GC Submittal Data Contractor: P.O.: Engineer: Project Name: Unit Tag: ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. Page ______ of ______ Rev.: 03/13/03 *LC279* LC279 Genesis Compact (GC) Series Submittal Data Models GCH/V 018B - 060B 50Hz - R22 English Language/SI Units REVISION: 03/13/03 SERIES: HZ: UNIT OF MEAS: LANGUAGE: GC - R22 50 SI ENGLISH
Transcript
Page 1: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

Genesis Compact (GC)Series Submittal DataModels GCH/V 018B - 060B

50Hz - R22English Language/SI Units

REVISION: 03/13/03

SERIES:HZ:UNIT OF MEAS:LANGUAGE:

GC - R2250SI

ENGLISH

Page 2: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

MODEL DECODER

CGC

Model TypeGC = Genesis Compact Series

036 B 3 L BH

Configuration

SU

Controls

Cabinet Insulation3 = Standard Range4 = Standard Range, Mute

0 C

Future use0 = None

Rev:. 6/19/02 A

018, 024, 030, 036, 041, 042, 048, 060Size 041 available in vertical only

Voltage & RefrigerantV = 220-240/50/1 R22U = 380-420/50/3 R22

Unit Size, Nominal kbtuhH = Horizontal, V = Vertical

Water CoilC = CopperN = Cupro-Nickel

Standard

L = Left ReturnR = Right ReturnF = Front Return, vertical 018 - 030 only

T = Topflow, vertical onlyV = Topflow - High Static, vertical onlyB = Back Discharge, horiz. onlyS = Straight Discharge, horz. onlyY = Back Discharge - High Static, horz. onlyZ = Straight Discharge - High Static, horz. only

Supply Air Options

Return Air Options

Revision LevelA = Horizontal sizes 042 - 060B = Horziontal sizes 018 - 036

B = All Vertical sizes

C = CXM ControllerD = DXM Controller

L = CXM w/LonworksM = DXM w/Lonworks

F = CXM - CE MarkG = DXM - CE Mark

H = CXM w/Lonworks - CE MarkJ = DXM w/Lonworks - CE Mark

Page 3: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAARI/ASHRAE/ISO 13256-1

ARI/ASHRAE/ISO 13256-1Metric (SI) Units

ModelLiquidFlow

AirFlow Cooling 30°C EWT Heating 20°C EWT Cooling 15°C EWT Heating 10°C EWT Cooling 25°C EWT Heating 0°C EWT

(l/s) (l/s) CapacityWatts

EER(W/W)

CapacityWatts

COP(W/W)

CapacityWatts

EER(W/W)

CapacityWatts

COP(W/W)

CapacityWatts

EER(W/W)

CapacityWatts

COP(W/W)

GCV/H018 0.215 236 4,671 3.6 5,529 4.2

GCV/H024 0.284 319 6,119 3.9 7,381 5.0

GCV/H030 0.353 401 6,918 3.7 8,482 4.7

GCV/H036 0.429 472 8,842 3.5 11,458 4.5

GCV041 0.498 543 9,709 3.7 11,991 4.4

GCV/H042 0.505 566 10,513 3.8 13,187 4.5

GCV/H048 0.568 649 12,107 3.8 14,693 4.9

GCV/H060 0.713 779 14,786 3.9 18,714 4.5

Cooling capacities based upon 27°C DB, 19°C WB entering air temperature Rev.: 02/14/03 B

Heating capacities based upon 20°C DB, 15°C WB entering air temperatureAll air flow is rated on high speedAll ratings based upon operation at lower voltage of dual voltage rated models

ARI/ASHRAE/ISO 13256-1English (IP) Units

ModelLiquidFlow

AirFlow Cooling 86°F EWT Heating 68°F EWT Cooling 59°F EWT Heating 50°F EWT Cooling 77°F EWT Heating 32°F EWT

(gpm) (cfm) Capacity

BtuhEER

Btuh/W Capacity

Btuh COP CapacityBtuh

EERBtuh/W

CapacityBtuh COP Capacity

BtuhEER

Btuh/W Capacity

Btuh COP

GCV/H018 3.4 500 15,937 12.3 18,865 4.2

GCV/H024 4.5 676 20,878 13.3 25,184 5.0

GCV/H030 5.6 850 23,604 12.6 28,941 4.7

GCV/H036 6.8 1000 30,169 11.9 39,095 4.5

GCV041 7.9 1150 33,127 12.6 40,913 4.4

GCV/H042 8.0 1199 35,870 13.0 44,994 4.5

GCV/H048 9.0 1375 41,309 13.0 50,133 4.9

GCV/H060 11.3 1650 50,450 13.3 63,852 4.5

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B

Heating capacities based upon 68°F DB, 59°F WB entering air temperatureAll air flow is rated on high speedAll ratings based upon operation at lower voltage of dual voltage rated models

cfm*0.472 = l/s

gpm*0.0631 = l/s

in wg*249 = pascals

ft of hd *2990 = pascals

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Page 4: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAGCH/V 018B

236 l/s Nominal Airflow Performance capacities shown in kW

EWT °CWaterFlow WPD

COOLING - EAT 27/19°C HEATING - EAT 20°C

l/s kPA TCkW

SCkW

Sens/Tot Ratio

PowerkW

HRkW

EERW/W

HCkW

PowerkW

HEkW

LAT°C

COPW/W

0.146 14.4 5.1 4.0 0.78 1.12 6.2 4.55 5.1 1.26 3.8 37.9 4.05

15 0.215 21.0 5.3 4.1 0.77 1.05 6.4 5.05 5.3 1.29 4.0 38.6 4.11

0.283 29.2 5.4 4.1 0.76 1.02 6.4 5.29 5.4 1.30 4.1 39.0 4.15

0.146 14.0 4.9 3.9 0.80 1.19 6.1 4.12 5.4 1.30 4.1 39.0 4.15

20 0.215 20.2 5.1 4.0 0.78 1.12 6.2 4.55 5.6 1.32 4.3 39.7 4.24

0.283 28.5 5.2 4.0 0.77 1.09 6.3 4.77 5.7 1.33 4.4 40.0 4.29

0.146 13.6 4.7 3.8 0.81 1.27 6.0 3.70 5.8 1.34 4.5 40.4 4.33

25 0.215 19.6 4.9 3.9 0.80 1.20 6.1 4.08 6.0 1.37 4.6 41.1 4.38

0.283 27.7 5.0 3.9 0.78 1.18 6.2 4.24 6.1 1.38 4.7 41.4 4.42

0.146 13.2 4.4 3.6 0.82 1.34 5.7 3.28 6.1 1.37 4.7 41.4 4.45

30 0.215 19.1 4.6 3.7 0.80 1.29 5.9 3.57 6.3 1.40 4.9 42.1 4.50

0.283 27.0 4.7 3.8 0.81 1.26 6.0 3.73 6.3 1.41 4.9 42.1 4.47

0.146 12.8 4.0 3.3 0.83 1.41 5.4 2.84

35 0.215 18.5 4.3 3.5 0.81 1.36 5.7 3.16 Operation Not Recommended

0.283 26.3 4.4 3.6 0.82 1.33 5.7 3.31

Rev: 03/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

See Performance Correction Tables for operating conditions other than those listed above.

