+ All Categories
Home > Documents > GBI Decoupled Ventilation Systems - mgbc.org.my€¦ · Modulating Valve By-pass Damper F.A Filter...

GBI Decoupled Ventilation Systems - mgbc.org.my€¦ · Modulating Valve By-pass Damper F.A Filter...

Date post: 23-Oct-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
21
25/9/14 Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 1 Professor Chandra Sekhar PhD, Fellow ASHRAE, Fellow ISIAQ Department of Building, School of Design and Environment ASHRAE Distinguished Lecturer Talk GBI PROFESSIONAL SERIES ON IEQ 2014 Kuala Lumpur 10 October 2014 Dedicated Outdoor Air Systems or Decoupled Ventilation Systems Outdoor Air DEMAND VENTILATION Recirculated Air DEMAND COOLING IAQ - Exposure Control Professor Chandra Sekhar
Transcript
  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 1

    Professor Chandra Sekhar PhD, Fellow ASHRAE, Fellow ISIAQ

    Department of Building, School of Design and Environment

    ASHRAE Distinguished Lecturer Talk

    GBI  PROFESSIONAL  SERIES  ON  IEQ  2014  Kuala  Lumpur  

    10  October  2014  

    Dedicated Outdoor Air

    Systems or

    Decoupled Ventilation Systems

    Outdoor Air

    DEMAND VENTILATION

    Recirculated Air

    DEMAND COOLING

    IAQ - Exposure Control

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 2

    Dedicated Outdoor Air System (DOAS)

    Professor Chandra Sekhar

    DOAS1  

    CHWS=6-‐7  °C  

    CHWS=20  °C  

    Outdoor  Air  (O/A)    condiDon:  •  Full  dehumidifica?on  by  DOAS  to      required  Dew  Point  Temperature  

    •  Insulated  duct  

    O/A   O/A   O/A  

    O/A   O/A   O/A  

    O/A   O/A   O/A  

    O/A   O/A   O/A  

    O/A   O/A   O/A  

    O/A   O/A   O/A  

    O/A   O/A   O/A  

    O/A   O/A   O/A  

    Outdoor  Air  

    Two  Chillers  are  needed  due  to    different  CHWS  temp  requirements  

    What  is  Dedicated  Outdoor    Air  System  (DOAS)?  

    DOAS with Chilled Ceiling

    Chilled  Ceiling  Panels    Decoupling  Ven-la-on    From  Cooling  

    DEMAND  VENTILATION  &  DEMAND  COOLING  at  the    Independent  zone  level  Achieved  in  the  case  of  DOAS  with  Chilled  Ceiling  

    DOAS2  OR

    DOAS1  –  Chilled  water  coil  AHU  

    DOAS2  –  Desiccant  Dehumidifica?on  System  

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 3

    DEMAND  VENTILATION  &  DEMAND  COOLING  at  the    Independent  zone  level  NOT  ACHIEVED  in  the  case  of  DOAS  with  Secondary  AHU    

    DOAS  

    CHWS=6-‐7  °C  

    CHWS=7-‐9  °C  

    Outdoor  Air  (O/A)    condiDon:  •  Par?ally    dehumidified  by  DOAS      –  addi?onal  dehumidifica?on  done      by  secondary  AHU    OR  

    •  Full  dehumidifica?on  by  DOAS  to      required  Dew  Point  Temperature  

    •  Insulated    Duct  

    S/A   S/A   S/A  Secondary  AHU  

    Outdoor  Air  

    One  Chiller  can  provide  the    required  CHWS  Temp  for  DOAS    as  well  as  Secondary  AHU  (For  eg:  Sequen?al    feed)  

    What  is  Dedicated  Outdoor    Air  System  (DOAS)?  

    DOAS with Secondary AHU

    Decoupling  Ven-la-on    From  Cooling  

    Professor Chandra Sekhar

    Single Coil Twin Fan (SCTF) Air-conditioning & Air distribution system

    Sekhar, S.C., Uma Maheswaran, C.R., Tham, K.W, and Cheong K.W, 2004. Development of energy efficient single coil twin fan air-conditioning system with zonal ventilation control, ASHRAE Transactions, 2004, Vol. 110, Pt 2, pp 204-217 (Paper presented in Nashville, June 2004).

