 238 283 328 373 460 523 637 723 896 1051 123614 103 129 155 205 254 303 351 400 495 563 686 780 970 1139 13418 111 137 163 216 264 313 361 409 505 573 697 790 976 1142 1340
8 10 118 147 175 231 285 339 393 446 551 626 763 866 1074 1259 148112 125 156 187 247 306 365 424 483 597 680 828 943 1172 1376 162114 132 166 199 263 327 391 455 520 643 734 893 1019 1270 1493 17628 135 167 200 262 322 382 443 503 620 704 856 971 1203 1409 1656
10 10 144 179 215 282 348 415 482 549 677 771 937 1067 1325 1555 183212 153 192 230 301 375 448 521 595 735 838 1019 1162 1448 1702 200714 162 204 245 321 401 481 561 640 792 905 1101 1257 1570 1848 21838 152 189 226 298 369 439 510 580 718 817 996 1133 1407 1651 1945
12 10 163 204 244 322 400 479 557 636 787 898 1094 1247 1554 1827 215512 174 218 263 346 432 518 604 691 856 978 1192 1362 1701 2003 236614 184 233 281 369 463 558 652 746 925 1059 1290 1476 1848 2178 2577
NOTE: Approximate Water Weight = # of Rows x Face Area x 0.9
98 YORK INTERNATIONAL
Physical DataFULL FACED COILSCOIL WEIGHTS – 5/8" (CDW/CDX) (Ibs) (DRY WEIGHT)
ROWS FPI UNIT WEIGHT65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
8 48 57 66 89 102 115 128 141 178 195 222 243 285 393 449
1 10 49 59 68 91 105 119 133 147 186 205 233 256 301 413 47412 51 60 70 94 109 124 138 153 195 215 244 268 318 434 49814 52 62 72 97 112 128 144 160 203 224 255 281 334 454 5238 61 74 86 117 138 159 180 201 258 288 326 363 438 584 677
2 10 64 77 90 122 145 168 191 213 275 307 348 389 470 625 72612 66 81 95 127 152 177 201 226 291 327 370 414 503 666 77514 69 84 99 133 159 186 212 239 308 346 392 440 536 707 8258 81 98 116 153 184 214 244 274 352 396 447 502 610 810 944
3 10 85 103 122 162 195 227 260 293 378 425 480 540 660 872 101812 88 108 128 170 205 241 277 313 403 454 513 578 709 934 109214 92 113 135 178 216 255 293 332 428 483 545 616 758 995 11668 96 117 138 185 224 262 300 338 438 494 559 630 771 1010 1181
4 10 101 124 146 196 238 280 322 364 472 533 603 681 836 1093 127912 106 130 155 207 253 298 344 389 505 572 647 732 902 1175 137814 111 137 163 218 267 316 366 415 539 611 690 782 967 1257 14778 109 134 159 213 260 306 352 399 518 586 664 750 924 1201 1408
5 10 115 142 169 227 278 329 380 430 560 635 718 814 1005 1304 153212 121 151 180 241 296 351 407 462 602 684 773 877 1087 1407 165514 128 159 190 254 314 374 434 494 644 732 827 941 1169 1510 17798 122 150 179 241 296 350 404 459 598 679 768 871 1076 1393 1636
6 10 129 161 192 258 317 377 437 497 649 737 833 947 1174 1516 178412 137 171 205 274 339 405 470 535 699 796 899 1023 1272 1640 193314 145 181 217 290 361 432 503 573 749 854 964 1100 1370 1763 20818 156 193 230 308 380 452 523 595 777 883 998 1134 1406 1815 2137
8 10 166 206 247 330 409 488 567 646 843 961 1085 1236 1537 1980 233412 176 220 264 352 438 524 611 697 910 1039 1172 1337 1668 2145 253214 186 234 281 374 467 561 654 748 977 1116 1260 1439 1799 2310 27298 190 236 282 376 465 554 643 733 955 1087 1228 1397 1737 2242 2642
10 10 203 253 304 403 501 599 698 796 1038 1185 1337 1525 1900 2448 288912 215 270 325 430 537 645 752 860 1122 1282 1446 1652 2064 2654 313614 228 287 346 457 574 690 807 923 1206 1380 1555 1779 2227 2860 33838 216 270 324 432 537 642 748 853 1115 1272 1436 1638 2042 2625 3098
12 10 231 290 349 464 580 697 813 929 1215 1389 1567 1791 2238 2872 339412 246 310 374 497 624 751 878 1006 1315 1506 1698 1943 2435 3119 369114 262 331 400 530 668 806 944 1082 1416 1623 1829 2096 2631 3366 3987
NOTE: Approximate Water Weight = # of Rows x Face Area x 1.15
FORM 100.10-EG2
YORK INTERNATIONAL 99
REDUCED FACE COILSCOIL WEIGHTS – 5/8" (CDW/CDX) (Ibs) (DRY WEIGHT)
ROWS FPI UNIT WEIGHT65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
8 38 46 53 70 81 92 102 113 140 154 178 195 230 255 291
1 10 39 47 55 72 83 95 106 118 146 161 186 205 242 270 30912 40 48 56 74 86 98 110 122 152 169 195 215 255 285 32614 41 49 58 76 89 101 114 127 159 176 203 224 267 299 343
8 47 58 68 90 107 124 141 157 199 222 258 288 347 390 452
2 10 49 60 71 94 112 131 149 167 212 237 275 307 372 420 48712 51 63 74 98 118 137 157 176 224 251 291 327 397 449 52214 53 65 77 102 123 144 165 185 236 266 308 346 422 478 5568 63 77 91 119 142 166 190 214 271 305 352 396 482 545 634
3 10 65 80 95 125 150 176 202 228 290 326 378 425 519 589 68712 68 84 100 131 158 186 214 242 308 348 403 454 557 632 73914 71 88 105 137 166 196 226 256 327 370 428 483 595 676 7918 73 90 107 142 172 201 231 261 335 377 438 494 605 686 801
4 10 77 95 113 150 182 215 247 279 359 406 472 533 655 744 87112 81 100 119 158 193 228 263 298 384 435 505 572 705 802 94114 84 105 125 166 204 241 279 317 409 464 539 611 755 861 10118 83 102 122 162 198 234 269 305 394 446 518 586 722 821 962
5 10 87 108 129 172 211 250 289 328 425 482 560 635 785 894 104912 92 114 137 182 225 267 309 352 456 518 602 684 847 967 113714 96 120 144 192 238 284 329 375 486 554 644 732 910 1039 12248 92 114 136 183 225 266 308 349 453 514 598 679 839 956 1123
6 10 97 121 145 195 240 286 332 377 490 557 649 737 914 1043 122812 103 129 154 207 256 306 356 405 527 600 699 796 989 1131 133214 108 136 164 219 272 326 379 433 564 644 749 854 1064 1218 14378 117 146 175 233 288 342 397 451 587 667 777 883 1095 1249 1470
8 10 125 156 187 249 309 369 429 489 636 725 843 961 1195 1366 161012 132 165 199 265 331 396 461 526 686 782 910 1039 1295 1482 174914 139 175 211 281 352 422 493 563 735 840 977 1116 1395 1598 18898 143 179 215 284 352 420 487 555 721 821 955 1087 1352 1544 1819
10 10 152 191 230 304 379 453 527 602 783 893 1038 1185 1477 1689 199412 162 203 245 324 405 486 567 648 845 965 1122 1282 1602 1835 216814 171 215 260 344 432 520 607 695 906 1037 1206 1380 1728 1980 23428 162 203 244 325 405 484 564 644 839 958 1115 1272 1586 1814 2141
12 10 173 218 262 349 437 524 612 699 914 1044 1215 1389 1736 1989 235012 184 232 280 373 469 564 660 755 988 1131 1315 1506 1886 2163 255914 195 247 298 397 501 604 708 811 1062 1217 1416 1623 2037 2337 2769
NOTE: Approximate Water Weight = # of Rows x Face Area x 1.15
100 YORK INTERNATIONAL
Physical Data
MOTORHORSEPOWER
1 1-1/2 2 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100HI-EFF ODP 36 42 42 67 78 106 118 170 212 240 283 372 440 591 670 750PREMIUM-EFF ODP 36 42 42 87 94 130 126 217 250 309 300 415 414 652 706 7822 SPD ODP (1800/900) 26 29 33 60 71 94 116 203 208 266 280 358 398 N/A N/A N/A2 SPD ODP (1800/1200) 29 32 61 71 115 131 192 298 270 295 296 400 N/A N/A N/A N/AHI-EFF TEFC 38 46 44 81 89 142 154 250 287 394 436 661 686 790 840 1450PREMIUM-EFF TEFC N/A 66 66 92 99 158 200 259 290 358 436 661 686 800 850 14752 SPD TEFC (1800/900) 28 39 42 65 83 83 107 218 331 393 440 504 538 N/A N/A N/A2 SPD TEFC (1800/1200) 31 37 68 73 107 128 222 223 361 334 470 516 796 N/A N/A N/A
MOTOR WEIGHTS (lbs.)
COIL WEIGHTS1" STEAM DISTRIBUTING COIL (1 ROW) FULL & REDUCED FACE COILS (DRY WEIGHT)
UNIT SIZECOIL
65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030
FULL FACE 67 84 99 119 158 187 216 244 330 374 431 488 614 768 921
REDUCED FACE 54 67 79 95 127 150 172 195 264 299 345 391 491 614 736
SECTIONUNIT SIZE
65 85 105 125 170 215 250 305 350 400 460 530 680 860 1030IFB - 2 ROW N/A 220 260 N/A 398 525 562 562 755 755 N/A N/A N/A N/A N/AIFB - 4 ROW N/A 374 442 N/A 677 893 955 955 1284 1284 N/A N/A N/A N/A N/AVIFB - 1 ROW N/A N/A N/A 327 386 453 534 600 673 760 840 950 1270 1460 1658VIFB - 2 ROW N/A N/A N/A 354 422 498 535 700 736 838 966 1107 1479 1683 1917VIFB - 3 ROW N/A N/A N/A 384 462 548 596 750 811 925 1062 1218 1639 1894 2150
INTEGRAL FACE & BYPASS COILS (lbs.)
FURNACE WEIGHTS (Including Section)
MBH (lbs.)CurbPak SIZE
43 44 45 46 47 66 67 86 87 89 910
150 - 250 — 1,419 — — — — — — — — —
300 - 400 — — 1,603 — — — — — — — —
450 - 500 — — — 2,008 2,112 2,380 2,510 2,715 2,926 — —
600 - 750 — — — 2,338 2,442 2,710 2,840 3,025 3,256 — —
850 - 1000 — — — — 2,682 — 3,080 — 3,496 — —
1250 - 1500 — — — — — — — — 4,271 4,692 —
1750 - 2000 — — — — — — — — — 5,192 6,462
FORM 100.10-EG2
YORK INTERNATIONAL 101
WING VIFB COIL CONNECTION LOCATION
UNIT L.J. WING 1 ROW COIL 2 ROW COIL 3 ROW COIL 2 ROW COIL
SIZE MODEL NO. HW or STEAM STEAM STEAM HOT WATERA B CONN. A B CONN. A B CONN. A B CONN.
