+ All Categories
Home > Documents > GE Energy

GE Energy

Date post: 31-Dec-2015
Category:
Upload: idola-yang
View: 21 times
Download: 0 times
Share this document with a friend
Description:
GE Energy. Asia Development Bank Wind Energy Grid Integration Workshop: Wind Grid Codes. Nicholas W. Miller GE Energy Consulting Beijing September 22-23, 2013. Grid Code Development. Debate… Should wind generation be treated differently? - PowerPoint PPT Presentation
Popular Tags:
24
GE Energy Asia Development Bank Wind Energy Grid Integration Workshop: Wind Grid Codes Nicholas W. Miller GE Energy Consulting Beijing September 22-23, 2013
Transcript
Page 1: GE Energy

GE Energy

Asia Development BankWind Energy Grid Integration Workshop:

Wind Grid Codes

Nicholas W. Miller

GE Energy Consulting

BeijingSeptember 22-23, 2013

Page 2: GE Energy

2 /

Grid Code Development

Debate…

• Should wind generation be treated differently?

• What is the obligation of generation to provide voltage control?

• How should generation respond to system disturbances?

• How should generation prove it meets performance requirements?

These questions are still being debated in the industry today.

Page 3: GE Energy

3 /

US Grid Code Development

In the US, relationships between transmission system operators (TSO), generators and users of energy are governed by multiple entities:

• FERC (Federal Energy Regulatory Commission)• NERC (North American Reliability Council)• Regional Reliability Councils (e.g.:)

- WECC (Western Energy Coordinating Council)

- ERCOT (Electric Reliability Council of Texas)

• State Reliability Councils• State Regulators• Standards Organizations (ANSI/IEEE/NESC/NEC)• A similar Federal/Provincial structure applies in

Canada

Page 4: GE Energy

4 /

North American Grid Code Development In NA, rules are generally identified in terms of:

• Reliability Standards

• Interconnection Requirements• These interconnection requirements correspond

approximately to European Grid Codes

The objectives are:• To make sure generation and transmission is

efficient and reliable, and• To regulate rights and responsibilities of generators,

TSO’s and energy users.

Note: Interconnection Requirements for Wind Energy in the US are continuing to develop. Regulating groups (FERC) and Reliability groups (NERC) are debating terms of current grid codes.

Page 5: GE Energy

5 /

What consensus is emerging NA Grid Codes?• Reactive Power: +/- 0.95 pf @ POI

• Voltage Control: required, with ISO voltage setpoints

• Frequency Tolerance: +/- 3 hz continuous

• Voltage Tolerance (Low Voltage Ride-Through): ZVRT (FERC 661a), NERC PRC-024 up for ballot

• Models and Data: required cooperation

• Telemetry and Metering: specific minima

• Power Quality: IEEE 519 for Harmonics and Flicker

• Frequency Control: debate just starting

• Validation requirements: NERC MOD Standards up for ballot

• Plant Protection Coordination: NERC PRC-019 up for ballot

Page 6: GE Energy

6 /

Grid Code DevelopmentTight

More Expensive EquipmentReduced Efficiency

Loose Compromised System

Reliability

Grid Code Functional Specifications

Grid Codes should be no more specific than they need to be to avoid over-designed equipment and reduced efficiency of wind generation, but should be specific enough for adequate system

reliability.

Page 7: GE Energy

7 /

Global Renewable Codes & Standards DevelopmentCalifornia ISO Interconnection Requirements for Variable Energy Resources

ISO-NE Technical Requirements for Wind Interconnection & Integration

NERC Standards Drafting and Task Forces

— Integration of Variable Generation Task Force (IVGTF)

— Generator Verification Standards Drafting Team (GVSDT)

International

— Ontario IESO Amended Market Rules for Generation Facilities

— Chinese State Power Grid Technical Code for Wind Interconnection

— Indian CERC Electricity Grid Code for Wind

— German FGW Technical Guidelines for Wind Energy

— Australian Energy Market Operator (AEMO) Guidelines for Wind Energy

FERC now mandates that all new reliability standards address VER

Page 8: GE Energy

8 /

NERC GVSDT* standards currently in draft

MOD (Model Validation):

MOD-025: Verification of Generator/Plant Real & Reactive capability

MOD-026: Verification of Dynamic Models and Data for Generator Excitation Control and Plant Volt-Var Control Functions

MOD-027: Verification of Dynamic Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions

PRC (Protection & Control):

PRC-019: Coordination of Generating Unit/Plant Voltage Regulating Controls with Unit/Plant Capabilities and Protection

PRC-024: Generator Performance During Frequency and Voltage Excursions

* Generator Verification Standards Drafting Team

Applicability has been modified to include wind & large solar.

