+ All Categories
Home > Documents > FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION...

FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION...

Date post: 11-Sep-2021
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
52
Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check www.jci.com/frick for the latest version of this publication. OPERATION FRICK ® QUANTUM HD UNITY SYSTEM CONTROLLER ENGINE ROOM • CONDENSER • VESSEL • EVAPORATOR Version 10.00 CURRENT DESIGN – AUGUST 2015
Transcript
Page 1: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

Form 090.670-O (AUG 2015) OPERATION

File: SERVICE MANUAL - Section 90Replaces: NOTHINGDist: 3, 3a, 3b, 3c

Please check www.jci.com/frick for the latest version of this publication.

OPERATION

FRICK® QUANTUM™ HD UNITYSYSTEM CONTROLLER

ENGINE ROOM • CONDENSER • VESSEL • EVAPORATOR

Version 10.00

CURRENT DESIGN – AUGUST 2015

Page 2: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 2

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

TABLE OF CONTENTSSECTION 1 - QUANTUM HD UNITY SYSTEM CONTROLLERSETUP DESCRIPTION .................................................. 4

WIRING .......................................................................... 4CONFIGURATION ............................................................ 4OPERATION .................................................................... 4

TYPICAL SYSTEM ....................................................... 4QUANTUM HD UNITY SYSTEM CONTROLLER ................ 4EVAPORATOR REMOTE I/O PANEL ................................. 4TYPICAL SYSTEM CONFIGURATION ............................... 4

SYSTEM INSTALLATION .............................................. 5WIRING FOR AC POWER ............................................. 5

QUANTUM HD UNITY SYSTEM CONTROLLER ................ 5REMOTE EVAPORATOR I/O PANELS ............................... 5

CHECKING THE AC POWER ......................................... 5QUANTUM HD UNITY SYSTEM CONTROLLER ................ 5REMOTE EVAPORATOR I/O PANELS ............................... 5

WIRING FOR COMMUNICATIONS ................................ 6QUANTUM HD UNITY SYSTEM CONTROLLER ................ 6REMOTE EVAPORATOR I/O PANELS ............................... 6

SECTION 2 - STARTUP AND CONFIGURATIONINITIAL STARTUP AND LOGIN ..................................... 8SYSTEM CONFIGURATION ........................................... 8

SECURITY – SYS CONFIG. > SECURITY .......................... 9PANEL – SYSTEM CONFIG. > PANEL ............................ 10

SECTION 3 - ENGINE ROOM CONTROLINTRODUCTION .........................................................12MAIN MENU & NAVIGATION ......................................12

EVENTS: .......................................................................13TRENDING: ...................................................................13

Trending Sub-menus ..............................................13ABOUT: ....................................................................... 14STATUS: ...................................................................... 14ALARMS: ..................................................................... 14CALIBRATION: ..............................................................15

Calibration Sub-menus ..........................................15CONFIGURATION: ........................................................ 16

Configuration Sub-menus ..................................... 16Analog Refrigerant Detection ................................ 16Digital Refrigerant Detection ................................. 16

SERVICE: ..................................................................... 19CLEAN SCREEN: .......................................................... 19

ENGINE ROOM ALARMS ........................................... 20

SECTION 4 - CONDENSER CONTROLINTRODUCTION .........................................................22MAIN MENU & NAVIGATION ......................................22

EVENTS: ...................................................................... 23TRENDING: .................................................................. 23

Trending Sub-menus ............................................. 23ABOUT: ....................................................................... 24STATUS: ...................................................................... 24ALARMS: ..................................................................... 25CALIBRATION: ............................................................. 25

Calibration Sub-menus ......................................... 25CONFIGURATION: ........................................................ 26

Configuration Sub-menus ..................................... 26Condenser Controller Setpoints ........................... 27

SERVICE: ..................................................................... 28CLEAN SCREEN: .......................................................... 28

CONDENSER ALARMS ................................................29

SECTION 5 - VESSEL CONTROLINTRODUCTION .........................................................32MAIN MENU & NAVIGATION ......................................32

EVENTS: ...................................................................... 33TRENDING: .................................................................. 33

Trending Sub-menus ............................................. 33ABOUT: ....................................................................... 34STATUS: ...................................................................... 34ALARMS: ..................................................................... 34CALIBRATION: ............................................................. 35

Calibration Sub-menus ......................................... 35CONFIGURATION: ........................................................ 36

Configuration Sub-menus ..................................... 36SERVICE: ..................................................................... 38CLEAN SCREEN: .......................................................... 38

VESSEL ALARMS .......................................................39

SECTION 6 - EVAPORATOR CONTROLINTRODUCTION .........................................................42MAIN MENU & NAVIGATION ......................................42

EVENTS: ...................................................................... 43TRENDING: .................................................................. 43

Trending Sub-menus ............................................. 43ABOUT: ....................................................................... 44STATUS: ...................................................................... 44ALARMS: ..................................................................... 45CALIBRATION: ............................................................. 45

Calibration Sub-menus ......................................... 45CONFIGURATION: ........................................................ 46

Configuration Sub-menus ..................................... 46Digital Auxiliaries .................................................. 49Analog Auxiliaries ................................................. 49Communications ................................................... 49Proportional Integral Control ................................ 50

SERVICE: ..................................................................... 50CLEAN SCREEN: ...........................................................51

EVAPORATOR ALARMS ..............................................51

Page 3: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 3

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

SECTION 1INTRODUCTION TO THE QUANTUM™ HD UNITY

SYSTEM CONTROLLER

SECTION 1 - Quantum HD Unity System Controller

Page 4: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 4

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

Setup Description

The following Setup Guide is meant to assist the installation technician in making all necessary electrical power, con-trol and communications connections to a Quantum™ HD Unity system. This guide also provides the basic information necessary to login and configure the system, and will aid in troubleshooting the system should problems arise.

This Guide will help to ensure:

Wiring

• Location of incoming AC source power to all panels, main controller and Remote I/O Panels

• Basic installation guidelines are followed.• Location, polarity & grounding of communications wiring.• Location of all control (I/O) wiring.• Proper powering up of all panels.

Configuration

• Logging into the system• Verifying communications.• Configuring Zones• Calibrating sensors.• Setting up operating Setpoints.

Operation

• Setting the operating Mode.• Verifying the data being returned to the Interface panel

from all remote panels. (Zones)• Checking and clearing of alarms.• Ammonia Configuration

Typical System

A system will typically include one Quantum HD Unity System Controller to control the engine room, condensers, vessels and evaporators along with remote I/O panels for the evapo-rators. The I/O for the engine room, condensers and vessels is contained in the Quantum HD Unity System Controller enclosure.

Quantum HD Unity System Controller

Evaporator Remote I/O Panel

One remote Evaporator I/O panel can control up to 3 zones or valve stations. Each system may have one or more Engine Room, Vessel, Evaporator or Condenser remote I/O panels. The Evaporator Remote I/O panel (below) does not have a display.

Typical System Configuration

The typical Quantum HD Unity System Controller consists of one centrally located control and I/O panel that contains the controllers for condenser, vessel, engine room and evapora-tor control. This panel also contains the digital and analog I/O for condenser, vessel and engine room control.

The evaporator I/O is located in smaller remote I/O panels that can be mounted wherever it is convenient for installation and maintenance. Up to 10 remote evaporator I/O panels (30 zones) are controlled by one evaporator controller.

Page 5: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 5

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

System Installation

Follow these basic installation rules:

• Maximum total serial communications cable distance between the main unit controller and the very last Re-mote Evaporator I/O Panel on any one communications cable run is 2000 feet. It is possible to have two separate communications cable runs depending upon the total number of Remote I/O Panels. Keep in mind, however, that neither of these cable runs can exceed 2000 feet in length.

• Keep all communications wiring in a separate conduit from control or power wiring.

• When wiring for serial communications, it is important to ground only one end of the communications cable. This ground will be located in the very last Remote Panel of each communications cable run. Ground loops could develop if the communications were to be grounded at both ends, impairing communications between panels.

• The Main Unity controller panel is rated NEMA Type-12. This needs to be considered when selecting a location to install the main Quantum HD Unity System Controller enclosure.

• Remote I/O Panels are rated for both indoor and outdoor use. Although the need to access Remote Panels will be rare after installation and setup, it is still advantageous to keep them accessible for potential maintenance situa-tions (reasonable lighting, sufficient door swing, etc.).

• Install all panels within a convenient distance of a power source.

Wiring For AC Power

Quantum HD Unity System Controller

The incoming AC power will consist of 3 #10 AWG wires (Hot Neutral and Ground that are fed from a 20 Amp service minimum.

• Connect the three incoming AC wires to the terminal screws as shown on the drawings for the Main Quantum HD Unity System Controller enclosure.

• Proceed to the section entitled Checking the AC Power.

Remote Evaporator I/O Panels

The incoming AC power will consist of three 12 AWG wires (hot neutral and ground) from a 15 amp service (minimum).

• Unlatch the two ¼ turn cover latches to the Interface panel, and open the door.

• Inside the enclosure, there is a long DIN rail at the right side of the panel. At the top of the DIN rail is a terminal strip.

• Connect the three incoming AC wires to the terminal screws per the remote evaporator I/O panel drawing.

• Notice that there are multiple number 2 terminals, con-nection may be made to any of them.

