1 G30 Relay Application & Configuration Craig Wester GE Multilin
Transcript
Page 1: GE Multilin-g30 Training

1

G30 RelayApplication & Configuration

Craig WesterGE Multilin

Page 2: GE Multilin-g30 Training

2

G30 is Member of

UR Relay Family

imagination at work

g

Page 3: GE Multilin-g30 Training

3

The UR FamilyA Common Hardware/Software Architecture

Modular Construction Reduces Part Inventory

Page 4: GE Multilin-g30 Training

4

Generation Protection G30 – Generator & Transformer Protection G60 – Generator Protection

Transformer Protection T35 – Transformer Protection (6 winding)T60 – Transformer Protection

Transmission Line Protection L60 – Line Phase Comparison Protection L90 – Line Differential Protection D30 – Backup Distance ProtectionD60 – Line Distance Protection (pilot schemes)

Bus ProtectionB30 – Bus Differential Protection (6 Circuits)B90 – Bus Differential System (8 to 24 Circuits)F35+HID – High Impedance Bus DifferentialF35 – Bus Overcurrent Protection

Feeder Protection F35 – Feeder Protection (1-6 feeders)F60 – Feeder Protection (with Hi-Z)

Capacitor Bank Protection C70 – Capacitor Bank Protection & Control

Motor Protection M60 – Motor Protection

Network Protection N60 – Network Protection and Synchrophasors (4 PMU’s)

Controllers C30 – ControllerC60 – Breaker Management

Covering all Protection and Control ApplicationsThe Universal Relay Family

Page 5: GE Multilin-g30 Training

5

Topics Overview of application

ANSI functions in relay needed for application Modules needed Creating the part number Wiring to modules

• Terminals • Voltage monitoring • Current monitoring

Programming the relay • Protection summary • Trip Bus • FlexLogic • Viewpoint Engineer

Page 6: GE Multilin-g30 Training

6

Overview of Application

imagination at work

g

Page 7: GE Multilin-g30 Training

7

ANSI Functions within G30

Page 8: GE Multilin-g30 Training

8

Single-Line DiagramWith Step-Up Transformer

Main Generator Protection uses Transformer High-side CTs & PTs

1

3

2 or 3

1, 2 or 3

3

1

87GT

87RGF

Y

Page 9: GE Multilin-g30 Training

9

Single-Line DiagramNo Step-up Transformer

Main Generator Protection Assigned to Generator Terminal CTs & PTs

87GT

87RGF1

3

2 or 3

1, 2 or 33

Page 10: GE Multilin-g30 Training

10

Modules Needed & Model Number

Selection

imagination at work

g

Page 11: GE Multilin-g30 Training

Model: G30-N00-HLH-F8L-H6P-M8L-P5C-UXX-WXXH

ori

zon

tal M

od

el N

um

ber

Str

uctu

re

Page 12: GE Multilin-g30 Training

Model: G30-N00-VLH-F8L-H6P-M8L-PXXV

ert

ical M

od

el N

um

ber

Str

uctu

re

Page 13: GE Multilin-g30 Training

13

Module Details & Wiring

imagination at work

g

Page 14: GE Multilin-g30 Training

14

Backlit Keypad

16 Large User Programmable Pushbuttons

3 Small User Programmable Pushbuttons

Status LED for Each Pushbutton

Eliminates Existing Panel Control Switches

Local Control/Display (Type L Faceplate)

Page 15: GE Multilin-g30 Training

15

4CT (F1)4CT (M1)

Example Model: G30-N00-HLH-F8L-H6P-M8L-P5C-UXX-WXX

Rear Terminals of Horizontal G30 Relay

I/O(6P)

RTD(5C)

4VT (M5) 4VT (F5)

CPU PwrSupply

Page 16: GE Multilin-g30 Training

16

Example Model: G30-N00-VLH-F8L-H6P-M8L-PXX

Rear Terminals of Vertical G30 Relay

Page 17: GE Multilin-g30 Training

17

Pow

er

Su

pp

lyPower Supply

•Two Ranges •19-60 VDC (L)•88-300 VDC / 88-288 VAC (H) •Battery for Memory Backup

