CE compliant according to European regulations
With TROXNETCOM as an option
Tested to VDI 6022
HYGI
ENISCH GETESTET
VDI 6022
Fire dampers Type FV-EU
1
Circular fire protection valve for the isolation of duct penetrations betweenfire compartments; suitable for supply air and extract air systems.They also satisfy ventilation requirements
Nominal sizes 100, 125, 160, 200 mm For installation in walls and ceilings Low differential pressure and sound power level Integration into the central BMS with TROXNETCOM
Optional equipment and accessories Electric limit switch Extension piece Trim ring, circular or square
FV-EU 1.1
X X FV-EU testregistrierung
K 4 1.1 1
Fire protection valves for supply and extract air
01/2015 DE/en
Fire dampers General information FV-EU
1 Type FV-EU General information 1.1 2Correct use 1.1 5Order code 1.1 6Trim ring / Installation kit 1.1 7Flexible connector 1.1 8Limit switch 1.1 9Installation details Solid walls 1.1 10Installation details Solid ceiling slabs 1.1 11Installation details Lightweight partition walls 1.1 12Dimensions and weight 1.1 14Specification text 1.1 15Basic information and nomenclature 1.3 1
Application Fire protection valves of Type FV-EU, with CE marking and declaration of
performance, for the isolation of duct penetrations between fire compartments
in the event of a fire To prevent the propagation of fire and smoke
through ductwork to adjacent designated fire compartmentsClassification Class of performance to EN 13501-3, up to EI 120 (ve, ho, i o) SVariants With fusible link With fusible link and limit switchNominal sizes 100, 125, 160, 200 mm L: 150 mmAttachments Limit switch for capturing the valve positionAccessoriesMortar-based installation Trim ring, circular Trim ring, square
Special characteristics Declaration of performance according to
Construction Products Regulation Classification to EN 13501-3, up to EI 120 (ve, ho, i o) S Building inspectorate licence Z-56.4212-991,
non-combustible and non-hazardous to health Complies with the requirements of EN 15650 Tested to EN 1366-2 for fire resistance properties Hygiene complies with VDI 6022 part 1 (07/ 2011), VDI 3803 (10/2002),
DIN 1946 part 4 (12/2008), and EN 13779 (09/2007) Corrosion protection according to EN 15650 in connection with EN 60068-2-52 Closed valve cone air leakage to EN 1751,
class 2 Low differential pressure and sound power level Any airflow directionConstruction features Adjustment device for large or small air volumes Valve cone with bayonet fixing
Page
K 4 1.1 2
Variant
Product example
Description
FV-EU For detailed information on attachmentssee Chapter K4 1.2.
FV-EU
01/2015 DE/en
Fire dampers General information FV-EU
1 Materials and surfaces Installation subframe, spigot and valve disc made of sheet steel Installation subframe and spigot with stove- enamelled finish, black Exposed surface of valve disc powder-coated
RAL 9010 Valve cone made of special insulation material Seal made of polyurethane Attachments made of galvanised steel Increased corrosion protection due to powder- coated casingInstallation and commissioningInstall the fire damper according to the operating and installation manual.
Mortar-based installation: In solid walls and ceiling slabs In lightweight partition walls with metal support
structure and cladding on both sidesStandards and guidelines Construction Products Regulation EN 15650: 2010 Ventilation for buildings fire dampers EN 1366-2-1999 Fire resistance tests for
service installations Fire dampers EN 13501-3:2010 Fire classification of
construction products and building elements EN 1751:1999 Ventilation for buildings Air terminal devices
Maintenance The functional reliability of the fire protection
valve must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306
and DIN 31051. If two consecutive tests, one 6 months after the other, are successful,
the next test can be conducted one year later. Fire protection valves must be included in the regular cleaning schedule of the ventilation system For details on maintenance and inspection,
refer to the installation and operating manual
K 4 1.1 3
Technical data Nominal sizes 100, 125, 160, 200 mmCasing length 150 mm (320 mm with extension)Release temperature 72 COperating temperature 0 50 CVolume flow rate range Extract air up to 350 m/h or supply air up to 400 m/h
01/2015 DE/en
Fire dampers General information FV-EU
1 Functional descriptionIn the event of a fire, fire protection valves shut automatically to prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments.In the event of a fire, the valve is triggered at 72 C by a fusible link. The release mechanism is accessible and can be tested from the outside.