Checking The AC Power

Quantum HD Unity System Controller

• Ensure the Control Power switch is in the OFF position.

• Energize the 120 Volt circuit at its source.

• Using a DVM, measure the voltage at the AC power ter-minal strip. Ensure that you read approximately 120 VAC between Hot and Neutral, and Hot and Ground. There must not be voltage between Neutral and Ground.

• Once the incoming voltage has been verified, turn the Control Power switch to ON.

• Watch the Quantum™ HD Unity controller circuitry on the backside of the door. You should notice various LEDs blinking or flashing.

• Watch the display on the front of the door. After a short period of time, you should notice the display showing a boot sequence. Various text messages will be shown as it proceeds with the boot-up process. When finished, a screen similar to the following image should be visible:

• If the panel has reached the point of showing the previ-ous screen, the boot process was successful. Turn OFF the Control Power switch, and de-energize the 120 Volt circuit at its source.

• If the panel does not reach to the point of showing the above screen, then troubleshooting will be required. Refer to end of this guide entitled Troubleshooting.

Remote Evaporator I/O Panels

• The remote evaporator I/O panel can come with optional HOA switches that can be used to manually energize evaporator zone components. These are easily added in the field after startup if determined to be necessary.

Page 6: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 6

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

Red, power OFF tab

Black, power ON plunger

• Notice in the above pictorial, there is a Red power OFF tab, and a black power ON plunger. These items are located on a circuit breaker for each of the two HOA modules.

• Push each of the Red power OFF tabs down. The Black power ON plunger should pop up. If the plunger does not pop up, then the power was already off. Do this to both HOA modules.

• Energize the 120 Volt circuit by switching on the control power switch on the right side of the enclosure.

• Using a DVM, measure the voltage at the AC power ter-minals (1, 2 and PE). Ensure that you read approximately 120 VAC between Hot and Neutral, and Hot and Ground. There must not be voltage between Neutral and Ground.

• Above the optional HOA modules are the I/O boards. There will be at least one Digital board (recognizable by the plug-in I/O modules), and one Analog board. Inspect all boards for the presence of flashing, blinking or steadi-ly lit LED’s. If LED’s are lit on all boards, then power has been properly applied.

• If LED’s are not lit on all boards, then refer to the section entitled Troubleshooting.

Wiring For Communications

Quantum HD Unity System Controller

All serial communications between the condenser, vessel and engine room control are factory wired and tested. Verify that the Rx/TX lights for all analog and digital boards for condens-er, vessel and engine room control are flashing.

Remote Evaporator I/O Panels

Use the following wiring procedure:

• Open the Quantum HD Unity controller door.

• At the bottom left there is a DIN rail with several termi-nals for the Condenser, Vessel, Engine Room and Evapo-rator serial communications. The Condenser, Vessel and engine Room comms are already are factory wired.

• The terminals are marked by product. The Evaporator terminals are marked as

• E -R/T 3 and E +R/T 3 for the first 5 remote I/O panels, and E -R/T 4 and E +R/T 4 for the second set of 5 remote I/O panels.

• Follow the wiring diagrams for both the Evaporator I/O panels and the Quantum HD Unity System Controller/Evaporator Control to properly wire the serial commu-nications observing the grounding points, wire sizes and general serial communications daisy chaining practices

• Refer to the CONDENSER/VESSEL SYSTEM COMMUNICA-TIONS WIRING DIAGRAM to verify dipswitch settings.

Page 7: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 7

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

SECTION 2 - STARTUP AND CONFIGURATION

Page 8: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 8

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

System Configuration

System configuration requires the user to be logged in at the service user level. Once logged in the system configuration must be completed before moving to the individual control configuration for Engine Room, Condenser, Vessel and Evapo-rator.

System Networking - If all segments of the control (depen-dent on which segments were ordered) are listed and shown on the System Overview page (shown above) no action needs taken on the System Networking page.

If a segment of control does not appear on the System Over-view page, or a segment is being added after delivery, select Sys Config. > System Networking (shown below).

System Networking has several pages. The landing page for System Networking is the “List” page (below) which will list each control section that is currently networked and com-municating. Controls sections can be edited on this page with regard to product category, IP address, port and URL. Control sections can also be deleted from the network on this page.

Initial Startup And Login

The touch-screen was calibrated at the factory but this calibration may be compromised during shipment. During the booting process the touch-screen calibration page will occur with a 5 second timer as shown here. Touch anywhere on the screen before the timer times out to initiate the touch-screen calibration process.

Once calibration has been initiated this animated symbol below will appear in the top left corner of the screen.

• Touch this symbol and follow it through all 16 points of the screen calibration.

• Once the touch-screen calibration is complete, the boot process will continue to the System Overview Screen shown below.

• This screen will list the areas of control provided by this system that may include Engine Room, Condenser, Vessel and Evaporator control.

As indicated on the previous image a login is required to interact with the controller. The factory default logins are as follows;

• Basic User – 1• Operator User – 2• Service User – 3

Page 9: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 9

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

A “Scan Network” button is available on this page as a quick means to adding control sections that may be added after initial startup. Other pages within “System Networking” are Network and Add.

The “Network” page is where a network’s Gateway Ad-dress and Subnet Mask settings can be entered. There is also an “Auto Detect” button that can be used to identify these values if connected to a network. Be sure to press the Save button to save any changes made on this page before exiting.

The “Add” page is where control sections such as Condenser, Vessel, Engine Room and Evaporator can be manually added.

To add a control section on the Add page:

1. Select the control section from the drop down box.2. If Condenser/Vessel select Condenser, Vessel or Both3. Enter the IP Address4. Enter the Port number (a common port configuration is 80).5. Enter a website URL if a website will be used to connect to

the Quantum HD Unity controller6. Be sure to save any changes that were made before leaving

this page.

Security – Sys Config. > Security

There must always be at least one user for each user level - Basic, Operator and Service. To add, edit or delete a user touch the corresponding button for that action. To Add or Edit User, select that action and fill in or edit the appropri-ate fields. To delete a user select the Delete User button that corresponds with the user being deleted. Respond to the question “Are you sure you want to delete this user” accord-ingly.

Once on the “Add” page…

1. Fill in the information for the user being added. Email Ad-dress, Mobile Phone Number and Mobile Carrier are not required.

2. Select a level of access for that user3. Enter a PIN number for that user (typically 1-6 characters)4. Save changes before leaving this page

Page 10: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 10

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

Panel – System Config. > Panel

The Panel configuration page is where the basic panel con-figuration with regard to date, time, language, temperature and pressure units are configured. There are 4 drop down selection boxes on this page and are described below. Other parameters are setpoints that are defined by ranges. When changing any of the date and time configuration the Submit Changes button must be selected for the changes to be in effect.

Date Format

• mm/dd/yyyy, dd/mm/yyyy

Language

• English

Pressure Units

• KPaA, Bar, BarA, PSIA, PSIG

Clean Screen Mode Timeout – Establishes the amount of time that the touch-screen is locked out when Clean Screen is selected from any menu page.

At the end of any session be sure to Logout from any Menu page before leaving.

An Auto-Logout will occur after 5 minutes of inactivity.

Page 11: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 11

QUANTUM™ HD UNITYENGINE ROOM OPERATION

SECTION 3 - ENGINE ROOM CONTROL

Page 12: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 12

QUANTUM™ HD UNITYENGINE ROOM OPERATION

Introduction

Engine Room Control provides monitoring and control for the following:

• Refrigerant Detection – Monitors up to 4 refrigerant sensors and provides the appropriate level of notification and response based on the level reading.

• Engine Room Ventilation – Up to four output to control ventilation based on temperature or refrigerant level in the space.

• Floor Warming – Pumped glycol or electric heat control for floor warming.

• Additional digital and analog auxiliaries along with pro-portional and integral control loops can be configured to control other ancillary items as necessary.

Select Engine Room control by touching anywhere in the Engine Room control block on the System Overview page or selecting from the drop down if on another control page such as Evaporator.

The Engine Room home page illustrates all the pertinent operating data on the left side of the page and operational status and interactive control buttons on the right. A System Operating Values area is in the lower left of the page. This is used to display non-standard analog values that may be configured and read by the system.

The “System Operating Values” data is configured by touch-ing the Select Data button shown in the next graphic. From the user defined page select the additional items to be displayed on the Engine Room home page and select Save Changes.

Main Menu & Navigation

Home – Returns the user to the Engine Room home page

Alarms – Displays current and historical alarms as well as freeze data for each alarm

Calibration – Calibration for all enabled analog inputs

Configuration – Configuration for all operational feature such as refrigerant detection, ventilation and floor warming

About – Displays all software information for the processor, interface, analog and digital boards

Status – Displays current status of the analog and digital I/O, serial comm. Ports 1-3, I/O comms., Modbus TCP and Ether-net I/P

Service – Diagnostics, software maintenance, security, down-load system data

Logout – Logs out user when session is complete

Page 13: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 13

QUANTUM™ HD UNITYENGINE ROOM OPERATION

ACCESSING:

ACCESSING:

EVENTS:

The “Events” page displays record-ed events such as power down and power up times. Touch the Next button in the lower right to view earlier events that do not appear on this screen.

