Fuel cell inverter HYDRO BOY 1124 / 1324 Technical Description HB1124-TEN093421 | 98-2001921 | Version 2.1 EN
Transcript
Page 1: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Fuel cell inverterHYDRO BOY 1124 / 1324Technical Description

HB1124-TEN093421 | 98-2001921 | Version 2.1 EN

Page 2: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The
Page 3: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Table of Contents

Technical Description HB1124-TEN093421 3

Table of Contents1 Notes on this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71.1 Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71.2 Target Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71.3 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82.1 Appropriate Usage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82.2 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103.1 Packing List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103.2 Identifying the Hydro Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113.3 Mounting the Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134.1 Selecting the Mounting Location. . . . . . . . . . . . . . . . . . . . . . . . 134.1.1 Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134.1.2 Ambient Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144.2 Mounting the Hydro Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165.1 Overview of the Connection Area . . . . . . . . . . . . . . . . . . . . . . 165.2 Connecting the Public Grid (AC) . . . . . . . . . . . . . . . . . . . . . . . 175.3 Connecting the Fuel Cell (DC) . . . . . . . . . . . . . . . . . . . . . . . . . 226 Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246.1 RS232 and RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246.2 CAN Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246.2.1 CAN Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246.2.2 "Heartbeat" Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256.2.3 CAN Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Page 4: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Table of Contents SMA Solar Technology AG

4 HB1124-TEN093421 Technical Description

6.2.4 Error Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

7 (Initial) Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308 Opening and Closing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318.1 Opening the Hydro Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318.2 Closing the Hydro Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319 Display Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329.1 Activating the Display Illumination . . . . . . . . . . . . . . . . . . . . . . 329.2 Display Messages in the Startup Phase . . . . . . . . . . . . . . . . . . 329.3 Display Messages during Operation . . . . . . . . . . . . . . . . . . . . 329.3.1 StatusMessages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339.4 Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3310 Blinking Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3710.1 Operating Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3710.1.1 All LEDs are on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3710.1.2 All LEDs are off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3710.1.3 The green LED is blinking slowly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3810.1.4 Green LED glows continuously . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3810.1.5 The green LED is blinking quickly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3810.1.6 The green LED goes out briefly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3910.2 Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3910.2.1 The red LED glows continuously . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3910.2.2 The yellow LED glows continuously. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4010.2.3 The yellow LED blinks twice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4010.2.4 The yellow LED blinks 3 times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4110.2.5 The yellow LED blinks 4 times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4210.2.6 The yellow LED blinks five times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

11 Maintenance and Care . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Page 5: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Table of Contents

Technical Description HB1124-TEN093421 5

12 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4412.1 Disassembling the Hydro Boy. . . . . . . . . . . . . . . . . . . . . . . . . . 4412.2 Packing the Hydro Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4412.3 Storing the Hydro Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4412.4 Disposing of the Hydro Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . 4413 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4513.1 Checking/Replacing Varistors . . . . . . . . . . . . . . . . . . . . . . . . . 4514 Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4614.1 Parameter Settings for Germany. . . . . . . . . . . . . . . . . . . . . . . . 4814.2 Country-specific Parameter Settings . . . . . . . . . . . . . . . . . . . . . 4915 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5016 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Page 6: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Table of Contents SMA Solar Technology AG

6 HB1124-TEN093421 Technical Description

Page 7: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Notes on this manual

Technical Description HB1124-TEN093421 7

1 Notes on this manualThis manual describes how to mount, install, commission, operate, and maintain the Hydro Boy 1124 / 1324 (HB 1124 / HB 1324). Ensure that the Hydro Boy manual is stored in a location easily accessible at all times.

1.1 ValidityThe manual applies to the firmware version BFR 7.15, SRR 1.37, and higher.

1.2 Target GroupThis manual is intended for installers and users.

1.3 Symbols UsedThe following types of safety instructions and general information appear in this manual as described below:

DANGER!

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING!

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION!

CAUTION indicates a hazardous situation which, if not avoided, could result in minor or serious injury.

NOTICE!

NOTICE indicates a situation that can result in property damage if not avoided.InformationInformation provides tips that are valuable for the optimal installation and operation of your product.

Page 8: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Safety SMA Solar Technology AG

8 HB1124-TEN093421 Technical Description

2 Safety2.1 Appropriate UsageThe Hydro Boy is an inverter that converts the DC current from fuel cell systems or fuel cell stacks to AC current and feeds it into the available public grid. The Hydro Boy is particularly suitable for common PEM fuel cells of well-known manufacturers. However, there is no general restriction prohibiting it from use with other fuel cell technologies.Principle of a fuel cell system with Hydro Boy

The Hydro Boy may only be operated with fuel cell systems or stacks whose performance data comply with the technical data of the Hydro Boy.The Hydro Boy does not assume control of the the fuel cell system. The operator must take special preventive measures in case the Hydro Boy disconnects itself from the grid (in case of a fault or grid failure). In this case, the fuel cell can no longer deliver its output to the Hydro Boy.Make absolutely certain that when the Hydro Boy is idle (Hydro Boy does not extract any power from the fuel cell), the input voltage on the Hydro Boy does not exceed the maximum specified value.Due to its design, the input current of the Hydro Boy features a high ripple level during feeding operation. Make sure that this high ripple level does not permanently damage the connected fuel cell, or that the number of operating hours of the fuel cell is reduced by this.

Page 9: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Safety

Technical Description HB1124-TEN093421 9

2.2 Safety InstructionsDANGER!Danger to life due to high voltages in the Hydro Boy.

• All work on the Hydro Boy must be carried out by a qualified electrician.

CAUTION!Danger of burn injuries due to hot housing parts.

• Do not touch the housing of the Hydro Boy during operation.

Page 10: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Unpacking SMA Solar Technology AG

10 HB1124-TEN093421 Technical Description

3 Unpacking3.1 Packing ListCheck the packing list for completeness and the device for visible external damage, such as cracks in the housing or in the display of the Hydro Boy. If anything is missing or damaged, contact your dealer.

Object Quantity DescriptionA 1 Hydro BoyB 1 Wall mounting bracketC 1 Fan (only with HB 1324)D 2 Socket element (PG 13.5 and PG 16)E 2 Termination resistorF 1 Data transfer cableG 1 CD-Rom (Sunny Data Control)H 1 EC Declaration of ConformityI 1 Technical DescriptionJ 2 Jumper

Page 11: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Unpacking

Technical Description HB1124-TEN093421 11

3.2 Identifying the Hydro BoyYou can identify the Hydro Boy using the device type and the series number on the type label. The type label is on the right side of the housing.