    Cheyyar, R U M, S C Sekhar, K W Tham and K W Cheong, "Single coil twin fan air-conditioning and air distribution system - Towards the development of a mathematical model of the compartmented coil". HVAC&R RESEARCH - International Journal of Heating, Ventilating, Air-conditioning and Refrigerating Research, 12, no. 3c, pp 825-842 (Special Issue) (October 2006).

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 4

    Fan  

    CHWS=6-‐8  °C  

    UncondiDoned  Outdoor  Air  (O/A)  •  Uninsulated  duct  if  O/A  from      roof-‐top  

    •  Alterna?vely,  O/A  can  be  drawn      at  each  level  

    S/A   S/A   S/A  SCTF  AHU  with  Compartmented  Coil  

    Outdoor  Air  

    One  Chiller  can  provide  the    required  CHWS  Temp  for  the  SCTF  System  

    Outdoor  Air  –      Zone  level  Demand  Ven?la?on  

    Recirculated  Air  –      Zone  level  Demand  Cooling  

    Single  Coil  Twin  Fan  (SCTF)  System    –  A  form  of  DOAS  

    Decoupling  Ven-la-on    From  Cooling  

    DEMAND  VENTILATION  &  DEMAND  COOLING  at  the    Independent  zone  level  Achieved  in  the  case  of  SCTF  System  

    SCTF System with Compartmented Cooling Coil

    Professor Chandra Sekhar

    F/A VAV Box

    R/A VAV Box

    Mixing Box

    CO2 T

    To other VAV Boxes In Other Zones

    R/A S/A

    Typical Zone VAV Box

    ΔP

    ΔP

    F/A VAV Fan

    R/A

    F/A

    CHWS

    CHWR Modulating Valve

    By-pass Damper

    F.A Filter F/A Comp Coil

    R/A Filter

    R/A Comp Coil

    R/A VAV Fan

    SCTF Air-conditioning and Air Distribution System (US and PCO Patents)

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 5

    R/A  plen

    um

    R/A  Filte

    r

    R/A  Co

    il  Co

    mpa

    rtmen

    t R/A  Drain  Pa

    n

    R/A  Fan

     R/A

     Filter    

    Compa

    rtmen

    t  Ac

    cess  doo

    r

     R/A

     Fan

     Co

    mpa

    rtmen

    t  Ac

    cess  doo

    r

    F/A  plen

    um

    F/A  Filte

    r

    F/A  Co

    il  Co

    mpa

    rtmen

    t

    F/A  Drain  Pa

    n

    F/A  Fan

     F/A

     Filter    

    Compa

    rtmen

    t  Ac

    cess  doo

    r

     F/A

     Fan

     Co

    mpa

    rtmen

    t  Ac

    cess  doo

    r Single    Coil  Twin  Fan  AHU  &  FCU  

    Professor  Chandra  Sekhar  

    SCTF system for independent conditioning of fresh air and return air streams – A Psychrometric Performance

    Return Air R/A : ON Coil VAV System 2 : Coil Condition Curve R/A : OFF Coil

    Outside Air O/A : ON Coil VAV System 1 : Coil Condition Curve O/A : OFF Coil

    Space Condition

    10-15% energy savings

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 6

    Comparison of Energy Consumption

    02468

    101214

    Conventional SCTF

    Type of System

    Coo

    ling

    Cap

    acity

    (kW

    )SCTF Prototype Findings

    12% Co

    oling (a

    ir-cond

    itionin

    g) ener

    gy savin

    gs

    Professor Chandra Sekhar

    Field Trial – A Test-Bedding Project

    The Enterprise Challenge (TEC) Grant

    DESIGN DATA F/A = 5,400 cmh R/A = 60,000 cmh Coil Cap = 86 kW (F/A) 233 kW (R/A)

    Bldg TOP = June 2005 SCTF Installed = June 2005

    Air-conditioned = 2,750m2 Floor Area for SCTF system

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 7

    Conference Room

    Meeting Room

    SCTF AHU

    Core

    Return-duct mountedT & CO2 sensors

    Staircase

    OpenPlan Space

    Individual Offices

    F/AR/A

    12

    3

    4

    5

    Conference Room

    Meeting Room

    SCTF AHU

    Core

    Return-duct mountedT & CO2 sensors

    Staircase

    OpenPlan Space

    Individual Offices

    F/AR/A

    12

    3

    4

    5

    Field Trial – A Test-Bedding Project

    The Enterprise Challenge (TEC) Grant Professor Chandra Sekhar

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 8

    Fiel

    d Tr

    ial –

    A

    Test

    -Bed

    ding

    Pro

    ject

    9 ppm

    Professor Chandra Sekhar

    Temperature (Level 3)