Data table does not reflect ISO pump or fan corrections.

Page 5: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAGCH/V 024B

319 l/s Nominal Airflow Performance capacities shown in kW

EWT °CWaterFlow WPD

COOLING - EAT 27/19°C HEATING - EAT 20°C

l/s kPA TCkW

SCkW

Sens/TotRatio

PowerkW

HRkW

EERW/W

HCkW

PowerkW

HEkW

LAT°C

COPW/W

0.190 13.8 6.4 5.1 0.80 1.41 7.8 4.54 6.7 1.43 5.3 37.4 4.69

15 0.284 26.6 6.5 5.2 0.80 1.33 7.8 4.89 7.0 1.46 5.5 38.2 4.79

0.378 44.4 6.6 5.2 0.79 1.29 7.9 5.12 7.2 1.48 5.7 38.7 4.86

0.190 13.4 6.3 5.0 0.79 1.49 7.8 4.23 7.2 1.49 5.7 38.7 4.83

20 0.284 25.7 6.4 5.1 0.80 1.42 7.8 4.51 7.5 1.51 6.0 39.5 4.97

0.378 43.0 6.4 5.1 0.80 1.38 7.8 4.64 7.6 1.53 6.1 39.8 4.97

0.190 13.0 6.1 4.9 0.80 1.58 7.7 3.86 7.7 1.54 6.2 40.0 5.00

25 0.284 25.0 6.3 5.0 0.79 1.52 7.8 4.14 7.9 1.57 6.3 40.5 5.03

0.378 41.8 6.3 5.0 0.79 1.48 7.8 4.26 8.0 1.58 6.4 40.8 5.06

0.190 12.6 5.8 4.7 0.81 1.67 7.5 3.47 8.0 1.59 6.4 40.8 5.03

30 0.284 24.5 6.0 4.9 0.82 1.61 7.6 3.73 8.2 1.61 6.6 41.3 5.09

0.378 41.0 6.1 4.9 0.80 1.57 7.7 3.89 8.2 1.63 6.6 41.3 5.03

0.190 12.2 5.4 4.5 0.83 1.75 7.2 3.09

35 0.284 23.8 5.7 4.6 0.81 1.69 7.4 3.37 Operation Not Recommended

0.378 39.8 5.9 4.7 0.80 1.66 7.6 3.55

Rev: 03/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

See Performance Correction Tables for operating conditions other than those listed above.

Data table does not reflect ISO pump or fan corrections.

Page 6: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAGCH/V 030B

401 l/s Nominal Airflow Performance capacities shown in kW

EWT °CWaterFlow WPD

COOLING - EAT 27/19°C HEATING - EAT 20°C

l/s kPA TCkW

SCkW

Sens/TotRatio

PowerkW

HRkW

EERW/W

HCkW

PowerkW

HEkW

LAT°C

COPW/W

0.240 10.8 7.3 5.7 0.78 1.64 8.9 4.45 8.0 1.81 6.2 36.5 4.42

15 0.353 19.4 7.4 5.8 0.78 1.57 9.0 4.71 8.2 1.83 6.4 36.9 4.48

0.473 30.2 7.4 5.8 0.78 1.53 8.9 4.84 8.3 1.84 6.5 37.1 4.51

0.240 10.5 7.1 5.6 0.79 1.75 8.9 4.06 8.4 1.85 6.6 37.3 4.54

20 0.353 18.7 7.3 5.7 0.78 1.66 9.0 4.40 8.6 1.86 6.7 37.8 4.62

0.473 29.2 7.3 5.7 0.78 1.62 8.9 4.51 8.7 1.87 6.8 38.0 4.65

0.240 10.3 6.9 5.5 0.80 1.88 8.8 3.67 8.8 1.88 6.9 38.2 4.68

25 0.353 18.3 7.1 5.6 0.79 1.79 8.9 3.97 9.0 1.90 7.1 38.6 4.74

0.473 28.4 7.1 5.7 0.80 1.75 8.9 4.06 9.1 1.91 7.2 38.8 4.76

0.240 9.9 6.6 5.4 0.82 2.00 8.6 3.30 9.2 1.92 7.3 39.0 4.79

30 0.353 17.9 6.8 5.5 0.81 1.91 8.7 3.56 9.4 1.94 7.5 39.4 4.85

0.473 27.7 6.9 5.5 0.80 1.87 8.8 3.69 9.5 1.95 7.6 39.6 4.87

0.240 9.7 6.2 5.2 0.84 2.11 8.3 2.94

35 0.353 17.4 6.4 5.3 0.83 2.04 8.4 3.14 Operation Not Recommended

0.473 26.9 6.6 5.4 0.82 2.00 8.6 3.30

Rev: 03/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

See Performance Correction Tables for operating conditions other than those listed above.

Data table does not reflect ISO pump or fan corrections.

Page 7: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAGCH/V 036B

472 l/s Nominal Airflow Performance capacities shown in kW

EWT °CWaterFlow WPD

COOLING - EAT 27/19°C HEATING - EAT 20°C

l/s kPA TCkW

SCkW

Sens/TotRatio

PowerkW

HRkW

EERW/W

HCkW

PowerkW

HEkW

LAT°C

COPW/W

0.284 12.3 9.6 7.2 0.75 2.24 11.8 4.29 10.0 2.41 7.6 37.6 4.15

15 0.429 22.1 9.8 7.2 0.73 2.12 11.9 4.62 10.6 2.48 8.1 38.6 4.27

0.567 35.2 9.9 7.3 0.74 2.05 12.0 4.83 10.9 2.52 8.4 39.1 4.33

0.284 11.8 9.3 7.1 0.76 2.38 11.7 3.91 11.0 2.52 8.5 39.3 4.37

20 0.429 21.6 9.6 7.2 0.75 2.26 11.9 4.25 11.6 2.60 9.0 40.4 4.46

0.567 34.0 9.7 7.2 0.74 2.19 11.9 4.43 11.8 2.63 9.2 40.7 4.49

0.284 11.5 8.8 6.9 0.78 2.53 11.3 3.48 11.9 2.65 9.3 40.9 4.49

25 0.429 21.1 9.2 7.1 0.77 2.42 11.6 3.80 12.4 2.72 9.7 41.8 4.56

0.567 33.1 9.4 7.1 0.76 2.35 11.8 4.00 12.6 2.74 9.9 42.1 4.60

0.284 11.3 8.3 6.7 0.81 2.67 11.0 3.11 12.7 2.75 10.0 42.3 4.62

30 0.429 20.6 8.7 6.9 0.79 2.57 11.3 3.39 13.1 2.81 10.3 43.0 4.66

0.567 32.4 8.9 7.0 0.79 2.51 11.4 3.55 13.2 2.84 10.4 43.2 4.65

0.284 10.9 7.6 6.3 0.83 2.81 10.4 2.70

35 0.429 20.1 8.1 6.6 0.81 2.72 10.8 2.98 Operation Not Recommended

0.567 31.4 8.3 6.7 0.81 2.66 11.0 3.12

Rev: 03/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

See Performance Correction Tables for operating conditions other than those listed above.

