+ All Categories
Home > Documents > G + 5 ( Calculation Details )

G + 5 ( Calculation Details )

Date post: 02-Jun-2018
Category:
Upload: shashikantcivil025
View: 217 times
Download: 0 times
Share this document with a friend

of 104

Transcript
  • 8/10/2019 G + 5 ( Calculation Details )

    1/104

    1

    FIRSTPOINT CONSTRUCTION SERVICES

    (INDIA ) PRIVATE LIMITED

    Electrical Design for G+5 Building

  • 8/10/2019 G + 5 ( Calculation Details )

    2/104

    2

    ABSTRCAT

    PROJECT TITLE : -GROUND + 5 FLOORS RESIDENTIAL BUILDING.

    NOVELTY :- This Project is about G + 5 Floors with 20 Flats. Each flat consisting of Two

    Bed Rooms , Provided with SPLIT ACS in each room. OWER is distributed

    throughout the building using 315 KVA T/F with IMPEDANCE (Z) = 5 % .

    Also Power Backup of 100 KVA DG SET has been Provided for Ground Floor

    (SMDBS) .

    DESCRIPTION :- Illumination i.e. No.of Light Fixtures required in each room is Calculated by

    considering Standard Lux Levels . Based on Lighting , Power , AC Loads

    LOAD BALANCING SHEET has been provided to avoid phase difference

    between each phases.T/F sizing is done base on calculated TCL & Similarly

    D.G set sizing is done based on SMDBS Load. CAPACITOR BANKS have

    been provided in grond floor for Inductive Loads.

    Various Calculations that have been performed at each Feeder are as Follows

    Cable Sizing is done based on Full Load Current (FLC).

    Voltage Drop is done based on Resistance of the cable.

    S.C is done based on Impedance of the cable.

    Circuit Breaker (C.B) sizing is done based on FLC.

    Cable Checking , Breaking Capacity and Tripping Time of C.B short

    circuit currents (ISC) and No.of Runs of the cable.

    Bus Bar Sizing is done at LT Side based on Current Carrying

    Capacity (CCC) of the Material.

    Earthing is done based on the calculated Max S.C Fault Current at

    particular feeder.

    Lighting Protection is also provided based on the Avg No.of Strokes

    or Thunders of that particular area.

    Finally, SLD and WIRING details have been shown using AUTO CAD

    software.

  • 8/10/2019 G + 5 ( Calculation Details )

    3/104

    3

    S. NO TOPIC PAGE. NO

    1 Civil Layout 4

    2

    Total Connected Load ( TCL ) OF G + 5 BUILDING

    Load Balancing Sheet of Flat 1 & 2

    Load Balancing Sheet of Flat 3 & 4

    5 - 31

    15

    24

    3 Transformer Sizing Calculation 32- 34

    4 DG Set Sizing Calculation 3537

    5 Capacitor Bank Sizing Calculation 38 , 39

    6 Cable Sizing Calculation 40 - 48

    7 Voltage Drop Calculation 49 - 60

    8 Short Circuit Current Calculation 61 - 76

    9 Circuit Breaker Rating 77 - 81

    10Cable Checking , Breaking Capacity &

    Tripping Time of Circuit Breaker82 - 93

    11 LT Side Bus Bar Size Calculation 94 , 95

    12 Earthing Calculation 96 - 98

    13 Lighting Protection Calculation 99 - 101

    14 Bill of Quantity ( BOQ ) 102

    15 SUMMARY OF G + 5 PROJECT 103

    16 LIST OF AUTO CAD DRAWINGS 104

    Lighting Wiring Layout

    Power Wiring Layout

    AC Wiring LayoutMain Schematic Layout (SLD )

    -

    -

    --

  • 8/10/2019 G + 5 ( Calculation Details )

    4/104

    4

  • 8/10/2019 G + 5 ( Calculation Details )

    5/104

    5

    TOTAL CONNECTED LOAD

  • 8/10/2019 G + 5 ( Calculation Details )

    6/104

    6

    FORMULAES USED:-

    ROOM INDEX ( R.I) =

    ()NOTE : - Given dimensions are converted from Feets to Meters.

    No.of Light Fixtures NOTE : -

    Coefficient of utilization factor (CUF), manufacturing unit (M.U) and lumens

    output values are chosen from catalogue lamp output data.

    Type of light fixture value depends on no. of lights in a frame.

    Height (H) is taken as 2 mt i.e., from Floor Finishing Level (FFL) .

    LIGHTING FIXTURE LOAD :-

    Total Fixtures Load = Total No.of Lights Fixtures x Wattage

    Ceiling Fan Load = No.of Ceilng Fans x Wattage

    Exhaust Fan Load = No.of Exhaust Fans x Wattage

    LIGHTING FIXTURE LOAD = Total Fixtures Load + Ceiling Fan

    Load +Exhaust Fan Load

    POWER LOAD FORMULAE:-

    POWERLOAD = ( No.of 6A Sockets x 200 W ) + { No.of 16 A Sockets x

    (7501500) W } + { No.of 20 A Socket x ( 2000 - 3000) W }

    AC LOAD FORMULAE:-

    STEP 1:- Given dimensions are converted to Square Feet (Sq. Ft).

    STEP 2 :- As per standards from 10 x 10 ( 100 Sq. Ft ) to 10 x 12 ( 120 Sq. Ft)

    choose 1 TR Split AC.

  • 8/10/2019 G + 5 ( Calculation Details )

    7/104

    7

    STEP 3 :- Calculate required TR as Follows,

    Room Sq. Ft

    ---------------------

    120 Sq. Ft

    STEP 4 :- If calculated value is greater than 1.5 then choose 1.5 TR AC .

    NOTE :-

    1 TON RADIATION ( TR ) = 1400 Watts .

    1.5 TR = 1400 X 1.5 = 2100 W , 2 TR = 1400 X 2 = 2800 W .

    AC LOAD = Total No.of ACs X Wattages.

    TOTAL CONNECTED LOAD ( TCL ) =

    LIGHTING FIXTURE LOAD + POWER LOAD + AC LOAD

  • 8/10/2019 G + 5 ( Calculation Details )

    8/104

  • 8/10/2019 G + 5 ( Calculation Details )

    9/104

    9

    No.of Fixture : (3.15x1.2x100)/(0.5x0.95x1x3350) = 0.356 1

    Choose No.of Light Fixtures as 1

    __________________________________________________________________________

    Room Application : BED ROOM ( BR )

    Lux Level : 200

    Room Length : 3.15mt

    Room width : 4.2 mt

    Height of lighting fixture : 2.5mt

    Type of Lighting Fixture : 1 x 36W( FL LAMP )

    Room Index : (3.15 x 4.2)/ (3.15 +4.2)x 2.5=0.75

    No.of Fixture : (3.15x4.2x200) / (0.5x0.95x1x3350) = 1.66 2

    Choose No.of Light Fixtures as 2

    __________________________________________________________________________

    Room Application : Dinning Area (DA)

    Lux Level : 200

    Room Length : 2.25mt

    Room width : 2.44mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W( FL LAMP )

    Room Index : (2.25 x 2.44 ) / (2.25 + 2.44 ) x 2.5 = 0.75

    No.of Fixture : (2.25x2.44x200) / (0.5x0.95x1x3350) = 0.69 1

  • 8/10/2019 G + 5 ( Calculation Details )

    10/104

    10

    Choose No.of Light Fixtures as 1

    Room Application : TOILET1 ( T1 )

    Lux Level : 100

    Room Length : 2.4 mt

    Room width : 1.2 mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (2.4 x 1.2) / (2.4+1.2) x 2.5 = 0.32

    No.of Fixture : (2.4x1.2x100)/(0.5x0.95x1x3350) = 0.18 1

    Choose No.of Light Fixtures as 1

    __________________________________________________________________________

    Room Application : TOILET2 ( T2 )

    Lux Level : 100

    Room Length : 2.4 mt

    Room width : 1.2 mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (2.4 x 1.2) / (2.4+1.2) x 2.5 = 0.32

    No.of Fixture : (2.4x1.2x100)/(0.5x0.95x1x3350) = 0.18 1

    Choose No.of Light Fixtures as 1

    _______________________________________________________________________

    Room Application : Master Bed Room (MBR)

  • 8/10/2019 G + 5 ( Calculation Details )

    11/104

    11

    Lux Level : 250

    Room Length : 3.64

    Room width : 3.19

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W( FL LAMP )

    Room Index : (3.64 x 3.19)/ (3.64 + 3.19)x2.5= 0.75

    No.of Fixture : (3.64x3.19x250) / (0.5x0.95x1x3350) = 1.824 2

    Choose No.of Light Fixtures as 2

    __________________________________________________________________________

    Room Application : Hall

    Lux Level : 300

    Room Length : 3.15mt

    Room width : 4.89

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W( FL LAMP )

    Room Index : (3.15 x 4.89)/ (3.15 + 4.89)x2.5= 0.76

    No.ofFixture : (3.15x4.89x300)/(0.54x0.95x1x3350) = 2.86 3

    Choose No.of Light Fixtures as 3

    __________________________________________________________________________

    Consider Each Light Point as 36 W

    A. Total No.of Fixtures = 13 Nos Lights ( 36 W FL LAMP)

    a. Total Fixtures Load = Total No.of Lights x Wattage

  • 8/10/2019 G + 5 ( Calculation Details )

    12/104

    12

    = 13 Nos x 36 W

    = 468 Watts = 0.468 KW .

    Total Fixtures Load = 468 Watts = 0.468 KW

    b. Ceiling Fan Load = 5 Nos Ceiling Fan x 80 W

    = 400 Watts

    Ceiling Fan Load = 400 Watts = 0.4 KW

    c. Exhaust Fan Load = 3 Nos Exhaust Fan x 75 W

    = 225 Watts

    Exhaust Fan Load = 225 Watts = 0.225 KW

    A.LIGHTING FIXTURE LOAD = a + b + c = 468 + 400 + 225 = 1093 W

    B. POWER LOAD ( Typical Flat 1 ) :-

    i.Balcony : - 2 Nos 6 A Socket ( 200 W each ) = 400 Wii.Kitchen :- 1 No Micro oven (16 A Socket ) = 1000 W

    1 No Rice Cooker(16 A Socket ) = 450 W

    1 No Feezer Socket (16 A Socket) = 550 W

    1 No Mixer (16 A Socket) = 450 W

    iii.Bed Room :- 2 Nos 6 A Socket ( 200 W each ) = 400 W1 No Iron Box (16 A Socket) = 450 W

    iv. Dinning Area:- 1 No 6 A Socket = 200 W

    1 No Washng M/c (16A Socket) = 450 W

    v. Toilet1 :- 1 No 6 A Socket = 200W1 No Water Heater (16A Socket) = 1000 W

    vi. Toilet2 :- 1 No 6 A Socket = 200W1 No Water Heater (16A Socket) = 1000 W

    vii. Master Bed Room :- 4 Nos 6 A Socket = 800 Wviii. Hall :- 4 Nos 6 A Socket = 800 W

    TOTAL - 8,350 W

    LIGHTING FIXTURE LOAD = 1093 Watts = 1.093 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    13/104

    13

    C. AC LOAD ( Typical Flat 1 ) :-

    Note: As per standard 100 to 120 Square Feet area requires 1 Ton refrigeration

    of Cooling.

    a. Master Bedroom ( MBR ) :-

    Room Dimension :- 122 x 108 = (12.16) x (10.66) = 129 Sq Ft.

    Therefore Tonnage = 129 / 120 = 1.08 TR 1 TR AC = 1400 W

    b. Bedroom ( BR ) :-

    Room Dimension :-106x 142 = (10.5) x (14.16)= 148.68Sq Ft.

    Therefore Tonnage = 148 / 120 = 1.23 TR 1 TR AC = 1400 W

    Total AC Load = 1400 + 1400 = 2800 W

    TOTAL CONNECTED LOAD (TCL) = LIGHTING LOAD + POWER LOAD + AC LOAD

    = 1093 + 8,350 + 2800

    = 12,243W

    After considering a Maximum Demand of 60 % Load

    TCL = 12,243 x 60 % = 7,345.8 W = 7.34 KW .

