Page 1: General Catalogue VRV

130

Page 2: General Catalogue VRV

131

HRV

VRVIII

VRVII

INDOOR UNITS1. Cassette units

2. Concealed ceiling units

3. Wall mounted units

4. Ceiling suspended units

5. Floor standing units

6. Outdoor air processing unit

HRV

Rising energy and general building services running costs have led end users to expect far more than just cooling and heating from their air conditioning. A truly complete and acceptable system therefore, must be energy effi cient, economic to run, easy to install, fl exible, reliable and user friendly.Fresh air must also be supplied without increasing energy consumption and central management and control facilities have gained in importance, particularly for medium to large sized buildings.The Daikin Hi-VRV system meets all these requirements:

VRV air conditioning can be found in offi ces, restaurants, theatres, hospitals, universities, museums, shops - in short, in any location where the provision of a balanced, pleasant working environment can improve the lifestyle and comfort of the individual.

Air Conditioning

Ventilation Control & Management

DAIKINNETWORKSOLUTION

RXYSQ4-6P7V3B 132RXYSQ4-6P7Y1B 133RXQ5-18P7W1B(A) 134RXYQ5-18P7W1B(A) 135RXYQ20-36P7W1B(A) 136RXYQ38-54P7W1B(A) 137RXYQ16-36P7W1B 138REYQ18-48P7Y1B 139

REYQ8-48M8W1B(A) 140RWEYQ-MY1 141

FXFQ-P7VEB 143FXZQ-M8V1B 144FXCQ-M8V3B 145FXKQ-MAVE 146

FXDQ-M8V3B 147FXDQ-P/NA 148FXSQ-M8V3B 149FXMQ-MAVE 150

FXAQ-MAVE 151

FXHQ-MAVE 152FXUQ-MAV1 153

FXNQ-MAVE 154FXLQ-MAVE 155

FXMQ-MFV1 156SELECTION PROGRAMMES 157

VAM-FA 158VKM-GA(M) 159

new

new

new

Page 3: General Catalogue VRV

VRVIII-S Inverter heat pump

High COP values Maximum 9 indoor units per outdoor unit Silent operation Small capacities - 4, 5 & 6HP Super wide range of indoor units Slim & fl exible design Space saving outdoor unit

HEAT PUMPOutdoor UnitOutdoor Unit RXYSQ4P7V3B RXYSQ5P7V3B RXYSQ6P7V3BCapacity range HP 4 5 6Capacity Cooling kw 11.2 14.0 15.5

Heating kw 12.5 16.0 18.0Dimensions (Height x Width x Depth) mm 1,345x900x320Weight kg 125Sound Level Sound Power Cooling dBA 66 67 69

Sound Pressure Cooling dBA 50 51 53Heating dBA 52 53 55

Air Flow Rate (nominal at 230V)

Cooling m³/min 106Heating m³/min 102 105

Operation Range Cooling Min~Max °CDB -5.0~46Heating Min~Max °CWB -20~15.5

Refrigerant R-410APower Supply 1~/230V/50HzMax n° of indoor units to be connected 6 8 9Piping connections Liquid (OD)/Gas/Drain mm 9.52 / 15.9 / 26 x 3 9.52 / 19.1 / 26 x 3Max total length m 300

132

RXYSQ4-6P7V3B

RXYSQ-P7V3B

Page 4: General Catalogue VRV

VRVIII-S Inverter heat pump

High COP values Maximum 9 indoor units per outdoor unit Silent operation Small capacities - 4, 5 & 6HP Super wide range of indoor units Slim & fl exible design Space saving outdoor unit

HEAT PUMPOutdoor UnitOutdoor Unit RXYSQ4P7Y1B RXYSQ5P7Y1B RXYSQ6P7Y1BCapacity range HP 4 5 6Capacity Cooling kw 11.2 14.0 15.5

Heating kw 12.5 16.0 18.0Dimensions (Height x Width x Depth) mm 1,345x900x320Weight kg 120Sound Level Sound Power Cooling dBA 66 67 69

Sound Pressure Cooling dBA 50 51 53Heating dBA 52 53 55

Air Flow Rate (nominal at 230V)

Cooling m³/min 106Heating m³/min 102 105

Operation Range Cooling Min~Max °CDB -5.0~46Heating Min~Max °CWB -20~15.5

Refrigerant R-410APower Supply 3~/280-415V/50HzMax n° of indoor units to be connected 6 8 9Piping connections Liquid (OD)/Gas/Drain mm 9.52 / 15.9 / 26 x 3 9.52 / 19.1 / 26 x 3Max total length m 300

133

RXYSQ4-6P7Y1B

RXYSQ-P7Y1B

Page 5: General Catalogue VRV

VRVIII inverter cooling only

Wide range of indoor units: 13 different models in a total of 75 variations

Compact size of outdoor units Increased COP 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st

step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DS-

net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF

Easy installation thanks to automatic refrigerant charging operation, automatic test operation

Quiet operation Leak detection function

COOLING ONLYRXQ-P(A)RXQ-P(A) 5 8 10 12 14 16 18Capacity range HP 5 8 10 12 14 16 18Capacity Cooling kw 14.0 22.4 28.0 33.5 40.0 45.0 49.0Power input (Nominal) Cooling kw 3.52 5.56 7.42 9.62 12.4 14.2 16.2Dimensions (Height x Width x Depth) mm 1,680x635x765 1,680x930x765 1,680x1,240x765Weight kg 157 185 238 314 322Sound Level Sound Power Cooling dBA 72 78 80 83

Sound Pressure Cooling dBA 54 57 58 60 63Air Flow Rate (nominal at 230V) Cooling m³/min 95 171 185 196 233 239Operation Range Cooling Min~Max °CDB -5.0~43.0Refrigerant R-410APower Supply 3N~/400V/50HzMax n° of indoor units to be connected 8 13 16 19 23 26 29Piping connections Liquid (OD)/Gas mm 9.5 / 15.9 9.5 / 19.1 9.5 / 22.2 12.7 / 28.6 12.7 / 28.6 15.9 / 28.6

134

RXQ5-18P7W1B(A)

RXQ5P RXQ8-12P RXQ14-18P

Page 6: General Catalogue VRV

VRVIII Inverter heat pumpSmall footprint combination

Increased outdoor unit capacity up to 54 HP Wide range of indoor units: 13 different models in a

total of 75 variations Flexible combination of outdoor units: small

footprint combination, high COP combination or any other combination of your choice