These drafts in various stages of being finalized.

Page 9: GE Energy

9 /

FAULT RIDE-THROUGHNERC PRC-024: Generator Performance During Frequency and Voltage ExcursionsRequirement 1: Frequency Ride-Through• Each Generator Owner (GO) shall:

– Set in service frequency protective relaying so that it does not operate to trip the generating unit during frequency excursions within the band described in Attachment 1

– Conditions and exceptions:– Must operate between 59.5 and 60.5 Hz continuous– May trip if rate of change >2.5 Hz/sec (Aurora exclusion)

Requirement 2: Voltage Ride-Through• Each Generator Owner (GO) shall:

– Set in service voltage protective relaying so that it does not operate to trip the generating unit during voltage excursions within the specified band

– Conditions and Exceptions:– Consider 3-phase Zone 1 faults with normal clearing– Site-specific clearing time may be used– Generator tripping for SPS, RAS or to clear the fault allowed

Page 10: GE Energy

10 /

NERC PRC-024: Frequency Ride-ThroughQUEBECHigh Frequency Low Frequency

Time (Sec)

Frequency (Hz)

Time (Sec)

Frequency (Hz)

0 - 5 66 0 – 0.35 55.55 -90 63 0.35 - 2 56.5

90 - 660 61.5 2 - 10 57> 660 60.6 10 - 90 57.5

90 - 660 58.5> 660 59.4

OFF NOMINAL FREQUENCY CAPABILITY CURVE

54

56

58

60

62

64

66

68

0.1 1 10 100 1000 10000

Time (sec)

Freq

uenc

y (Hz

)

No Trip Zone(not including the lines)

WECC

WECC

ALL REGIONS EXCEPT WECC & Quebec

ALL REGIONS EXCEPT WECC & Quebec

QUEBEC

QUEBEC

ALL OTHERSHigh Frequency Low Frequency

Time (Sec)

Frequency (Hz)

Time (Sec)

Frequency (Hz)

0 - 2 62.2 0 - 2 57.8

2 - 60062.41 – 0.686

log(t) 2 - 180057.63 + 0.575

log(t)>600 60.5 >1800 59.5

WECCHigh Frequency Low Frequency

Time (Sec)

Frequency (Hz)

Time (Sec)

Frequency (Hz)

0 – 30 61.7 0 – 0.75 5730 – 180

61.60.75 -

3057.3

>180 60.6 30 - 180 57.8>180 59.4

Page 11: GE Energy

11 /

NERC PRC-024: Voltage Ride-Through

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.55

0.60

0.65

0.70

0.75

0.80

0.85

0.90

0.95

1.00

1.05

1.10

1.15

1.20

1.25

1.30

1.35

1.40

0.1 1.0 10.0 100.0 1000.0

Po

int o

f In

terc

on

necti

on

-V

olt

ag

e (

PU

)

Time (Seconds)

Voltage Ride-ThroughTime Duration Curves

High Voltage Duration Low Voltage Duration

No Trip Zone

Return to between .95 PU and 1.05 PU dependant on automatic or manual changes to the system.

HVRT DURATION LVRT DURATION

Time (Sec)

Voltage (p.u.)

Time (Sec)

Voltage (p.u.)

0.20 1.200 0.15 0.000

0.50 1.175 0.30 0.450

1.00 1.150 2.00 0.650

600 1.100 3.00 0.750

    600 0.900

Generators / Plant must not trip for credible faults inside the zone unless:

•SPS / RAS requires it

•Generator critical clearing time requires it (synchronous generators)

Page 12: GE Energy

12 /

Ride-Thru Capabilities

Medium voltage bus drops to

0.0

Power recovers to pre-disturbance level in

<200ms

GE's Standard WindRIDE-THRU Offerings

0

20

40

60

80

100

120

-1.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0

Time (seconds)

Volta

ge a

t Poi

nt o

f In

terc

onne

ctio

n (P

erce

nt)

200 ms

LVRT

ZVRT

3-phase zero retained voltage, 200ms fault:(GE Standard ZVRT offering) P, Q (Mw,Mvar)

Field Test Results (2.5 unit)

Page 13: GE Energy

13 /

3-phase 18.5% retained voltage, 700ms fault:P, Q (Mw,Mvar)

Reactive Power well behaved: supports grid

during voltage depression

Field Test Results (2.5 unit)

