+ All Categories
Home > Documents > Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0...

Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0...

Date post: 12-Jul-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
58
M2x3 & I500 Communications Manual Communications Manual iSTAT M2x3 & I500 Publication Reference: M2x3C+I500C/EN/M/D M2x3C+I500C/EN/M/D © 2014. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. GRID
Transcript
Page 1: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3 & I500 Communications Manual

Communications Manual

iSTAT M2x3 & I500

Publication Reference: M2x3C+I500C/EN/M/D

M2x3C+I500C/EN/M/D © 2014. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names

mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only.

Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to

the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or

change this data at any time without further notice.

GRID

Page 2: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.
Page 3: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 1

CONTENT

1. COMMUNICATIONS SETUP 3

1.1 Setup communications on the M2x3 and I500 3 1.2 Ethernet 3 1.2.1 Using Fixed IP address 3 1.3 Ethernet (XPort) communication 3

2. MODBUS INFORMATION 6

2.1 introduction 6 2.2 Transactions 6 2.3 Request 6 2.4 Response 6 2.5 Request - response cycle example 6 2.5.1 Request Frame 7 2.5.2 Response Frame 7 2.6 Framing 7 2.7 RTU framing 7

3. MODBUS SUPPORTED FUNCTIONS AND USAGE 8

3.1 03 read from holding registers 8 3.1.1 Request Frame 8 3.1.2 Response Frame 8 3.2 04 read from input registers 8 3.2.1 Request Frame 8 3.2.2 Response Frame 9 3.3 06 write to a single holding register 9 3.3.1 Request Frame 9 3.3.2 Response Frame 9 3.4 16 (10 HEX) write to one or more registers 9 3.4.1 Request Frame 9 3.4.2 Response Frame 10 3.5 17 (11HEX) report slave id 10 3.5.1 Request Frame 10 3.5.2 Response Frame 10 3.6 77 (4D HEX) read measurement string 10 3.6.1 Request Frame 10 3.6.2 Response Frame 10 3.6.3 Value Codes 11 3.7 82 (52 HEX) re-read output buffer 12

Page 4: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 2 iSTAT M2x3 & I500 Modbus & DNP3.0

3.7.1 Request Frame 12 3.7.2 Response Frame 12

4. MODBUS ERROR RESPONSES 13

4.1 Exception codes 13

5. MODBUS REGISTER MAPS 14

6. MODBUS DATA FOR M2X3 AND I5MT/MR/MQ 15

6.1 SYSTEM DATA 15 6.2 MEASUREMENTS 17 6.3 NORMALIZED MEASUREMENTS 27 6.4 MEASUREMENTS (IEEE 754) 29 6.5 OUTTYPES 32 6.6 MODBUS DATA TYPES 39

7. MODBUS DATA FOR I5MC/MV/MS/ML 42

7.1 MEASUREMENTS 42 7.2 NORMALISED MEASUREMENTS 43 7.3 MEASUREMENTS (IEEE 754 ) 45 7.4 PRODUCT SETTINGS 46 7.5 MODBUS DATA TYPES 46

8. DNP3.0 PROGRAMMING FOR M2X3 AND I5MT/MR/MQ 48

8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52

9. RELATED DOCUMENTS 54

Page 5: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 3

1. COMMUNICATIONS SETUP

The Setup of the communications on the I500 or M2x3 is achieved using the QDSP configuration software. QDSP can communicate with the iSTAT products via RS232, RS485, USB and Ethernet. The option used will depend on which communication port is fitted to the product.

The QDSP software always uses Modbus protocol to communicate with the product.

1.1 Setup communications on the M2x3 and I500

The setup of the communication ports is done using the QDSP software and is detailed in a separate manual.

It is suggested that the communications channel for the product required by the application is initially set up using QDSP running on a PC. Then when that is working correctly the product can be connected to the required intelligent device.

1.2 Ethernet

When using the QDSP over Ethernet the set-up will depend on how the PC and the product are connected. The Communication interface must have a unique IP address in the Ethernet network. Two modes for assigning IP are available:

Fixed IP address: In most installations a fixed IP address is required. A system provider usually defines IP addresses. An IP address should be within a valid IP range, unique for your network and in the same Subnet mask as your PC.

DHCP: Automatic method of assigning IP addressed (DHCP) is used in most networks. If you are not sure if DHPC is used in your network, check it with your system provider.

1.2.1 Using Fixed IP address

When the PC is directly connected to the Instrument a Fixed IP address will have to be used with the PC configured in the local area connection. If the connection is made without a Hub or Switch, the connection has to be made with a Crossover Ethernet cable.

There are 2 types of Ethernet interfaces used on the M2x3 and i500.

Standard Ethernet interface, which is usually supplied along with a USB port which can be used to set the IP address.

An older XPORT interface (only early M2x3) which requires Lantronix software to be able to set the IP address. See section 1.3.

The IP address for both interfaces can also be set using the keypad/display on the M2x3.

1.3 Ethernet (XPort) communication

QDSP does not allow the setting of Local Port etc. on Ethernet (XPORT) devices (only early M2x3). If required these can be accessed using an internet browser.

Any internet browser available can be used to access the interface in the product, type in the IP address of the product as the required internet address.

The browser will communicate with the instrument and then display a request for password; press OK without entering a password and the ‘XPORT’ screen will be displayed.

Page 6: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 4 iSTAT M2x3 & I500 Modbus & DNP3.0

Select <Server> to display Network settings where ‘Subnet Mask’ and ‘Default Gateway’ can be modified if required.

Select <Channel 1 - Connection> to show connection settings, where ‘local port’ can be modified.

Page 7: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 5

No other settings need to be changed.

When changes are complete select <Apply settings>

After downloading the settings it is necessary to reset the M2x3 device to make the changes active.

Page 8: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 6 iSTAT M2x3 & I500 Modbus & DNP3.0

2. MODBUS INFORMATION

2.1 introduction

The Modbus protocol is a widely supported open interconnect protocol originally designed by Modicon that can be enabled on the M2x3 and I500 via RS232, RS485, USB or Ethernet communication.

There are two Modbus protocol types: Modbus RTU for serial communication (and USB) and Modbus TCP for Ethernet communication. It is also possible to pass Modbus RTU communications over Ethernet.

On Serial Communication, Modbus is a single master multiple slave protocol suitable for a multi-drop configuration as provided by the RS485 connection. Up to 32 devices can be connected in this way. Single - drop RS232 or USB connection is also possible.

2.2 Transactions

Communication operates on a master-slave basis where only one device (the master) can initiate transactions called 'Requests'. The other devices (slaves) respond by supplying the requested data to the master. This is called the 'Request - Response Cycle'.

Master to slave request:

Device address Function Code nx8 bit data bytes Error check

Slave to master response:

Device address Function Code nx8 bit data bytes Error check

2.3 Request

This Master to Slave transaction takes the form:

Device address: Master addressing a slave (Address 0 is used for the broadcast address, which all slave devices recognise.).

Function code: E.g. 04 ask the slave to read its Input Registers and respond with their contents.

Data bytes: Tells the slave which register to start at and how many registers to read.

2.4 Response

This Slave to Master transaction takes the form:

Device address: To let the master know which slave is responding.

Function code: This is an echo of the request function code.

Data bytes: Contains the data collected from the slave.

2.5 Request - response cycle example

Ia 160.00 A = 16000* 10-2 A

Data type “T3” 32 bit unsigned

FE 00 3E 80(16)

Data held in Modbus addresses

30036(10) & 30037(10) 30036(10) - 30000(10) = 36(10) � 00 24(16)

Page 9: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 7

2.5.1 Request Frame

Starting Register Register Count CRC

Slave Address HI LO

Function code HI LO LO HI

21 04 00 24 00 02

2.5.2 Response Frame

Register Data CRC

Slave Address LO HI

Function code Byte Count HI LO HI LO

21 04 04 FE 00 3E 80

2.6 Framing

There are two types of message framing for the serial communications, ASCII or RTU. iSTAT products supports RTU framing.

2.7 RTU framing

In RTU mode, messages start and end with a silent interval of at least 3.5 character times (t1-t2-t3-t4 as shown below).

The advantage of this mode of framing is that it enables a greater character density and a better data throughput. However, each message must be transmitted in a continuous stream. If a silent interval of more than 1.5 character times occurs before completion of the frame, the device flushes the incomplete message and assumes that the next byte will be the address field of a new message.

Start Address Function Data CRC Check End

t1-t2-t3-t4 8 bits 8 bits n x 8 bits 16 bits t1-t2-t3-t4

The Cyclic Redundancy Check (CRC) field is two bytes, containing a 16 bit binary value. The CRC value is calculated by the transmitting device, which appends the CRC to the message. The receiving device recalculates a CRC during receipt of the message, and compares the calculated value to the actual value it received in the CRC field. If the two values are not equal an error results. The CRC-16 calculation is an industry standard method used for error detection.

One frame is transmitted as 1 start bit, 8 data bits and 2 stop bit. If parity is selected then the frame is transmitted as 1 start bit, 8 data bits, and 1 stop bit.

Where n > 1 data is transmitted most significant byte first.

The CRC check is transmitted least significant byte first.

Page 10: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 8 iSTAT M2x3 & I500 Modbus & DNP3.0

3. MODBUS SUPPORTED FUNCTIONS AND USAGE

Code Code Function References

DEC HEX

3 03 to read from holding registers (4XXXX memory references)

4 04 to read from input registers (3XXXX memory references)

6 06 to write to a single holding register (4XXXX memory references)

16 10 to write to one or more holding registers (4XXXX memory references)

17 11 report slave ID 6 characters

77 4D read measurement string 1 byte value code (request)

82 52 re-read output buffer Use after broadcast request

3.1 03 read from holding registers

Reads the binary content of holding registers (4X references) in the slave. Broadcast is also supported.

3.1.1 Request Frame

The query message specifies the starting register and quantity of registers (1 to 28) to be read. Registers are addressed starting at zero.

Here is an example of a request to read registers 40009 ... 40010 from slave device 33:

Starting Register Register Count CRC

Slave Address Function Code HI LO HI LO LO HI

21 03 00 09 00 02

3.1.2 Response Frame

The register data in the response message is packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits.

Data is scanned in the slave at the rate of 28 registers per scan. The response is returned when the data is completely assembled.

Here is an example of a response to the query:

Register Data CRC

Slave Address Function Code Byte Count HI LO HI LO LO HI

21 03 04 75 03 42 15

The contents of registers 40009 ... 40010 are 75 03 and 42 15 hex.

3.2 04 read from input registers

Reads the binary content of input registers (3X references) in the slave. Broadcast is also supported

3.2.1 Request Frame

The query message specifies the starting register and quantity (1 to 28) of registers to be read. Registers are addressed starting at zero.

Here is an example of a request to read registers 30036 ... 30037 from slave device 33:

Starting Register Register Count CRC

Slave Address Function Code HI LO HI LO LO HI

21 04 00 24 00 02

Page 11: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 9

3.2.2 Response Frame

The register data in the response message is packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits.