Device type Series number

Page 12: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Unpacking SMA Solar Technology AG

12 HB1124-TEN093421 Technical Description

3.3 Mounting the FanAn additional fan must be installed on a Hydro Boy (HB 1324) to operate it at a constant power of over 1200 W (DC), or at an ambient temperature at the installation location of over 40 °C.Proceed as follows to install the fan on the Hydro Boy:1. Position the provided fan in the center of the cooling fins of the Hydro Boy. Leave approximately

14 cm of space on the right and left side.2. Insert the fan in the first and twelfth cooling fin on the front of the Hydro Boy housing. The fan

housing must rest on the cooling fins.3. Insert the fan plug in the socket on the front of the cooling fins. The plug will audibly snap into

place.☑ The fan is now mounted on the Hydro Boy.

Page 13: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Mounting

Technical Description HB1124-TEN093421 13

4 Mounting4.1 Selecting the Mounting Location

4.1.1 Dimensions and Weight

DANGER!Danger to life due to fire or explosion.

Despite careful construction, a fire can occur with electrical devices.Do not install the Hydro Boy

• on flammable construction materials,• in areas where highly flammable materials are stored,• or in potentially explosive areas!

Page 14: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Mounting SMA Solar Technology AG

14 HB1124-TEN093421 Technical Description

4.1.2 Ambient Conditions• The installation location and installation method must be suitable for the weight and dimensions.• Mounting on a solid surface.• The mounting location must be accessible at all times.• It must be easy to remove the Hydro Boy from the mounting location at all times.• The ambient temperature should be between –25 °C and +60 °C to ensure optimum

operation.• Do not expose the Hydro Boy to direct sunlight to avoid a power reduction due to excessive

heating.• In living areas, do not install the unit on

plasterboard walls, etc. so as to avoid audible vibrations. The Hydro Boy may make noises when in use which may be perceived as a nuisance in a living area.

• Observe the following safety clearances to walls, other devices or other objects to ensure sufficient heat dissipation. If several Hydro Boys are installed next to each other, the clearances between the individual devices must be increased.

• Vertical installation or tilted backwards by max. 45°.• Install at eye level to allow operating modes to be read at all times.

Page 15: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Mounting

Technical Description HB1124-TEN093421 15

4.2 Mounting the Hydro Boy

1. Use the wall mounting bracket as a drilling template, and mark the position of the drill holes.2. Secure the wall mounting bracket using suitable

screws and washers.

3. Attach the Hydro Boy by inserting its upper mounting slots into the wall mounting bracket.

4. Secure the Hydro Boy in position by installing a M6x10 screw.

5. Check that the unit is securely in place.

CAUTION!Risk of injury due to the heavy weight of the Hydro Boy.

• Note that the Hydro Boy weighs 29 kg.

Page 16: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Electrical Connection SMA Solar Technology AG

16 HB1124-TEN093421 Technical Description

5 Electrical Connection

5.1 Overview of the Connection Area

NOTICE!Static discharges can damage the Hydro Boy.

Internal components of the Hydro Boy can be irreparably damaged by static discharge.• Ground yourself before you touch a component.

Object DescriptionA Connection terminal for "DC+" cable of the fuel cellB Connection terminal for "DC–" cable of the fuel cellC "COM" connection socket for RS232 or RS485 communicationD "CAN1" connection socket for CAN communicationE "CAN2" connection socket for CAN communicationF AC socket for grid connection

Page 17: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Electrical Connection

Technical Description HB1124-TEN093421 17

5.2 Connecting the Public Grid (AC)Connection regulations

• Observe the connection regulations of your grid operator.• The Hydro Boy must have a three-cable connection to the gird (PE, N, L).• The grid connection terminals on the AC connection socket included in the accessories kit can

take cables with a cross-section of up to 2.5 mm2. If you would like to connect a cable with a diameter of 9 to 13.5 mm, you must use the PG 13.5 connection socket provided. When connecting a cable with a diameter of 13.5 to 17 mm, the PG 16 connection socket provided must be used.

Cable requirements

Cable designAC grid impedance should not exceed 1 Ohm. This is required for the correct operation of impedance monitoring.The cable cross-section should be sized using the "Sunny Design" design program (www.SMA.de/en) so that line losses do not exceed 1 % at nominal power. The maximum cable lengths, depending on the cable cross-section, are shown in the following table. Do not exceed the maximum cable length.

Object DescriptionA Outer diameter: 9 - 17 mmB Cable cross section: max. 2.5 mm2

C Stripping length : approx. 12 mmPE conductorThe PE conductor must be 5 cm longer than the N and L conductors.

Cable cross-section Max. cable length1.5 mm2 21 m2.5 mm2 35 m

Page 18: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Electrical Connection SMA Solar Technology AG

18 HB1124-TEN093421 Technical Description

Connection procedure for the PG 13.5 AC connection socket1. Test the grid voltage and compare it with the permitted voltage range

(see section 15 „Technical Data“ (50)).

2. Slide the pressure screw over the AC cable.

3. Press the seal ring into the fastening case and slide it over the AC cable.

4. Slide the threaded sleeve over the AC cable.

5. Insert the protective earth PE (green-yellow) in the screw terminal with the ground symbol on the socket element and tighten the screw.

6. Insert the neutral conductor N (blue) in screw terminal 1 on the socket element and tighten the screw.

7. Insert the live wire L (brown or black) in screw terminal 2 and tighten the screw.

8. Do not use screw terminal 3.

DANGER!Danger to life due to high voltages in the Hydro Boy.

• Switch off the line circuit breaker and secure it to prevent it from being reactivated.• Make sure that no voltage is present in the device.

Page 19: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Electrical Connection

Technical Description HB1124-TEN093421 19

9. Screw the threaded sleeve onto the socket element.

10. Screw the pressure screw tightly onto the threaded sleeve. The fastening case with the seal ring is pressed into the threaded sleeve and can no longer be seen.

11. Close the socket element with the cap supplied in the accessories kit if the Hydro Boy is not being connected immediately.

12. Remove the protecting cap of the flange plug on the Hydro Boy.13. Connect the AC connection socket to the flange plug on the Hydro Boy.14. Firmly tighten the threaded ring on the AC connection socket onto the flange plug. The threaded

ring is used to seal and provide strain relief for the AC connection socket.

DANGER!Danger to life due to high voltages in the Hydro Boy..

When laying the AC cable, the PE conductor and the other conductors can be extracted from the socket element after they have been connected.

• Make sure the connection wires are securely connected.

• Do not bend the AC cable once it has been connected.

• Do not subject the socket element to heavy loads.

DANGER!Danger to life due to high voltages in the Hydro Boy.

• Only switch on the line circuit breaker after all cables on the Hydro Boy have been connected.

Page 20: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Electrical Connection SMA Solar Technology AG

20 HB1124-TEN093421 Technical Description

Connection procedure for the PG 16 AC connection socket1. Slide the PG16 cable gland with the pressure screw over the AC cable.2. Slide the threaded sleeve over the AC cable.

3. Insert the protective earth PE (green-yellow) in the screw terminal with the ground symbol on the socket element and tighten the screw.