65 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A85 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A105 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A125 VIFB - VA-3 11.69 44.63 3" NPT 8.88 46.38 3" NPT 8.56 46.88 3" NPT 9.38 12.38 2" NPT170 VIFB - VA-4 11.69 44.63 3" NPT 8.88 46.38 3" NPT 8.56 46.88 3" NPT 9.38 12.38 2" NPT215 VIFB - VA-5 11.69 44.63 3" NPT 8.88 46.38 3" NPT 8.56 46.88 3" NPT 9.38 12.38 2" NPT250 VIFB - VA-6 11.69 44.63 3" NPT 8.88 46.38 3" NPT 8.56 46.88 3" NPT 9.38 12.38 2" NPT305 VIFB - VA-7 11.69 44.63 3" NPT 8.88 46.38 3" NPT 8.56 46.88 3" NPT 9.38 12.38 2" NPT350 VIFB - VC-6 11.69 68.63 3" NPT 8.88 70.38 3" NPT 8.56 70.88 3" NPT 9.38 12.38 2" NPT400 VIFB - VC-7 11.69 68.63 3" NPT 8.88 70.38 3" NPT 8.56 70.88 3" NPT 9.38 12.38 2" NPT460 VIFB - VE-6 8.75 95.69 3" NPT 8.88 100.38 3" NPT 8.56 100.88 3" NPT 9.38 12.38 2" NPT530 VIFB - VE-7 8.75 95.69 3" NPT 8.88 100.38 3" NPT 8.56 100.88 3" NPT 9.38 12.38 2" NPT680 VIFB - VE-10 8.75 95.69 3" NPT 8.88 100.38 3" NPT 9.69 100.88 4" NPT 9.38 12.38 2" NPT860 VIFB - VE-11 8.75 95.69 3" NPT 9.38 100.38 4" NPT 9.69 100.88 4" NPT 9.38 12.38 2" NPT1030 VIFB - VE-12 8.75 95.69 3" NPT 9.38 100.38 4" NPT 9.69 100.88 4" NPT 9.38 12.38 2" NPT
LD03617
“C” DIMENSIONSTEAM WATER
UNIT SIZE 1 ROW 2 ROW 3 ROW 1 ROW 2 ROW125-215 28.75 28.25 28.00 28.75 28.06
250-1030 24.13 30.25 31.25 24.13 28.06
102 YORK INTERNATIONAL
Physical Data
WING IFB COIL CONNECTION LOCATION
LD03618
AIRFLOW
SINGLE SECTION DOUBLE SECTIONUNIT L.J. WING 2 ROW 4 ROWSIZE MODEL NO. HOT WATER or STEAM HOT WATER or STEAM
A B CONN. A B CONN.65 N/A N/A N/A N/A N/A N/A N/A85 IFB - A-42 9.69 23.69 3" NPT 9.69 23.69 3" NPT
105 IFB - A-54 9.69 23.69 3" NPT 9.69 23.69 3" NPT125 N/A N/A N/A N/A N/A N/A N/A170 IFB - C-42 9.69 39.06 3" NPT 9.69 39.06 3" NPT215 IFB - D-54 9.69 48.25 3" NPT 9.69 48.25 3" NPT250 IFB - D-60 9.69 48.25 3" NPT 9.69 48.25 3" NPT305 IFB - D-60 9.69 48.25 3" NPT 9.69 48.25 3" NPT350 IFB - F-60 9.69 63.56 3" NPT 9.69 63.56 3" NPT400 IFB - F-60 9.69 63.56 3" NPT 9.69 63.56 3" NPT460 N/A N/A N/A N/A N/A N/A N/A530 N/A N/A N/A N/A N/A N/A N/A680 N/A N/A N/A N/A N/A N/A N/A860 N/A N/A N/A N/A N/A N/A N/A
1030 N/A N/A N/A N/A N/A N/A N/A
FORM 100.10-EG2
YORK INTERNATIONAL 103
WATER COIL CONNECTION LOCATIONS1/2" STANDARD COILS – CP65 through CP305
CONN.A MDIA.
1.25 0.75 4.691.50 0.88 4.692.00 1.13 4.942.50 1.38 5.223.00 1.63 5.47
ROWSGDEEP
1-4 7.385-6 10.008 12.63
10 15.2512 17.63
TUBEJDIA.
1/2" 1.31
1.50
L = FL + 3.00
2. RETURN BENDS PROJECT 7/8" (MAX) BEYOND CASING FLANGE.
3. DIMENSIONS - INCHES ± 1/4"
1. STANDARD COILS ARE PROVIDED ON - NOTES
A. 1/2" TUBE DIA - 6 THRU 40 TUBES HIGH
FLL/2
Z = 0.312 DIA HOLES, 6.00" CENTER TO CENTER
H =
FH
H/2
1.50
ZZ
0.75
1.50
1.50
ZZ
0.75
SUPPLY
RETURN
H =
FH
G
1.75
A
J TY
P
1/4" FPT PLUGGEDVENT FITTING
2.001.75 AM
** NOTE : HOLES ARE NOT PUNCHED ON TOP ANDBOTTOM CHANNELS ON COILS WITH FL > 144"
SEENOTE#4
4. CONNECTOR LENGTHS ARE MEASURED FROM THE OUTSIDE OF THE HEADER TO THE END OF THE CONNECTOR.
TUBES HIGH6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
1/2" TUBE DIA. FH 7.50 10.00 12.50 15.00 17.50 20.00 22.50 25.00 27.50 30.00 32.50 35.00 37.50 40.00 42.50 45.00 47.50 50.00
LD06587
AIRFLOWLEFT HAND SHOWNRIGHT HAND OPPOSITE
104 YORK INTERNATIONAL
Physical Data
WATER COIL CONNECTION LOCATIONS5/8" STANDARD COILS – CP65 through CP305
CONN.A MDIA.
1.25 1.50 4.691.50 1.63 4.692.00 1.88 4.942.50 2.13 5.223.00 2.38 5.47
ROWSGDEEP
1-4 7.385-6 10.008 12.6310 15.2512 17.63
TUBEJDIA.
5/8" 0.75
1.50
L = FL + 3.00
2. RETURN BENDS PROJECT 7/8" (MAX) BEYOND CASING FLANGE.3. DIMENSIONS - INCHES ± 1/4"
1. EXPANDED FACE COILS ARE PROVIDED ON - NOTES
A. 5/8" TUBE DIA - 6 THRU 32 TUBES HIGH
FL
L/2
Z = 0.312 DIA HOLES, 6.00" CENTER TO CENTER
H =
FH
+ 1
.50
FH
H/2
0.75
ZZ
0.75
1.50
0.75
ZZ
0.37
5
SUPPLY
RETURN
H =
FH
+ 1
.50
G
1.75
A
J TY
P
1/4" FPT PLUGGEDVENT FITTING
2.001.75 AM
** NOTE : HOLES ARE NOT PUNCHED ON TOP ANDBOTTOM CHANNELS ON COILS WITH FL > 144"
SEENOTE#4
4.CONNECTOR LENGTHS ARE MEASURED FROM THE OUTSIDE OF THE HEADER TO THE END OF THE CONNECTOR.
LD06588
AIRFLOWLEFT HAND SHOWNRIGHT HAND OPPOSITE
TUBES HIGH6 8 10 12 14 16 18 20 22 24 26 28 30 32
5/8" TUBE DIA. FH 9.25 12.25 15.25 18.25 21.25 24.25 27.25 30.25 33.25 36.25 39.25 42.25 45.25 48.25
FORM 100.10-EG2
YORK INTERNATIONAL 105
WATER COIL CONNECTION LOCATIONSTALL COILS – CP350 through CP680
LD02339(r)
AIRFLOWLEFT HAND SHOWNRIGHT HAND OPPOSITE
NOTES: 1. Dimensions – Inches ± 1/4".2. See page 21 for FL.
FH (Fin Height) NOTE: See next page for Full Face 860 - 1030 Coils.UNIT SIZES
TUBE DIM. 350 - 400 460 - 680 860 - 1030DIA. COIL TYPE FULL FACE REDUCED FULL FACE REDUCED FULL FACE REDUCED
FH 67.50 47.50 90.00 67.50 102.50 72.50
1/2"B 35.50 *N/A 45.50 35.50 56.00 38.00C 33.00 *N/A 45.50 33.00 53.50 35.50D 68.00 47.50 90.50 68.00 106.50 73.00
FH 69.50 51.50 90.50 69.50 103.00 72.50
5/8"B 36.25 27.25 45.25 36.25 54.50 38.00C 33.25 24.25 45.25 33.25 54.50 35.50D 69.50 51.50 90.50 69.50 106.00 73.00
TUBEJDIA.
1/2" 1.315/8" 1.50
CONN.A MDIA.
1.25 2.25 4.691.50 2.38 4.692.00 2.63 4.942.50 2.88 5.223.00 3.13 5.47
ROWSGDEEP
1-4 7.385-6 10.008 12.6310 15.2512 17.63
106 YORK INTERNATIONAL
14
3
2
9
G*
A*
C*
A*
B*
Physical Data
TALL - SPLIT COILSBDW and CDW FULL FACE COIL CP860 through CP1030
6
8
9
5
7
ITEM DESCRIPTION QUANTITY / COIL BANK1 Top Assembled Coil 12 Bottom Assembled Coil 13 Intermediate Drain Pan 14 Secondary Drain Pan 29 Headers 2 Supply / 2 Return
ITEM DESCRIPTION QUANTITY / COIL FINPACK
5 Top Fin Pack 16 Bottom Fin Pack 17 End Sheet Connectors 28 Secondary Drain Pan 2
9 Continuous Headers1 Supply and
1 Return
Exploded View of Top Assembled Coil
NOTE: Top and Bottom Assembled Coils are fabricated in the same manner.
LD06475
LD06476
FIN HEIGHTTOTAL COIL TOTAL FIN LENGTH COIL HEIGHT
TYPE Top Bottom 6" Added for 3" Add for CoilBank Bank Coil Channels Channels
CDW 51.5" 51.5" 103.0" CP-860 CP-1030 BDW 50.0" 52.5" 102.5" 120" 144"
*See page 105 for dimensional data.
FORM 100.10-EG2
YORK INTERNATIONAL 107
FH (Fin Height)
STEAM COIL CONNECTION LOCATIONSSTANDARD COILS – CP65 through CP305
LD02601
NOTES: 1. Dimensions – Inches ± 1/4".2. Coil shown is for Horizontal Airflow.3. See page 23 for FL.
NOTES:1. Dimensions – Inches ± 1/4".2. Coil shown is for Horizontal
Airflow.3. See page 23 for FL.
AIRFLOWLEFT HAND SHOWNRIGHT HAND OPPOSITE
TALL COILS – CP350 through CP1030
LD02602(910)
AIRFLOWLEFT HAND SHOWNRIGHT HAND OPPOSITE
CP350-680
CP860-1030
FH (Fin Height)
UNIT SIZESTUBE DIM. 65 - 105 125 - 305DIA. COIL TYPE FULL FACE REDUCED FULL FACE REDUCED
1"FH 21.00 15.00 45.00 33.00A 12.00 9.00 24.00 18.00
UNIT SIZESTUBE DIM. 350 - 400 460 - 680 860 - 1030DIA. COIL TYPE FULL FACE REDUCED FULL FACE REDUCED FULL FACE REDUCED
FH 69.00 48.00 90.00 69.00 102.00 72.00A 19.50 25.50 24.00 19.50 19.50 19.50
1" B 37.75 *N/A 46.75 37.75 38.00 37.75SDC C 54.00 *N/A 69.00 54.00 54.00 55.50
D N/A N/A N/A N/A 73.50 N/AE N/A N/A N/A N/A 88.50 N/A
108 YORK INTERNATIONAL
Physical DataEXPANSION COIL CONNECTION LOCATIONS
1/2" STANDARD COILS – CP65 through CP305
CONN.A MDIA.