Data is scanned in the slave at the rate of 28 registers per scan. The response is returned when the data is completely assembled.

Here is an example of a response to the query:

Register Data CRC

Slave Address Function Code Byte Count HI LO HI LO LO HI

21 04 04 FE 00 3E 80

The contents of registers 30036 ... 30037 are FE 00 and 3E 80 hex.

3.3 06 write to a single holding register

Pre-sets a value into a single holding register (4X reference). When broadcast, the function pre-sets the same register reference in all attached slaves.

3.3.1 Request Frame

The query message specifies the register reference to be pre-set. Registers are addressed starting at zero; register 1 is addressed as 0.

Here is an example of a request to pre-set register 40010 to 42 15 hex in slave device 33:

Register Address Register Data CRC

Slave Address Function Code HI LO HI LO LO HI

21 06 00 0A 42 15

3.3.2 Response Frame

The normal response is an echo of the query, returned after the register contents have been pre-set. Here is an example of a response to the query:

Register Address Register Data CRC

Slave Address Function Code HI LO HI LO LO HI

21 06 00 0A 42 15

3.4 16 (10 HEX) write to one or more registers

Pre-sets values into a sequence of holding registers (4x references). When broadcast the function pre-sets the same register references in all attached slaves.

3.4.1 Request Frame

The query message specifies the register references to be pre-set. Registers are addressed starting at zero; register 1 is addressed as 0. Here is an example of a request to pre-set two registers starting at 40000 to 41 42 and 43 44 hex (Enter Password ABCD), in slave device 33:

Starting Register

Register Count

Register

Data CRC Slave

Address Function

Code HI LO HI LO

Byte

Count HI LO HI LO LO HI

21 16 00 00 00 02 04 41 42 4344

Page 12: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 10 iSTAT M2x3 & I500 Modbus & DNP3.0

3.4.2 Response Frame

The normal response returns the slave address, function code, starting address, and quantity of registers pre-set. Here is an example of a response to the query shown above.

Starting Register Register Count CRC Slave

Address

Function

Code HI LO HI LO LO HI

21 16 00 00 00 02

If the password is not correct (L1 or L2 or BP), the response to the query is:

Starting Register Register Count CRC Slave

Address

Function

Code HI LO HI LO LO HI

21 16 00 00 00 02

3.5 17 (11HEX) report slave id

Returns a description of the type of controller present at the slave address.

3.5.1 Request Frame

Here is an example of a request to report the ID of slave device 33:

CRC

Slave Address Function Code LO HI

21 11

3.5.2 Response Frame

The format of a normal response is shown below:

Register Data CRC Slave Address Function Code Byte Count

HI LO HI LO HI LO LO HI

21 11 06 20 4D 30 32 32 30

3.6 77 (4D HEX) read measurement string

Reads the measurement value as an ASCII string. Broadcast is also supported. See list of value codes in section 4.6.3

3.6.1 Request Frame

The query message specifies the value code of the measurement to be read.

Here is an example of a response to read Total Real Power from slave device 33:

CRC Slave

Address

Function

Code

Value Code

LO HI

21 4D 04

3.6.2 Response Frame

The ASCII string in the response message is packed as data bytes. The quantity of data bytes depends on the value code.

Here is an example of the query:

String Data CRC Slave

Address

Function

Code

Byte Count

1. 2. 3. 4. 5. 6. 7. 8. LO HI

21 4D 08 2B 32 31 2E 31 33 35 6B 49 35

Page 13: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 11

3.6.3 Value Codes

The value codes are described in the following table:

Value Code DEC

Value Code Hex

Measurement Value Byte Count

Example String Data

00 00 Energy counter 1 15 "0000004.46kWh"

01 01 Energy counter 2 15 "0000001.24kvarh"

02 02 Energy counter 3 15 "0000005.71kWh"

03 03 Energy counter 4 15 "0000002.86kvarh"

04 04 Total Real Power 8 "+21.135k"

05 05 A Phase Real Power 8 "+7046.3"

06 06 B Phase Real Power 8 "+7037.3"

07 07 C Phase Real Power 8 "+7051.1"

08 08 Total Reactive Power 12 "1208.7 var L"

09 09 A Phase Reactive Power 12 "0400.2 var L"

10 0A B Phase Reactive Power 12 "0406.4 var L"

11 0B C Phase Reactive Power 12 "0400.9 var L"

12 0C Total I 7 "93.671"

13 0D IA 7 "31.227"

14 0E IB 7 "31.222"

15 0F IC 7 "31.222"

16 10 Average V 7 "226.06"

17 11 VA 7 "226.08"

18 12 VB 7 "225.83"

19 13 VC 7 "226.27"

20 14 Total Apparent Power 7 "21.170k"

21 15 A Phase Apparent Power 7 "7057.3"

22 16 B Phase Apparent Power 7 "7049.0"

23 17 C Phase Apparent Power 7 "7062.8"

24 18 Total Power Factor 8 "+0.998 L"

25 19 Power Factor A 8 "+0.998 L"

26 1A Power Factor B 8 "+0.998 L"

27 1B Power Factor C 8 "+0.998 L"

28 1C Frequency 7 "46.008"

29 1D Frequency 7 "46.008"

30 1E Frequency 7 "46.008"

31 1F Frequency 7 "46.008"

32 20 Total Power Angle 7 "+003.26"

33 21 Power Angle A 7 "+003.25"

34 22 Power Angle B 7 "+003.30"

35 23 Power Angle C 7 "+003.25"

Page 14: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 12 iSTAT M2x3 & I500 Modbus & DNP3.0

Value Code DEC

Value Code Hex

Measurement Value Byte Count

Example String Data

36 24 IN 6 "93.67"

37 25 Angle AB 7 "+000.00"

38 26 Angle BC 7 "+000.01"

39 27 Angle CA 7 "-000.01"

40 28 Average Vxy 6 "000.3"

41 29 VAB 6 "000.2"

42 2A VBC 6 "000.24"

43 2B VCA 6 "000.2"

44 2C Dynamic Demand Value 1 13 "Pt=+9.818kW"

45 2D Dynamic Demand Value 2 12 "Qt=6.504kvar"

46 2E Dynamic Demand Value 3 12 "St=12.89kVA"

47 2F Dynamic Demand Value 4 12 "It=56.91 A"

48 30 Max Demand Since Reset 1 13 "Pt=+11.26kW"

49 31 Max Demand Since Reset 2 12 "Qt=14.64kvar"

50 32 Max Demand Since Reset 3 12 "St=18.46kVA"

51 33 Max Demand Since Reset 4 12 "It=81.01 A"

52 34 Time Stamp MD 1 12 "03.SEP 14:11"

53 35 Time Stamp MD 2 12 "03.SEP 14:10"

54 36 Time Stamp MD 3 12 "03.SEP 14:10"

55 37 Time Stamp MD 4 12 "03.SEP 14:12"

3.7 82 (52 HEX) re-read output buffer

This function should be used after the broadcast request. The addressed slave transmits the response frame of the previous request.

3.7.1 Request Frame

Here is an example of a request to re-read the output buffer of slave device 33:

CRC

Slave Address Function Code LO HI

21 52

3.7.2 Response Frame

The response to the query depends on the previous function code.

Page 15: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 13

4. MODBUS ERROR RESPONSES

When a slave detects an error other than a CRC error, a response will be sent to the master. The most significant bit of the function code byte will be set to 1 (i.e. the function code sent from the slave will be equal to the function code sent from the master plus 128). The following byte will be an exception code indicating the type of error that occurred.

The slave will ignore transmissions received from the master with CRC errors.

An example of an illegal request and the corresponding exception response is shown below. The request in this example is to read registers 0201H to 0209H. If these addresses are not supported in the slave then the following occurs:

Request Message

Starting Register Register Count

Address Function Code HI LO HI LO CRC

01 01 02 01 00 08 6D B4

Exception Response Message

Address Function Code Exception Code CRC

01 81 02 C1 91

4.1 Exception codes

Code Name Meaning

01 ILLEGAL FUNCTION The function code transmitted is not one of the functions supported by the slave.

02 ILLEGAL DATA ADDRESSES The data address received in the request is not an allowable value for the slave. Write to password protected registers.

03 ILLEGAL DATA VALUE The value referenced in the data field transmitted by the master is not within family for the selected data address. The register count is greater than 28 (functions 03 and 04).

06 SLAVE DEVICE BUSY The slave is engaged in processing a long duration program command. The master should re-transmit the message later when the slave is free.

Page 16: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 14 iSTAT M2x3 & I500 Modbus & DNP3.0

5. MODBUS REGISTER MAPS

The Modbus register map consists of the following columns:

Code Function codes as described in Section 3.

Address 16 bit register address starting from zero.

Please Note:

Most Modbus master devices assume that 30001 or 40001 are subtracted from the defined address for the registers. The M2x3 and i500 subtract 30000 and 40000, meaning that the addresses may have to be offset by 1.

Contents Description of parameters assigned to registers.

MODBUS data types T1 etc. are described in section 6.6.

UNSIGNED INTEGER

family 0 ... 65535

one 16-bit register

SIGNED INTEGER family 32768 ... 32767

one 16-bit register

ASCII Family 32…159

16 bit registers (two ASCII codes per register)

Data type

BINARY FLAGS Each bit of a 16 bit register can be used as a binary flag

Indicator Each bit of a 16-bit register can be either assigned as flags or filled with binary data.

Values Definitions of settings, data values and any dependencies that exist between settings.

Register type Declares whether a register is to be read/write register (setting) or a read register (data).

Min, max step The minimum and maximum numerical family and the incremental step size.

Password There is a numerical password that allows save/abort settings and a factory accessible password constructed from the serial number that allows entry/exit to and from the calibration and configuration settings.