Power Supply Module

Control Power:B6b-B6a 24VdcB5b-B6a 125Vdc

GroundsB8a, B8b, Chassis Gnd

Page 18: GE Multilin-g30 Training

18

CPU C

PU

Main

Pro

cessor

•High-speed 32-Bit RISC CPU> 50 MIPS, up to 120 MIPS

(MIPS - Million Instructions per Second)

FLASH memory •Easy firmware upgrades

•High-Speed Comms support

•10/100 Mbps Ethernet LAN•RS485

•IRIG-B Input•Capacitor Memory Backup

CPU Module

Ethernet Port

Page 19: GE Multilin-g30 Training

19

• Internet/Intranet Ready - IP AddressInternet/Intranet Ready - IP Address

• Simple Network Time Protocol (SNTP) for Real Time Clock Simple Network Time Protocol (SNTP) for Real Time Clock SynchronizationSynchronization

• Modbus RTU protocolModbus RTU protocol– Standard Front Port: RS232 (point-to-point)Standard Front Port: RS232 (point-to-point)– Rear Ports: RS485 up to 115kbps, 10/100BaseT (Ethernet) or Rear Ports: RS485 up to 115kbps, 10/100BaseT (Ethernet) or

10/100BaseF (Fiber Optic) 10/100BaseF (Fiber Optic) – Available over TCP/IPAvailable over TCP/IP

• DNP 3.0 Protocol (CERTIFIED)DNP 3.0 Protocol (CERTIFIED)– Rear Ports: RS485 up to 115kbps and 10/100BaseT/F EthernetRear Ports: RS485 up to 115kbps and 10/100BaseT/F Ethernet

• IEC61850 protocol (optional)IEC61850 protocol (optional)– Physical: 10/100BaseT (Ethernet) or 10/100BaseF (Fiber Optic) Physical: 10/100BaseT (Ethernet) or 10/100BaseF (Fiber Optic) – Available Only on CPUs with Ethernet Port(s)Available Only on CPUs with Ethernet Port(s)

• HTML View Access with Netscape or Internet ExplorerHTML View Access with Netscape or Internet Explorer– Ethernet ConnectionsEthernet Connections

• Internet/Intranet Ready - IP AddressInternet/Intranet Ready - IP Address

• Simple Network Time Protocol (SNTP) for Real Time Clock Simple Network Time Protocol (SNTP) for Real Time Clock SynchronizationSynchronization

• Modbus RTU protocolModbus RTU protocol– Standard Front Port: RS232 (point-to-point)Standard Front Port: RS232 (point-to-point)– Rear Ports: RS485 up to 115kbps, 10/100BaseT (Ethernet) or Rear Ports: RS485 up to 115kbps, 10/100BaseT (Ethernet) or

10/100BaseF (Fiber Optic) 10/100BaseF (Fiber Optic) – Available over TCP/IPAvailable over TCP/IP

• DNP 3.0 Protocol (CERTIFIED)DNP 3.0 Protocol (CERTIFIED)– Rear Ports: RS485 up to 115kbps and 10/100BaseT/F EthernetRear Ports: RS485 up to 115kbps and 10/100BaseT/F Ethernet

• IEC61850 protocol (optional)IEC61850 protocol (optional)– Physical: 10/100BaseT (Ethernet) or 10/100BaseF (Fiber Optic) Physical: 10/100BaseT (Ethernet) or 10/100BaseF (Fiber Optic) – Available Only on CPUs with Ethernet Port(s)Available Only on CPUs with Ethernet Port(s)

• HTML View Access with Netscape or Internet ExplorerHTML View Access with Netscape or Internet Explorer– Ethernet ConnectionsEthernet Connections

Communication Protocols

DNP, Modbus, IEC61850 protocols simultaneously available on Ethernet port

Page 20: GE Multilin-g30 Training

20

DSP + CT/VTD

SP

& M

ag

neti

cs

DS

P p

rocessor

+ C

T/V

Ts

•Modular CT/VT configurations • up to 8 CT/VTs

•High-speed digital sampling>16 Bit A/D converter> 64 samples / cycle

•High-speed 16-Bit DSP> 32 MIPS, up to 80 MIPS

•“Sources” ConceptUser Selects CT/VT Input forProtection Element

CT ShortingClip

CT/VT Modules (Type 8L)F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

CT ShortingClip

Page 21: GE Multilin-g30 Training

21

Terminal Blocks

Page 22: GE Multilin-g30 Training

22

•Control outputs •Solid State•Electromechanical - multiple types•Fast activation (< 4ms)