TRENDING: The “Trending” page displays his-torical data and provides a means to “Select Data To Trend”, the read “Interval” and Download Trend-ing Data. A USB Thumb Drive must be inserted into the respective controller USB port to Download System Data.

Trending Sub-menus

Select Data To Trend - Select Data to be trended from the list shown when the “Select Data To Trend” button is pushed.

Interval - Change the read interval by touching the “Inter-val” setpoint box, select the desired value using the on-page keypad and press Enter.

Download Trending Data - Download Trending Data, plug in a flash drive/thumb drive (configured for FAT32). Once the drive

is detected touch the “Download Trending Data” button on the trending page.

Download Trending Data can also be done by a networked computer, tablet or smartphone that has the ability to save and open Excel spreadsheets.

Page 14: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 14

QUANTUM™ HD UNITYENGINE ROOM OPERATION

ACCESSING:

ABOUT:

The “About” page lists the software and firmware version for the pro-cessor, interface, analog and digital boards. It also lists the Sales Order and Item numbers.

ACCESSING:

ACCESSING:

STATUS:

The Status page displays the real time status of the analog and digital I/O, serial comm. ports 1-3, I/O comms., Modbus TCP and Ethernet I/P.

ALARMS:

The Alarms page displays current and historical alarms as well as freeze data for each alarm. Alarm Silence or Clear All alarms from this page. Freeze Data Selection is also initiated from this page. View earlier alarms by pressing the Next button.

Page 15: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 15

QUANTUM™ HD UNITYENGINE ROOM OPERATION

ACCESSING:

CALIBRATION:

The Calibration page is used to calibrate all enabled analog inputs, analog auxiliaries and analog out-puts.

Calibration Sub-menus

Calibration – Enter the value for the device being calibrated into the Current Value box for that device. The Offset value will automatically calculate and populate that cell. Offsets can also be zeroed which will change the Current Value accord-ingly. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled.

From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled in the same manner. To Calibrate an analog output requires a calibrated meter that can read a milliamp (mA) signal.

To calibrate an analog output for a 4-20mA or 0-20mA do the following from the Output calibration page.

• Select the Analog Board and Channel for the output to be calibrated.

• Attach the black lead to the negative terminal and the red probe to the positive terminal for the channel to be cali-brated.

• Set the calibrated meter to read DC mA

• Select Calibrate Low End and use the + and – value buttons of various change values to calibrate to the desired value of 0 or 4 mA.

• Select Calibrate High End and use the + and – buttons of various change values to calibrate the high end to 20 mA.

Page 16: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 16

QUANTUM™ HD UNITYENGINE ROOM OPERATION

ACCESSING:

CONFIGURATION:

The Configuration page/menu is used to access main areas of configuration such as Refrigerant Detection, Ventilation, Floor Warm-ing Digital and Analog Auxiliaries, Communications, P/I Control, Digital and Analog I/O.

Configuration Sub-menus

Configuration for Refrigerant Detection, Ventilation, Floor Warming, Digital I/O and Analog I/O are covered on the fol-lowing pages. Common configuration items such Digital Aux-iliaries, Analog Auxiliaries, Communications and Proportional Integral Control are covered in their respective sections.

Refrigerant Detection – Up to 4 analog inputs and 2 digital inputs can be configured for Refrigerant Detection. Start by enabling Analog Refrigerant Detection/Warning, Digital Re-frigerant Detection/Warning or both.

Analog Refrigerant Detection

Number of Detectors – Select up to 4 sensors to be moni-tored with two levels of warning

Detector – Custom tag the detectors listed or leave at default tags

Refrigerant Warning 1 – Sets the value at which a Refriger-ant Warning 1 alarm is issued after the delay. A Refrigerant Warning 1 will energize the audible/visual alarm. It self-clears once the level drops below 20PPM.

Refrigerant Warning 1 – Sets the value at which a Refriger-ant Warning 2 alarm is issued after the delay. A Refrigerant Warning 2 energizes the audible/visual alarm and initiates Emergency Ventilation (all ventilation steps are on at full ca-pacity). It cannot be cleared until the PPM level is below the Refrigerant Warning 1 level.

Digital Refrigerant Detection

Refrigerant Warning 1 When – This warning can be set so that the warning occurs when the input module is de-ener-gized or energized (based on configuration) for the delay.

Refrigerant Warning 2 When – This warning can be set so that the warning occurs when the input module is de-ener-gized or energized (based on configuration) for the delay.

NOTICEIn digital mode the Refrigerant Warning 1 and Refriger-ant Warning 2 are independent and can occur out of sequence and can be cleared independently if the digital status is corrected per the configuration.

Ventilation – Up to 4 digital outputs can be enabled, named and configured to manage the ventilation of the engine room relative to minimum air flow and emergency air flow re-quirements. All four can be configured for independent VFD operation.

Number of Fan Outputs – Selectable from 0 – 4. The number selected sets the number of fan outputs to be configured. Each output can be custom named based on the users prefer-ence or building drawing designations.

Page 17: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 17

QUANTUM™ HD UNITYENGINE ROOM OPERATION

Type – Select between Fixed and VSD for the type of fan control that will be used.

Step On – Establishes the order which each step will come on-line. More than one output can be configured with the same Step On number.

Control Setpoint – Set the desired Temperature to be main-tained in the engine room.

Upper Dead Band – Sets the degrees of temperature above the control setpoint where steps are brought on-line.

Upper Dead Band – Sets the degrees of temperature below the control setpoint where steps are taken off-line.

Step Delay – The delay to bring step on-line or take steps off-line.

All Outputs On – Sets the temperature at which all ventilation outputs will energize. Steps configured as VSD will go to the Maximum Output configured in VSSD Ventilation Control.

VSD Ventilation Control – If any of the ventilation steps are configured as VSD, the following setpoints are used to control the output to the VSD.

Proportional Band – The value over the Control Setpoint at which time the VSD output will be at it’s maximum propor-tionally.

Integration Time – The time in which additional VSD output is integrated into the total VSD output, enabling the control to maintain the Control Setpoint.

Maximum Output – Sets the maximum drive output that can be emitted from the assigned analog output. If the output is configured as 4-20 mA and the Maximum Output is 80% the output would be limited to 16.8 mA.

Minimum Output – As with the Maximum Output, the Mini-mum Output set the low limit for the VSD output signal.

Floor Warming – Floor Warming is used to prevent freezing and heaving of the freezer space floors. It can be done by circulating glycol through tubes that run within the floor or resistive heating also integrated into the floor.

Glycol Heating – Floor temperature readings are used to control the On/Off of glycol Circulation Pump while returning glycol temperature is used to control the Glycol Heating.

Electric Heating – Floor Temperature Readings are used to control the On/Off of the Electric Heating.

Underfloor Temperatures – Select and name up to 4 under-floor temperature probes used to monitor floor temperature and control the Glycol Circulation Pump or the Electric Heat-ing.

Glycol Temperatures – Enable to monitor the supply and return temperatures as well as control glycol heating On/Off from the glycol return temperature.

Digital I/O Configuration – Used to configure standard Engine Room Control digital I/O by board and channel as well as display current status. Non-standard items can be config-ured for monitoring, alarms and control in Digital Auxiliaries configuration.

Page 18: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 18

QUANTUM™ HD UNITYENGINE ROOM OPERATION

Analog I/O Configuration (inputs) – Used to configure stan-dard Engine Room Control analog inputs by sensor range (low/high), sensor type, board and channel. Non-standard items can be configured for monitoring, alarms and control in Analog Auxiliaries configuration.

Analog I/O Configuration (outputs) – Used to configure stan-dard Engine Room Control analog outputs for VSD fan control by board and channel.

Page 19: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 19

QUANTUM™ HD UNITYENGINE ROOM OPERATION

ACCESSING:

ACCESSING:

SERVICE:

The Service page is for Diagnostics, Communications Testing, Software Maintenance, Ethernet Integrity, System Data Downloads and I/O Integrity.

CLEAN SCREEN:

Clean Screen disables the screen for cleaning purposes. Timeout is displayed on the page.

Page 20: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 20

QUANTUM™ HD UNITYENGINE ROOM OPERATION

Engine Room AlarmsFollowing is the listing of all possible Engine Room alarms:

Analog Aux Low Warning (1)

Occurs if the warning is enabled on Analog Aux Input A – J and the respective analog input reading is less than or equal to the low setpoint for the time delay.

Analog Aux High Warning (1)

Occurs if the warning is enabled on Analog Aux Input A – J and the respective analog input reading is greater than or equal to the high setpoint for the time delay.

Digital Aux Input Warning (digital aux input a-j) (2)

Occurs if the warning is enabled on Digital Aux Input A – J and the respective input is de-energized for the time delay.

Analog Board 1 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 1 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 1 Reset

Occurs if the watchdog circuit on the respective digital board does not see active communications with the processor board for 5 seconds or if the 5vdc power to the board drops below 4.85vdc.

Engine Room Temperature Sensor Fault (5)

Occurs if the digital count for the respective sensor is outside of the low or high end of the count range.

Refrigerant Warning 1 - Refrigerant Detector A, B, C or D (3)

Occurs if Analog Refrigerant Detection Warnings are enabled, the Refrigerant Warning 2 Digital Output is safe, and the respective Refrigerant Detector reading is above this warning’s setpoint for its time delay.

