VITREOUS CHINALAVATORYLADENAK-2214
72" U
U
UUUU
UUU
+42"
+42"
+42"
+42"
+42"
72"
+48"+48"+48"
PANEL 'E'
EXISTING RTU-2ON ROOF ABOVE
E-2,4
E-5
E-7E-8E-9E-10 E-12
E-11
E-13
E-15 E-14
E-16
WH-1
IWH-1
E-6
E-21,23
E-22,24WITH #8
72"72"
103B
PATIENT ROOM
103C
PATIENT ROOM
103D
PATIENT ROOM
103A
STORAGE
103G
RECEPTION
103E
LAB
103F
PATIENT ROOM
WITH#10
MIC
ICE
DW
VITREOUS CHINALAVATORYLADENAK-2214
F
E E E
E
E
E E E E E E E
E
E
E E
E
J
J
EE
E E
E
E
E
EEE
K
E
L
M
E
E
E
E
E
E
E
E
E
(R)
E-17
E-19
LV LV LV103B
PATIENT ROOM
103C
PATIENT ROOM
103D
PATIENT ROOM
103A
STORAGE
103G
RECEPTION
103E
LAB
103F
PATIENT ROOM
VS
LV
LV
1
E-181
1
Drawn
Approved
Project No.
Date
17211.00
28
08
F
airm
ou
nt S
tre
et, S
uite
3
00
Da
lla
s, T
exa
s 7
52
01
| 2
14
.3
03
.1
50
0
33
00
W
est 7
th
S
tre
et, S
uite
1
10
Fo
rt W
orth
, T
exa
s 7
61
07
| 8
17
.3
03
.1
50
0
RevisionDateNo.
FU
SIO
N M
ED
IC
AL
A
ES
TH
ET
IC
S
WH
EE
LH
OU
SE
II
2625 W
HIT
MO
RE
S
TR
EE
T
FO
RT
W
OR
TH
, T
X 76107
BHB PROJECT #
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116
[email protected] • 817.338.1277 • bhbinc.com
TBPE Firm #44 • TBPLS FIRM #10011300
2017.013.095
01
POWER PLAN
SCALE: 1/8" = 1'-0"
PLAN NORTHTRUE NORTH
02
LIGHTING PLAN
SCALE: 1/8" = 1'-0"
PLAN NORTHTRUE NORTH
MSBPANEL "E"
NF NON-FUSIBLE (DISCONNECT)
30/3/25 DISCONNECT SIZE / POLES / FUSE SIZE
MC MECHANICAL CONTRACTOR
EC ELECTRICAL CONTRACTOR
1.2.3.4. SOME OF THESE SYMBOLS AND ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS.
GROUND FAULT CIRCUIT INTERRUPTING
ABOVE FINISHED FLOORAFF
GFI
ALL LIGHT FIXTURES ON LIGHTING PLANS ARE TYPE 'A' UNLESS NOTED OTHERWISE.
CONDUIT W/ ONE PHASE, ONE NEUTRAL AND ONE GROUND
WHEN NO HASH MARKS ARE SHOWN, PROVIDE ONE PHASE, ONE NEUTRAL AND ONE GROUND CONDUCTOR.LETTER ADJACENT TO FIXTURE DENOTES FIXTURE TYPE. REFER TO FIXTURE SCHEDULE.
NOTES:
WP
*
ELECTRICAL SYMBOL LIST
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
WEATHERPROOF
CEILING MOUNTED VACANCY SENSOR
CEILING MOUNTED OCCUPANCY SENSOR
DATA OUTLET/POINT OF SALE OUTLET WITH 3/4" C STUBBED INTO CLG
TELEPHONE OUTLET WITH 3/4" C STUBBED INTO CLG
JUNCTION BOX
SPECIAL PURPOSE RECEPTACLE
GFI RECEPTACLE, WP FOR ALL OUTDOOR LOCATIONS
DUPLEX RECEPTACLE
MOUNTED ABOVE COUNTER
NON-FUSED DISCONNECT SWITCH
MOTOR
GROUND
CONDUIT W/ ONE GROUND, 3 PHASE & ONE NEUTRAL
CONDUIT AND HOMERUN TO PANEL - NOTE 2
208/120 V PANELBOARD
MOTOR RATED SWITCH
LOW VOLTAGE SWITCH
THREE WAY SWITCH
SINGLE POLE SWITCH
EMERGENCY LIGHTING UNIT WITH 2 LAMPS
EXIT LIGHT FIXTURES
EMERGENCY/NIGHT LIGHT
PENDANT MOUNTED LIGHT FIXTURE
TRACK LIGHT FIXTURE
LED LIGHT FIXTURE - REFER TO NOTE 1
FUSED DISCONNECT SWITCH
03
RISER DIAGRAM
SCALE: NTS
ELECTRICAL SPECIFICATIONS:1. PERFORM ALL WORK IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL CODES AND CODE AUTHORITIES.