•Status inputs•Dry and Wet contacts•18 - 300 VDC•Fast detection speeds (0.5-16ms Selectable)

DIG

ITA

L I

/OS

tatu

s I

np

uts

/ C

on

trol O

utp

uts

Digital I/O • Many Module ChoicesMany Module Choices

– 2 Form A, 2 Form C and 8 Inputs2 Form A, 2 Form C and 8 Inputs– 2 Form A, 4 Form C and 4 Inputs2 Form A, 4 Form C and 4 Inputs– 8 Form C Outputs8 Form C Outputs– 4 Form C, 8 Inputs4 Form C, 8 Inputs– 8 Fast Form C 8 Fast Form C – 6 Form A, 4 Inputs6 Form A, 4 Inputs– 16 Inputs16 Inputs– 4 Form A, 8 Inputs (6N)4 Form A, 8 Inputs (6N)– 4 Form C, 8 Inputs (6P)4 Form C, 8 Inputs (6P)– 4 Form C, 4 Fast Form C4 Form C, 4 Fast Form C– 14 Latching Relays14 Latching Relays

• Transducer I/OTransducer I/O– 8 dcmA8 dcmA– 8 RTD inputs (5C)8 RTD inputs (5C)– 4 dcmA & 4 RTD4 dcmA & 4 RTD

• Digital Inputs FlexibilityDigital Inputs Flexibility– Dry or Wet Type (48 Vdc provided by Dry or Wet Type (48 Vdc provided by

relay)relay)– Minimum Pickup Value Software Minimum Pickup Value Software

SettingSetting– 17, 33, 84 or 166 Vdc17, 33, 84 or 166 Vdc

• Digital Output MonitoringDigital Output Monitoring– Current and Voltage Monitoring of Trip Current and Voltage Monitoring of Trip

& Close Circuits& Close Circuits

• Many Module ChoicesMany Module Choices– 2 Form A, 2 Form C and 8 Inputs2 Form A, 2 Form C and 8 Inputs– 2 Form A, 4 Form C and 4 Inputs2 Form A, 4 Form C and 4 Inputs– 8 Form C Outputs8 Form C Outputs– 4 Form C, 8 Inputs4 Form C, 8 Inputs– 8 Fast Form C 8 Fast Form C – 6 Form A, 4 Inputs6 Form A, 4 Inputs– 16 Inputs16 Inputs– 4 Form A, 8 Inputs (6N)4 Form A, 8 Inputs (6N)– 4 Form C, 8 Inputs (6P)4 Form C, 8 Inputs (6P)– 4 Form C, 4 Fast Form C4 Form C, 4 Fast Form C– 14 Latching Relays14 Latching Relays

• Transducer I/OTransducer I/O– 8 dcmA8 dcmA– 8 RTD inputs (5C)8 RTD inputs (5C)– 4 dcmA & 4 RTD4 dcmA & 4 RTD

• Digital Inputs FlexibilityDigital Inputs Flexibility– Dry or Wet Type (48 Vdc provided by Dry or Wet Type (48 Vdc provided by

relay)relay)– Minimum Pickup Value Software Minimum Pickup Value Software

SettingSetting– 17, 33, 84 or 166 Vdc17, 33, 84 or 166 Vdc

• Digital Output MonitoringDigital Output Monitoring– Current and Voltage Monitoring of Trip Current and Voltage Monitoring of Trip

& Close Circuits& Close Circuits

Input/Output Modules

Page 23: GE Multilin-g30 Training

23

Input/Output Module (6P module in “H” slot)

H

HH

HH

H

H

HH

HHH

HH

HHH

HH

HHH

HH

H

H

H

H

H

H

H

HH

HH

Page 24: GE Multilin-g30 Training

24

Input/Output Module (6N module in “H” slot)