Function
Constructionwith fusible link
K 4 1.1 4
Schematic illustration of the FV-EU with extension piece and limit switches
Installation subframe (subframe and fixing material are supplied separate) Spigot Valve cone Flat springs Fusible link 72 C Spring (for closure) Seal
Valve disc with seal Adjustment device (position 1: large air volume; position 2: small air volume) Bayonet fixing Extension piece Sheet metal cover Limit switch, indicating OPEN Limit switch, indicating CLOSED
01/2015 DE/en
Fire dampers Correct use FV-EU
1 Design information Approved only for use in ventilation and air conditioning sytems Ducting must be installed in such a manner
that it does not impose any significant loads on the fire protection valve in the event of a fire For particular applications it is recommended
that flexible connectors are used to connect rigid ducting to the unit
K 4 1.1 5
Correct use
Installation loca tion Constructionand building material
Minimum thickness Performance class Mortar-based
instal lationDry mortarless
instal lationmm EI TT (ve, ho, i o) S
Solid walls
Solid walls,gross density 500 kg/m 100 EI 120 S N
Solid ceiling slabs
Solid ceiling slabs, gross density 600 kg/ m 150 EI 120 S N
Lightweight partition walls with metal support structureand claddingon both sides
Lightweight partition walls 100 EI 120 S N
N = Mortar-based installation
01/2015 DE/en
Fire dampers Order code FV-EU
1
K 4 1.1 6
Order examples
FV-EU
FV EU / DE / 160 / R / Z05
TypeFV-EU Fire protection valve Country of destinationDE Germany Other destination countries upon request
Nominal size [mm]100125160200
Accessories No entry: noneR Trim ring - circularQ Trim ring - square AttachmentsZ04 Z07
Order code
FV-EUMake TROXType FV-EU / DE / 160
FV-EU with circular trim ring, extension piece and limit switch for indicating CLOSEDMake TROXType FV-EU / DE / 160 / R / Z05
01/2015 DE/en
Accessories 1 Trim ring / Installation kit FV-EU
1 Application For mortar-based installation a trim ring may be used. Materials and surfaces Trim ring, circular or square, made of galvanised sheet steel, powder-coated RAL 9010
Description
K 4 1.1 7
/ R / Q
Order code detail
AccessoriesMortar-based installation Dry mortarless installa tion Order code
Trim ring, circular RTrim ring, square Q
Nominal size 100 125 160 200A / A 200 200 250 300D5 270 295 330 370
FV-EU with trim ring (mortar-based installation)
B
D5
Trim ring, circular or square Screw fixing, by others, pitch circle = D5
Solid wall or lightweight partition wall
01/2015 DE/en
Accessories 2 Flexible connector FV-EU
1 Application Ducting must be installed in such a manner that it does not impose any significant loads on the fire protection valve in the event of a fire For information on how to limit such loads
please refer to the guideline regarding fire protection requirements on ventilation systems (Lftungsanlagen-Richtlinie, LAR)
As ducts may expand and walls may become deformed in the event of a fire, flexible connectors should be used when
connecting the unit to rigid ducting for installation into lightweight partition walls
Flexible connectors should be installed in such a way that they can compensate both tension and compression Flexible ducts can be used as an alternative Flexible connectors are to be ordered separately
Materials and surfaces Flexible connectors made of fibre-reinforced plastic Fire resistance properties to 4102; B2
Description
K 4 1.1 8
Flexible connector
215
~ 200*
* flexible length 100 mm when installed
01/2015 DE/en
Attachments Limit switch FV-EU
1
Limit switch
Application Limit switches with volt-free contacts enable the valve position indication Up to the maximum switch rating, relays or indicator lights for fire alarm systems can be used One limit switch each is required for damper