2. SUBMIT SHOP DRAWINGS FOR ALL MATERIAL FURNISHED UNDER THIS DIVISION OF WORK. PROVIDE A MINIMUM OF SIX COPIES.
3. SECURE AND PAY FOR ALL NECESSARY PERMITS, LICENSES AND INSPECTIONS REQUIRED BY LAW FOR THE COMPLETION OFTHE WORK. SECURE AND PAY FOR ALL CERTIFICATES OF APPROVAL THAT ARE REQUIRED AND DELIVER THEM TO THEARCHITECT BEFORE FINAL ACCEPTANCE OF THE WORK.
4. IDENTIFY ELECTRICAL EQUIPMENT USING LAMINATED THREE-PLY, ENGRAVED, PLASTIC NAMEPLATES WITH BLACK SURFACEAND WHITE INTERIOR CORE, AT LEAST 1/16 INCH THICK. ATTACH NAMEPLATES USING CHROMIUM PLATED SCREWS. PROVIDENAMEPLATES FOR PANELBOARDS, TRANSFORMERS AND DISCONNECT SWITCHES.
5. EXAMINE THE PROJECT SITE AND MAKE ALLOWANCES IN THE BID TO ACCOMMODATE EXISTING CONDITIONS.
6. ALL MATERIAL SHALL BE NEW, UL LISTED, AND FREE FROM DEFECTS, UNLESS EXISTING MATERIAL IS SPECIFICALLY SHOWN TOBE REUSED. INSTALL ALL MATERIAL IN ACCORDANCE WITH GOOD WORKMANSHIP STANDARDS.
7. SUBSTITUTIONS OF SPECIFIED MATERIAL SHALL BE APPROVED IN WRITING BY THE ARCHITECT PRIOR TO BIDDING.
8. PROVIDE FACTORY FINISH ON ALL MATERIAL FURNISHED TO THE JOBSITE AND TOUCH UP FINISHES WHICH HAVE BEENDAMAGED.
9. PROVIDE TYPEWRITTEN DIRECTORIES IN ALL NEW PANELBOARDS. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR EXISTINGPANELBOARDS IN WHICH THE LOADS SERVED HAVE BEEN CHANGED BY THE SCOPE OF THIS PROJECT.
10. PROVIDE A COPY OF AS-BUILT PLANS TO THE OWNER UPON COMPLETION OF PROJECT.
11. MAINTAIN OPERATIONS OF ALL BUILDING SYSTEMS DURING CONSTRUCTION. COORDINATE ALL SHUTDOWNS OR SYSTEMDISRUPTIONS WITH OWNER SEVEN DAYS IN ADVANCE.
12. USE EMT CONDUIT WITH SET-SCREW TYPE FITTINGS AND INSULATED BUSHINGS, 3/4 INCH MINIMUM, FOR INTERIOR,CONCEALED WORK AND EXPOSED WORK ABOVE SWITCH HEIGHT.
13. USE RIGID GALVANIZED STEEL CONDUIT FOR EXPOSED WORK BELOW SWITCH HEIGHT.
14. USE SCHEDULE 40 PVC CONDUIT, 3/4 INCH MINIMUM, FOR ALL UNDERGROUND WORK. PROVIDE PVC COATED, RIGIDGALVANIZED STEEL BENDS.
15. USE 4" SQUARE (MINIMUM) GALVANIZED STEEL OUTLET BOXES.
16. USE COPPER CONDUCTORS, TYPE THHN INSULATION, OR APPROVED EQUAL. USE SOLID CONDUCTORS FOR #10 AWG ANDSMALLER AND STRANDED CONDUCTORS FOR #8 AWG AND LARGER. ALUMINUM CONDUCTORS ARE NOT ACCEPTABLE.
17. PROVIDE CONNECTIONS TO ALL EQUIPMENT FURNISHED UNDER THIS CONTRACT AND BY OTHER DIVISIONS OF THE WORK.MAKE ALL CONNECTIONS AS RECOMMENDED BY THE MANUFACTURER AND AS REQUIRED BY APPLICABLE CODES.
18. CONNECT ALL MOTORS AND TRANSFORMERS WITH FLEXIBLE CONDUIT SUCH THAT VIBRATION IS NOT TRANSMITTED TO THESTRUCTURE. USE LIQUID TIGHT FLEXIBLE CONDUIT IN DAMP AND WET LOCATIONS.
19. MAKE SPLICES AND PROVIDE WORK AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO EXISTING DEVICES AND EQUIPMENTTO REMAIN IN SERVICE.
20. REMOVE ALL EXISTING CONDUCTORS, CABLES AND EXPOSED CONDUIT RENDERED UNUSED BY THE SCOPE OF THIS PROJECTBACK TO THE SOURCE OF SUPPLY.