1.25 0.75 4.691.50 0.88 4.692.00 1.13 4.942.50 1.38 5.223.00 1.63 5.47
ROWSGDEEP
1-4 7.385-6 10.008 12.63
10 15.2512 17.63
TUBES HIGH6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
1/2" TUBE DIA. FH 7.50 10.00 12.50 15.00 17.50 20.00 22.50 25.00 27.50 30.00 32.50 35.00 37.50 40.00 42.50 45.00 47.50 50.00
TUBEJDIA.
1/2" 1.31
TUBE ROWSWDIA. DEEP
1/2"1, 2, 4, 5, 6, 10 & 12 -0.312
3 & 8 0.312
M
L = FL + 3.00
1.50
A. 1/2" TUBE DIA - 6 THRU 40 TUBES HIGH
3. DIMENSIONS - INCHES ± 1/4"
1. STANDARD COILS ARE PROVIDED ON -
2. RETURN BENDS PROJECT 7/8" (MAX) BEYOND CASING FLANGE.
NOTES:
Z = 0.312 DIA HOLES, 6.00" CENTER TO CENTER
L/2
FL
H =
FH
H/2
1.50
0.75
ZZ
1.50
1.50
ZZ
0.75
1.75
H =
FH
H/2
+ W
GJ
TY
P A
1.75
SUPPLY
RETURN
AIRFLOWLEFT HAND SHOWNRIGHT HAND OPPOSITE
LD06591
FORM 100.10-EG2
YORK INTERNATIONAL 109
M
L = FL + 3.00
1.50
A. 5/8" TUBE DIA - 6 THRU 32 TUBES HIGH
3. DIMENSIONS - INCHES ± 1/4"
1. STANDARD COILS ARE PROVIDED ON -
2. RETURN BENDS PROJECT 7/8" (MAX) BEYOND CASING FLANGE.
NOTES:
Z = 0.312 DIA HOLES, 6.00" CENTER TO CENTER
L/2
FL
FH
H =
FH
+ 1
.500
H/2
0.75
0.75
ZZ
0.75
1.50
ZZ
0.37
5
1.75
H =
FH
+ 1
.50
H/2
+ W
G
J T
YP A
1.75
SUPPLY
RETURN
CONN.A MDIA.
1.25 1.50 4.691.50 1.63 4.692.00 1.88 4.942.50 2.13 5.223.00 2.38 5.47
ROWSGDEEP
1-4 7.385-6 10.008 12.63
10 15.2512 17.63
TUBEJDIA.
5/8" 0.75
TUBE ROWSWDIA. DEEP
5/8"1, 2, 4, 5, 6, 10 & 12 -0.375
3 & 8 0.375
AIRFLOWLEFT HAND SHOWNRIGHT HAND OPPOSITE
LD06592
EXPANSION COIL CONNECTION LOCATIONS5/8" STANDARD COILS – CP65 through CP305
TUBES HIGH6 8 10 12 14 16 18 20 22 24 26 28 30 32
5/8" TUBE DIA. FH 9.25 12.25 15.25 18.25 21.25 24.25 27.25 30.25 33.25 36.25 39.25 42.25 45.25 48.25
110 YORK INTERNATIONAL
Physical Data
EXPANSION COIL CONNECTION LOCATIONSTALL COILS – CP350 through CP1030
AIRFLOWLEFT HAND SHOWNRIGHT HAND OPPOSITE
NOTES: 1. Return bends project 7/8" (max.) beyond casing flange.2. Dimensions – Inches ± 1/4".
LD03620
CONN.A MDIA.
1.25 2.25 4.691.50 2.38 4.692.00 2.63 4.942.50 2.88 5.223.00 3.13 5.47
ROWSGDEEP
1-4 7.385-6 10.008 12.6310 15.2512 17.63
TUBEJDIA.
1/2" 1.315/8" 1.50
FH (Fin Height)
UNIT SIZESTUBE DIM. 350 - 400 460 - 680 860 - 1030DIA. COIL TYPE FULL FACE REDUCED FULL FACE REDUCED FULL FACE REDUCED
FH 67.50 47.50 90.00 67.50 102.50 72.50
1/2"B 35.50 *N/A 45.50 35.50 56.00 38.00C 33.00 *N/A 45.50 33.00 53.50 35.50D 68.00 47.50 90.50 68.00 106.50 73.00
FH 69.50 51.50 90.50 69.50 103.00 72.50
5/8"B 36.25 27.25 45.25 36.25 54.50 38.00C 33.25 24.25 45.25 33.25 54.50 35.50D 69.50 51.50 90.50 69.50 106.00 73.00
FORM 100.10-EG2
YORK INTERNATIONAL 111
PIPE CHASE ENCLOSURE
LD06280
Drain connection opposite pipe chase is standard.A header panel covers entire segment.
NOTE: All pipe chases are factory assembled. Typically pipe chases for unit sizes65 to 215, will be factory-mounted. Pipe chases on unit sizes 250 and abovewill ship loose for field mounting.
COIL CONNECTION LOCATIONS (For reference only)
LD00060(r)
NOTES: 1. All coil connection locations begin at a reference point 6.5" above the bottom of the base of the unit for cooling coils in SC, MCand LC segments, and 3.0" downstream the entering air side of the coil segment. For heating coil segments, the reference point is5.75" above the bottom of the base.
2. Sizes 65 - 305 with multiple coils in the same segment, coils are adjacent to one another with no space in between.3. Sizes 350 - 1030 allow 3.0" space after cooling coils and no space after heating coils.4. Condensate connection is 1-1/4" MPT, schedule 40 pipe. Connection is located 2.625" above the bottom of the base of the unit and
at the midpoint of the coil segment.5. Pipe chase is not in air stream. Access to unit cannot be achieved through pipe chase because of header cover panel.6. Wall thickness of pipe chase, header covers, return bend panel are 1 inch with insulation.
* Usable working clearance depth is approximately 18".
All dimensions are approximate andnot certified for construction.
112 YORK INTERNATIONAL
Physical DataINLET CONE DIMENSIONS
LD02507
LD02603
FORWARD CURVED FANS
FAN INLET DIMENSIONS “A”DIAMETER WITHOUT VIV WITH VIV
10 x 10 8.78" N/A12 x 12 10.24" 10.38"15 x 15 12.52" 12.62"18 x 18 15.47" 15.50"20 x 20 16.22" 16.25"22 x 22 18.19" 18.06"25 x 25 20.39" 21.31"27 x 27 N/A 23.94"28 x 28 22.95" N/A30 x 30 N/A 26.38"32 x 32 25.79" N/A33 x 33 N/A 29.38"36 x 36 29.02" 32.00"40 x 40 32.72" N/A
AIRFOIL FANS
FANDIAMETER
PLENUM FAN AIRFOIL FAN
INLET DIMENSIONS “B”12" N/A 8.54"13" 8.50" N/A15" 9.44" 10.83"16" 10.41" N/A18" 11.50" 12.01"20" 12.59" 13.46"22" 14.03" 15.16"24" 15.44" N/A25" N/A 17.09"27" 17.03" N/A28" N/A 19.29"30" 18.94 N/A32" N/A 21.65"33" 20.81 N/A36" 23.00" 24.02"40" 25.38" 26.89"44" 28.03" 28.25"49" 30.88" 31.25"54" 34.19" N/A60" 37.81" N/A
FORM 100.10-EG2
YORK INTERNATIONAL 113
UNIT AND COIL HAND SELECTION
LD00051
FAN SEGMENT ACCESS DOOR LOCATIONS
LD00052A
114 YORK INTERNATIONAL
Physical Data
POWER WIRING OPTIONS
U.L. Listed Starter PanelsAnd Disconnects Are Available On All SizesAs A Factory-mounted Option.
LD00059
NOTES: 1. NEMA 3R equivalent panel factory-mounted onthe exterior wall of the unit.
2. NEMA 3R equivalent motor control panel (with aninterlocking non-fused disconnect through thedoor) mounted on the exterior wall of the unit.
LD00053
Diagram represents general mountinglocation of starter panel.
FORM 100.10-EG2
YORK INTERNATIONAL 115
CURBPAK STARTER WIRING
M
AY
BE
LO
CA
TE
D O
N T
HE
LIN
E S
IDE
OF
TH
E M
AIN
DIS
CO
NN
EC
T.
2 -
IF T
HE
120
VA
C L
IGH
TIN
G T
RA
NS
FO
RM
ER
OP
TIO
N IS
US
ED
. T
HE
MO
TO
R C
ON
TR
OL
CIR
CU
IT
(H3)
- R
EM
OT
E D
EV
ICE
- B
Y O
TH
ER
S
1 -
CO
NN
EC
T R
EM
OT
E C
ON
TR
OL
CO
NT
AC
TN
OT
E:
(H2)
(X3)
(H1)
208V
(X1)
2L1
X1
120V
(H1)
2L2
X2
(X1)
2L1
X1
2L1
X1
(H4)
(X2)
120V
2L2
X2
(H2)
230V
(H1)
(H4)
120V
(X1)
(X2)
2L2
X2
(H2)
460V
(H3)
T1
SE
E T
RA
NS
FO
RM
ER
HA
ND
FIR
ES
TA
T
1 FR
EE
ZE
ST
AT
SW
ITC
H
CO
NN
EC
TIO
N D
IAG
RA
MS
OF
F OO
X
XO
OA
UT
O
SE
LEC
TO
R
FU
12X
1
NO
TE
1M
1
CO
NN
EC
TIO
NS
FO
R P
RO
PE
R
FU
SE
OV
ER
LOA
D X2
MO
TO
R
X2
FU
SE
CO
NT
AC
TO
R
T3
OV
ER
LOA
D
T2T1
MO
TO
R3
PH
FR
OM
DR
AW
ING
#202
440
LD06
805
DWG. NO. 202441
116 YORK INTERNATIONAL
Physical DataCURBPAK LIGHTING AND POWER WIRING
SE
GM
EN
TG
AS
OR
HE
AT
ER
ELE
CT
RIC
- T
ER
MIN
AL
PO
INT
- R
EM
OT
E D
EV
ICE
- B
Y O
TH
ER
S
FU
SE O
PT
ION
AL
J1J1
(X2)
G.F
.I
(X4)
115V
SE
RV
ICE
LIG
HT
4T 75V
ALO
AD
CLA
SS
II24
VA
C
LIN
E11
0V
SW
ITC
H
12 A
WG
.
5T
110V
LIN
E
LOA
D24
VA
CC
LAS
S II
75V
A
OP
TIO
NA
L
OP
TIO
NA
L
OP
TIO
NA
L
12 A
WG
.