    182022242628

    06/26/06

    06/26/06

    06/27/06

    06/28/06

    06/28/06

    06/29/06

    06/30/06

    06/30/06

    2006-7-1

    2006-7-2

    2006-7-2

    Time

    T(C)

    point 1

    point 2

    point 3

    point 4

    point 5

    Relative Humidity (Level 3)

    40455055606570

    06/26/06

    06/26/06

    06/27/06

    06/27/06

    06/28/06

    06/28/06

    06/29/06

    06/30/06

    06/30/06

    2006-7-1

    2006-7-1

    2006-7-2

    Time

    RH(%)

    point 1

    point 2

    point 3

    point 4

    point 5

    Fiel

    d Tr

    ial –

    A

    Test

    -Bed

    ding

    Pro

    ject

    Indo

    or te

    mpe

    ratu

    re

    rang

    e : 2

    1.8

    - 23.

    8 °C

    Av

    erag

    e =

    23 °C

    Indo

    or re

    lativ

    e hu

    mid

    ity

    rang

    e : 4

    7 - 5

    4 %

    RH

    Av

    erag

    e =

    50 %

    RH

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 9

    Dynamic Response Characteristics of the

    SCTF System

    Prof Chandra SEKHAR, NUS Professor Chandra Sekhar

    Continuous plot of CO2 levels in various sampling points in the occupied zones in Level 3 (CO2 set point = 1000 ppm)

    Time Occ

    Density VSD FA Fan(Hz)

    VSD RA Fan(Hz)

    9:00 75 27.3 32.1 9:30 75 27.4 31.9

    10:00 82 27.3 31.9 10:30 75 27.3 31.9 11:00 77 27.4 31.9 11:30 78 27.3 31.9 12:00 70 27.1 31.9 12:30 79 27.1 31.7 13:00 15 27.1 31.5 13:30 30 27 31.2 14:00 48 27 31 14:30 74 27.4 31.9 15:00 74 27.3 31.9 15:30 74 27.4 32.1 16:00 74 27.3 31.9 16:30 78 27.3 32.2 17:00 75 27.2 31.9 17:30 76 27.2 31.5 18:00 71 27 31.4 18:30 35 26.5 31.2 19:00 5 26.2 31

    CO2 Set-point = 1000 ppm

    TLV

    Sunny Day

    Prof Chandra SEKHAR, NUS Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 10

    Continuous plot of CO2 levels in various sampling points in the occupied zones in Level 3 (CO2 set point = 500 ppm)

    Time Occupant Density

    VSD FA Fan(Hz)

    VSD RA Fan(Hz)

    9:00 72 40.5 35.3 9:30 76 41 35.6

    10:00 74 41.1 35.6 10:30 73 41.2 35.6 11:00 76 41.2 35.5 11:30 71 41.2 35.6 12:00 78 41.5 35.5 12:30 70 41.3 35.1 13:00 20 41.1 34.9 13:30 23 40.2 34.6 14:00 42 40.5 34.6 14:30 72 41.2 35.1 15:00 74 41.6 35.3 15:30 74 41.6 35.6 16:00 72 41.6 35.6 16:30 68 41.5 35.6 17:00 69 41.2 35.7 17:30 71 41.2 35.6 18:00 68 32.8 34.8 18:30 17 27.4 33.8 19:00 5 27.2 32.2

    CO2 Set-point = 500 ppm

    TLV

    Sunny Day

    Prof Chandra SEKHAR, NUS Professor Chandra Sekhar

    Zero Energy Building @ BCA Academy

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 11

    0

    2000

    4000

    6000

    8000

    10000

    12000

    14000

    6:00 am

    7:00 am

    8:00 am

    9:00 am

    10:00 am

    11:00 am

    12:00 pm

    1:00 pm

    2:00 pm

    3:00 pm

    4:00 pm

    5:00 pm

    6:00 pm

    7:00 pm

    8:00 pm

    Air

    flo

    w

    [m3 /

    h]

    AHU 2-1 Recirculated Airflow

    Fresh Airflow

    SCTF Fresh Airflow

    Actual F/A is independent

    and controlled by CO2 sensors

    IMPROVED FRESH AIR CONTROL

    Reduced F/A during low occupancy hours

    Slightly less F/A in afternoon during high

    occupancy hours

    Fresh air is a constant percentage

    (20.6%)

    Prof Chandra SEKHAR, NUS

    Professor C

    handra Sekhar

    AHU 2-1

    AHU 3-1

    AHU 3-2

    AHU 3-3

    Baseline

    cooling

    [kW]

    14300

    7930

    5600

    4530

    Actual

    cooling

    [kW]

    12400

    7530

    3950

    3890

    Percent

    difference *

    [%]

    13.28

    5.05

    29.46

    14.13

    IMPROVED FRESH AIR CONTROL = LESS ENERGY !!!

