ORNL is managed by UT-Battelle for the US Department of Energy FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data Air Handling Unit Fans with Varying Air Filtration David Fugate March 01, 2017
Transcript
Page 1: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

ORNL is managed by UT-Battelle

for the US Department of Energy

FRP #1 Air Handling Fault

Testing Notes for June 24 &

30 Data

Air Handling Unit Fans with

Varying Air Filtration

David Fugate

March 01, 2017

Page 2: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

2 Presentation_name

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Outline

1. Summary of Testing

2. Data File Description

3. Example Plots

4. Appendix

Page 3: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

3 Presentation_name

June 24 Summary of Testing

1. Return duct filtration was recently installed on the FRP#1 air handling systems.

2. On June 24, tests were performed with varying filtration conditions. See appendix.

1. AHU-1 & 2 with the same TRI-PLEAT filter.

2. AUH-2 with the TRI-PLEAT filter and AHU-1 without a filter.

3. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with one small paper

square flow blockage.

4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper

squares of flow blockage.

5. AUH-2 with the TRI-PLEAT filter and AHU-1 with the GlasFlos filter.

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 4: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

4 Presentation_name

June 24 Data File Description

Richman Surrey Data Collection System Data Files:

1. Test#1 7:02am – 7:15am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with TRI-PLEAT Filter (MERV 8).

2. Test#2 7:20am – 7:32am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with no filter.

3. Test#3 7:40am – 7:50am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with TRI-PLEAT Filter (MERV 8) and one small paper square for blockage.

4. Test#4 8:40am – 8:55am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with TRI-PLEAT Filter (MERV 8) and two small paper squares for blockage.

5. Test#5 9:00am – 9:10am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with GlasFlos filter (MERV 5).

6. FRP#1 Instrumentation

1. Building Power, HVAC Power for June 24 - FRP1_HVAC_PWR_Only_June24.xls

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 5: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

5 Presentation_name

June 30 Summary of Testing

1. Return duct filtration was recently installed on the FRP#1 air handling systems.

2. On June 30, tests were performed with varying filtration conditions. See appendix.

1. AUH-2 with the TRI-PLEAT filter and AHU-1 with the GlasFlos filter.

2. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with one small paper & one large paper square flow

blockage.

3. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with one small paper & two large paper squares flow

blockage.

4. AUH-2 with the TRI-PLEAT filter and AHU-1 with the GlasFlos filter with one small paper square flow blockage.

5. AUH-2 with the TRI-PLEAT filter and AHU-1 with the GlasFlos filter with one small paper square and one large paper

square flow blockage.

6. AUH-2 with the TRI-PLEAT filter and AHU-1 with the GlasFlos filter with one small paper square and two large paper

squares flow blockage.

7. AUH-2 with the TRI-PLEAT filter and AHU-1 with the GlasFlos filter with one small paper square and three large

paper squares flow blockage.

8. AHU-1 & 2 with the same TRI-PLEAT filter.

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 6: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

6 Presentation_name

June 30 Data File Description

Richman Surrey Data Collection System Data Files:

1. Test#6 7:15am – 7:25am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with GlasFlos Filter (MERV 5).

2. Test#7 7:30am – 7:35am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with TRI-PLEAT Filter (MERV 8) & 1 small paper & 1 large paper blockage.

3. Test#8 7:40am – 7:45am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with TRI-PLEAT Filter (MERV 8) & 1 small paper & 2 large paper blockage.

4. Test#9 7:48am – 7:50am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with GlasFlos Filter (MERV 5) & 1 small paper blockage

5. Test#10 7:52am – 7:55am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with GlasFlos Filter (MERV 5) & 1 small paper & 1 large paper blockage.

6. Test#11 7:57am – 8:00am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with GlasFlos Filter (MERV 5) & 1 small paper & 2 large paper blockage.

7. Test#12 8:01am – 8:05am

1. AHU-2 with TRI-PLEAT Filter (MERV 8).

2. AHU-1 with GlasFlos Filter (MERV 5) & 1 small paper & 3 large paper blockage.

8. Test#13 8:07am

1. AHU-2 & AHU-1 with TRI-PLEAT Filter (MERV 8).

1. FRP#1 Instrumentation

1. Building Power, HVAC Power for June 24 -

FFRP1_HVAC (June24 - 30).xls

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 7: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

7 Presentation_name

Test 1 Data – AHU-1 & 2 Current Signals

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 8: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

8 Presentation_name

Test 2 Data – AHU-1 & 2 Current Signals

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 9: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

9 Presentation_name

Test 3 Data – AHU-1 & 2 Current Signals

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 10: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

10 Presentation_name

Test 4 Data – AHU-1 & 2 Current Signals

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 11: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

11 Presentation_name

Test 5 Data – AHU-1 & 2 Current Signals

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 12: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

12 Presentation_name

Appendix

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 13: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

13 Presentation_name

TRI-PLEAT Filter Information

1. Fiberglass Pleated, MERV 8 2. 12”x 24” x 1” Thick

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 14: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

14 Presentation_name

GlasFloss Filter Information

1. Fiberglass, MERV 5 2. 12”x 24” x 1” Thick

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration

Page 15: FRP #1 Air Handling Fault Testing Notes for June 24 & 30 ...square flow blockage. 4. AUH-2 with the TRI-PLEAT filter and AHU-1 with same filter with two small paper squares of flow

15 Presentation_name

Filter Blockage Information

1. Each filter is 12” x 24” x 1” 1. 288 Square Inches

2. Small paper square is 5.625 square inches 3. Large paper square is 15.75 square inches 4. Filter Blockage Combinations

Combination Filter Area

(Sq Inches)

Filter Area %

No Blockage 288 100%

1 small paper square 282.4 98%

2 small paper square 276.8 96%

1 small paper square

& 1 large paper square

266.6 93%

1 small paper square

& 2 large paper square

250.9 87%

1 small paper square

& 3 large paper square

235.1 82%

FRP #1 Air Handling Fault Testing Notes for June 24 & 30 Data

Air Handling Unit Fans with Varying Air Filtration