SU
PP
LY F
AN
RE
TU
RN
FA
N
FU
SE
FU
SE
.5 T
O 7
5 H
.P T
O D
RA
WIN
G #
2024
42
.5 T
O 7
5 H
.P T
O D
RA
WIN
G #
2024
42(V
FD
)
(FU
LL V
OLT
AG
E)
.5 T
O 1
00 H
.P T
O D
RA
WIN
G #
2024
41
(FU
LL V
OLT
AG
E)
.5 T
O 1
00 H
.P T
O D
RA
WIN
G #
2024
41
(VF
D)
DIS
C H4
3T
(H4) 2K
VA
(H1)(H
3)(H
2)
H1
FU
SE
15 A
MP
.C
B1
X4
3PH,60HZINCOMING POWER
PER ORDER
SE
E T
RA
NS
FO
RM
ER
FO
R P
RO
PE
R W
IRIN
GC
ON
NE
CT
ION
LA
BE
L
1X2
LD06
806
DWG. NO. 202440
FORM 100.10-EG2
YORK INTERNATIONAL 117
3PH
MO
TOR
T1 T2 T3
OL1
M1
M2
DES
CR
IPTI
ON
PLC
CM
1
FW
5
P24
FAC
TOR
YJU
MPE
R B
AR
TER
MIN
AL #
THE
MO
TOR
TO
RU
N.
4 23 1
CH
OKE
DC
LIN
K
P
(OPT
ION
AL)
CO
MM
ON
FO
R IN
PUT
INTE
RN
AL IN
TER
FAC
E C
OM
MO
N.
INTE
RN
AL 2
4V P
OW
ER S
UPP
LY.
THE
DR
IVE
TO S
TAR
T. (C
M1
TO 3
MU
ST B
E C
LOSE
D)
SELE
CTS
0-1
0VD
C S
PEED
SIG
NAL
.
THE
DR
IVEA
FTER
A T
RIP
OR
ALA
RM
.
SET
PAR
AMET
ER T
O 6
0HZ
OR
DES
IRED
PU
RG
E SP
EED
.
THE
MO
TOR
TO
REV
ERSE
RU
N.
NO
TE:
MO
DE
WIT
H R
UN
CO
NTA
CT.
2 - R
EMO
VE J
UM
PER
TO
CO
NTR
OL
BYPA
SS
AND
TER
MIN
AL 4
.D
RY
CO
NTA
CT
CLO
SUR
E BE
TWEE
N T
ERM
INAL
CM
1SE
T PA
RAM
ETER
FO
R 6
0 H
Z.1
- SM
OKE
PU
RG
E
FIELD WIRED CUSTOMER SUPPLIED
A C
ON
TAC
T C
LOSU
RE
BETW
EEN
CM
1 AN
D F
W C
AUSE
S
A C
ON
TAC
T C
LOSU
RE
BETW
EEN
CM
1 AN
D 5
WIL
L C
AUSE
A JU
MPE
R F
RO
M C
M1
TO 2
SEL
ECTS
4-2
0mA
ANAL
OG
C
UR
REN
T SP
EED
SIG
NAL
NO
JU
MPE
R F
RO
M C
M1
TO 2
(NO
JU
MPE
R R
EQU
IRED
WH
EN U
SIN
G T
HE
EZ P
AD)
NO
TE: F
OR
SM
OKE
PU
RG
E A
CO
NTA
CT
CLO
SUR
E BE
TWEE
N
CM
1 AN
D 4
WIL
L C
AUSE
DR
IVE
TO R
UN
AT
PUR
GE
SPEE
D.
A C
ON
TAC
T C
LOSU
RE
BETW
EEN
CM
1 AN
D 3
WIL
L EN
ABLE
A C
ON
TAC
T C
LOSU
RE
BETW
EEN
CM
1 AN
D 1
WIL
L R
ESET
G
M3
R(L
1)
T(L3
)
S(L2
)
FU11
X2T12L
2
SPAC
E H
EATE
R(O
PTIO
NAL
)
A2 B2
CO
NN
ECTI
ON
SFO
R P
RO
PER
SEE
TRAN
SFO
RM
ERFU
11(O
PTIO
NAL
)C2
X1FU
12
2L1
CO
NN
ECTI
ON
DIA
GR
AMS
L1 L2LO
ADL1
(2L1
)
(2L2
)
RFI
FIL
TER
LIN
EL2
1L1
1L2
L3(2
L3)
L3 (OPT
ION
AL)
1
1L3
A1 B1 C1
5% R
EAC
TOR
HEA
TER
RO
12M
2(P
24) +
24V
SUPP
LY
(PLC
) VD
C C
OM
MO
N
(4) M
ULT
ISPE
ED(5
) REV
RU
N
(FW
) RU
N\F
OR
WAR
D
(CM
1) C
OM
MO
N
(3) R
OK
(RU
N P
ERM
ISSI
VE)
(1) R
ESET
(SM
OKE
PU
RG
E)
(+) 4
-20m
A SI
GN
AL IN
PUT
(OI)
SPEE
D R
EFER
ENC
E (O
)
(+) R
EFER
ENC
E SU
PPLY
(H)
(2) A
T SE
LEC
T
10 11R
R
OL1
4BY
PASS
VFD
OU
TPU
T
VFD
INPU
T
10
RU
N
X2
2L2
(H4)
(H2)
460V
X2(X
2)12
0V
REL
AY(S
EE N
OTE
1)
FREQ
.
(AL2
)
IND
ICAT
ION
IND
ICAT
ION
RU
N
ARR
IVAL
(11A
)
(11C
)
(12A
)
(12C
)
(+) 4
-20m
A SI
GN
AL O
UTP
UT
(AM
1)
(+) 0
-10V
DC
OU
TPU
T (A
M)
CO
NTR
OL
CO
MM
ON
(L)
(AL1
)
(ALO
)IN
DIC
ATIO
NAL
ARM
FAU
LT R
ELAY
AL2
AL1
AL0
2.5
A R
ES.
ALAR
MIN
DIC
ATIO
N
M1
LT1
M2
3R
R
5
M3
6
3AO
OX
BYPA
SS
XOO
OFF
1AVF
D
SS1
ON OX
TEST
M2
SS2
OFF
(SEE
NO
TE 2
)
RR (H1)
2L1
(H4)
2L2
(X1)
X1(X
2)X2
230V
(H1)
(H3)
7
2L1
120V
(X1)
X1
(H2)
FIR
ESTA
T
FREE
ZEST
AT (H2)
1
2L1
(H1)
CLO
CK
208V
X2(X
3)X1
(X1)
120V
RU
N/T
IME
2L2
+ -LO
IOH
100
OH
MIM
PED
ANC
E
H OI LO
-+
10K
OH
MIM
PED
ANC
E4-20
mA
OU
TPU
T SI
GN
AL
LAM1
+ -AM L
+ -2m
A4-
20m
A25
0 O
HM
PRO
GR
AMM
ED F
OR
FREQ
UEN
CY
SPEE
D P
OT
H OI LO
OU
TPU
T C
ON
TAC
T
11C
11A
12C
12A
2.5
A R
ES.
RU
N
FREQ
.AR
RIV
ALIN
DIC
ATIO
N
IND
ICAT
ION
CO
NTA
CT
RAT
ING
250
VAC
0-10
VDC
0-10
VDC
500
TO
2K
EXTE
RN
AL S
PEED
REF
EREN
CE
N.O
.N
.C.
CO
M
CO
NTA
CT
RAT
ING
250
VAC
X (H3)
SAFE
TIES
TOBY
PASS
ON
R
LIN
K IS
CO
NN
ECTE
DJU
MPE
R W
HEN
DC
* REM
OVE
INTE
RN
AL
PD
W(T
3)
V(T2
)
U(T
1)
#202
440
FRO
M
DR
AWIN
G
- REM
OTE
DEV
ICE
(BY
OTH
ERS)
CURBPAK AIRMOD WIRING
LD06
807
DWG. NO. 202442
118 YORK INTERNATIONAL
Physical Data
TYPICAL ELECTRIC HEATER WIRING DIAGRAM
LD02466
CAUTION: EXTERNAL MULTISTEP THERMOSTAT OR STEP CONTROLLERS MUST BE WIRED SOTHAT THE HEATER STAGES ARE TURNED ON SEQUENTIALLY STARTING WITH STAGES 1, 2, 3 . . .AND TURNED OFF SEQUENTIALLY IN THE REVERSE ORDER; i.e. . . . 3, 2, 1.
NOTES: 1. FOR SUPPLY CONNECTIONS, USE MIN AW.G. COPPER CONDUCTORSSUITABLE FOR AT LEAST 78°C (167°F).
2. SUPPLY VOLTAGE , PHASE , CONTROL VOLTAGE .3. FIELD TERMINALS SUITABLE FOR USE WITH AW.G. COPPER
CONDUCTORS ONLY.4. THIS HEATER REQUIRES 1 SUPPLY CIRCUIT OF kW.5. CONTROL CIRCUIT WIRING TO BE N.E.C. CLASS 1.
POWER: (FACTORY WIRED)POWER: (FIELD WIRED)CONTROL (FACTORY WIRED)CONTROL (FIELD WIRED)
FORM 100.10-EG2
YORK INTERNATIONAL 119
This Page Intentionally Left Blank.
120 YORK INTERNATIONAL
Physical Data
SLOPED CURB
ROOFTOP ROOFTOP
LENGTH-WISE SLOPE
SUPPLY > RETURN RETURN > SUPPLY
OUTSIDEAIR
OUTSIDEAIR
SUPPLY AIR
SUPPLY AIR
RETURNAIR
RETURNAIR*14"
LD04189
WIDTH-WISE SLOPE
RIGHT > LEFT LEFT > RIGHT
ROOFTOP ROOFTOP
RETURNAIR IN
PIP
EC
HA
SE
RETURNAIR IN
PIP
EC
HA
SE
LD04190
* Curb Height selected is always the shortest dimension.
SUGGESTED INSTALLATION METHODS SECTIONAL VIEWS
CURB INSTALLATION
FORM 100.10-EG2
YORK INTERNATIONAL 121
LD06470
ROOF CURB [TYPICAL DESIGN]
NOTES: 1. Curb, Nailer and Gasket only, furnished by YORK.All other parts furnished “By Others”.
2. Roof Curb shipped in pieces for field assembly.3. Roof Curb must be installed square and level.4. Curb material is 14-gauge galvanized steel, unpainted
for 14", 18", 22"; 12-gauge for 26" & 30" curbs.5. Curbs must be fully supported by the roof structure.