blade positions OPEN and CLOSED Fire protection valves can be supplied with one or two limit switches; the switches can also be fitted later Limit switches require an extension piece
Description
For detailed information on limit switchessee Chapter 1.2
K 4 1.1 9
/ Z04 / Z05 / Z06 / Z07
Order code detail
Technical data
Wiring Examples
Attachments Order codeExtension piece Z04
Extension piece Z04 and limit switch for indicating CLOSED Z05
Extension piece Z04 and limit switch for indicating OPEN Z06
Extension piece Z04 and limit switches for indicating CLOSED and OPEN Z07
Limit switchConnecting cable length/cross section 2 m/3 0.75 mmProtection level IP 56IEC protection class I with protective earth; III without protective earthMaximum switching current 5 AMaximum switching voltage 30 V DC, 250 V AC
CLOSED or OPEN position reached limit switch is actuated
3 30 V DC230 V AC/DCN(-)
230 VL(+)
GY
BK
Indicator light or relay, to be provided by othersNO contact:grey/black
CLOSED or OPEN position not reached limit switch is not actuated
3 30 V DC230 V AC/DCN(-)
230 VL(+)
BNBK
Indicator light or relay, to be provided by othersNC contact:brown/black
01/2015 DE/en
Fire dampers Installation details Solid walls FV-EU
1 Installation location In solid walls Solid fire wallsConstruction and building material Concrete, aerated concrete or solid gypsum
wallboards to EN 12859 (without open spaces) Minimum thickness 100 mm Gross density 500 kg/mInstallation type Mortar-based installation, with perimeter mortar infillRequirements Minimum distance between two fire protection valves: 200 mm Minimum distance to load-bearing structural elements: 75 mm
Installation information An opening or a cut hole (circular or square) of the nominal size plus 80 mm is required;
alternatively, the fire protection valve can be concreted into the wall during construction
Completely close off gap s with one of the following: mortar of group II, IIa, III or IIIa according to DIN 1053; fire protection mortar
of group II or III or equivalent according to EN 998-2 (classes M 2.5 to 10); fire protection mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete An extension piece is required if the thickness
of the wall exceeds 115 mm
Fire protection valves must be installed, connected and secured according tothe operating and installation manual.
In solid walls Mortar-basedinstalla tion, withperimeter mortar infill
K 4 1.1 10
Dimensions of installation opening [mm]Nominal size 100 125 160 200
A/A 200 200 250 300
Wall installation A
/ A
s
W
W: 100 115 mm Mortar, concrete or gypsum mortar 3 fixing tabs, one every 120
Wall installation
W
W > 115 mm Mortar, concrete or gypsum mortar 3 fixing tabs, one every 120 Extension piece
01/2015 DE/en
Fire dampers Installation details Solid ceiling slabs FV-EU
1 Installation location In solid ceiling slabsConstruction and building material Concrete or aerated concrete Gross density 600 kg/m Minimum thickness 150 mmInstallation type Mortar-based installation, with perimeter mortar infillRequirements Minimum distance to load-bearing structural elements: 75 mm Minimum distance between two fire protection valves: 200 mm
Installation information An opening or a cut hole (circular or square) of the nominal size plus 80 mm is required;
alternatively, the fire protection valve can be concreted into the ceiling slab during construction Completely close off gap s with one of the following: mortar of group II, IIa, III or IIIa
according to DIN 1053; fire protection mortar of group II or III or equivalent according to
EN 998-2 (classes M 2.5 to 10); fire protection mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete Extension piece, if required
Fire protection valves must be installed, connected and secured according tothe operating and installation manual.