4. Insert the neutral conductor N (blue) in screw terminal 1 on the socket element and tighten the screw.

5. Insert the live wire L (brown or black) in screw terminal 2 and tighten the screw.

6. Do not use screw terminal 3.

DANGER!Danger to life due to high voltages in the Hydro Boy.

When laying the AC cable, the PE conductor and the other conductors can be extracted from the socket element after they have been connected.

• Make sure the connection wires are securely connected.

• Do not bend the AC cable once it has been connected.

• Do not subject the socket element to heavy loads.

Page 21: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Electrical Connection

Technical Description HB1124-TEN093421 21

7. Screw the threaded sleeve onto the socket element.

8. Screw the PG16 cable gland with the pressure screw (B) tightly onto the threaded sleeve (A).

9. Close the socket element with the cap supplied in the accessories kit if the Hydro Boy is not being connected immediately.

10. Remove the protecting cap of the flange plug on the Hydro Boy.11. Connect the AC connection socket to the flange plug on the Hydro Boy.12. Firmly tighten the threaded ring on the AC connection socket onto the flange plug. The threaded

ring is used to seal and provide strain relief for the AC connection socket.DANGER!Danger to life due to high voltages in the Hydro Boy.

• Only switch on the line circuit breaker after all cables on the Hydro Boy have been connected.

Page 22: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Electrical Connection SMA Solar Technology AG

22 HB1124-TEN093421 Technical Description

5.3 Connecting the Fuel Cell (DC)The following thresholds at the DC input of the Hydro Boy must not be exceeded:

• Max. input voltage: 60 V (DC)• Max. input current: 56 A (DC)

Cable RequirementsFor the connection of the fuel cell, use a cable with a cross-section of 25 mm2. The cable must be suitable for ambient temperatures of up to 110 °C.

Connection procedure for the fuel cell1. Check the connection cable of the fuel cell for correct polarity and that the maximum input

voltage of the Hydro Boy is not exceeded.2. Open the Hydro Boy. Remove the lid screws and the lid. 3. Unscrew the lock nut from the cable screw connection (A), and slide it over the "DC+" cable of

the fuel cell.4. Pull the "DC+" cable of the fuel cell through the cable screw connection into the inside of the

Hydro Boy, and connect it to the "DC+" connection terminal (B).5. Unscrew the lock nut from the cable screw connection (C), and slide it over the "DC–" cable of

the fuel cell.6. Pull the "DC–" cable of the fuel cell through the cable screw connection into the inside of the

Hydro Boy, and connect it to the "DC–" connection terminal (D).7. Tighten the lock nut of the cable screw connection.

Notice!Damage of the DC cable due to overheating.

Cables that are not suitable for ambient temperatures of up to 110 °C may be damaged due to overheating with respect to the maximum temperatures inside the Hydro Boy.

• Use cables of the type "H07G-K" or similar for the connection of the fuel cell.

Page 23: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Electrical Connection

Technical Description HB1124-TEN093421 23

Page 24: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Communication SMA Solar Technology AG

24 HB1124-TEN093421 Technical Description

6 Communication6.1 RS232 and RS485The Hydro Boy can communicate with a PC through a RS232 or RS485 interface. When using the RS232 interface, the cable between the PC and Hydro Boy can have a maximum length of 15 m.Requirements

• The communication interface is installed in the Hydro Boy• Sunny Data Control is installed correctly• Use the interface converter if the PC is equipped with a USB port

Procedure for connecting the device to a PC1. Connect the provided data transfer cable to the "COM" port of the Hydro Boy.2. Connect Hydro Boy to the PC using the data transfer cable.☑ The Hydro Boy is connected to the PC, and can be commissioned as described in section

7 „(Initial) Start-Up“ (30).

6.2 CAN Communication

The Hydro Boy is equipped with a CAN interface that, for example, allows it to communicate with a PC. Specific formats and functions have been defined for the CAN data transfer. They are explained in more detail in the following sections. A CAN bus baud rate of 500 kBit/s is used.Connection layout of the CAN interface on the "CAN1" and "CAN2" connection socket

6.2.1 CAN TerminationThe CAN bus system must be terminated using a termination resistor. If the CAN bus system is incorrectly or not terminated, the Hydro Boy may only operate at a limited capacity or not at all.If only one connection is occupied, the unused connection must be fitted with a termination resistor. The termination resistors are included in the delivery.If the CAN communication is not used, both connections must be fitted with termination resistors.

CAN interfaceThe CAN interface design is not safely isolated.

CAN High Pin 7CAN Low Pin 2CAN GND Pin 3

Page 25: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Communication

Technical Description HB1124-TEN093421 25

6.2.2 "Heartbeat" FunctionIf, for example, the PC does not receive any values from the Hydro Boy within the time period defined in the "Timeout CAN" parameter, the Hydro Boy is switched off.If you do not want to use the "Heartbeat" function, the "Timeout CAN" parameter must be set to 0.Proceed as described in section 7 „(Initial) Start-Up“ (30) to restart the Hydro Boy.

6.2.3 CAN ProtocolThe CAN protocol contains the CAN identifier used and the cyclically transmitted PDOs (Process Data Objects). The process data (a PDO (tx) in each case) is cyclically transmitted with varying contents. A telegram with an ascending ID is transmitted during the next cycle. The process is repeated after the last telegram.PDO telegrams (tx)

Up to four data fields are transferred in one PDO (tx) (parameters are transferred in Motorola format).

Designation Identifier (HEX) DescriptionID_CAN_SERVICE_BFR_PDO_TX 0x90 DC data, E-total

0x91 AC data, H_mode0x92 Error code, operating mode,

temperature0x93 Zac, dZac, Fac, Riso

CAN ID Word 1 Word 2 Word 3 Word 4BYTE 1 BYTE 2 BYTE 3 BYTE 4 BYTE 5 BYTE 6 BYTE 7 BYTE 8

ID_CAN_SERVICE_BFR_PDO_TX

PARA_NR#1 PARA_NR#2 PARA_NR#3 PARA_NR#4

Page 26: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Communication SMA Solar Technology AG

26 HB1124-TEN093421 Technical Description

Definition of PDO (tx)Designation Parameter Data range / unit Scaling Data type / description0x90 CBS_DATA_SET1

UDC 0 - 1000 V *10 WORD input voltage (example: 455 = 45.5 V)

IDC 0 - 100 A *10 WORD input current (example: 102 = 10.2 A)

PDC 0 - 3000 W - WORD input powerE_Total 0 - 65535 kWh - WORD accumulated energy

fed into the grid0x91 CBS_DATA_SET2

UAC 0 - 300 V *10 WORD output voltage (example: 2375 = 237.5 A)

IAC 0 - 15000 mA - WORD output currentPAC 0 - 3000 W - WORD output powerH_ON 0 - 65535 - WORD operating hours

0x92 CBS_DATA_SET3E_Code - - WORD error codeSTATUS - - WORD operating modeTEMP_TKK 0 - 120 °C - WORD temperature

(example 35 = 35 °C)ERRORSTACK 0 - 255 - HIGH BYTE error numberHB MODE Enabling type

(0 - 1)- LOW BYTE HB in feeding

operation0x93 CBS_DATA_SET4

ZAC 0 - 30000 mOhm -dZac –5000 -

+5000 mOhm- (The CAN measured value is

transferred using an offset of +5000 mW, i.e. the display range is between 0 and 10000 mOhm)

FAC 0 - 100 *100 WORD grid frequencyRiso 0 - 3000 kOhm Insulation resistance in kOhm.