A = TOTAL UNIT LENGTH FROM YORKWORKS MINUS 9”B = TOTAL SEGMENT LENGTH AFTER COIL MINUS 1"C = COIL SEGMENT LENGTH MINUS 3"D = (SEE CHART BELOW)
CURB CALCULATION FOR INSIDE DIMENSIONS
CURB WEIGHT = 8# / FOOT OF CURB PERIMETER(FOR 14" H CURBS)
D = INSIDE CURB (WIDTH)
UNIT INSIDEWIDTH
65,125 29.75"85, 170 41.75"105, 215 53.75"
250, 350, 460 65.75"305, 400, 530 77.75"
680 101.75"860 113.75"1030 137.75"
122 YORK INTERNATIONAL
Physical Data
2.60
0.75
1.95
2.10
2.002.00
1.75
5.75
WALL PANEL
UNIT SIDEBASE RAIL
GASKET
LIFTING1.00
5.80
3.00
FLEX MATERIAL
FAN COLLARLUG
CURB
2" SIDE
FLOOR
UNIT
From YORKworks Submittal DrawingUNIT WIDTH
1.872.50
2.13
FANDOWN DISCHARGE
(Not the Curb Drawing)
INSIDE DIMENSIONS
UNITS65-12585-170
105-215250-350-460305-400-530
6808601030
29.7541.75
77.7565.7553.75
137.75113.75101.75
WIDTH
VERTICALFRAME
FLOOR
1.20
0.752.00
2.00
5.75
PANEL
UNIT END
GASKET
1.00
Inside Curb Length Dimension Equals
3.00
FLEX MATERIAL
FAN COLLAR
BASE RAIL
CURB
2" WALL
UNIT1.87
FLOOR
COIL FILTERS
FAN
INLET OPENING
FIELD HOOK-UP
AIRFLOW
DUCT WORK
YORKworks Submittal Drawing Length Minus 9"
(DO NOT Use the YORKworks Curb Drawing)
UNIT LENGTHFrom the YORKworks Submittal Drawing
CURB DETAIL
LD06809
LD06810
FORM 100.10-EG2
YORK INTERNATIONAL 123
BASE RAIL DETAIL
LD06590
LD06472
AIR FLOW
BASE RAILSIDE (TYP)
BASE RAILEND (TYP)
124 YORK INTERNATIONAL
Physical Data
HEADER COVER ASSEMBLY
(EVERY COIL SEGMENTSUPPLIED AS STANDARD)
PIPE CHASEBASE ASSEMBLY
PIPE CHASEPANEL ASSEMBLY
PIPE CHASEACCESS DOOR
(CP65-400)
PIPE CHASEACCESS DOOR(CP460-1030)
UNIT BASE
HEADER COVERASSEMBLY
PIPE CHASE CURB WITH WOODEN NAILER
28.75" (25")40.75" (37")52.75" (49")
3" 3"
14" 12-5/16"
UNIT CURBWOODEN NAILER
WITH
PIPE CHASE TOP PANEL
ACCESS DOOR
PIPE CHASEBASE RAIL
PIPE CHASE DETAIL
PIPE CHASE CURB DIMENSIONS
LD06842
LD06843
NOTE:Remove screws from top and front panel fromheader cover assembly. Do Not remove panels.Place top panel from pipe chase assembly overthe header cover top panel. Line up the holes andreplace the screws. Line the two side panel holesup with the front panel of header. Replace screws.
FORM 100.10-EG2
YORK INTERNATIONAL 125
PIPE CHASE PANEL ASSEMBLY PIPE CHASE BASE ASSEMBLY
PIPE CHASE CURB ASSEMBLY
RH SIDE
PIPECHASE
PIPE CHASETOP PANEL
LH SIDE
ASSEMBLEDVIEW
EXPLODEDVIEW
BASE RAILFRONT PIPE CHASE
RH SIDE PIPE CHASEBASE RAIL
BASE RAILLH SIDE PIPE CHASE
FLOOR PANELPIPE CHASE
CLOSED CELL INSULATION
UNIT CURB
UNIT
ROOFOPENING12-5/16"
2x4 NAILER
PIPE CHASE
OPENINGROOF
2x4 NAILER
SIDE CURB
SIDE CURBPIPE CHASE
PIPE CHASE
14"
END CURB
BASE RAIL
LD06844 LD06845
LD06846
126 YORK INTERNATIONAL
NOTES:- Installing contractor is responsible for baserail / dunnage steel interface.- Unit baserail should not be penatrated.- Unit must be supported with dunnage steel around the entire perimeter of the unit base.
DUNNAGE STEEL DETAILS
Physical Data
2.50
(TYP)
Air
Flow
CL
2.501.25
Detail "A"
Detail "B"
LH Unit SideBase Rail
RH Unit SideBase Rail
2" Double WallFloor
A
Base RailUnit End
Unit Side
Unit EndDunnage Steel
Dunnage Steel
Unit Dimensions
A BSize
65, 12585, 170
105, 215250, 350,
305, 400,
680860
1030
530
460
84.50
108.50120.50144.50
72.50
60.5048.5036.50
ReferenceFormulas
Unit Length
below
B
DETAIL B (Length of Unit)
B
1.20
2.00
DUNNAGESTEEL
UNIT ENDBASE RAIL
DETAIL A (Width of Unit)
A
2.502.60
UNIT SIDEBASE RAIL
DUNNAGESTEEL
From: Engineering Guide• Add all your segment lengths together• Add 1.20" from that figure (0.6" each side)
i.e.: CP65 with the following segments: Add - FS 45"
SC 21" FF 9" MB 30"
105" + 1.20" = 106.2" toDunnage Steel
CL CL
CL
OR
From: YorkWorks Program• Take the YorkWorks drawing length• Subtract 2.8" from this dimension (1.4" each side)
i.e.: CP65 would be: YW Length = 109" 109" - 2.8" = 106.2" to
Dunnage SteelCL
LD06847
CALCULATING DUNNAGE FOR THE LENGTH OF UNIT – (DETAIL B ABOVE)
FORM 100.10-EG2
YORK INTERNATIONAL 127
Guide SpecificationsPART 1: GENERAL
1.01 SECTION INCLUDES
A. Outdoor air handling units and components as shown,scheduled and indicated on the Drawings, including butnot limited to:
1. Completely factory packaged air handling unit
2. Roof Curb
3. Chilled water [Refrigerant] connections
4. Steam [Hot Water] [Natural Gas] connections
5. Electrical power connections
1.02 RELATED DOCUMENTS
A. The requirements of the General Conditions, Supple-mentary Conditions, Division 1, and Drawings apply toall Work herein.
B. Requirements of the following Division 15 Sections ap-ply to this section:
1. Other sections defined by design engineer.
1.03 SYSTEM DESCRIPTION
A. Air handling unit manufacturer’s standard materials andcomponents as indicated by published product informa-tion, designed and constructed as recommended by themanufacturer and as required for a complete air han-dling unit installation as specified herein. The air han-dling unit shall be specifically designed for curb mount-ing in an outdoor application. Weatherized indoor airhandling units are not acceptable.
B. Air handling unit shall meet or exceed the scheduledcooling and heating capacity, selected and rated in ac-cordance with ARI 410. All necessary components formeeting scheduled performance shall be factory as-sembled per ARI 430 and shipped as one (1) piecewhere possible.
C. Air Handling Units shall be provided with all necessarytags and decals to aid in the service and/or indicatecaution areas. Electrical wiring diagrams shall be at-tached to the control panel access door. Lifting lugs willbe supplied to facilitate rigging of the air handling unit.
1.04 QUALITY ASSURANCE
A. Manufacturers: The design shown on the drawing isbased upon products of the manufacturer scheduled.Alternate equipment manufacturers will be acceptableif equipment meets the scheduled performance andcomplies with these specifications. If equipment manu-factured by manufacturer other than that scheduled is
utilized, then the Mechanical Contractor shall be re-sponsible for coordinating with the General Contrac-tor and all affected Subcontractors to ensure properprovisions for installation of the furnished unit. Thiscoordination shall include, but not limited to, the fol-lowing:
1. Structural supports for units.
2. Piping size and connection/header locations.
3. Electrical power requirements and wire/conduit andovercurrent protection sizes.
4. The Mechanical Contractor shall be responsible forall costs incurred by the General Contractor, Sub-contractors, and Consultants to modify the buildingprovisions to accept the furnished units.
1.05 REFERENCES
A. AMCA 99 – Standard Handbook
B. AMCA 210 – Laboratory Methods of Testing Fans forRating Purposes
C. AMCA 300 – Test Code for Sound Rating Air MovingDevices
D. AMCA 301 – Method of Publishing Sound Ratings forAir Moving Devices
E. AMCA 500 – Test Methods for Louver, Dampers, andShutters
F. ANSI/AFBMA 9 – Load Ratings and Fatigue Life forBall Bearings
G. ANSI/UL 900 – Test Performance of Air Filter Units
H. ARI 410 – Forced-Circulation Air Cooling and Air Heat-ing Coils
I. ARI 430 – Standard for Application of Central-StationAir Handling Units
J. NFPA 90A – Installation of Air Conditioning and Venti-lation Systems
K. SMACNA – Low Pressure Duct Construction Standards
1.06 SUBMITTALS
A. Shop drawing submittals shall include, but not limitedto, the following:
1. Drawings indicating components, dimensions,weights, required clearances, and location and sizeof field connections.
B. Product data shall include dimensions, weights, capaci-ties, ratings, fan performance, motor electrical charac-
128 YORK INTERNATIONAL
Guide Specificationsteristics, and gauges and finishes of materials.
1. Fan curves with specified operating point clearlyplotted shall be provided.
2. Product data of filter media, filter performance data,filter assembly, and filter frames shall be provided.
3. Electrical requirements for power supply wiring, in-cluding wiring diagrams for interlock and control wir-ing shall be supplied.a. Factory-installed and field installed wiring shall be
clearly indicated.
4. Manufacturer’s standard published installation in-structions shall be provided.
C. Manufacturer’s standard operating and maintenanceinstructions shall be supplied in accordance with Sec-tion 01830 – Operation and Maintenance, including butnot limited to instructions for lubrication, filter replace-ment, motor and drive replacement, spare parts lists,and wiring diagrams.
1.07 RATINGS AND CERTIFICATIONS
A. Conform to AMCA 210 for fan performance ratings.
B. Conform to E.T.L. standards.
C. Conform to ARI 410 for capacities, pressure drops,and selection procedures of air coils.
D. Conform to ARI 430 for all fabrication procedures of airhandling units.
E. Utilize only ANSI/UL 900 listed Class I or Class II filtermedia, approved by local authorities.
F. Utilize only ISO9000 certified facilities in the manufac-turing of the air handling unit.
1.08 DELIVERY, STORAGE AND HANDLING
A. All handling and storage procedures shall be permanufacturer’s recommendations.
1.09 WARRANTY
A. The manufacturer’s standard warranty shall be for aperiod of one year from the date of start-up or eighteenmonths from the date of shipment, whichever occursfirst.
1. The warranty shall include parts only during thisperiod.
2. The warranty shall not include parts associated withroutine maintenance, such as belts, air filters, etc.
1.10 MAINTENANCE
A. ____ additional sets of specified filters shall be pro-vided with each air handling unit.
B. ____ additional drive belts shall be provided with eachair handling unit.
C. Air handling unit manufacturer shall have a local, directservice office for the supply of replacement parts.
D. Manufacturer’s direct, local service office shall providea single point of contact for any service and mainte-nance agreement purchased.
E. Independent HVAC service organizations shall not beacceptable.
PART 2: PRODUCTS
2.01 MANUFACTURERS
A. Acceptable manufacturer shall be York InternationalCorp. or approved equal.
2.02 UNIT CASING
A. Air handling unit shall be supplied with a full length,continuous base rail channel.
1. The base rail channel shall be formed of 12-gaugeminimum galvanized steel.
2. The base rail channel shall support all major compo-nents.
3. The unit base shall be supplied with a recessed curbmounting location.a. The recessed curb-mounting surface shall provide
a continuous surface for field application of curbgasketing to create a weather-tight seal betweenthe curb and unit.
b. Units without a recessed mounting location for theroof curb shall not be acceptable.
B. Air handling unit shall be supplied with a frame con-struction consisting of integral galvanized steel verticaland horizontal structural members.
1. The frame shall be constructed to permit completeremoval of the wall and roof panels without affectingthe structural integrity of the unit.
C. Air handling unit shall be supplied with double wall pan-els for walls, roof, and floor constructed of G90 mill gal-vanized sheet steel.