21. PROVIDE SPECIFICATION GRADE WIRING DEVICES EQUAL TO HUBBELL 1221 FOR SWITCHES AND HUBBELL 5262 FORRECEPTACLES. PROVIDE COVERPLATES FOR ALL WIRING DEVICES AND COMMUNICATIONS OUTLETS. INSTALL RECEPTACLESAT +18 INCHES AND SWITCHES AT +48" UNLESS NOTED OTHERWISE. INSTALL DEVICES IDENTIFIED WITH AN "*" SIX INCHESABOVE THE COUNTER BACKSPLASH.
22. PROVIDE FUSIBLE CLASS "R" DISCONNECT SWITCHES OF AMPERE RATING AS REQUIRED OR AS NOTED ON THE DRAWINGS.FURNISH HEAVY DUTY, QUICK MAKE, QUICK BREAK, THREE PHASE, THREE POLE SWITCHES. USE NEMA 1 ENCLOSURESINDOORS AND NEMA 3R ENCLOSURES OUTDOORS. DISCONNECT SWITCHES SHALL BE OF THE SAME MANUFACTURER AS THEPANELBOARDS.
23. FUSES SHALL BE CURRENT LIMITING, WITH 200,000 R.M.S. SYMMETRICAL AMPERES INTERRUPTING RATING AND SHALL BE ULLISTED. ALL FUSES SHALL BE OF THE SAME MANUFACTURER. FUSES 600 AMPERES AND SMALLER SHALL BE CLASS RK1, DUALELEMENT EQUAL TO BUSSMANN LPS-RK. FUSES IN MOTOR CIRCUITS SHALL BE SIZED AS FOLLOWS: FUSES FOR NOT LESSTHAN 1.15 SERVICE FACTOR MOTORS SHALL HAVE AN AMPERE RATING 125 PERCENT OF MOTOR FULL LOAD CURRENT ORNEXT HIGHER FUSE RATING. FUSES FOR 1.0 SERVICE FACTOR MOTORS SHALL HAVE AN AMPERE RATING 115 PERCENT OFMOTOR FULL LOAD CURRENT OF NEXT HIGHER FUSE RATING.
24. CIRCUIT BREAKERS SHALL BE BOLT-ON THERMAL MAGNETIC TYPE WITH NUMBER OF POLES AND AMPERE RATING AS SHOWNON PLANS. CIRCUIT BREAKERS SHALL BE CAPABLE OF INTERRUPTING THE FAULT CURRENT AVAILABLE TO THEM WITHOUTTHE USE OF SERIES CONNECTED RATINGS WITH UPSTREAM CIRCUIT BREAKERS.
25. PROVIDE A GROUND SYSTEM THAT INCLUDES ALL CONNECTIONS AND TESTING OF: GROUND RODS, GROUND CABLES,GROUND BUSES, CONDUITS, FITTINGS, ANCHORS, SUPPORTS, AND OTHER MATERIALS AS REQUIRED FOR A COMPLETEINSTALLATION.
26. ALL TELEPHONE AND DATA SYSTEMS CONDUITS ARE ONE INCH UNLESS NOTED OTHERWISE.
27. PROVIDE PANELBOARDS WITH FLUSH ENCLOSURE, HINGED LOCKABLE DOOR, COPPER BUSING, FULL SIZE NEUTRAL BUS ANDA GROUND BUS. PROVIDE PANELBOARDS WITH AN INTERRUPTING RATING AS INDICATED ON PLANS. PROVIDE CIRCUITBREAKERS WHICH SIMULTANEOUSLY OPEN ALL POLES ON DOUBLE AND THREE POLE CIRCUIT BREAKERS. PROVIDE SINGLEPOLE CIRCUIT BREAKERS SERVING FLUORESCENT LIGHTING LOADS WITH SWD MARKING. PROVIDE PANELBOARDS ASMANUFACTURED BY GENERAL ELECTRIC, SIEMENS OR SQUARE D.
VACANCY SENSOR SWITCH
CEILING MOUNTED DAYLIGHT SENSOR
CEILING MOUNTED POWER PACK
DUPLEX RECEPTACLE WITH USB PORTU
UNDERCABINET LED LIGHTING
CEILING MOUNTED SPEAKER
3#4/0,1#4G.,2 1/2"C.
NOTES BY SYMBOL " " 1. PROVIDE CIRCUIT WITH 500W CURRENT LIMITER.
2. PROVIDE A NEW 225/2 CIRCUIT BREAKER IN EXISTING MAIN PANELTO SERVE PANEL "E".
(EXISTING)
01.15.2018
FLOOR PLANS
ELECTRICAL
E1.0
MA
CP
01/15/2018