FT SERIES-LONG LIFE 1 Nominal Voltage Approx Weight Max. Discharge Current Internal Resistance Operating Temp.Range Nominal Operating Temp. Range Self Discharge Terminal Container Material 12V 0 0 at 25 C(77 F) and then a freshening charge is required. For higher temperatures the time interval will be shorter. Specification Cycle Use Standby Use Initial Charging Current less than 37.5A.Voltage 0 0 0 14.4V~15.0V at 25 C(77 F)Temp. Coefficient -30mV/ C No limit on Initial Charging Current Voltage 0 0 0 13.5V~13.8V at 25 C(77 F)Temp. Coefficient -20mV/ C Capacity affected by Temperature 103% 100% 86% o o 40 C (104 F) o o 25 C ( 77 F) o o 0C ( 32 F) Nominal Capacity(8HR) 125.0AH Dimension Length Width Container Height Total Height (with Terminal) Rated Capacity 0 0 (20hr ,1.80V/cell,25 C/77 F) 0 0 (10hr,1.80V/cell,25 C/77 F) 0 0 (8hr,1.80V/cell,25 C/77 F) 0 0 (5hr,1.75V/cell,25 C/77 F) ABS Approx 41.5 Kg (91.5 Ibs) T6 1100A (5s) Approx 3.2mÙ 0 0 25 3 C (77 5 F ) 551 3mm (21.69 inches) 110 2mm (4.33 inches) 287 3mm (11.30 inches) 287 3mm (11.30 inches) 0 0 (1hr,1.67V/cell,25 C/77 F) For standard 19 inches or 23 inches power cabinets Network connection equipment of communication system Power system of special network or local area network UPS, standby power supply Power station systems Railway and marine systems Applications 0 0 Discharge : -15 50 C (5 122 F) 0 0 Charge : 0 40 C (32 104 F ) 0 0 Storage : -15 40 C (5 104 F) 0 0 Constant Current Discharge (Amperes) at 25 C (77 F ) 0 0 Constant Power Discharge (Watts/cell) at 25 C (77 F ) FT series batteries may be stored for up to 6 months FT12125(12V125AH) F.V/Time 1.85V/cell 1.80V/cell 1.75V/cell 1.70V/cell 1.67V/cell 1.60V/cell 10min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h 20min 405.9 341.8 296.3 234.9 183.7 149.9 90.0 65.0 52.4 43.5 37.9 29.7 24.8 13.2 454.8 375.8 323.1 253.2 196.1 159.1 94.3 68.8 54.8 45.5 39.7 31.1 25.9 13.7 491.2 401.8 341.6 263.9 201.7 164.0 95.7 69.6 56.0 46.4 40.2 31.4 26.2 13.9 513.7 417.4 352.7 270.1 203.6 165.7 96.9 70.2 56.3 46.5 40.6 31.8 26.4 14.0 529.5 426.0 358.5 273.0 205.6 166.0 97.0 70.4 56.6 47.0 41.0 32.2 26.6 14.1 541.3 433.6 369.3 276.2 208.8 168.6 97.8 71.4 57.5 48.0 41.6 32.8 27.1 14.1 1.85V/cell 1.80V/cell 1.75V/cell 1.70V/cell 1.67V/cell 1.60V/cell F.V/Time 10min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h 20min 217.4 181.2 155.5 122.0 94.6 76.9 45.9 33.0 26.5 21.9 19.1 14.9 12.4 6.57 246.5 202.0 172.1 133.5 101.8 82.1 48.4 35.1 27.9 23.1 20.1 15.6 13.0 6.87 270.5 218.6 183.7 140.3 105.7 85.0 49.3 35.7 28.6 23.6 20.4 15.8 13.1 6.98 289.3 230.2 191.1 144.4 108.1 86.1 50.0 36.1 28.8 23.8 20.6 16.0 13.3 7.03 299.4 236.0 195.0 146.2 108.5 86.5 50.1 36.3 29.0 24.0 20.9 16.3 13.4 7.06 314.7 245.0 203.8 149.9 111.4 88.8 51.0 37.0 29.6 24.6 21.3 16.6 13.6 7.10 137.4 AH/6.87A 130.0 AH/13.0A 125.0 AH/15.6A 118 AH/23.6A 86.5 AH/86.5A
Transcript
Page 1: FT SERIES-LONG LIFE - Triathlon System

FT SERIES-LONG LIFE

1

Nominal Voltage

Approx Weight

Max. Discharge Current

Internal Resistance

Operating Temp.Range

Nominal Operating Temp. Range

Self Discharge

Terminal

Container Material

12V

0 0at 25 C(77 F) and then a freshening charge is required.For higher temperatures the time interval will be shorter.