Data table does not reflect ISO pump or fan corrections.

Page 8: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAGCV 041B

543 l/s Nominal Airflow Performance capacities shown in kW

EWT °CWaterFlow WPD

COOLING - EAT 27/19°C HEATING - EAT 20°C

l/s kPA TCkW

SCkW

Sens/TotRatio

PowerkW

HRkW

EERW/W

HCkW

PowerkW

HEkW

LAT°C

COPW/W

0.335 6.6 10.1 7.8 0.77 2.28 12.4 4.43 11.0 2.63 8.4 36.8 4.18

15 0.498 15.2 10.2 7.8 0.76 2.19 12.4 4.66 11.4 2.69 8.7 37.4 4.24

0.662 27.8 10.3 7.8 0.76 2.15 12.5 4.79 11.6 2.72 8.9 37.7 4.26

0.335 6.4 9.9 7.8 0.79 2.42 12.3 4.09 11.7 2.74 9.0 37.9 4.27

20 0.498 15.0 10.0 7.8 0.78 2.31 12.3 4.33 12.1 2.79 9.3 38.5 4.34

0.662 26.8 10.1 7.8 0.77 2.26 12.4 4.47 12.3 2.82 9.5 38.8 4.36

0.335 6.3 9.7 7.7 0.79 2.60 12.3 3.73 12.4 2.84 9.6 38.9 4.37

25 0.498 14.5 9.8 7.8 0.80 2.47 12.3 3.97 12.8 2.89 9.9 39.5 4.43

0.662 26.2 9.9 7.8 0.79 2.41 12.3 4.11 12.9 2.91 10.0 39.7 4.43

0.335 6.0 9.3 7.4 0.80 2.77 12.1 3.36 13.0 2.93 10.1 39.8 4.44

30 0.498 14.3 9.6 7.6 0.79 2.65 12.3 3.62 13.3 2.97 10.3 40.3 4.48

0.662 25.6 9.7 7.7 0.79 2.59 12.3 3.75 13.5 2.99 10.5 40.6 4.52

0.335 5.9 8.7 7.1 0.82 2.94 11.6 2.96

35 0.498 14.0 9.1 7.3 0.80 2.83 11.9 3.22 Operation Not Recommended

0.662 24.9 9.3 7.4 0.80 2.77 12.1 3.36

Rev: 03/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

See Performance Correction Tables for operating conditions other than those listed above.

Data table does not reflect ISO pump or fan corrections.

Page 9: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAGCH/V 042B

566 l/s Nominal Airflow Performance capacities shown in kW

EWT °CWaterFlow WPD

COOLING - EAT 27/19°C HEATING - EAT 20°C

l/s kPA TCkW

SCkW

Sens/TotRatio

PowerkW

HRkW

EERW/W

HCkW

PowerkW

HEkW

LAT°C

COPW/W

0.335 7.2 10.9 8.3 0.76 2.48 13.4 4.40 12.0 2.85 9.2 37.6 4.21

15 0.505 18.6 11.0 8.3 0.75 2.37 13.4 4.64 12.5 2.93 9.6 38.3 4.27

0.694 38.0 11.1 8.3 0.75 2.33 13.4 4.76 12.8 2.98 9.8 38.7 4.30

0.335 7.0 10.7 8.3 0.78 2.65 13.4 4.04 12.9 2.99 9.9 38.9 4.31

20 0.505 18.1 10.9 8.3 0.76 2.51 13.4 4.34 13.4 3.07 10.3 39.6 4.36

0.694 36.8 10.9 8.3 0.76 2.45 13.4 4.45 13.7 3.10 10.6 40.0 4.42

0.335 6.7 10.4 8.1 0.78 2.86 13.3 3.64 13.8 3.12 10.7 40.2 4.42

25 0.505 17.5 10.6 8.3 0.78 2.70 13.3 3.93 14.3 3.20 11.1 40.9 4.47

0.694 35.8 10.7 8.3 0.78 2.62 13.3 4.08 14.5 3.23 11.3 41.2 4.49

0.335 6.6 9.9 7.9 0.80 3.07 13.0 3.22 14.6 3.23 11.4 41.4 4.52

30 0.505 17.3 10.3 8.1 0.79 2.92 13.2 3.53 15.1 3.29 11.8 42.1 4.59

0.694 35.2 10.4 8.2 0.79 2.83 13.2 3.67 15.3 3.32 12.0 42.4 4.61

0.335 6.4 9.2 7.5 0.82 3.25 12.5 2.83

35 0.505 16.8 9.7 7.9 0.81 3.13 12.8 3.10 Operation Not Recommended

0.694 34.2 10.0 8.0 0.80 3.05 13.1 3.28

Rev: 03/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

See Performance Correction Tables for operating conditions other than those listed above.

Data table does not reflect ISO pump or fan corrections.

Page 10: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAGCH/V 048B

649 l/s Nominal Airflow Performance capacities shown in kW

EWT °CWaterFlow WPD

COOLING - EAT 27/19°C HEATING - EAT 20°C

l/s kPA TCkW

SCkW

Sens/TotRatio

PowerkW

HRkW

EERW/W

HCkW

PowerkW

HEkW

LAT°C

COPW/W

0.379 8.7 12.7 9.6 0.76 3.01 15.7 4.22 13.3 3.03 10.3 37.0 4.39

15 0.568 20.0 12.8 9.7 0.76 2.85 15.7 4.49 14.0 3.11 10.9 37.9 4.50

0.757 36.7 12.9 9.7 0.75 2.78 15.7 4.64 14.3 3.15 11.2 38.3 4.54

0.379 8.5 12.4 9.5 0.77 3.20 15.6 3.88 14.4 3.16 11.2 38.4 4.56

20 0.568 19.6 12.6 9.6 0.76 3.03 15.6 4.16 15.0 3.23 11.8 39.1 4.64

0.757 35.6 12.7 9.6 0.76 2.95 15.7 4.31 15.4 3.26 12.1 39.7 4.72

0.379 8.2 11.9 9.4 0.79 3.41 15.3 3.49 15.5 3.28 12.2 39.8 4.73

25 0.568 19.0 12.3 9.5 0.77 3.24 15.5 3.80 16.1 3.35 12.8 40.6 4.81

0.757 34.6 12.4 9.5 0.77 3.16 15.6 3.92 16.4 3.38 13.0 40.9 4.85

0.379 8.0 11.3 9.1 0.81 3.61 14.9 3.13 16.4 3.38 13.0 40.9 4.85

30 0.568 18.5 11.8 9.3 0.79 3.46 15.3 3.41 16.9 3.44 13.5 41.6 4.91

0.757 33.7 12.0 9.4 0.78 3.38 15.4 3.55 17.2 3.46 13.7 42.0 4.97

0.379 7.8 10.5 8.8 0.84 3.79 14.3 2.77

35 0.568 18.0 11.1 9.1 0.82 3.66 14.8 3.03 Operation Not Recommended

0.757 32.7 11.4 9.2 0.81 3.59 15.0 3.18

Rev: 03/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

See Performance Correction Tables for operating conditions other than those listed above.