Page 17: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 15

6. MODBUS DATA FOR M2X3 AND I5MT/MR/MQ

6.1 SYSTEM DATA

Code Address Contents Data Ind Values and Dependencies

04 30001 30018 Model Number Str_16

04 30009 30012 Serial Number Str_8

04 30013 Software Ref 1 T1 Software version

04 30014 Hardware Ref Str_2 Hardware version

30015 Calibration voltage T4 mV

30016 Voltage auto-range T1 1=auto-range

30017 Calibration current T4 mA

30018 Current auto-range T1 1=auto-range

30019 Accuracy class T17 50 = 0.5%

20 = 0.2%

30020 MiNet Flag T1 0

30021 Language Pack T1

30022 LCD type T1 0 128x64 yellow green

1 128x64 yellow green negative

2 128x64 red negative

30023 Power supply T1 0 Unknown

1 Universal AC 48-276V:

DC 20 – 300V

2 57.64v, 50/60Hz

3 63.5v, 50/60Hz

4 100v, 50/60Hz

5 110v, 50/60Hz

6 230v, 50/60Hz

7 400v, 50/60Hz

8 500v, 50/60Hz

9 Universal AC 48 – 77V:

DC 20 – 100V

10 Universal AC 70 – 276V;

DC 70 – 300V

30024 COM1: communication type T1 0 No communication

1 RS232

2 RS485

3 RS232 & RS485

4 Ethernet (X-Port)

5 Ethernet & USB

6 Ethernet

7 USB

30025 COM2: communication type T1 0 No communication

1 RS232

2 RS485

Page 18: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 16 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

30026 30027 Reserved

30028 Memory type T1 0 No memory

1 2Mb flash

2 4Mb flash

3 8Mb flash

30029 I/O 1 T1 0 No I/O

1 Unipolar analogue output

2 Bipolar analogue output

3 Jumperless analogue output

4 Pulse output

5 Tariff Input

6 Bistable alarm output

7 Relay alarm output

8 Analogue output 20mA

9 Analogue input

10 Digital input

11 Pulse input

12 S0 output

13 Fast Analogue Output

14 Jumperless unipolar Analog output

15 Watch dog output

16 Reserved

17 RS232

18 RS485

19 Reserved

20 COM2 - Ex

30030 I/O 2

30031 I/O 3

30032 I/O 4

30033 30043 Reserved

30044 Status Register (M2x3 only) T1 0 Locked

1 Wrong Connection

2 Low Battery

3 Low Supply

4 Clock not Set

30045 30046 Configuration time stamp T10

30047 30048 Calibration time stamp T10

30049 30050 Last upgrade time stamp T10

30051 Digital input 1 voltage range T1 0 230V

1 63 – 110V

2 48V

30052 Digital input 2 voltage range T1 See Digital input 1

30053 Digital input 3 voltage range T1 See Digital input 1

30054 Digital input 4 voltage range T1 See Digital input 1

Page 19: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 17

Code Address Contents Data Ind Values and Dependencies

30055 30057 Ethernet MAC Address T_Hex6

30058 Ethernet Software Reference T1 Ethernet Software Version

30059 30060 Ethernet IP Address T_Hex4 Actual Ethernet IP Address

30061 30097 Reserved location

30098 Active communications port T1 1 COM1

2 COM2

30099 Modbus max.register read at once

T1

6.2 MEASUREMENTS

Code Address Contents Data Ind Values and Dependencies

ACTUAL MEASUREMENTS

04 30101 30104 Actual time T_Time

04 30105 30106 Frequency T5

04 30107 30108 U1 T5

04 30109 30110 U2 T5

30111 30112 U3 T5

04 30113 30114 Uavg (phase to neutral) T5

04 30115 j12 (angle between U1 and U2) T17

04 30116 j23 (angle between U2 and U3) T17

04 30117 j31 (angle between U3 and U1) T17

04 30118 30119 U12 T5

04 30120 30121 U23 T5

04 30122 30123 U31 T5

04 30124 30125 Uavg (phase to phase) T5

04 30126 30127 I1 T5

04 30128 30129 I2 T5

04 30130 30131 I3 T5

04 30132 30133 INc T5

04 30134 30135 Reserved

04 30136 30137 Iavg T5

04 30138 30139 Σ I T5

30140 30141 Active Power Total (Pt) T6

30142 30143 Active Power Phase L1 (P1) T6

30144 30145 Active Power Phase L2 (P2) T6

30146 30147 Active Power Phase L3 (P3) T6

30148 30149 Reactive Power Total (Qt) T6

30150 30151 Reactive Power Phase L1 (Q1) T6

30152 30153 Reactive Power Phase L2 (Q2) T6

30154 30155 Reactive Power Phase L3 (Q3) T6

Page 20: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 18 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

30156 30157 Apparent Power Total (St) T5

30158 30159 Apparent Power Phase L1 (S1) T5

30160 30161 Apparent Power Phase L2 (S2) T5

30162 30163 Apparent Power Phase L3 (S3) T5

30164 30165 Power Factor Total (PFt) T7

30166 30167 Power Factor Phase 1 (PF1) T7

30168 30169 Power Factor Phase 2 (PF2) T7

30170 30171 Power Factor Phase 3 (PF3) T7

30172 Power Angle Total

(atan2(Pt,Qt)) T17

30173 φ1 (angle between U1 and I1) T17

30174 φ2 (angle between U2 and I2) T17

30175 φ3 (angle between U3 and I3) T17

30176 U unbalance T16

30177 30180 Reserved

30181 Internal Temperature T17

THD HARMONIC DATA

30182 U1 THD% T16

30183 U2 THD% T16

30184 U3 THD% T16

30185 U12 THD% T16

30186 U23 THD% T16

30187 U31 THD% T16

30188 I1 THD% T16

30189 I2 THD% T16

30190 I3 THD% T16

Page 21: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 19

Code Address Contents Data Ind Values and Dependencies

I/O STATUS

30191 Alarm Status Flags (No.

1…16) T1 bit-i Alarm i+1

30192 Alarm Status Flags (No.

17…32) T1 bit-i Alarm i+17

30193 I/O 1 Value T17

30194 I/O 2 Value T17

30195 I/O 3 Value T17

30196 I/O 4 Value T17

30197 30200 Reserved

MAXIMUM MEASUREMENTS

30201 30204 Last reset time T_Time

30205 30206 Frequency T5

30207 30208 U1 T5

30209 30210 U2 T5

30211 30212 U3 T5

30213 30217 Reserved:

30218 30219 U12 T5

30220 30221 U23 T5

30222 30223 U31 T5

30224 30225 Reserved

30226 30227 I1 T5

30228 30229 I2 T5

30230 30231 I3 T5

30232 30239 Reserved

30240 30241 Active Power Total (Pt) T6

30242 30243 Active Power Phase L1 (P1) T6

30244 30245 Active Power Phase L2 (P2) T6

30246 30247 Active Power Phase L3 (P3) T6

30248 30255 Reserved

30256 30257 Apparent Power Total (St) T5

30258 30259 Apparent Power Phase L1 (S1) T5

30260 30261 Apparent Power Phase L2 (S2) T5

30262 30263 Apparent Power Phase L3 (S3) T5

30264 30265 Reserved: Power Factor Total

(PFt) T7

30266 30280 Reserved

30281 Internal Temperature T17

30282 30300 Reserved

Page 22: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 20 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

MINIMUM MEASUREMENTS

30301 30304 Last reset time T_Time

30305 30306 Frequency T5

30307 30308 U1 T5

30309 30310 U2 T5

30311 30312 U3 T5

30313 30317 Reserved

30318 30319 U12 T5

30320 30321 U23 T5

30322 30323 U31 T5

30324 30325 Reserved

30326 30327 I1 T5

30328 30329 I2 T5

30330 30331 I3 T5

30332 30339 Reserved

30340 30341 Active Power Total (Pt) T6

30342 30343 Active Power Phase L1 (P1) T6

30344 30345 Active Power Phase L2 (P2) T6

30346 30347 Active Power Phase L3 (P3) T6

30348 30355 Reserved

30356 30357 Apparent Power Total (St) T5

30358 30359 Apparent Power Phase L1 (S1) T5

30360 30361 Apparent Power Phase L2 (S2) T5

30362 30363 Apparent Power Phase L3 (S3) T5

30364 30380 Reserved

30381 Internal Temperature T17

30382 30400 Reserved

ENERGY

30401 Energy Counter 1 Exponent T2

30402 Energy Counter 2 Exponent T2

30403 Energy Counter 3 Exponent T2

30404 Energy Counter 4 Exponent T2

30405 Current Active Tariff T1

30406 30407 Energy Counter 1 T3

30408 30409 Energy Counter 2 T3

30410 30411 Energy Counter 3 T3

30412 30413 Energy Counter 4 T3

30414 30415 Energy Counter 1 Tariff 1 T3

30416 30417 Energy Counter 2 Tariff 1 T3

Page 23: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 21

Code Address Contents Data Ind Values and Dependencies

30418 30419 Energy Counter 3 Tariff 1 T3

30420 30421 Energy Counter 4 Tariff 1 T3

30422 30423 Energy Counter 1 Tariff 2 T3

30424 30425 Energy Counter 2 Tariff 2 T3

30426 30427 Energy Counter 3 Tariff 2 T3

30428 30429 Energy Counter 4 Tariff 2 T3

30430 30431 Energy Counter 1 Tariff 3 T3

30432 30433 Energy Counter 2 Tariff 3 T3

30434 30435 Energy Counter 3 Tariff 3 T3

30436 30437 Energy Counter 4 Tariff 3 T3

30438 30439 Energy Counter 1 Tariff 4 T3

30440 30441 Energy Counter 2 Tariff 4 T3

30442 30443 Energy Counter 3 Tariff 4 T3

30444 30445 Energy Counter 4 Tariff 4 T3

30446 30447 Energy Counter 1 Cost T3

30448 30449 Energy Counter 2 Cost T3

30450 30451 Energy Counter 3 Cost T3

30452 30453 Energy Counter 4 Cost T3

30454 30500 Reserved

DEMAND VALUES

DYNAMIC DEMAND VALUES

30501 Time Into Period (minutes) T1

30502 30503 I1 T5

30504 30505 I2 T5

30506 30507 I3 T5

30508 30509 Apparent Power Total (St) T5

30510 30511 Active Power Total (Pt) -

(positive) T6

30512 30513 Active Power Total (Pt) -

(negative) T6

30514 30515 Reactive Power Total (Qt) - L T6

30516 30517 Reactive Power Total (Qt) - C T6

MAX DEMAND SINCE LAST RESET

30518 30519 I1 T5

30520 30523 Time Stamp T_Time

30524 30525 I2 T5

30526 30529 Time Stamp T_Time

30530 30531 I3 T5

30532 30535 Time Stamp T_Time

30536 30537 Apparent Power Total (St) T5

Page 24: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 22 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

30538 30541 Time Stamp T_Time

30542 30543 Active Power Total (Pt) -

(positive) T6

30544 30547 Time Stamp T_Time

30548 30549 Active Power Total (Pt) -

(negative) T6

30550 30553 Time Stamp T_Time

30554 30555 Reactive Power Total (Qt) - L T6

30556 30559 Time Stamp T_Time

30560 30561 Reactive Power Total (Qt) - C T6

30562 30565 Time Stamp T_Time

30566 30579 Reserved

FLICKERS (M253 & i5MQ only)

30580 Flicker Pst1 T17 <0 until the first measure

30581 Flicker Pst2 T17 <0 until the first measure

30582 Flicker Pst3 T17 <0 until the first measure

30583 Flicker Plt1 T17 <0 until the first measure

30584 Flicker Plt2 T17 <0 until the first measure

30585 Flicker Plt3 T17 <0 until the first measure

30586 30600 Reserved

ACTUAL PERIOD QUALITY (M253 & i5MQ only)