Page 27: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Communication

Technical Description HB1124-TEN093421 27

PDO telegrams (rx)

A maximum of four parameters can be set in a PDO (rx).

DefinitionThe "ENABLING" parameter must be sent in each telegram. The "Heartbeat" is sent using this parameter.The following parameter numbers (PARA_NO#) are currently supported:

Depending on the capacity at which the processor is operating, the cycle time can slightly vary (several ms). The thresholds and the parameters set in the Sunny Data Control are valid for all parameters. The software ignores invalid thresholds.

Designation Identifier (HEX) DescriptionID_CAN_SERVICE_BFR_PDO_RX 0x80 PDO from control computer

CAN ID Word 1 Word 2 Word 3 Word 4BYTE 1 BYTE 2 BYTE 3 BYTE 4 BYTE 5 BYTE 6 BYTE 7 BYTE 8

ID_CAN_SERVICE_BFR_PDO_RX

PARA_NR#1 ENABLING PARA_VAL# GET_ERROR RESERVE1

Designation Value DescriptionNone 0 -DCVtgStr 1 Start voltage DC (in volts)DCCurSt_Pt 4 Current ramp (in mA/s *10)DCCurStpt 6 Nominal current value (in mA/s *10)DCVtgMin 41 Min. DC voltagePwrMax 11 Max. AC output (in W)DCVtgMax 15 Voltage limit (UDC, max)ImpIsoMin 22 Insulation resistance (in kOhm)ComTm 47 CAN Timeout (in s)

Page 28: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Communication SMA Solar Technology AG

28 HB1124-TEN093421 Technical Description

6.2.4 Error MemoryA FIFO error memory with a maximum of 16 entries is implemented in the Hydro Boy. The memory can be sequentially read out using CAN.The errors are consecutively saved along with the corresponding error number in the memory. If more than 16 errors occur within a query period, the oldest messages are overwritten.Entering errorsIf an error from the error table occurs, the software enters the error number in the error stack at the location where the writing pointer is located. The error is incremented so that it points to the next position. The reading pointer is not incremented. If the writing pointer points to the last position in the stack, the writing pointer will be set to the first position upon the next error entry.Reading out errorsIf a 1 is sent by the PDO (rx) using the "GET_ERROR" parameter, the next valid error number on the PDO (tx) (CBS_DATA_SET3) is defined in the "ERRORSTACK" channel and can be evaluated. The signal in the PDO is displayed as long as a 1 is sent using "GET_ERROR". After the control system has read out and/or evaluated the error, a 0 can be sent. In the next PDO (CBS_DATA_SET3), the "ERRORSTACK" channel displays a 0.The software of the Hydro Boy increments the reading pointer of the error memory after the error has been read out. If the memory contains another error, it can be read out. If the error memory is empty, a 0 is returned. Now, the reading pointer is no longer incremented. The error memory is empty after it has been switched off. It cannot be saved.Error codeDescription Value DesignationNo error 0 -Measurement difference between BFR and SRR regarding grid voltage 1 NUW-UACMeasurement difference between BFR and SRR regarding grid frequency 2 NUW-FACMeasurement difference between BFR and SRR regarding grid impedance 3 NUW-ZACError during relay test 4 K1-TrennAverage value of the grid voltage is too high 5 U-St-SchutzThe EEPROM cannot be accessed 6 EEPROM dbhError during memory test 7 ROMThe EEPROM cannot be accessed (parameter) 13 EeRestoreV/l offset adjustment failed 18 OFFSETThe EEPROM cannot be accessed 19 EEPROMCommunication between both computers is interrupted 20 Bfr-SrrError during relay test 21 K1-SchliessError in the program flow monitoring 22 WatchdogInput voltage is above permitted maximum value 24 UdcMax

Page 29: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Communication

Technical Description HB1124-TEN093421 29

Operating mode

Insulation resistance, value outside tolerance 25 RisoHeartbeat remained off longer than the time set under the "CAN-ComTime" parameter

26 Timeout CAN

BFR grid frequency voltage, value outside tolerance 28 Uac-BfrBFR grid impedance measurement, value outside tolerance 29 Fac-BfrBFR grid impedance measurement, value outside tolerance 30 Zac-BfrBFR grid impedance measurement, value outside tolerance 31 dZac-BfrDevice-internal overcurrent 56 ImaxPower transistor lock 57 Shut-DownSRR grid voltage measurement, value outside tolerance 59 Uac-SrrSRR grid frequency measurement, value outside tolerance 60 Fac-SrrSRR grid impedance measurement, value outside tolerance 61 Zac-SrrSRR grid impedance measurement, value outside tolerance 62 dZac-SrrCommunication between both computers is interrupted 63 NUW-Timeout

Designation Value (HEX) DescriptionZ_BFR_INIT 0xFFFF Initialization statusZ_BFR_STOP 0x0001 Stop statusZ_BFR_OFFS 0x0002 Offset Calibration statusZ_BFR_WARTEN 0x0004 Waiting statusZ_BFR_TEST_NUW 0x0008 Grid monitoring text statusZ_BFR_KONST_U 0x0010 l-Const status (constant current mode)Z_BFR_U-KONST 0x0020 U-Const status (constant voltage mode)Z_BFR_DERATING 0x0040 Derating statusZ_BFR_STOERUNG 0x0080 Failure statusZ_BFR_FEHLER 0x0100 Error status

Description Value Designation

Page 30: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

(Initial) Start-Up SMA Solar Technology AG

30 HB1124-TEN093421 Technical Description

7 (Initial) Start-UpCheck the following requirements before (initial) start-up:

• Secure fit on wall mounting bracket• Full connection of the DC cables (fuel cell)• Correct connection of the AC cable (public grid)• Correct termination of CAN communication• All housing openings are sealed• The housing lid is securely screwed in place• Connection to the PC via RS232 or RS485

Procedure for (initial) start-up1. Switch on line circuit breaker and start fuel cell.2. Detect Hydro Boy using the provided Sunny Data Control software as described in the

Sunny Data Control documentation.3. Select type of communication (RS485 or RS232).4. Set the baud rate to 1200.5. Set the "EnOp" parameter to 1.

The Hydro Boy now begins to operate. An illuminated green LED signals fault-free feeding operation.

6. Set the "DCCurChgSp" parameter to the required value.7. Set the "DCCurSt_Pt" parameter to the required value.☑ (Initial) start-up is complete.