    * SAVINGS FOR APRIL 2010.

    Prof Chandra SEKHAR, NUS

    Professor C

    handra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 12

    Personalized Ventilation (PV) system

    Professor Chandra Sekhar

    Personalised Ventilation (PV) System

    Deliver fresh air directly to the Occupant breathing zone

    Potential to enhance •  Acceptability of ventilation •  Indoor Air Quality •  Thermal comfort

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 13

    CHWR

    SECONDARY AHU

    CH

    WS

    CHWR

    E/A

    U/F Supply P/V

    Sec S/A

    (P/V + Sec) R/A

    CHWS : Chilled water supply P/V : Personalised ventilation F/A : Fresh air CHWR : Chilled water return U/F Supply : Under floor supply R/A : Return air AHU : Air Handling Unit Sec S/A : Secondary supply air E/A : Exhaust air

    R/A

    CHWS

    100% F/A

    PRIMARY AHU

    CHWS

    CH

    WR

    Professor Chandra Sekhar

    Desk-mounted PV System integrated with

    Ceiling Supply MV System

    Gong, N, K W Tham, AK Melikov, DP Wyon, S C Sekhar and K W Cheong, "The acceptable air velocity range for local air movement in the Tropics". HVAC&R Research, International Journal of Heating, Ventilating and Air-Conditioning Engineers (ASHRAE), Vol 12, No. 4, pp 1065-1076, (October 2006). (United States).

    Sekhar, S C, N Gong, K W Tham, K W Cheong, A.K. Melikov, D.P. Wyon and P.O. Fanger, "Findings of personalised ventilation studies in a hot and humid climate". International Journal of Heating, Ventilating, Air-conditioning and Refrigerating Research (HVAC&R Research), Vol 11, no. 4

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 14

    •  Ambient and PV air temperatures

    •  Thermal comfort parameters within the occupied zone

    •  Breathing temperature in the occupant breathing zone

    •  Concentration levels of various indoor pollutants

    •  SF6 tracer gas measurements - ventilation effectiveness

    •  Questionnaire responses

    Experimental Protocol

    52 Professor Chandra Sekhar

    00.20.40.60.81

    1.21.41.61.82

    Vent

    ilatio

    n Ef

    fect

    iven

    ess

    26-23-15

    26-26-15

    26-20-7

    26-23-7

    26-0-15

    Experimental conditions

    • Higher the Better• Saves ENERGY

    PV

    WithoutPV

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 15

    -1.00

    -0.50

    0.00

    0.50

    1.00

    1 2 3 4 5 6 7 8 9 10 11

    Ther

    mal

    com

    fort

    acce

    ptab

    ility

    Subjects

    With PV W/O PV

    Mean responses of Thermal Comfort acceptability

    Very Acceptable

    Very Unacceptable

    Professor Chandra Sekhar

    -1.00-0.80-0.60-0.40-0.200.000.200.400.600.801.00

    1 2 3 4 5 6 7 8 9 10 11

    IAQ

    acc

    epta

    bilit

    y

    Subjects

    with PV without PV

    Mean responses of IAQ acceptability

    Very Acceptable

    Very Unacceptable

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 16

    PV system Consistent trends of thermal comfort & IAQ ratings Observed – INCREASE with INCREASING PV flow rate And DECREASING with INCREASING PV temps at Ambient temp of 26° C

    59 Professor Chandra Sekhar

    •  A warmer space temperature, such as 26 °C, accompanied by a PV air temperature of 23 °C, implies that the space cooling load is reduced in comparison with a conventional air-conditioning system in which the space is typically maintained at 23 °C.

    •  An absolute reduction in the total fresh air quantity provided is possible, as it is now directly supplied as inhaled air to the occupant breathing zone.