Data table does not reflect ISO pump or fan corrections.

Page 11: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATAGCH/V 060B

779 l/s Nominal Airflow Performance capacities shown in kW

EWT °CWaterFlow WPD

COOLING - EAT 27/19°C HEATING - EAT 20°C

l/s kPA TCkW

SCkW

Sens/TotRatio

PowerkW

HRkW

EERW/W

HCkW

PowerkW

HEkW

LAT°C

COPW/W

0.474 30.3 15.3 11.3 0.74 3.58 18.9 4.27 16.1 4.11 12.0 37.1 3.92

15 0.713 52.3 15.4 11.6 0.75 3.42 18.8 4.50 17.3 4.23 13.1 38.4 4.09

0.946 79.7 15.5 11.6 0.75 3.34 18.8 4.64 17.8 4.30 13.5 38.9 4.14

0.474 29.3 14.9 11.5 0.77 3.78 18.7 3.94 18.1 4.32 13.8 39.3 4.19

20 0.713 50.9 15.2 11.6 0.76 3.61 18.8 4.21 19.2 4.44 14.8 40.4 4.32

0.946 77.1 15.3 11.6 0.76 3.53 18.8 4.33 19.8 4.50 15.3 41.1 4.40

0.474 28.4 14.5 11.4 0.79 4.04 18.5 3.59 20.0 4.53 15.5 41.3 4.42

25 0.713 49.5 14.8 11.5 0.78 3.85 18.7 3.84 21.0 4.64 16.4 42.3 4.53

0.946 75.2 15.0 11.6 0.77 3.76 18.8 3.99 21.5 4.69 16.8 42.9 4.58

0.474 27.8 13.9 11.2 0.81 4.32 18.2 3.22 21.6 4.71 16.9 43.0 4.59

30 0.713 48.3 14.3 11.4 0.80 4.11 18.4 3.48 22.4 4.79 17.6 43.8 4.68

0.946 73.3 14.5 11.5 0.79 4.01 18.5 3.62 22.8 4.83 18.0 44.3 4.72

0.474 26.9 13.1 10.9 0.83 4.63 17.7 2.83

35 0.713 47.0 13.7 11.2 0.82 4.41 18.1 3.11 Operation Not Recommended

0.946 71.2 14.0 11.3 0.81 4.30 18.3 3.26

Rev: 03/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

See Performance Correction Tables for operating conditions other than those listed above.

Data table does not reflect ISO pump or fan corrections.

Page 12: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PERFORMANCE DATACORRECTION TABLES

Air Flow Correction Table

Entering Air Correction Table

Airflow

% ofNominal Htg Cap Power Heat of

Ext Total Cap Sens Cap Power Heat of Rej

75% 0.966 1.051 0.939 0.970 0.899 0.953 0.967

81% 0.976 1.037 0.956 0.979 0.924 0.966 0.976

88% 0.985 1.023 0.973 0.987 0.949 0.979 0.985

94% 0.993 1.012 0.987 0.994 0.975 0.990 0.993

100% 1.000 1.000 1.000 1.000 1.000 1.000 1.000

106% 1.006 0.991 1.010 1.005 1.026 1.008 1.005

113% 1.011 0.982 1.020 1.009 1.051 1.016 1.010

119% 1.014 0.975 1.027 1.011 1.077 1.022 1.013

125% 1.017 0.968 1.033 1.013 1.102 1.027 1.016

Rev: 06/12/01 B

Heating Cooling

Heating Corrections Cooling Corrections

Sens Clg Cap Multiplier - Entering DB °FEnt Air DB

°CHtg Cap Power Heat of

ExtEnt AirWB °C

Total ClgCap 21 23 25 27 29.5 32 35

Power Heat ofRej

15 1.026 0.935 1.054 15 0.855 0.810 0.948 1.095 1.190 * * * 0.983 0.880

17 1.016 0.962 1.032 17 0.928 0.681 0.836 0.983 1.095 * * * 0.989 0.939

20 1.000 1.000 1.000 19 1.000 0.552 0.707 0.853 1.000 1.147 * * 1.000 1.000

22 0.984 1.025 0.972 21 1.059 0.052 0.422 0.690 0.853 1.026 1.164 1.328 1.006 1.049

24 0.969 1.050 0.944 23 1.105 0.371 0.664 0.845 1.017 1.207 1.006 1.086

26 0.953 1.072 0.917 25 1.125 0.233 0.586 0.776 0.966 1.155 1.008 1.103

Rev: 08/08/02 B

* Sensible capacity equals total capacity

Page 13: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

BLOWER PERFORMANCE DATA

Airflow in l/s with dry coil and clean air filter.

Model Rated Min Fan

l/s l/s Speed 0 25 50 75 100 125 150 175 200 225 250 275 300 325

HI 297 274 255 222 165

H/V 018 236 175 MED 302 288 269 245 222 170

LOW 288 274 255 236 175

HI 378 345 283 241

H/V 024 319 235 MED 439 420 392 359 326 274 222

LOW 378 363 340 321 245 236

HI 505 463 420 378 312

H/V 030 401 305 MED 543 510 467 425 382 316

LOW 514 491 448 411 312

HI 609 585 543 500 453 368

H/V 036 472 355 MED 500 486 463 439 406 340

LOW 467 453 430 411 411

HI 534 517 500 470 431 397 342

V041 543 378 MED 487 474 461 440 406 371

LOW 418 406 397 380 359

HI 694 670 647 618 585 548 505 467

H/V 042 566 425 MED 647 628 604 581 548 519 486 439

LOW 505 500 496 486 467

HI 812 765 713 632 543

H/V 048 649 495 MED 807 769 741 694 609

LOW 784 765 746 732 694 642 590

HI 953 949 935 902 873 854 831 798 760 703

H/V 060 779 590 MED 902 887 864 840 821 793 774 741 703 637

LOW 826 817 802 788 769 741 708 670 604

Gray areas denote ESP where operation is not recommended Rev.: 08/09/02 B

Units factory shipped on medium speed. Other speeds require field selection.

All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 200V for 200-220V units.

All units ARI/ISO/ASHRAE 13256-1 rated on high fan speed.

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [mpm] = Airflow [l/s]/1000 / Face Area [m2]).

Then for velocities of 61 m per min reduce the static capability by 7.5 Pa, 91 m per min by 20 Pa, 121 m per min by 30 Pa.

and 150 m per min by 40 Pa.