Page 31: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Opening and Closing

Technical Description HB1124-TEN093421 31

8 Opening and Closing8.1 Opening the Hydro Boy

1. Unscrew the lid screws and set them aside.2. Pull the lid slightly forward.3. Disconnect the PE connection from the lid.4. Remove the lid and set it aside.

8.2 Closing the Hydro Boy1. Establish the PE connection to the lid.2. Close the Hydro Boy. Fasten the lid to the housing using four screws.3. Switch on the line circuit breaker.4. Look at the LED display to check whether the Hydro Boy is in a fault-free operating status.

DANGER!Danger to life due to high voltages in the Hydro Boy.

• Switch off the line circuit breaker and secure it to prevent it from being reactivated.• Make sure that no voltage is present in the device.

DANGER!Danger to life due to high voltages in the Sunny Boy.

• Wait 5 minutes for the capacitors to discharge.

Page 32: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Display Messages SMA Solar Technology AG

32 HB1124-TEN093421 Technical Description

9 Display Messages9.1 Activating the Display IlluminationThe background illumination is switched on by tapping on the lid. Tapping again switches the display to the next message.After 2 minutes, the illumination switches off automatically.

9.2 Display Messages in the Startup Phase

9.3 Display Messages during OperationThe display shows the most important operation data of the Hydro Boy in a continuous cycle. The following diagrams serve to clarify the messages. Every message is displayed for 5 seconds. Then the cycle begins again.

Display screen DescriptionInverter nameDevice type

Firmware version of the operation control unit (BFR)Firmware version of the current control unit (SRR)

Display screen DescriptionCurrent feed-in powerFuel cell voltage

Energy generated by the Hydro Boy (total)Operating hours (total)

Energy generated todayEnergy generated yesterday

StatusWeekdayTime

Page 33: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Display Messages

Technical Description HB1124-TEN093421 33

9.3.1 StatusMessages

9.4 Error Messages

Display screen Meaning DescriptionStop StopOffset Calibration Self-test and if necessary, calibration of

measurement electronicsWait Waiting The Hydro Boy checks whether the initial

conditions necessary for feeding electricity into the grid are satisfied (e.g. start voltage, start time) and then begins monitoring the grid.

GridMon Grid monitoring

DCCurMod Constant current operation

Standard grid feeding mode. The Hydro Boy controls the DC input current according to the nominal current value, which can be specified using the "DCCurStPt" parameter.

DCVtgMod Constant voltage mode If the DC input current falls below the value specified using the "DCVtgMin" parameter, the input current is no longer controlled, but rather the input voltage. This is intended to prevent the input voltage from dropping further.

Disturbance Disturbance Is displayed if a fault occurs.Failure Error Is displayed if an error occurs.

Name Cause / description RemedyF-Bfr-Srr Communication error

Error during the data transfer between both processors

If the error occurs frequently, contact SMA Serviceline.

F-dZac-Srr Grid impedance errorThe grid impedance changes so that the permitted threshold is exceeded.

-

F-dZac-Srr Grid impedance errorExcessive grid impedance.

-

F-EEPROM Memory errorTransmission error when reading or writing EEPROM

If the error occurs frequently, contact SMA Serviceline.

F-EEPROM dBh Memory errorData loss due to faulty memory (EEPROM)

If the error occurs frequently, contact SMA Serviceline.

Page 34: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Display Messages SMA Solar Technology AG

34 HB1124-TEN093421 Technical Description

F-EeRestore Memory errorFaulty datasetwas restored.

If the error occurs frequently, contact SMA Serviceline.

F-Fac-BfrF-Fac-Srr

Grid frequency disturbanceThe grid frequency is outside the permitted range. For safety reasons, the Hydro Boy disconnects itself from the grid.

If possible, test the grid frequency and the frequency of major fluctuations.If repeated deviations occur and this is causing these errors, ask the grid operator if he agrees to a modification of the operating parameters.Discuss the proposed parameters with the SMA Serviceline.

F-Imax OvercurrentDevice-internal overcurrent.

If the error occurs frequently, contact SMA Serviceline.

F-K1-CloseF-K1-Open

Relay errorRelay test failed.

If the error occurs frequently, contact SMA Serviceline.

F-NUW-FAC Communication errorThe frequency measurement in the device-internal processors does not match.

If the error occurs frequently, contact SMA Serviceline.

F-NUW-Timeout Communication errorCommunication fault between the two device-internal processors.

If the error occurs frequently, contact SMA Serviceline.

F-NUW-UAC Communication errorThe voltage measurement in the device-internal processors does not match.

If the error occurs frequently, contact SMA Serviceline.

F-NUW-ZAC Communication errorDie impedance measurement of the device-internal processors does not match.

If the error occurs frequently, contact SMA Serviceline.

F-OFFSET OFFSET errorOFFSET test failed.

If the error occurs frequently, contact SMA Serviceline.

Name Cause / description Remedy

Page 35: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Display Messages

Technical Description HB1124-TEN093421 35

F-Riso Insulation resistance is below the preset threshold.

• Check and if necessary, replace varistors as described in section 6.1 "Checking/Replacing Varistors" (39).

F-ROM Memory errorROM test failed.

If the error occurs frequently, contact SMA Serviceline.

F-Shut-Down Hardware errorDevice-internal hardware error.

If the error occurs frequently, contact SMA Serviceline.

F-Timeout CAN Communication errorData transfer on CAN bus interrupted.

If the error occurs frequently, contact SMA Serviceline.

F-Vac-BfrF-Vac-Srr

Grid voltage errorThe grid voltage is outside the permitted range.

• Check the grid voltage and grid connection.

If the grid voltage lies outside the permissible range because of local grid conditions, ask the grid operator if the voltages can be adjusted at the feed-in point, or if he agrees to changes in the values of the monitored operation limits.If the grid voltage is within the acceptable range, but the error is still displayed, contact the SMA Serviceline.

F-VdcMax DC overvoltageThe DC input voltage at the Hydro Boy is too high.

• Disconnect the Hydro Boy from the fuel cell immediately! Otherwise, the Hydro Boy may be irreparably damaged.

Check the DC voltage for compliance with the maximum input voltage of the Hydro Boy before you reconnect the fuel cell to the Hydro Boy.

Name Cause / description Remedy

Page 36: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Display Messages SMA Solar Technology AG

36 HB1124-TEN093421 Technical Description

F-U-St-Schutz Voltage increase protectionThe average grid voltage over 10 minutes is no longer within the permissible range.This can be caused by either of the following:

• The grid voltage at the connection point of the Hydro Boy is too high.

• The grid impedance at the connection point of the Hydro Boy is too high.

• Test the grid voltage at the connection point of the Hydro Boy.

If the grid voltage lies outside the permissible range because of local grid conditions, ask the grid operator if the voltages can be adjusted at the feed-in point, or if he agrees to changes in the values of the monitored operation limits.If the grid voltage is within the acceptable range, but the error is still displayed, contact the SMA Serviceline.