Compact size of outdoor units Increased COP Increased external static pressure: up to 78.4Pa 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st

step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DS-

net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF

Easy installation thanks to automatic refrigerant charging operation, automatic test operation

Quiet operation Leak detection function

HEAT PUMPRXYQ-P(A)RXYQ-P(A) 5 8 10 12 14 16 18Capacity range HP 5 8 10 12 14 16 18Capacity Cooling kw 14.0 22.4 28.0 33.5 40.0 45.0 49.0

Heating kw 16.0 25.0 31.5 37.5 45.0 50.0 56.5Power input (Nominal) Cooling kw 3.52 5.56 7.42 9.62 12.4 14.2 16.2

Heating kw 4.00 5.86 7.70 9.44 11.30 12.90 15.30Dimensions (Height x Width x Depth) mm 1,680x635x765 1,680x930x765 1,680x1,240x765Weight kg 159 187 240 316 324Sound Level Sound Power Cooling dBA 72 78 80 83

Sound Pressure Cooling dBA 54 57 58 60 63Air Flow Rate (nominal at 230V)

Cooling m³/min 95 171 185 196 233 239Heating m³/min 95 171 185 196 233 239

Operation Range Cooling Min~Max °CDB -5.0~43.0Heating Min~Max °CWB -20.0~15.0

Refrigerant R-410APower Supply 3N~/400V/50HzMax n° of indoor units to be connected 8 13 16 19 23 26 29Piping connections Liquid (OD)/Gas mm 9.5 / 15.9 9.5 / 19.1 9.5 / 22.2 12.7 / 28.6 15.9 / 28.6Max total length m 1000

135

RXYQ5-18P7W1B(A)

RXYQ5P RXYQ8-12P RXYQ14-18P

Page 7: General Catalogue VRV

HEAT PUMPRXYQ-P(A)RXYQ-P(A) 20 22 24 26 28 30 32 34 36Modules RXYQ8P 1 1

RXYQ10P 1 1RXYQ12P 1 1 2 1RXYQ14PA 1RXYQ16PA 1RXYQ18PA 1 1 1 1 1 2

Capacity range HP 20 22 24 26 28 30 32 34 36Capacity Cooling kw 55.9 61.5 67.0 71.4 77.0 82.5 89.0 94.0 98.0

Heating kw 62.5 69.0 75.0 81.5 88.0 94.0 102.0 107.0 113.0Power input (Nominal) Cooling kw 15.2 17.0 19.2 21.8 23.6 25.8 28.6 30.4 32.4

Heating kw 15.3 17.1 18.9 21.2 23.0 24.7 26.6 28.2 30.6Dimensions (Height x Width x Depth) mm -Weight kg -Sound Level Sound Power Cooling dBA -

Sound Pressure Cooling dBA -Air Flow Rate (nominal at 230V)

Cooling m³/min 171 + 196 185 + 196 196 + 196 171 + 239 185 + 239 196 + 239 233 + 239 239 + 239Heating m³/min 171 + 196 185 + 196 196 + 196 171 + 239 185 + 239 196 + 239 233 + 239 239 + 239

Operation Range Cooling Min~Max °CDB -5.0~43.0Heating Min~Max °CWB -20.0~15.0

Refrigerant R-410APower Supply 3N~/400V/50HzMax n° of indoor units to be connected 32 35 39 42 45 49 52 55 58Piping connections Liquid (OD)/Gas mm 15.9 / 28.6 15.9 / 34.9 19.1 / 34.9 19.1 / 41.3Max total length m 1000

VRVIII Inverter heat pumpSmall footprint combination

Increased outdoor unit capacity up to 54 HP Wide range of indoor units: 13 different models in a

total of 75 variations Flexible combination of outdoor units: small

footprint combination, high COP combination or any other combination of your choice

Compact size of outdoor units Increased COP Increased external static pressure: up to 78.4Pa 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st

step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DS-

net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF

Easy installation thanks to automatic refrigerant charging operation, automatic test operation

Quiet operation Leak detection function

136

RXYQ20-36P7W1B(A)

RXYQ20-24P RXYQ26-30P RXYQ32-36P

Page 8: General Catalogue VRV

HEAT PUMPRXYQ-P(A)RXYQ-P(A) 38 40 42 44 46 48 50 52 54Modules RXYQ8P 1 1

RXYQ10P 1 1RXYQ12P 1 1 2 1RXYQ14PA 1RXYQ16PA 1RXYQ18PA 1 1 1 2 2 2 2 2 3

Capacity range HP 38 40 42 44 46 48 50 52 54Capacity Cooling kw 105.0 111.0 116.0 120.0 126.0 132.0 138.0 143.0 147.0

Heating kw 119.0 126.0 132.0 138.0 145.0 151.0 158.0 163.0 170.0Power input (Nominal) Cooling kw 31.4 33.2 35.4 38.0 39.8 42.0 44.8 46.6 48.6

Heating kw 30.6 32.4 34.2 36.5 38.3 40.0 41.9 43.5 45.9Dimensions (Height x Width x Depth) mm -Weight kg -Sound Level Sound Power Cooling dBA -

Sound Pressure Cooling dBA -Air Flow Rate (nominal at 230V)

Cooling m³/min 171 + 196 + 239 185 + 196 + 239 196 + 196 + 239 171 + 239 + 239 185 + 239 + 239 196 + 239 + 239 233 + 239 + 239 239 + 239 + 239Heating m³/min 171 + 196 + 239 185 + 196 + 239 196 + 196 + 239 171 + 239 + 239 185 + 239 + 239 196 + 239 + 239 233 + 239 + 239 239 + 239 + 239

Operation Range Cooling Min~Max °CDB -5.0~43.0Heating Min~Max °CWB -20.0~15.0

Refrigerant R-410APower Supply 3N~/400V/50HzMax n° of indoor units to be connected 61 64Piping connections Liquid (OD)/Gas mm 19.1 / 41.3Max total length m 1000

VRVIII Inverter heat pumpSmall footprint combination

Increased outdoor unit capacity up to 54 HP Wide range of indoor units: 13 different models in a

total of 75 variations Flexible combination of outdoor units: small

footprint combination, high COP combination or any other combination of your choice

Compact size of outdoor units Increased COP Increased external static pressure: up to 78.4Pa 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st

step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DS-

net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF

Easy installation thanks to automatic refrigerant charging operation, automatic test operation

Quiet operation Leak detection function

137

RXYQ38-54P7W1B(A)