External Static Pressure (Pa)

Page 14: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

PHYSICAL DATA

y

Model H/V 018 H/V 024 H/V 030 H/V 036 V041 H/V 042 H/V 048 H/V 060

Compressor (1 each) Recip Recip Recip Recip Recip Recip Recip Scroll

Factory R22 Charge Vertical, oz [kg] 26 [0.74] 38 [1.08] 37 [1.05] 42 [1.19] 50 [1.42] 51 [1.45] 66 [1.87] 74 [2.10]

Factory R22 Charge Horizontal - oz. [kg] 25 [0.71] 38 [1.08] 37 [1.05] 41 [1.16] 50 [1.42] 51 [1.45] 66 [1.87] 74 [2.10]

PSC Fan Motor & Blower

Fan Motor Type/Speeds PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3

Fan Motor - hp [W] 1/6 [124] 1/4 [187] 3/4 [560] 1/2 [373] 3/4 [560] 3/4 [560] 3/4 [560] 1 [746]

Blower Wheel Size (Dia x W) - in. [cm] 8 x 7[20.3x17.8]

9 x 7[22.9x17.8]

9 x 7[22.9x17.8] 9 x 8 [22.9x20.3] 9 x 8 [22.9x20.3] 9 x 8 [22.9x20.3] 10 x 10

[25.4x25.4] 11 x 10 [27.9x25.4]

Water Connection Size

FPT - American Std Pipe thread - in. [mm] 1/2 [12.7] 3/4 [19.1] 3/4 [19.1] 3/4 [19.1] 3/4 [19.1] 3/4 [19.1] 1 [25.4] 1 [25.4]

Horizontal

Air Coil Dimensions (H x W) - in. [cm] 16 x 22[40.6x55.9]

16 x 22[40.6x55.9]

16 x 22[40.6x55.9]

20 x 25[50.8x63.5] - 20 x 25

[50.8x63.5]20 x 35

[50.8x88.9] 20 x 35 [50.8x88.9]

Air Coil Total Face Area - ft2 [m2] 2.44 [0.227] 2.44 [0.227] 2.44 [0.227] 3.47 [0.323] - 3.47 [0.323] 4.86 [0.452] 4.86 [0.452]

Air Coil Tube Diam - in. [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] - 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]

Air Coil Distance between fins, in. [mm] 0.083 [2.1] 0.083 [2.1] 0.083 [2.1] 0.077 [2.0] - 0.083 [2.1] 0.083 [2.1] 0.083 [2.1]

Air Coil Number of rows 2 3 3 2 - 3 3 3

Filter Standard - 1" [25.4mm] Throwaway -in. [cm] 16 x 25 16 x 25 16 x 25 1 - 20x28 or

2 - 20x14 - 1 - 20x28 or2 - 20x14

1 - 20x24 &1 - 20x14

1 - 20x24 &1 - 20x14

[40.6x63.5] [40.6x63.5] [40.6x63.5] [1 - 50.8x71.1 or2 - 50.8x35.6] - [1 - 50.8x71.1 or 2

- 50.8x35.6][1 - 50.8x61.0 & 1 -

50.8x35.6][1 - 50.8x61.0 &

1 - 50.8x35.6]

Vertical

Air Coil Dimensions (H x W) - in. [cm] 20 x 17.25[50.8x43.8]

20 x 17.25[50.8x43.8]

20 x 17.25[50.8x43.8]

24 x 21.75[61.0x55.2]

20 x 17.25[50.8x43.8]

24 x 21.75[61.0x55.2]

24 x 28.25[61.0x71.8]

24 x 28.25[61.0x71.8]

Air Coil Total Face Area - ft2 [m2] 2.40 [0.223] 2.40 [0.223] 2.40 [0.223] 3.62 [0.337] 2.40 [0.223] 3.62 [0.337] 4.71 [0.438] 4.71 [0.438]

Air Coil Tube Diam - in. [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]

Air Coil Distance between fins, in. [mm] 0.083 [2.1] 0.083 [2.1] 0.083 [2.1] 0.077 [2.0] 0.091 [2.3] 0.083 [2.1] 0.083 [2.1] 0.083 [2.1]

Air Coil Number of rows 2 3 3 2 4 3 3 3

Filter Standard - 1" [25.4mm] Throwaway -in. [cm] 20 x 20 20 x 20 20 x 20 24 x 24 20 x 20 24 x 24 1 - 14x24 &

1 - 18x241 - 14x24 &

1 - 18x24

[50.8x50.8] [50.8x50.8] [50.8x50.8] [61.0x61.0] [50.8x50.8] [61.0x61.0] [1 - 35.6x61.0 &1 - 45.7x61.0]

[1 - 35.6x61.0 &1 - 45.7x61.0]

Weight - Operating - lbs. [kg] 181 [82.1] 189 [85.7] 197 [89.4] 203 [92.1] 207 [93.9] 218 [98.9] 263 [119.2] 278 [126.1]

Weight - Packaged - lbs. [kg] 186 [84.4] 194 [88.0] 202 [91.6] 209 [94.8] 212 [96.2] 224 [101.6] 270 [119.3] 285 [129.3]

Notes: Rev.: 07/18/02 B

"-" Data not available at time of printing

All units have grommet compressor mountings,and 1/2" & 3/4" electrical knockouts.

Check serial plate for refrigerant type (R22).

Page 15: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

HORIZONTAL DIMENSIONALDATA

F

Right Return Straight Discharge

Front

L N

O

M

LegendCAP=Control Access PanelCSP=Compressor Service PanelBSP=Blower Service PanelASP=Alternate Service Panel

Right Return

Front

StraightDischarge

CSP

BackDischarge

Condensate3 / 4” FPT

3.3

0.7

Front-View

E D

KJ 2

1

1.1

A

CAP

BSP

Right Return Right View -Air Coil Opening

Air Coil

C

TS

B

ASP R

Q

Front

L

N O

M

Left Return Straight Discharge

Front

BSP

LEFT RETURN RIGHT RETURN

Air Coil

CSP

Front

Left Return Left View -Air Coil Opening

1.75

C

T

R

QS

B

Unit Hanger Detail

U

V

Fro

nt

WModel U V W018-030 43.1 22.2 18.0036-042 47.1 22.2 18.0048-060 54.1 26.2 22.0

Right Return Back Discharge

A

Air

Coi

l Sid

e

C

PN

O

M

ASP CSP

BSP

2’ ServiceAccess

Front

Left Return

0.7

3.3

CSP

Condensate3 / 4” FPT

ASP

2’ ServiceAccess

Air

Coi

l Sid

e

M

A

C

Left Return Back Discharge

NO

P

BSP

Rev.: 08/09/01 B

BlowerOutlet

BlowerOutlet

BlowerOutlet

BlowerOutlet

Optional 2’ServiceAccess

Optional 2’ServiceAccess

G

H

Power Supply3 / 4” Knockout

1 / 2”Knockout

Low Voltage1 / 2” Knockout

3StraightDischarge

BackDischarge

Overall CabinetWater Connections Electrical Knockouts

Return ConnectionHorizontal 1 - In 2 - Out H J K using return air opening

Model A B C D E F G 1/2" cond 1/2" cond 3/4" cond L M N O P Q R S T

Width Depth Height LowVoltage

LowVoltage

PowerSupply

SupplyHeight

SupplyDepth

ReturnDepth

ReturnHeight

018-030 in. 20.1 43.1 17.1 15.3 2.4 1.9 2.1 12.1 9.1 6.1 2.6 13.3 9.9 4.1 1.3 23.0 15.0 1.1 1.0

cm. 51.1 109.5 43.4 38.9 6.1 4.9 5.3 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 38.1 2.8 2.5