Refrigerant Warning 2 - Refrigerant Detector A, B, C or D (3)

Occurs if Analog Refrigerant Detection Warnings are enabled and the respective Refrigerant Detector reading is above this warning’s setpoint for its time delay.

Refrigerant Warning 1 - Digital Input

Occurs if Digital Refrigerant Detection Warnings are enabled, the Refrigerant Warning 2 Digital Output is safe, and the Refrigerant Warning 1 Digital Input is in the user-selected state for this warning for its time delay.

Refrigerant Warning 2 - Digital Input

Occurs if Digital Refrigerant Detection Warnings are enabled, and the Refrigerant Warning 2 Digital Input is in the user-selected state for this warning for its time delay.

SENSOR FAULT COUNT RANGESensor Type Low End Count High End Count

ICTD (temperature) 1597 3505RTD (temperature 1100 40851-5v or 2-10v or

4-20mA <614 No Upper Limit

Note: Sensor faults are not provided for these sensor types: 0-5v, 0-10v or 0-20mA.

1. Analog Aux Inputs A-J may be custom named by user.2. Digital Aux Inputs A-J may be custom named by user.3. Refrigerant Detector A-D may be custom named by user.4. Underfloor Temp Sensor A-D may be custom named by user.5. See the count range table for various sensor types.

Refrigerant Detector A Sensor Fault (3) (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Refrigerant Detector B Sensor Fault (3) (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Refrigerant Detector C Sensor Fault (3) (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Refrigerant Detector D Sensor Fault (3) (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Underfloor Glycol Return Temp. Sensor Fault (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Underfloor Glycol Supply Temp. Sensor Fault (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Underfloor Temperature A Sensor Fault (4) (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Underfloor Temperature B Sensor Fault (4) (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Underfloor Temperature C Sensor Fault (4) (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. The count range can be viewed on the Analog Board status page.

Underfloor Temperature D Sensor Fault (4) (5)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Page 21: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 21

QUANTUM™ HD UNITYCONDENSER OPERATION

SECTION 4 - CONDENSER CONTROL

Page 22: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 22

QUANTUM™ HD UNITYCONDENSER OPERATION

IntroductionCondenser Control provides monitoring and control for the following:

• Condenser Steps – 16 steps of condenser control that can be configured as a fixed speed fan, 2 Sp Fan Lo, 2 Sp Fan Hi, Var. Sp Fan or Water Pump. Eight analog outputs are avail-able for Var. Sp Fan control.

• Dynamic Setpoint Control – Monitors humidity and out-door temperature to calculate wet-bulb temperature. The condenser approach is added to the wet-bulb temperature to establish a dynamic condenser control setpoint that will change with the ambient conditions.

• Non-Condensable Gas Notification – Alerts the operator if a high level of non-condensable gas is detected in the system.

• Alternate Pressure Control – Can be configured to adjust the condensing control setpoint to a value which will ensure adequate defrost.

• Bleed Control – Turns on a bleed output for a used defined period of time at a user defined interval.

• Additional digital and analog auxiliaries along with propor-tional and integral control loops can be configured to control other ancillary items as necessary.

Select Condenser control by touching anywhere in the Condenser control block on the System Overview page or selecting from the drop down if on another control page such as Evaporator.

The Condenser home page illustrates all the pertinent oper-ating data on the left side of the page and operational status and interactive control buttons on the right. A System Oper-ating Values area is in the lower left of the page. This is used to display non-standard analog values that may be configured and read by the system.

The “System Operating Values” data is configured by touch-ing the Select Data button shown above. From the user de-fined page select the additional items to be displayed on the Condenser home page and select Save Changes.

Main Menu & NavigationHome – Returns the user to the Condenser home page

Alarms – Displays current and historical alarms as well as freeze data for each alarm

Calibration – Calibration for all enabled analog inputs

Configuration – Configuration for all operational feature such as refrigerant detection, ventilation and floor warming

About – Displays all software information for the processor, interface, analog and digital boards

Status – Displays current status of the analog and digital I/O, serial comm. Ports 1-3, I/O comms., Modbus TCP and Ether-net I/P

Service – Diagnostics, software maintenance, security, down-load system data

Logout – Logs out user when session is complete

Page 23: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 23

QUANTUM™ HD UNITYCONDENSER OPERATION

ACCESSING:

ACCESSING:

EVENTS:

The “Events” page displays record-ed events such as power down and power up times. Touch the Next button in the lower right to view earlier events that do not appear on this screen.

TRENDING:

The “Trending” page displays his-torical data and provides a means to “Select Data To Trend”, the read “Interval” and Download Trend-ing Data. A USB Thumb Drive must be inserted into the respective controller USB port to Download System Data.

Trending Sub-menus

Select Data To Trend - Select Data to be trended from the list shown when the “Select Data To Trend” button is pushed.

Interval - Change the read interval by touching the “Inter-val” setpoint box, select the desired value using the on-page keypad and press Enter.

Download Trending Data - Download Trending Data, plug in a flash drive/thumb drive (configured for FAT32). Once the drive is detected touch the “Download Trending Data” button on the trending page.

Download Trending Data can also be done by a networked computer, tablet or smartphone that has the ability to save and open Excel spreadsheets.

Page 24: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 24

QUANTUM™ HD UNITYCONDENSER OPERATION

ACCESSING:

ABOUT:

The “About” page lists the software and firmware version for the pro-cessor, interface, analog and digital boards. It also lists the Sales Order and Item numbers.

ACCESSING:

STATUS:

The Status page displays the real time status of the analog and digital I/O, serial comm. ports 1-3, I/O comms., Modbus TCP and Ethernet I/P.

Page 25: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 25

QUANTUM™ HD UNITYCONDENSER OPERATION

ACCESSING:

ALARMS:

The Alarms page displays current and historical alarms as well as freeze data for each alarm. Alarm Silence or Clear All alarms from this page. Freeze Data Selection is also initiated from this page. View earlier alarms by pressing the Next button.

ACCESSING:

CALIBRATION:

The Calibration page is used to calibrate all enabled analog inputs, analog auxiliaries and analog out-puts.

Calibration Sub-menus

Calibration – Enter the value for the device being calibrated into the Current Value box for that device. The Offset value will automatically calculate and populate that cell. Offsets can also be zeroed which will change the Current Value accord-ingly. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled.

From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled in the same manner. To Calibrate an analog output requires a calibrated meter that can read a milliamp (mA) signal.

To calibrate an analog output for a 4-20mA or 0-20mA do the following from the Output calibration page.

• Select the Analog Board and Channel for the output to be calibrated.

• Attach the black lead to the negative terminal and the red probe to the positive terminal for the channel to be calibrated.

• Set the calibrated meter to read DC mA

• Select Calibrate Low End and use the + and – value buttons of various change values to calibrate to the desired value of 0 or 4 mA.

• Select Calibrate High End and use the + and – buttons of various change values to calibrate the high end to 20 mA.

Page 26: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 26

QUANTUM™ HD UNITYCONDENSER OPERATION

ACCESSING:

CONFIGURATION:

The Configuration page/menu is used to access main areas of configuration such as Pumps and Fans, Summer/Winter Sequence, Condenser Control Setpoints and overrides and Analog Auxiliaries, Communications, P/I Control, Digital and Analog I/O.

Configuration Sub-menus

Configuration for Pumps and Fans, Summer/Winter Sequence, Condenser VSD, Condenser Control Setpoints and Overrides, Digital I/O and Analog I/O are covered on the following pages. Common configuration items such Digital Auxiliaries, Analog Auxiliaries, Communications and Proportional Integral Control are covered in their respective sections.

Condenser Information – Select the number of individual condenser/s and enter model number and serial number information for each.

Pumps and Fans – Pumps and Fans A-H (8) and I-P (8) are configured on this page. Select each condenser step as a Water Pump, Single Spd Fan, Var Speed Fan or 2-Spd Fan Lo. Selecting a step as 2-Spd Fan Lo automatically sets the next step as 2-Spd Fan Hi. Each step can have an Aux. Failure enabled. Water pumps will have an Outside Air Stop enabled. If selected as a VFD the analog output used for that step is selectable. If set as a 2-Spd Fan Lo/Hi a delay between high speed and low speed is available.

The name for each step is has a default tag relative to the selection and can be changed by the user to match plant designations.

Summer/Winter Sequence – Set the step sequence for the summer sequence on this page. There is also a winter sequence page. The Step On / Off Sequence can be selected as standard or custom. Standard sequence sets the Off sequence relative to the On sequence in a first On, last Off order. Custom sequence allows the user to set both the On and Off sequence to best fit the application.

Condenser VSD Control – If any of the condenser steps are configured as VSD Fan, the VSD control setpoints are on this page. These setpoints are the same as used in other areas for P/I control. The fan control strategy can be selected as one of the following;

• Ramp After All Steps On – After all VSD Fan steps are on at minimum speed (30%), the fans will ramp up and down together.

• Ramp After Each Step – Each VSD Fan is allowed to ramp after it is turned on. When other VSD Fan steps come on they will sink to the speed of the others on line.

Page 27: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 27

QUANTUM™ HD UNITYCONDENSER OPERATION

Condenser Controller Setpoints

Summer / Winter – Controls setpoints for both Summer and Winter nodes are set on this page. The control setpoint is a calculated value when the Control Strategy is selected as Dynamic. Also selecte between Automatic and manual with regard to transitioning from Summer to Winter modes.

