WS-415-091 / 06.26.00 GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM INSTALLATION AND OPERATION INSTRUCTIONS FOR MULTI-VIEW DECORATIVE FIREPLACE NATURAL GAS MODEL GD40-N PROPANE GAS MODEL GD40-P CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / AGA / CGA METHODS INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER. CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA-2.22 AND ANSI Z21.50 RESPECTIVELY FOR VENTED GAS FIREPLACE. Fax: (705)722-6031 Email: [email protected] Web: www.napoleon.on.ca Wolf Steel Ltd., RR#1, 9 Napoleon Rd., Barrie, ON., Canada L4M 4Y8 (705)721-1212 R-2000 W ARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. FOR YOUR SAFETY Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance. WHA T TO DO IF Y OU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. Follow the gas suppli- er's instructions. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Transcript
Page 1: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

1

WS-415-091 / 06.26.00

GAS FIRED - DIRECT VENT MILLIVOLT SYSTEMINSTALLATION AND OPERATION INSTRUCTIONS FOR

MULTI-VIEW DECORATIVE FIREPLACE

NATURAL GAS MODEL GD40-NPROPANE GAS MODEL GD40-P

CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / AGA / CGA METHODS

INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA-2.22 AND ANSI Z21.50 RESPECTIVELY FOR VENTED GAS FIREPLACE.

Fax: (705)722-6031 Email: [email protected]: www.napoleon.on.ca

Wolf Steel Ltd., RR#1, 9 Napoleon Rd.,Barrie, ON., Canada L4M 4Y8 (705)721-1212

R-2000

WARNING: If the information in these instructions is not followed exactly, a fire orexplosion may result causing property damage, personal injury or death.

FOR YOUR SAFETYDo not store or use gasoline or other flammable vapours and liquids in the vicinity of

this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:• Do not try to light any appliance.• Do not touch any electrical switch.• Do not use any phone in your building.

• Immediately call your gas supplier from aneighbor's phone. Follow the gas suppli-er's instructions.

• If you cannot reach your gas supplier, callthe fire department.

Installation and service must be performed by a qualified installer, service agencyor the gas supplier.

Page 2: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

2

WS-415-091 / 06.26.00

PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE

TABLE of CONTENTSPg 4-5 INTRODUCTION

WarrantyGeneral InstructionsGeneral InformationCare of Glass & Plated Parts

6-10 VENTINGVent LengthsVenting OptionsMobile Home InstallationAir Terminal Locations

11-12 PENINSULA INSTALLATION PROCE-DURE

FramingBar / Countertop InstallationBrick Panel InstallationFacing

13-14OPEN END INSTALLATION PROCE-DURE

FramingBrick Panel InstallationFacing

15 SEE-THRU INSTALLATION PROCEDUREFramingBrick Panel InstallationFacing

PG 16-20 VENTING SPECIFICSHorizontal Venting InstallationVertical Venting InstallationFireplace Vent ConnectionGas Supply Connection

20-22FINISHINGMantle Height LocationsLog Placement/Charcoal EmbersDoor, Louvre & Trim Installation

23 OPTIONAL BLOWER INSTALLATION24 OPERATION / MAINTENANCE

Operating InstructionsMaintenance

25 ADJUSTMENTSPilot Burner AdjustmentVenturi Adjustments

25-28 REPLACEMENTSOrdering Replacement PartsReplacement PartsVent KitsTerminal KitsAccessories

29-30TROUBLE SHOOTING GUIDE31 SERVICE HISTORY

WARNING• Do not burn wood or other materials in this fireplace.• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay

away to avoid burns or clothing ignition. Supervise young children when they are in the same room as thefireplace.

• Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.• Clothing or other flammable material should not be placed on or near the fireplace.• Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace.• It is imperative that the control compartments, burners and circulating blower and its passageway in the fireplace

and venting system are kept clean. The fireplace and its venting system should be inspected before use and atleast annually by a qualified service person. More frequent cleaning may be required due to excessive lint fromcarpeting, bedding material, etc. The fireplace area must be kept clear and free from combustible materials,gasoline and other flammable vapours and liquids.

• Under no circumstances should this fireplace be modified.• This fireplace must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.• Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect

the fireplace and to replace any part of the control system and any gas control which has been under water.• Do not operate the fireplace with the glass door removed, cracked or broken. Replacement of the glass should be

done by a licensed or qualified service person.• Do not strike or slam shut the fireplace glass door.

Page 3: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

3

WS-415-091 / 06.26.00

RIGHT OPEN END MODEL

LEFT OPEN END MODEL PENINSULA MODEL

SEE-THRU MODEL

Page 4: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

4

WS-415-091 / 06.26.00

NAPOLEON gas fireplaces are manufactured under the strict Standard of the world recognizedISO9002 Quality Assurance Certificate.

NAPOLEON products are designed with superior components and materials, assembled by trained craftsmenwho take great pride in their work. The burner and valve assembly are leak and test-fired at a quality teststation. The complete fireplace is thoroughly inspected by a qualified technician before packaging to ensure thatyou, the customer, receives the quality product that you expect from NAPOLEON.

NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY

The following materials and workmanship in your new The following materials and workmanship in your new The following materials and workmanship in your new The following materials and workmanship in your new The following materials and workmanship in your new NAPOLEONNAPOLEONNAPOLEONNAPOLEONNAPOLEON gas fireplace are war- gas fireplace are war- gas fireplace are war- gas fireplace are war- gas fireplace are war-ranted against defects for as long as you own the fireplace. This covers: combustion chamber,ranted against defects for as long as you own the fireplace. This covers: combustion chamber,ranted against defects for as long as you own the fireplace. This covers: combustion chamber,ranted against defects for as long as you own the fireplace. This covers: combustion chamber,ranted against defects for as long as you own the fireplace. This covers: combustion chamber,heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakageheat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakageheat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakageheat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakageheat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakageonly), gold plated parts against tarnishing, porcelainized enamelled components and aluminumonly), gold plated parts against tarnishing, porcelainized enamelled components and aluminumonly), gold plated parts against tarnishing, porcelainized enamelled components and aluminumonly), gold plated parts against tarnishing, porcelainized enamelled components and aluminumonly), gold plated parts against tarnishing, porcelainized enamelled components and aluminumextrusion trims.extrusion trims.extrusion trims.extrusion trims.extrusion trims.

Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arecovered and covered and covered and covered and covered and NAPOLEONNAPOLEONNAPOLEONNAPOLEONNAPOLEON will provide replacement parts free of charge during the first year ofwill provide replacement parts free of charge during the first year ofwill provide replacement parts free of charge during the first year ofwill provide replacement parts free of charge during the first year ofwill provide replacement parts free of charge during the first year ofthe limited warranty.the limited warranty.the limited warranty.the limited warranty.the limited warranty.

Labour related to warranty repair is covered free of charge during the first year. Repair work,Labour related to warranty repair is covered free of charge during the first year. Repair work,Labour related to warranty repair is covered free of charge during the first year. Repair work,Labour related to warranty repair is covered free of charge during the first year. Repair work,Labour related to warranty repair is covered free of charge during the first year. Repair work,however, requires the prior approval of an authorized company official. Labour costs to thehowever, requires the prior approval of an authorized company official. Labour costs to thehowever, requires the prior approval of an authorized company official. Labour costs to thehowever, requires the prior approval of an authorized company official. Labour costs to thehowever, requires the prior approval of an authorized company official. Labour costs to theaccount of account of account of account of account of NAPOLEONNAPOLEONNAPOLEONNAPOLEONNAPOLEON are based on a predetermined rate schedule and any repair work must are based on a predetermined rate schedule and any repair work must are based on a predetermined rate schedule and any repair work must are based on a predetermined rate schedule and any repair work must are based on a predetermined rate schedule and any repair work mustbe done through an authorized be done through an authorized be done through an authorized be done through an authorized be done through an authorized NAPOLEONNAPOLEONNAPOLEONNAPOLEONNAPOLEON dealer. dealer. dealer. dealer. dealer.

CONDITIONS AND LIMITATIONSNAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the

warranty registration card filed with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions and limitations:This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with the

product and all local and national building and fire codes.This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify

this warranty.This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel

parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years NAPOLEON will replace

or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.In the first year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been operated

in accordance with the operation instructions and under normal conditions.After the first year, with respect to this President's Limited Lifetime Warranty, NAPOLEON may, at its discretion, fully discharge all obligations with respect to this warranty by refunding

to the original warranted purchaser the wholesale price of any warranted but defective part(s).After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are not

covered by this warranty.Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON’S responsibility under this warranty is defined as above and it shall not in any event

extend to any incidental, consequential or indirect damages.This warranty defines the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fireplace and any other warranties expressed or implied with respect to this product,

its components or accessories are excluded.NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible

for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive ventingconfigurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.

Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damagingchemicals or cleaners will not be the responsibility of NAPOLEON.

The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration cardmust be returned within fourteen days to register the warranty.

NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.

ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTEREDTRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL LTD.