30601 30602 Report Start Time T9

30603 30604 Report Start Date T10

30605 30606 Report End Date T10

30607 Report Status T1 0 No monitoring

1 Not complete

2 Complete

30608 Report Compliance T1 Bit-0 Failed: Frequency Variations 1

Bit-1 Failed: Frequency Variations 2

Bit-2 Failed: Voltage Unbalances

Bit-3 Failed: Voltage Variations 1

Bit-4 Failed: Voltage Variations 2

Bit-5 Failed: THD's

Bit-6 Failed: Harmonics

Bit-7 Failed: Short term Flickers

Bit-8 Failed: Long term Flickers

Bit-9 Failed: Transients

Bit-10Failed: Temporary Overvoltages

Bit-11 Failed: Voltage Dips

Bit-12 Failed: Short Interruptions

Page 25: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 23

Code Address Contents Data Ind Values and Dependencies

Bit-13 Failed: Long Interruptions

30609 Reserved

30610 Frequency Variations 1: % /

Period T16

30611 Frequency Variations 1: % /

Year T16

30612 Frequency Variations 2: % /

Period T16

30613 Frequency Variations 2: % /

Year T16

30614 Voltage Unbalances: % /

Period T16

30615 Voltage Unbalances: % / Year T16

30616 Voltage Variations 1 - L1: % /

Period T16

30617 Voltage Variations 1 - L1: % /

Year T16

30618 Voltage Variations 1 - L2: % /

Period T16

30619 Voltage Variations 1 - L2: % /

Year T16

30620 Voltage Variations 1 - L3: % /

Period T16

30621 Voltage Variations 1 - L3: % /

Year T16

30622 Voltage Variations 2 - L1: % /

Period T16

30623 Voltage Variations 2 - L1: % /

Year T16

30624 Voltage Variations 2 - L2: % /

Period T16

30625 Voltage Variations 2 - L2: % /

Year T16

30626 Voltage Variations 2 - L3: % /

Period T16

30627 Voltage Variations 2 - L3: % /

Year T16

30628 THD's - L1: % / Period T16

30629 THD's - L1: % / Year T16

30630 THD's - L2: % / Period T16

30631 THD's - L2: % / Year T16

30632 THD's - L3: % / Period T16

30633 THD's - L3: % / Year T16

30634 Harmonics - L1: % / Period T16

30635 Harmonics - L1: % / Year T16

30636 Harmonics - L2: % / Period T16

Page 26: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 24 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

30637 Harmonics - L2: % / Year T16

30638 Harmonics - L3: % / Period T16

30639 Harmonics - L3: % / Year T16

30640 Short term Flickers - L1: % /

Period T16

30641 Short term Flickers - L1: % /

Year T16

30642 Short term Flickers - L2: % /

Period T16

30643 Short term Flickers - L2: % /

Year T16

30644 Short term Flickers - L3: % /

Period T16

30645 Short term Flickers - L3: % /

Year T16

30646 Long term Flickers - L1: % /

Period T16

30647 Long term Flickers - L1: % /

Year T16

30648 Long term Flickers - L2: % /

Period T16

30649 Long term Flickers - L2: % /

Year T16

30650 Long term Flickers - L3: % /

Period T16

30651 Long term Flickers - L3: % /

Year T16

30652 Transients - L1: No. / Period T1

30653 Transients - L1: No. / Year T1

30654 Transients - L2: No. / Period T1

30655 Transients - L2: No. / Year T1

30656 Transients - L3: No. / Period T1

30657 Transients - L3: No. / Year T1

30658 Temporary Overvoltages - L1:

No. / Period T1

30659 Temporary Overvoltages - L1:

No. / Year T1

30660 Temporary Overvoltages - L2:

No. / Period T1

30661 Temporary Overvoltages - L2:

No. / Year T1

30662 Temporary Overvoltages - L3:

No. / Period T1

30663 Temporary Overvoltages - L3:

No. / Year T1

30664 Voltage Dips - L1: No. / Period T1

Page 27: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 25

Code Address Contents Data Ind Values and Dependencies

30665 Voltage Dips - L1: No. / Year T1

30666 Voltage Dips - L2: No. / Period T1

30667 Voltage Dips - L2: No. / Year T1

30668 Voltage Dips - L3: No. / Period T1

30669 Voltage Dips - L3: No. / Year T1

30670 Short Interruptions - L1: No. /

Period T1

30671 Short Interruptions - L1: No. /

Year T1

30672 Short Interruptions - L2: No. /

Period T1

30673 Short Interruptions - L2: No. /

Year T1

30674 Short Interruptions - L3: No. /

Period T1

30675 Short Interruptions - L3: No. /

Year T1

30676 Long Interruptions - L1: No. /

Period T1

30677 Long Interruptions - L1: No. /

Year T1

30678 Long Interruptions - L2: No. /

Period T1

30679 Long Interruptions - L2: No. /

Year T1

30680 Long Interruptions - L3: No. /

Period T1

30681 Long Interruptions - L3: No. /

Year T1

30682 30700 Reserved

PREVIOUS PERIOD QUALITY (M253 & i5MQ only)

30701 30781 Last finished period quality See Actual period quality

Code Address Contents Data Ind Values and Dependencies

PHASE VOLTAGE HARMONIC DATA

U1 Harmonic Data

31001 31002 Base for % calculation T5

31003 U1 1 Harmonic Abs % T16

31004 U1 1 Harmonic Phase Angle T17

31006 31126 U1 Harmonics from 2 to 62 T17

31127 U1 63 Harmonic Abs % T16

31128 U1 63 Harmonic Phase Angle T17

U2 Harmonic Data

31129 31130 Base for % calculation T5

Page 28: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 26 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

31131 U2 1 Harmonic Abs % T16

31132 U2 1 Harmonic Phase Angle T17

31134 31254 U2 Harmonics from 2 to 62 T17

31255 U2 63 Harmonic Abs % T16

31256 U2 63 Harmonic Phase Angle T17

U3 Harmonic Data

31257 31258 Base for % calculation T5

31259 U3 2 Harmonic Abs % T16

31260 U3 2 Harmonic Phase Angle T17

31262 31382 U3 Harmonics from 2 to 62 T17

31383 U3 63 Harmonic Abs % T16

31384 U3 63 Harmonic Phase Angle T17

LINE VOLTAGE HARMONIC DATA

U12 Harmonic Data

31385 31386 Base for % calculation T5

31387 U12 1 Harmonic Abs % T16

31388 U12 1 Harmonic Phase Angle T17

31390 31510 U12 Harmonics from 2 to 62 T17

31511 U12 63 Harmonic Abs % T16

31512 U12 63 Harmonic Phase Angle T17

U23 Harmonic Data

31513 31514 Base for % calculation T5

31515 U23 1 Harmonic Abs % T16

31516 U23 1 Harmonic Phase Angle T17

31518 31638 U23 Harmonics from 2 to 62 T17

31639 U23 63 Harmonic Abs % T16

31640 U23 63 Harmonic Phase Angle T17

U31 Harmonic Data

31641 31642 Base for % calculation T5

31643 U31 2 Harmonic Abs % T16

31644 U31 2 Harmonic Phase Angle T17

31646 31766 U31 Harmonics from 2 to 62 T17

31767 U31 63 Harmonic Abs % T16

31768 U31 63 Harmonic Phase Angle T17

PHASE CURRENT HARMONIC DATA

I1 Harmonic Data

31769 31770 Base for % calculation T5

31771 I1 1 Harmonic Abs % T16

31772 I1 1 Harmonic Phase Angle T17

31774 31894 I1 Harmonics from 2 to 62 T17

Page 29: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 27

Code Address Contents Data Ind Values and Dependencies

31895 I1 63 Harmonic Abs % T16

31896 I1 63 Harmonic Phase Angle T17

I2 Harmonic Data

31897 31898 Base for % calculation T5

31899 I2 1 Harmonic Abs % T16

31900 I2 1 Harmonic Phase Angle T17

31902 32022 I2 Harmonics from 2 to 62 T17

32023 I2 63 Harmonic Abs % T16

32024 I2 63 Harmonic Phase Angle T17

I3 Harmonic Data

32025 32026 Base for % calculation T5

32027 I3 1 Harmonic Abs % T16

32028 I3 1 Harmonic Phase Angle T17

32030 32150 I3 Harmonics from 2 to 62 T17

32151 I3 63 Harmonic Abs % T16

32152 I3 63 Harmonic Phase Angle T17

32153 32483 Reserved

6.3 NORMALIZED MEASUREMENTS

The normalization (100%) values are shown in section 6.5.

Code Address Contents Data Ind Values and Dependencies

NORMALIZED ACTUAL MEASUREMENTS

30801 U1 T16

30802 U2 T16

30803 U3 T16

30804 Uavg (phase to neutral) T16

30805 U12 T16

30806 U23 T16

30807 U31 T16

30808 Uavg (phase to phase) T16

30809 I1 T16

30810 I2 T16

30811 I3 T16

30812 I T16

30813 I neutral (calculated) T16

30814 I neutral (measured) T16

30815 Iavg T16

30816 Active Power Phase L1 (P1) T17

30817 Active Power Phase L2 (P2) T17

Page 30: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 28 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

30818 Active Power Phase L3 (P3) T17

30819 Active Power Total (Pt) T17

30820 Reactive Power Phase L1 (Q1) T17

30821 Reactive Power Phase L2 (Q2) T17

30822 Reactive Power Phase L3 (Q3) T17

30823 Reactive Power Total (Qt) T17

30824 Apparent Power Phase L1 (S1) T16

30825 Apparent Power Phase L2 (S2) T16

30826 Apparent Power Phase L3 (S3) T16

30827 Apparent Power Total (St) T16

30828 Power Factor Phase 1 (PF1) T17

30829 Power Factor Phase 2 (PF2) T17

30830 Power Factor Phase 3 (PF3) T17

30831 Power Factor Total (PFt) T17

30832 CAP/IND P. F. Phase 1 (PF1) T17

30833 CAP/IND P. F. Phase 2 (PF2) T17

30834 CAP/IND P. F. Phase 3 (PF3) T17

30835 CAP/IND P. F. Total (PFt) T17

30836 1 (angle between U1 and I1) T17

30837 2 (angle between U2 and I2) T17

30838 3 (angle between U3 and I3) T17

30839 Power Angle Total (atan2(Pt,Qt)) T17

30840 12 (angle between U1 and U2) T17

30841 23 (angle between U2 and U3) T17

30842 31 (angle between U3 and U1) T17

30843 Frequency T17

30844 U unbalance T16

30845 I1 THD% T16

30846 I2 THD% T16

30847 I3 THD% T16

30848 U1 THD% T16

30849 U2 THD% T16

30850 U3 THD% T16

30851 U12 THD% T16

30852 U23 THD% T16

30853 U31 THD% T16

MAX DEMAND SINCE LAST RESET

30854

Active Power Total (Pt) - (positive) T16

Page 31: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 29

Code Address Contents Data Ind Values and Dependencies

30855

Active Power Total (Pt) - (negative) T16

30856 Reactive Power Total (Qt) - L T16

30857 Reactive Power Total (Qt) - C T16

30858 Apparent Power Total (St) T16

30859 I1 T16

30860 I2 T16

30861 I3 T16

DYNAMIC DEMAND VALUES

30862

Active Power Total (Pt) - (positive) T16

30863

Active Power Total (Pt) - (negative) T16

30864 Reactive Power Total (Qt) - L T16

30865 Reactive Power Total (Qt) - C T16

30866 Apparent Power Total (St) T16

30867 I1 T16

30868 I2 T16

30869 I3 T16

ENERGY

30870 Energy Counter 1 T17

30871 Energy Counter 2 T17

30872 Energy Counter 3 T17

30873 Energy Counter 4 T17

30874 Energy Counter 1 Cost T17

30875 Energy Counter 2 Cost T17

30876 Energy Counter 3 Cost T17

30877 Energy Counter 4 Cost T17

30878 Total Energy Counter Cost T17

30879 Active Tariff T1

30880 Internal Temperature T17

30881 30900 Reserved

6.4 MEASUREMENTS (IEEE 754)

Code Address Contents Data Ind Values and Dependencies

MEASUREMENTS (IEEE 754)