H

HH

HH

H

HH

HH

H

H

HH

HHH

HH

HHHH

H

HH

HH

H

HH

HH

H

H

H

H

Page 25: GE Multilin-g30 Training

25

Contact Input Wiring

Contact Inputs are polarity

sensitive

Page 26: GE Multilin-g30 Training

26

• Transducer type inputs & outputs

•dcmA•RTD

Analog I/OA

NA

LO

G I

/OA

nalo

g T

ran

sd

ucer

I/O

dcMA or RTD Inputs/Outputs

26

PPPPP

PPPPP

PPPPP

PPPPP

P

RTD Inputs (Type 5C)

Page 27: GE Multilin-g30 Training

27

4CT (F1)4CT (M1)

Example Model: G30-N00-HLH-F8L-H6P-M8L-P5C-UXX-WXX

Rear Terminals of G30 Relay

I/O(6P)

RTD(5C)

4VT (M5) 4VT (F5)

CPU PwrSupply

Page 28: GE Multilin-g30 Training

28

Metering & Monitoring

• Current (Phase, Neutral and Ground) - [mag & ang]Current (Phase, Neutral and Ground) - [mag & ang]– Accuracy: ± 0.25% of reading or ± 0.1% of rating from 0.1 to 2.0 x CT rating Accuracy: ± 0.25% of reading or ± 0.1% of rating from 0.1 to 2.0 x CT rating

(whichever is greater)(whichever is greater)• Voltage (Vab Vbc Vca Van Vbn Vcn) - [mag& ang]Voltage (Vab Vbc Vca Van Vbn Vcn) - [mag& ang]

– Accuracy: ± 0.25% of reading from 10 to 208 VAccuracy: ± 0.25% of reading from 10 to 208 V• Sequence Components of I & VSequence Components of I & V

– I0, I1, I2, V0, V1, V2I0, I1, I2, V0, V1, V2

• Apparent Power (VA)Apparent Power (VA) - 1ph & 3ph - 1ph & 3ph– Accuracy: ± 1.0% of readingAccuracy: ± 1.0% of reading

• Real Power (Watts) - 1ph & 3phReal Power (Watts) - 1ph & 3ph– Accuracy: ± 1% of readingAccuracy: ± 1% of reading

• Reactive Power (Vars) - 1ph & 3phReactive Power (Vars) - 1ph & 3ph– Accuracy: ± 1%Accuracy: ± 1%

• Power Factor - 1ph & 3phPower Factor - 1ph & 3ph– Accuracy: ± 0.02Accuracy: ± 0.02

• Energy (Pos & Neg Wh, Varh) - 3phEnergy (Pos & Neg Wh, Varh) - 3ph

• FrequencyFrequency

• Differential CurrentsDifferential Currents

• Synchrocheck (V, Hz, Mag)Synchrocheck (V, Hz, Mag)

• Phasor DiagramsPhasor Diagrams

• Current (Phase, Neutral and Ground) - [mag & ang]Current (Phase, Neutral and Ground) - [mag & ang]– Accuracy: ± 0.25% of reading or ± 0.1% of rating from 0.1 to 2.0 x CT rating Accuracy: ± 0.25% of reading or ± 0.1% of rating from 0.1 to 2.0 x CT rating

(whichever is greater)(whichever is greater)• Voltage (Vab Vbc Vca Van Vbn Vcn) - [mag& ang]Voltage (Vab Vbc Vca Van Vbn Vcn) - [mag& ang]

– Accuracy: ± 0.25% of reading from 10 to 208 VAccuracy: ± 0.25% of reading from 10 to 208 V• Sequence Components of I & VSequence Components of I & V

– I0, I1, I2, V0, V1, V2I0, I1, I2, V0, V1, V2

• Apparent Power (VA)Apparent Power (VA) - 1ph & 3ph - 1ph & 3ph– Accuracy: ± 1.0% of readingAccuracy: ± 1.0% of reading

• Real Power (Watts) - 1ph & 3phReal Power (Watts) - 1ph & 3ph– Accuracy: ± 1% of readingAccuracy: ± 1% of reading

• Reactive Power (Vars) - 1ph & 3phReactive Power (Vars) - 1ph & 3ph– Accuracy: ± 1%Accuracy: ± 1%