Page 5: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

5

WS-415-091 / 06.26.00

INTRODUCTIONGENERAL INSTRUCTIONSTHIS GAS FIREPLACE SHOULD BE INSTALLED ANDSERVICED BY A QUALIFIED INSTALLER to conform withlocal codes. In absence of local codes, install to the cur-rent CAN/CGA -B149 Installation Code in Canada or to theNational Fuel Gas Code, ANSI Z223.1-1988, and NFPA 54-1988 in the United States. Suitable for mobile home instal-lation if installed in accordance with the current standardCAN/CSA Z240MH Series, for gas equipped mobile homes,in Canada or ANSI Z223.1-1988 and NFPA 54-1988 in theUnited States.Purge all gas lines with the glass door of the fireplaceremoved. Assure that a continuous gas flow is at theburner before installing the door.Under extreme vent configurations, allow several min-utes (5-15) for the flame to stabilize after ignition.All horizontal runs must have a minimum 1 inch rise perfoot when using Napoleon flexible venting components.Eight (8") inches is the minimum bend radius allowedfor the 7" diameter flexible air liner.The fireplace and its individual shutoff valve must be dis-connected from the gas supply piping system during anypressure testing of that system at test pressures in ex-cess of 1/2 psig (3.5 kPa). The fireplace must be isolatedfrom the gas supply piping system by closing its individualmanual shutoff valve during any pressure testing of thegas supply piping system at test pressures equal to orless than 1/2 psig (3.5 kPa).When the fireplace is installed directly on carpeting, vinyltile or other combustible material other than wood flooring,the fireplace shall be installed on a metal or wood panelextending the full width and depth.If the optional heat circulating blower is installed, the blowermust be electrically connected and grounded in accord-ance with local codes. In the absence of local codes, usethe current CSA C22.1 CANADIAN ELECTRICAL CODE inCanada or the ANSI/NFPA 70-1996 NATIONAL ELECTRI-CAL CODE in the United States.

Minimum clearance to combustible constructionfrom fireplace and vent surfaces:

sides, back, bottom, and top 0 inchesvent pipe 2 inch*****recessed depth (corner installation) 243/4 inches

*The first 2 feet of outer 7 inch diameter ventpipe from the appliance must be wrapped in the 1inch thick insulation sleeve (supplied) as well ashaving a 1 inch air gap. After the insulation sleevea 2" air gap must be maintained between the re-maining vent system and combustibles. FIGURE 39.

GENERAL INFORMATIONFOR YOUR SATISFACTION, ALL BURNER ASSEMBLIESHAVE BEEN TEST-FIRED TO ASSURE THEIR OPERA-TIONS AND QUALITY! Maximum input is 40,000 BTU/hfor natural gas and 36,000BTU/h for propane. When thefireplace is installed at elevations above 4,500ft, and in theabsence of specific recommendations from the local au-thority having jurisdiction, the certified high altitude inputrating shall be reduced at the rate of 4% for each additional1,000ft. Maximum output for natural gas is 33,200 BTU/hrat an efficiency of 83% with the fan on.Minimum inlet gas supply pressure is 4.5 inches watercolumn for natural gas and 11 inches water column forpropane. Maximum inlet gas pressure is 7 inches watercolumn for natural gas and 13 inches water column forpropane. Manifold pressure under flow conditions is 3.5inches water column for natural gas and 10 inches watercolumn for propane.This fireplace is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile homeinstallation. The natural gas model can only be installed ina mobile home that is permanently positioned on its siteand fuelled with natural gas.NO EXTERNAL ELECTRICITY (110 VOLTS OR 24 VOLTS) ISREQUIRED FOR THE GAS SYSTEM OPERATION. Expan-sion / contraction noises during heating up and coolingdown cycles are normal and are to be expected.

CARE OF GLASS, AND PLATED PARTSDo not use abrasive cleaners to clean plated parts. Bufflightly with a clean dry cloth. The glass is 3/16" ceramicglass available from your Napoleon / Wolf Steel Ltd. dealer.

Do not substitute materials.If the door glass should crack or break, do not operate thefireplace. Replace only with a door assembly certified withthe fireplace. See DOOR, LOUVRE AND TRIM INSTALLA-TION for removal and replacement details. Clean the glassafter the first 10 hours of operation with a recommendedgas fireplace glass cleaner. Thereafter clean as required.

Do not clean glass when hot!If the glass is not kept clean permanent discolourationand / or blemishes may result.

Provide adequate ventilation. Provide adequate acces-sibility clearance for servicing and operating the fire-place. Never obstruct the front openings of the fire-place.Objects placed in front of the fireplace must be kept aminimum of 48" away from the front face of the unit.

Page 6: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

6

WS-415-091 / 06.26.00

The air terminal must remain unobstructed at all times.Examine the air terminal at least once a year to verify that itis unobstructed and undamaged.

When terminating vertically,the vertical rise is a mini-mum 34 inches and a maxi-mum 40 feet above the fire-place. FIGURE 2.

Do not radius vertical ventrises.

FIGURE 1

FIGURE 3

FIGURE 2

All horizontal runs must have a 1 inch rise per foot in allcases using Napoleon flexible venting components.Horizontal runs can have a 0 inch rise per foot usingSimpson Dura-Vent components or Napoleon rigid vent-ing components.Provide a means for visually checking the vent connec-tion to the fireplace after the fireplace is installed.Do not allow the inside liner to bunch up on horizontal orvertical runs and elbows. Keep it pulled tight. A 1¼" airgap between the inner and outer liner all around is re-quired for safe operation.For safe and proper operation of the fireplace follow theventing instruction exactly.Deviation from the minimum vertical vent length can cre-ate difficulty in burner start-up and/or carboning.

If vertical rises greater than 57 inches are necessary,the increased rise must be deducted from the horizontalrun. (figures 3, and 5a-c.)The first 2 feet of outer 7 inch diameter vent pipe fromthe appliance (or from the unit to the first firestop spacerif under 2 feet) must be wrapped in the 1 inch thick insu-lation sleeve (supplied) as well as having a 1 inch airgap.Use a firestop when penetrating interior walls, floor orceiling.The fireplace must be installed against finished walls. Donot install against a vapour barrier or exposed insulation.Vent lengths that pass through unheated spaces (attics,garages, crawl spaces) should be insulated with the in-sulation wrapped in a protective sleeve to minimize con-densation.

VENTINGVENTING LENGTHSUse only Napoleon or Simpson Dura-Vent Model DV-GSventing components. Minimum and maximum vent lengths,for both horizontal and vertical installations, and air termi-nal locations for either system are set out in this manualand must be adhered to.

When using Napoleon venting components, use only thefollowing vent kits: WALL TERMINAL KIT GD222, or 1/12 TO7/12 PITCH ROOF TERMINAL KIT GD110, 8/12 TO 12/12ROOF TERMINAL KIT GD111, FLAT ROOF TERMINAL KITGD112 or PERISCOPE KIT GD201 (for wall penetrationbelow grade) in conjunction with the various terminations,use either the 5 foot vent kit GD220 or the 10 foot vent kitGD330. For Simpson Dura-Vent, follow the installation pro-cedure provided with the venting components.

These vent kits allow for either horizontal or vertical ventingof the fireplace. The maximum number of 4" flexible con-nections is three horizontally or four vertically (excludingthe fireplace and the air terminal connections).

For optimum flame appearance and fireplace performance,keep the vent length and number of elbows to a minimum.

Page 7: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

7

WS-415-091 / 06.26.00

Use the chart on this page to calculate vertical rises forhorizontal runs between 3 and 20 feet. FIGURE 5.When calculating maximum run lengths, include 10 feetfor each 90° elbow or 5 feet for each 45° elbow. (DO NOTINCLUDE THE FIRST ELBOW DIRECTLY OFF THE UNIT.)

Only the following Napoleon Vent Kits, used in combina-tion with each other can be used:GD201, GD222, GD110, GD111 or GD112 (Periscope, Wall

or Roof Terminals)and

GD220 (5ft vent kit) or/and GD330 (10ft vent kits)

VENTING OPTION #2Use this chart to calculate vertical rise for horizontal runbetween 1 foot (maximum length when the vertical rise isat its minimum of 1 foot) and 8 feet. FIGURES 6.

A terminal shall not terminate directly above a sidewalkor paved driveway which is located between two sin-gle family dwellings and serves both dwellings. Localcodes or regulations may require different clearances.

All horizontal runs must have a minimum 1 inch rise perfoot when using flexible venting components.

Do not allow the inside liner to bunch up on horizontal orvertical runs and elbows. Keep it pulled tight. A 1¼" airgap all around between the inner liner and outer stovepipe is required for safe operation. Use a firestop whenpenetrating interior walls, floor or ceiling.

VENTING OPTION #1When venting, the horizontal run must be kept to a mini-mum of 10 inches or a maximum of 20 feet. If a 20 foothorizontal run is required, the fireplace must have a mini-mum vertical rise immediately off the fireplace of 57 inches.FIGURES 4a-c.