RXYQ38-42P RXYQ44-48P RXYQ50-54P

Page 9: General Catalogue VRV

VRVIII Inverter heat pumpHigh COP combination

Wide range of indoor units: 13 different models in a total of 75 variations

Compact size of outdoor units Increased COP Increased external static pressure: up to 78.4Pa 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st

step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DS-

net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF

Easy installation thanks to automatic refrigerant charging operation, automatic test operation

Quiet operation Leak detection function

HEAT PUMPRXYQ-PRXYQ-P 16 18 20 22Modules RXYQ8P 2 1

RXYQ10P 1 2 1RXYQ12P 1

Capacity range HP 16 18 20 22Capacity Cooling kw 44.8 50.4 56.0 61.5

Heating kw 50.0 56.5 63.0 69.0Power input (Nominal) Cooling kw 11.1 13.0 14.8 17.0

Heating kw 11.7 13.6 15.4 17.1Dimensions (Height x Width x Depth) mm -Air Flow Rate (nominal at 230V)

Cooling m³/min 171 + 171 171 + 185 185 + 185Heating m³/min 171 + 171 171 + 185 185 + 185

Operation Range Cooling Min~Max °CDB -5.0~43.0Heating Min~Max °CWB -20.0~15.0

Refrigerant R-410APower Supply 3N~/400V/50HzMax n° of indoor units to be connected 26 29 32 35Piping connections Liquid (OD)/Gas mm 12.7 / 28.6 15.9 / 28.6Max total length m 1000

HEAT PUMPRXYQ-PRXYQ-P 24 26 28 30 32 34 36Modules RXYQ8P 3 2 1 1

RXYQ10P 1 2 3 1RXYQ12P 2 2 3

Capacity range HP 24 26 28 30 32 34 36Capacity Cooling kw 67.2 72.8 78.4 84.0 89.4 95.0 101.0

Heating kw 75.0 81.5 88.0 94.5 100.0 107.0 113.0Power input (Nominal) Cooling kw 16.7 18.5 20.4 22.3 24.8 26.7 28.9

Heating kw 18.9 19.4 21.3 23.1 24.7 26.6 28.3Dimensions (Height x Width x Depth) mm -Air Flow Rate (nominal at 230V)

Cooling m³/min 171 + 171 + 171 171 + 171 + 185 171 + 185 + 185 185 + 185 + 185 171 + 196 + 196 185 + 196 + 196 196 + 196 + 196Heating m³/min 171 + 171 + 171 171 + 171 + 185 171 + 185 + 185 185 + 185 + 185 171 + 196 + 196 185 + 196 + 196 196 + 196 + 196

Operation Range Cooling Min~Max °CDB -5.0~43.0Heating Min~Max °CWB -20.0~15.0

Refrigerant R-410APower Supply 3N~/400V/50HzMax n° of indoor units to be connected 39 42 45 48 52 55 58Piping connections Liquid (OD)/Gas mm 15.9 / 34.9 19.1 / 34.9 19.1 / 41.3Max total length m 1000

138

RXYQ16-36P7W1B

RXYQ8-12P

Page 10: General Catalogue VRV

VRVIII Heat recovery

Its operation range for example 8hp to 48hp in 2hp increment steps (21 system combinations), is wider than any of its contemporaries.

Its ability to run no less than 64 indoor units in heat recovery format cannot at present be matched by other comparable systems.

The ability to control each conditioned zone keeps VRVIII system running costs to an absolute minimum.

Only those areas calling for air conditioning need to be cooled or heated and the system can be shut down completely in unoccupied rooms.

Modular design enables Daikin VRVIII outdoor units to be joined together in rows with an outstanding degree of uniformity.

The design of the outdoor units is suffi ciently compact to allow them to be taken up to the top of a building in a commercial elevator, overcoming site transportation problems.

Increased EER/COP Extra low noise during night time operation (step

1: 50 dBA; step 2: 45 dBA). Continuous heating (resulting in a higher

integrated heating capacity). Quick cool/heat change over. Typical VRVIII specs (longer piping length,

higher distance between outdoor & indoor unit, autocharging).

HEOutdoor UnitOutdCapacModu

Capac

DimenWeighAir FlowRefrigePowerPiping

HEAT RECOVERYOutdoor unitOutdoor unit 18 20 22 24 26 28 30 32Capacity range HP 18 20 22 24 26 28 30 32Modules REMQ8P 1 1

REMQ10P 1 1 1REMQ12P 1 1 2 1REMQ14P 1REMQ16P 1 1 1 2

Capacity Cooling kw 50.4 55.9 61.5 67.0 73.0 78.5 85.0 90.0Heating kw 56.5 62.5 69.0 75.0 81.5 87.5 95.0 100.0

Dimensions (Height x Width x Depth) mm 1,680x930 + 930x765 1,680x930 + 1,240x765 1,680x1,240 + 1,240x765Weight kg 204 + 254 254 + 254 254 + 334 334 + 334Air Flow Rate (nominal at 230V) Cooling m³/min 180 + 185 180 + 200 185 + 200 200 + 200 185 + 230 200 + 230 230 + 230Refrigerant R-410APower Supply 3~/380-415V/50HzPiping connections Liquid (OD) mm 15.9 19.1

Gas mm 28.6 34.9Discharge Gas mm 22.2 28.6Oil Equalising mm 19.1

HEAT RECOVERYOutdoor UnitOutdoor Unit 34 36 38 40 42 44 46 48Capacity range HP 34 36 38 40 42 44 46 48Modules REMQ8P 1 1

REMQ10P 1 1 1REMQ12P 1 1 2 1REMQ14P 1REMQ16P 1 1 1 1 2 2 2 3

Capacity Cooling kw 95.4 101.0 107.0 112.0 118.0 124.0 130.0 135.0Heating kw 107.0 113.0 119.0 125.0 132.0 138.0 145.0 150.0

Dimensions (Height x Width x Depth) mm 1,680x930 + 930 + 1,240x765 1,680x930 + 1,240 + 1,240x765 1,680x1,240 + 1,240 + 1,240x765Weight kg 204 + 254 + 334 254 + 254 + 334 254 + 334 + 334 334 + 334 + 334Air Flow Rate (nominal at 230V) Cooling m³/min 180 + 185 + 230 180 + 200 + 230 185 + 200 + 230 200 + 200 + 230 185 + 230 + 230 200 + 230 + 230 230 + 230 + 230Refrigerant R-410APower Supply 3~/380-415V/50HzPiping connections Liquid (OD) mm 19.1

Gas mm 34.9 41.3Discharge Gas mm 28.6 34.9Oil Equalising mm 19.1

139

REYQ18-48P7Y1B

REYQ42-44PREYQ18-24P

Page 11: General Catalogue VRV

VRVII Heat recovery

Its operation range for example 8hp to 48hp in 2hp increment steps (21 system combinations), is wider than any of its contemporaries.