Page 14: GE Energy

14 /

HVRT Requirement: Traditional vs. Severity-Duration

Voltage

Time0

Voltage

Time0

0

a

b c d

= a

= b + c + d

Voltage

Time0

a

b c d

= a

= b + c + d

Voltage

Time

Traditional HVRT Req’mtTimer starts at beginning of fault

Recommended HVRT Req’mtTimer starts when voltage exceeds high-voltage thresholdObjective is to align criteria with equipment duties/capabilities

Page 15: GE Energy

15 /

PROTECTION COORDINATIONNERC PRC-019: Coordination of Generating Unit/Plant Voltage Regulating Controls with Unit/Plant Capabilities and Protection

Coordination• Verify limiters are set to operate before protection• Verify protection is set to operate before conditions exceed

equipment capabilities

Elements may include (but are not limited to):• Field over-excitation limiter and associated protective functions• Inverter over current limit and associated protective functions• Volts per Hertz limiter and associated protective functions• Stator over-voltage protection system settings• Generator and transformer volts per Hertz capability• Time versus field current or time versus stator current capability• Converter over temperature limiter and associated protective

functions

Page 16: GE Energy

16 /

MODEL VALIDATIONNERC MOD-026: Plant Volt / Var ControlNERC MOD-027: Plant Active Power / Frequency Control

Main Requirements• Each Transmission Planner shall provide existing model and data to the

Generator Owner within 30 days of receiving an information request• Each Generator Owner shall provide to the Transmission Planner a

verified and accurate model in accordance with the standard’s periodicity table

• Other requirements that cover special circumstances

Staged test or ambient monitoring is allowed

The GO “owns” the model and is responsible for its validity• Responsible for selecting proper structure and determining parameters • Responsible for determining if match is “good enough”• Peer Review process is included to facilitate technical discussions

between the Generator Owner (GO) and the Transmission Planner (TP)

Page 17: GE Energy

17 /

Existing NERC Standards Relevant for Renewables

Page 18: GE Energy

18 /

VOLTAGE REGULATIONNERC VAR-001: Voltage and Reactive ControlNERC VAR-002 : Generator Operation for Maintaining Network Voltage Schedules

Main Requirements•Each Transmission Operator shall acquire sufficient

reactive resources and specify a voltage or reactive power schedule at the POI

•Each Generation Operator shall operate each generator in automatic regulation mode and follow the voltage or reactive power schedule provided by the Transmission Operator or as otherwise directed by the Transmission Operator

Page 19: GE Energy

19 /

Reactive/Voltage Requirement Variations

• Fixed power factor

• Power factor range (permissive)

• Dispatched reactive or pf, within pf range

• Voltage regulation, within pf range– May regulate local or remote bus

P

Q

P

Q

P

Q

Permissive Range

RequiredRange

Page 20: GE Energy

20 /

DISTURBANCE CONTROL / FREQUENCY REGULATIONNERC BAL-002: Disturbance Control PerformanceNERC BAL-003: Frequency Response and BiasMain Requirements

• Each Balancing Authority shall have access to and/or operate Contingency Reserve to respond to Disturbances. Contingency Reserve may be supplied from generation, controllable load resources, or coordinated adjustments to Interchange Schedules.

• Frequency Response Obligation (FRO): The Balancing Authority’s share of the Frequency Response required for reliable operation across the entire interconnected system. This will be calculated as MW/0.1Hz. [Included in BAL-003.1x draft, now in balloting process]

New and highly

visible in the US now

Page 21: GE Energy

21 /

DISTURBANCE CONTROL / FREQUENCY REGULATIONNERC BAL-002: Disturbance Control PerformanceNERC BAL-003: Frequency Response and Bias

Frequency Response Measurement and Calculation

Primary Response

Reliability Risk

Page 22: GE Energy

22 /

• Report was written by a team of industry experts

and NERC members

• Sub-groups worked on individual chapters

• Draft of consolidated document was sent to entire project team for

review

• Final version of the report was accepted by NERC in

September 2012

• Various regulatory and technical standards teams

now may use this reference for future development

NERC IVGTF 1.3

Page 23: GE Energy

Executive Summary

1.Introduction

2.Reactive Power and Voltage Control

3.Performance During and After Disturbances

4.Active Power Control Capabilities

5.Harmonics and Subsynchronous Interaction

6.Models for Facility Interconnection Studies

7.Communications Between Variable Generation Plants and Grid Operators

Appendices

Table of Contents

Page 24: GE Energy

Thank you!


Recommended