FIGURE 5

FIGURES 4a - c

FIGURES 6

40 FT MAX1 FT MIN

8 FT MAX(1 FT MAX)

HORIZONTAL VENT RUNin feet

VERTICALRISE in feet

Page 8: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

8

WS-415-091 / 06.26.00

20 FT MAX1 FT MIN

10 FT MAX(1 FT MAX)

8 FT MAX(2 FT MAX)

FIGURES 8

HORIZONTAL VENT RUNin feet

VERTICALRISE in feet

VENTING OPTION #3Use this chart to calculate vertical rise for horizontal runbetween 3 feet (maximum length when the vertical rise isat its minimum of 1 foot) and 18 feet. FIGURES 7.

VENTING OPTION #4Use this chart to calculate the vertical rise when using atotal of 2 horizontal runs that consist of 8 feet maximum or2 feet (maximum length when the vertical rise is at its mini-mum of 1 foot) for the first run and a 10 feet maximum or1 foot (maximum length when the vertical rise is at its mini-mum of 1 foot) for the second run. FIGURES 8.

COMBINED HORIZONTALVENT RUN in feet

VERTICALRISE in feet

20 FT MAX1 FT MIN

18 FT MAX(3 FT MAX)

FIGURES 7

Page 9: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

9

WS-415-091 / 06.26.00

HORIZONTAL VENT RUNin feet

COMBINEDVERTICAL

RISE in feet

VENTING OPTION #5Use this chart to calculate the total vertical rise requiredwhen the horizontal run is between 18 feet maximum or3 feet maximum length when the initial vertical rise is at itsminimum of 1 foot. FIGURES 9.

MOBILE HOME INSTALLATIONIn Canada, mobile home installation may be vented hori-zontally or vertically. In the United States, it may only beinstalled vertically. See "Vertical Venting" or "HorizontalAir Terminal Installation" for installation.

The fireplace is equipped with four 1/4" diameter holeslocated near each corner of the base. For mobile homeinstallations, the fireplace must be fastened in place. Use#10 screws, inserted through the holes in the base to se-cure. It is recommended that the fireplace be secured in allinstallations.

FIGURES 9

34 FT MAX(1 FT MAX)

6 FT MAX1 FT MIN

18 FT MAX(3 FT MAX)

Page 10: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

10

WS-415-091 / 06.26.00

FIGURE 10

AIR AIR AIR AIR AIR TERMINTERMINTERMINTERMINTERMINAL INSTAL INSTAL INSTAL INSTAL INSTALLAALLAALLAALLAALLATIONS:TIONS:TIONS:TIONS:TIONS:

***** Recommended to prevent condensation on windows and thermal breakage********** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.*************** The periscope GD-201 requires a minimum 18 inches clearance from an inside corner.******************** This is a recommended distance. For additional requirements check local codes.††††† Three feet above if within 10 feet horizontally.‡‡‡‡‡ A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family

dwellings and serves both dwellings.†††††††††† Permitted only if the veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.†*†*†*†*†* Recommenced to prevent recirculation of exhaust products. For additional requirements check local codes.

A

B

C

D

EF

G

H

I

J

K

L

MNO

12 INCHES

9 INCHES

12 INCHES*

18 INCHES**

12 INCHES**

0 INCHES

0 INCHES***

2 INCHES***

3 FEET****

3 FEET****

9 INCHES

3 FEET†

7 FEET****

12 INCHES****

16 INCHES

2 FEET†*

Clearance above grade, veranda porch, deck or balcony.

Clearance to windows or doors that open.

Clearance to permanently closed windows.

Vertical clearance to ventilated soffit located above the terminal withina horizontal distance of 2 feet from the centerline of the terminal.

Clearance to unventilated soffit.

Clearance to an outside corner wall.

Clearance to an inside non-combustible corner wall or protrudingnon-combustible obstructions (chimney, etc.).

Clearance to an inside combustible corner wall or protruding com-bustible obstructions ( vent chase, etc.).

Clearance to each side of the centerline extended above the meter/ regulator assembly.

Clearance to a service regulator vent outlet.

Clearance to a non-mechanical air supply inlet to the building or acombustion air inlet to any other appliance.

Clearance to a mechanical air supply inlet.

Clearance above a paved sidewalk or paved driveway located onpublic property unless fitted with a heat shield kit GD-301.

Clearance under a veranda, porch, deck or balcony.

Clearance above the roof.

Clearance from an adjacent wall including neighbouring buildings.

CANADIAN U.S.A.12 INCHES

12 INCHES

12 INCHES*

18 INCHES**

12 INCHES**

0 INCHES

0 INCHES***

2 INCHES***

3 FEET

6 FEET

12 INCHES

6 FEET

7 FEET‡

12 INCHES††

16 INCHES

2 FEET†*

INSTALLATIONS

Page 11: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

11

WS-415-091 / 06.26.00

VENTINGRefer to page 16-19. The first 2 feet of outer 7 inch diam-eter vent pipe from the appliance or from the unit to the firstfirestop spacer (whichever distance is less) must bewrapped in the 1 inch thick insulation sleeve (supplied) aswell as having a 1 inch air gap.

FRAMINGIt is best to frame your fireplace after it is positioned andthe vent system is installed. Use 2x4's and frame to localbuilding codes. FIGURE 11.

To install the fireplace face flush with the finished wall,position the framework to accommodate the thicknessof the finished wall. The fireplace must be installedagainst finished walls. Do not install against a vapourbarrier or exposed insulation.

Care should be taken to maintain sufficient clearance forthe vent installation. A horizontal vent installation requiresa minimum height of 42" (including the 2" clearance tocombustibles). FIGURE 12.

AFIGURE 11

TOP EXTENTIONTOP OF THE UNIT

FIGURE 14

42"

38¼"

FIGURE 12

COUNTERTOP / BAR INSTALLATIONWhen finishing the fireplace, a combustible material mayrest directly on top of the fireplace extension frame. In or-der to achieve a countertop or bar type appearance withthe minimum height allowed, framing must be non-com-bustible and may be done with metal studding attached tothe heat shield sides or the upper frame of the fireplace.FIGURE 13.

* The three-sided top extension frame may be removed ifframing is faced with a non-combustible material placedflush with the front face of the unit and extending from thetop of the unit. (Example: cement board) (not supplied).

A = 21-3/4" minus finishing material thickness each side.

EXTENSIONTOP FRAMENONCOMBUSTIBLE

MATERIAL *METAL STUDS

3"

3" COMBUSTIBLEMATERIAL*

PENINSULA INSTALLATION PROCEDURE

FIGURE 13

Page 12: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

12

WS-415-091 / 06.26.00

FACINGCombustible materials may be installed flush with the frontof the fireplace but must not cover any of the black face-areas of the fireplace. Non-combustible material (brick,stone or ceramic tile) may protrude in these areas.It is not necessary to install a hearth extension with thisfireplace system.Objects placed in front of the fireplace should bekept a minimum of 48" away from the front face.

FINISHINGRefer to page 20 for complete instructions regarding man-tle requirements and installations, log placement, glassdoor and upper and lower louvre attachments.

BRICK PANEL INSTALLATIONInsert the side panel and install the retaining brackets ateither side to secure the panel. Install the remaining pan-els as illustrated. FIGURES 15.

RETAINING BRACKET

STEP 1

STEP 2

STEP 3

FIGURES 15

4" MIN

DRYWALLDRYWALL

FIGURE 16

Page 13: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

13

WS-415-091 / 06.26.00

BRICK PANEL INSTALLATIONStart by inserting the top of the rear panel into the brickholder as illustrated. Push the bottom of the panel tightagainst the door cover. Insert the side panel and install theretaining bracket at the end to secure the panel. (Only onebracket is required.) Install the remaining panels as illus-trated. When installing the bricks in step 3, slide the leftfloor panel underneath the rear brick panel.

VENTINGRefer to page 16-19 for venting specifics. The first 2 feet ofouter 7 inch diameter vent pipe from the appliance or fromthe unit to the first firestop spacer (whichever distance isless) must be wrapped in the 1 inch thick insulation sleeve(supplied) as well as having a 1 inch air gap.

FRAMINGIt is best to frame your fireplace after it is positioned andthe vent system is installed. Use 2x4's and frame to localbuilding codes. FIGURE 18.See PAGE 11 for bar type / countertop installation.

If a blower is to beused, for ease of in-stalling or servicingthe blower, routethe gas line throughthe rear gas accesshole.

FIGURE 18NOTE: LEFT CORNER UNIT ILLUSTRATED

To install the fireplace face flush with the finished wall,position the framework to accommodate the thicknessof the finished wall. The fireplace must be installedagainst finished walls. Do not install against a vapourbarrier or exposed insulation.

N

O

T

O

L OI

FFP

HI

LO

FIGURE 17

AA = 21-3/4" minus finishing material thickness each side.