In solid ceiling slabs Mortar-basedinstalla tion, withperimeter mortar infill
K 4 1.1 11
Dimensions of installation opening [mm]Nominal size 100 125 160 200
A/A 200 200 250 300
Ceiling slab installation, upright
D
s
D 150 mm Mortar, concrete or gypsum mortar 3 fixing tabs, one every 120 Extension piece
Ceiling slab installation, suspended
D
s
D 150 mm Mortar, concrete or gypsum mortar 3 fixing tabs, one every 120 Extension piece
01/2015 DE/en
Fire dampers Installation details Lightweight partition walls FV-EU
1 Installation location In lightweight partition walls with metal support structure and cladding on both sidesConstruction and building material Metal support structure Cladding on both sidesInstallation type Mortar-based installation, with perimeter mortar infillRequirements Minimum distance to load-bearing structural elements: 75 mm Minimum distance between two fire protection valves: 200 mm Lightweight partition walls with a metal support structure and cladding on both sides,
with European classification to EN 13501-3 or equivalent national classification Cladding on both sides made of gypsum
bonded or cement bonded panel materials Wall thickness W 100 mm Additional layers of cladding or double stud systems are approved Installation details upon request
Installation information An opening or a cut hole of the nominal size
plus 80 mm is required Completely close off gap s with one of the following: mortar of group II, IIa, III or IIIa
according to DIN 1053; fire protection mortar of group II or III or equivalent according to
EN 998-2 (classes M 2.5 to 10); fire protection mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete An extension piece is required if the thickness
of the wall exceeds 115 mm
Fire protection valves must be installed, connected and secured according tothe operating and installation manual.
In lightweightpartition wallswith metal sup port structure and clad ding on both sides
Mortar-basedinstalla tion, withperimeter mortar infill
K 4 1.1 12
Mortar-based installation
s
D5
W
Mortar or plaster Trim ring, circular or square Screw fixing, by others, pitch circle = D5 3 fixing tabs, one every 120
Metal support structure, examples
01/2015 DE/en
Fire dampers Installation details Lightweight partition walls FV-EU
1
K 4 1.1 13
Dimensions of installation opening [mm]Nominal size 100 125 160 200
A 200 200 250 300D5 270 295 330 370
Metal support structure, examples
625
A / A1A
/ A1
01/2015 DE/en
Fire dampers Dimensions and weight FV-EU
1
K 4 1.1 14
Description
FV-EU with fusible link
Dimensions [mm] / Weight [kg]Nominal size 100 125 160 200
D 98 123 158 198D1 164 189 224 264D2 158 183 218 258
Weight 1.7 2.2 3.0 4.0
FV-EU with extension piece and limit switch
A2 1
A2 1
A
D D2
D D2
D1
L ~ 320
01/2015 DE/en
Fire dampers Specification text FV-EU
1 Fire protection valve for the isolation of duct penetrations between fire compartments.For use in supply air and extract air systems;with two- stage adjustment device for adjusting the air volume.Ready-for-operation unit,which includes a fire- resistant valve coneand a release mechanism.Tested for fire resistance properties to EN 1366-2, with CE marking and declarationof performance according tothe Construction Products Regulation.For mortar-based installation into solid wallsand ceiling slabs, and into lightweight partition walls with metal support structure and claddingon both sides.Casing length of 150 mm,or 320 mm with extension pieceFor the connection to ducts made ofnon- combustible or combustible materials.Thermal release at 72 C.Special characteristics Declaration of performance according to
Construction Products Regulation Classification to EN 13501-3, up to EI 120 (ve, ho, i o) S Building inspectorate licence Z-56.4212-991,
non-combustible and non-hazardous to health Complies with the requirements of EN 15650 Tested to EN 1366-2 for fire resistance properties Hygiene complies with VDI 6022 part 1 (07/ 2011), VDI 3803 (10/2002),
DIN 1946 part 4 (12/2008), and EN 13779 (09/2007) Corrosion protection according to EN 15650 in connection with EN 60068-2-52 Closed valve cone air leakage to EN 1751,
class 2 Low differential pressure and sound power level Any airflow direction
Materials and surfaces Installation subframe, spigot and valve disc
made of sheet steel Installation subframe and spigot with stove- enamelled finish, black Exposed surface of valve disc powder-coated
RAL 9010 Valve cone made of special insulation material Seal made of polyurethane Attachments made of galvanised steel Increased corrosion protection due to powder- coated casingTechnical data Nominal sizes: 100, 125, 160, 200 mm Casing length: 150 mm, or 320 mm with extension piece Release temperature: 72 C Operating temperature: 10 to 50 C Volume flow rate range: Extract air up to
350 m/h or supply air up to 400 m/hSizing data ______________________________ [m/h] pst ______________________________ [Pa] LWA Air-regenerated noise __________ [dB(A)]
Description
This specification text describes the general properties of the product. Texts for variants can be generated with ourEasy Product Finder design programme.