Its ability to run no less than 40 indoor units in heat recovery format cannot at present be matched by other comparable systems.

The ability to control each conditioned zone keeps VRVII system running costs to an absolute minimum.

Only those areas calling for air conditioning need to be cooled or heated and the system can be shut down completely in unoccupied rooms.

Modular design enables Daikin VRVII outdoor units to be joined together in rows with an outstanding degree of uniformity.

The design of the outdoor units is suffi ciently compact to allow them to be taken up to the top of a building in a commercial elevator, overcoming site transportation problems.

REYQOutdoor UnitOutdoor Unit 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48Modules REYQ8M 1 1

REYQ10M 1 1 2 1 1 1 2 2 1 1 1REYQ12MA 1 1 1 1 1REYQ14MA 1 1 1 1 1 1REYQ16MA 1 1 1 1 2 1 1 1 2 2 2 3

Capacity range HP 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48Capacity Cooling kw 22.40 28.00 33.50 40.00 44.50 50.40 56.00 61.50 68.00 72.50 78.00 84.50 89.00 96.00 101.00 106.00 113.00 117.00 123.00 129.00 134.00

Heating kw 25.00 31.50 37.50 45.00 50.00 56.50 63.00 69.00 76.50 81.50 87.50 95.00 100.00 108.00 113.00 119.00 127.00 132.00 138.00 145.00 150.00Power input (Nominal) Cooling kw 6.97 9.00 10.60 14.24 15.60 16.00 18.00 19.60 23.24 24.60 26.20 29.90 31.20 32.20 33.60 35.20 38.90 40.20 41.80 45.50 46.90

Heating kw 6.89 9.31 10.80 12.90 14.00 16.50 19.00 20.50 22.60 23.80 25.30 27.50 28.60 32.10 33.30 34.80 37.00 38.10 39.60 41.80 42.90Dimensions (Height x Width x Depth) mm 1,600x930x765 1,600x1,240x765 -Weight kg 245 291 337 -Sound Level Sound Power Cooling dBA 78.0 80.0 81.0 82.0 83.0 84.0 85.0

Sound Pressure Cooling dBA 57.0 58.0 60.0 61.0 62.0 63.0 64.0 65.0Air Flow Rate (nominal at 230V)

Cooling m³/min 175.00 180.00 210.00 355.00 360.00 390.00 420.00 570.00 600.00 630.00Heating m³/min 175.00 180.00 210.00 355.00 360.00 390.00 420.00 570.00 600.00 630.00

Operation Range Cooling Min~Max °CDB -5.0~43.0Heating Min~Max °CWB -20.0~15.5

Refrigerant R-410APower Supply 3N~/400V/50HzMax n° of indoor units to be connected 13 16 19 20 22 32 34 36 38 40Piping connections Liquid (OD)/Gas mm 9.5 / 19.1 9.5 / 22.2 12.7 / 28.6 15.9 / 28.6 15.9 / 34.9 19.1 / 34.9 19.1 / 41.3Max total length m 300

140

REYQ8-48M8W1B(A)

REYQ8-10M REYQ12-16M

Page 12: General Catalogue VRV

Water-cooled VRV

Wide condensing unit range: 10, 20 & 30HP via 1 single refrigerant circuit

High COP values: 5.21 nominal value Up to 32 indoor units connectable to a 30HP

condensing unit Wide range of indoor units: 13 different models in a

total of 75 variations Compact design Operation range (inlet water temperature): 10-45°C Connectable to current Daikin control systems: DS-

net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF

Flexible piping length

HEAT PUMPOutdoor UnitOutdoor Unit RWEYQ10MY1 RWEYQ20MY1 RWEYQ30MY1Capacity range HP 10 20 30Capacity Cooling kw 26.70 53.40 80.10

Heating kw 31.50 63.00 94.50Power input (Nominal) Cooling kw 6.03 12.10 18.10

Heating kw 6.05 12.10 18.20Dimensions (Height x Width x Depth) mm 1000x780x550 -Weight kg 150 300 450Sound Level Sound Pressure Cooling dBA 51.0 54.0 56.0Refrigerant R-410APower Supply 3~/380-415V/50HzMax n° of indoor units to be connected 16 20 32Piping connections Liquid (OD)/Discharge Gas mm 9.5/22.2 15.9/28.6 19.1/34.9

141

RWEYQ-MY1

RWEYQ10M

Page 13: General Catalogue VRV

Water-cooled VRV

Wide condensing unit range: 10, 20 & 30HP via 1 single refrigerant circuit

High COP values: 5.21 nominal value Up to 32 indoor units connectable to a 30HP

condensing unit Wide range of indoor units: 13 different models in a

total of 75 variations Compact design Operation range (inlet water temperature): 10-45°C Connectable to current Daikin control systems: DS-

net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF

Flexible piping length

HEAT RECOVERYOutdoor UnitOutdoor Unit RWEYQ10MY1 RWEYQ20MY1 RWEYQ30MY1Capacity range HP 10 20 30Capacity Cooling kw 26.70 53.40 80.10

Heating kw 31.50 63.00 94.50Power input (Nominal) Cooling kw 6.03 12.10 18.10

Heating kw 6.05 12.10 18.20Dimensions (Height x Width x Depth) mm 1000x780x550 -Weight kg 150 300 450Sound Level Sound Pressure Cooling dBA 51.0 54.0 56.0Refrigerant R-410APower Supply 3~/380-415V/50HzMax n° of indoor units to be connected 16 20 32Piping connections Liquid (OD)/Discharge Gas mm 9.5 / 22.2 / 19.1 15.9 / 28.6 / 22.2 19.1 / 34.9 / 28.6

142

RWEYQ-MY1

RWEYQ10M

Page 14: General Catalogue VRV

Round Flow Cassette

Modern style decoration panel in white (RAL9010) 360° air discharge ensures uniform air fl ow and

temperature distribution Air discharge from the corners avoids dead zones

that may be subject to temperature differences Comfortable horizontal air discharge ensures

draughtfree operation and prevents ceiling soiling 23 different air fl ow patterns possible Fresh air intake: up to 20 % Reduced installation height: 214mm for class 20-63 Easy visible drain check thanks to clear drain socket Drain-up pump with 850 mm lift fi tted as standard.