036-042 in. 20.1 47.1 21.1 18.8 2.2 4.7 1.2 16.1 13.1 10.1 2.5 16.1 11.0 3.0 2.5 25.9 19.0 1.1 1.0

cm. 51.1 119.6 53.6 47.6 5.5 11.9 3.0 41.0 33.3 25.7 6.3 40.9 27.9 7.7 6.4 65.8 48.3 2.8 2.5

048 in. 24.1 54.1 21.1 19.4 5.9 4.3 2.3 16.1 13.1 10.1 3.7 16.1 13.7 4.1 1.3 35.9 19.0 1.1 1.0

cm. 61.2 137.4 53.6 49.2 14.9 11.0 5.8 41.0 33.3 25.7 9.5 41.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5

060 in. 24.1 54.1 21.1 19.4 5.9 4.3 2.3 16.1 13.1 10.1 1.7 18.1 13.7 4.1 1.3 35.9 19.0 1.1 1.0

cm. 61.2 137.4 53.6 49.2 14.9 11.0 5.8 41.0 33.3 25.7 4.4 46.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5

Condensate is 3/4" FPT copper. Rev.: 08/09/01 B

Horizontal unit shipped with filter bracket only. This bracket should be removed for return duct connection.Hanger kit is factory installed

Verify high static option discharge connection dimensions with ClimateMaster

duct flange (± 0.10 in)

Discharge Connections

Page 16: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

VERTICAL DIMENSIONAL DATA

Access Panels

Top View-Left ReturnTop View-Right Return

U

RSIsometric

View

Left Return Left View- Air Coil Opening

T

CPower Supply

3/4” (19.1 mm) HVKnockout

Low Voltage1/2” (12.7 mm) LV

KnockoutLow Voltage

1/2” (12.7 mm) LVKnockout

Condensate 3/4”(19.1 mm) FPT

Front-View

K

1.00 [25.4 mm]

F

JH

D

L

Air Coil

Field InstalledDischarge Flange

FrontBack

U

R S

T

C

BackFront

Right Return Right View- Air Coil Opening

BSP

CAP

Standard Filter Bracket

ASP

Air Coil

Front

P N

O

Q

Fro

nt

2’ (61cm)Service

Access *Left Rtn(Right RtnOpposite

Side)

NB

P

A

O

M

2’ (61cm)Service

3

2

1

E

I

G

LegendCAP=Control Access PanelCSP=Compressor Service PanelBSP=Blower Service PanelASP=Alternate Service Panel

CSP

CAP

CSPCSP

CSP

Air Coil

Air Coil SideAir Coil Side

Rev.: 05/07/02 B

* Note: Shaded areas are recommended service areas, not required.

BSP

Vertical Overall CabinetWater Connections Electrical Knockouts

Discharge Connection Return Connection

Upflow 1 2 Water J K L using return air opening

Model A B C D E F G H I FPT 1/2" cond 1/2" cond 3/4" cond M N O P Q R S T U

Width Depth HeightSize

LowVoltage

LowVoltage

PowerSupply

SupplyWidth

SupplyDepth

ReturnDepth

ReturnHeight

018-030 in. 21.5 21.5 39.0 1.8 3.8 15.2 3.6 8.1 2.3 3/4" 4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.2 0.7

cm. 54.6 54.6 99.1 4.5 9.7 38.6 9.1 20.6 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 51.3 1.9

036 & 042 in. 21.5 26.0 44.0 2.0 3.7 16.2 2.6 10.4 2.3 3/4" 4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.1 2.3 22.8 24.2 0.7

cm. 54.6 66.0 111.8 5.1 9.4 41.1 6.6 26.4 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.1 5.8 57.9 61.4 1.9

041 in. 21.5 21.5 39.0 1.7 3.6 16.4 2.6 8.1 2.3 3/4" 4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.2 0.7

cm. 54.6 54.6 99.1 4.4 9.1 41.7 6.6 20.6 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 51.3 1.9

048-060 in. 24.0 32.5 46.0 1.8 5.9 16.7 2.3 10.1 2.3 1" 4.1 7.1 10.1 6.9 7.3 16.0 18.0 5.1 2.3 29.3 24.2 0.7

cm. 61.0 82.6 116.8 4.5 14.9 42.4 5.8 25.7 5.8 2.5 10.5 18.1 25.7 17.4 18.4 40.6 45.7 13.1 5.8 74.4 61.4 1.9

Rev.: 05/13/02 B

Condensate is 3/4" ( 19.1 mm) FPTFilter bracket extending from unit 2.5" (6.4 cm). This bracket should be removed when connecting return duct.Discharge flange field installed

duct flange installed (±0.10 in)

In Out

3

Condensate

Page 17: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

UNIT ELECTRICAL DATA

Voltage Rated Voltage Compressor Fan Total Min Max

Model Code Voltage Min/Max Motor Unit Circ Fuse/

Qty RLA LRA FLA FLA Amp HACR

V/H018 V 220-240/50/1 197/254 1 8.1 44.0 0.86 8.9 11.0 15

V/H024 V 220-240/50/1 197/254 1 9.1 55.0 1.30 10.4 12.7 20

U 380-420/50/3 342/462 1 3.5 25.0 0.76 4.2 5.1 15

V/H030 V 220-240/50/1 197/254 1 10.0 58.0 2.70 12.7 15.2 25

U 380-420/50/3 342/462 1 3.6 28.0 1.70 5.3 6.2 15

V/H036 V 220-240/50/1 197/254 1 14.4 83.0 2.00 16.4 20.0 30

U 380-420/50/3 342/462 1 4.9 33.0 1.24 6.1 7.4 15

V041 U 380-420/50/3 342/462 1 4.3 40.0 1.70 6.0 7.1 15

V/H042 U 380-420/50/3 342/462 1 5.3 42.0 1.70 7.0 8.3 15

V/H048 U 380-420/50/3 342/462 1 5.7 42.0 1.80 7.5 8.9 15

V/H060 U 380-420/50/3 342/462 1 7.4 59.6 2.50 9.9 11.8 15

HACR circuit breaker in USA only Rev:. 06/22/02 BAll fuses Class RK-5

Page 18: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

TYPICAL WIRING DIAGRAMSINGLE PHASE WIRING DIAGRAMGC UNITS WITHCXM CONTROLLER

GC, GR, GSH/V006-070 Commercial with CXM208-230/60/1, 265/60/1 & 220-240/50/1 96B0006N01 Rev H 6/8/01

Page 19: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

TYPICAL WIRING DIAGRAMTHREE PHASE WIRING DIAGRAMGC UNITS WITHCXM CONTROLLER(460/575 Volt)

GC, GR, GSH/V024-070 Commercial with CXM460/60/3, 575/60/3, & 380-420/60/3 96B0008N01 Rev. F 5/7/01

Page 20: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

TYPICAL WIRING DIAGRAMSINGLE PHASE WIRING DIAGRAMGC UNITS WITHDXM CONTROLLER

GC, GR, GSH/V006-070 Commercial with DXM208-230/60/1, 265/60/1 & 220-240/50/1 96B0006N02 Rev. F 6/8/01

Page 21: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

TYPICAL WIRING DIAGRAMTHREE PHASE WIRING DIAGRAMGC UNITS WITH DXM CONTROLLER (460/575 volt)

GC, GR, GSH/V024-070 Commercial with DXM460/60/3, 575/60/3, & 380-420/60/3 96B0008N02 Rev. E 5/7/01

Page 22: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

GeneralFurnish and install ClimateMaster Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired.Capacities and characteristics as listed in the schedule and the specifications that follow.