32484 32485 Uavg (phase to neutral) T_float

32486 32487 Uavg (phase to phase) T_float

32488 32489 I T_float

Page 32: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 30 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

32490 32491 Active Power Total (Pt) T_float

32492 32493 Reactive Power Total (Qt) T_float

32494 32495 Apparent Power Total (St) T_float

32496 32497 Power Factor Total (PFt) T_float

32498 32499 Frequency T_float

32500 32501 U1 T_float

32502 32503 U2 T_float

32504 32505 U3 T_float

32506 32507 Uavg (phase to neutral) T_float

32508 32509 U12 T_float

32510 32511 U23 T_float

32512 32513 U31 T_float

32514 32515 Uavg (phase to phase) T_float

32516 32517 I1 T_float

32518 32519 I2 T_float

32520 32521 I3 T_float

32522 32523 I T_float

32524 32525 I neutral (calculated) T_float

32526 32527 I neutral (measured) T_float

32528 32529 Iavg T_float

32530 32531 Active Power Phase L1 (P1) T_float

32532 32533 Active Power Phase L2 (P2) T_float

32534 32535 Active Power Phase L3 (P3) T_float

32536 32537 Active Power Total (Pt) T_float

32538 32539 Reactive Power Phase L1 (Q1) T_float

32540 32541 Reactive Power Phase L2 (Q2) T_float

32542 32543 Reactive Power Phase L3 (Q3) T_float

32544 32545 Reactive Power Total (Qt) T_float

32546 32547

Apparent Power Phase L1 (S1) T_float

32548 32549

Apparent Power Phase L2 (S2) T_float

32550 32551

Apparent Power Phase L3 (S3) T_float

32552 32553 Apparent Power Total (St) T_float

32554 32555 Power Factor Phase 1 (PF1) T_float

32556 32557 Power Factor Phase 2 (PF2) T_float

32558 32559 Power Factor Phase 3 (PF3) T_float

32560 32561 Power Factor Total (PFt) T_float

32562 32563 CAP/IND P. F. Phase 1 (PF1) T_float

32564 32565 CAP/IND P. F. Phase 2 (PF2) T_float

Page 33: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 31

Code Address Contents Data Ind Values and Dependencies

32566 32567 CAP/IND P. F. Phase 3 (PF3) T_float

32568 32569 CAP/IND P. F. Total (PFt) T_float

32570 32571 1 (angle between U1 and I1) T_float

32572 32573 2 (angle between U2 and I2) T_float

32574 32575 3 (angle between U3 and I3) T_float

32576 32577

Power Angle Total (atan2(Pt,Qt)) T_float

32578 32579

12 (angle between U1 and U2) T_float

32580 32581

23 (angle between U2 and U3) T_float

32582 32583

31 (angle between U3 and U1) T_float

32584 32585 Frequency T_float

32586 32587 U unbalace T_float

32588 32589 I1 THD% T_float

32590 32591 I2 THD% T_float

32592 32593 I3 THD% T_float

32594 32595 U1 THD% T_float

32596 32597 U2 THD% T_float

32598 32599 U3 THD% T_float

32600 32601 U12 THD% T_float

32602 32603 U23 THD% T_float

32604 32605 U31 THD% T_float

MAX DEMAND SINCE LAST RESET

32606 32607

Active Power Total (Pt) - (positive) T_float

32608 32609

Active Power Total (Pt) - (negative) T_float

32610 32611 Reactive Power Total (Qt) - L T_float

32612 32613 Reactive Power Total (Qt) - C T_float

32614 32615 Apparent Power Total (St) T_float

32616 32617 I1 T_float

32618 32619 I2 T_float

32620 32621 I3 T_float

DYNAMIC DEMAND VALUES

32622 32623

Active Power Total (Pt) - (positive) T_float

32624 32625

Active Power Total (Pt) - (negative) T_float

32626 32627 Reactive Power Total (Qt) - L T_float

32628 32629 Reactive Power Total (Qt) - C T_float

Page 34: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 32 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Address Contents Data Ind Values and Dependencies

32630 32631 Apparent Power Total (St) T_float

32632 32633 I1 T_float

32634 32635 I2 T_float

32636 32637 I3 T_float

ENERGY

32638 32639 Energy Counter 1 T_float

32640 32641 Energy Counter 2 T_float

32642 32643 Energy Counter 3 T_float

32644 32645 Energy Counter 4 T_float

32646 32647 Energy Counter 1 Cost T_float

32648 32649 Energy Counter 2 Cost T_float

32650 32651 Energy Counter 3 Cost T_float

32652 32653 Energy Counter 4 Cost T_float

32654 32655 Total Energy Counter Cost T_float

32656 32657 Active Tariff T_float

32658 32659 Internal Temperature T_float

ANALOGUE INPUTS

32660 32661 Analogue input 1 T_float

32662 32663 Analogue input 2 T_float

32664 32665 Analogue input 3 T_float

32666 32667 Analogue input 4 T_float

32668 33000 Reserved

6.5 OUTTYPES

Page 35: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 33

Code Parameter °

LC

D

Ala

rm

Mem

ory

An

_Ou

t

M25

3/i5

MQ

M24

3/i5

MR

M23

3/i5

MT

M21

3

M20

3

-100

%

+10

0%

+30

0%

1 U1 U1 * * * * * * * * * -Un +Un

2 U2 U2 * * * * * * * * * -Un +Un

3 U3 U3 * * * * * * * * * -Un +Un

4 U~ Uavg (phase to neutral) * * * * * * * * * -Un +Un

5 U12 U12 * * * * * * * * * -Un +Un

6 U23 U23 * * * * * * * * * -Un +Un

7 U31 U31 * * * * * * * * * -Un +Un

8 Uff~ Uavg (phase to phase) * * * * * * * * * -Un +Un

9 I1 I1 * * * * * * * * * -In +In

10 I2 I2 * * * * * * * * * -In +In

11 I3 I3 * * * * * * * * * -In +In

12 I S I * * * * * * * * * -It +It

13 INc I neutral (calculated) * * * * * * * * * -In +In

14 INm I neutral (measured) -In +In

15 I~ Iavg * * * * * * * * * -In +In

16 P1 Active Power Phase L1 (P1) * * * * * * * * * -Pn +Pn

17 P2 Active Power Phase L2 (P2) * * * * * * * * * -Pn +Pn

18 P3 Active Power Phase L3 (P3) * * * * * * * * * -Pn +Pn

19 P Active Power Total (Pt) * * * * * * * * * -Pt +Pt

20 Q1 Reactive Power Phase L1 (Q1) * * * * * * * * * -Pn +Pn

21 Q2 Reactive Power Phase L2 (Q2) * * * * * * * * * -Pn +Pn

22 Q3 Reactive Power Phase L3 (Q3) * * * * * * * * * -Pn +Pn

23 Q Reactive Power Total (Qt) * * * * * * * * * -Pt +Pt

Page 36: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 34 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Parameter °

LC

D

Ala

rm

Mem

ory

An

_Ou

t

M25

3/i5

MQ

M24

3/i5

MR

M23

3/i5

MT

M21

3

M20

3

-100

%

+10

0%

+30

0%

24 S1 Apparent Power Phase L1 (S1) * * * * * * * * * -Pn +Pn

25 S2 Apparent Power Phase L2 (S2) * * * * * * * * * -Pn +Pn

26 S3 Apparent Power Phase L3 (S3) * * * * * * * * * -Pn +Pn

27 S Apparent Power Total (St) * * * * * * * * * -Pt +Pt

28 PF1 Power Factor Phase 1 (PF1) * * * * * * * * * -1 +1

29 PF2 Power Factor Phase 2 (PF2) * * * * * * * * * -1 +1

30 PF3 Power Factor Phase 3 (PF3) * * * * * * * * * -1 +1

31 PF Power Factor Total (PFt) * * * * * * * * * -1 +1

32 PF1-C/I CAP/IND P. F. Phase 1 (PF1) * * * * * * * * * -1 CAP +1 -1IND

33 PF2-C/I CAP/IND P. F. Phase 2 (PF2) * * * * * * * * * -1 CAP +1 -1IND

34 PF3-C/I CAP/IND P. F. Phase 3 (PF3) * * * * * * * * * -1 CAP +1 -1IND

35 PF-C/I CAP/IND P. F. Total (PFt) * * * * * * * * * -1 CAP +1 -1IND

36 PA1 φ1 (angle between U1 and I1) * * * * * * * * * -100° +100°

37 PA2 φ2 (angle between U2 and I2) * * * * * * * * * -100° +100°

38 PA3 φ3 (angle between U3 and I3) * * * * * * * * * -100° +100°

39 PA Power Angle Total (atan2(Pt,Qt)) * * * * * * * * * -100° +100°

40 fi U12 φ12 (angle between U1 and U2) * * * * * * * * * -100° +100°

41 fi U23 φ23 (angle between U2 and U3) * * * * * * * * * -100° +100°

42 fi U31 φ31 (angle between U3 and U1) * * * * * * * * * -100° +100°

43 F Frequency * * * * * * * * * Fn-10Hz Fn+10Hz

44 Uu U unbalance * * * * * * * -100% +100%

45 THD I1 I1 THD% * * * * * * * -100% +100%

46 THD I2 I2 THD% * * * * * * * -100% +100%

Page 37: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 35

Code Parameter °

LC

D

Ala

rm

Mem

ory

An

_Ou

t

M25

3/i5

MQ

M24

3/i5

MR

M23

3/i5

MT

M21

3

M20

3

-100

%

+10

0%

+30

0%

47 THD I3 I3 THD% * * * * * * * -100% +100%

48 THD U1 U1 THD% * * * * * * * -100% +100%

49 THD U2 U2 THD% * * * * * * * -100% +100%

50 THD U3 U3 THD% * * * * * * * -100% +100%

51 THD U12 U12 THD% * * * * * * * -100% +100%

52 THD U23 U23 THD% * * * * * * * -100% +100%

53 THD U31 U31 THD% * * * * * * * -100% +100%

MAX DEMAND SINCE LAST RESET

54 MV-P+ Active Power Total (Pt) - (positive) * ° * * * * * -Pt +Pt

55 MV-P- Active Power Total (Pt) - (negative) * * * * * * -Pt +Pt

56 MV-QL Reactive Power Total (Qt) - L * * * * * * -Pt +Pt

57 MV-QC Reactive Power Total (Qt) - C * * * * * * -Pt +Pt

58 MV-S Apparent Power Total (St) * * * * * * -Pt +Pt

59 MV-I1 I1 * * * * * * -In +In

60 MV-I2 I2 * * * * * * -In +In

61 MV-I3 I3 * * * * * * -In +In

DYNAMIC DEMAND VALUES

62 DMV-P+ Active Power Total (Pt) - (positive) * * * * * * * * -Pt +Pt

63 DMV-P- Active Power Total (Pt) - (negative) * * * * * * * * -Pt +Pt

64 DMV-QL Reactive Power Total (Qt) - L * * * * * * * * -Pt +Pt

65 DMV-QC Reactive Power Total (Qt) - C * * * * * * * * -Pt +Pt

66 DMV-S Apparent Power Total (St) * * * * * * * * -Pt +Pt

67 DMV-I1 I1 * * * * * * * * -In +In

Page 38: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 36 iSTAT M2x3 & I500 Modbus & DNP3.0