FXFQ-P7VEBIndoor UnitsIndoor Units 20 25 32 40 50 63 80 100 125Capacity Cooling kw 2.20 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00

Heating kw 2.50 3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00Power input Cooling kw 0.053 0.063 0.083 0.095 0.120 0.173 0.258

Heating kw 0.045 0.055 0.067 0.114 0.108 0.176 0.246Dimensions (Height x Width x Depth) mm 204x840x840 246x840x840 288x840x840Weight kg 20 21 24 26Air Flow Rate Cooling High/Low m³/min 12.5 / 9.0 13.5 / 9.0 15.5 / 10.0 16.5 / 11.0 23.5 / 14.5 26.5 / 17.0 33.0 / 20.0

Heating High/Low m³/min 12.5 / 9.0 13.5 / 9.0 15.0 / 9.5 17.5 / 12.0 23.5 / 14.5 28.0 / 17.5 33.0 / 20.0Sound power (nominal) Cooling dBA 49.0 50.0 51.0 52.0 55.0 58.0 61.0Sound Pressure Cooling High/Low dBA 31.0 / 28.0 32.0 / 28.0 33.0 / 28.0 34.0 / 29.0 38.0 / 32.0 41.0 / 33.0 44.0 / 34.0

Heating High/Low dBA 31.0 / 28.0 32.0 / 28.0 33.0 / 28.0 36.0 / 30.0 38.0 / 32.0 42.0 / 34.0 44.0 / 34.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.35 / 12.7 / 32 6.40 / 12.7 / 32 9.5 / 15.9 / 32Decoration Panel Model BYCQ140CW1

Colour RAL9010HeightxWidthxDepth mm 50x950x950Weight kg 5.5

except VRV inverter

cooling only

optional standard

optional

optional

143

FXFQ-P7VEB

Page 15: General Catalogue VRV

600x600 4-Way Blow Ceiling Mounted Cassette

New and extremely compact casing (575mm in width and depth) enables unit to fi t fl ush into ceilings and match standard architectural modules, without cutting ceiling tiles

Modern style decoration panel in white (RAL9010) Whisper quiet operation: down to 25 dBA sound

pressure level Excellent low draught characteristics Vertical auto-swing function moves the discharge

fl aps up and down for effi cient air distribution throughout the room

Since the fl aps can move to a 0 degree position, virtually no draught can be experienced

5 different air fl ow patterns: Any one of 5 air fl ow patterns can be freely

selected between zero and 40 degrees and will then be maintained during the operational cycle of the air conditioner.

Air can be discharged in any of 4 directions Possibility to shut 1 or 2 fl aps for easy installation

in corners

FXZQ-M8V1BIndoor UnitsIndoor Units FXZQ20M8V1B FXZQ25M8V1B FXZQ32M8V1B FXZQ40M8V1B FXZQ50M8V1BCapacity Cooling kw 2.20 2.80 3.60 4.50 5.60

Heating kw 2.50 3.20 4.00 5.00 6.30Power input Cooling kw 0.073 0.076 0.089 0.115

Heating kw 0.064 0.068 0.080 0.107Dimensions (Height x Width x Depth) mm 286x575x575Weight kg 18Air Flow Rate Cooling High/Low m³/min 9.00 / 7.00 9.50 / 7.50 11.00 / 8.00 14.00 / 10.00Sound power (nominal) Cooling dBA 47.0 49.0 53.0 58.0Sound Pressure Cooling High/Low dBA 30.0 / 25.0 32.0 / 26.0 36.0 / 28.0 41.0 / 33.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / 26Decoration Panel Model BYFQ60B7W1

Colour White (Ral 9010)HeightxWidthxDepth mm 55x700x700Weight kg 2.7

except VRVInverter

Cooling only

optional

optional

optional

144

FXZQ-M8V1B

FXZQ-M8 BRC1D52 BRC7E531/E530

Page 16: General Catalogue VRV

2-Way Blow Ceiling Mounted Cassette

Compact dimensions, can easily be mounted in a ceiling void of only 355mm

Easy to install: depth of all units is 600mm Auto-swing function ensures effi cient air and

temperature distribution and prevents ceiling soiling.

Quiet operation Leaves maximum fl oor and wall space for

furniture, decorations and fi ttings Easy to clean fl at suction grille

FXCQ-M8V3BIndoor UnitsIndoor Units 20 25 32 40 50 63 80 125Capacity Cooling kw 2.20 2.80 3.60 4.50 5.60 7.10 9.00 14.00

Heating kw 2.50 3.20 4.00 5.00 6.30 8.00 10.00 16.00Power input Cooling kw 0.077 0.092 0.130 0.161 0.209 0.256

Heating kw 0.044 0.059 0.097 0.126 0.176 0.223Dimensions (Height x Width x Depth) mm 305x780x600 305x995x600 305x1180x600 305x1670x600Weight kg 26 31 32 35 47 48Air Flow Rate Cooling High/Low m³/min 7.0 / 5.0 9.0 / 6.5 12.0 / 9.0 16.5 / 13.0 26.0 / 21.0 33.0 / 25.0

Heating High/Low m³/min 7.0 / 5.0 9.0 / 6.5 12.0 / 9.0 16.5 / 13.0 26.0 / 21.0 33.0 / 25.0Sound power (nominal) Cooling dBA 45.0 50.0 52.0 54.0 60.0Sound Pressure Cooling High/Low dBA 33.0 / 28.0 35.0 / 29.0 35.5 / 30.5 38.0 / 33.0 40.0 / 35.0 45.0 / 39.0

Heating High/Low dBA 33.0 / 28.0 35.0 / 29.0 35.5 / 30.5 38.0 / 33.0 40.0 / 35.0 45.0 / 39.0Refrigerant R-410APower Supply 1~/230V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.35 / 12.7 / 32 9.5 / 15.9 / 32Decoration Panel Model BYBC32GJW1 BYBC50GJW1 BYBC63GJW1 BYBC125GJW1

Colour White (10Y9/0,5)HeightxWidthxDepth mm 53x1030x680 53x1245x680 53x1430x680 53x1920x680Weight kg 8.0 8.5 9.5 12.0

except VRVInverter

Cooling only

optional

optional

optional

145

FXCQ-M8V3B

FXCQ20,25,32M8 BRC1D52 BRC7C67/C62

Page 17: General Catalogue VRV

Ceiling Mounted Corner Cassette

Slim design for fl exible installation Auto-swing function ensures effi cient air and

temperature distribution. Choice between 3 auto-swing positions for

maximum comfort: standard, draught prevention, ceiling soiling prevention

Optimum air fl ow conditions are created by either downward air discharge or frontal air discharge (via optional grille) or a combination of both