FIGURES 19 BRICK HOLDER

STEP 3

STEP 4

STEP 2

RETAINING BRACKET

STEP 1

OPEN END INSTALLATION PROCEDURE

Page 14: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

14

WS-415-091 / 06.26.00

DRYWALL DRYWALL

4" MIN

FIGURE 20

FACINGCombustible materials may be installed flush with the frontof the fireplace but must not cover any of the black face-areas of the fireplace. Non-combustible material (brick,stone or ceramic tile) may protrude in these areas.It is not necessary to install a hearth extension with thisfireplace system.Objects placed in front of the fireplace should bekept a minimum of 48" away from the front face.

FINISHINGRefer to page 20 for complete instructions regarding man-tle requirements and installations, log placement, glassdoor and upper and lower louvre attachments.

Page 15: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

15

WS-415-091 / 06.26.00

FACINGCombustible materials may be installed flush with the frontof the fireplace but must not cover any of the black face-areas of the fireplace. Non-combustible material (brick,stone or ceramic tile) may protrude in these areas.It is not necessary to install a hearth extension with thisfireplace system.Objects placed in front of the fireplace should bekept a minimum of 48" away from the front face.

FINISHINGRefer to page 20 for complete instructions regarding man-tle requirements and installations, log placement, glassdoor and upper and lower louvre attachments.

VENTINGRefer to page 16-19 for venting specifics. The first 2 feet ofouter 7 inch diameter vent pipe from the appliance or fromthe unit to the first firestop spacer (whichever distance isless) must be wrapped in the 1 inch thick insulation sleeve(supplied) as well as having a 1 inch air gap.

FRAMINGIt is best to frame your fireplace after it is positioned andthe vent system is installed. Use 2x4's and frame to localbuilding codes. FIGURE 21.See PAGE 11 for bar type / countertop installation.

To install the fireplace face flush with the finishedwall, position the framework to accommodate thethickness of the finished wall. The fireplace must beinstalled against finished walls. Do not install againsta vapour barrier or exposed insulation.

BRICK PANEL INSTALLATIONInsert the first side panel and install the retaining bracketsat either end to secure the panel. Install the remainingpanels as illustrated. Install the second side panel withthe notch to the top. Secure with a retainer and screw.

DRYWALL

4" MIN

DRYWALL

FIGURE 23

A

A = 21-3/4" minus finishing material thickness, each side.

FIGURE 21

FIGURES 22

RETAINER

STEP 4

STEP 3

RETAINING BRACKET

STEP 1

STEP 2

SEE-THRU INSTALLATION PROCEDURE

Page 16: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

16

WS-415-091 / 06.26.00

For safe and proper operation of the fireplace, fol-low the venting instructions exactly.

HORIZONTAL INSTALLATION:This application occurswhen venting through anexterior wall. FIGURES4a-d. Having determinedthe air terminal location,cut and frame a hole inan exterior wall with aminimum square orround opening of 11½".(As an alternative to fram-ing, a vent pipe shieldmay be installed, ensur-ing a 2" clearance tocombustibles.

1. Mark and cut the vent pipe shield to the determineddepth of the combustible wall. Apply a bead of caulking(not supplied) to the shield plate, centre a firestop spacerover it and secure the shield to the firestop spacer. Apply abead of caulking all around the framed opening of the ventshield or the firestop spacer. Place the spacer/shield as-sembly over the framed opening in the wall and secure.This will restrict cold air from being drawn into the room oraround the fireplace. The location of the vent pipe shield /firestop assembly must maintain the required (2") clear-ance to the 7" vent pipe / liner. Do not fill this cavity with anytype of material. Once the vent pipe / liner is installed in itsfinal position, apply sealant between the pipe / liner andthe firestop spacer.

VERTICAL INSTALLATION: This application occurs whenventing through a roof. FIGURE 2. Installation kits for vari-ous roof pitches are available from your Napoleon dealer.See Accessories to order the specific kit required.

1. Determine the air terminal location, cut and frame11½ inch openings in the ceiling and the roof to provide theminimum 2 inch clearance between the fireplace pipe /liner and any combustible material. Try to centre the ex-haust pipe location midway between two joist to preventhaving to cut them. Use a plumb bob to line up the centre ofthe openings.

Do not fill this space with any type of material.A vent pipe shield willprevent any materi-als such as insula-tion, from filling upthe 1" air spacearound the pipe. Nailheaders betweenthe joist for extrasupport.

2. Apply a bead of caulking (not supplied) all around thevent shield and place onto the firestop spacer. Secure.Apply a bead of caulking to the framework and secure overthe opening in the ceiling. FIGURE 27. Ensure that bothspacer and shield maintain the required clearance tocombustibles. Place over the framed opening and secure.This will restrict cold air from being drawn into the room oraround the fireplace. A firestop must be placed on the bot-tom of each framed opening in a roof or ceiling that theventing system passes through. FIGURE 28. Once thevent pipe / liner is installed in its final position, apply seal-ant between the pipe / liner and the firestop spacer.

3. In the attic, after the pipe /liner has been installed, slidethe vent pipe collar down tocover up the open end of theshield and tighten. This will pre-vent any materials, such as in-sulation, from filling up the 1" airspace around the pipe.

FIGURE 28

VENT PIPESHIELD

VENTPIPE

COLLAR

FIGURE 24

FIGURE 26

FIGURE 27

INSTALLATIONWALL AND CEILING PROTECTION

FIGURE 25 OR

Page 17: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

17

WS-415-091 / 06.26.00

All horizontal runs must have a minimum 1 inch riseper foot using flexible venting.For safe and proper operation of the fireplace, followthe venting instructions exactly.

HORIZONTAL AIR TERMINAL INSTAL-LATION

1. Stretch the 4" diameter aluminium flexible liner to therequired length taking into account the additional lengthneeded for the finished wall surface. Apply a heavy bead ofthe high temperature sealant, supplied with the unit, to theinside of the 4" liner approximately 1" from the end. Slip theliner a minimum of 2" over the fireplace vent collar andsecure with 3 #8 screws.

2. Using the 7" diameter flexible aluminium liner, applysealant, slide a minimum of 2" over the fireplace combus-tion air collar and secure with 3 #8 screws.

3. Insert the liners through the firestop. Position andsecure the fireplace using the nailing tabs (2 per side)and/or secure to the floor using screws inserted throughthe two ¼" diameter holes in the front left and right cornersof the base. The liners should be flush with the exteriorwall.The air terminal mounting plate may be recessed intothe exterior wall or siding by 1½", the depth of the returnflange.

4. From outside, apply a bead of the high temperaturesealant to the inside of both liners, approximately 1" fromthe end of each liner.

5. Holding the air terminal (lettering in an upright, read-able position), insert into both liners with a twisting motionto ensure that both the terminal sleeves engage into theliners / sealant. Secure the terminal to the exterior wall andmake weather tight by sealing with caulking (not supplied).

6. If more liner needs to be used to reach the fireplace,couple them together as illustrated in FIGURE 30. The ventsystem must be supported approximately every 3 feet forboth vertical and horizontal runs. Use noncombustible strap-ping to maintain the minimum 2" clearance to combustibles.

FIGURE 30

FIGURE 29

USING FLEXIBLE VENT COMPONENTS

Page 18: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

18

WS-415-091 / 06.26.00

VERTICAL VENTING INSTALLATION

1. Fasten the roof sup-port to the roof using thescrews provided. Theroof support is optional.In this case the ventingis to be adequately sup-ported using either analternate method suit-able to the authority hav-

ing jurisdiction or the optional roof support.2. Stretch the 4" diameter aluminium flexible liner to the

required length. Slip the liner a minimum of 2" over theinner sleeve of the air terminal and secure with 3 #8 screws.Seal using a heavy bead of the high temperature sealant.

3. Repeat using 7" diameter aluminium flexible liner.4. Thread the air terminal

pipe assembly down throughthe roof. The air terminal mustbe located vertically and plumb.Attach the air terminal assem-bly to the roof support, ensur-ing that a minimum 16" of airterminal will penetrate the roofwhen fastened.

DO NOT CLAMP THE FLEX-IBLE ALUMINIUM LINER.

5. Remove nails from the shingles, above and to thesides of the chimney. Place the flashing over the air termi-nal and slide it underneath the sides and upper edge ofthe shingles. Ensure that the air terminal is properly cen-tred within the flashing, giving a 3/4" margin all around.Fasten to the roof. Do not nail through the lower portion ofthe flashing. Make weather-tight by sealing with caulking.Where possible, cover the sides and top edges of the flash-ing with roofing material.

6. Apply a heavy bead of weatherproof caulking 2 inchesabove the flashing. Slide the storm collar around the airterminal and down to the caulking. Tighten to ensure that aweather-tight seal between the air terminal and the collaris achieved. Attach the other storm collar centred betweenthe air intake and the air exhaust slots onto the air termi-nal. Tighten securely. FIGURE 33. Attach the vertical raincap.

Spacers are attached to the 4" inner flex liner at prede-termined intervals to maintain a 1-1/4" air gap to the 7"outer liner. These spacers must not be removed.