Specification

Cycle Use

Standby Use

Initial Charging Current less than 37.5A.Voltage 0 0 014.4V~15.0V at 25 C(77 F)Temp. Coefficient -30mV/ C

No limit on Initial Charging Current Voltage 0 0 013.5V~13.8V at 25 C(77 F)Temp. Coefficient -20mV/ C

Capacity affected by

Temperature

103%

100%

86%

o o 40 C (104 F)o o 25 C ( 77 F)

o o 0 C ( 32 F)

Nominal Capacity(8H R) 125.0AH

Dimension

Length

Width

Container Height

Total Height (with Terminal)

Rated Capacity

0 0(20hr ,1.80V/cell,25 C/77 F)0 0(10hr,1.80V/cell,25 C/77 F)0 0(8hr,1.80V/cell,25 C/77 F)0 0(5hr,1.75V/cell,25 C/77 F)

ABS

Approx 41.5 Kg (91.5 Ibs)

T6

1100A (5s)

Approx 3.2mÙ

0 025 3 C (77 5 F )

551 3mm (21.69 inches)

110 2mm (4.33 inches)

287 3mm (11.30 inches)

287 3mm (11.30 inches)

0 0(1hr,1.67V/cell,25 C/77 F) For standard 19 inches or 23 inches

power cabinets

Network connection equipment

of communication system

Power system of special network

or local area network

UPS, standby power supply

Power station systems

Railway and marine systems

Applications

0 0Discharge : -15 50 C (5 122 F)0 0Charge : 0 40 C (32 104 F )0 0Storage : -15 40 C (5 104 F)

0 0Constant Current Discharge (Amperes) at 25 C (77 F )

0 0Constant Power Discharge (Watts/cell) at 25 C (77 F )

FT series batteries may be stored for up to 6 months

FT12125(12V125AH)

F.V/Time

1.85V/cell

1.80V/cell

1.75V/cell

1.70V/cell

1.67V/cell

1.60V/cell

10min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h20min

405.9 341.8 296.3 234.9 183.7 149.9 90.0 65.0 52.4 43.5 37.9 29.7 24.8 13.2

454.8 375.8 323.1 253.2 196.1 159.1 94.3 68.8 54.8 45.5 39.7 31.1 25.9 13.7

491.2 401.8 341.6 263.9 201.7 164.0 95.7 69.6 56.0 46.4 40.2 31.4 26.2 13.9

513.7 417.4 352.7 270.1 203.6 165.7 96.9 70.2 56.3 46.5 40.6 31.8 26.4 14.0

529.5 426.0 358.5 273.0 205.6 166.0 97.0 70.4 56.6 47.0 41.0 32.2 26.6 14.1

541.3 433.6 369.3 276.2 208.8 168.6 97.8 71.4 57.5 48.0 41.6 32.8 27.1 14.1

1.85V/cell

1.80V/cell

1.75V/cell

1.70V/cell

1.67V/cell

1.60V/cell

F.V/Time 10min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h20min

217.4 181.2 155.5 122.0 94.6 76.9 45.9 33.0 26.5 21.9 19.1 14.9 12.4 6.57

246.5 202.0 172.1 133.5 101.8 82.1 48.4 35.1 27.9 23.1 20.1 15.6 13.0 6.87

270.5 218.6 183.7 140.3 105.7 85.0 49.3 35.7 28.6 23.6 20.4 15.8 13.1 6.98

289.3 230.2 191.1 144.4 108.1 86.1 50.0 36.1 28.8 23.8 20.6 16.0 13.3 7.03

299.4 236.0 195.0 146.2 108.5 86.5 50.1 36.3 29.0 24.0 20.9 16.3 13.4 7.06

314.7 245.0 203.8 149.9 111.4 88.8 51.0 37.0 29.6 24.6 21.3 16.6 13.6 7.10

137.4 AH/6.87A

130.0 AH/13.0A

125.0 AH/15.6A

118 AH/23.6A

86.5 AH/86.5A

Page 2: FT SERIES-LONG LIFE - Triathlon System

Dimensions

T6 TerminalUnit: mm [inches]

16

M6

2 3

2

0 4 8 12 16 20 24 28

Charging Time(hours)

32 36

2.0

2.1

2.2

2.3

2.4

(V/cell)(A)

0.02C

0C

0.04C

0.06C

0.08C

0.10C

%

20

40

60

80

100

120

ChargeVolume

Charging Current

Charging Voltage

After 50% Discharge

After 100% Discharge

Charge Voltage(Constant 2.25V/cell)

Charged Volume

Charging Current

00.1CA-2.25V/cell temperature25 C

Float Charging Characteristics

No supplementary charge required

(Carry out supplementary charge before use if 100% capacity is required.)

Supplementary charge required before use.Optional charging way as below:

1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.

2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.

3.Charged for 8~10hours at limted current 0.05CA .

Supplementary charge may often fail to recover the capacity.

The battery should never be left standing till this is reached.

A

B

C

Storage Time(Months)

Rem

aini

ng C

apac

ity(%

)

8 10 120

4 6

60

80

100

0 2

20

40

025 C

030 C040 C

010 C A

B

C

Self Discharge Characteristics

0.5

2

5

8

10

12

16

Charging voltage

2.25V/cell

2068

0C30

8640104

50122

OF

Battery temperature

Life

exp

ecta

ncy(

year

)

Effect of Temperature on Long Term Float Life

100.1 2 4 6 20 40 60 2 4 6 8 103.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

8.0

9.0

10.0

11.0

12.0

13.0

HMin

0.1CA0.2CA0.35CA

0.6CA1CA2.5CA

6CA

V V

6VBattery

12VBattery

0Temperature:25C

Term

inal

Vol

tage

(V)

Discharge Time

Discharge Characteristics

11

Temperature Effects in Relation to Battery Capacity

1CA

0.65CA

0.25CA

0.1CA

Ca

pa

city

%

0

20

40

60

80

100

120

-20 -10 0 10 20 30 40 50

0Temperature( C)

222