Leaves maximum fl oor and wall space for furniture, decorations and fi ttings

FXKQ-MAVEIndoor UnitsIndoor Units FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVECapacity Cooling kw 2.80 3.60 4.50 7.10

Heating kw 3.20 4.00 5.00 8.00Power input Cooling kw 0.066 0.076 0.105

Heating kw 0.046 0.056 0.085Dimensions (Height x Width x Depth) mm 215x1110x710 215x1310x710Weight kg 31 34Air Flow Rate Cooling High/Low m³/min 11.00 / 9.00 13.00 / 10.00 18.00 / 15.00Sound Pressure Cooling High/Low dBA 38.0 / 33.0 40.0 / 34.0 42.0 / 37.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / 32 9.5 / 15.9 / 32Decoration Panel Model BYK45FJW1 BYK71FJW1

Colour WhiteHeightxWidthxDepth mm 70x1240x800 70x1440x800Weight kg 8.5 9.5

except VRVInverter

Cooling only

optional

optional

optional

146

FXKQ-MAVE

FXKQ63MA BRC1D52 BRC4C63/C61

Page 18: General Catalogue VRV

Concealed Ceiling Unit (Small)

Designed for hotel bedrooms Compact dimensions (230mm high & 652mm

deep), can easily be mounted in a ceiling void Blends unobtrusively with any interior décor: only

the suction and discharge grilles are visible Extremely quiet in operation both indoors and

outdoors The air suction direction can be altered from rear

to bottom suction Air suction fi lter fi tted as standard For easy mounting, the drain pan can be located

to the left or the right of the unit.

FXDQ-M8V3BIndoor UnitsIndoor Units FXDQ20M8V3B FXDQ25M8V3BCapacity Cooling kw 2.20 2.80

Heating kw 2.50 3.20Power input Cooling kw 0.050

Heating kw 0.050Dimensions (Height x Width x Depth) mm 230x502x652Weight kg 17Air Flow Rate Cooling High/Low m³/min 6.70 / 5.20 7.40 / 5.80

Heating High/Low m³/min 6.70 / 5.20 7.40 / 5.80Sound power (nominal) Cooling dBA 50.0Sound Pressure Cooling High/Low dBA 37.0 / 32.0

Heating High/Low dBA 37.0 / 32.0Refrigerant R-410APower Supply 1~/230V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / 27.2

except VRVInverter

Cooling only

optional

optional

optional

147

FXDQ-M8V3B

BRC1D52 BRC4C64/C62 FXDQ20,25M8

Page 19: General Catalogue VRV

Slim Concealed Ceiling Unit

Slim design for fl exible installation Compact dimensions, can easily be mounted in a

ceiling void of only 240mm Quiet operation: down to 29 dBA sound pressure

level Blends unobtrusively with any interior décor Can be installed in both new and existing

buildings. Leaves maximum fl oor and wall space for

furniture, decorations and fi ttings Medium external static pressure facilitates unit use

with fl exible ducts of varying lengths

FXDQ-PVE/FXDQ-NAVEIndoor UnitsIndoor Units FXDQ20PVE FXDQ25PVE FXDQ32PVE FXDQ40NAVE FXDQ50NAVE FXDQ63NAVECapacity Cooling kw 2.20 2.80 3.60 4.50 5.60 7.10

Heating kw 2.50 3.20 4.00 5.00 6.30 8.00Power input Cooling kw 0.086 0.089 0.160 0.165 0.181

Heating kw 0.067 0.070 0.147 0.152 0.168Dimensions (Height x Width x Depth) mm 200x700x620 200x900x620 200x1100x620Weight kg 23.0 27.0 28.0 31.0Air Flow Rate Cooling High/Low m³/min 8.0 / 6.4 10.50 / 8.50 12.50 / 10.00 16.50 / 13.00Sound Pressure Cooling High/Low dBA 33.0 / 29.0 34.0 / 30.0 35.0 / 31.0 36.0 / 32.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / VP20 (I.D. 20/O.D. 26) 9.5 / 15.9 / VP20 (I.D. 20/O.D. 26)

except VRVInverter

Cooling only

optional

optional

optional

148

FXDQ-P/NA

FXDQ20-32PBRC1D52 BRC4C64/C62

Page 20: General Catalogue VRV

Concealed Ceiling Unit

Blends unobtrusively with any interior décor Leaves maximum fl oor and wall space for

furniture, decorations and fi ttings Drain pump fi tted as standard Long life fi lter fi tted as standard The air suction direction can be altered from rear

to bottom suction Ideal for shops, restaurants or offi ces requiring

maximum fl oor space for furniture, decorations and fi ttings

High external static pressure facilitates unit use with fl exible ducts of varying lengths

FXSQ-M8V3BIndoor UnitsIndoor Units 20 25 32 40 50 63 80 100 125Capacity Cooling kw 2.20 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00

Heating kw 2.50 3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00Power input Cooling kw 0.110 0.114 0.127 0.143 0.189 0.234 0.242 0.321

Heating kw 0.090 0.094 0.107 0.123 0.169 0.214 0.222 0.301Dimensions (Height x Width x Depth) mm 300x550x800 300x700x800 300x1000x800 300x1400x800Weight kg 30 31 41 51 52Air Flow Rate Cooling High/Low m³/min 9.00 / 6.50 9.50 / 7.00 11.50 / 9.00 15.00 / 11.00 21.00 / 15.50 27.00 / 20.00 28.00 / 20.50 38.00 / 28.00

Heating High/Low m³/min 9.00 / 6.50 9.50 / 7.00 11.50 / 9.00 15.00 / 11.00 21.00 / 15.50 27.00 / 20.00 28.00 / 20.50 38.00 / 28.00Sound power (nominal) Cooling dBA 50.0 51.0 56.0 58.0 56.0 55.0 56.0 65.0Sound Pressure Cooling High/Low dBA 32.0 / 28.0 33.0 / 28.0 33.0 / 29.0 35.0 / 31.0 35.0 / 30.0 37.0 / 31.0 38.0 / 33.0 40.0 / 35.0

Heating High/Low dBA 32.0 / 28.0 33.0 / 28.0 33.0 / 29.0 35.0 / 31.0 35.0 / 30.0 37.0 / 31.0 38.0 / 33.0 40.0 / 35.0Refrigerant R-410APower Supply 1~/230V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.35 / 12.7 / 32 9.5 / 15.9 / 32Decoration Panel Model BYBS32DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1