TypeFV-EU Fire protection valve Country of destination
Other destination countries upon request
Nominal size [mm]
DE Germany
100125160200
Accessories No entry: none
Attachments
R Trim ring - circularQ Trim ring - square
Z04 Z07
K 4 1.1 15
Order options
01/2015 DE/en
Fire dampers Basic informationand nomenclature
1
Product selection Principal dimensions Nomenclature Colour codes according to IEC 60757 Sizing
1.3
X X Basic information and nomenclature testregistrierung
K 4 1.3 1 01/2015 DE/en
Fire dampers Basic information and nomenclature
1 Product selection Fire dampers
K 4 1.3 2
Application Type
Installationloca tion
Construction/ building material
Minimum thickness
FK-EU FKS-EU FKR-EUMortar- based
installation
Drymor tarlessinstal lation
Mortar- based
installation
Drymor tarless instal lation
Mortar- based
installation
Drymor tarless instal lation
peri -meter
part-i ally
Fire batt
Instal lation kit
peri-meter
Installation kit
peri-meter
Installation kit
mm Fire resistance classIn solid walls Walls/grossdensity 500 kg/m 100 EI 90 S EI 90 S EI 120 S EI 90 S EI 120 S EI 90 S EI 120 S In solid walls with flexible gap
Walls/grossdensity 500 kg/m 100 EI 90 S
On the faceof solid walls
Walls/grossdensity 500 kg/m 100 EI 90 S
Adjacent tosolid walls
Walls/grossdensity 500 kg/m 100 EI 90 S
Remote from solid walls
Walls/grossdensity 500 kg/m 100 EI 90 S
In solid ceiling slabs
Ceiling slabs/gross density 600 kg/m 125 EI 90 S
Ceiling slabs/gross density 600 kg/m 150 EI 90 S EI 120 S EI 120 S EI 90 S EI 120 S
Insolid ceiling slabs, with concrete base
Ceiling slabs/gross density 600 kg/m 125 EI 90 S EI 90 S EI 90 S
Lightweight partition walls with metal support structure and claddingon both sides
Lightweight partition walls 100 EI 90 S EI 120 S EI 90 S EI 90 S EI 90 S EI 90 S EI 90 S
Lightweight partition walls with metal support structure and claddingon both sides, flexible ceiling joint
Lightweight partition walls 100 EI 90 S
Fire wallswith metal support structure and claddingon both sides
Fire walls 115 EI 90 S EI 90 S EI 90 S EI 90 S EI 90 S EI 90 S
Lightweight partition walls with metal support structure and claddingon one side
Shaft walls 90 EI 90 S EI 90 S EI 90 S EI 90 S EI 90 S
Lightweight partition walls without metal support structure but with cladding on one side
Shaft walls 40 or 50 EI 90 S EI 90 S EI 90 S
In self supporting fire-resistant suspended ceilings
Tile ceilings, screw- fixed and primed Lay-in ceiling tiles
made of panel mate rials
Metal ceilings Not for FK-EU as air transfer damper Installation kit for the selected installation situation For DN 100 to 200 in lightweight partition wall with metal support structure and mineral wool 50 only for FKR-EU Additional mineral wool
01/2015 DE/en
Fire dampers Basic information and nomenclature
1
K 4 1.3 3 01/2015 DE/en
Product selection Fire dampers
Application Type
Installationloca tion
Construction/building material
Minimum thickness
FKRS-EU FV- EU KA-EU FVZ- K30 KU-K30Mortar-based
installation