1. All panels shall be formed and reinforced to providea rigid assembly.
FORM 100.10-EG2
YORK INTERNATIONAL 129
2. The exterior casing shall be constructed of 18-gaugeminimum galvanized steel.a. Exterior casing screws shall be zinc chromate
coated.
3. The interior lining of the walls and roof panels shallbe a solid [perforated wall] lining of 20-gauge mini-mum galvanized steel.
4. The interior lining of the floor panels shall be a solidlining of 18-gauge minimum galvanized steel.
5. All wall, roof, and floor panels in the air handler shallbe supplied with 2" (two inches) of insulation.a. Insulation shall be a full 2" (non-compressed)
throughout the entire unit.b. Insulation shall be of 1.5 [3] pound per cubic foot
in density with a thermal conductivity R of 8.33BTU/hr-ft2-°F.
c. Units with less than 2" of insulation in any part ofthe walls, floor, or roof shall not be acceptable.
d. Insulation shall meet the flame and smoke gen-eration requirements of NFPA 90A.
e. Units with polyurethane and polystyrene foam in-sulations are not acceptable.
f. All pipe chase, header covers and return bendpanels are 1" thick with 1" insulation.
6. All wall and roof panels shall be completely remov-able for unit access and removal of components.a. Panel removal shall not affect the structural unit
frame.
7. All panels shall be completely gasketed with a co-polymer rubber sealant ribbon.
8. All panel fasteners shall be secured through stand-ing seams to prevent fastener penetrations that areexposed to the airstream.
9. Roof and sidewall seams shall be continuouslycaulked and covered with formed 20 gauge galva-nized seam caps.
D. Air handling unit shall be supplied with a sloped roof topromote drainage of precipitation and prevent standingwater.
1. The roof shall have a minimum pitch of 1/4" perfoot.
2. The roof shall overhang the side panels by a mini-mum of 3 inches to prevent precipitation drainagefrom streaming down the unit side panels.
3. Units supplied with flat roofs shall not be acceptable.
2.03 FANS AND MOTORS
A. Air handling unit shall be supplied with a segment con-taining a fan and fan motor.
1. The fan segment shall be supplied with internallymounted double width, double inlet (DWDI) centrifu-gal type wheels.a. DWDI fan and unit performance shall be rated and
certified in accordance with ARI Standard 430.b. DWDI fan shall be a forward curved type.
—OR—b. DWDI fan shall be an airfoil type.
1. Airfoil fans shall bear the AMCA Seal.
2. Airfoil fan performance shall be based on testsmade in accordance with AMCA standards 210and comply with the requirements of the AMCAcertified ratings program for air and sound.
3. Airfoil wheels shall comply with AMCA stan-dard 99-2408-69 and 99-2401-82.
c. Fan bearings shall be self-aligning, pillow blockor flanged type regreasable ball bearings.
1. Bearings shall be designed for an average life(L50) of at least 200,000 hours for a forwardcurved fan and 200,000 for an airfoil fan.
2. All bearings shall be factory lubricated andequipped with standard hydraulic grease fittingsand lube lines extended to the motor side ofthe fan. Class I fans have sealed bearings.
d. Fan shall be provided with a belt drive using anti-static belts and selected for 1.2 [1.5] service factorfrom brake horse power.
e. Fan discharge shall be connected to the fan cabi-net using a flexible connection to ensure vibra-tion free operation.
f. The fan shall be supplied with variable inlet vanesfor variable air volume control.1. Variable inlet vanes for forward curved wheels
shall be attached to the scroll of the fan.2. Variable inlet vanes for forward curved wheels
shall have a support ring of rolled angle iron.3. Variable inlet vanes for forward curved wheels
shall have blades constructed of heavy gaugegalvanized steel.
4. Variable inlet vanes for forward curved wheelsshall have actuator rods and rings plated forcorrosion resistance.
5. Variable inlet vanes shall operate from a singleshaft and be synchronized for precise control.
130 YORK INTERNATIONAL
Guide Specifications
1. Variable inlet vanes for airfoil wheels shall bean integral part of the inlet cone.
2. Variable inlet vanes for airfoil wheels shall beconstructed of heavy gauge corrosion resistantblades with zinc-plated steel interlocking andoperating mechanism.
3. Variable inlet vanes shall operate from a singleshaft and be synchronized for precise control.
g. The fan shall be supplied with a variable frequencydrive (VFD) for variable air volume control.
—OR—1. The variable frequency drive shall be Factory-
mounted in a dedicated conditioned NEMA3R control panel.
2. The VFD shall bear the same label as the unitmanufacturer to assure compatibility and properfan balancing.
3. The VFD shall operate at a carrier frequencyin the range of .5 - 16 kHz to ensure quietoperation.
4. The VFD shall be U.L. listed and comply withall applicable provisions of the National Elec-tric Code.
2. DWDI fan segment shall be provided with an ac-cess door on the coil header side of the unit for fan/motor access.
3. DWDI fans shall be supplied with rear [rear in-verted] [top] [top inverted] [bottom] [bottom in-verted] discharge.
—OR—
1. The fan segment shall be supplied with internallymounted single width, single inlet (SWSI) centrifu-gal type wheels.a. SWSI fan shall be an airfoil or BI type.
1. Airfoil fans shall bear the AMCA Seal.2. Airfoil fan performance shall be based on tests
made in accordance with AMCA standards 210and comply with the requirements of the AMCAcertified ratings program for air and sound.
3. Airfoil wheels shall comply with AMCA stan-dard 99-2408-69 and 99-2401-82.
b. Fan bearings shall be self-aligning, pillow blockor flanged type regreasable ball bearings.1. Bearings shall be designed for an average life
(L50) of at least 200,000 hours.2. All bearings shall be factory lubricated and
equipped with standard hydraulic grease fittingsand lube lines extended to the motor side ofthe fan.
c. Fan shall be provided with a belt drive using anti-static belts and selected for 1.2 [1.5] service factorfrom brake HP.
d. Fan inlet shall be connected to the fan cabinetusing a flexible connection to ensure vibrationfree operation.
e. The fan shall be supplied with variable inlet vanesfor variable air volume control.1. Variable inlet vanes for airfoil wheels shall be
an integral part of the inlet cone.2. Variable inlet vanes for airfoil wheels shall be
constructed of heavy gauge corrosion resistantblades with zinc-plated steel interlocking andoperating mechanism.
3. Variable inlet vanes shall operate from a singleshaft and be synchronized for precise control.
f. The fan shall be supplied with a variable frequencydrive (VFD) for variable air volume control.1. The variable frequency drive shall be Factory-
mounted in a dedicated conditioned controlcompartment inside the air handling unit.
2. The VFD shall bear the same label as the unitmanufacturer to assure compatibility and properfan balancing.
3. The VFD shall operate at a carrier frequencyin the range of .5 - 16 kHz to ensure quietoperation.
4. The VFD shall be U.L. listed and comply withall applicable provisions of the National Elec-tric Code.
2. The SWSI fan segment shall be provided with an in-swinging door on the coil header side of the unit forfan/motor access on most unit sizes.
3. The SWSI fan shall be available with multiple top,bottom, and horizontal discharge locations.
4. The fan segment shall be supplied with an internallymounted fan motor.a. Fan motors shall be NEMA design ball-bearing
type with electrical characteristics and horsepoweras specified.
b. Motors shall be 1750 RPM, open drip-proof [to-tally enclosed, fan cooled] type.
c. Fan motor shall satisfy the Federally mandatedEnergy Policy Act (EPACT).
d. The fan motor shall be located within the unit onan adjustable base.
5. The fan and fan motor shall be isolated on a full widthisolator support channel using rubber-in-shear [2"springs] [2" springs with seismic restraints].
FORM 100.10-EG2
YORK INTERNATIONAL 131
2.04 HEATING/COOLING COMPONENTS
A. Air handling unit shall be supplied with a segment(s)designed and selected to cool the airstream as indi-cated on the schedule.
1. The cooling coil segment shall accommodate cool-ing coils and/or heating coils.a. Coil performance shall be certified in accordance
with ARI Standard 410.b. Coil casings shall be constructed of 16-gauge
galvanized steel [stainless steel] with aluminum[copper] die-formed corrugated fins with drawncollars, and be belled and mechanically expandedto firmly bond the copper tubes to the fins.
c. Coils shall be circuited for counterflow of air andwater [refrigerant].1. Water velocities shall not exceed 7 feet per sec-
ond and/or exceed the water pressure dropsscheduled.
d. All coils shall be removable from the unit by un-bolting the wall panels and coil.1. Units with welded or spot welded panels re-
quire bolted coil pull panels for coil.
2. The cooling segment shall be supplied with a cool-ing coil for use with chilled water.a. Cooling coils shall be drainable water coils with a
design working pressure of 250 PSIG at tem-peratures up to 300°F.
b. Cooling coils shall be tested with 325 PSIG com-pressed air under water.
c. Cooling coil circuiting shall provide free and com-plete draining and venting when installed in theunit.1. All vent and drain connections shall be ex-
tended to the outside of the unit casing.
—OR—
2. The cooling segment shall be supplied with a cool-ing coil for direct expansion of refrigerant in lieu of oras well as the chilled water coil.a. Direct expansion cooling coil shall be designed
and conform to ANSI B9.1 Safety Code for Me-chanical Refrigeration.
3. The cooling segment shall be supplied with a fullwidth, sloped drain pan that extends downstream ofthe coil to provide sufficient amount of space to con-tain possible moisture carryover.a. The drain pan shall be of double wall construc-
tion with a G90 galvanized [stainless steel] liner.b. The drain pan shall have a minimum of 2" insulation.
c. Intermediate drain pans shall be provided for anycooling segment with a coil height of more than48" with drop tubes to guide the condensate tothe main drain pan.
d. Cooling segments having overall coil height ofgreater than 48" shall not be acceptable withoutan intermediate drain pan.
e. Drain pan shall be provided with a minimum 1-1/4"FPT condensate connection positioned beneath thelowest point of the drain pan, opposite the coilheader.
B. Air handler shall be supplied with a segment(s) designedand selected to heat the airstream as scheduled on thedrawings.
1. Each heating segment shall accommodate up to afour-row drainable water coil, a one-row steam-dis-tributing coil, an indirect fired gas furnace, or an elec-tric heater.a. Hot water or steam coils may be supplied in cool-
ing coil segment if space permits.b. Coil performance shall be certified in accordance
with ARI Standard 410.c. Coil casings shall be constructed of 16 gauge gal-
vanized steel [stainless steel] with aluminum[copper] die-formed corrugated fins with drawncollars, and be belled and mechanically expandedto firmly bond the copper tubes to the fins.
d. Coils shall be circuited for counterflow of air andwater.1. Water velocities shall not exceed 7 feet per
second and/or exceed the water pressuredrops scheduled.
e. All coils shall be removable from the unit by un-bolting the wall panels and coil.1. Units with welded or spot welded panels re-
quire bolted coil pull panels for coil removal.
2. The heating segment shall be supplied with a heat-ing coil for use with hot water.a. The heating coil shall be drainable water coil with
a design working pressure of 250 PSIG at up to300°F.
b. The heating coil shall be tested with 325 PSIGcompressed air under water.
c. Heating coil circuiting shall provide free and com-plete draining and venting when installed in theunit.1. All vent and drain connections shall be ex-
tended to the outside of the unit casing.