Horizontal/Vertical Water Source Heat Pumps:Units shall be supplied completely factory built and capable of operation with an entering water temperature range from 60° to 95°F (15.6° to 35.0°C) asstandard. Equivalent units from other manufacturers can be proposed provided approval to bid is given 10 days prior to bid closing. All equipment listed in thissection must be rated and certified in accordance with ARI/ISO/ASHRAE, NRTL, CSA or optional CE Mark. The units shall have ARI/ISO, NRTL, CSA oroptional CE Mark labels. All units shall be factory run tested under normal operating conditions at nominal water flow rates. This testing shall generate a reportcard to be shipped with each unit stating performance in both heating and cooling modes. Serial numbers will be recorded by factory and furnished tocontractor for ease of unit warranty status. Units tested without water flow ARE NOT acceptable.

Basic ConstructionHorizontal Units shall have one of the following air flow arrangements: Right-Discharge/Left-Inlet; Left-Discharge/Right-Inlet; Back-Discharge/Left-Inlet; orBack-Discharge/Right-Inlet as shown on the plans. Units must have the ability to be field convertible from side to back or back to side discharge with noadditional parts or unit structure modification. Units will have factory installed hanger brackets and isolation grommets.

Vertical Units shall have one of the following air flow arrangements: Right-Return/Top-Discharge or Left-Return/Top-Discharge as shown on the plans. Unitswill have factory-installed internal condensate trap.

If units with these arrangements ARE NOT used, the contractor is responsible for any extra costs incurred by other trades. All units must have a minimum oftwo access panels for serviceability of compressor compartment. If other arrangements make servicing difficult, the contractor must provide access panelsand clear routes to ease service. Architect must approve any changes in layout.

The horizontal heat pumps shall be fabricated from heavy gauge galvanized sheet metal. All interior surfaces shall be lined with 1/2 inch thick (12mm), 1-1/2lb/ft3 (24kg/m3) density acoustic type glass fiber insulation. All fiberglass shall be coated and have exposed edges tucked under flanges to prevent theintroduction of glass fibers into the air stream. All insulation must meet NFPA 90A.

The vertical heat pumps shall be fabricated from heavy gauge galvanized sheet metal. All interior surfaces shall be lined with 1/2 inch thick (12mm), 1-1/2 lb/ft3 (24kg/m3) density acoustic type glass fiber insulation. All fiberglass shall be coated and have exposed edges tucked under flanges to prevent theintroduction of glass fibers into the air stream. All insulation must meet NFPA 90A. All vertical heat pumps shall have a powder coat paint finish. The colorshall be polar ice.

Option: Mute package shall consist of sound attenuating materials that are strategically applied to the cabinet, and will consist of 1" (25.4mm) fiberglassinsulation that is specifically selected to focus on Noise Reduction at the lower 125 and 250 Hz frequencies. All surfaces that normally have 0.5" (12.7mm)insulation would be substituted the noise dampening 1" (25.4mm) insulation.

All units must have an insulated panel separating the fan compartment from the compressor compartment. Units with the compressor in the air streamARE NOT acceptable. Units shall have a factory installed 1 inch wide filter bracket for filter removal from either side. Units shall have a 1 inch (25.4mm)thick throwaway type glass fiber filter. The contractor shall purchase one spare set of filters and replace factory shipped filters on completion of start-up.Filters shall be standard sizes. If units utilize non-standard filter sizes then the contractor shall provide 12 spare filters for each unit.

Option: Contractor shall install 2 inch (50.8mm) filter brackets and 2 inch (50.8mm) glass fiber throwaway filters on all units.

Cabinets shall have separate openings and knockouts for entrance of line voltage and low voltage control wiring. Supply and return water connections shall becopper FPT fittings. All water connections and electrical knockouts must be in the compressor compartment corner post as to not interfere with theserviceability of unit. Contractor shall be responsible for any extra costs involved in the installation of units that do not have this feature. Contractor must ensurethat units can be easily removed for servicing and coordinate locations of electrical conduit and lights with the electrical contractor.

Fan and Motor AssemblyUnits rated 60,000 BTUH and under shall have a direct-drive centrifugal fan. The fan motor shall be 3-speed (2 speed 575V), permanently lubricated, PSCtype with internal thermal overload protection. Blower shall have inlet rings to allow removal of wheel and motor from one side without removing housing. Unitssupplied without permanently lubricated motors must provide external oilers for easy service. The fan motor shall be isolated from the fan housing by torsionallyflexible isolation grommets. The fan and motor assembly must be capable of overcoming the external static pressures as shown on the schedule. CFM/Staticpressure rating of the unit shall be based on a dry coil and a clean filter in place.

Option: High static motors available for sizes 018 through 060 (except GCV041).

Refrigerant CircuitUnits shall have a sealed refrigerant circuit including a high efficient rotary or reciprocating compressor designed for heat pump operation, a capillary tubeassembly for refrigerant metering, an enhanced aluminum lanced fin and rifled copper tube refrigerant to air heat exchanger, a reversing valve, a coaxial (tubein tube) refrigerant to water heat exchanger, and safety controls including a high pressure switch, a low pressure sensor, and a low water temperature sensor.

GENESIS COMPACT (GC) SERIESENGINEERING GUIDESPECIFICATIONSRevision: 08/08/02 B

Page 23: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

Access fittings shall be factory installed on high and low pressure refrigerant lines to facilitate field service. Activation of any safety device shall preventcompressor operation via a lockout device. The lockout shall be reset at the thermostat or at the contractor supplied disconnect switch. Units which may bereset only at the disconnect switch only SHALL NOT be acceptable.

Hermetic reciprocating compressors shall be internally sprung. The compressor will be mounted on external computer selected isolating grommets. Theexternal grommets will be secured to a heavy gauge compressor plate that has rubber grommet isolation from the cabinet base, which provides multiplelevels of isolation. Compressor shall have thermal overload protection and be located in an insulated compartment away from air stream to minimize soundtransmission. Refrigerant to air heat exchangers shall utilize enhanced lanced aluminum fins and rifled copper tube construction rated to withstand 450PSIG (3108 kPa) refrigerant working pressure. Refrigerant to water heat exchangers shall be of copper inner water tube and steel refrigerant outer tubedesign, rated to withstand 450 PSIG (3108 kPa) working refrigerant pressure and 450 PSIG (3108 kPa) working water pressure. Plate to plate heatexchangers ARE NOT acceptable.Reversing valves shall be four-way solenoid activated refrigerant valves which shall fail to heating operation should the solenoid fail to function. If the reversingvalve solenoid fails to cooling, a low temperature thermostat must be provided to prevent over-cooling an already cold room.

Option: The unit will be supplied with cupro-nickel coaxial water to refrigerant heat exchangers.