Colour White (10Y9/0,5)HeightxWidthxDepth mm 55x650x500 55x800x500 55x1100x500 55x1500x500Weight kg 3 3.5 4.5 6.5

except VRVInverter

Cooling only

optional

optional

optional

FXSQ-M8V3B

FXSQ20,25,32M8 BRC1D52 BRC4C64/C62

149

Page 21: General Catalogue VRV

Concealed Ceiling Unit (Large)

Leaves maximum fl oor and wall space for furniture, decorations and fi ttings

Complete range of models (5 -> 31,5 kW) More than 150 Pa external static pressure allows

extensive ductwork runs and fl exible application: ideal for use in large areas

Built-in drain pump (accessory): housing the drain pump inside the unit has reduced the required installation space

FXMQ-MAVEIndoor UnitsIndoor Units 40 50 63 80 100 125 200 250Capacity Cooling kw 4.50 5.60 7.10 9.00 11.20 14.00 22.40 28.00

Heating kw 5.00 6.30 8.00 10.00 12.50 16.00 25.00 31.50Power input (Nominal) Cooling kw 0.211 0.284 0.411 0.619 1.294 1.465

Heating kw 0.211 0.284 0.411 0.619 1.294 1.465Dimensions (Height x Width x Depth) mm 390x720x690 390x1110x690 470x1380x1100Weight kg 44 45 63 65 137Air Flow Rate Cooling High/Low m³/min 14.00 / 11.50 19.50 / 16.00 29.00 / 23.00 36.00 / 29.00 58.00 / 50.00 72.00 / 62.00Sound Pressure Cooling High/Low dBA 39.0 / 35.0 42.0 / 38.0 43.0 / 39.0 45.0 / 42.0 48.0 / 45.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / 32 9.5 / 15.9 / 32 9.5 / 19.1 / PS1B 9.5 / 22.2 / PS1B

except VRV inverter

cooling only

optional

optional

optional

optional

FXMQ-MAVE

FXMQ80,100,125MA BRC1D52 BRC4C64/C62

150

Page 22: General Catalogue VRV

Wall Mounted Unit

Compact design Fits neatly on a wall Auto-swing function ensures effi cient air

distribution via louvers that close automatically when the unit is switched off

5 different discharge angles can be programmed via the remote control

Both horizontal fl aps and front panel can easily be removed and washed

Discharge angle automatically returns to its previous position on restart (initial setting 10 degrees for cooling and 70 degrees for heating)

All maintenance operations can be carried out from the front of the unit

FXAQ-MAVEIndoor UnitsIndoor Units FXAQ20MAVE FXAQ25MAVE FXAQ32MAVE FXAQ40MAVE FXAQ50MAVE FXAQ63MAVECapacity Cooling kw 2.20 2.80 3.60 4.50 5.60 7.10

Heating kw 2.50 3.20 4.00 5.00 6.30 8.00Power input Cooling kw 0.016 0.022 0.027 0.020 0.027 0.050

Heating kw 0.024 0.027 0.032 0.020 0.032 0.060Dimensions (Height x Width x Depth) mm 290x795x230 290x1050x230Weight kg 11 14Air Flow Rate Cooling High/Low m³/min 7.50 / 4.50 8.00 / 5.00 9.00 / 5.50 12.00 / 9.00 15.00 / 12.00 19.00 / 14.00Sound Pressure Cooling High/Low dBA 35.0 / 29.0 36.0 / 29.0 37.0 / 29.0 39.0 / 34.0 42.0 / 36.0 46.0 / 39.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / 18 6.35 / 12.7 / 18 9.5 / 15.9 / 18

except VRVInverter

Cooling only

optional

optional

optional

151

FXAQ-MAVE

FXAQ40,50,63MABRC1D52 BRC7E619/E618

Page 23: General Catalogue VRV

Ceiling Suspended Unit

Reduced sound pressure level Leaves maximum fl oor and wall space for

furniture, decorations and fi ttings Can be installed in both new and existing

buildings. Use of W-shaped Coanda fl ap enhances horizontal

and vertical air circulation characteristics Wider air discharge thanks to Coanda effect: up to

100 degrees Easy installation and maintenance Long life fi lter fi tted as standard Drain pump kit available as accessory

FXHQ-MAVEIndoor UnitsIndoor Units FXHQ32MAVE FXHQ63MAVE FXHQ100MAVECapacity Cooling kw 3.60 7.10 11.20

Heating kw 4.00 8.00 12.50Power input Cooling kw 0.111 0.115 0.135

Heating kw 0.111 0.115 0.135Dimensions (Height x Width x Depth) mm 195x960x680 195x1160x680 195x1400x680Weight kg 24 28 33Air Flow Rate Cooling High/Low m³/min 12.00 / 10.00 17.50 / 14.00 25.00 / 19.50Sound Pressure Cooling High/Low dBA 36.0 / 31.0 39.0 / 34.0 45.0 / 37.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / 26 9.5 / 15.9 / 26

except VRVInverter

Cooling only

optional

optional

optional

optional

152

FXHQ-MAVE

BRC1D52 BRC7E66/E63 FXHQ32MA

Page 24: General Catalogue VRV

4-Way Blow Ceiling Suspended Cassette

Can be installed in both new and existing buildings.

Group control with other VRV indoor units possible

Cool heat selection Prevention of cold draught at hot start, defrost and

oil return in heating 5m maximum distance between FXUQ unit and

junction box Air can be discharged in any of 4 directions Possibility to shut 1 or 2 fl aps for easy installation

in corners Auto-swing function ensures effi cient air and

temperature distribution. Air fl ow distribution for ceiling heights up to 3.5m

without loss of capacity. Air can be discharged at 5 different angles

between 0 and 60 degrees Air fi lter, drain pan and heat exchanger fi n are

mildew proof and anti-bacterial treated.