    POWER LOAD = 8,350 Watts = 8.35 KW

    AC LOAD = 2,800 Watts = 2.8 KW

    TCL OF FLAT - 1 = 12,243 Watts = 12.24 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    14/104

    14

    Now Similarly,

    TCL for Flat 2 = 12.24 KW

    TCL for Flat 1 + TCL for Flat 2 = 12.24 + 12 .42

    = 24.48 KW

    TOTAL CONNECTED LOAD OF FLAT 1 & 2 = 24,486W = 24.48 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    15/104

    15

    LOAD BALANCING SHEET FOR TYPICAL FLAT 1 & FLAT 2

    ( 3 - 8 WAY DISTRIBUTION BOARD)

    CKT NO. CABLE SIZE MCB LOAD & LOCATION R Y B

    R1 2.5 sq mm 5A KITCHEN + BAL + BR 415

    Y1 2.5 sq mm 5A SPARE 0

    B1 2.5 sq mm 5A DA + T 1 + T 2 + MBR 338

    R2 2.5 sq mm 5A SPARE 0

    Y2 2.5 sq mm 5A MBR + HALL 340

    B2 2.5 sq mm 5A SPARE 0

    R3 4sqmm 10A K(2 16A SKT-MIXER & RICE CKR) + BAL (1 6A SKT) 1100

    Y3 4sqmm 10A SPARE 0

    B3 4sqmm 16AK(1 16A SKT-FRZ) + BR(2 6A & 1 16A IRON BOX) +

    BAL(1 6A SKT) 1600

    R4 4sqmm 10A K(1 16A MICROOVEN SKT) 1000

    Y4 4sqmmDA(1 6A&1 16 A WASH M/C SKT) + T 1 (1 16A

    WATER HTR SKT) 1650

    B4 4sqmm 10A SPARE 0

    R5 4sqmm 10A SPARE 0

    Y5 4sqmm 10A T 1 (1 6A SKT) + T 2 (1 6A SKT) + MBR (1 6A SKT) 600

    B5 4sqmm 10A T 2 (1 16A WATER HTR SKT ) 1000

    `

    R6 4sqmm 10A MBR (3 6A SKT) + HALL (1 6A SKT) 800

    Y6 4sqmm 10A HALL (3 6A SKT) 600

    B6 4sqmm 10A SPARE 0

    R7 6sqmm 16A BR ( 1 TR AC ) 426.6

    Y7 6sqmm 16A BR ( 1 TR AC ) 426.6

    B7 6sqmm 16A BR ( 1 TR AC ) 546.6

    R8 6sqmm 16A MBR ( 1 TR AC ) 426.6

    Y8 6sqmm 16A MBR ( 1 TR AC ) 426.6

    B8 6sqmm 16A MBR ( 1 TR AC ) 546.6

    4168.2 4043.2 4031.2

    TOTAL 12242.6

    Note- ADD DIVERSITY FACTOR OF 0.6 FOR RESIDENTIAL PURPOSE = 12.24 KW X 0.6 =7354.8 W =7.35KW

  • 8/10/2019 G + 5 ( Calculation Details )

    16/104

    16

    Load Calculations of FLAT 3 4 :-

    a.LIGHTING LOAD CALCULATION

    a.

    LIGHTING FIXTURE LOAD:

    Room Application : HALL( H )

    Lux Level : 300

    Room Length : 3.15mt

    Room width : 4.89mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (3.15 x 4.89) / (3.15 + 4.89) x 2.5 = 0.76

    No.of Fixture : (3.15 x 4.89 x 300) /( 0.54 x 0.95 x 1 x 3350) = 2.68 2

    Choose No.of Light Fixtures as 2

    __________________________________________________________________________

    Room Application : KITCHEN ( K )

    Lux Level : 300

    Room Length : 3.65 mt

    Room width : 2.47mt

    Height of lighting fixture : 2 .5mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (3.65 x 2.47)/ (3.65+2.47)x2.5= 0.59

  • 8/10/2019 G + 5 ( Calculation Details )

    17/104

    17

    No.of Fixture : (3.65x2.47x300) / (0.5x0.95x1x3350) = 1.69 2

    Choose No.of Light Fixtures as 2

    __________________________________________________________________________

    Room Application : DINNING AREA ( DA )

    Lux Level : 200

    Room Length : 2.22mt

    Room width : 2.2 mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (2.22 x 2.2) / (2.22 + 2.2 ) x 2.5= 0.44

    No.of Fixture : (2.22x2.2x200) / (0.5x0.95x1x3350) = 0.61 1

    Choose No.of Light Fixtures as 1

    __________________________________________________________________________

    Room Application : TOILET 1 (T - 1)

    Lux Level : 100

    Room Length : 1.2mt

    Room width : 2.2mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (1.2 x 2.2 ) / (1.2 + 2.2 ) x 2.5 = 0.31

    No.of Fixture : (1.2x2.2x100) / (0.5x0.95x1x3350) = 0.165 1

  • 8/10/2019 G + 5 ( Calculation Details )

    18/104

    18

    Choose No.of Light Fixtures as 1

    ___________________________________________________________________________

    Room Application : MASTER BEDROOM ( MBR )

    Lux Level : 250

    Room Length : 3.65mt

    Room width : 4.25mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (3.65 x 4.25) / (3.65+4.25) x 2.5 = 0.78

    No.of Fixture : (3.65x4.25x250) / (0.54x0.95x1x3350) = 2.25 2

    Choose No.of Light Fixtures as 2

    __________________________________________________________________________

    Room Application : BED ROOM ( BR )

    Lux Level : 200

    Room Length : 3.15mt

    Room width : 4.25mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (3.15 x 4.25) / (3.15+4.25) x 2.5 = 0.72

    No.of Fixture : (3.15x4.25x200) / (0.54x0.95x1x3350) = 1.68 2

    Choose No.of Light Fixtures as 2

    Room Application : BALCONY ( BAL)

  • 8/10/2019 G + 5 ( Calculation Details )

    19/104

    19

    Lux Level : 150

    Room Length : 1.77

    Room width : 1.2

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (1.77 x 1.2) / (1.77 + 1.2) x 2.5 = 0.367

    No.of Fixture : (1.77x1.2x150) / (0.5x0.95x1x3350) = 0.2007 1

    Choose No.of Light Fixtures as 1

    __________________________________________________________________________

    Room Application : TOILET 2 (T2)

    Lux Level : 100

    Room Length : 2.4mt

    Room width : 1.2 mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (2.4 x 1.2) / (2.4 + 1.2) x 2.5 = 0.32

    No.of Fixture : (2.4x1.2x100) / (0.54x0.95x1x3350) = 0.189 1

    Choose No.of Light Fixtures as 1

    Room Application : TOILET 3 (T3)

    Lux Level : 100

  • 8/10/2019 G + 5 ( Calculation Details )

    20/104

    20

    Room Length : 2.4mt

    Room width : 1.2 mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (2.4 x 1.2) / (2.4 + 1.2) x 2.5 = 0.32

    No.of Fixture : (2.4x1.2x100) / (0.54x0.95x1x3350) = 0.189 1

    Choose No.of Light Fixtures as 1

    _________________________________________________________________________

    Consider Each Light Point as 36 W

    Total No.of Fixtures = 14 Nos Lights ( 36 W FL LAMP)

    a. Total Fixtures Load = Total No.of Lights x Wattage

    = 14 Nos x 36 W= 504 Watts = 0.504 KW .

    Total Fixtures Load = 504 Watts = 0.504 KW

    b. Ceiling Fan Load = 5 Nos Ceiling Fan x 80 W

    = 400 Watts

    Ceiling Fan Load = 400 Watts = 0.4 KW

    c. Exhaust Fan Load = 4 Nos Exhaust Fan x 75 W

    = 300 Watts

    Exhaust Fan Load = 300 Watts = 0.3 KW

    A. LIGHTING FIXTURE LOAD = a + b + c = 504 + 400 + 300 = 1204 W

  • 8/10/2019 G + 5 ( Calculation Details )

    21/104

    21

    A. LIGHTING FIXTURE LOAD = 1204 Watts = 1.204 KW

    B. POWER LOAD ( Typical Flat 3 ) :-

    I. Balcony : - 2 Nos 6 A Socket ( 200 W each ) = 400 W

    II. Kitchen :- 1 No Micro oven (16 A Socket ) = 1000 W

    1 No Rice Cooker (16 A Socket ) = 450 W1 No Freezer Socket (16 A Socket) = 550 W1 No Mixer (16 A Socket) = 450 W1 No 6 A Socket = 200 W

    III. Bed Room :- 2 Nos 6 A Socket ( 200 W each ) = 400 W

    1 No Iron Box (16 A Socket) = 450 W

    IV. Dinning Area:- 1 No 6 A Socket = 200 W

    1No Washng M/c (16A Socket) = 450 W

    V. Toilet1 :- 1 No 6 A Socket = 200W

    1 No Water Heater (16A Socket) = 1000 W

    VI. Toilet2 :- 1 No 6 A Socket = 200W

    1 No Water Heater (16A Socket) = 1000 W

    VII. Master Bed Room :- 4 Nos 6 A Socket = 800 W

    VIII. Hall :- 4 Nos 6 A Socket = 800 W

    IX. Toilet3 :- 1 No 6 A Socket = 200W

    1 No Water Heater (16A Socket) = 1000 W

    TOTAL - 9,750 W

    B.POWER LOAD = 9,750 W = 9,75 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    22/104

    22

    C. AC LOAD ( Typical Flat 3 ) :-

    Note:- As per standard 100 to 120 Square Feet area requires

    1 Ton refrigeration of Cooling.

    a. Master Bedroom ( MBR ) :-

    Room Dimension :- 122 x 142 = (12.66) x (140.166) = 179.35Sq

    Therefore Tonnage = 179.35 / 120 = 1.49 TR 1.5 TR AC

    = 1.5 x 1400 W= 2100 W

    b. Bedroom ( BR ) :-

    Room Dimension :- 106 x 142 = (10.5) x (14.16) = 148.75Sq Ft.

    Therefore Tonnage = 148 / 120 = 1.23 TR 1 TR AC = 1400 W

    Total AC Load = 2100 + 1400 = 3500 W

    C. AC LOAD = 3,500 W = 3.5 KW

    TOTAL CONNECTED LOAD( TCL) = LIGHTING LOAD + POWER LOAD + AC LOAD

    = 1204 + 9,750 + 3500

    = 14,454 W

    TCL OF FLAT 3 = 14,454 W = 14.45 KW

    After considering a Maximum Demand of 60 % Load

    TCL = 14,454 x 60 % = 8,672.4W = 8.67KW .