Drymortarless installation
Mortar-based
installation Drymortarless installationperi-
meterFirebatt
Installa tion kit
peri-meter
Mortar-based
installationInstal lation
kit
mm Fire resistance class
In solid walls Walls/grossdensity 500 kg/m 100 EI 120 SEI 120 S,
EI 90 S EI 90 S EI 120 S K90 In solid walls with flexible gap
Walls/grossdensity 500 kg/m 100
On the faceof solid walls
Walls/grossdensity 500 kg/m 100 EI 90 S EI 90 S
Adjacent tosolid walls
Walls/grossdensity 500 kg/m 100
Remote from solid walls
Walls/grossdensity 500 kg/m 100
In solid ceiling slabs
Ceiling slabs/grossden sity 600 kg/m 125 Ceiling slabs/grossden sity 600 kg/m 150 EI 120 S
EI 120 S, EI 90 S EI 90 S EI 120 S K90
Insolid ceiling slabs, with concrete base
Ceiling slabs/grossden sity 600 kg/m 125
Lightweight partition walls with metal support structure and claddingon both sides
Lightweightpartition walls 100
EI 120 S,EI 90 S
EI 120 S, EI 90 S
EI 120 S, EI 90 S EI 120 S K90
Lightweight partition walls with metal support structure and claddingon both sides, flexible ceiling joint
Lightweightpartition walls 100 EI 90 S
Fire wallswith metal support structure and claddingon both sides
Fire walls 115 EI 90 S EI 90 S K90
Lightweight partition walls with metal support structure and claddingon one side
Shaft walls 90 EI 90 S EI 90 S
Lightweight partition walls without metal support structure but with cladding on one side
Shaft walls 40 or 50
In self supporting fire-resistant suspended ceilings
Tile ceilings, screw- fixed and primed K30-U K30-U
Lay-in ceiling tiles made of panel materials K30-U K30-U
Metal ceilings K30-U K30-U Not for FK-EU as air transfer damper Installation kit for the selected installation situation For DN 100 to 200 in lightweight partition wall with metal support structure and mineral wool 50 only for FKR-EU Additional mineral wool
Fire dampers Basic information and nomenclature
1 Rectangular fire dampersB [mm]Width of the fire damperH [mm]Height of the fire damper
[m/h] and [l/s]Volume flow rateLWA [dB(A)]A-weighted sound power levelof air-regenerated noisefor the fire damperA [m]Free area Resistance coefficient (fully ducted)
This catalogue provides convenient quick sizing tables for fire dampers.The volume flow rates for all available dimensions and nominal sizes are provided based on a particular differential pressure.Sizing data for other volume flow rates and differential pressures can be determined quickly and precisely using the Easy Product Finder design programme.
Circular fire dampers
Nominal size [mm]Diameter of the fire damperL [mm]Length of the fire damper
pst [Pa]Static differential pressurev [m/s]Airflow velocity based onthe upstream cross section (B H or diameter)KCorrection value
Principal dimensions
Nomenclature
Sizingwith the helpof this catalogue
K 4 1.3 6
Wiring Colour codes according to IEC 60757
Code ColourBK blackBN brownRD redOG orangeYE yellowGN greenBU blue
Colour codes according to IEC 60757
Code ColourVT violetGY greyWH whitePK pinkTQ turquoise
GNYE green-yellow