—OR—
132 YORK INTERNATIONAL
Guide Specifications2. The heating segment shall be supplied with a heat-
ing coil for use with 50 PSIG – saturated steam.a. Steam distributing coil shall have an outside di-
ameter (OD) of 1" (one and one eighth inch).b. Steam distributing coil shall have an inner distrib-
uting tube with 5/8" OD.c. Steam coil shall discharge steam in the direction
of condensate flow to facilitate even distributionand heat transfer through the full length of eachtube.
2.05 FILTERS
A. Air handling unit shall be supplied with a filter segmentas an integral part of the unit
1. The filter frames shall be built of galvanized steel.
2. The filter section shall be side service [front load-ing] with a standard access door on the coil headerside of the unit.
—OR—
2. The HEPA filter section shall be front loading with astandard access door on the coil header side of theunit.
3. The air handling unit shall be supplied with a flat fil-ter segment accommodating 2 [4] inch media.a. The 2 inch media shall be throwaway [permanent]
[cleanable] [30% pleated] type.—OR—
a. The 4 inch media shall be 30% efficient pleatedmedia [rigid type high efficiency media with aminimum efficiency of 65% [85%] [95%] as de-termined by ASHRAE Standard 52-76].
—OR—
3. The air handling unit shall be supplied with an anglefilter segment accommodating 2-inch media.a. The 2 inch filter media shall be throwaway [per-
manent] [cleanable] [30% pleated].
—OR—
3. The air handling unit shall be supplied with a highefficiency rigid filter segment accommodating 2 inchprefilters and high efficiency rigid type filters of thespecified efficiency.a. Prefilter media shall be throwaway [permanent]
[cleanable] [30% pleated].b. Rigid filter media shall be 12 inches deep and the
efficiency shall be a minimum of 65% [85%] [95%]as determined by ASHRAE standard 52-76.
c. Filter media shall be listed Class II [Class I] inaccordance with U.L. Standard 900.
—OR—
3. The air handling unit shall be supplied with a highefficiency bag filter segment accommodating 2 inchprefilters and high efficiency bag type filters of thespecified efficiency.a. Prefilter media shall be throwaway [permanent]
[cleanable] [30% pleated].b. Bag filter media shall be 21 [32] inches deep
and the efficiency shall be a minimum of 65%[85%] [95%] as determined by ASHRAE stan-dard 52-76.
c. Filter media shall be listed Class II [Class I] inaccordance with U.L. Standard 900.
—OR—
3. The air handling unit shall be supplied with a car-bon filter segment accommodating 2-inch prefilterand 1-inch deep trays of carbon media.a. Prefilter media shall be throwaway [permanent]
[cleanable] [30% pleated].b. Carbon filter media shall be activated char-
coal [potassium permanganate] suitable forgas filtration.
—OR—
3. The air handling unit shall be supplied with an ab-solute HEPA filter segment accommodating abso-lute HEPA (High Efficiency Particulate Air) filters.a. HEPA filter media shall be 12 inches deep and
the efficiency shall be a minimum of 99.97% onthermally generated, .3 micrometer particles, asdetermined by ASHRAE standard 52-76.
b. HEPA filter media shall be listed Class I in accor-dance with U.L. Standard 900.
c. HEPA filter media shall be constructed of ultrafine fiberglass formed into high-density paper andpleated.
d. HEPA filter media shall be water-resistant andflame retardant.
e. The media pack shall be sealed to the cell withpolyurethane foam.
f. The filter media frame shall be constructed of ex-truded aluminum and be specifically designed forHEPA filters including all of the single and doublefilter clamps required for media installation.
g. The filter media shall be sealed to the media framewith neoprene expanded rubber gasket.
h. The pleats of filter media shall be separated bycorrugated aluminum.
i. The filter cell sides shall be made of galvanizedsteel.
j. HEPA filters shall be sealed against the holdingfilter frame with spring-loaded, nut and clip as-
FORM 100.10-EG2
YORK INTERNATIONAL 133
semblies to minimize air bypassing around thefilter.
4. Filter segment shall be supplied with a filter gaugeto measure the pressure drop across the filter bank.a. Filter gauge shall be a magnahelic, differential
pressure gauge factory installed and flushmounted on the coil side.
2.06 INLET/ECONOMIZER SEGMENTS
A. Air handling unit shall be supplied with an inlet seg-ment designed to form a plenum.
1. The inlet segment shall have outside and return air-streams, directed into each other by damper assem-blies to facilitate mixing of the airstreams.
2. The inlet segment shall consist of multi-leaf, parallelacting, Low-leak [Ultra Low-leak] blades.a. The dampers shall be located in the bottom and
front of the unit.b. Outside air damper shall be sized for 30% [100%]
of unit airflow and covered with a factory as-sembled rain hood with a drip-lip the full width ofthe hood to channel moisture away from the airbeing drawn into the unit.
—OR—
2. The inlet segment shall consist of multi-leaf, parallelacting, Low-leak [Ultra Low-leak] blades.a. The outside air damper shall be sized for 100% of
the unit airflow.b. The outside air damper shall be located at the rear
of the unit and covered with a factory assembledrain hood which has a drip-lip the full width of thehood to channel moisture away from the air beingdrawn into the unit.
—OR—
2. The inlet segment shall consist of multi-leaf, parallelacting, Low-leak [Ultra Low-leak] blades.a. The return air damper shall be sized for 100% of
the unit airflow.b. The return air damper shall be located in the bot-
tom of the unit.
3. The inlet air segment shall be supplied with a factoryinstalled steel safety screen over the return air open-ing in the floor of the unit.
—OR—A. Air handling unit shall be supplied with an economizer
segment instead of an inlet segment to provide a meansof exhausting air from the air handling unit.
1. The economizer segment shall consist of multi-leaf,parallel acting, Low-leak blades.
2. The return air, outside air, and exhaust air dampersshall be sized for 100% of unit airflow.
3. The return air opening shall be located in the bot-tom [rear] of the unit.a. Bottom return air openings shall include a fac-
tory installed safety screen.b. Economizer segments using SWSI vertical (ple-
num) fans shall have bottom return air openingonly.
4. A rainhood and bird screen assembly shall pro-tect the outside and exhaust air dampers from theelements.
5. Economizer segment shall be supplied without afan.a. The outside and exhaust control air dampers shall
be located on opposite sides of the unit to pre-vent mixing of fresh air and exhaust air.
—OR—
5. Economizer segment shall be supplied with a DWDIforward curved [Airfoil] Return air fan.a. The outside air and exhaust air dampers shall be
located on opposite sides of the unit to preventmixing of fresh air and exhaust air.
b. The return air fan shall be a DWDI forward curved[airfoil] fan.1. DWDI fan shall be a forward curved type.
—OR—
1. DWDI fan shall be an airfoil type.a. Airfoil fans shall bear the AMCA Seal.b. Airfoil fan performance shall be based on
tests made in accordance with AMCA stan-dards 210 and comply with the requirementsof the AMCA certified ratings program forair and sound.
c. Airfoil wheels shall comply with AMCA stan-dard 99-2408-69 and 99-2401-82.
2. Fan bearings shall be self-aligning, pillow blockor flanged type regreasable ball bearings.a. Bearings shall be designed for an average
life (L50) of at least 200,000 hours for a for-ward curved fan and 200,000 for an airfoilfan.
b. All greasable bearings shall be factory lu-bricated and equipped with standard hydrau-lic grease fittings and lube lines extendedto the motor side of the fan, with the ex-ception of Class I fans, which are sealed.
3. Fan shall be provided with a belt drive usingantistatic belts and selected for 1.2 [1.5] ser-vice factor from brake HP.
134 YORK INTERNATIONAL
Guide Specifications
4. Fan discharge shall be connected to the fancabinet using a flexible connection to ensurevibration free operation.
—OR—
5. The economizer segment shall be supplied with aSWSI vertical [horizontal] (plenum) fan for use asan exhaust or return air fan.a. The SWSI (plenum) fan shall be positioned such
that it operates as a return air fan.b. The SWSI fan shall have a vertical configuration.
1. The outside air dampers shall be located oneach side of the unit.
2. The exhaust air dampers shall be located onthe end of the unit.
—OR—
b. The SWSI fan shall have a horizontal configuration.1. The outside and exhaust air dampers shall be
located on opposite sides of the unit to preventmixing of fresh air and exhaust air.
2. SWSI fan shall be an airfoil/BI type.a. Airfoil/BI fans shall bear the AMCA Seal.b. Airfoil fan performance shall be based on
tests made in accordance with AMCA stan-dards 210 and comply with the requirementsof the AMCA certified ratings program forair and sound.
c. Airfoil wheels shall comply with AMCA stan-dard 99-2408-69 and 99-2401-82.
3. Fan bearings shall be self-aligning, pillow blockor flanged type regreasable ball bearings.a. Bearings shall be designed for an average
life (L50) of at least 200,000 hours.b. All greasable bearings shall be factory lu-
bricated and equipped with standard hydrau-lic grease fittings and lube lines extendedto the motor side of the fan.
4. Fan shall be provided with a belt drive usingantistatic belts and selected for 1.2 [1.5] ser-vice factor from brake HP.
—OR—
5. Economizer segment shall be supplied with a for-ward curved exhaust air fan.a. The outside air and exhaust air dampers shall be
located on opposite sides of the unit to preventmixing of fresh air and exhaust air.
b. A DWDI forward curved fan shall be used as theexhaust air fan.
c. The exhaust air dampers shall be barometric re-lief type dampers.
2.07 ACCESSORIES
A. Dampers in Inlet [Economizer] segments shall be Lowleak.
1. Dampers shall be of low leak design having stamped16 gauge galvanized steel blades.a. Damper blades shall be provided with extruded
vinyl edge seals and stainless steel jamb seals.b. Damper blades shall be parallel [opposed]
acting.
2. Leakage shall not exceed 3.7 cfm/ft2 @ 1" w.g.
—OR—A. Dampers in Inlet segment shall be Ultra Low leak.
1. Dampers shall be of ultra-low leak design havingairfoil blades.a. Damper blades shall be provided with extruded
vinyl edge seals and stainless steel jamb seals.b. Damper blades shall be parallel [opposed]
acting.
2. Leakage shall not exceed 3.0 cfm/ft2 @ 1" w.g.
B. Air handling unit shall be supplied with a diffuser seg-ment to assure even distribution of airflow across theentire unit air tunnel.
1. Diffuser segment shall be constructed with a perfo-rated diffuser plate.
2. Units with blow-through coils and final filters (down-stream of the fan) must have a diffuser segment im-mediately downstream of the fan.
3. Units with fans blowing directly into coils and/or fil-ters shall be unacceptable.
C. Air handling unit shall be supplied with an access seg-ment placed as indicated on the drawings.
1. The access segment shall have a depth of 24" [18"][30"].
2. The access segment shall be provided with a dooras standard on the coil header side of the unit.a. Doors open against internal pressure at all times.
When occasion warrants swinging with pressuredoor, safety chain and warning label is supplied.
D. Air handling unit shall be supplied with an air blendersegment to maximize the performance of the down-stream components.
1. The air blender segment shall be supplied factoryinstalled as an integral part of the air handling unit.
2. Air blenders shall be fixed devices, with no movingparts.
FORM 100.10-EG2
YORK INTERNATIONAL 135
E. Air handling unit shall be supplied with an internal faceand bypass segment to provide accurate temperaturecontrol while full flow is maintained through the heat-ing or cooling coil.