F-Watchdog Software errorThe device-internal monitoring "Watchdog" was triggered.

-

F-Zac-BfrF-Zac-Srr

Grid impedance errorExcessive grid impedance.

-

Name Cause / description Remedy

Page 37: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Blinking Codes

Technical Description HB1124-TEN093421 37

10 Blinking Codes10.1 Operating Modes

10.1.1 All LEDs are onInitializationThe Hydro Boy‘s on-board computer is currently in the initialization phase. The on-board power supply is present, but there is not sufficient energy for feeding the grid and data communication is also not yet possible.

10.1.2 All LEDs are offNo powerThe Hydro Boy is off.

All LEDs are on

All LEDs are off

Page 38: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Blinking Codes SMA Solar Technology AG

38 HB1124-TEN093421 Technical Description

10.1.3 The green LED is blinking slowlyWaiting, grid monitoringThe Hydro Boy checks whether the initial conditions necessary for feeding electricity into the grid are satisfied (e.g. start voltage, start time) and then begins monitoring the grid.

10.1.4 Green LED glows continuouslyGrid feedingThe Hydro Boy has passed the self-test of the measurement electronics and grid monitoring, and is now in normal grid-feed operation.

10.1.5 The green LED is blinking quicklyStopThe Hydro Boy is in Stop mode. Among other functions, the measurement electronics are calibrated, then the device switches to "Waiting" mode. The "Stop" operating mode can also be manually set by the system operator via the Sunny Data Control. In this case, the inverter remains in "Stop" mode until a new operating mode has been set.

The green LED blinks 1 time per second

The green LED glows continuously

The green LED blinks 3 times per second

Page 39: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Blinking Codes

Technical Description HB1124-TEN093421 39

10.1.6 The green LED goes out brieflyDeratingThe "Derating" operating mode is a normal operating mode, which may occur occasionally and can have several causes:

• Temperature derating The temperature monitoring of the Hydro Boy has reduced the output power to prevent the device from overheating. The Hydro Boy enters into "Temperature derating" mode.If the Hydro Boy frequently switches to this operating mode, you should check the heat dissipation, and install the Hydro Boy in a more suitable position with better ventilation.

10.2 Failures

10.2.1 The red LED glows continuouslyVaristor is defectiveThe red LED on the Hydro Boy glows continuously. With this blinking code, it is not relevant whether the green or yellow LEDs are glowing or blinking. The insulation resistance is below the preset threshold.One of the thermally monitored varistors on the DC input side may be defective and require replacement due to overcurrent oraging.

The green LED turns off briefly once per second

The red LED glows continuously

Page 40: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Blinking Codes SMA Solar Technology AG

40 HB1124-TEN093421 Technical Description

10.2.2 The yellow LED glows continuouslyPermanent disableIn the event of a recurring fault, the Hydro Boy switches to "Permanent Disable" mode, and ceases grid feeding. A fault may exist that cannot be resolved on-site. You can attempt to rectify the fault with the aid of a communication interface and the corresponding communication product (e.g. PC with Sunny Data Control). If this is unsuccessful, contact the SMA Serviceline to discuss further action to solve the problem.

10.2.3 The yellow LED blinks twiceGrid side fault

The yellow fault LED lights up for 5 seconds when the fault occurs, and then begins emitting the blinking code. The LED goes off for 3 seconds and then blinks twice. The code is repeated 3 times. If the fault is still present, the fault display starts again from the beginning.With this fault signal, the inverter indicates a grid fault which can havethe following causes:

• Grid undervoltage (UAC < "ACVtgMin")• Grid overvoltage (UAC > "ACVtgMax")• Grid underfrequency• Grid overfrequency• Grid frequency change

Check if a general power outage has occurred (check the operation of other electrical loads), and check that the fuse in the feeding cable of the inverter is not damaged, and check if the line circuit breaker is switched on.

The yellow LED glows continuously

The yellow LED briefly blinks twice in succession

Page 41: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Blinking Codes

Technical Description HB1124-TEN093421 41

10.2.4 The yellow LED blinks 3 timesGrid impedance

The yellow fault LED lights up for 5 seconds when the fault occurs, and then begins emitting the blinking code. The LED goes off for 3 seconds and then blinks 3 times. The code is repeated 3 times. If the fault is still present, the fault display starts again from the beginning.The Hydro Boy has detected a fault due to impermissible grid impedance values. If the Hydro Boy frequently deactivates and displays the aforementioned fault during grid monitoring, this may be caused by excessive grid impedance.A qualified electrician can usually fix this problem by increasing the cross-section of the power line. Tightening the terminal clamps on the connection cable may also help. Other measures can be taken to correct this fault, but they require the explicit agreement and cooperation of the grid operator.

The yellow LED briefly blinks 3 times in succession

Page 42: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Blinking Codes SMA Solar Technology AG

42 HB1124-TEN093421 Technical Description

10.2.5 The yellow LED blinks 4 timesThe maximum permissible input voltage range is exceeded

The yellow fault LED lights up for 5 seconds when the fault occurs, and then begins emitting the blinking code. The LED goes off for 3 seconds and then blinks 4 times. This code is emitted 3 times in succession. If the fault is still present, the fault display starts again from the beginning.The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy!

10.2.6 The yellow LED blinks five timesDevice fault

The yellow fault LED lights up for 5 seconds when the fault occurs, and then begins emitting the blinking code. The LED goes off for 3 seconds and then blinks 5 times. The code is sent 3 times in succession. If the fault is still present, the fault display starts again from the beginning.If this fault leads to a major impairment of normal operation, the Hydro Boy and the entire system installation should be checked by a qualified electrician.

The yellow LED briefly blinks 4 times in succession

The yellow LED briefly blinks 5 times in succession

Page 43: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Maintenance and Care

Technical Description HB1124-TEN093421 43

11 Maintenance and CareCleaning the cooling finsIt is only necessary to clean the cooling fins if the Hydro Boy‘s heat dissipation is restricted by dirt.Clean the cooling fins using a suitable, soft brush.

Page 44: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Decommissioning SMA Solar Technology AG

44 HB1124-TEN093421 Technical Description

12 Decommissioning12.1 Disassembling the Hydro Boy

1. Wait until the LED on the Hydro Boy has gone out.2. Remove the AC connection socket from the Hydro Boy.3. Remove the communication cables from the Hydro Boy.4. Open the Hydro Boy. Remove the lid screws and the lid.5. Remove all cables from the Hydro Boy.6. Close the Hydro Boy. Fasten the lid to the Hydro Boy using four screws.7. Remove the Hydro Boy.

12.2 Packing the Hydro BoyIf possible, please always pack the Hydro Boy in the original packaging. If this is no longer available, you can also use an equivalent box that fulfills the following requirements:

• With handle system• Suitable for loads of up to 29 kg• Can be closed fully

12.3 Storing the Hydro BoyStore the Hydro Boy in a dry place where the ambient temperatures are always between –25 °C and +60 °C.