7. If more liner needs to be used to reach the fireplace,couple them together as illustrated in FIGURE 30. The ventsystem must be supported approximately every 3 feet forboth vertical and horizontal runs. Use noncombustible strap-ping to maintain a clearance to combustibles of 2".

FIREPLACE VENT CONNECTION1. Slide the insulation sleeve over the 7" diameter alu-

minium flex liner. The insulation sleeve is only required forthe first 24" off the fireplace or from the fireplace to the firstfirestop spacer (whichever distance is less) and needs onlya 1" clearance.

2. Install the 4 inch diameter aluminium flexible liner tothe fireplace. Secure with 3 screws. Seal the joint and screwholes using the high temperature sealant provided.

3. Install the 7 inch diameter aluminium flexible liner tothe fireplace. Attach and seal the joints. Pull the insulationsleeve tight to the top of the fireplace.

Read Page 22 for information on opening the door priorto proceeding to prevent damage to the unit. Proceedonce the vent installation is complete.

FIGURE 33

FIGURE 32

FIGURE 34

FIGURE 31

Page 19: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

19

WS-415-091 / 06.26.00

VERTICAL VENTING INSTALLATION1. Move the fireplace into position.2. Fasten the roof support to the roof using the screws

provided. FIGURE 31. The roof support is optional. In thiscase the venting is to be adequately supported using ei-ther an alternate method suitable to the authority havingjurisdiction or the optional roof support.

3. Apply high temperature sealant to the outer edge of theinner sleeve of the air terminal. Slip a 4" diameter coupler aminimum of 2" over the sleeve and secure using 3 screws.

4. Apply high temperature seal-ant to the outer edge of the of theoutside sleeve of the air terminal.Slip a 7" diameter coupler over thesleeve and secure as before. Trimthe 7" coupler even with the 4" cou-pler end. FIGURE 35.

5. Thread the air terminal pipeassembly down through the roofsupport and attach, ensuring thata minimum 16" of air terminal willpenetrate the roof when fas-tened. FIGURE 33.If the attic space is tight, we recommend threading the WolfSteel vent pipe collar or equivalent loosely onto the air termi-nal assembly as it is passed through the attic. FIGURE 28.The air terminal must be located vertically and plumb.

6. Remove nails from the shingles, above and to thesides of the chimney. Place the flashing over the air termi-nal and slide it underneath the sides and upper edge ofthe shingles. Ensure that the air terminal is properly cen-tred within the flashing, giving a 3/4" margin all around.Fasten to the roof. Do NOT nail through the lower portion ofthe flashing. Make weather-tight by sealing with caulking.Where possible, cover the sides and top edges of the flash-ing with roofing material.

7. Apply a heavy bead of waterproof caulking 2 inchesabove the flashing. Slide the storm collar around the airterminal and down to the caulking. Tighten to ensure that aweather-tight seal between the air terminal and the collaris achieved. Attach the other storm collar centred betweenthe air intake and air exhaust slots onto the air terminal.Tighten securely. Attach the rain cap.

8. Continue adding rigid venting sections, sealing andsecuring as above. Attach a 4" collapsed telescopic pipeto the last section of rigid piping. Secure with screws andseal. Repeat using a 7" telescopic pipe.

9. Run a bead of high temperature sealant around theoutside of the 4" elbow. Pull the adjustable pipe a mini-mum 2" onto the elbow. Secure with 3 screws. Repeat withthe 7" telescopic pipe.

10. In the attic, slide the vent pipe collar down to cover upthe open end of the shield and tighten. This will preventany materials, such as insulation, from filling up the 1" airspace around the pipe.

For safe and proper operation of the fireplace, followthe venting instructions exactly.Horizontal runs may have a zero inch rise per foot usingSimpson Dura-Vent or Napoleon rigid venting compo-nents.The vent system must be supported approximately every 3feet for both vertical and horizontal runs. Use Napoleonvent spacers WS-615-33 or equivalent every 3 feet andeither side of each elbow to maintain the minimum 1¼"clearance between the outer and inner vent pipes. Usenoncombustible strapping to maintain the minimum 2"clearance to combustibles for both vertical and horizontalruns.

FIREPLACE VENT CONNECTION1. Apply high temperature sealant to the outer edge of

the 4" inner collar of the fireplace. Attach the first ventcomponent and secure using 3 self tapping screws. Re-peat using 7" piping.

2. Slide the insulation sleeve over the 7" pipe. The insu-lation sleeve is only required for the first 2 feet off the fire-place or from the fireplace to the first firestop spacer (which-ever distance is less) and needs only a 1" clearance. Fig-ure 34.Ensure that the insulation sleeve is pulled tight to thefireplace after all vent components are installed.

HORIZONTAL AIR TERMINAL INSTALLATION1. Move the fireplace into position. Measure the vent length

required between terminal and fireplace taking into ac-count the additional length needed for the finished wallsurface and any 1¼" overlaps between venting compo-nents.

2. Holding the air terminal (lettering in an upright, read-able position), insert into both vent pipes with a twistingmotion to ensure that both the terminal sleeves engageinto the vent pipes and the sealant. Secure the terminal tothe exterior wall and make weather tight by sealing withcaulking (not supplied). Figure 29.The air terminal mounting plate may be recessed intothe exterior wall or siding by 1½", the depth of the returnflange.

FIGURE 35

INSTALLATIONUSING RIGID VENT COMPONENTS

Page 20: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

20

WS-415-091 / 06.26.00

4. Install the rigid black pipe, ½" type-L copper tubing or,if local codes permit, a 3/8" flex connector and shutoff valveto the gas line and the fireplace gas valve. Seal and tightensecurely. An adapter fitting is required between the gasvalve and the copper tubing or flex connector.

Do not kink flexible connector.5. Check for gas leaks by brushing on a soap and water

solution.Do not use open flame.

GAS SUPPLY CONNECTION1. Move the fireplace into position and secure to the floor

using #10 hex head screws (not supplied).2. Route a 3/8" N.P.T. black iron gas line, 1/2" type-L

copper tubing or equivalent to the fireplace.3. For ease of accessibility, an optional remote wall switch

or millivolt thermostat may be installed in a convenientlocation. Route 2-strand (solid core) millivolt wire throughthe electrical hole located at the bottom left side of the unit.

The recommended maximum lead length depends onwire size:

WIRE SIZE MAX. LENGTH14 gauge 100 feet16 gauge 60 feet18 gauge 40 feet

Do not connect either the wall switch, thermostat orgas valve to electricity (110 volts).

Attach the two leads to terminals 1 and 3 located on thegas valve.

FIGURE 37

P

I

PI3

1

2

LOT

N O

L

O

T

HI

LO

FF O

FIGURE 36

7" MANTLE3" MANTLE

TOP EXTENTIONTOP OF THE UNIT

FIGURES 38

FINISHINGMANTLE INSTALLATIONCombustible mantle clearance can vary according to themantle depth. Use the graph to help evaluate the clear-ance needed. The three-sided top extension frame may beremoved if framing is faced with a non-combustible mate-rial.

Page 21: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

21

WS-415-091 / 06.26.00

Place logs 1 and 2 tight to the main burner deflector, asshown in 39b, and the end portion (A) of the main burner.(39c) Both logs should be parallel.

LOG, CHARCOAL & GLOWING EMBERSPLACEMENT INSTRUCTIONSPHAZERTM logs, glowing and charcoal embers, exclusiveto Napoleon fireplaces, provide a unique and realistic glow-ing effect that is different in every installation. Take the timeto carefully position the embers for a maximum glowingeffect. (39a)

The remaining logs are positioned to fit onto posts asshown in 39d.

Align logs #4a and #4b nose to nose (39g).

Log #6 may be positioned as desired providing it does notinterfere with the burner ports and the flames. (39i)Log #6 is not included in the See-Thru unit.

MAIN BURNER DEFLECTOR

MAIN BURNER

Log colours may vary. During the initial use of the fireplace, thecolours will become more uniform as colour pigments burn induring the heat activated curing process.

GLOWING EMBERS: (39j) Tear the embers into piecesand place along the perimeter of the runner burners aswell as covering all of the burner area beneath and in frontof the hollowed out section of log 1 & 2. Care should betaken to shred the embers into thin, small irregular piecesas only the exposed edges of the fibre hairs will glow. Theember material will only glow when exposed to direct flame;however, care should be taken to not block the burnerports. Blocked burner ports can cause an incorrect flamepattern, carbon deposits and delayed ignition. PHAZERTM

logs glow when exposed to direct flame.

CHARCOAL EMBERS: (39j) Randomly place the embersaround the bottom brick panels in a realistic manner butnot in contact with the flames. Keep ember dust away fromburner ports to avoid plugging them.

Fine dust found in bottom of bag not to be used. Do notplace any embers on the main burner. PHAZERTM logs,and embers glow when exposed to direct flame. Use onlycertified PHAZERTM logs, glowing embers and charcoalembers available from your Napoleon / Wolf Steel Ltd. dealer.