    Now Similarly,

    TCL for Flat 4 = 14.45 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    23/104

    23

    Therefore,

    TCL for Flat 3 + TCL for Flat 4 = 14.45 + 14 .45

    = 28.90 KW

    TCL OF FLAT 3 & FLAT 4 = 14,454 W = 14.45 KW

    TCL OF FOUR FLATS= TCL OF FLAT 1 & 2 + TCL OF FLAT 3 & 4

    = 24,486 + 28,908

    = 53,394 W

    TCL OF 4 FLATS = 53,394 W = 53.394 KW

    Note : - Each Floor 4 Flats , here total 5 Floors

    TCL of Flats Load = 5 x TCL OF FOUR FLATS

    = 5 x 53,394

    = 266,970 W

    TTCCLLOOFF FFLLAATTSSLLOOAADD==226666,,997700WW==226666..9977KKWW

  • 8/10/2019 G + 5 ( Calculation Details )

    24/104

    24

    LOAD BALANCING SHEET FOR TYPICAL FLAT 3 & FLAT 4

    ( 3 - 8 WAY DISTRIBUTION BOARD)CKT NO. CABLE SIZE MCB RATING LOAD & LOCATION R Y B

    R1 2.5 sq mm 5A HALL + KITCHEN 415

    Y1 2.5 sq mm 5A SPARE 0

    B1 2.5 sq mm 5A DA + T 1 + MBR 379

    R2 2.5 sq mm 5A SPARE 0

    Y2 2.5 sq mm 5A BR + BAL + T 2 + T3 410

    B2 2.5 sq mm 5A SPARE 0

    R3 4sqmm 10A HALL ( 4 6A SKT ) 800

    Y3 4sqmm 10A K(1 16A SKT-FRZ & 1 6 A SKT) 750

    B3 4sqmm 10A K(MICROOVE 16A SKT) 1000

    R4 4sqmm 10A K(2 16A RICE CKR & MIXER SKT) 900

    Y4 4sqmm 16A

    DA(1 6A&1 16 A WASH M/C SKT)

    + T 1 (1 16A WATER HTR SKT) 1650

    B4 4sqmm 10A

    T 1 ( 1 6A SKT ) + MBR ( 4 6A SKT

    ) 1000

    R5 4sqmm 10A

    T 2 (1 16A WATER HTR SKT & 1

    6A SKT ) + T 3(1 6A SKT) 1400

    Y5 4sqmm 10A T 3 (1 16A WATER HTR SKT ) 1000

    B5 4sqmm 10A

    BR (1 6A SKT & 1 16A IRON BOX

    SKT) 650

    `

    R6 4sqmm 10A SPARE 0

    Y6 4sqmm 10A SPARE 0

    B6 4sqmm 10A BR (1 6A SKT) + BAL (1 2 6A SKT) 600

    R7 6sqmm 16A MBR ( 1.5 TR AC ) 780

    Y7 6sqmm 16A MBR ( 1.5 TR AC ) 660

    B7 6sqmm 16A MBR ( 1.5 TR AC ) 660

    R8 6sqmm 16A BR ( 1 TR AC ) 426.6

    Y8 6sqmm 16A BR ( 1 TR AC ) 426.6

    B8 6sqmm 16A BR ( 1 TR AC ) 546.6

    4721.6 4896.6 4835.6

    TOTAL 14453.8Note :- ADD DIVERSITY FACTOR OF 0.6 FOR RESIDENTIAL PURPOSE = 14.45 KW X 0.6 =

    8672.8 W = 8.67 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    25/104

    25

    2.LOAD CALCULATIONS OF DISTRIBUTIN BOARDSERVICE ( DBS)

    DBS = CORRIDOR LIGHTING LOAD + GROUND FLOOR

    PARKING LIGHTING LOAD +GROUND FLOOR PARKING

    POWER LOAD

    A. CORRIDOR LIGHTING LOAD :-

    Room Application : CORRIDOR 1 (CORR1)

    Lux Level : 150

    Room Length : 16.14mt

    Room width : 1.5 mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 24 W ( FL LAMP )

    Room Index : (16.14 x 1.5) / (16.14 + 1.5) x 2.5 = 0.54

    No.of Fixture : (16.14x1.5x150) / (0.5x0.95x1x1750) = 4.36 4

    Choose No.of Light Fixtures as 4

    ____________________________________________________________________________

    Room Application : CORRIDOR 2 (COR2)

    Lux Level : 150

    Room Length : 23.7mt

    Room width : 1.2 mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 24 W ( FL LAMP )

  • 8/10/2019 G + 5 ( Calculation Details )

    26/104

    26

    Room Index : (23.7 x 1.2) / (23.7 + 1.2) x 2.5 = 0.4

    No.of Fixture : (23.7x1.2x150) / (0.54x0.95x1x1750) = 5.13 5

    Choose No.of Light Fixtures as 5

    __________________________________________________________________________

    Now, Total lights required in Corridor of First Floor = 9 Nos Light

    Here, Total 5 Floors i.e. 9 x 5 = 45 Lights

    A. Corridor Lighting Load = 45 Nos x 24 W (CFL LAMP)

    = 1080 W

    A .Corridor Lighting Load = 1080 W = 0.108 KW

    B. GROUND FLOOR PARKING LIGHTING LOAD :-

    Room Application : GROUND FLOOR PARKING (GF - PARKING)

    Lux Level : 100

    Room Length : 23.7mt

    Room width : 16.14 mt

    Height of lighting fixture : 2.5 mt

    Type of Lighting Fixture : 1 x 36 W ( FL LAMP )

    Room Index : (23.7 x 16.14) / (23.7 + 16.14) x 2.5 = 3.84

    No.of Fixture : (23.7x16.14x100) / (0.67x0.95x1x3350) = 17.93 18

    Choose No.of Light Fixtures as 18

    __________________________________________________________________

    B.GF Parking Lighting Load= 18 Nos x 36 W = 648 W

  • 8/10/2019 G + 5 ( Calculation Details )

    27/104

    27

    B. GF Parking Lighting Load = 648 W

    C.GROUND FLOOR PARKING POWER LOAD :-

    FORMULAE FOR NO.OFSOCKETS:-

    2 ( L + W )NO.OF SOCKETS = ----------------------

    15

    Room Application : GROUND FLOOR PARKING (GF - PARKING)

    Room Length : 23.7mt

    Room width : 16.14 mt

    NO.OF SOCKETS = 2 ( 23.7 + 16.14) / 15 = 5.3 6 SOCKETS

    3 Nos 6A Socket 200 Wand 3 Nos 16A Socket 1000 W

    GFPARKING POWER LOAD = 3 X 200 W + 3 X 1000 W= 600 + 30000 = 3,600 W

    C. GFPARKING POWER LOAD = 3,600 W = 3.6 KW

    DISTRIBUTIN BOARDSERVICE ( DBS) LOAD

    = A + B + C

    = 1080 + 648 + 3,600 = 5,328 W

    DBS LOAD = 5,328 W = 5.32 KW

    MCC PANEL LOAD:-

    MCC LOAD = LIFT LOAD + WATER SUPPLY (W.S) + FIRE FIGHTING LOAD (FF)

    = 20 KW + 7.45 KW + 11.17 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    28/104

    28

    = 38.62 KW

    3. MCC LOAD = 38.62 KW

    TOTAL CONNECTED LOAD OF THE G + 5 BUILDING:-

    TCL OF G+5 BUILDING =FLATS LOAD + DBS LOAD + MCC LOAD

    = 266.97 KW + 5.32 KW + 38.66 KW

    = 310.95 KW

    TTCCLLOOFFGG++55BBUUIILLDDIINNGGoorrMMDDBBLLOOAADD==331100..9955KKWW

    MAIN DISTRIBUTION BOARD ( MDB LOAD ) :-

    SMDB-S + SMDB-1F+ SMDB-2F + SMDB-3F + SMDB-4F + SMDB-5F

    = 43.88 KW + 53.39 + 53.39 + 53.39 + 53.39 + 53.939

    = 310.95 KW

    MDB LOAD = 310.95 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    29/104

    29

  • 8/10/2019 G + 5 ( Calculation Details )

    30/104

    30

  • 8/10/2019 G + 5 ( Calculation Details )

    31/104

    31

  • 8/10/2019 G + 5 ( Calculation Details )

    32/104

    32

    TRANSFORMER SIZING CALCULATIONS

  • 8/10/2019 G + 5 ( Calculation Details )

    33/104

    33

    TRANSFORMER CALCULATIONS

    SIZING :-

    TCL OF BUILDING = 310.95 KW

    Add 10 % Extra for future purpose ,

    TCL = 310.95 + 31.095 = 342.045 KW

    Considering Maximum Demand of 60 % Load (Diversity Factor),

    TCL = 342.045 x 0.6 = 205.22 KW

    Convert KW Rating to KVA Rating using Formulae shown below

    KVA= =

    = 256.33 KVA

    Efficiency of Transformer is 90 % .So, take Derating Factor as 0.9 toimprove Eff .

    = 284.81 KVA

    So, Proposed Transformer size is 315 KVAand is available in Market

    CHECKING OF T/F WITH HIGHEST MOTOR RATING :-

    Here Highest Motor Rating is Lift Load = 20 KW

    KVA= =

    =25 KVA

    Add Derating Factor as 0.9 for Motor Voltage Fluctuations,

    = 27.77 KVA

    At the time of Starting Motor take 4 times the Full Load Current (FLC),

    27.44 x 4 = 111.11 KVA

  • 8/10/2019 G + 5 ( Calculation Details )

    34/104

    34

    We considered Normal Motor current while calculating TCL, so Deduct and add 4 times

    FLC Load.

    I.e. 284.8127.77 + 111.11 = 366.22 KVA ------ Eqn 1

    T/F Tolerance Factor is taken as 1.5 ,

    284.81 x 1.5 = 427.21 KVA ------ Eqn 2

    Eqn 2 > Eqn 1, that implies Proposed T/F is Safe.

    ProposedTransformer size is 315 KVA (Impedamce) Z = 5 %

  • 8/10/2019 G + 5 ( Calculation Details )

    35/104

    35

    DG SET SIZING CALCULATIONS

  • 8/10/2019 G + 5 ( Calculation Details )

    36/104

    36

    DG SET CALCULATIONS

    Proposed DG SETis only for Ground Floor. ( SMDBS )

    SIZING :-

    TCL OF SMDB - S = 43.98 KW

    Add 10 % Extra for future purpose ,

    TCL = 43.98 + 4.398 = 48.37 KW

    Considering Maximum Demand of 60 % Load (Diversity Factor),

    TCL = 48.37 x 0.6 = 29.02 KW

    Convert KW Rating to KVA Rating using Formulae shown below

    KVA= =

    = 36.27 KVA

    Efficiency of Transformer is 90 % .So, take Derating Factor as 0.9 toimprove Eff .

    = 45.33 KVA

    So, Proposed DG Set size is 50 KVAand is available in Market

    CHECKING OF DG SET WITH HIGHEST MOTOR RATING :-

    Here Highest Motor Rating is Lift Load = 20 KW

    KVA= =

    = 25 KVA

    Add Derating Factor as 0.9 for Motor Voltage Fluctuations,

    = 27.77 KVA

    At the time of Starting Motor take 4 times the Full Load Current (FLC)

    27.44 x 4 = 111.11 KVA

  • 8/10/2019 G + 5 ( Calculation Details )

    37/104

    37

    We considered Normal Motor current while calculating TCL, so Deduct and add 4 times

    FLC Load.

    50 27.77 + 111.11 = 133.34 KVA ------ Eqn 1

    DG SET Tolerance Factor is taken as 1.5 ,

    50 x 1.5 = 75 KVA ------ Eqn 2

    Eqn 2 < Eqn 1, that implies Proposed DG SET not is Safe.

    Choose 100 KVA DG SET which is Next Size available in the market.

    DG SET Tolerance Factor is taken as 1.5 ,

    1000 x 1.5 = 150 KVA ------ Eqn 3

    Eqn3>Eqn 1, that implies Proposed DG SET is Safe.

    Proposed DG SET size for Ground Floor is 100 KVAand is available in Market.

  • 8/10/2019 G + 5 ( Calculation Details )

    38/104

  • 8/10/2019 G + 5 ( Calculation Details )

    39/104

    39

    CAPACITOR BANK SIZING CALCULATIONS

    Capacitor Bank is used only for Motor Loads.

    Here, Total MCC Load = 38. 66 KW

    Formulae for Calculating Capacitor Size :-

    Capacitor Bank = KW { Tan Cos -10.8Tan Cos -1( Req P.F ) }

    Here , Req P.F is 0.96

    Therefore , Capacitor Size = 17.74 KVAR 18 KVAR

    Proposed , Capacitor Bank Size is 25 KVARand is available in Market.

    Note:-

    In order to minimize the cost we use Automatic Power Factor Relay Correction Panel (APFCP)

    and here Choose 3 steps .

    Step 1 10 KVAR ON / OFF

    Step 2 10 KVAR ON / OFF

    Step 3 5 KVAR ON / OFF

  • 8/10/2019 G + 5 ( Calculation Details )

    40/104

    40

    CABLE SIZING CALCULATIONS

  • 8/10/2019 G + 5 ( Calculation Details )

    41/104

    41

    CABLE SIZING CALCULATIONS

    NOTE :-

    Cable Size mainly depends on Load Current .

    Current Carrying Capacity ( CCC ) Ranges as Follows

    1 Sqmm Copper Cable = 2.2 A to 2.4 A

    1 Sqmm Aluminium Cable = 1.2 A to 1.4 A

    From 1 Sqmm to 16 Sqmm 4 Core Copper Cable is Chosen.