Drain PanThe drain pan shall be constructed to inhibit corrosion and fully insulated. Drain outlet shall be located on pan as to allow complete and unobstructed drainageof condensate. The unit as standard will be supplied with solid-state electronic condensate overflow protection. Mechanical float switches WILL NOT beaccepted.

ElectricalA control box shall be located within the unit compressor compartment and shall contain a 50VA transformer, 24 Volt activated, 2 or 3 pole compressorcontactor, terminal block for thermostat wiring and solid-state controller for complete unit operation. Electro-mechanical operation WILL NOT be accepted.Units shall be name-plated for use with time delay fuses or HACR circuit breakers. Unit controls shall be 24 Volt and provide heating or cooling as required bythe remote thermostat/sensor.Option: CE Mark Construction: To include power connection block, compressor grounding, fully insulated terminals and CE listed electrical components.

Solid-State Control SystemUnits shall have a solid-state control system (CXM). The control shall interface with a heat pump (Y,O) wall thermostat, mechanical or electronic. The controlsystem microprocessor board shall be specifically designed to protect against building electrical system noise contamination, EMI, and RFI interference. Thecontrol system shall have the following features:a. Anti-short cycle time delay on compressor operation, time delay shall be 5 minutes minimum.b. Random start on power up mode.c. Low voltage protection.d High voltage protection.e. Unit shutdown on high or low refrigerant pressures.f. Unit shutdown on low water temperature.g. Water coil low temperature cutout (selectable for water or anti-freeze).h. Condensate overflow shutdown.i. Option to reset unit at thermostat or disconnect. Fault type shall be retained in memory if reset at thermostat.j. Automatic intelligent reset. Unit shall automatically reset 5 minutes after trip if the fault has cleared. Should a fault re-occur 3 times sequentially then

permanent lockout will occur.k. Ability to defeat time delays for servicing.l. Light emitting diodes (LED) to indicate high pressure, low pressure, low voltage, high voltage, low water temperature cut-out, condensate overflow and

control status.m. The low pressure switch SHALL NOT be monitored for the first 120 seconds after a compressor start command to prevent nuisance safety trips.n. Remote fault type indication at thermostat.o. Selectable 24V or pilot duty dry contact alarm output.p. 24V output to cycle a motorized water valve with compressor contactor.

Option: Enhanced control features (DXM)Control shall have all the features of the CXM control with the following additional features:a. A removable thermostat connector.b. Random start on return from night setback.c. Minimized reversing valve operation for extended life and quiet operation.d. Night setback control from low temperature thermostat, with 2-hour override initiated by a momentary signal from the thermostat.e. Dry contact night setback output for digital night setback thermostats.f. Ability to work with heat/cool (Y, W) thermostats.

GENESIS COMPACT (GC) SERIESENGINEERING GUIDESPECIFICATIONS (cont.)Revision: 06/03/02 B

Page 24: GC Submittal Set - Climate Master 11.3 1650 50,450 13.3 63,852 4.5 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B Heating capacities

GC Submittal DataContractor: P.O.:

Engineer:

Project Name: Unit Tag:

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.

Page ______ of ______Rev.: 03/13/03

*LC279*LC279

g. Ability to work with heat pump thermostats using O or B reversing valve control.h. Single grounded wire to initiate night setback, or emergency shutdown.i. Boilerless system control can switch automatically to electric heat at low loop water temperature.j. Control board shall allow up to 3 units to be operated from one thermostat without any auxiliary controls.k. A relay to operate an external damper. The control to be such that the damper WILL NOT open until 30 minutes after the unit comes back from

unoccupied mode.l. Fan speed selection at thermostat.m. A relay to restart a central pump or control a 24V motorized water valve.n. Intelligent fan speed selection based upon thermostat demand and/or dehumidistat signal.

Option: LonWorks Control SystemUnits shall have all the features listed above and the control board will be supplied with a LonWorks interface board. This will permit all units to be daisy chainconnected by a 2-wire twisted pair shielded cable. The following points must be available at a central or remote computer location:a. space temperature.b. leaving water temperature.c. discharge air temperature.d. command of space temperature setpoint.e. cooling status.f. heating status.g. fan “ON/AUTO” position of space thermostat as specified above.h. unoccupied/occupied command.i. compressor shutdown (load shedding) command.j. emergency shutdown command.k. cooling command.l. heating command.m. fan “ON/AUTO” command.

Field Installed Options

Hose KitsAll units 120,000 BTUH (35 kW) and below shall be connected with hoses. The hoses shall be 2 feet (0.6m) long, braided stainless steel; fire rated hosescomplete with adapters. Only fire rated hoses will be accepted.

Thermostats

Electromechanical ThermostatsThermostats shall be single-stage manual change-over with HEAT-OFF-COOL system switch and fan ON-AUTO switch.

Electronic ThermostatsThermostat shall be single-stage, manual changeover with HEAT-OFF-COOL system switch and fan ON-AUTO switch. Thermostat shall have a LCD displaywith temperature and setpoint indication selectable for °F or °C. Thermostat shall only require 4 wires for connection.

Thermostat shall be single-stage, manual or automatic changeover with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Thermostatshall have a back-lit LCD display with temperature, setpoints, mode, and status indication. The temperature indication shall be selectable for °F or °C. ASystem Test feature shall be provided to simplify troubleshooting. The thermostat shall provide permanent memory of setpoints without batteries. A fault LEDshall be provided. Thermostat shall provide optional extended end of cycle fan operation, outdoor air temperature display, heating setpoint range limit, coolingsetpoint range limit, and temperaturedisplay offset.

Thermostat shall be multi-stage (3H/2C), manual or automatic change over with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings.Thermostat shall have an LCD display with temperature, set-points, mode, and status indication. The temperature indication shall be selectable for °F or °C. ASystem Test feature shall be provided to simplify troubleshooting. The thermostat shall provide permanent memory of setpoints without batteries. A fault LEDshall be provided. Thermostat shall provide optional extended end of cycle fan operation, heating setpoint range limit, cooling setpoint range limit, temperaturedisplay offset, temperature display disable, keypad lockout, dead-band range setting, and inter-stage differential settings. Thermostat shall provide capability toaverage from 1 to 9 remote sensors. Thermostat shall switch to selectable unoccupied setpoints upon signal from DXM control within unit. The thermostat shallrevert to occupied setpoints when the Override key is pressed.

Thermostat shall be 7 day programmable, multi-stage (3H/2C), manual or automatic change over with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, set-points, mode, and status indication. The temperature indication shall be selectablefor °F or °C. A System Test feature shall be provided to simplify troubleshooting. The thermostat shall provide permanent memory of setpoints and programwithout batteries. A fault LED shall be provided. Thermostat shall provide optional extended end of cycle fan operation, heating setpoint range limit, cooling set-point range limit, temperature display offset, temperature display disable, keypad lockout, dead-band range setting, and inter-stage differential settings.Thermostat shall provide capability to average from 1 to 9 remote sensors.

GENESIS COMPACT (GC) SERIESENGINEERING GUIDESPECIFICATIONS (cont.)Revision: 06/03/02 B


Recommended