39b 39c

39d 39e

39f

39g

39i

39j

GLOWING EMBERS

CHARCOAL EMBERS

39a

#6#2

#5 #3

#1 #4a

#4b

#1#2

A

POSTS

#3

#4a

#4b

LOG #6

#3

39h

LOG #5

Page 22: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

22

WS-415-091 / 06.26.00

DOOR, LOUVRE AND TRIM REMOVAL& INSTALLATIONEnsure that thedoor is properlyclipped onto thesteel lip to pre-vent overheat-ing, glass break-age and / or dis-colouration ofthe upper trim.

VERTICAL END TRIM Corner and Peninsula Units only:The two vertical end trims are each held on with a magnet,centred on each corner post. Insert the trim under the topfacing and align along the corner posts with the bottoms ofeach end trim level with the bottom of the unit.DOOR TRIM: Hang the side door trim onto each doorside with the notches towards the centre of the unit. Thetop and bottom door trim may be installed next. Attachmagnets to the top and bottom door trim approximately 4"from either end. Lift up the top trim and hook over the top ofthe door. The bottom trim is inserted into the bottom doorsill. Push in to engage the magnets. Centre both side trims.Side door trim is not required for the end door.OPTIONAL LOUVRES: The louvres are installed as il-lustrated in FIGURES 42. Optional plated door trim is alsoavailable at your local Napoleon / Wolf Steel dealer.

LOUVRE BRACKETS AND DOOR INSTALLATION:Attach all louvre brackets as required with louvre securingtabs facing out. Do not attach optional louvres at thistime. To install the door(s), hook it over the rail locatedabove the door opening and secure with screws along thesides and bottom of the door. Tighten screws snugly. Donot over-tighten.

FIGURES 42

FIGURES 41

FIGURE 40

DOORSTEEL LIP

Page 23: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

23

WS-415-091 / 06.26.00

Do not overtighten thermodisc or distort housing. Attachthe connectors from the black and white wires to thethermodisc.Attach the connectors from theblack and red wires to theblower. Attach and secure thevariable speed switch using thenut provided. Plug the harnesscord into the receptacle.

The wire harness provided in this kit is a universal har-ness. When installed, ensure that any excess wire iscontained, preventing it from making contact with mov-ing or hot objects.Drywall dust will penetrate into the blower bearings,causing irreparable damage. Care must be taken toprevent drywall dust from coming into contact with theblower or its compartment. Any damage resulting fromthis condition is not covered by the warranty policy.Because the blower is thermally activated, when turnedon, it will automatically start approximately 10 minutesafter lighting the fireplace and will run for approximately30 - 45 minutes after the fireplace has been turned off.Use of the fan increases the output of heat.

The blower bracket contains slots that allow the blower tobe positioned away from the intended gas supply hole.Secure the blower using the lock washers and wing nutsprovided.Remove the thermodiscfrom the "Z" shaped mount-ing bracket and re-attach tothe bracket supplied in theburner kit. This bracket isfound secured to the pilothousing behind the variablespeed / piezo ignitorbracket.

INSTALLATION TO BE DONE BY A QUALIFIED IN-STALLER and must be electrically connected and groundedin accordance with local codes. In the absence of localcodes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE

in Canada or the ANSI/NFPA 70-1996 NATIONAL ELECTRICAL CODE

in the United States.Remove theblower from itsmounting bracketand attach to thebracket suppliedwith the fireplace.This bracket isfound secured onthe mountingstuds located atthe bottom of thevent side wall.

red

white

black

OPTIONAL BLOWER INSTALLATION

Position the vibration reducing pad, centred, onto the 2threaded studs, piercing 2 holes into the pad. The blowermust be able to be positioned entirely onto the pad.Tilt the blower onto its side and slide it past the controls.Position the blower onto the studs.

O IHFFO N

LO

P L O

TI

PI LOT

FIGURE 46

FIGURE 43

FIGURE 45

FIGURE 47

O IHFFO N

LO

P L

O

T

I

P I L O T

FIGURE 48

FIGURE 49

FIGURE 44

Page 24: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

24

WS-415-091 / 06.26.00

WHAT TO DO IF YOU SMELL GAS:• Turn off all gas to the fireplace.• Open windows.• Do not try to light any appliance.• Do not touch any electric switch; do

not use any phone in your building.• Immediately call your gas supplier from a neighbour's

phone. Follow the gas supplier's instructions.• If you cannot reach your gas supplier, call the fire de-

partment.

P

I

NO

L

O

T

F FO

GAS KNOB

LON/OFFKNOB

F FO

P

I

NO

L

O

T

IHPILOTO

PI LOT ADJUSTMENTKNOBFLAME

OPERATION / MAINTENANCEOPERATING INSTRUCTIONSWhen lit for the first time, the fireplace will emit a slightodour for a few hours. This is a normal temporary condi-tion caused by the curing of the logs and the "burn-in" ofinternal paints and lubricants used in the manufacturingprocess and will not occur again. Simply open a window tosufficiently ventilate the room.

After extended periods of non-operation such as followinga vacation or a warm weather season, the fireplace mayemit a slight odour for a few hours. This is caused by dustparticles in the heat exchanger burning off.Purge the gas line with a glass door removed. Assurethat a continuous gas flow is at the burner before re-installing the door.

FOR YOUR SAFETY READ BEFORE OPERATINGA. This fireplace is equipped with a pilot which must be lit by

hand while following these instructions exactly.B. Before operating smell all around the fireplace area for

gas and next to the floor because some gas is heavierthan air and will settle on the floor.

C. Use only your hand to turn the gas control knob. Neveruse tools. If the knob will not turn by hand, do not try torepair it. Call a qualified service technician. Force or at-tempted repair may result in a fire or explosion.

D. Do not use this fireplace if any part has been under water.Immediately call a qualified service technician to inspectthe fireplace and replace any part of the control systemand any gas control which has been under water.

LIGHTING INSTRUCTIONSWARNING: The gas valve has an interlock device whichwill not allow the pilot burner to be lit until the thermocou-ple has cooled. Allow approximately 60 seconds for thethermocouple to cool.When lighting and re-lighting, the gas knob cannot beturned from pilot to off unless the knob is depressedslightly.1. Stop! Read the above safety information on this label.2. Turn off all electric power to the fireplace.3. Turn the gas knob clockwise to off.4. Wait five (5) minutes to clear out any gas. If you smell

gas including near the floor. Stop! Follow "B" in theabove safety information on this label. If you don't smellgas go the next step.

5. Turn gas knob counter-clockwise to pilot.6. Depress slightly and hold gas knob while lighting the

pilot with the push button ignitor. Keep knob depressedfor one minute, then release. If pilot does not continueto burn, repeat steps 3 through 5.

7. With pilot lit, depress and turn gas knob counter-clock-wise to on.

8. If equipped with remote on-off switch/thermostat, mainburner may not come on when you turn valve to on.Remote switch must be in the on position to igniteburner.

9. Turn on all electric power to the fireplace.

TO TURN OFF GAS1. Turn off all electric power to the fireplace if service is to be

performed.2. For a complete shut-down procedure: push in gas control

knob slightly and turn clockwise to off. Do not force.

3. For a temporary shut-down procedure: set thermostat tolowest setting or remote switch to off. Press and turn thegas knob clockwise to pilot.

MAINTENANCE Turn off the gas and electricalpower before servicing the fireplace.CAUTION: Label all wires prior to disconnection when servic-ing controls. Wiring errors can cause improper and danger-ous operation. Verify proper operation after servicing. This fire-place and its venting system should be inspected before useand at least annually by a qualified service person. The fire-place area must be kept clear and free of combustible materi-als, gasoline or other flammable vapours and liquids. The flowof combustion and ventilation air must not be obstructed.1. In order to properly clean the burner and pilot assembly,remove the logs to expose both assemblies.2. Keep the control compartment, logs, burner, air shutter open-ing and the area surrounding the logs clean by vacuuming orbrushing, at least once a year.

3. Check to see that all burner ports are burning. Clean out anyof the ports which may not be burning or are not burning prop-erly. (End brick panel must be removed in order to facilitateburner removal, where applicable.)4. Check to see that the pilot flame is large enough to engulfthe thermocouple and thermopile and reaches toward theburner with the third jet.5. Replace the cleaned logs.6. Check to see that the main and runner burners ignite com-pletely on all openings when the gas knob for the burners isturned on. A 5 to 10 second total light-up period is satisfactory. Ifignition takes longer, consult your Napoleon dealer / distributor.7. Check that the gasketing on the sides, top and bottom ofadjustments the door is not broken or missing. Replace ifnecessary.

Page 25: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

25

WS-415-091 / 06.26.00

ADJUSTMENTSPILOT BURNER ADJUSTMENTAdjust the pilot screw to provide properly sized flame. Turnin a clockwise direction to reduce the gas flow.