• Power Factor - 1ph & 3phPower Factor - 1ph & 3ph– Accuracy: ± 0.02Accuracy: ± 0.02

• Energy (Pos & Neg Wh, Varh) - 3phEnergy (Pos & Neg Wh, Varh) - 3ph

• FrequencyFrequency

• Differential CurrentsDifferential Currents

• Synchrocheck (V, Hz, Mag)Synchrocheck (V, Hz, Mag)

• Phasor DiagramsPhasor Diagrams

Page 29: GE Multilin-g30 Training

29

Large LED’sLarge Label Text

Easy Labeling

Programmable LEDs and Labels

Page 30: GE Multilin-g30 Training

30

Programming Relay

imagination at work

g

Page 31: GE Multilin-g30 Training

31

GE Multilin Software

•EnerVista UR Setup• Manages communications to all relays• Retrieves event logs, fault reports,

oscillography• Settings file firmware management and

firmware management• Lock configurations for repeatability

•ViewPoint Engineer• FlexLogic Editor to create logic using a

graphical interface• FlexLogic Monitor for real-time

debugging/testing/commissioning

Page 32: GE Multilin-g30 Training

32

Functional Diagram

IEC61850 GSSEIEC61850 GOOSE

CT & VT Inputs

Remote InputsIEC61850 GSSEIEC61850 GOOSE

Page 33: GE Multilin-g30 Training

33

Settings Configuration:• Communicate with multiple relays at the same time• Configure settings both On-Line and Offline• Copy and paste settings• Duplicate settings files• Easy to navigate menu tree• Quick connect communications• Common look and feel for all products

Metering:• Status of all inputs and outputs• Real-time metering with phasor diagrams• Analyzing of current and voltage harmonics• Viewing of relay front panel

Troubleshooting & Maintenance:• Analyzing of event records• Powerful oscillography COMTRADE viewer• Real time data logging and fault reports• Compare relay settings with setting file• Upgrade firmware

EnerVista: Setup Software. . . Simplified Device Configuration

Page 34: GE Multilin-g30 Training

34

Protection Summary. . . Quickly Lists which Protection Functions are Enabled and Gives Link to That Function

Page 35: GE Multilin-g30 Training

35

Trip Bus – Set Relay without Using Logic. . . 16 input OR gate….up to 6 TRIP BUS elements can be configured

Page 36: GE Multilin-g30 Training

36

Sources and Transformer Configuration

Note CT polarities in Typical Wiring Diagram and connections to G30. These are necessary to correctly meter forward power. The transformer phase shift setting must compensate the measured relay currents for both the actual phase shift of the transformer, and any phase due to the CT polarities and connections.

Page 37: GE Multilin-g30 Training

37

Sources and Transformer Configuration Assumption:

Step-up Transformer is -30° lagging (from line side to generator side)

Sources to match Typical Wiring Diagram:

Transformer Configuration

Page 38: GE Multilin-g30 Training

38

Single-Line DiagramWith Step-Up Transformer

Main Generator Protection uses Transformer High-side CTs & PTs

1

3

2 or 3

1, 2 or 3

3

1

87GT

87RGF

Y

F1-F3

M1-M3

F8

F5-F7

M4

Page 39: GE Multilin-g30 Training

39

Graphical Flexlogic Editor

• Create logic using a graphical editor

• Document logic and store documentation in setting file

• Detects errors commonly made in logic creation

• Allows for configuration through to elements, I/O, LEDs, etc.

• Capability to build and organize logic on separate worksheetsGraphical Flexlogic Analyzer

• Analyze the status of Flexlogic in Real-Time

• Easily detect problems in wiring• Simplify commissioning by easily

following status of logic on the screen

Programmable Logic - Viewpoint Engineer. . . Design Ease and Productivity Improvement

Page 40: GE Multilin-g30 Training

40

Graphical Programmable Logic Designer. . . Customized Control and Operation Logic

Page 41: GE Multilin-g30 Training

41

“Click To” Protection Elements for Editing . . . Reduces Engineering and Setting File Creation Time

Page 42: GE Multilin-g30 Training

42

Highlights show asserted logic

Dynamic Logic Monitor. . . Aids in Troubleshooting and Reduces Installation Time

Page 43: GE Multilin-g30 Training

43