    From 25 Sqmm and above 3 Core or 3.5 Core Aluminium Cable is Chosen.

    For Underground Cable Derating Factor= 0.7.

    Factors to be considered for Underground Cable are

    a.)Soil Resistivity b) Temperature of Cable c.) Cable Trenches

    d) Space between the Cables and e) grouping factor

    For Cable being laid in Air Derating Factor = 0.8

    For LT Cable ie, From Transformer Secondary Side to MDB always Choose

    Underground Cable.

    Formulaes Used:-

    Load Currentis calculated using below equations

    Case 1:- If Load is in KWthen P = 3 V I Cos (3) (Above 4 KW Load)

    P = V I Cos (1)

    Case 2:- If Load is in KVAthen P = 3 V I (3 )

    P = V I (1 )

    Case 3:- IfLoad is in KVARthen P = 3 V I Sin (3)

    Where, = 36.8in all cases.

  • 8/10/2019 G + 5 ( Calculation Details )

    42/104

    42

    In case Load Current amps is very High and not available in Catalogue

    then No.of Runs need to be calculated using below equation.

    ()

    Note:-

    Diversity Factor is chosen based on Cable Lying i e. Air or Ground.

    Chosen cable size must have less No.of Runs in order to reduce cost and Space

    consumption .

    _________________________________________________________________

    HT SIDE CABLE (1)Standard cable size is considered.

    Proposed cableis 1R X 3C X 240 SQMM ( Al )

    ___________________________________________________________________

    LT SIDE CABLE (2)FROM T/F SECONDARY TO MDB

    Consider Cable as Underground and Derating Factor is 0.7

    Here, Load is 310.95 KW( 3) and using the Formulae provided

    Load Current (I) = 540.76 A

    Since, Load Current is high as mentioned above No.of Runs need to be calculated

    based on Formulae provided.

    .For 3.5 C x 400 SQMM (Al) Cable = CCC = 426 A

    ()

    a. For 3.5 C x 300 SQMM (Al) Cable = CCC = 375 A No.of Runs = 2

  • 8/10/2019 G + 5 ( Calculation Details )

    43/104

    43

    Similarly,

    b. For 3.5 C x 300 SQMM (Al) Cable = CCC = 375 A No.of Runs = 2

    c. For 3.5 C x 240 SQMM (Al) Cable = CCC = 333 A No.of Runs = 2

    d. For 3.5 C x 185 SQMM (Al) Cable = CCC = 287 A No.of Runs = 3

    Conclusion: - 240 SQMM Cable is chosen because its most Economicaland less cost.

    Therefore, Proposed Cable is 2Rx 3.5C x 240 SQMM (Al).

    _______________________________________________________________

    SMDB - S CABLE (3)SUB MAIN DB SERVICE CABLE

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 44KW( 3) and using the Formulae provided

    Load Current (I) = 76.5 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue

    a.For 3 C x 25 SQMM (Al) Cable = CCC = 95 A x 0.8 = 76 A (Not Satisfied)b. For 3 C x 35 SQMM (Al) Cable = CCC = 117 A x 0.8= 93.8 (Satisfied)

    So, Proposed SMDBSCable is 1R X 3C X 35 SQMM (Al)

    _______________________________________________________________

    SMDB1F (4),SMDB2F (5),SMDB3F (6),SMDB4F (7),SMDB5F(8)

    CABLE OF 1st, 2

    nd, 3

    rd, 4

    thand 5

    thFloor

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 53.39KW( 3) and using the Formulae provided

    Load Current (I) = 92.84 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a.For 3 C x 25 SQMM (Al) Cable = CCC = 95 A x 0.8 = 76 A (Not Satisfied)

    b.For 3 C x 35 SQMM (Al) Cable = CCC = 117 A x 0.8= 93.8 (Satisfied)

    So, Proposed SMDBCABLE OF 1st, 2

    nd, 3

    rd, 4

    thand 5

    thFloor

    1R X 3C X 35 SQMM (Al)

  • 8/10/2019 G + 5 ( Calculation Details )

    44/104

    44

    DB - S CABLE (9)SMDBS to DB SERVICE CABLE

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 5.32KW (3) and using the Formulae provided

    Load Current (I) = 9.25 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a)For 4 C x 1.5 SQMM (Cu) Cable = CCC = 22 A x 0.8 = 17.6 A (Satisfied)

    Note:-

    Though, CCC of 1.5 SQMM Cu cable is Satisfied but it cannot withstand its

    System Fault Current so, we Propose 6 SQMM Cu Cable

    So, Proposed DBSCable is 1R X 4C X 6 SQMM (Cu) .

    _______________________________________________________________

    MCC PANEL CABLE (10)SMDBS to MCC PANEL CABLE

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 38.66KW( 3) and using the Formulae provided

    Load Current (I) = 67.22 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 3 C x 16 SQMM (Al) Cable = CCC = 70 A x 0.8 = 56 A (Not Satisfied)

    b) For 3 C x 25 SQMM (Al) Cable = CCC = 95 A x 0.8 = 76 A (Satisfied)

    So, Proposed MCC PANEL CABLE is 1R X 3C X25 SQMM (Al) .

    _______________________________________________________________

    CAPACITOR BANK CABLE (11)MCC PANEL TO CAPACITOR BANK

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 25 KVAR ( 3) and using the Formulae provided

    Load Current (I) = 57.9 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 3 C x 16 SQMM (Al) Cable = CCC = 70 A x 0.8 = 56 A (Not Satisfied)

    b) For 3 C x 25 SQMM (Al) Cable = CCC = 95 A x 0.8 = 76 A (Satisfied)

  • 8/10/2019 G + 5 ( Calculation Details )

    45/104

    45

    So, Proposed CAPACITOR BANK CABLE 1R X 3C X 25 SQMM (Al) .

    _______________________________________________________________

    LIFT MOTOR CABLE (12)MCC PANEL CABLE TO LIFT MOTOR

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 20KW( 3) and using the Formulae provided

    Load Current (I) = 34.77 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 4 C x 6 SQMM (Cu) Cable = CCC = 51 A x 0.8 = 40.8 A (Satisfied)

    So, ProposedLIFT MOTOR CABLE 1R X 4C X 6 SQMM (Cu) .

    _______________________________________________________________

    WATER SERVICE (W.S) MOTOR CABLE (13)MCC TO W.S MOTOR

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 7.45KW( 3) and using the Formulae provided

    Load Current (I) = 12.9 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 4 C x 4 SQMM (Cu) Cable = CCC = 40 A x 0.8 = 32 A (Satisfied)

    So, Proposed W.S MOTOR CABLE is1R X 4C X4 SQMM (Cu) .

    _______________________________________________________________

    FIRE FIGHTING (F.F) MOTOR CABLE (14)MCC TO F.F MOTOR

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 11.17KW( 3) and using the Formulae provided

    Load Current (I) = 19.24 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 4 C x 4 SQMM (Cu) Cable = CCC = 40 A x 0.8 = 32 A (Satisfied)

    So, Proposed F.F MOTOR CABLE is 1R X 4C X 4 SQMM (Cu) .

  • 8/10/2019 G + 5 ( Calculation Details )

    46/104

    46

    DBF1(15), DBF2 (16) OF SMDB 1FAND DBF1(19), DBF2 (20) OF

    SMDB 2F CABLE .

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 12.24KW( 3) and using the Formulae provided

    Load Current (I) = 21.28 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 4 C x 2.5 SQMM (Cu) Cable = CCC = 30A x 0.8 = 28 A (Satisfied)

    Note:-

    Though, CCC of 1.5 SQMM Cu cable is Satisfied but it cannot withstand its System Fault

    Current so, we Propose 6 SQMM Cu Cable

    So, Proposed Cable(15) , (16) , (19) , (20)is 1R X 4C X 6 SQMM (Cu) .

    ___________________________________________________________

    DBF1(23), DBF2 (24) OF SMDB 3F,DBF1(27), DBF2 (28) OF SMDB

    4FAND DBF1(31), DBF2 (32) OF SMDB 5F CABLE.

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 12.24KW( 3) and using the Formulae provided

    Load Current (I) = 21.28 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 4 C x 4 SQMM (Cu) Cable = CCC = 40 A x 0.8 = 32 A (Satisfied)

    So, Proposed Cable(23),(24),(27),(28),(31),(32)is 1R X 4C X 2.5 SQMM (Cu) .

    _______________________________________________________________

    DBF3(17), DBF4 (18) OF SMDB 1F,DBF3(21), DBF4(22) OF SMDB 2F,

    DBF3(25),DBF4(26) OF SMDB 3F,DBF3(29), DBF4 (30) OF SMDB 4F,

    DBF3(33), DBF4 (34) OF SMDB 5F CABLE DB-F3, DB-F4 of SMDB1F to

    DB-F3,DB-F4OF SMDB5F CABLE

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 14.45KW( 3) and using the Formulae provided

  • 8/10/2019 G + 5 ( Calculation Details )

    47/104

    47

    Load Current (I) = 25.12 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 4 C x 4 SQMM (Cu) Cable = CCC = 40 A x 0.8 = 32 A (Satisfied)

    So, ProposedCable(17),(18),(21),(22),(25),(26),(29),(30),(33),(34) is

    1R X 4C X 2.5 SQMM (Cu) .

    _______________________________________________________________

    DG SET CABLE (35)SMDB - S TO DG SET

    Cable is in Air and Derating Factor is 0.8

    Here, Load is 100 KVA ( 3) and using the Formulae provided

    Load Current (I) = 139.12 A

    Now, Check with Nearest CCC of various Cable Size from LT Catalogue.

    a) For 3 C x 70 SQMM (Al) Cable = CCC = 176 A x 0.8 = 140.8 A (Satisfied)

    So, Proposed DG SET CABLE is1R X 3C X 70 SQMM (Al)

    LIST OF PROPOSED CABLE SIZES

    FEEDERN0 PROPOSED CABLE SIZE

    1 1R X 3C X 240 SQMM ( Al )

    2 2R x 3.5C x 240 SQMM (Al)

    3 1R X 3C X 35 SQMM (Al)

    4,5,6,7,8 1R X 3C X 35 SQMM (Al)

    9 1R X 4C X 6 SQMM (Cu)

    10 1R X 3C X 25 SQMM (Al)

  • 8/10/2019 G + 5 ( Calculation Details )

    48/104

    48

    11 1R X 3C X 25 SQMM (Al)

    12 1R X 4C X 6 SQMM (Cu)

    13 1R X 4C X 4 SQMM (Cu)

    14 1R X 4C X 4 SQMM (Cu)

    15,16,19,20 1R X 4C X 6 SQMM (Cu)

    23,24,27,28,31,32 1R X 4C X 2.5 SQMM (Cu)

    17,18,21,22,25,26,29,30,33,34 1R X 4C X 2.5 SQMM (Cu)

    351R X 3C X 70 SQMM (Al)

  • 8/10/2019 G + 5 ( Calculation Details )

    49/104

    49

    VOLTAGE DROP SIZING CALCULATIONS

  • 8/10/2019 G + 5 ( Calculation Details )

    50/104

    50

    VOLTAGE DROP SIZING CALCULATIONS

    Voltage drop plays a very important role in operation of any Equipment.

    Ex- If a system works with a minimum voltage of 207 V and in case 206 V is supplied thenParticular system doesnt works.

    As per NBC Standards Voltage drop for Lighting Loop should be Less than 3 % to 5 % for

    Each loop.

    As per NBC Standards Voltage drop for Power Loop should be Less than 10 % to 15 % for

    each loop.

    In case , after adding the voltage drops for all feeders in Lighting (or) Power Loops & total

    value of %VDis greater than 3 % or 10 %then Choose the Feeder with highest value

    of%VD& change the Size of the Cable.