Control / Safety – The following condenser control features are configured on this page.

• Control Strategy – Fixed Setpoint or Dynamic: Dynamic control calculates the wet-bulb temperature along with the condenser approach setpoint and the refrigerant selection to establish a saturated condensing temperature/pressure to control to.

• Condenser Bleed Control – Will control the energizing of a bleed solenoid for a user defined period of time at a user defined interval.

• Alternate Pressure Control – Can be set as Defrost, Standby or Disabled: Often set as defrost, the controller will commu-nicate to the evaporator controller to determine if units are going into defrost. When units go into defrost the Condenser Control Setpoint will change to the Defrost Setpoint on the Summer / Winter setpoints page if the current setpoint is less than that value.

Condenser Control Overrides – Override setpoints are de-signed to take control over the configured control strategies if the operation is outside of the bounds listed below for the associated delay.

Digital I/O – Used to configure standard Condenser Control digital I/O by board and channel as well as display current status. Non-standard items can be configured for monitoring, alarms and control in Digital Auxiliaries configuration. There 4 pages to cover all of the standard I/O for condenser control.

Analog I/O Configuration – Used to configure standard Con-denser Control analog inputs by board and channel. Non-standard items can be configured for monitoring, alarms and control in Analog Auxiliaries configuration.

Analog I/O Configuration (outputs) – Used to configure stan-dard Condenser Control analog outputs for VSD fan control by board and channel. The Analog Outputs page is used to configure the VSD Fan outputs by board and channel if used.

Page 28: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 28

QUANTUM™ HD UNITYCONDENSER OPERATION

ACCESSING:

ACCESSING:

SERVICE:

The Service page is for Diagnostics, Communications Testing, Software Maintenance, Ethernet Integrity, System Data Downloads and I/O Integrity.

CLEAN SCREEN:

Clean Screen disables the screen for cleaning purposes. Timeout is displayed on the page.

Page 29: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 29

QUANTUM™ HD UNITYCONDENSER OPERATION

Condenser AlarmsFollowing is the listing of all possible Condenser alarms:

Analog Aux Low Warning (1)

Occurs if the warning is enabled on Analog Aux Input A – J and the respective analog input reading is less than or equal to the low setpoint for the time delay.

Analog Aux High Warning (1)

Occurs if the warning is enabled on Analog Aux Input A – J and the respective analog input reading is greater than or equal to the high setpoint for the time delay.

Digital Aux Input Warning (digital aux input a-j) (2)

Occurs if the warning is enabled on Digital Aux Input A – J and the respective input is de-energized for the time delay.

Analog Board 1 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 1 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 2 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 1 Reset

Occurs if the watchdog circuit on the respective digital board does not see active communications with the processor board for 5 seconds or if the 5vdc power to the board drops below 4.85vdc.

Digital Board 2 Reset

Occurs if the watchdog circuit on the respective digital board does not see active communications with the processor board for 5 seconds or if the 5vdc power to the board drops below 4.85vdc.

Ammonia 1, 2 or 3 Warning (analog) (3)

Occurs if the respective warning is enabled and the respective Ammonia Input reading is greater than the warning setpoint for the time delay.

Condenser Step Aux. (4)

Up to 16 condenser steps can be enabled. They are listed as Steps A-P. The Condenser Step Aux. alarm occurs if the Aux Failure feature is enabled for the respective condenser step and the aux. input is de-energized when the output for that step is energized

Condenser False Run Input (4)

Up to 16 condenser steps can be enabled. They are listed as Steps A-P. The Condenser False Run Input alarm occurs if the “Aux Failure” feature is enabled for the respective condenser step and the aux. input is energized when the output for that step is de-energized.

SENSOR FAULT COUNT RANGESensor Type Low End Count High End Count

ICTD (temperature) 1597 3505RTD (temperature 1100 40851-5v or 2-10v or

4-20mA <614 No Upper Limit

Note: Sensor faults are not provided for these sensor types: 0-5v, 0-10v or 0-20mA.

1. Analog Aux Inputs A-J may be custom named by user.2. Digital Aux Inputs A-J may be custom named by user.3. Ammonia Inputs 1-3 may be custom named by user.4. Condenser Steps A-P may be custom named by user.5. Underfloor Temp Sensor A-D may be custom named by user.6. See the count range table for various sensor types.

High Pressure Warning

Occurs if the active condensing pressure A or B is above the high pressure warning setpoint for the time delay.

Non-Condensable Gas Warning

Occurs if the warning is enabled and the condensing pressure is greater than the saturated condensing pressure plus the Non-Condensable Gas Dead Band for the delay.

Note: The saturated condensing pressure is derived by converting the Condenser Liquid Temperature to a saturated pressure relative to the selected refrigerant.

Ammonia 1, 2 or 3 Sensor Fault (5) (6)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Condensing Pressure A Sensor Fault (5) (6)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Condensing Pressure B Sensor Fault (5) (6)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Liquid Temperature Sensor Fault (5) (6)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Outside Air Temperature Sensor Fault (5) (6)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Outside Air Humidity Sensor Fault (5) (6)

Occurs if the if the digital count for the respective sensor is at the low or high end of the count range.

Page 30: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 30

QUANTUM™ HD UNITYCONDENSER OPERATION

Page 31: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 31

QUANTUM™ HD UNITYVESSEL OPERATION

SECTION 5 - VESSEL CONTROL

Page 32: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 32

QUANTUM™ HD UNITYVESSEL OPERATION

Introduction

Vessel Control provides monitoring and control for the fol-lowing:

• Recirculator Vessel Control – Level and pump control for up to 3 vessels with up to 4 pumps each.

• Digital or analog liquid makeup – Choose between digital or analog controlled liquid makeup on up to 2 makeup circuits on each vessel.

• Pump Order Rotation – Rotate the pump order manually or automatically based on run hours.

Select Vessel control by touching anywhere in the Vessel control block on the System Overview page or selecting from the drop down if on another control page such as Evaporator.

Vessel Overview Page shows all enable vessels with basic operational status. Select a particular vessel by touching anywhere in the vessel field to go to the home page for that vessel.

The Vessel home page illustrates all the pertinent operating data on the left side of the page and operational status and interactive control buttons on the right. A System Operating Values area is in the lower left of the page. This is used to display non-standard analog values that may be configured and read by the systems.

Main Menu & Navigation

Home – Returns the user to the Vessel home page

Alarms – Displays current and historical alarms as well as freeze data for each alarm

Calibration – Calibration for all enabled analog inputs

Configuration – Configuration for all operational features such as refrigerant detection, ventilation and floor warming

About – Displays all software information for the processor, interface, analog and digital boards

Status – Displays current status of the analog and digital I/O, serial comm. Ports 1-3, I/O comms., Modbus TCP and Ether-net I/P

Service – Diagnostics, software maintenance, security, down-load system data

Logout – Logs out user when session is complete

Page 33: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 33

QUANTUM™ HD UNITYVESSEL OPERATION

ACCESSING:

ACCESSING:

EVENTS:

The “Events” page displays record-ed events such as power down and power up times. Touch the Next button in the lower right to view earlier events that do not appear on this screen.

TRENDING:

The “Trending” page displays his-torical data and provides a means to “Select Data To Trend”, the read “Interval” and Download Trend-ing Data. A USB Thumb Drive must be inserted into the respective controller USB port to Download System Data.

Trending Sub-menus

Select Data To Trend - Select Data to be trended from the list shown when the “Select Data To Trend” button is pushed.

Interval - Change the read interval by touching the “Inter-val” setpoint box, select the desired value using the on-page keypad and press Enter.

Download Trending Data - Download Trending Data, plug in a flash drive/thumb drive (configured for FAT32). Once the drive is detected touch the “Download Trending Data” button on the trending page.

Download Trending Data can also be done by a networked computer, tablet or smartphone that has the ability to save and open Excel spreadsheets.

Page 34: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 34

QUANTUM™ HD UNITYVESSEL OPERATION

ACCESSING:

ABOUT:

The “About” page lists the software and firmware version for the pro-cessor, interface, analog and digital boards. It also lists the Sales Order and Item numbers.

ACCESSING:

ACCESSING:

STATUS:

The Status page displays the real time status of the analog and digital I/O, serial comm. ports 1-3, I/O comms., Modbus TCP and Ethernet I/P.

ALARMS:

The Alarms page displays current and historical alarms as well as freeze data for each alarm. Alarm Silence or Clear All alarms from this page. Freeze Data Selection is also initiated from this page. View earlier alarms by pressing the Next button.

Page 35: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 35

QUANTUM™ HD UNITYVESSEL OPERATION

ACCESSING:

CALIBRATION:

The Calibration page is used to calibrate all enabled analog inputs, analog auxiliaries and analog out-puts.

Calibration Sub-menus

Calibration – Enter the value for the device being calibrated into the Current Value box for that device. The Offset value will automatically calculate and populate that cell. Offsets can also be zeroed which will change the Current Value accord-ingly. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled.

From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled in the same manner. To Calibrate an analog output requires a calibrated meter that can read a milliamp (mA) signal.

To calibrate an analog output for a 4-20mA or 0-20mA do the following from the Output calibration page.

• Select the Analog Board and Channel for the output to be calibrated.