    Energy savings occur due to

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 17

    Ceiling-Mounted PV System integrated with

    Ceiling Supply MV System

    Professor Chandra Sekhar

    YANG, B, Arsen Melikov and S C Sekhar, "Performance evaluation of ceiling mounted personalized ventilation system". ASHRAE Transactions 2009, Vol. 115, Part 2, pp 395-406. (United States).

    Yang, B, S.C.Sekhar and Arsen Melikov, “Ceiling mounted personalized ventilation system integrated with a secondary air distribution system – A human response study in hot and humid climate”. Indoor Air – International Journal of Indoor Environment and Health (2010). Volume 20, no. 4 (2010): 309-319. (Denmark).

    YANG, B, S C Sekhar and Melikov Arsen, "Ceiling mounted personalized ventilation system in hot and humid climate –An energy analysis". Energy and Buildings, (2010). (Switzerland).

    Yang, B and S C Sekhar, "Three dimensional numerical simulations of a hybrid fresh air and recirculated air diffuser for decoupled ventilation strategy". Building and Environment, (2007), Vol.42, Issue 5, pp 1975-1982. (United Kingdom).

    Ceiling mounted PV System integrated with ambient MV system

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 18

    CFD simulation

    more fresh air is supplied directly into the breathing zone without mixing with recirculated air and much better IAQ in the occupied zone can be realized.

    Professor Chandra Sekhar

    ◊ 23.5/21

    □ 23.5/23.5

    ∆ 26/21

    Χ 26/23.5

    ﹡ 26/26

    0.0

    0.1

    0.1

    0.2

    0.2

    0.3

    0 4 8 12 16

    PV airflow rate (L/s)

    Inhaled air quality

    Y-ax

    is

    -1 =

    ver

    y un

    acce

    ptab

    le,

    0 =

    just

    una

    ccep

    tabl

    e/ac

    cept

    able

    , +1

    = v

    ery

    acce

    ptab

    le

    Ceiling-mounted PV system in conjunction with ceiling supply mixing ventilation system

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 19

    Desk-mounted PV System Integrated with UFAD System

    Li Ruixin, S.C.Sekhar and Arsen Melikov, “Thermal comfort and IAQ assessment of under-floor air distribution system integrated with personalized ventilation in hot and humid climate”. Building and Environment journal, Vol 45 (2010): 1906-1913. (United Kingdom).

    Li, Ruixin, S.C.Sekhar and A.K.Melikov, 2011. Thermal Comfort and Indoor Air Quality in rooms with Integrated Personalized Ventilation and Under-Floor Air Distribution Systems. HVAC&R Research, Volume 17, Number 5, pp 829-846 ,ASHRAE .

    Professor Chandra Sekhar

    Field Environmental Chamber (FEC) experimental setup - Desk mounted PV with UFAD system

    Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 20

    y = 1.4807x - 41.198 R² = 0.85823

    y = -0.6024x + 84.891 R² = 0.68715

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    72 74 76 78 80 82 84 86 88

    Perc

    eive

    d in

    hale

    d ai

    r tem

    pera

    ture

    Per

    ceiv

    ed in

    hale

    d ai

    r fre

    shne

    ss

    Acceptability of perceived air quality

    inhaled air freshness

    inhaled air temperature

    Cold

    Hot Fresh

    Stuffy

    Professor Chandra Sekhar

    Key Findings

    •  The use of PV-UFAD improved subjects’ thermal sensation in

    comparison with UFAD alone or mixing ventilation.

    •  The “cold feet” complaint decreased when the temperature of the

    air supplied from the UFAD was increased.

    •  The use of the PV provided the subjects with the preferred slightly

    cool thermal sensation at the head and face.

    •  Local cooling of the head and face could be achieved by

    decrease of the temperature of the personalized air or increase

    of its flow rate, i.e. increase of the air velocity at the head and

    face region. Professor Chandra Sekhar

  • 25/9/14

    Prof Chandra Sekhar, National University of Singapore, ASHRAE DL, Oct 2014 21

    Energy Efficient Healthy Buildings – Decoupled Ventilation Systems

    Air-conditioning Systems

    • Dedicated Outdoor Air System • Single Coil Twin Fan System

    Final Words

    Air Distribution Systems

    • Single Coil Twin Fan • Personalized Ventilation with Mixing Ventilation • Personalized Ventilation with UFAD

    Professor Chandra Sekhar

    Professor Chandra Sekhar


Recommended