1. The internal face and bypass damper segment shallconsist of multi-leaf, opposed acting face blades andparallel acting bypass blades interlocked with onecontrol point.
2. The blades shall rotate in nylon bearings, providingsmooth action and requiring no lubrication.
3. Dampers shall be sectionalized to assure tight clo-sure by limiting blade length and resulting blade warp.
4. Reduced face coils shall be immediately downstreamof the section.
F. Air handling unit shall be supplied with a humidifiersegment.
1. The humidifier segment shall be sized to accom-modate the manifolds.
2. The humidifier shall be supplied with a full width,sloped drain pan that extends downstream of the coilto provide sufficient amount of space to contain pos-sible moisture carryover.a. The drain pan shall be of double walled construc-
tion with a G90 galvanized [stainless steel] liner.b. The drain pan shall have a minimum of 2" insulation.
3. Steam humidifiers shall be a steam separator typeproviding full separation ahead of a control valve thatdischarges through an internal drying chamber.a. Steam humidifiers shall be electrically [pneumati-
cally] controlled.
4. The humidifier capacity shall meet or exceed the ca-pacity specified on the schedule.
5. The size and number of distribution manifolds shallbe sized so all steam is absorbed by the air beforereaching the next component in the airstream.
G. Air handling unit shall be supplied with one or more at-tenuator segments of the size and type specified to meetthe sound level on the schedule.
1. The sound attenuators shall be 3 [5] [7] feet in length.
2. The outer shell of the attenuator shall be constructedof 22-gauge galvanized steel in accordance withASHRAE recommendations for a high-pressure rect-angular duct.
H. Air handling unit shall be supplied with a discharge ple-num segment provided with a bottom [top] [horizontal][side] discharge opening.
I. Air handling unit shall be supplied with a shipping splitsegment to allow for a unit split for shipping or instal-lation purposes.
J. Air handling unit shall be supplied with vapor-proof ser-vice lights in the segments indicated on the drawings.
1. Lights shall include a 100-watt, marine-type servicelight.
2. If two or more lights are provided in a unit, the lightsshall be wired to one (1) on/off toggle switch whichbrings all the lights on at once.a. Convenience outlets shall be rated at 15 amps
and mounted in a duplex outlet/switch, gang box.
K. Air handling unit shall be provided with an external pipechase to enclose field piping and valves.
1. Pipe chase shall be 25" [37"] [ 49"] in nominal depth.Internal clearance approximately 7" less than nomi-nal depth.
2. Pipe chase shall be of double wall construction.
L. Air handling unit shall be supplied with access doors inthe fan, filter, and inlet sections on the coil header side.
1. Doors shall be of double wall construction with asolid liner.
2. Doors shall have a minimum thickness of 2".
3. Doors shall be attached to the unit by a continu-ous, full-length piano-type stainless steel hinge.
4. Vent-Loc handles shall be positive-action, creatingan airtight seal between the door and the unit. Thesehandles are standard on unit sizes 65 - 400.
5. In lieu of the standard latch, doors for units 460 -1030 shall be available with a single-point, multi-latch system including handles on the interior andexterior of the door.a. Latch system shall include a 3 point deadbolt
latch with flat rods and tapered take-up side bolts,glass reinforced nylon plastic handles outsidehandle designed for 90° rotation, and zinc platedinside handle.
6. Door panels shall be completely gasketed with aclosed-cell neoprene gasket.
7. Specified access doors shall be supplied with 9" x9" wire reinforced double pane viewing windows.
M.Air handling unit shall be supplied with themanufacturer’s standard curb, shipped loose for fieldinstallation by others prior to unit placement.
1. Roof curb shall be a prefabricated galvanized steel-mounting curb.
136 YORK INTERNATIONAL
Guide Specifications
2. Roof curb shall be a perimeter type with a completeperimeter support of the air handling unit.
3. The curb shall be a minimum of 14 [18] [22] [26][30] inches high.
4. Gasketing shall be provided for field mounting be-tween the unit base and the roof curb.
5. The curb shall include a 2" x 4" wood nailer.
6. The roof curb shall be insulated with 2" thick 3 pcfinsulation.
7. The roof curb shall be sloped to accommodate in-stallation on a sloped surface.
2.08 FINISHES
A. Air handling unit shall be painted prior to shipment.
1. The exterior of the unit shall be completely cleanedprior to application of finished coats.
2. A prime coat of two component epoxy wash shall beapplied to the unit.
3. A finish coat of desert sand acrylic polyurethane shallbe applied to a minimum thickness of 2.5 mills.
4. The finished unit shall exceed 500-hour salt spraysolution (5%) without any sign of red rust when testedin accordance with ASTM B-117.
2.09 CONTROLS
A. Air handling unit shall be equipped with a single pointmotor starter panel serving fan motor(s).
1. The panel and all associated components shall beU.L. listed.
2. All wiring shall be done within NEC guidelines.
3. The single point motor starter panel shall be pro-tected by a NEMA 3R enclosure.
4. The panel shall contain a main power block, single-speed fan motor contactor(s) with overload device(s),three phase ambient compensated overload heaterelements, two primary control fuses, one secondarycontrol line size fuse, terminal strip and a door-mounted on/off auto switch.
5. Power wiring from the starter panel to the fan motorshall be factory installed.
6. A single panel enclosure containing supply and re-turn fan motor starters shall be provided with sepa-rate door-mounted on/off/auto switches when a re-turn air fan is specified.
7. The motor control panel shall be supplied with anindependent disconnect for the 115 V circuit and atransformer for the lights, receptacles, and control
devices to allow operation of 1-phase devices when3 phase power is disconnected.
8. Control voltage shall be 115 Volts.
B. Air handling unit shall be supplied with a unit mountednon-fused disconnect.
1. The disconnect shall be an integral part of the motorstarter panel [in a separate NEMA 3R enclosure].
C. Air handling unit shall be supplied with factory-pack-aged end devices furnished by the air handling unitmanufacturer.
1. End devices shall be factory-mounted, wired andtested by the air handling unit manufacturer.
2. The complete control system shall include the fol-lowing end devices, factory-mounted and wired,where applicable: damper actuators, temperaturesensors, differential pressure transmitters, differen-tial pressure switches, low limit thermostats, con-trol valves actuators, control valve junction box.
3. All control valves shall be shipped loose for fieldinstallation.a. Control valve leads shall be factory marked to
match terminal strip in the junction box.
D. Factory-packaged End Devices enclosure shall be locatedflush mounted on unit exterior and shall be NEMA 3R.
E. All control end devices, except control valves, spacetemperature sensor, and the outdoor air temperaturesensor (if no outdoor air damper), are to be factoryinstalled and wired in accordance with NEC codes.
1. All control wiring shall be Class II.
2. Wiring shall be contained in the integral unit-fram-ing members.
3. Control panel wiring and power supplies shall becomplete, except for 120VAC power wiring by elec-trical contractor and remote mounted devices asnoted below.
4. Wires crossing shipping splits shall terminate injunction boxes with numbered plug in connectorsfor easy field connection.
5. Kits shall be provided for field installation of staticpressure pickups for space static, outdoor air staticand remote duct static, if required for the controlapplication.a. Kits shall include probe and appropriate mount-
ing hardware.b. One-quarter inch fire rated PVC tubing or
equivalent shall be supplied by the (mechani-cal) contractor.
FORM 100.10-EG2
YORK INTERNATIONAL 137
6. Four wire space temperature sensors shall be pro-vided by the factory for field installation by (electri-cal) contractor and wired to the terminal strip incentral control panel.
7. Valve actuators shall be field wired by (electrical)contractor.
a. Two 24VAC power wires and two 0-10 VDC con-trol wires shall be run to each valve actuator fromthe terminal strip provided in the control panel.
2.10 SOURCE QUALITY CONTROL
A. All factory-installed fans shall be balanced.
1. The fan segment shall be run-balanced at the speci-fied speed to ensure smooth and trouble free op-eration after the fan is installed in the air handler.a. The run balance shall include filter-in balancing
in two (2) planes on both sides of the fan as-sembly at the bearings.
—OR—
1. The fan segment shall be run-balanced for 10% -100% of the design speed of the air handling unitequipped with a variable frequency drive.a. Units equipped with a variable frequency drive
that is balanced for a specific point of operationshall be field balanced for the entire RPM range.
B. All air handling units shall be inspected prior to ship-ment for dirt and loose debris.
2.11 INDIRECT GAS-FIRED FURNACE
1. The unit shall contain a factory-installed, forced-air,indirect-fired gas heater with an output capacity of BTU/hour. The combustion chamberprimary heating surface shall be fabricated of [16-gauge (up thru 1000 MBH)] [14-gauge] type 430stainless steel. The flue gases shall pass through a16-gauge stainless steel secondary heating surfaceone-pass tubular economizer equipped withturbulators.
2. All economizer tubes shall be accessible for clean-ing through an external access panel. The accessshall be located at the same end of the unit as theburner and flue outlet.
3. The forced air power burner for gas-firing shall beU.L. labeled, factory-mounted, wired, and tested.It shall be equipped with combustion air blower,motor, air-proving switch and primary Flame Safe-
guard Control. Additional controls required are;spark-ignited gas pilot, pilot gas cock, pilot sole-noid valve, pilot gas regulator, electric main gasvalves, main gas pressure regulator, main gas cock,and downstream manual firing valve. Componentsshall meet the requirements for (U.L.) (FM) (IRI)approval.
4. The burner shall be equipped for controlled modu-lated fired, including modulating damper motor, pro-portioning air damper fuel metering valves, endswitch, solenoid valves and necessary linkage toassure proper air fuel ratio at all rates. The burnershall be factory adjusted for a high-fire to low-firecapacity turndown ratio of 3 to 1 or 10 to 1.
5. A factory-installed induced draft blower shall bedirect driven by single purpose self-ventilating motorand controlled separately from the blowers andfactory-installed. The design shall be such thatcooling air is drawn over the inboard motor bear-ing and shaft. An integral draft proving switch shallassure proper operation of the ID fan before burnerignition.
6. All controls shall be factory-installed, including thesafety control. Required, relays, transformers,switches, fuse holders, and sequencing controlsshall be factory wired with suitable conduit andmounted in adequate enclosures of approved type.
7. Installation, operating instructions and wiring dia-grams shall be provided with each unit.
PART 3: EXECUTION
3.01 INSTALLATION
A. General: Installing contractor shall install air han-dling unit(s), including components and controls re-quired for operation, in accordance with air handlingunit manufacturer’s written instructions and recom-mendations. Air handling units shall be installed asspecified in Section _________________.
1. Air handling unit(s) shall be stored and protectedin accordance with Section _________________.
2. Air handling unit(s) shall be stored only in a clean,dry place, protected from weather and construc-tion traffic.
3. Air handling unit shall be handled such that dam-age to components, enclosure, and finish is avoided.
138 YORK INTERNATIONAL
B. Location:
3.02 STARTUP SERVICES
A. Manufacturer’s Supervision: A factory-trained servicerepresentative of the manufacturer shall supervise theunit startup and application specific calibration of con-trol components.
1. The air handling unit shall not be operated for anypurpose, temporary or permanent, until ductwork isclean, filters are in place, bearings are lubricated,and fan has been test run under observation.
2. After the air handling unit is installed, the variablefrequency drive (if supplied) shall be field commis-sioned by a factory trained and employed servicetechnician.
Guide Specifications
FORM 100.10-EG2