    Formulaesused to Calculate %VD:-

    VOLTAGR DROP ( VD )

    %VD=

  • 8/10/2019 G + 5 ( Calculation Details )

    51/104

    51

    Feeder 1HT Side

    Given Data :-

    a) Cable Size = 3c x 240 SQMM (Al)

    b) Length of Cable (L) = 45 mt

    c) Resistance of Cable (R) = 0.167 / KM

    d) No.of Runs = 1e. Load Current = 16.53 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 0.2061 V

    %VD=

    = 0.00187

    %VD= 0.00187

    Feeder 2 LT Side

    Given Data :-

    a. Cable Size = 3.5C x 240 SQMM (Al) b. Length of Cable (L) = 35 mt c. Resistance of Cable

    (R) = 0.167 / KM d. No.of Runs = 2 e. Load Current = 540.76 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 0.2655 V

    %VD=

    = 0.639

    %VD= 0.639

  • 8/10/2019 G + 5 ( Calculation Details )

    52/104

    52

    Feeder 3 SMDB - S

    Given Data :-

    a. Cable Size = 3C x 35 SQMM (Al) b. Length of Cable (L) = 3 mt c. Resistance of Cable

    (R) = 1.113 / KM d. No.of Runs = 1 e. Load Current = 76.5 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 0.442 V

    %VD=

    = 0.106639

    %VD = 0.1066

    Feeder 4(SMDB1F) ,Feeder 5(SMDB2F) , Feeder 6(SMDB3F) ,Feeder 7(SMDB - 4F),

    Feeder 8 (SMDB5F)

    Given Data :-

    a. Cable Size = 3C x 35 SQMM (Al) b. Length of Cable (L) = 3 mt c. Resistance of Cable

    (R) = 1.113 / KM d. No.of Runs = 1 e. Load Current = 92.84 A

    Voltage Drop is calculated using the Formulae Provided,

    VOLTAGR DROP ( VD ) = 0.536 V

    %VD=

    = 0.129

    %VD = 0.129

  • 8/10/2019 G + 5 ( Calculation Details )

    53/104

    53

    Feeder 9 DB - S

    Given Data :-

    a. Cable Size = 4C x 6 SQMM (Cu) b. Length of Cable (L) = 2mt c. Resistance of Cable

    (R) = 3.95 / KM d. No.of Runs = 1 e. Load Current = 9.25 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 0126 V

    %VD=

    = 0.0303

    %VD = 0.0303

    Feeder 10MCC PANEL

    Given Data :-

    a. Cable Size = 3C x 25 SQMM (Al) b. Length of Cable (L) = 2 mt c. Resistance of Cable

    (R) = 1.539 / KM d. No.of Runs = 1 e. Load Current = 67.22 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 0.358 V

    %VD=

    = 0.0836

    %VD = 0.0863

    Feeder 11 CAPACITOR BANK

    Given Data :-

    a. Cable Size = 3C x 25 SQMM (Al) b. Length of Cable (L) = 3 mt c. Resistance of Cable

  • 8/10/2019 G + 5 ( Calculation Details )

    54/104

    54

    (R) = 1.539 / KM d. No.of Runs = 1 e. Load Current = 57.9 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD )

    = 0.463 V

    %VD=

    = 0.111415

    %VD = 0.111

    Feeder 12 LIFT MOTOR LOAD

    Given Data :-

    a. Cable Size = 4C x 6 SQMM (Cu) b. Length of Cable (L) = 30 mt c. Resistance of Cable

    (R) = 3.95 / KM d. No.of Runs = 1 e. Load Current = 34.77 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 7.136 V

    %VD=

    = 1.719

    %VD = 1.719

    Feeder 13 WATER SERVICE MOTOR (W.S)

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Length of Cable (L) = 25mt c. Resistance of Cable

    (R) = 5.91 / KM d. No.ofRuns = 1 e. Load Current = 12.9 A

    Voltage Drop is calculated using the Formulae Provide,

  • 8/10/2019 G + 5 ( Calculation Details )

    55/104

    55

    VOLTAGR DROP ( VD ) = 3.301V

    %VD=

    = 0.795

    %VD = 0.795

    Feeder 14FIRE FIGHTING MOTOR (FF)

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Al) b. Length of Cable (L) = 30 mt c. Resistance of Cable

    (R) = 5.91 / KM d. No.of Runs = 1 e. Load Current = 19.42 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 5.96 V

    %VD=

    = 1.437

    %VD = 1.437

    NOTE:- For Power Loop i.e. ,

    Feeder 1 + Feeder 2 + Feeder 10 + Feeder 9 + Feeder 11

    = 0.00187 + 0.639 + 0.1066 + 0.0863 + 1.719 = 2.552 V

    TOTAL %VDof one Power Loop = 2.552 V

    Therefore, As per Standards % VD is less than 10 % and is satisfied.

  • 8/10/2019 G + 5 ( Calculation Details )

    56/104

    56

    Feeder 15(SMDB1F TO DB F1) , Feeder 16(SMDB1F TO DB F2)

    Given Data :-

    a. Cable Size = 4C x 6 SQMM (Cu) b. Length of Cable (L) = 3 mt c. Resistance of Cable

    (R) = 3.95 / KM d. No.of Runs = 1 e. Load Current = 21.28 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 0.436 V

    %VD=

    = 0.105

    %VD = 0.105

    NOTE :- For Lighting Loop i.e.,

    Feeder 1 + Feeder 2 + Feeder 4 + Feeder 15

    = 0.00187 + 0.639 + 0.1066 + 0.129 + 0.105 = 1.022 V

    TOTAL %VDof one Lighting Loop = 1.022 V

    Therefore, As per Standards % VD is less than 3% and is satisfied.

    Feeder 17(SMDB1F TO DB F3) , Feeder 18(SMDB1F TO DB F4)

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Length of Cable (L) = 4 mt c. Resistance of Cable

    (R) = 5.91 / KM d. No.of Runs = 1 e. Load Current = 25.12 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 1.028 V

  • 8/10/2019 G + 5 ( Calculation Details )

    57/104

    57

    %VD=

    = 0.247

    %VD = 0.247

    Feeder 19(SMDB2F TO DB F1) , Feeder 20(SMDB2F TO DB F2)

    Given Data :-

    a. Cable Size = 4C x 6 SQMM (Cu) b. Length of Cable (L) = 5 mt c. Resistance of Cable

    (R) = 3.95 / KM d. No.of Runs = 1 e. Load Current = 21.28 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 0.727 V

    %VD=

    = 0.175

    %VD = 0.175

    Feeder 21(SMDB2F TO DB F3) , Feeder 22(SMDB2F TO DB F4)

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Length of Cable (L) = 6mt c. Resistance of Cable

    (R) = 5.91 / KM d. No.of Runs = 1 e. Load Current = 25.12 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 1.542V

    %VD=

    0.371

    Feeder 23(SMDB3F TO DB F1) , Feeder 24(SMDB3F TO DB F2)

    %VD = 0.371

  • 8/10/2019 G + 5 ( Calculation Details )

    58/104

    58

    Given Data :-

    a) Cable Size = 4C x 2.5 SQMM (Cu) b. Length of Cable (L) = 7 mt c. Resistance of Cable

    (R) = 9.5 / KM d. No.of Runs = 1 e. Load Current = 21.28 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 2.45V

    %VD=

    = 0.5905

    %VD = 0.5905

    Feeder 25(SMDB3F TO DB F3) , Feeder 26(SMDB3F TO DB F4)

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Length of Cable (L) = 8mt c. Resistance of Cable

    (R) = 5.91 / KM d. No.of Runs = 1 e. Load Current = 25.12 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 2.507 V

    %VD=

    = 0.495

    Feeder 27(SMDB4F TO DB F1) , Feeder 28(SMDB4F TO DB F2)

    Given Data :-

    a) Cable Size = 4C x 2.5 SQMM (Cu) b. Length of Cable (L) = 9 mt c. Resistance of Cable

    (R) = 9.5 / KM d. No.ofRuns = 1 e. Load Current = 21.28 A

    %VD = 0.495

  • 8/10/2019 G + 5 ( Calculation Details )

    59/104

    59

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 3.51 V

    %VD= = 0.759

    Feeder 29(SMDB4F TO DB F3) , Feeder 30(SMDB4F TO DB F4)

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Length of Cable (L) = 10 mt c. Resistance of Cable

    (R) = 5.91 / KM d. No.of Runs = 1 e. Load Current = 25.12 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 2.571 V

    %VD= = 0.169

    Feeder 31(SMDB5F TO DB F1) , Feeder 32(SMDB5F TO DB F2)

    Given Data :-

    a. Cable Size = 4C x 2.5 SQMM (Cu) b. Length of Cable (L) = 11mt c. Resistance of Cable

    (R) = 9.5 / KM d. No.of Runs = 1 e. Load Current = 21.28 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 3.851 V

    %VD= = 0.928

    %VD = 0.759

    %VD = 0.619

  • 8/10/2019 G + 5 ( Calculation Details )

    60/104

    60

    %VD = 0.928

    Feeder 33(SMDB5F TO DB F3) , Feeder 34(SMDB5F TO DB F4)

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Length of Cable (L) = 12 mt c. Resistance of Cable

    (R) = 5.91 / KM d. No.of Runs = 1 e. Load Current = 25.12 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD )

    = 3.085 V

    %VD=

    = 0.743

    Feeder 35 DG SET

    Given Data :-

    a) Cable Size = 3C x 70 SQMM (Al) b. Length of Cable (L) = 2 mt c. Resistance of Cable

    (R)= 0.568 / KM d. No.ofRuns = 1 e. Load Current = 139.12 A

    Voltage Drop is calculated using the Formulae Provide,

    VOLTAGR DROP ( VD ) = 0.273 V

    %VD=

    = 0.0659

    %VD = 0.0659

    %VD = 0.743

  • 8/10/2019 G + 5 ( Calculation Details )

    61/104

  • 8/10/2019 G + 5 ( Calculation Details )

    62/104

    62

    SHORT CIRCUIT ( S.C) CALCULATIONS

    S.C Calculation is done to know the amount of fault current passing through a cable.

    S.C Current Values For Different C.B :-

    a.Miniature Circuit Breaker ( MCB ) - 10 KA to 16 kA( 0.5 A to 63 A )

    b.Moulded Case Circuit Breaker ( MCCB ) - 25 KA to 35 kA

    ( 63 A to 800 A )

    c.VCB / ACB / SF6C.B - 50 KA to 65 kA

    (800 A to 6300 A )

    FORMULAES USED TO CALCULATE S.C CURRENT

    Impedance of cable

    Pu Impedance of T/F

    Pu Imp of Cable =

    Pu Impedance based on System Voltage=

    ( )

    Total Pu Imp =Previous Pu Imp + Present Pu Imp

    HT Side PreviousPu Imp is POS

    Pu Impedance based at POS=

    Note:-While Changing a Loop PrevPu Imp has to be taken carefully

  • 8/10/2019 G + 5 ( Calculation Details )

    63/104

    63

    Max Fault Current Upto C.B=

    Total Max Fault Current = _________________________________________________________________

    Feeder 1:- HT SIDE

    Given Data :-

    a. Cable Size = 3C x 240 SQMM (Al) b. Length of Cable (L) = 45mt c. Cable Impedance

    = () ()= 0.157 / KM d. No.of Runs = 1e) Maximum Fault Current = 350 MVA (Taken from nearest Substation) and

    f) Minimum Fault Current or Base MVA = 100 MVA (Taken from nearest Substation)

    Calculate S.C Current by using FormulaesProvided,

    Pu Impedance of 45 mtCable = = 0.007065Pu

    Pu Impedance based on System Voltage =

    () = 0.00632231405Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    HT Side PreviousPu Imp is at POS

    Pu Impedance at Point of Supply (POS) = = 0.285714285Pu

    Total Pu Imp = 0.285714285 + 0.00632231405 = 0.292036599Pu

  • 8/10/2019 G + 5 ( Calculation Details )

    64/104

    64

    MAX FAULT CURRENT UPTO C.B (1) =

    = 342.422834 MVA

    Note : - 342.422834 MVA > 350 MVA ( Given Max Fault Current )

    TOTAL MAX FAULT CURRENT =

    = 17.973KA 18 KA

    S.C Current at HT Side = 18 KA

    Only For T/F:

    Pu Impedance of T/F =

    = 15.87301587Pu

    Total PuImp of T/F = Previous Pu Imp + Present Pu Imp

    = 0.292036599 + 15.87301587= 16.16505247Pu

    Feeder 2 :-LT SIDEAlways Choose Underground Cable .