VENTURI ADJUSTMENTNatural gas models have air shutters set at 3/16 (.188")inch open. Propane gas models have air shutters set at 3/8 (.375) inch open. Closing the air shutter will cause amore yellow flame, but can lead to carboning. Opening theair shutter will cause a more blue flame, but can causeflame lifting from the burner ports. The flame may not ap-pear yellow immediately; allow 15 to 30 minutes for thefinal flame colour to be established.

FIGURE 52

P

I

PI

PILOT SCREW

LOT

N O

L

O

THI

LO

FF O

FIGURE 50

FLAME MUST ENVELOPUPPER 3/8" TO 1/2" OFTHERMOCOUPLE & THERMOPILE

ELECTRODE

THERMO-COUPLE

THERMOPILETHERMOPILEBURNERPILOT FIGURE 51

AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY AQUALIFIED GAS INSTALLER!

REPLACEMENTSORDERING REPLACEMENT PARTSContact your dealer or the factory for questions concerningprices and policies on replacement parts. Normally all partscan be ordered through your Napoleon dealer or distribu-tor.

When ordering replacement parts always give the follow-ing information:

1. Model & Serial Number of the unit.2. Installation date of the unit.3. Part Number4. Part Description5. Finish

Page 26: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

26

WS-415-091 / 06.26.00

REPLACEMENT PARTSFor warranty replacement parts, a photocopy of the origi-nal invoice will be required to honour the claim.PART No. DESCRIPTION

COMPONENTS COMMON TO ALL UNITS:GA-GD-135.062 LOG #1GA-GD-135.063 LOG #2GA-GD-135.064 LOG #3GA-GD-135.065 LOG #4GA-GD-135.066 LOG #5GL-621 LOG SET ASSEMBLY c/w EMBERSGA-GD-361.16 GLOWING EMBERSGA-GI-550.01 CHARCOAL EMBERSGA-GD-562.09 DOOR GASKET (100 INCHES)WS-300-20 SIDE DOOR GLASS ONLYGA-GD-321K BLACK SIDE DOOR c/w GLASSGA-GD-225.36 BLACK SIDE DOOR FRAMEGA-GD-020.042 PKG OF 5 DOOR SCREWSGA-GD-715.136 TOP SIDE DOOR TRIMGA-GD-715.137 BOTTOM SIDE DOOR TRIMGD-500.136 FIRESTOP - RIGID VENTINGGD-500.106 FIRESTOP - FLEXIBLE VENTINGGD 781-KT SET OF 4 BRICK PANELSGA-GD-500.104 RETAINING BRACKETGA-GD-475.160 SIDE BRICK PANELGA-GD-475.159 END BRICK PANELGA-GD-475.158 RIGHT BRICK PANELGA-GD-475.157 LEFT BRICK PANELGD-500.106 FIRE STOP SPACERGD-500.136 FIRESTOP SPACERWS-385-33 NAPOLEON LOGOGA-GD-500.103 TERMINAL EXTENSION PLATEGA-GD-361.027 INSULATION SLEEVEWS-573-008 HIGH TEMP SEALANTGA-GD-080.23 UPPER LOUVRE BRACKETWS-430-001 CERAMIC MAGNETGA-GD-200.055 LEFT / RIGHT SIDE DOOR TRIM

COMPONENTS UNIQUE TO OPEN END UNIT:GA-GD-135.067 LOG #6GA-GD-010.421 SIDE DOOR COVERGA-GD-010.423 SIDE DOOR HEAT SHIELDGA-GD-020.042 PKG OF 5 DOOR SCREWSGA-GD-475.161 REAR BRICK PANELGA-GD-225.045 BLACK END DOOR FRAMEGA-GD-322K BLACK END DOOR c/w GLASSWS-300-027 END DOOR GLASS ONLYGD-010.540 END DOOR GLASS C/W GASKETWS-430-001 CERAMIC MAGNETGA-GD-715.180 VERTICAL END TRIMGA-GD-715.185 BOTTOM END DOOR TRIMGA-GD-715.186 TOP END DOOR TRIMGA-GD-080.277 BOTTOM LOUVRE BRACKETGA-GD-080.23 UPPER LOUVRE BRACKETGA-GD-562.09 DOOR GASKET (100 INCHES)

COMPONENTS UNIQUE TO SEE-THRU UNIT:GA-GD-010.424 END DOOR HEAT SHIELDGA-GD-010.422 END DOOR COVERGA-GD-500.101 SIDE BRICK PANEL RETAINERGA-GD-475.163 SIDE BRICK PANELGA-GD-321K BLACK SIDE DOOR c/w GLASSGA-GD-562.09 DOOR GASKET (100 INCHES)GA-GD-225.36 BLACK SIDE DOOR FRAMEWS-300-20 SIDE DOOR GLASS ONLYGD-010.540 END DOOR GLASS C/W GASKETGA-GD-080.277 BOTTOM LOUVRE BRACKETGA-GD-080.23 UPPER LOUVRE BRACKETGA-GD-200.055 LEFT / RIGHT SIDE DOOR TRIMGA-GD-715.136 TOP SIDE DOOR TRIMGA-GD-715.137 BOTTOM SIDE DOOR TRIMGA-GD-020.042 PKG OF 5 DOOR SCREWSWS-430-001 CERAMIC MAGNET

GA-GD-715.185

GA-GD-715.186

GD2E-PB

GD2E-PB

WS-300-027

GA-GD-225.045

GD-500.106/GD-500.136

GA-GD-500.103

GA-GD-361.027

GA-GD-715.136GD202-PB

GD-200.055

GD202-PB GA-GD-225.36

GD-200.055

GA-GD-715.137

GA-GD-020.042

WS-300-20

WS-430-001

GA-GD-475.159GA-GD-500.104

GA-GD-475.158

GD 781 KTGA-GD-475.157

GA-GD-475.160

GA-GD-475.163

GA-GD-500.101

GA-GD-475.161

GA-GD-010.421

GA-GD-010.423

GA-GD-080.23

GA-GD-010.422

GA-GD-080.277

GA-GD-010.424

Page 27: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

27

WS-415-091 / 06.26.00

PART NO. DESCRIPTIONCOMPONENTS UNIQUE TO PENINSULA UNIT:WS-430-001 CERAMIC MAGNETGA-GD-135.067 LOG #6WS-300-027 END DOOR GLASS ONLYGD-010.540 END DOOR GLASS C/W GASKETWS-300-20 SIDE DOOR GLASS ONLYGA-GD-225.36 BLACK SIDE DOOR FRAMEGA-GD-225.045 BLACK END DOOR FRAMEGA-GD-322K BLACK END DOOR c/w GLASSGA-GD-321K BLACK SIDE DOOR c/w GLASSGA-GD-080.277 BOTTOM LOUVRE BRACKETGA-GD-080.23 UPPER LOUVRE BRACKETGA-GD-715.180 VERTICAL END TRIMGA-GD-200.055 LEFT / RIGHT SIDE DOOR TRIMGA-GD-715.185 BOTTOM END DOOR TRIMGA-GD-715.137 BOTTOM SIDE DOOR TRIMGA-GD-715.186 TOP END DOOR TRIM

BURNER COMPONENTS:WS-455-4 #36 MAIN BURNER ORIFICE - NGWS-455-027 #55 RUNNER BURNER ORIFICE - NGWS-455-03 #54 MAIN BURNER ORIFICE - LPWS-455-028 #70 RUNNER BURNER ORIFICE - LPWS-100-38 NATURAL GAS PILOT ASSEMBLYWS-100-39 PROPANE GAS PILOT ASSEMBLYWS-455-23 NATURAL GAS PILOT ORIFICE - #51WS-455-24 PROPANE GAS PILOT ORIFICE - #30WS-660-05 BURNER ON/OFF SWITCHGA-GD-100.048 LEFT RUNNER BURNERGA-GD-100.049 RIGHT RUNNER BURNERWS-100-042 MAIN BURNERWS-680-04 THERMOPILEWS-680-05 THERMOCOUPLEWS-725-26 PROPANE GAS VALVEWS-725-25 NATURAL GAS VALVEWS-357-01 PIEZO IGNITER

VENT KITS:GD220 (5 FOOT)GA-GD-010.397 4" FLEXIBLE ALUMINIUM LINER - (5 FT.) C/W SPACERS

WS-410-17 7" FLEXIBLE ALUMINIUM LINER - (5 FT.)GD330 (10 FOOT)WS-410-018 7" FLEXIBLE ALUMINIUM LINER -(10 FT.)GS-10.300 4" FLEXIBLE ALUMINIUM LINER - (10 FT.) C/W SPACERS

GA-GD-010.370 WALL SUPPORT ASSEMBLY

TERMINAL KITS:ROOF TERMINAL KITS:

1/12 TO 7/12 PITCH - GD1108/12 TO 12/12 PITCH - GD111FLAT ROOF - GD112

GD-120.036 VERTICAL CAPWS-170-063 STORM COLLARGD-010.453 ROOF SUPPORTWS-263-054 / WS-263-055 / WS-263-056 ROOF FLASHING

PERISCOPE - GD201WALL TERMINAL KIT - GD222

WS-100-042

WS-455-027WS-455-028

WS-455-4WS-455-03

GD-100.049GD-100.048

GD110GD111GD112

GD201

WS-263-054 /WS-263-055 / WS-263-056

GD222

WS-170-063

GD010.569GD120.036

WS-680-04WS-680-05

WS-455-23/WS-455-24

WS-100-38/WS-100-39

WS-725-25/WS-725-26

KB-35

WS-357-01

WS-660-5

GA-GD-361.16

GD-135.064#3

GD-135.065

#4a

#4b

GD-135.067#6 GD-135.066

#5GD-135.063

#2

GD-135.062 #1GA-GI-550.01

GL 621

Page 28: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

28

WS-415-091 / 06.26.00

ACCESSORIES:WS-690-1 MILLIVOLT THERMOSTATGD301 HEAT GUARDGD303 VINYL SIDING SHIELDWS-573-008 HI-TEMP SEALANTGA-GD-010.370 WALL SUPPORT ASSEMBLYGD225-K DOOR FACIA - BLACK side door onlyGD225-PB DOOR FACIA - POLISHED BRASS side door onlyGD250K WEBBED DOOR FACIAGZ-550-1KT BLOWER KITWS-175-053 DURA-VENT ZERO CLEARANCE ADAPTORGD202-PB RECTANGULAR DOOR TRIM KIT - POLISHED BRASS SIDE DOOR ONLY

GD2E-PB RECTANGULAR DOOR TRIM KIT - POLISHED BRASS END DOOR ONLY

GD320B-KT BAY WINDOW KIT - SIDE DOOR ONLY

WS-660-2 HAND HELD WIRELESS REMOTE SWITCHWS-660-010 REMOTE CONTROL - ADVANTAGE

WS-660-011 REMOTE CONTROL - ADVANTAGE PLUS

WS-175-1 4" COUPLERWS-175-13 7" COUPLERKB35 VARIABLE SPEED SWITCHWS-500-33 V.S.S. MOUNTING PLATE FOR WALL SWITCH

GDELK END DOOR LOUVRE SET - BLACK

GDELPB END DOOR LOUVRE SET - POLISHED BRASS

GDELAB END DOOR LOUVRE SET - ANTIQUE BRASS

GDELSS END DOOR LOUVRE SET - STAINLESS STEEL

GDLK SIDE DOOR LOUVRE SET - BLACK

GDLPB SIDE DOOR LOUVRE SET - POLISHED BRASS

GDLAB SIDE DOOR LOUVRE SET - ANTIQUE BRASS

GDLSS SIDE DOOR LOUVRE SET - STAINLESS STEEL

GDLK / GDLPB / GDLAB / GDLSS

GD250K

GZ-550-1KT

GD320B-KT

GD225-K / PB

WS-573-008

GD-303

GD-301

WS-690-01

GDELK / GDELPBGDELAB / GDELSS

Page 29: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

29

WS-415-091 / 06.26.00

TROUBLE SHOOTING GUIDETEST SOLUTIONSYMPTOM PROBLEM

BEFORE ATTEMPTING TO TROUBLESHOOT, PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR REMOVED.

Carbon is beingdeposited onglass, logs orc o m b u s t i o nchamber sur-faces.

Flame is impinging on thelogs or combustion cham-ber.

- check that the logs are correctly positioned.- open air shutter to increase the primary air.- check the input rate: check the manifold pressure and orifice sizeas specified by the rating plate values.- check that the door gasketing is not broken or missing and that theseal is tight.- check that both 4" and 7" vent liners are free of holes and wellsealed at all joints.- check that minimum rise per foor has been adhered to for anyhorizontal venting.

Air shutter has becomeblocked

- ensure air shutter opening is free of lint or other obstructions.

Flames are con-sistently too largeor too small.Carboning occurs.

- check pressure readings:Inlet pressure can be checked by turning screw (A) counter-clock-wise 2 or 3 turns and then placing pressure gauge tubing over thetest point. Gauge should read 7" (minimum 4.5") water column fornatural gas or 13" (11" minimum) water column for propane. Checkthat main burner is operating on "HI".Outlet pressure can be checked the same as above using screw (B).Gauge should read 3.5" water column for natural gas or 10" watercolumn for propane. Check that main burner is operating on "HI".AFTER TAKING PRESSURE READINGS, BE SURE TO TURNSCREWS CLOCKWISE FIRMLY TO RESEAL. DO NOTOVERTORQUE.Leak test with a soap and water solution.

Unit is over-fired or under-fired.

P

I

AB

PILOT

N O

L

O

T

HI

LO

FF O

Main burner flameis a blue, lazy,t r a n s p a r e n tflame.

Blockage in vent. - remove blockage. In really cold conditions, ice buildup may occuron the terminal and should be removed as required.

Incorrect installation. - refer to Figure 34 to ensure correct location of storm collars.

White / grey filmforms.

Sulphur from fuel is beingdeposited on glass, logs orcombustion chamber sur-faces.

- clean the glass with a recommended gas fireplace glass cleaner.Do not clean glass when hot!If deposits are not cleaned off regularly, the glass may become per-manently marked.

Exhaust fumessmelled in room,headaches.

Fireplace is spilling. - check door seal and relief flap seal.- check for chimney blockage- check that chimney is installed to building code.- room is in negative pressure; increase fresh air supply.

Pilot goes outwhen the gas knobis released.The gas valve hasan interlock de-vice which will notallow the pilotburner to be lituntil the thermo-couple hascooled. Allow ap-proximately 60seconds for thethermocouple tocool.

System is not correctlypurged.

- purge the gas line with a glass door removed.

Out of propane gas. - fill the tank.Pilot flame is not largeenough

- turn up the pilot flame.

- gently twist the pilot head to improve the flame pattern around thethermocouple.

Pilot flame is not engulfingthe thermocouple.Thermocouple shorting /faulty.

- loosen and tighten thermocouple.- clean thermocouple and valve connection.- replace thermocouple.- replace valve.

Faulty valve. - replace.

Page 30: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

30

WS-415-091 / 06.26.00

TEST SOLUTIONPROBLEMSYMPTOM

Main burner goesout; pilot goes out.

Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON"

Vent is blocked - check for vent blockage.- check joint seals and installation.

4" flexible vent has becomedisconnected from fireplace.

- re-attach to fireplace.

Vent is re-circulating

Pilot burning; nogas to mainburner; gas knobis on 'HI'; wallswitch / thermo-stat is on.

Themostat or switch is de-fective.

- connect a jumper wire across the wall switch terminals; if mainburner lights, replace switch / thermostat.

Wall switch wiring is defec-tive.

- disconnect the switch wires from the valve & connect a jumper wireacross terminals 1 & 3; if the main burner lights, check the wires fordefects and / or replace wires.

Main burner orifice isplugged.

- remove stoppage in orifice.

- replace.Faulty valve.

Pilot goes outwhile standing;Main burner is in'OFF' position.

Gas piping is undersized. - turn on all gas appliances and see if pilot flame flutters, dimin-ishes or extinguishes, especially when main burner ignites. Monitorappliance supply working pressure.- check if supply piping size is to code. Correct all undersized piping.

Pilot will not light. - check if pilot can be lit by a match- check that the wire is connected to the push button ignitor.- check if the push button ignitor needs tightening.- replace the wire if the wire insulation is broken or frayed.- replace the electrode if the ceramic insulator is cracked or broken.- replace the push button ignitor.

No spark at pilot burner

PILOTTHERMOPILEBURNER

ELECTRODE

THERMO-COUPLE - fill the tank.Out of propane gas

Spark gap is incorrect - spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.) fromthe electrode tip and the pilot burner. To ensure proper electrodelocation, tighten securing nut (finger tight plus 1/4 turn).

No gas at the pilot burner - check that the manual valve is turned on.- check the pilot orifice for blockage.- replace the valve.- call the gas distributor.

Main burner goesout; pilot stays on.

Pilot flame is not largeenough or not engulfing thethermopile

- turn up pilot flame.- replace pilot assembly.

Thermopile shorting - clean thermopile connection to the valve. Reconnect.- replace thermopile / valve.

Remote wall switch wire istoo long; too much resist-ance in the system.

- shorten wire to correct length or wire gauge.

Faulty thermostat or switch. - replace.

Remote wallswitch is in "OFF"position; mainburner comes onwhen gas knob isturned to "ON" po-sition.

Wall switch is mounted up-side down

- reverse.

Faulty valve. - replace.

- replace.Remote wall switch isgrounding.

- check for ground (short); repair ground or replace wire.Remote wall switch wire isgrounding.

Page 31: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

31

WS-415-091 / 06.26.00

Wolf Steel Fireplace Service HistoryThis fireplace must be serviced at least annually depending on usage.

Date Service TechnicianName

Service Performed Special ConcernsDealer Name

Page 32: GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM · 2015-03-10 · 1 ws-415-091 / 06.26.00 gas fired - direct vent millivolt system installation and operation instructions for multi-view

32

WS-415-091 / 06.26.00

NOTES:


Recommended