12.4 Disposing of the Hydro BoyDispose of the Hydro Boy at the end of its service life in accordance with the disposal regulations for electronic waste that apply at the installation site at that time. Alternatively, send it back to SMA Solar Technology with shipping paid by sender and labeled "ZUR ENTSORGUNG" (FOR DISPOSAL).

CAUTION!Risk of injury due to the heavy weight of the Hydro Boy.

• Note that the Hydro Boy weighs 29 kg.

DANGER!Danger to life due to high voltages in the Hydro Boy.

• Switch off all fuses and secure them to prevent them from being reactivated.

Page 45: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Troubleshooting

Technical Description HB1124-TEN093421 45

13 Troubleshooting13.1 Checking/Replacing VaristorsVaristors are wearing parts. Their functioning diminishes with age or following repeated responses as a result of overvoltages. If the red LED glows continuously, it is possible that one of the thermally monitored varistors has lost its protective function.You can check these varistors in the following way:1. Open the Hydro Boy as described in section 8.1 „Opening the Hydro Boy“ (31).2. Use a multimeter to check all the varistors, and determine whether there is a conducting

connection between connectors 2 and 3.

3. Replace all varistors with new ones as shown in this drawing. Varistor failure is generally due to influences which affect all varistors similarly (temperature, age, induced overvoltages). If you do not receive a special tool together with the replacement varistors, please contact SMA Solar Technology. However, the terminal contacts can be operated using a 3.5 mm wide screwdriver. Ensure the varistor is installed the right way round!

4. Close the Hydro Boy as described in section 8.2 „Closing the Hydro Boy“ (31).

If... Then...There is a conducting connection... There is probably another fault in the Hydro Boy.

Contact the SMA Serviceline.Continue with point 4.

There is no conducting connection... The respective varistor is defective and must be replaced.The varistors are specially manufactured for use in the Hydro Boy and are not commercially available. They must be ordered directly from SMA Solar Technology. To replace the part, proceed to step 3.

Insert the extractor tool to open the terminal

Remove the varistor

The pole with the small loop (crimp) must be fitted to terminal 1 when replacing the varistor.

Page 46: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Operating Parameters SMA Solar Technology AG

46 HB1124-TEN093421 Technical Description

14 Operating ParametersThe different operating parameters control the functionality of the Hydro Boy. They can only be viewed and changed via a communication device or communication software. Some parameters can only be seen and changed by an installer (parameters marked in gray). The so-called "installer password" is required for this.Parameters designated with * are safety-related grid monitoring parameters. To change the SMA grid guard parameters, you must enter your personal SMA grid guard password. Call the SMA Serviceline to obtain your personal SMA grid guard password.

DANGER!Danger to life through changing the internal safety specifications of the Hydro Boy.Unauthorized changes to the SMA grid guard parameters void the operation permission.

• SMA grid guard parameters may only be changed with the express authorization of the grid operator.

Name DescriptionACVtgMin *ACVtgMax *

Lower (Uac-Min) and upper (Uac-Max) thresholds of the permissible AC voltage, before the grid monitoring system disconnects the device from the grid.

ACVtgProt * Voltage increase protection (only relevant for Germany).The Hydro Boy can feed electricity into the public grid with up to 260 V AC. However, DIN VDE 0126-1-1 stipulates that the average AC voltage over 10 minutes must not exceed 253 V. If the average over 10 minutes exceeds the threshold of 253 V, the Hydro Boy disconnects itself from the grid. Once the average over 10 minutes returns to a value of less than 253 V, the Hydro Boy resumes grid feeding. If overvoltage protection is not required in the relevant grid area (outside Germany), it can be deactivated by presetting the LDVtgC parameter accordingly.

CurTstPls * Setting the impulse for impedance monitoring. This parameter can only be changed if the Hydro Boy is deactivated (disconnection on the AC side), or has been set to "Stop" mode.

Default * This parameter allows settings to be defined for countries without any predefined settings.

DCCurChgSp Rate of change at which a new nominal DC current value is to be reached.DCCurSt_Pt Nominal DC current valueDCVtgMin Parameter for setting the lower threshold of the DC voltage for switching from

the "DCCur mode" into "DCVtg mode".DCVtgStr The DC voltage required before the Hydro Boy begins feeding power into the

grid.EnOp Enabling signal for operation

Page 47: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Operating Parameters

Technical Description HB1124-TEN093421 47

E-Total Total energy yield of the inverter. This change may be necessary when you exchange your Hydro Boy, and want to use the data from the old device.

Fac-Tavg Averaging time of grid frequency measurement.FanStrt Starting temperature for fan (only for HB 1324)FanStp Stopping temperature for fan (only for HB 1324)Firmware BFR Firmware version of the operation control unit (BFR).Firmware SSR Firmware version of the current control unit (SRR).FrqDifMax * Maximum permissible deviation of the frequency from the previous value.FrqDifNg * Maximum frequency above and below the grid frequency, before the grid

monitoring system disconnects the device from the grid.FrqDifPos *ImpDifMax * Maximum permissible positive change in impedance.FrqLim1 Only for off-grid mode: Frequency at which the output is to be adjusted.FrqLim2 Only for off-grid mode: Frequency at which the output is adjusted to zero.h_Total Total operating hours of the Hydro Boy. This change may be necessary when

you exchange your Hydro Boy, and want to use the data from the old device.Inst.-Code Parameters for stand-alone grid recognition can only be changed after entering

the SMA grid guard password.LDVtgC * Compensation for the voltage drop in the cabling.

With this parameter, the voltage drop between the inverter and the grid connection point is taken into account. The 10-minute average voltage at the inverter connection must not exceed the sum of ACVtgRPro plus LDVtgC. The parameter LDVtgC is preset to 0 V for Germany. In grid areas in which the additional voltage increase protection (see parameter ACVtgRPro) is not required, the parameter LDVtgC is preset to 50 V. Thus, the voltage increase protection is deactivated for these grid areas (253 V + 50 V = 303 V), and only the fast cut-off via the Uac-Max parameter intervenes.

Modus Operating mode of the Hydro Boy.Plimit Upper threshold for AC output power.RippleCtrlFrq Frequency of the local ripple control signal.RippleCtrlLev Level of the local ripple control signal.RippleCtlRcv Enable signal for activating the ripple control signal detection.Seriennummer Series number of the Hydro Boy.Stofnct Default parameter: returns all parameters to the factory settings.

Reset Betriebsdaten: returns all user level parameters to the factory settings.Reset Fehler: resets a permanent fault.

Name Description

Page 48: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Operating Parameters SMA Solar Technology AG

48 HB1124-TEN093421 Technical Description

14.1 Parameter Settings for Germany

Storage Permanent: modified parameters are stored in the EEPROM and can be used even when the Hydro Boy has been restarted.Volatil: prevents the parameters being stored in the EEPROM, the parameters are only stored until the next restart.