• Attach the black lead to the negative terminal and the red probe to the positive terminal for the channel to be cali-brated.

• Set the calibrated meter to read DC mA

• Select Calibrate Low End and use the + and – value buttons of various change values to calibrate to the desired value of 0 or 4 mA.

• Select Calibrate High End and use the + and – buttons of various change values to calibrate the high end to 20 mA.

Page 36: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 36

QUANTUM™ HD UNITYVESSEL OPERATION

ACCESSING:

CONFIGURATION:

The Configuration page/menu is used to access main areas of con-figuration such as Vessel Enable, Level and Pump Control, Safeties, Digital and Analog Auxiliaries, Communications, P/I Control, Digital and Analog I/O.

Configuration Sub-menus

Configuration to enable vessels, pumps, level control, pump control, safeties, refrigerant detection, digital and analog I/O are covered on the following pages. Common configuration items such Digital Auxiliaries, Analog Auxiliaries, Communica-tions and Proportional Integral Control are covered in their respective sections.

Vessel/Receiver Enable – Enable Vessels 1-3 for full vessel control including pumps liquid make-up and safeties. Also enable receivers for level monitoring only. All vessels and receivers can custom named to match the plant designations.

Level Control – Select between modulating level control or solenoid level control or a combination as shown here. The setpoints for the modulating control work the same as all other Quantum HD P/I Control loops. Select up to 2 modulat-ing valves, up to 2 solenoid valves and whether the solenoid control is analog from a level sensor or digital from float switches. To configure other enabled vessels touch the next vessel to be configured.

Pump Control – Configure up to 4 pumps (Pumps A & B), (Pumps C & D) per vessel. To configure another vessel, select that vessel from this page.

Key pump control configuration items are:

• Auto Pump Operation – Runs With Compressors, Runs Con-tinuously, Off on High Level. Low level safeties are active for all auto pump operation selections

• Auto Pump Rotate – Rotates pump operating order based on pump run hours.

• Pump Diff. Control – Monitors the pressure differential across each pump to protect the pump against cavitation.

• Pump Bypass Control – If the pressure differential rises above the Bypass Pressure Diff. setpoint for the delay the bypass output is turned on.setpoint

Safeties – Level safeties are configured on this page for both analog (probe) and digital (float/s) along with associated de-lays. Configure the safeties for other vessels by selecting the vessel from this page.

Page 37: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 37

QUANTUM™ HD UNITYVESSEL OPERATION

Refrigerant Detection – Configure up to three analog refriger-ant detection channels. Three corresponding digital outputs can be configured to be Normally On or Normally Off. These are triggered to the opposing position when triggered. Board and channel configuration is in Analog and/or Digital I/O con-figuration. Names can be “user defined” to match the plant designations for these devices.

Digital I/O Configuration - Used to configure standard Vessel Control digital I/O by board and channel as well as display current status. Non-standard items can be configured for monitoring, alarms and control in Digital Auxiliaries con-figuration. There 6 pages to cover all of the standard I/O for condenser control.

Analog I/O Configuration (inputs) - Used to configure stan-dard Vessel Control analog inputs by board and channel. Non-standard items can be configured for monitoring, alarms and control in Analog Auxiliaries configuration.

Analog I/O Configuration (Outputs) – Used to configure modulating makeup valves A & B for vessel 1, 2 and 3 by board and channel.

Page 38: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 38

QUANTUM™ HD UNITYVESSEL OPERATION

ACCESSING:

ACCESSING:

SERVICE:

The Service page is for Diagnostics, Communications Testing, Software Maintenance, Ethernet Integrity, System Data Downloads and I/O Integrity.

CLEAN SCREEN:

Clean Screen disables the screen for cleaning purposes. Timeout is displayed on the page.

Page 39: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 39

QUANTUM™ HD UNITYVESSEL OPERATION

Vessel AlarmsMost vessel alarms are duplicated from an original or “template” alarm, and the particular vessel name defines

the corresponding alarm. In the alarms definitions below the letter “X” represents any respective vessel. Vessels can be custom named by the user. That custom name will be the prefix for all alarms associated with that vessel.

Analog Aux Low Warning (1)

Occurs if the warning is enabled on Analog Aux Input A – J and the respective analog input reading is less than or equal to the low setpoint for the time delay.

Analog Aux High Warning (1)

Occurs if the warning is enabled on Analog Aux Input A – J and the respective analog input reading is greater than or equal to the high setpoint for the time delay.

Digital Aux Input Warning (digital aux input a-j) (2)

Occurs if the warning is enabled on Digital Aux Input A – J and the respective input is de-energized for the time delay.

Analog Board 2 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Analog Board 3 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 4 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 4 Reset

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 5 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 5 Reset

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 6 Communications Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 6 Reset

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Vessel X - High Level Warning Digital Input

Occurs if the High Level Warning Digital Input is enabled and the digital input is de-energized for the time delay.

Vessel X - High Level Shutdown Digital Input

Occurs if the High Level Shutdown Digital Input is enabled and the digital input is de-energized for the time delay.

Vessel X - Low Level Warning Digital Input

Occurs if the Low Level Warning Digital Input is enabled and the digital input is de-energized for the time delay.

SENSOR FAULT COUNT RANGESensor Type Low End Count High End Count

ICTD (temperature) 1597 3505RTD (temperature 1100 40851-5v or 2-10v or

4-20mA <614 No Upper Limit

Note: Sensor faults are not provided for these sensor types: 0-5v, 0-10v or 0-20mA.

1. Analog Aux Inputs A-J may be custom named by user.2. Digital Aux Inputs A-J may be custom named by user.3. See the count range table for various sensor types.

Vessel X - Low Level Shutdown Digital Input

Occurs if the Low Level Shutdown Digital Input is enabled and the digital input is de-energized for the time delay.

Vessel X - High Level Warning

Occurs if Analog Input Safeties are enabled and the refrigerant level reading is above the high level warning setpoint for the time delay.

Vessel X - Low Level Warning

Occurs if Analog Input Safeties are enabled and the refrigerant level reading is below the low level warning setpoint for the time delay.

Vessel X - Low Level Shutdown

Occurs if Analog Input Safeties are enabled and the refrigerant level reading is below the low level shutdown setpoint for the time delay.

Vessel X - Pump A, B, C or D Pressure Differential Shutdown

Occurs if the Pressure Diff. Control alarm is enabled, the pump is running, and the differential between the high side pump pressure and low side pump pressure is less than the Min. Pressure Diff. setpoint for the time delay.

Vessel X - Refrigerant Pump A, B, C or D Auxiliary Shutdown

Occurs if the Pump Auxiliary Input is enabled, the pump is running, and the Pump Auxiliary Input is de-energized for the time delay.

Vessel X - Pump A, B, C or D Hi Side Press. Sensor Fault (3)

Occurs if the Pressure Diff. Control alarm is enabled, and the respective sensor is at the low end of the count range.

Vessel X - Pump A, B, C or D Lo Side Press. Sensor Fault (3)

Occurs if the Pressure Diff. Control alarm is enabled, and the respective sensor is at the low end of the count range.

Vessel X - Pump A, B, C or D High Pressure Shutdown

Occurs if the High Pressure Shutdown feature is enabled, the pump is running, and the high side pump pressure is greater than the High Pressure Shutdown setpoint for the time delay.

Vessel X - Refrigerant Level Sensor Fault (3)

Occurs if the digital count for the respective sensor is at the low end of the count range.

Page 40: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 40

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

Page 41: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 41

QUANTUM™ HD UNITYEVAPORATOR OPERATION

SECTION 6 - EVAPORATOR CONTROL

Page 42: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 42

QUANTUM™ HD UNITYEVAPORATOR OPERATION

Introduction

Evaporator Control provides monitoring and control for the following:

• Cooling & Defrost Control – Control cooling and defrost for up to 30 zones across 10 remote I/O panels.

• Dehumidification Control – Run additional cooling to draw excess moisture out of the space.

• Heating and Re-heating Control – Used for more complex space conditioning requirements.

• Load Shedding – Take evaporators off-line or set to a higher control setpoint/mode during periods of higher energy costs.

Select Evaporator control by touching anywhere in the Evaporator control block on the System Overview page or selecting from the drop down if on another control page such as Condenser.

Evaporator Overview Page shows all enable Evaporators with basic operational status. Select a particular Evaporator by touching the Select Zone and selecting the appropriate zone. Up to 15 zones will be displayed in 2 columns on this page for a total of 30.

The Evaporator home page illustrates all the pertinent oper-ating data on the left side of the page and operational status and interactive control buttons on the right. A System Oper-ating Values area is in the lower left of the page. This is used to display non-standard analog values that may be configured and read by the system.

Main Menu & Navigation

Home – Returns the user to the Evaporator home page

Alarms – Displays current and historical alarms as well as freeze data for each alarm

Calibration – Calibration for all enabled analog inputs

Configuration – Configuration for all operational features such as refrigerant detection, ventilation and floor warming

About – Displays all software information for the processor, interface, analog and digital boards

Status – Displays current status of the analog and digital I/O, serial comm. Ports 1-3, I/O comms., Modbus TCP and Ether-net I/P

Service – Diagnostics, software maintenance, security, down-load system data

Logout – Logs out user when session is complete

Page 43: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 43

QUANTUM™ HD UNITYEVAPORATOR OPERATION

ACCESSING:

ACCESSING:

EVENTS:

The “Events” page displays record-ed events such as power down and power up times. Touch the Next button in the lower right to view earlier events that do not appear on this screen.