    Given Data :-

    a. Cable Size = 3C x 240 SQMM (Al) b.Cable Length (L) = 35 mt c. Cable Impedance

    =() ()= 0.157 / Kmd. No.of Runs = 2

    Pu Impedance of 35 mt Cable =

    = = 0.0027475 Pu

    Pu Impedance based on System Voltage =

    () = 1.59529685Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    = 16.16505247+ 1.59529685=17.76034932Pu

  • 8/10/2019 G + 5 ( Calculation Details )

    65/104

    65

    MAX FAULT CURRENT UPTO C.B (2) =

    = 5.630519 MVA

    TOTAL MAX FAULT CURRENT =

    = 7.833 KA

    S.C Current at LT Side = 7.833 KA

    Feeder 3(SMDB-S) , Feeder 4(SMDB-1F) , Feeder 5(SMDB-2F) , Feeder 6(SMDB-3F),Feeder 7(SMDB-4F) ,Feeder 8(SMDB-15F)

    Given Data :-

    a. Cable Size = 3C x 35 SQMM (Al) b. Length of Cable (L) = 3 mt c. Cable Impedance

    = () ()= 1.046 / KM d. No.of Runs = 1

    Pu Impedance of 3mt Cable =

    = 0.003138Pu

    Pu Impedance based on System Voltage =

    () = 1.822035128Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    = 17.76034932 +1.822035128= 19.58238445Pu

    MAX FAULT CURRENT UPTO C.B (3,4,5,6,7.8) =

    = 5.106630 MVA

    TOTAL MAX FAULT CURRENT = = 7.104KA

  • 8/10/2019 G + 5 ( Calculation Details )

    66/104

    66

    S.C Current at SMDB-S,SMDB-1F,SMDB-2F,SMDB-3F,SMDB-4Fand

    SMDB-5F = 7.10 KA

    Feeder 9 :- DB -S

    Given Data :-

    a. Cable Size = 4C x 6 SQMM (Cu) b. Length of Cable (L) = 2mt c. Cable Impedance

    = () () = 3.69 / KM d. No.of Runs = 1

    Pu Impedance of 3mt Cable =

    = 0.00738Pu

    Pu Impedance based on System Voltage =

    () = 4.285092176 Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    = 19.58238445+ 4.285092176= 23.86747663Pu

    MAX FAULT CURRENT UPTO C.B (9) =

    = 4.189801 MVA

    TOTAL MAX FAULT CURRENT = = 5.829 KA

    S.C Current at DB-S = 5.82 KA

    Feeder 10 :- MCC PANEL

    Given Data :-

  • 8/10/2019 G + 5 ( Calculation Details )

    67/104

    67

    a. Cable Size = 3C x 25 SQMM (Al) b. Length of Cable (L) = 3mt c. Cable Impedance

    = () () = 1.44 / KM d. No.of Runs = 1

    Pu Impedance of 3mt Cable =

    = 0.00432Pu

    Pu Impedance based on System Voltage =

    () = 2.50834664Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    = 19.58238445+ 2.50834664 = 22.09073109Pu

    MAX FAULT CURRENT UPTO C.B (10) =

    = 4.526785 MVA

    TOTAL MAX FAULT CURRENT =

    = 6.297KA

    S.C Current at MCC PANEL = 6.29 KA

    Feeder 11 : MCC PANEL To Capacitor Bank

    Given Data :-

    a. Cable Size = 3C x 25 SQMM (Al) b. Length of Cable (L) = 3mt c. Cable Impedance

    = () () = 1.44 / KM d. No.of Runs = 1

    Pu Impedance of 3mt Cable =

    = 0.00432Pu

  • 8/10/2019 G + 5 ( Calculation Details )

    68/104

    68

    Pu Impedance based on System Voltage =

    () = 2.50834664 Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    = 22.09073109+ 2.50834664 = 24.59907773Pu

    MAX FAULT CURRENT UPTO C.B (11) =

    = 4.065193 MVA

    TOTAL MAX FAULT CURRENT =

    = 5.655KA

    S.C Current at Capacitor Bank = 5.65 KA

    Feeder 12MCC PANEL To Lift Motor

    Given Data :-

    a. Cable Size = 4C x 6 SQMM (Cu) b. Cable Length (L) = 30mt c. Cable Impedance

    = () ()= 4.61 / KM d. No.of Runs = 1

    Pu Impedance of 3mt Cable = = 0.1383Pu

    Pu Impedance based on System Voltage =

    () = 80.40193061Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    = 22.09073109+ 80.40193061= 102.4926617Pu

    MAX FAULT CURRENT UPTO C.B (12) =

    = 9.75679 MVA

    TOTAL MAX FAULT CURRENT = = 1.357 KA

  • 8/10/2019 G + 5 ( Calculation Details )

    69/104

    69

    S.C Current at Lift Motor = 1.35 KA

    Feeder 13MCC PANEL To Water Service(W.S) Motor

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Cable Length (L) = 25mt c. Cable Impedance

    = () ()= 5.53 / KM d. No.of Runs = 1

    Pu Impedance of 3mt Cable = = 0.13325Pu

    Pu Impedance based on System Voltage = () = 77.36971984Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    = 22.09073109+ 77.36971984= 99.46045093Pu

    MAX FAULT CURRENT UPTO C.B (13) = = 1.00542 MVA

    TOTAL MAX FAULT CURRENT =

    = 1.398 KA

    S.C Current at W.S Motor = 1.39 KA

    Feeder 14MCC PANEL To Fire Fighting (F.F) Motor

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Cable Length (L) = 30mt c. Cable Impedance

    = () () = 5.53 / KM d. No.of Runs = 1

    Pu Impedance of 3mt Cable = = 0.1599Pu

  • 8/10/2019 G + 5 ( Calculation Details )

    70/104

    70

    Pu Impedance based on System Voltage =

    () = 92.84366381Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    = 22.09073109+ 92.84366381= 114.9326098Pu

    MAX FAULT CURRENT UPTO C.B (14) =

    = 0.870075 MVA

    TOTAL MAX FAULT CURRENT =

    = 1.210 KA

    S.C Current at F.F Motor = 1.21 KA

    Feeder 15 ( SMDB-1F to DB F1), Feeder 16 ( SMDB-1F to DB F2):-

    Given Data :-

    a. Cable Size = 4C x 6 SQMM (Cu) b. Cable Length (L) = 3mt c. Cable Impedance

    = () () = 3.69 / KM d. No.of Runs = 1

    Pu Impedance of 3mt Cable =0.01107Pu

    Pu Impedance based on System Voltage = 6.427638264Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+6.427638264 = 25.95002271Pu

    MAX FAULT CURRENT UPTO C.B (15,16) = 3.853561MVA

    TOTAL MAX FAULT CURRENT = 5.36KA

    S.C Current at Feeder 15,16 = 5.36 KA

  • 8/10/2019 G + 5 ( Calculation Details )

    71/104

    71

    Feeder 17( SMDB-1F to DB F3), Feeder 18 ( SMDB-1F to DB F4) :-

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Cable Length (L) = 4mt c. Cable Impedance

    = () () = 5.53 / KM d. No.of Runs = 1

    Pu Impedance of 4mt Cable = 0.022121616Pu

    Pu Impedance based on System Voltage = 12.84460212Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+12.84460212 = 32.36698657Pu

    MAX FAULT CURRENT UPTO C.B (17,18) = 3.089567 MVA

    TOTAL MAX FAULT CURRENT = 4.29KA

    S.C Current at Feeder 17,18 = 4.29 KA

    Feeder 19 ( SMDB-2F to DB F1), Feeder 20( SMDB-2F to DB F2) :-

    Given Data :-

    a. Cable Size = 4C x 6 SQMM (Cu) b. Cable Length (L) = 5mt c. Cable Impedance

    = () () = 3.69 / KMd. No.of Runs = 1 Pu Impedance of 5mt Cable =0.01845Pu

    Pu Impedance based on System Voltage= 10.71273044Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+ 10.71273044=30.23511489Pu

    MAX FAULT CURRENT UPTO C.B (19,20) = 3.307412 MVA

  • 8/10/2019 G + 5 ( Calculation Details )

    72/104

    72

    TOTAL MAX FAULT CURRENT= 4.60 KA

    S.C Current at Feeder 19,20 = 4.60 KA

    Feeder 21 ( SMDB-2F to DB F3), Feeder 22 ( SMDB-2F to DB F4):-

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Cable Length (L) = 6mt c. Cable Impedance

    = () ()= 5.53 / KM d. No.of Runs = 1

    Pu Impedance of 6mt Cable = 0.03318Pu

    Pu Impedance based on System Voltage= 19.26549572Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+19.26549572=38.78788017Pu

    MAX FAULT CURRENT UPTO C.B (21,22) = 2.578124 MVA

    TOTAL MAX FAULT CURRENT= 3.58 KA

    S.C Current at Feeder 21,22 = 3.58 KA

    Feeder 23 ( SMDB-3F to DB F1) , Feeder 24 ( SMDB-3F to DB F2) :-\

    Given Data :-

    a. Cable Size = 4C x 2.5 SQMM (Cu) b. Cable Length (L) = 7mt c. Cable Impedance

    = () () = 8.88 / KM d. No.of Runs = 1 Pu Impedance of 7mt Cable = 0.06216Pu

    Pu Impedance based on System Voltage= 36.09232109 Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

  • 8/10/2019 G + 5 ( Calculation Details )

    73/104

    73

    =19.52238445+ 36.09232109= 55.61470559 Pu

    MAX FAULT CURRENT UPTO C.B (23,24) = 1.798085 MVA

    TOTAL MAX FAULT CURRENT= 2.50 KA

    S.C Current at Feeder 23,24 = 2.50 KA

    Feeder 25 ( SMDB-3F to DB F3), Feeder 26 ( SMDB-3F to DB F4):-

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Cable Length (L) = 8mt c. Cable Impedance

    = () () = 5.53 / KM d. No.of Runs = 1 Pu Impedance of 8mt Cable = 0.04424 Pu

    Pu Impedance based on System Voltage= 25.68732762 Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+25.68732762 = 45.20971297 Pu

    MAX FAULT CURRENT UPTO C.B (25,26) = 2.211914 MVA

    TOTAL MAX FAULT CURRENT= 3.07 KA

    S.C Current at Feeder 25,26 = 3.07 KA

    Feeder 27 ( SMDB-4F to DB F1), Feeder 28 ( SMDB-4F to DB F2):-

    Given Data :-

    a. Cable Size = 4C x 2.5 SQMM (Cu) b. Cable Length (L) = 9mt c. Cable Impedance

    = () () = 8.88 / KM d. No.of Runs = 1 Pu Impedance of 9mt Cable = 0.07992Pu

  • 8/10/2019 G + 5 ( Calculation Details )

    74/104

    74

    Pu Impedance based on System Voltage= 46.40441283Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+46.40441283 = 65.92679728Pu

    MAX FAULT CURRENT UPTO C.B (27,28) = 1.516833 MVA

    TOTAL MAX FAULT CURRENT= 2.11 KA

    S.C Current at Feeder 27,28 = 2.11 KA

    Feeder 29 ( SMDB-4F to DB F3) , Feeder 30 ( SMDB-4F to DB F4):-

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Cable Length (L) = 10mt c. Cable Impedance

    = () ()= 5.53 / KM d. No.of Runs = 1 Pu Impedance of 10mt Cable = 0.0553 Pu

    Pu Impedance based on System Voltage= 32.10915953 Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+32.10915953 = 51.63154398 Pu

    MAX FAULT CURRENT UPTO C.B (25,26) = 1.936800 MVA

    TOTAL MAX FAULT CURRENT= 2.69 KA

    S.C Current at Feeder 29,30 = 2.69 KA

    Feeder 31 ( SMDB-5F to DB F1), Feeder 32 ( SMDB-5F to DB F2):-

    Given Data :-

    a. Cable Size = 4C x 2.5 SQMM (Cu) b. Cable Length (L) = 11mt c. Cable Impedance

  • 8/10/2019 G + 5 ( Calculation Details )

    75/104

    75

    = () () = 8.88 / KM d. No.of Runs = 1 Pu Impedance of 11mt Cable = 0.09768 Pu

    Pu Impedance based on System Voltage= 56.71650457Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+56.71650457=76.2388902Pu