Code Parameter °

LC

D

Ala

rm

Mem

ory

An

_Ou

t

M25

3/i5

MQ

M24

3/i5

MR

M23

3/i5

MT

M21

3

M20

3

-100

%

+10

0%

+30

0%

68 DMV-I2 I2 * * * * * * * * -In +In

69 DMV-I3 I3 * * * * * * * * -In +In

Code Parameter °

LC

D

Ala

rm

Mem

ory

An

_Ou

t

M25

3/i5

MQ

M24

3/i5

MR

M23

3/i5

MT

M21

3

M20

3

70 E1 Energy Counter 1 * * * * * * * (32-bit value) MOD 20000

71 E2 Energy Counter 2 * * * * * * * (32-bit value) MOD 20000

72 E3 Energy Counter 3 * * * * * * * (32-bit value) MOD 20000

73 E4 Energy Counter 4 * * * * * * * (32-bit value) MOD 20000

74 E1-$ Energy Counter 1 Cost * * * * * * (32-bit value) MOD 20000

75 E2-$ Energy Counter 2 Cost * * * * * * (32-bit value) MOD 20000

76 E3-$ Energy Counter 3 Cost * * * * * * (32-bit value) MOD 20000

77 E4-$ Energy Counter 4 Cost * * * * * * (32-bit value) MOD 20000

78 E-$ Total Energy Counter Cost * * * * * * (32-bit value) MOD 20000

Page 39: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0 Page 37

Code Parameter °

LC

D

Ala

rm

Mem

ory

An

_Ou

t

M25

3/i5

MQ

M24

3/i5

MR

M23

3/i5

MT

M21

3

M20

3

-100

%

+10

0%

79 AT Active Tariff * * * * * * *

80 Pst1 Flicker Pst1 * * * * -100 +100

81 Pst2 Flicker Pst2 * * * * -100 +100

82 Pst3 Flicker Pst3 * * * * -100 +100

83 Plt1 Flicker Plt1 * * * * -100 +100

84 Plt2 Flicker Plt2 * * * * -100 +100

85 Plt3 Flicker Plt3 * * * * -100 +100

100 Tint Internal Temperature * * * * * * * * * -100 +100

101 T Temperature -100º +100º

102 R Resistance

103 TAP Resistance ratio -100% +100%

104 DC-U DC Voltage

105 DC-I DC Current

106 Ufunc User function

107 AI1 Analogue input 1 * * * * * * -100% +100%

108 AI2 Analogue input 2 * * * * * * -100% +100%

109 AI3 Analogue input 3 * * * * * * -100% +100%

110 AI4 Analogue input 4 * * * * * * -100% +100%

111 DI1 Digital input 1 * * * * "1"

112 DI2 Digital input 2 * * * * "1"

113 DI3 Digital input 3 * * * * "1"

114 DI4 Digital input 4 * * * * "1"

Page 40: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 38 iSTAT M2x3 & I500 Modbus & DNP3.0

Un = (R40147 / R40146) * R30015 * R40149 40144 CT Secondary

In = (R40145 / R40144) * R30017 * R40148 40145 CT Primary

Pn = Un*In 40146 VT Secondary

It = In ;Conection Mode: 1b 40147 VT Primary

It = 3*In ;Conection Mode: 3b, 4b, 3u, 4u 40148 Current input range (%)

Pt = Pn ;Conection Mode: 1b 40149 Voltage input range (%)

Pt = 3*Pn ;Conection Mode: 3b, 4b, 3u, 4u 40150 Frequency nominal value

Fn = R40150 30015 Calibration voltage

30017 Calibration current

Page 41: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0

Page 39

6.6 MODBUS DATA TYPES

Registers defined in the Modbus database will define data as one of the data types described in the following table:

Type Value / Bit Mask Description

T1 Unsigned Value (16 bit)

Example: 12345 stored as 12345 = 3039(16)

T2 Signed Value (16 bit)

Example: -12345 stored as -12345 = CFC7(16)

T3 Signed Long Value (32 bit)

Example: 123456789 stored as 123456789 = 075B CD 15(16)

T4 Short Unsigned float (16 bit)

bits # 15..14 Decade Exponent(Unsigned 2 bit)

bits # 13..00 Binary Unsigned Value (14 bit)

Example: 10000*102 stored as A710(16)

T5 Unsigned Measurement (32 bit)

bits # 31..24 Decade Exponent(Signed 8 bit)

bits # 23..00 Binary Unsigned Value (24 bit)

Example: 123456*10-3 stored as FD01 E240(16)

T6 Signed Measurement (32 bit)

bits # 31..24 Decade Exponent (Signed 8 bit)

bits # 23..00 Binary Signed value (24 bit)

Example: - 123456*10-3 stored as FDFE 1DC0(16)

T7 Power Factor (32 bit)

bits # 31..24 Sign: Import/Export (00/FF)

bits # 23..16 Sign: Inductive/Capacitive (00/FF)

bits # 15..00 Unsigned Value (16 bit), 4 decimal places

Example: 0.9876 CAP stored as 00FF 2694(16)

T8 Time stamp (32 bit)

bits # 31..24 Minutes 00 - 59 (BCD)

bits # 23..16 Hours 00 - 23 (BCD)

bits # 15..08 Day of month 01 - 31 (BCD)

bits # 07..00 Month of year 01 - 12 (BCD)

Example: 15:42, 1. SEP stored as 4215 0109(16)

T9 Time (32 bit)

bits # 31..24 1/100s 00 - 99 (BCD)

bits # 23..16 Seconds 00 - 59 (BCD)

bits # 15..08 Minutes 00 - 59 (BCD)

bits # 07..00 Hours 00 - 24 (BCD)

Example: 15:42:03.75 stored as 7503 4215(16)

Page 42: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 40

iSTAT M2x3 & I500 Modbus & DNP3.0

Type Value / Bit Mask Description

T10 Date (32 bit)

bits # 31..24 Day of month 01 - 31 (BCD)

bits # 23..16 Month of year 01 - 12 (BCD)

bits # 15..00 Year (unsigned integer) 1998..4095

Example: 10, SEP 2000 stored as 1009 07D0(16)

T_Str4 Text String 4 characters

(T11) Two characters per 16 bit register

T_Str6 Text String 6 characters

(T12) Two charcters per 16 bit register

T_Str8 Text String 8 characters

Two characters per 16 bit register.

T_Str16 Text String 16 characters

Two characters per 16 bit register.

T_Str20 Text String 20 characters

Two characters per 16 bit register.

T16 Unsigned Value (16 bit), 2 decimal places

Example: 123.45 stored as 123.45 = 3039(16)

T17 Signed Value (16 bit), 2 decimal places

Example: -123.45 stored as -123.45 = CFC7(16)

T_Time Time and Date (64 bit)

bits # 63..56 1/100s 00 - 99 (BCD)

bits # 55..48 Seconds 00 - 59 (BCD)

bits # 47..40 Minutes 00 - 59 (BCD)

bits # 39..32 Hours 00 - 24 (BCD)

bits # 31..24 Day of month 01 - 31 (BCD)

bits # 23..16 Month of year 01 - 12 (BCD)

bits # 15..00 Year (unsigned integer) 1998..4095

Example: 15:42:03.75, 10. SEP 2000 stored as 7503 4215 1009 07D0(16)

T_TimeIEC Time and Date (64 bit) = IEC870-5-4 "Binary Time 2a"

bits # 63..55 Reserved

bits # 54..48 Years (0 .. 99)

bits # 47..44 Reserved

bits # 43..40 Months (1 .. 12)

bits # 39..37 Day of Week (1 .. 7)

bits # 36..32 Day of Month (1 .. 31)

bit # 31 Summer Time (0 .. 1): Summer time (1), Standard time (0)

bits # 30..29 Reserved

bits # 28..24 Hours (0 .. 23)

bit # 23 Invalid (0 .. 1): Invalid (1), Valid (0)

bit # 22 Reserved

Page 43: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0

Page 41

Type Value / Bit Mask Description

bits # 21..16 Minutes (0 .. 59)

bits # 15..00 Miliseconds (0 .. 59999)

Example: 15:42, 1. SEP stored as 4215 0109(16)

T_Data Record Data

Size and SubTypes depends on the Actual Memory Part

T_Str40 Text String 40 characters

Two characters per 16 bit register.