TStr * The period the Hydro Boy waits after the Udc start value has been reached.TStop The period the Hydro Boy waits before disconnecting from the grid when Pac

drops below the set value.Uac-Tavg Averaging time for measuring grid voltage.

Name Unit Value range Factory settingsDCVtgStr V - 21.6TStr* s 5 - 300 10TStp s 1 - 3600 2LDVtgC* V 0 - 50 0CurTstPls* mA 0 - 7500 6000ACVtgMin* V 160 - 230 198ACVtgMax* V 230 - 300 260FrgDifNg* Hz 0.1 - 4.5 2.45FrqDifPs* Hz 0.1 - 4.5 0.19FrqDifMax* Hz/s 0.1 - 4 4ImpDifMax* mOhm 0 - 20000 600E_Total kWh 0 - 2000000 -h_Total h 0 - 200000 -DCVtgMin V 15 - 75 19.5ACVtgProt* V 230 - 300 253Modus - - DCCur-ModusStofnct - - -Default* - - GER/VDE0126-1-1Storage - permanent, volatile permanent

Name Description

Page 49: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Operating Parameters

Technical Description HB1124-TEN093421 49

14.2 Country-specific Parameter SettingsName Unit Country settings Off-Grid

Germany Other KoreaDefault - GER/VDE0126-1-1 Other Korea Off-GridFrqDifMax Hz/s 4 4 4 4ImpDifMax mOhm 600 20 20 600FrqDifNg Hz 2.45 0.19 0.3 4.5FrqDifPs Hz 0.19 0.19 0.3 4.5CurTstPls mA 6000 0 6000 0TStr s 10 10 300 10ACVtgMin V 198 198 194 180ACVtgMax V 260 260 242 260LDVtgC V 0 50 50 50

Page 50: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Technical Data SMA Solar Technology AG

50 HB1124-TEN093421 Technical Description

15 Technical DataHB 1124 HB 1324

Fuel Cell System DataInput voltage during operation 20 V - 55 VMax. input current [IPV, max] 56 AMax. input open-circuit voltage [UPV 0] 60 VConnection of the DC input side DC screw terminalOvervoltage protection Thermally monitored varistorsVoltage ripple [Uss] < 10 % of the input voltageInternal consumption during operation < 4 W (waiting)Reverse polarity protection Yes, via short-circuit diodeGrid Connection DataNominal output power [PAC, nom] @ 30 °C 1100 W 1200 WNominal peak power [PAC, max] 1200 W 1300 WNominal output current[IAC, nom] 4.8 A 5.2 AHarmonic distortion of output current (at KUgrid < 2 %, PAC > 0.5 PAC, nom) [KIAC]

< 4 %

Short circuit tolerance grid-side via current regulationOperating range, grid voltage [UAC] 160 - 300 V AC

Germany: 198 - 253 / 260 V ACOperating range, grid frequency [fAC] 45.5 - 54.5 Hz / 55.5 - 64.5 Hz

Germany: 47.5 - 50.2 HzAll-pole disconnection unit (grid side) automatic disconnection device

(SMA grid guard 2), double implementationPhase shift (based on the currents fundamental frequency) [cosphi]

1

Overvoltage category IIITest voltage (DC) 1.6 kV (1 s routine testing / 5 s type testing)Surge testing voltage 4 kV (serial interface: 6 kV)Internal consumption 0.1 W (deactivated)

Page 51: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Technical Data

Technical Description HB1124-TEN093421 51

General DataDimensions (w x h x d) in mm 434 x 259 x 214Weight 29 kgProtection rating in accordance with DIN EN 60529

IP 42 IP 23

Altitude (operational) 2000 m above sea levelEC Declaration of Conformity enclosed,

download area www.SMA.de/enExternal InterfacesData transfer via separate data cable CANData transfer via separate data cable RS232, RS485 (galvanically isolated)EfficiencyMax. efficiency > 91 %

HB 1124 HB 1324

Page 52: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Contact SMA Solar Technology AG

52 HB1124-TEN093421 Technical Description

16 ContactIf you have technical problems concerning our products, contact the SMA Serviceline. We require the following information in order to provide you with the necessary assistance:

• Series number of the Hydro Boy• Type of the connected fuel cell• Communication method

SMA Solar Technology AGSonnenallee 134266 Niestetal, GermanyTel. +49 561 9522 399Fax +49 561 9522 [email protected]

Page 53: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Contact

Technical Description HB1124-TEN093421 53

Page 54: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

Contact SMA Solar Technology AG

54 HB1124-TEN093421 Technical Description

Page 55: Fuel cell inverter HYDRO BOY 1124 / 1324The fuel cell voltage exceeds the permissible input voltage range of the Hydro Boy! 10.2.6 The yellow LED blinks five times Device fault The

SMA Solar Technology AG Legal Restrictions

Technical Description HB1124-TEN093421 55

The information contained in this document is the property of SMA Solar Technology AG. Publishing its content, either partially or in full, requires the written permission of SMA Solar Technology AG. Any internal company copying of the document for the purposes of evaluating the product or its correct implementation is allowed and does not require permission.

Exclusion of liabilityThe general terms and conditions of delivery of SMA Solar Technology AG shall apply.The content of these documents is continually checked and amended, where necessary. However, discrepancies cannot be excluded. No guarantee is made for the completeness of these documents. The latest version is available online at www.SMA.de or from the usual sales channels.Guarantee or liability claims for damages of any kind are excluded if they are caused by one or more of the following: • Damages during transportation• Improper or inappropriate use of the product• Operating the product in an unintended environment• Operating the product whilst ignoring relevant, statutory safety regulations in the deployment location• Ignoring safety warnings and instructions contained in all documents relevant to the product• Operating the product under incorrect safety or protection conditions• Altering the product or supplied software without authority• The product malfunctions due to operating attached or neighboring devices beyond statutory limit values• In case of unforeseen calamity or force majeureThe use of supplied software produced by SMA Solar Technology AG is subject to the following conditions:• SMA Solar Technology AG rejects any liability for direct or indirect damages arising from the use of software developed by

SMA Solar Technology AG. This also applies to the provision or non-provision of support activities.• Supplied software not developed by SMA Solar Technology AG is subject to the respective licensing and liability agreements

of the manufacturer.

SMA Factory WarrantyThe current guarantee conditions come enclosed with your device. These are also available online at www.SMA.de and can be downloaded or are available on paper from the usual sales channels if required.

TrademarksAll trademarks are recognized even if these are not marked separately. Missing designations do not mean that a product or brand is not a registered trademark.SMA Solar Technology AGSonnenallee 134266 NiestetalGermanyTel. +49 561 9522-0Fax +49 561 9522-100www.SMA.deE-Mail: [email protected]© 2004 to 2008 SMA Solar Technology AG. All rights reserved