    MAX FAULT CURRENT UPTO C.B (31,32) = 1.311666 MVA

    TOTAL MAX FAULT CURRENT= 1.824 KA

    S.C Current at Feeder 31,32 = 1.82 KA

    Feeder 33 ( SMDB-5F to DB F3), Feeder 34 ( SMDB-5F to DB F4):-

    Given Data :-

    a. Cable Size = 4C x 4 SQMM (Cu) b. Cable Length (L) = 12mt c. Cable Impedance

    = () () = 5.53 / KM d. No.of Runs = 1 Pu Impedance of 12mt Cable = 0.06636 Pu

    Pu Impedance based on System Voltage= 38.53099144 Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+38.53099144 = 58.05337589 Pu

    MAX FAULT CURRENT UPTO C.B (33,34) = 1.722552 MVA

    TOTAL MAX FAULT CURRENT= 2.39 KA

  • 8/10/2019 G + 5 ( Calculation Details )

    76/104

    76

    S.C Current at Feeder 33,34 = 2.39 KA

    Feeder 35 ( SMDB-S TO DG SET ) :-

    Given Data :-

    a. Cable Size = 3C x 70 SQMM (Al) b. Cable Length (L) = 2mt c. Cable Impedance

    = () () = 0.53 / KM d. No.of Runs = 1 Pu Impedance of 2mt Cable = 0.00106Pu

    Pu Impedance based on System Voltage= 0.615473944Pu

    Total Pu Imp = Previous Pu Imp + Present Pu Imp

    =19.52238445+0.615473944 =20.13785839Pu

    MAX FAULT CURRENT UPTO C.B (35) = 4.965771 MVA

    TOTAL MAX FAULT CURRENT= 6.90 KA

    S.C Current at Feeder 35 = 6.90 KA

  • 8/10/2019 G + 5 ( Calculation Details )

    77/104

    77

    CIRCUIT BREAKER (C.B) RATING CALCULATIONS

  • 8/10/2019 G + 5 ( Calculation Details )

    78/104

    78

    CIRCUIT BREAKER(C.B) RATING CALCULATIONS

    FormulaesUsed:-

    Load Currentis calculated using below equationsCase 1:- If Load is in KWthen P = 3 V I Cos (3 ) (Above 4 KW Load)

    P = V I Cos (1 )

    Case 2:- If Load is in KVAthen P = 3 V I (3 )

    P = V I (1 )

    Case 3:- IfLoad is in KVARthen P = 3 V I Sin (3 )

    Where, = 36.8in all cases.

    C.B Rating = 1.25 x Full Load Current (FLC)

    __________________________________________________________________________

    HT SIDE :- C.B (1)

    Note:-

    a. As per Local standardsC.B Rating is 200A VCB / ACB.

    b.As per International standardsC.B Rating is 630A VCB / ACB.

    Here, C.B Size is chosen according to Local Standards

    Therefore, Proposed C.B(1) Rating is 200 A VCB.

    LT SIDE :- C.B (2) P = 310.95 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 540.76 A .

    C.B Raring = 1.25 x 540.76 = 675.95 A

    Therefore, Proposed C.B(2) Rating is 800 A ACB.

    SMDB-S :- C.B (3) P = 43.98 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 76.48A ,

  • 8/10/2019 G + 5 ( Calculation Details )

    79/104

    79

    C.B Raring = 1.25 x 76.48 = 95.6 A

    Therefore, Proposed C.B(3) Rating is 100 A MCCB.

    SMDB -1F C.B (4), SMDB - 2F C.B (5),SMDB - 3F C.B (6),SMDB - 4F C.B (7),

    SMDB - 5F C.B (8) have same Rating P = 53.39 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 92.84A ,

    C.B Raring = 1.25 x 92.84 = 116.05 A

    Therefore, Proposed C.B(4),C.B(5),C.B(6),C.B(7),C.B(8) Rating is 125 A MCCB

    DB-S C.B (9) P = 5.32 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 9.25A ,

    C.B Raring = 1.25 x 9.25 = 11.56 A

    Therefore, Proposed C.B(9) Rating is 16 A MCB.

    MCC PANEL C.B (10) P = 38.66 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 67.22A ,

    C.B Raring = 1.25 x 67.22 = 84.03 A

    Therefore, Proposed C.B(10) Rating is 100 A MCCB.

    MCC TO CAPACITOR BANK C.B (11) P = 25 KVAR

    Load Current is calculated by using Formulaes Provided

    ie. FLC = 57.96A ,

    C.B Raring = 1.25 x 57.96 = 72.45 A

    Therefore, Proposed C.B(11) Rating is 80 A MCCB.

    MCC TO LIFT MOTOR C.B (12) P = 20 KW

  • 8/10/2019 G + 5 ( Calculation Details )

    80/104

    80

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 34.77A ,

    C.B Raring = 1.25 x 34.77 = 43.77 A

    Therefore, Proposed C.B(12) Rating is 60 A MCB.

    MCC TO WATER SERVICE (W.S) C.B (13) P = 10 HP = 10 X0.745 = 7.45 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 12.95A ,

    C.B Raring = 1.25 x 12.95 = 16.19 A

    Therefore, Proposed C.B(13) Rating is25 A MCB.

    MCC TO FIRE FIGHTING (FF) C.B (14) P = 15 KW = 15 X 0.745 = 11.17 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 19.43A ,

    C.B Raring = 1.25 x 19.43 = 24.2 A

    Therefore, Proposed C.B(14) Rating is 25 A MCB.

    DB F1 AND DB F2OF SMDB 1F,SMDB 2F,SMDB 3F,SMDB 4F,SMDB 5F

    C.B 15,16,19,20,23,24,27,28,31,32 P = 12.24 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 21.28A ,

    C.B Raring = 1.25 x 21.28 = 26.60 A

    Therefore, Proposed C.B15,16,19,20,23,24,27,28,31,32 Rating is 32 A MCB.

    DB F3 AND DB F4OF SMDB 1F,SMDB 2F,SMDB 3F,SMDB 4F,SMDB 5F

    C.B 17,18,21,22,25,26,29,30,33,34 P = 14.45 KW

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 25.12A ,

  • 8/10/2019 G + 5 ( Calculation Details )

    81/104

    81

    C.B Raring = 1.25 x 25.12 = 31.41 A

    Therefore, Proposed C.B 17,18,21,22,25,26,29,30,33,34 Rating is 32 A MCB.

    SMDB - S TO DG SET C.B (35) P = 100 KVA

    Load Current is calculated by using Formulaes Provided

    i e. FLC = 139.12A ,

    C.B Raring = 1.25 x 139.12 = 173.89 A

    Therefore, Proposed C.B (35) Rating is 180 A MCCB.

  • 8/10/2019 G + 5 ( Calculation Details )

    82/104

    82

    CABLE CHECKING,C.B BREAKING CAPACITY AND

    TRIPPING TIME CALCULATIONS

  • 8/10/2019 G + 5 ( Calculation Details )

    83/104

    83

    CABLE CHECKING, C.B BREAKING CAPACITY AND TRIPPING TIME

    Full Data of C.B ----- -

    RATING OF C.B is calculated based on FLC

    BREAKING CAPACITY IS S.C CURRENT I e.SystemFault Current.

    Tripping Time is Duration of Fault Current

    List of Formulaes used :-

    1. HT Side :- t = 3 sec ( Constant )

    Cable withstanding capacity =

    Where, K = Constant value for material , A =Area of Cable (I e. Sqmm of cable)& t = Tripping

    Timeof C.B

    Here K = From HT cable Catalogue For Al = 0.143

    2. LT side : - t= 0.01 sec to 1 sec (I e. Check for t = 0.9,0.8,07 ..)

    Cable withstanding capacity =

    ISC` = Short Circuit Current taken from Gems Cab S.C Rating Catalogue

    ,Proposed Cable is Safe when

    {WITHSTANDING CAPACITY OF CABLE}> {SYSTEM FAULT CURRENT}

    S.C Current of Particular Feeder

    RATING OF C.B (Amps)

    BREAKING

    CAPACITY

    (KA)

    TRIPPING

    TIME

    (SEC)

  • 8/10/2019 G + 5 ( Calculation Details )

    84/104

    84

    Feeder N0 1HT SIDE t = 3 Sec ( Constant ) , K = 0.143 , A = 1R x 3C x 240 Sq mm(Al)

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 19.81 KA

    Full Data of C.B

    Cable withstanding capacity@ 3 sec = 19.81 KA ----- eqn 1

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 17.97 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    ____________________________________________________________________________

    Feeder N0 2LT SIDE Cable 2R x 3C x 240 Sq mm (Al) Isc= 18.18 @ t = 1 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 36.36 KA

    Full Data of C.B

    Cable withstanding capacity@ 1 sec = 36.36 KA----- eqn 1

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 7.85 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    ____________________________________________________________________________

    Feeder N0 3 SMDB-S

    Cable 1R x 3C x 35 Sq mm (Al) Isc= 2.65 @ t = 0.1 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    200 A VCB

    18 KA 3 Sec

    800 A (ACB)

    7.85 KA 1 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    85/104

    85

    Cable withstanding capacity =

    = 8.38 KACable withstanding capacity@ 0.1 sec = 8.38 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 7.12 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    _____________________________________________________________________________

    Feeder N0 4,5,6,7 & 8 SMDB 1F to SMDB 5F

    Cable 1R x 3C x 35 Sq mm (Al) Isc= 2.65 @ t = 0.1 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 8.38 KACable withstanding capacity@ 0.1 sec = 8.38 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 7.12 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe._____________________________________________________________________________

    Feeder N0 9 SMDBS to DB - S 1R x 3C x 6 Sq mm (Cu) Isc= 0.69 @ t = 0.01 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 6.9 KACable withstanding capacity@ 0.01 sec = 6.9 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    100 A MCCB

    7.12 KA 0.1 Sec

    125 A MCCB

    7.12 KA 0.1 Sec

    16 A MCB

    5.85 KA 0.01 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    86/104

    86

    = 5.85 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    _____________________________________________________________________________

    Feeder N0 10 SMDBS to MCC PANEL 1R x 3c x 25 Sqmm (Al) Isc= 1.89 @ t = 0.08s

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 6.68 KA

    Cable withstanding capacity@ 0.08 sec = 6.68 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 6.31 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    _____________________________________________________________________________

    Feeder N0 11 MCC PANEL to CAPACITOR BANK

    Cable 1R x 3c x 25 Sqmm (Al) Isc= Short Circuit Current Rating = 1.89 (Taken from

    Gems Cab S.C Rating Catalogue) @ t = 0.1 Sec

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 5.97 KA

    Cable withstanding capacity@ 0.1 sec = 5.97 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 5.65 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    Feeder N0 12 MCC PANEL to Lift Motor 1R x 4c x 6 Sqmm (Cu) Isc= 0.69 @ t = 0.2Sec

    100 A MCB

    6.31 KA 0.08 Sec

    80 A MCCB

    5.65 KA 0.1 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    87/104

    87

    Isc= S.C Circuit Current Rating = (Taken from Gems Cab S.C Rating Catalogue)

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 1.54 KA

    Cable withstanding capacity@ 0.2 sec = 1.54 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 1.35 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    ____________________________________________________________________________

    Feeder N0 13 MCC PANEL to Water Service (W.S) Motor

    Cable 1R x 4c x 4 Sqmm (Cu) Isc= 0.46 @ t = 0.1 Sec

    Isc= S.C Circuit Current Rating = (Taken from Gems Cab S.C Rating Catalogue)

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 1.45 KACable withstanding capacity@ 0.1 sec = 1.45 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 1.39 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    _____________________________________________________________________________

    Feeder N0 14 MCC PANEL to Fire Fighting (F.F) Motor

    Cable 1R x 4c x 4 Sqmm (Cu) Isc= 0.46 @ t = 0.1 Sec

    Isc= S.C Circuit Current Rating = (Taken from Gems Cab S.C Rating Catalogue)

    60 A MCB

    1.35 KA 0.2 Sec

    25 A MCB

    1.39 KA 0.1 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    88/104

    88

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 1.45 KA

    Cable withstanding capacity@ 0.1 sec = 1.45 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 1.21 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    _____________________________________________________________________________

    Feeder N0 15 ,16DBF1(15) , DBF2(16) OF SMDB1F

    Here For Cable 1R x 4C x 6 Sqmm (Cu) Isc= 0.69 @ t = 0.01 Sec

    Isc= S.C Circuit Current Rating = (Taken from Gems Cab S.C Rating Catalogue)

    Using FormulaesProvided :-

    Cable withstanding capacity =

    = 6.9 KA

    Cable withstanding capacity@ 0.01 sec = 6.9 KA----- eqn 1 Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 5.36 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    ____________________________________________________________________________

    Feeder N0 19,20DBF1(19) , DBF2(20) OF SMDB2F

    Here For Cable 1R x 4C x 6 Sqmm (Cu) Isc= 0.69 @ t = 0.01 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity = = 6.9 KA

    25 A MCB

    1.21 KA 0.1 Sec

    32 A MCB

    5.36 KA 0.01 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    89/104

    89

    Cable withstanding capacity@ 0.01 sec = 6.9 KA----- eqn 1

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 4.59 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    ____________________________________________________________________________

    Feeder N0 17,18DBF3 (17)& DBF4(18) OF SMDB1F

    Here For Cable 1R x 4c x 4 Sq mm (Cu) Isc= 0.46 @ t = 0.01 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 4.6 KACable withstanding capacity @ 0.01 sec = 4.6 KA----- eqn 1

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 4.29 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe.