T_float IEEE 754 Floating-Point Single Precision Value (32 bit)

bits # 31 Sign Bit (1 bit)

bits # 30..23 Exponent Field (8 bit)

bits # 22..0 Significand (23 bit)

Example: 123.45 stored as 123.45000 = 42F6 E666(16)

T9A Time (16 bit)

bits # 15..08 Minutes 00 - 59 (BCD)

bits # 07..00 Hours 00 - 24 (BCD)

Example: 15:42 stored as 4215(16)

T10A Date (16 bit)

bits # 15..08 Day of month 00 - 31 (BCD)

bits # 07..00 Month of year 00 - 12 (BCD)

Example: 30, SEP stored as 3009(16)

T18 Signed Value (16 bit), 4 decimal places

Example: -0.2345 stored as -2345 = F6D7(16)

T_RecTime Time and Date (32 bit)

bit # 31 Power Off

bis # 30 Reserved

bits # 29..26 (Year-2000) MOD 16

bits # 25..22 Month of year (1 - 12)

bits # 21..17 Day of month (1 - 31)

bits # 16..00 Seconds in Day (0 - 86400)

Example: 15:42:03, 10. SEP 2006 stored as 1A54 DCCB(16)

T_Hex4 4 Hex Bytes

Two Hex Bytes per 16-bit register

T_Hex6 6 Hex Bytes

Two Hex Bytes per 16-bit register

Page 44: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 42

iSTAT M2x3 & I500 Modbus & DNP3.0

7. MODBUS DATA FOR I5MC/MV/MS/ML

7.1 MEASUREMENTS

MODBUS

Register Parameter

Start End Type

Actual Measurements

Frequency 34101 34102 T5

U1 34103 34104 T5

I1 34105 34106 T5

Active Power (P1) 34107 34108 T6

Reactive Power (Q1) 34109 34110 T6

Apparent Power (S1) 34111 34112 T5

Power Factor (PF1) 34113 34114 T7

φ1 (angle between U1 and I1) 34115 T17

Internal Temperature 34116 T17

U1 THD% 34117 T16

I1 THD% 34118 T16

Alarm Status Flags (No. 1…16)

34119 T1

I/O 1 Value 34121 T17

I/O 2 Value 34122 T17

Energy (i5ML only)

Energy Counter 1 Exponent 34201 T2

Energy Counter 2 Exponent 34202 T2

Energy Counter 3 Exponent 34203 T2

Energy Counter 4 Exponent 34204 T2

Energy Counter 1 34206 34207 T3

Energy Counter 2 34208 34209 T3

Energy Counter 3 34210 34211 T3

Energy Counter 4 34212 34213 T3

Demand values

Dynamic demand values

U1 34302 34303 T5

I1 34304 34305 T5

Apparent Power (Sn) 34306 34307 T5

Active Power (Pn) - (positive) 34308 34309 T6

Active Power (Pn) - (negative) 34310 34311 T6

Page 45: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0

Page 43

MODBUS

Register Parameter

Start End Type

Reactive Power (Qn) - L 34312 34313 T6

Reactive Power (Qn) - C 34314 34315 T6

Max demand since last reset

U1 34316 34317 T5

I1 34318 34319 T5

Apparent Power (Sn) 34320 34321 T5

Active Power (Pn) - (positive) 34322 34323 T6

Active Power (Pn) - (negative) 34324 34325 T6

Reactive Power (Qn) - L 34326 34327 T6

Reactive Power (Qn) - C 34328 34329 T6

7.2 NORMALISED MEASUREMENTS

MODBUS Parameter

Register Type 100% value

U1 34401 T16 Un

I1 34402 T16 In

Active Power (P1) 34403 T17 Pn

Reactive Power (Q1) 34404 T17 Pn

Apparent Power (S1) 34405 T16 Pn

Power Factor (PF1) 34406 T17 1

CAP/IND P. F. (PF1) 34407 T17 1

φ1 (angle between U1 and I1) 34408

T17 100°

Frequency 34409 T17 Fn+10Hz

I1 THD% 34410 T16 100%

U1 THD% 34411 T16 100%

Max demand since last reset

Active Power (Pn) - (positive) 34412 T16 Pn

Active Power (Pn) - (negative) 34413 T16

Pn

Reactive Power (Qn) - L 34414 T16 Pn

Reactive Power (Qn) - C 34415 T16 Pn

Apparent Power (Sn) 34416 T16 Pn

I1 34417 T16 In

U1 34418 T16 Un

Page 46: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 44

iSTAT M2x3 & I500 Modbus & DNP3.0

MODBUS Parameter

Register Type 100% value

Dynamic demand values

Active Power (Pn) - (positive) 34419 T16 Pn

Active Power (Pn) - (negative) 34420 T16

Pn

Reactive Power (Qn) - L 34421 T16 Pn

Reactive Power (Qn) - C 34422 T16 Pn

Apparent Power (Sn) 34423 T16 Pn

I1 34424 T16 In

U1 34425 T16 Un

Energy (i5ML only)

Energy Counter 1 34426 T17

Energy Counter 2 34427 T17

Energy Counter 3 34428 T17

Energy Counter 4 34429 T17

Actual counter value MOD 20000 is returned

Internal Temperature 34430 T17 100°

100% values calculations for normalized measurements

Un = (R40147 / R40146) * R30015 * R40149

In = (R40145 / R40144) * R30017 * R40148

Pn = Un*In

Fn = R40150

Register Content

30015 Calibration voltage

30017 Calibration current

Page 47: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0

Page 45

7.3 MEASUREMENTS (IEEE 754 )

MODBUS

Register Parameter

Start End Type

U1 34601 34602 T_float

I1 34603 34604 T_float

Active Power (P1) 34605 34606 T_float

Reactive Power (Q1) 34607 34608 T_float

Apparent Power (S1) 34609 34610 T_float

Power Factor (PF1) 34611 34612 T_float

CAP/IND P. F. (PF1) 34613 34614 T_float

φ1 (angle between U1 and I1) 34615 34616 T_float

Frequency 34617 34618 T_float

I1 THD% 34619 34620 T_float

U1 THD% 34621 34622 T_float

Max demand since last reset

Active Power (Pn) - (positive) 34623 34624 T_float

Active Power (Pn) - (negative) 34625 34626 T_float

Reactive Power (Qn) - L 34627 34628 T_float

Reactive Power (Qn) - C 34629 34630 T_float

Apparent Power (Sn) 34631 34632 T_float

I1 34633 34634 T_float

U1 34635 34636 T_float

Dynamic demand values

Active Power (Pn) - (positive) 34637 34638 T_float

Active Power (Pn) - (negative) 34639 34640 T_float

Reactive Power (Qn) - L 34641 34642 T_float

Reactive Power (Qn) - C 34643 34644 T_float

Apparent Power (Sn) 34645 34646 T_float

I1 34647 34648 T_float

U1 34649 34650 T_float

Energy (i5ML only)

Energy Counter 1 34651 34652 T_float

Energy Counter 2 34653 34654 T_float

Energy Counter 3 34655 34656 T_float

Energy Counter 4 34657 34658 T_float

Internal Temperature 34659 34660 T_float

Page 48: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 46

iSTAT M2x3 & I500 Modbus & DNP3.0

7.4 PRODUCT SETTINGS

Register table for the basic settings

Register Content Type Ind Values / Dependencies

Min Max P. Level

40144 CT Secondary T4 mA 2

40145 CT Primary T4 A/10 2

40146 VT Secondary T4 mV 2

40147 VT Primary T4 V/10 2

40148 Current input range (%)

T16 10000 for 100% 5,00 200,00 2

40149 Voltage input range (%)

T16 10000 for 100% 2,50 100,00 2

40150 Frequency nominal value

T1 Hz 10 1000 2

7.5 MODBUS DATA TYPES

Registers defined in the Modbus database will define data as one of the data types described in the following table:

Type Bit mask Description

T1 Unsigned Value (16 bit)

Example: 12345 = 3039(16)

T2 Signed Value (16 bit)

Example: -12345 = CFC7(16)

T3 Signed Long Value (32 bit)

Example: 123456789 = 075B CD 15(16)

T4 bits # 15…14

bits # 13…00

Short Unsigned float (16 bit)

Decade Exponent(Unsigned 2 bit)

Binary Unsigned Value (14 bit)

Example: 10000*102 = A710(16)

T5 bits # 31…24

bits # 23…00

Unsigned Measurement (32 bit)

Decade Exponent(Signed 8 bit)

Binary Unsigned Value (24 bit)

Example: 123456*10-3 = FD01 E240(16)

T6 bits # 31…24

bits # 23…00

Signed Measurement (32 bit)

Decade Exponent (Signed 8 bit)

Binary Signed value (24 bit)

Example: - 123456*10-3 = FDFE 1DC0(16)

Page 49: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0

Page 47

Type Bit mask Description

T7

bits # 31…24

bits # 23…16

bits # 15…00

Power Factor (32 bit)

Sign: Import/Export (00/FF)

Sign: Inductive/Capacitive (00/FF)

Unsigned Value (16 bit), 4 decimal places

Example: 0.9876 CAP = 00FF 2694(16)

T9

bits # 31…24

bits # 23…16

bits # 15…08

bits # 07…00

Time (32 bit)

1/100s 00 - 99 (BCD)

Seconds 00 - 59 (BCD)

Minutes 00 - 59 (BCD)

Hours 00 - 24 (BCD)

Example: 15:42:03.75 = 7503 4215(16)

T10

bits # 31…24

bits # 23…16

bits # 15…00

Date (32 bit)

Day of month 01 - 31 (BCD)

Month of year 01 - 12 (BCD)

Year (unsigned integer) 1998..4095

Example: 10, SEP 2000 = 1009 07D0(16)

T16 Unsigned Value (16 bit), 2 decimal places

Example: 123.45 = 3039(16)

T17 Signed Value (16 bit), 2 decimal places

Example: -123.45 = CFC7(16)

T_Str4 Text: 4 characters (2 characters for 16 bit register)

T_Str6 Text: 6 characters (2 characters for 16 bit register)

T_Str8 Text: 8 characters (2 characters for 16 bit register)

T_Str16 Text: 16 characters (2 characters for 16 bit register)

T_Str40 Text: 40 characters (2 characters for 16 bit register)

Page 50: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 48

iSTAT M2x3 & I500 Modbus & DNP3.0

8. DNP3.0 PROGRAMMING FOR M2X3 AND I5MT/MR/MQ

Communication protocols:

Modbus and DNP3 protocol are enabled via RS232 and RS485 or Ethernet communication. Both communication protocols are supported on all communication ports of the device. The response is the same type as the request.

DNP3

DNP3 protocol enables operation of Measurement Centre on DNP3 networks. For devices with serial communication the DNP3 protocol enables point to point (for example device to PC) communication via RS232 communication and multi drop communication via RS485.

8.1 DNP 3.0 DEVICE PROFILE DOCUMENT

DNP 3.0 Device Profile Document

Device Name: Measurement centre Vendor Name: Alstom Grid Models Covered: M2x3, i5MT/MR/MQ Highest DNP Level Supported: For Requests: 2 For Responses: 2

Device Function: Master

Slave Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the DNP V3.0 Implementation table):

Maximum Data Link Frame Size (octets): Transmitted: 292 Received: 292 Maximum Data Link Re-tries: None

Configurable

Maximum Application Fragment Size (octets): Transmitted: 2048 Received: 249 Maximum Application Layer Re-tries: None

Configurable

Requires Data Link Layer Confirmation: Never

Always

Sometimes

Configurable

Requires Application Layer Confirmation: Never

Always

Sometimes

Configurable

Page 51: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0

Page 49

Timeouts while waiting for: Data Link Confirm: None Fixed at ____ Variable Configurable

Complete Appl. Fragment: None Fixed at ____ Variable Configurable

Application Confirm: None Fixed at ____ Variable Configurable

Complete Appl. Response: None Fixed at ____ Variable Configurable Others: Sends/Executes Control Operations: WRITE Binary Outputs Never Always Sometimes Configurable

SELECT/OPERATE Never Always Sometimes Configurable

DIRECT OPERATE Never Always Sometimes Configurable

DIRECT OPERATE – NO ACK Never Always Sometimes Configurable Count > 1 Never Always Sometimes Configurable

Pulse On Never Always Sometimes Configurable

Pulse Off Never Always Sometimes Configurable

Latch On Never Always Sometimes Configurable

Latch Off Never Always Sometimes Configurable Queue Never Always Sometimes Configurable

Clear Queue Never Always Sometimes Configurable Reports Binary Input Change Events when no specific variation requested: Never

Only non-time-tagged

Configurable

Reports time-tagged Binary Input Change Events when no specific variation requested: Never

Binary Input Change With Relative Time

Configurable

Sends Unsolicited Responses: Never

Configurable

Only certain Objects

Sometimes

ENABLE/DISABLE UNSOLICITED Function codes supported

Sends Static Data in Unsolicited Responses: Never

When Device Restarts

When Status Flags Change No other options are permitted.