TRENDING:

The “Trending” page displays his-torical data and provides a means to “Select Data To Trend”, the read “Interval” and Download Trend-ing Data. A USB Thumb Drive must be inserted into the respective controller USB port to Download System Data.

Trending Sub-menus

Select Data To Trend - Select Data to be trended from the list shown when the “Select Data To Trend” button is pushed. Each Evaporator will have it’s own trending page.

Interval - Change the read interval by touching the “Inter-val” setpoint box, select the desired value using the on-page keypad and press Enter.

Download Trending Data - Download Trending Data, plug in a flash drive/thumb drive (configured for FAT32). Once the drive is detected touch the “Download Trending Data” button on the trending page.

Download Trending Data can also be done by a networked computer, tablet or smartphone that has the ability to save and open Excel spreadsheets.

Page 44: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 44

QUANTUM™ HD UNITYEVAPORATOR OPERATION

ACCESSING:

ABOUT:

The “About” page lists the software and firmware version for the pro-cessor, interface, analog and digital boards. It also lists the Sales Order and Item numbers.

ACCESSING:

STATUS:

The Status page displays the real time status of the analog and digital I/O, serial comm. ports 1-3, I/O comms., Modbus TCP and Ethernet I/P.

Page 45: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 45

QUANTUM™ HD UNITYEVAPORATOR OPERATION

ACCESSING:

ALARMS:

The Alarms page displays current and historical alarms as well as freeze data for each alarm. Alarm Silence or Clear All alarms from this page. Freeze Data Selection is also initiated from this page. View earlier alarms by pressing the Next button.

ACCESSING:

CALIBRATION:

The Calibration page is used to calibrate all enabled analog inputs, analog auxiliaries and analog out-puts.

Calibration Sub-menus

Calibration – Enter the value for the device being calibrated into the Current Value box for that device. The Offset value will automatically calculate and populate that cell. Offsets can also be zeroed which will change the Current Value accord-ingly. Each Evaporator has a calibration page. Other pages include ammonia, kW, auxiliaries and outputs (analog).

From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled in the same manner. To Calibrate an analog output requires a calibrated meter that can read a milliamp (mA) signal.

To calibrate an analog output for a 4-20mA or 0-20mA do the following from the Output calibration page.

• Select the Analog Board and Channel for the output to be calibrated.

• Attach the black lead to the negative terminal and the red probe to the positive terminal for the channel to be cali-brated.

• Set the calibrated meter to read DC mA

• Select Calibrate Low End and use the + and – value buttons of various change values to calibrate to the desired value of 0 or 4 mA.

• Select Calibrate High End and use the + and – buttons of various change values to calibrate the high end to 20 mA.

Page 46: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 46

QUANTUM™ HD UNITYEVAPORATOR OPERATION

ACCESSING:

CONFIGURATION: The Configuration page/menu is used to access main areas of configuration such as Zone En-able, Refrigerant Detection, Zone Functions, Zone Cooling, Defrost, Dehumidification, Heating and Re-heating control, Digital and Analog Auxiliaries, Communications, P/I Control, Digital and Analog I/O.

Configuration Sub-menus

Configuration to enable evaporator zones, refrigerant detec-tion, zone function, zone cooling & defrost, zone heating, load shedding, digital and analog I/O are covered on the fol-lowing pages. Common configuration items such Digital Aux-iliaries, Analog Auxiliaries, Communications and Proportional Integral Control are covered in their respective sections.

Global Zone Configuration – Enable and name up to 30 zones along with defrost grouping, control input selection (entering temp, room temp or user defined temp). User defined naming of the of the user defined temp is done on this page.

Defrost Groups – Up to 10 defrost groups can be configured to better manage the number of units in any one area that are in defrost at the same time.

Global Refrigerant Detection – Name up to 30 refriger-ant detection points with alarm and shutdown values with delays. Up to three refrigerant detection sensor/inputs can be enabled per zone or multiple zones can use the same sensor/input. This is selectable in Zone Function Configuration.

Zone Function Configuration – Enable all zone functions on this page to include cooling, soft hot gas, dehumidification, defrost, heating and reheat. Enable up to 4 modes (capac-ity control setpoints). Configure all valve functions/actions and select refrigerant sensors associated with this zone. If enabled the Dehumidification and reheat setpoints are on the Zone Cooling Modes page and Heating setpoints are on the Zone Heating Modes page.

Page 47: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 47

QUANTUM™ HD UNITYEVAPORATOR OPERATION

Dehumidification – Requires an RH% humidity input. If the humidity level is above the on setpoint, cooling (liquid and fan) are turned on even if below their respective off setpoints to remove the non-wanted moisture from the space. A low temp. override setpoint will turn the liquid and fan off to prevent the space from getting too cold.

Reheat – This feature is used in conjunction with de-humid-ification where there is a dedicated reheat coil within the complete coil bundle. This is used to add heat to the space to prevent the space temperature from dropping to low while the cooling coil removes the non-wanted moisture from the space.

Heating – This feature is used to heat a space using hot gas in the main coil. The process of shifting from cooling to heat-ing and back to cooling is essentially the same as when going into and coming out of defrost.

Zone Cooling Modes – Configure each enable mode for each zone for Liquid.

Liquid - Liquid can be by solenoid control or modulating valve control if enable in zone function configuration. I configured for modulation valve additional setpoints for the P/I control of that valve are listed in the liquid section. If not enable only the liquid On and Off setpoints are present.

Fan – The fan can be configured a fixed speed or VSD fan. If fixed only a fan On and fan Off setpoint will be listed in the fan section. If fan cycling is enable in zone function setpoints to cycle the fan On for a period of time and a user defined interval will also appear. If selected as VSD fan as shown hereadditional setpoints for the P/I control will appear.

Alarm – Low and high temperature warning values with de-lays and mode switch delay.

Dehumidification/Reheat – These two features work together to remove unwanted moisture from the space while not allowing the space to get too cold. Requires a special coil within a coil or a secondary coil for the reheat process.

Zone Defrost – Standard defrost timer settings for pump out, soft hot gas, hotgas, bleed, fan delay are provided. If fan is VSD a pump out fan sped setpoint is provided. Initiate defrost from schedule, liquid timer, schedule w/liquid override. De-frost can also be iniated on demand by enabling the feature and energizing the demand defrost digital input.

Power Outage During Defrost – If a power outage occurs during defrost the controller will move straight to the bleed stage on power up to avoid any vapor propelled liquid slug-ging from occurring.

Hot Gas Warning – monitors the evaporator pressure when the hot gas is on to be ensure adequate pressure for defrost. There is also a warning for high pressure. Either a low or high Hot Gas Warning could indicate a problem with the back pressure regulator during defrost. Requires a pressure trans-ducer to read the evaporator pressure.

Manual Defrost Control – is initiated on the zone’s home screen. Once initiated, a service level operator can advance the stages in a manual defrost from the Zone Defrost page.

Defrost Schedule – Up to 8 defrosts can be scheduled per zone per day. The schedule of one day can be easily copied to other days by selecting the day to be copied from and the days to be copied to and touch the copy button.

Zone Heating Modes – Setpoints on this are used to transi-tion to heating mode, control in heating mode and transition back to cooling mode. Heating is an operation of using hot gas to heat a space as needed. Other than the initiation pro-cess, the transition to heating and back to cooling are similar to that of defrost. Fan setpoints are similar to that of cooling.

Page 48: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 48

QUANTUM™ HD UNITYEVAPORATOR OPERATION

Load Shedding – Provides a means of reducing system load during certain periods where it is advantageous to do so. This could be during higher rate periods or anytime when the fly-wheel effect will sustain the requirements for the space and product. Units can either be turned off by setting the mode to 0 (zero) or to a higher temperature setting by selecting the mode associated with that setting. An override temp will pre-vent the space from getting too warm. If the unit has a VSD fan, it’s speed during load shed is set on this page.

In and Out of Load Shed Sequence – Is set by the % Differ-ential value that proportionally compares the actual tempera-ture to the difference between the liquid On setpoint and the Override temperature for each zone. Colder units with the lower % differential values go into load shedding first while warmer units with higher % Differential values come out of load shedding first. Any unit that exceeds the Override Temp. comes out of load shedding at that point.

Load Shedding can be initiated manually, by schedule, kW reading or a combination of schedule and kW reading as shown here. Three timed schedules can be set per day. If the kW reading is above the start kW value and within the set start and stop period, load shedding will commence and stay in load shedding until the scheduled stop or the kW value drops below the stop value.

The “Source of kW Reading” is the controller from which a plant wide value can be read, Engine Room Controller or Evaporator Controller. kW control will require a kW meter to be wired into the analog board of the engine room or one of the evaporator zones. The input from this meter should represent the entire plant load or at least the entire refrigera-tion system load.

Zone Digital I/O Configuration – Used to configure standard Condenser Control digital I/O by board and channel as well as display current status. Non-standard items can be config-ured for monitoring, alarms and control in Digital Auxiliaries configuration. There 2 pages to cover each zone of evapora-tor control.