    ____________________________________________________________________________

    Feeder N0 21,22DBF3 (21)& DBF4(22) OF SMDB2F

    Here For Cable 1R x 4c x 4 Sq mm (Cu) Isc= 0.46 @ t = 0.01 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 4.6 KA

    Cable withstanding capacity @ 0.01 sec = 4.6 KA----- eqn 1

    32 A MCB

    4.59 KA 0.01 Sec

    32 A MCB

    4.29 KA 0.01 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    90/104

    90

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 3.58 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe

    ____________________________________________________________________________

    Feeder N0 23,24DBF1(23)& DBF2(24) OF SMDB3F

    Here For Cable 1R x 4C x 2.5 Sq mm (Cu) Isc= 0.287 @ t = 0.01 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 2.87 KACable withstanding capacity @ 0.01 sec = 2.87 KA----- eqn 1

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 2.50 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe

    ____________________________________________________________________________

    Feeder N0 27,28DBF1(27)& DBF2(28) OF SMDB4F

    Here For Cable 1R x 4C x 2.5 Sq mm (Cu) Isc= 0.287 @ t = 0.01 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 2.87 KA

    Cable withstanding capacity @ 0.01 sec = 2.87 KA----- eqn 1

    32 A MCB

    3.58 KA 0.01 Sec

    32 A MCB

    2.50 KA 0.01 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    91/104

    91

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 2.11 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe

    ____________________________________________________________________________

    Feeder N0 25,26DBF3 (25)& DBF4(26) OF SMDB3F t = (0.01 to 1 ) Sec

    Here For Cable 1R x 4c x 4 Sqmm (Cu) Isc= 0.46 @ t = 0.01 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 4.6 KACable withstanding capacity @ 0.01 sec = 4.6 KA----- eqn 1

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 3.07 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe

    ____________________________________________________________________________

    Feeder N0 29,30DBF3 (29)& DBF4(30) OF SMDB4F t = (0.01 to 1 ) Sec

    Here For Cable 1R x 4c x 4 Sqmm (Cu) Isc= 0.46 @ t = 0.02Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 3.25 KA

    Cable withstanding capacity @ 0.02 sec = 3.25 KA----- eqn 1

    32 A MCB

    2.11 KA 0.01 Sec

    32 A MCB

    3.07 KA 0.01 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    92/104

    92

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 2.69 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe

    ____________________________________________________________________________

    Feeder N0 31,32DBF1(31)& DBF2(32) OF SMDB5F t = (0.01 to 1 ) Sec

    Here For Cable 1R x 4C x 2.5 Sq mm (Cu) Isc= 0.287 @ t = 0.02 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 2.02 KA

    Cable withstanding capacity @ 0.02 sec = 2.02 KA----- eqn 1

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 1.82 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe

    ____________________________________________________________________________

    Feeder N0 33,34DBF3 (33)& DBF4(34) OF SMDB3F t = (0.01 to 1 ) Sec

    Here For Cable 1R x 4c x 4 Sqmm (Cu) Isc= 0.46 @ t = 0.02Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 3.25 KA

    32 A MCB

    2.69 KA 0.02 Sec

    32 A MCB

    1.82 KA 0.02 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    93/104

    93

    Cable withstanding capacity @ 0.02 sec = 3.25 KA----- eqn 1

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 2.39 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe

    ____________________________________________________________________________

    Feeder N0 35 SMDBS to DG SET t = (0.01 to 1 ) Sec

    Here For Cable 1R x 3c x 70 Sqmm (Al) Isc= 5.30 @ t = 0.5 Sec

    Isc= Short Circuit Current Rating = Taken from Gems Cab S.C Rating Catalogue

    Using Formulaes Provided :-

    Cable withstanding capacity =

    = 7.49 KA

    Cable withstanding capacity @ 0.5 sec = 7.49 KA----- eqn 1

    Full Data of C.B

    System Fault Current I e. Calculated S.C Current at HT Side is

    = 6.90 KA ------ eqn 2

    Comparing Eqn 1 & 2 I e. Eqn 1 > Eqn 2 So, Proposed Cable is Safe

    32 A MCB

    2.39 KA 0.02 Sec

    180 A MCCB

    6.90 KA 0.5 Sec

  • 8/10/2019 G + 5 ( Calculation Details )

    94/104

    94

    LT SIDE - BUSBAR SIZING CALCULATION

  • 8/10/2019 G + 5 ( Calculation Details )

    95/104

    95

    LT SIDE - BUSBAR SIZING CALCULATION

    As per Standard for 1 SQMM Cu Current Carrying Capacity (CCC) is 1.6 A

    As per Standard for 1 SQMM Al Current Carrying Capacity (CCC) is 0.8 A

    LT SIDEHere Cu material is used for Bus Bar I e . CCC = 1.6 A / SQMM

    Full Load Current (FLC) = 540.76 A

    SIZE OF BUS BAR = ( )

    ( )

    =

    = 337.97 SQMM

    Therefore, Proposed Copper Bus Bar Sizeavailable in Market is,

    SIZE OF BUS BAR = 75 x 6 (Width x Thickness)

  • 8/10/2019 G + 5 ( Calculation Details )

    96/104

    96

    EARTHING CALCULATION

  • 8/10/2019 G + 5 ( Calculation Details )

    97/104

    97

    EARTHING CALCULATION

    Earthling is calculated based on Maximum S.C Current Value.

    Here Max Fault Current is at HT SIDE: - 18 KA

    Earthing resistance should always be less than 1 .

    LIST OF FORMULAES USED :-

    EARTH STRIP SIZE =

    ISC= Max Fault Current , t = Duration of TimeK = Constant Value of Conductivity (Cu = 118, Al = 90, GI = 80 )

    Here K = 118 (Cu) ISC= 18000 A and t =3 Sec

    = 264.2

    Nearest Earth Strip Sizeavailable in Market = 75 x 6 (Width x Thickness)

    EARTH PIT RESISTANCE ( Rrod)= ( )

    r= Resistivity of Soil = 0.2 / km (Taken from soil Test Eng )L= Length of rod = 3 mt

    d= Diameter of rod ( 40mm or 65mm or 75mm) = 65 mm = 0.065 mt

    Earth Pit Resistance ( Rrod)= ( )

    Earth Resistance should be less than 1 .So increase N0.of Pits by using Formulae

    Earth Resistance=

    Case 1:- If No.of Pits are 2 then Earth Resistance =

    = 1.2 (Not Sufficient)

    Case 2:- If No.of Pits are 3 then Earth Resistance = = 0.8 (Sufficient) for safety

    purpose go for another pit .

  • 8/10/2019 G + 5 ( Calculation Details )

    98/104

    98

    Case 3:- If No.of Pits are 3 then Earth Resistance = = 0.6 (Sufficient and Safe)

    Therefore, Proposed No.of Pits = 4 and 1 Rod in Each Pit

    EARTH STRIP RESISTANCE () ()

    r = Resistivity of Soil= 0.2 / km (Taken from soil Test Eng )

    L = Length of the Strip = Assume as 30 mt (Distance from PanelTaken from Site Eng)

    W = Depth Level of the Strip (1Feet to 2 Feet)=Mostly 2Feet = 2 x 0.3 = 0.6 mt .

    S = Size of Strip = 75 mm = 0.075 mt.

    () ()

    For 1 Rod =

    0.68

    OVERAL RESISTANCE =

    = = 0.31

    Conclusion:-

    Overall Resistance is less than 1 , the Earthing Designed for Building is Safe.

    Rrod= 0.6

    ()

  • 8/10/2019 G + 5 ( Calculation Details )

    99/104

    99

    LIGHTING PROTECTION CALCULATION

  • 8/10/2019 G + 5 ( Calculation Details )

    100/104

    100

    LIGHTING PROTECTION CALCULATION

    Given Data :-

    a) Height of the Building (H) = 18 mt b) Width of the Building (W) = 17.94 mt

    c) Length of the Building (L) = 23.7 mt. d) Location of Building = Kurnool , India

    Flashes / km2 as per year ( Ng ) :-

    Ng= 0.7 (Collected from IS 2309 or NFDA70 2000 Codes )

    Where, Ng = Yearly Avg Flux Density in a Region .

    Effective Collection Area ( Ac ) :-

    Ac= (W x L) + 2 (W x H) + 2 (L x H) + ()= (17.94 x 23.7) + 2 (17.94 x 18) + 2 (23.7 x 18) + ( )Therefore, Total Effected Area of Building ( Ac) = 2,238.37 Sq. mt .

    Now, Over all Area of Building = L x W X H = 23.7 x 17.94 x 18 = 7,653.20 Sq.mt.

    That implies 2,238.37 sq.mt area of building needs to be protected from Flashes or

    lighting strokes 0ut of 7,653.20 Sq.mt ( Total Area of Building) .

    Propability of Stroke (P) :-

    Here, P = 2,238.37 x 0.7 x 10-6= 1.56 x 10-3

    Overall Weighting Factor (W):-

    a = 1.7 Use of Structure (Value Varies Depending on Building)

    b = 0.8 Type of Construction (Varies)

    c = 1.7 Content or Consequential Effect (Constant)

    d = 2.0 Degree of Isolation (Constant)

    P = Acx Ngx 10-

    W = a x b x c x d x e

  • 8/10/2019 G + 5 ( Calculation Details )

    101/104

  • 8/10/2019 G + 5 ( Calculation Details )

    102/104

    102

    BILL OF QUANTITY (BOQ)

    ITEM NAME

    G.F

    +

    COR

    1ST

    FLOOR 2ND

    FLOOR 3RD

    FLOOR 4TH

    FLOOR 5th

    FLOOR

    F1 F2 F3 F4 F1 F2 F3 F4 F1 F2 F3 F4 F1 F2 F3 F F1 F2 F3 F4 TOT

    36 W LAMP 18 13 13 14 14 13 13 14 14 13 13 14 14 13 13 14 14 13 13 14 14 288

    24 W LAMP 45 - - - - - - - - - - - - - - - - - - - - 45

    CEILING

    FANS- 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 100

    EXHAUST

    FANS- 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 60

    6A SOCKET 3 14 14 17 17 14 14 17 17 14 14 17 17 14 14 17 17 14 14 17 17 313

    16A

    SOCKET3 8 8 9 9 8 8 9 9 8 8 9 9 8 8 9 9 8 8 9 9 173

    1 TR AC - 2 2 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2 1 1 30

    1.5 TR AC - - - 1 1 - - 1 1 - - 1 1 - - 1 1 - - 1 1 10

    315 KVA

    T/F- - - - - - - - - - - - - - - - - - - - - - - 1

    100 KVA

    DG1 - - - - - - - - - - - - - - - - - - - - 1

    2


Recommended