Default Counter Object/Variation: No Counters Reported

Configurable

Default Object: 30

Default Variation: 2 Point-by-point list attached

Counters Roll Over at: No Counters Reported

Configurable

16 Bits

32 Bits

Other Value:____ Point-by-point list attached

Sends Multi-Fragment Responses: Yes

No

Page 52: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 50

iSTAT M2x3 & I500 Modbus & DNP3.0

8.2 DNP3.0 REGISTER MAP

Object Request Response

Object

Number

Variation

Number Description

Function

Codes (dec)

Qualifier

Codes (hex)

Function

Codes (dec)

Qualifier

Codes (hex)

30 2 16-Bit Analogue Input with flag 1 00, 01, 02, 06 129 00, 01, 02, 00

30 4 16-Bit Analogue Input without flag 1 00, 01, 02, 06 129 00, 01, 02, 00

Object Request Response

Object

Number

Variation

Number Description

Function

Codes (dec)

Qualifier

Codes (hex)

Function

Codes (dec)

Qualifier

Codes (hex)

60 1 CLASS 0 DATA 1 6 129 0

60 2 CLASS 1 DATA 1 00, 01, 02, 06 129 00, 01, 02, 00

60 3 CLASS 2 DATA 1 00, 01, 02, 06 129 00, 01, 02, 00

60 4 CLASS 3 DATA 1 00, 01, 02, 06 129 00, 01, 02, 00

DNP Point

Contents Data Type

Type -100% +100% Remark

0 U1 T16 Data -Un +Un

1 U2 T16 Data -Un +Un

2 U3 T16 Data -Un +Un

3 Uavg (phase to neutral) T16 Data -Un +Un

4 U12 T16 Data -Un +Un

5 U23 T16 Data -Un +Un

6 U31 T16 Data -Un +Un

7 Uavg (phase to phase) T16 Data -Un +Un

8 I1 T16 Data -In +In

9 I2 T16 Data -In +In

10 I3 T16 Data -In +In

11 I total T16 Data -In +In

12 I neutral (calculated) T16 Data -In +In

13 I neutral (measured) T16 Data -In +In

14 Iavg T16 Data -In +In

15 Active Power Phase L1 (P1) T17 Data -Pn +Pn

16 Active Power Phase L2 (P2) T17 Data -Pn +Pn

17 Active Power Phase L3 (P3) T17 Data -Pn +Pn

18 Active Power Total (Pt) T17 Data -Pt +Pt

19 Reactive Power Phase L1 (Q1) T17 Data -Pn +Pn

20 Reactive Power Phase L2 (Q2) T17 Data -Pn +Pn

21 Reactive Power Phase L3 (Q3) T17 Data -Pn +Pn

22 Reactive Power Total (Qt) T17 Data -Pt +Pt

23 Apparent Power Phase L1 (S1) T16 Data -Pn +Pn

24 Apparent Power Phase L2 (S2) T16 Data -Pn +Pn

25 Apparent Power Phase L3 (S3) T16 Data -Pn +Pn

26 Apparent Power Total (St) T16 Data -Pt +Pt

Page 53: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0

Page 51

DNP Point

Contents Data Type

Type -100% +100% Remark

27 Power Factor Phase 1 (PF1) T17 Data -1 +1

28 Power Factor Phase 2 (PF2) T17 Data -1 +1

29 Power Factor Phase 3 (PF3) T17 Data -1 +1

30 Power Factor Total (PFt) T17 Data -1 +1

31 CAP/IND P. F. Phase 1 (PF1) T17 Data -1

CAP +1 300% for -1 IND

32 CAP/IND P. F. Phase 2 (PF2) T17 Data -1

CAP +1 300% for -1 IND

33 CAP/IND P. F. Phase 3 (PF3) T17 Data -1

CAP +1 300% for -1 IND

34 CAP/IND P. F. Total (PFt) T17 Data -1

CAP +1 300% for -1 IND

35 j1 (angle between U1 and I1) T17 Data -100° +100°

36 j2 (angle between U2 and I2) T17 Data -100° +100°

37 j3 (angle between U3 and I3) T17 Data -100° +100°

38 Power Angle Total (atan2(Pt,Qt))

T17 Data -100° +100°

39 j12 (angle between U1 and U2) T17 Data -100° +100°

40 j23 (angle between U2 and U3) T17 Data -100° +100°

41 j31 (angle between U3 and U1) T17 Data -100° +100°

42 Frequency T17 Data Fn-

10Hz Fn+10

Hz

43 U unbalance T16 Data -100% +100%

44 I1 THD% T16 Data -100% +100%

45 I2 THD% T16 Data -100% +100%

46 I3 THD% T16 Data -100% +100%

47 U1 THD% T16 Data -100% +100%

48 U2 THD% T16 Data -100% +100%

49 U3 THD% T16 Data -100% +100%

50 U12 THD% T16 Data -100% +100%

51 U23 THD% T16 Data -100% +100%

52 U31 THD% T16 Data -100% +100%

MAX DEMAND SINCE LAST RESET

53 Active Power Total (Pt) - (positive)

T16 Data -Pt +Pt

54 Active Power Total (Pt) - (negative)

T16 Data -Pt +Pt

55 Reactive Power Total (Qt) - L T16 Data -Pt +Pt

56 Reactive Power Total (Qt) - C T16 Data -Pt +Pt

57 Apparent Power Total (St) T16 Data -Pt +Pt

58 I1 T16 Data -In +In

59 I2 T16 Data -In +In

60 I3 T16 Data -In +In

DYNAMIC DEMAND VALUES

61 Active Power Total (Pt) - (positive)

T16 Data -Pt +Pt

62 Active Power Total (Pt) - (negative)

T16 Data -Pt +Pt

63 Reactive Power Total (Qt) - L T16 Data -Pt +Pt

64 Reactive Power Total (Qt) - C T16 Data -Pt +Pt

65 Apparent Power Total (St) T16 Data -Pt +Pt

66 I1 T16 Data -In +In

Page 54: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 52

iSTAT M2x3 & I500 Modbus & DNP3.0

DNP Point

Contents Data Type

Type -100% +100% Remark

67 I2 T16 Data -In +In

68 I3 T16 Data -In +In

ENERGY

69 Energy Counter 1 T17 Data (32-bit value) MOD 20000

70 Energy Counter 2 T17 Data (32-bit value) MOD 20000

71 Energy Counter 3 T17 Data (32-bit value) MOD 20000

72 Energy Counter 4 T17 Data (32-bit value) MOD 20000

73 Energy Counter 1 Cost T17 Data (32-bit value) MOD 20000

74 Energy Counter 2 Cost T17 Data (32-bit value) MOD 20000

75 Energy Counter 3 Cost T17 Data (32-bit value) MOD 20000

76 Energy Counter 4 Cost T17 Data (32-bit value) MOD 20000

77 Total Energy Counter Cost T17 Data (32-bit value) MOD 20000

78 Active Tariff T1 Data 8.3 DATA TYPES − DECODING

Type Bit mask Description

T1 Unsigned Value (16 bit)

Example: 12345 = 3039(16)

T2 Signed Value (16 bit)

Example: -12345 = CFC7(16)

T3 Signed Long Value (32 bit)

Example: 123456789 = 075B CD 15(16)

T4 bits # 15…14

bits # 13…00

Short Unsigned float (16 bit)

Decade Exponent(Unsigned 2 bit)

Binary Unsigned Value (14 bit)

Example: 10000*102 = A710(16)

T16 Unsigned Value (16 bit), 2 decimal places

Example: 123.45 = 3039(16)

T17 Signed Value (16 bit), 2 decimal places

Example: -123.45 = CFC7(16)

8.4 100% VALUE CALCULATIONS

Un = (R40147 / R40146) * R30015 * R40149

In = (R40145 / R40144) * R30017 * R40148

Pn = Un*In

It = In ; for Connection Mode: 1b

It = 3*In ; for Connection Modes: 3b, 4b, 3u, 4u

Pt = Pn ; for Connection Mode: 1b

Pt = 3*Pn ; for Connection Modes: 3b, 4b, 3u, 4u

Fn = R40150

Page 55: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

Technical Manual M2x3C+I500C/EN M/D iSTAT M2x3 & I500 Modbus & DNP3.0

Page 53

Register Content

30015 Calibration voltage

30017 Calibration current

Register Content Data Ind Values / Dependencies Min Max

P. Level

40143 Connection Mode

T1 0 No mode 1 5 2

1 1b - Single Phase

2 3b - 3 phase 3 wire balanced

3 4b - 3 phase 4 wire balanced

4 3u - 3 phase 3 wire unbalanced

5 4u - 3 phase 4 wire unbalanced

40144 CT Secondary T4 mA 2

40145 CT Primary T4 A/10 2

40146 VT Secondary T4 mV 2

40147 VT Primary T4 V/10 2

40148 Current input range (%)

T16 10000 for 100% 5,00 200,00 2

40149 Voltage input range (%)

T16 10000 for 100% 2,50 100,00 2

40150 Frequency nominal value

T1 Hz 10 1000 2

Page 56: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

M2x3C+I500C/EN M/D Technical Manual Page 54

iSTAT M2x3 & I500 Modbus & DNP3.0

9. RELATED DOCUMENTS

Ref Document Title

1 PI-MBUS-300 Rev. E Modicon Modbus Protocol Reference Guide

2 QDSP EN/M iSTAT Configuration and Analysis Software Manual

Page 57: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.
Page 58: Front Cover Template - GE Grid Solutions€¦ · 8.1 DNP 3.0 DEVICE PROFILE DOCUMENT 48 8.2 DNP3.0 REGISTER MAP 50 8.3 DATA TYPES − DECODING 52 8.4 100% VALUE CALCULATIONS 52 9.

PXXX Product Description

Alstom Grid

© - ALSTOM 2014. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice.

Alstom Grid Worldwide Contact Centre

www.grid.alstom.com/contactcentre/

Tel: +44 (0) 1785 250 070

www.alstom.com

GRID


Recommended