Global Digital I/O Configuration – Global Digital I/O are for the configuration of global evaporator system control outputs. Two commonly used outputs are Main Hot Gas and Main Liquid which can be turned off in the event of a Refrigerant Detection shutdown.

Zone Analog I/O Configuration (inputs and Outputs) – Used to configure standard Evaporator Control analog inputs by sensor range (low/high), sensor type, board and channel. Non-standard items can be configured for monitoring, alarms and control in Analog Auxiliaries configuration. Also configure analog outputs for each zone for VSD Fan and Modulating Liquid Valve.

Page 49: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 49

QUANTUM™ HD UNITYEVAPORATOR OPERATION

Global Analog I/O Configuration – Used to configure non-zone specific analog input channels that can be used anywhere in the evaporator system. As an example one NH3 sensor can be linked to all zones for refrigerant detection warning and shutdown. This is where a kW meter input would be config-ured to read to kW load.

Digital Auxiliaries

Digital Auxiliary Inputs – Digital Auxiliary inputs can be con-figured to expand the operation and control of the Quantum HD Unity System Controller beyond that which is standard. They allow the operator to configure additional safeties based on the status of other system components. These can be configured as warning when running, warning always, shutdown when running or shutdown always. The text can be user defined.

Digital Auxiliary Outputs – Digital Auxiliary outputs can be configured to expand the operation and control of the system by configuring digital outputs to energize and de-energize based on an analog value (control Input) relative to the On When and Off When values.

Analog Auxiliaries

Analog Auxiliary Inputs – Can be configured to expand the control and operation of the Evaporator control.

Channel Configuration – Set the Name, I/O Board, Channel and Sensor Output

Sensor Configuration – Displays current value, select Sen-sor Type and set the low range and high range limits of the sensor

Safety Configuration – Configure the safety for when active along with low and high end safeties and their delays.

Communications

Ethernet – Enable one or both of the Ethernet Protocols de-pendent on the integration

Serial – Configure the serial comm port relative to the master device protocol, baud rate etc… Evaporator control has just comm 1 and comm 2 available for external comms. Coms 3 & 4 are used for the I/O comms between the controller and the remote units.

Page 50: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 50

QUANTUM™ HD UNITYEVAPORATOR OPERATION

Map File – Provides a means to download the Quantum HD Map File of addresses for the purpose of grouping items and uploading these groups. This allows an integrator to grab chunks of data with one query rather than many single item queries.

You must have a USB thumb drive plugged into the appro-priate controller prior to touching the Download Map File button.

Proportional Integral Control

P/I Control – P/I controls expands the operation and control of the Quantum HD Unity System Controller by controlling ancillary modulating devices based on the value of analog input signal

Name: User Defined

Control Input: Select the analog value to be used for the control.

Control: Select between the following option relative to the control.

Engine Room: Disabled, Enabled

Condenser: Disabled, Enabled

Vessel: Disabled, Enabled

Evaporator: Disabled, Running, Always, Heating, Cooling, De-frost (running = anytime unit is Active or not Off as shown)

P/I Configuration – Set Action for Forward for the input to increase if the actual value is above the setpoint and Reverse for the output to increase when the actual value is below the setpoint. Set all control setpoints, along with board and channel for the output.

NOTICEMay require calibrating of the analog output channel, covered in the calibration section for each control.

ACCESSING:

SERVICE:

The Service page is for Diagnostics, Communications Testing, Software Maintenance, Ethernet Integrity, System Data Downloads and I/O Integrity.

Page 51: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 51

QUANTUM™ HD UNITYEVAPORATOR OPERATION

ACCESSING:

CLEAN SCREEN:

Clean Screen disables the screen for cleaning purposes. Timeout is displayed on the page.

Evaporator AlarmsThere may be up to 30 evaporator zones enabled per evaporator control system. The following alarms

can be received (individually) for each enabled zone relative to its individual configuration.

Analog Aux Low Warning (1)

Occurs if the warning is enabled on Analog Aux Input A – J and the respective analog input reading is less than or equal to the low setpoint for the time delay.

Analog Aux High Warning (1)

Occurs if the warning is enabled on Analog Aux Input A – J and the respective analog input reading is greater than or equal to the low setpoint for the time delay.

Analog Aux Low Shutdown (1)

Occurs if the shutdown is enabled on Analog Aux Input A – J and the respective analog input reading is less than or equal to the low setpoint for the time delay.

Analog Aux High Shutdown (1)

Occurs if the shutdown is enabled on Analog Aux Input A – J and the respective analog input reading is greater than or equal to the high setpoint for the time delay.

Digital Aux Input Shutdown (digital aux input a-e) (2)

Occurs if the warning is enabled on Digital Aux Input A – E and the respective input is de-energized for the time delay.

Digital Aux Input Shutdown (digital aux input a-e) (2)

Occurs if the warning is enabled on Digital Aux Input A – E and the respective input is de-energized for the time delay.

Consecutive Defrost Warning

Occurs if the number of consecutive defrosts goes above the Maximum Consecutive Defrosts setpoint.

Max Days Between Defrosts Exceeded Warning

Occurs if demand defrost is enabled and defrost does not occur for the time determined by the Max Hours Between Defrosts setpoint.

Fan Auxiliary Shutdown

Occurs if Fan Auxiliary is enabled, the fan is on and the fan auxiliary input is de-energized for the time delay.

Low Evaporator Pressure Warning

Occurs if the Hot Gas Warning is enabled, the hot gas is on, the Low Evaporator Pressure Warning Ignore Period is not active, and the evaporator pressure is below the Low Evaporator Pressure Warning setpoint for the time delay

High Evaporator Pressure Warning

Occurs if the Hot Gas Warning is enabled and the evaporator pressure is above the High Evaporator Pressure Warning setpoint for the time delay.

Low Temperature Warning

Occurs if the control temperature is below the Low Temperature Warning setpoint for the time delay.

High Temperature Warning

Occurs if the control temperature is above the High Temperature Warning setpoint for the time delay.

High Humidity Warning

Occurs if the humidity reading is above the High Humidity Warning setpoint for the time delay.

Smoke Detector Shutdown

Occurs if the Smoke Detector input is configured and the input is de-energized for the time delay.

Entering Temperature Sensor Fault (3)

Occurs if the if the digital count for the respective sensor is at the low end of the count range.

Room Temperature Sensor Fault (3)

Occurs if the if the digital count for the respective sensor is at the low end of the count range.

Page 52: FRICK QUANTUM HD UNITY SYSTEM CONTROLLER · 2020. 2. 11. · Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c Please check

090.670-O (AUG 2015)Page 52

QUANTUM™ HD UNITYENGINE ROOM/CONDENSER/VESSEL/EVAPORATOR OPERATION

JOHNSON CONTROLS100 CV AvenueWaynesboro, PA 17268-1206 USAPhone: 717-762-2121 • FAX: 717-762-8624www.jCI.com/frick

Form 090.670-O (2015-08)Supersedes: NOTHING

Subject to change without noticePublished in USA • 08/15 • PDF

© 2015 Johnson Controls Inc. - ALL RIGHTS RESERVED

SENSOR FAULT COUNT RANGESensor Type Low End Count High End Count

ICTD (temperature) 1597 3505RTD (temperature 1100 40851-5v or 2-10v or

4-20mA <614 No Upper Limit

Note: Sensor faults are not provided for these sensor types: 0-5v, 0-10v or 0-20mA.

1. Analog Aux Inputs A-J may be custom named by user.2. Digital Aux Inputs A-E may be custom named by user.3. See the count range table for various sensor types.

User Defined Temperature Sensor Fault (3)

Occurs if the if the digital count for the respective sensor is at the low end of the count range.

Humidity Sensor Fault (3)

Occurs if the if the digital count for the respective sensor is at the low end of the count range.

The following safeties are not zone specific as one refrigerant detector can be configured on multiple zones. There are up to 30 refrigerant detectors that can be selected from. The warning and/or shutdown:

Ammonia Input X Warning (X = 1 to 30)

Occurs if the warning is enabled and the input reading is greater than or equal to the Ammonia Warning setpoint for the time delay.

Ammonia Input X Shutdown (X = 1 to 30)

Occurs if the shutdown is enabled and the input reading is greater than or equal to the Ammonia Shutdown setpoint for the time delay.

Ammonia Input X Sensor Fault (X = 1 to 30)

Occurs if the if the digital count for the respective sensor is at the low end of the count range. See the count range for various sensor types below.

Each Evaporator system can have up to 5 analog boards on Comm 3 and 5 analog boards on Comm 4.

Analog Board 1-5 Comm 3 Comms Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Analog Board 1-5 Comm 4 Comms Shutdown

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Each Evaporator system can have up to 10 digital boards on Comm 3 and 10 digital boards on Comm 4. For both Comm 3 and 4, boards 1-5 represent digital board 1 in each of the 5 remote I/O panels. Boards 6-10 represent digital board 2 in each of the 5 remote I/O panels (both Comm 3 and 4).

Digital Board 1-10 Comm 3 Reset

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 1-10 Comm 4 Reset

Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds.

Digital Board 1-10 Comm 3 Comms Shutdown

Occurs if the processor does not communicate with the respective digital board for a period of 5 seconds.

Digital Board 1-10 Comm 4 Comms Shutdown

Occurs if the processor does not communicate with the respective digital board for a period of 5 seconds.


Recommended