FXUQ-MAV1Indoor UnitsIndoor Units FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1Capacity Cooling kw 8.0 11.2 14.0

Heating kw 9.0 12.5 14.0Power input Cooling kw 0.180 0.289

Heating kw 0.160 0.269Dimensions (Height x Width x Depth) mm 165x895x895 230x895x895Weight kg 25 31Air Flow Rate Cooling High/Low m³/min 19.00 / 14.00 29.00 / 21.00 32.00 / 23.00

Heating High/Low m³/min 19.00 / 14.00 29.00 / 21.00 32.00 / 23.00Sound power (nominal) Cooling dBA 56.0 59.0 60.0Sound Pressure Cooling High/Low dBA 40.0 / 35.0 43.0 / 38.0 44.0 / 39.0

Heating High/Low dBA 40.0 / 35.0 43.0 / 38.0 44.0 / 39.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 9.5 / 15.9 / I.D. 20/O.D. 26Combination with junction box BEVQ71M BEVQ100M BEVQ125M

optional

2 steps optional

optional

153

FXUQ-MAV1

FXUQ71MAV1BRC1D52 BRC7C529/C528

Page 25: General Catalogue VRV

Concealed Floor Standing Unit

Ideal for installation beneath a window All models are available with remote control Long life fi lter fi tted as standard Requires very little installation space The connecting port faces downward, eliminating

the need to attach auxiliary piping

FXNQ-MAVEIndoor UnitsIndoor Units FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVECapacity Cooling kw 2.20 2.80 3.60 4.50 5.60 7.10

Heating kw 2.50 3.20 4.00 5.00 6.30 8.00Power input Cooling kw 0.049 0.090 0.110

Heating kw 0.049 0.090 0.110Dimensions (Height x Width x Depth) mm 610x930x220 610x1070x220 610x1350x220Weight kg 19 23 27Air Flow Rate Cooling High/Low m³/min 7.00 / 6.00 8.00 / 6.00 11.00 / 8.50 14.00 / 11.00 16.00 / 12.00Sound Pressure Cooling High/Low dBA 35.0 / 32.0 38.0 / 33.0 39.0 / 34.0 40.0 / 35.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / O.D. 21 9.5 / 15.9 / O.D. 21

except VRVInverter

Cooling only

optional

optional

optional

154

FXNQ-MAVE

FXNQ20,25MA BRC1D52 BRC4C64/C62

Page 26: General Catalogue VRV

Floor Standing Unit

Ideal for installation beneath a window All models are available with remote control Requires very little installation space Running the pipes from connections at the back,

enables the unit to be wall mounted which in turn allows cleaning beneath the unit where dust tends to accumulate

Long life fi lter fi tted as standard

FXLQ-MAVEIndoor UnitsIndoor Units FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVECapacity Cooling kw 2.20 2.80 3.60 4.50 5.60 7.10

Heating kw 2.50 3.20 4.00 5.00 6.30 8.00Power input Cooling kw 0.049 0.090 0.110

Heating kw 0.049 0.090 0.110Dimensions (Height x Width x Depth) mm 600x1000x222 600x1140x222 600x1420x222Weight kg 25 30 36Air Flow Rate Cooling High/Low m³/min 7.00 / 6.00 8.00 / 6.00 11.00 / 8.50 14.00 / 11.00 16.00 / 12.00Sound Pressure Cooling High/Low dBA 35.0 / 32.0 38.0 / 33.0 39.0 / 34.0 40.0 / 35.0Refrigerant R-410APower Supply 1~/220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / O.D. 21 9.5 / 15.9 / O.D. 21

except VRVInverter

Cooling only

optional

optional

optional

155

FXLQ-MAVE

FXLQ20,25MA BRC1D52 BRC4C64/62

Page 27: General Catalogue VRV

Outdoor Air Processing Unit

100% fresh air intake possible Leaves maximum fl oor and wall space for

furniture, decorations and fi ttings Operation range: -5°C to 43°C 225 Pa external static pressure allows extensive

ductwork runs and fl exible application: ideal for use in large areas

Drain pump kit available as accessory

FXMQ-MFV1Indoor UnitsIndoor Units FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1Capacity Cooling kw 14.0 22.4 28.00

Heating kw 8.9 13.9 17.40Power input Cooling kw 0.359 0.548 0.638

Heating kw 0.359 0.548 0.638Dimensions (Height x Width x Depth) mm 470x744x1100 470x1380x1100Weight kg 86 123Air Flow Rate Cooling Medium m³/min 18.0 28.0 35.0

Heating Medium m³/min 18.0 28.0 35.0Refrigerant -Power Supply 220-240V/50HzPiping connections Liquid (OD)/Gas/Drain mm 9.5 / 15.9 / PS1B 9.5 / 19.1 / PS1B 9.5 / 22.2 / PS1B

156

FXMQ-MFV1

FXMQ250MF

Page 28: General Catalogue VRV

157

VRV XpressDaikin has developed a new user friendly, software tool that allows rapid VRV selection and provides a professional result in the 7 following steps:

1. Select indoor units2. Connect outdoor units to indoor units3. Automatic receipt of piping diagram with joints4. Automatic receipt of wiring diagram5. Connect appropriate centralised control systems6. Visualise result in Word or Excel format7. Save project

Using VRV Xpress enables VRV selection to be achieved in a simple, complete and professional manner.

Windows95®, Windows98®, WindowsNT®, Windows2000® and WindowsXP® are registered trademarks of Microsoft corporation.

VRV Pro Selection ProgrammeFEATURES:

• the VRV Pro selection programme offers 3 separate modes to accommodate different design formats according to customer requirements. Multi languages are possible.

1. Expert mode: once the cooling and heating loads in the different rooms have been calculated,

the software will select the most appropriate system plus an estimate of the power consumption.

2. Quick mode: based on calculated system loads, the software will select the most appropriate system.

3. Drawing mode: selecting the indoor and outdoor units from a list enables the user to design a system in

no time at all.

A simple to use, Daikin computerised selection programme, designed for use with Windows 95®, Windows 98®, WindowsNT®, Windows 2000® and Windows XP® systems, enables consulting engineers, design and build contractors, property developers and architects etc. to plan a Daikin air conditioning project on a step by step basis, complete with detailed drawings, bills of quantities and costs.The programme thus enables VRV air conditioning systems to be engineered precisely and economically (without over-sizing units), thereby ensuring optimum operating cycles and maximum energy effi ciency.

157

Page 29: General Catalogue VRV

158

Heat Recovery Ventilation

The Daikin heat recovery ventilation system modulates the temperature and humidity of incoming fresh air to match indoor conditions. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load placed on the air conditioning system to be reduced signifi cantly. HRV units can be controlled individually or integral with the air conditioning system (Daikin VRV or Sky Air series).

• 9 models to choose from• Compact, energy saving ventilation• Specially developed heat exchange element

with HEP (High Effi ciency Paper)• Easy integration into the VRV system• Connectable to current Daikin control systems:

Total heat exchanged foul air

Clean outdoor air

Total heat exchanged clean airFoul indoor air

VAM-FA7

Ventilation VAM150FA7 VAM250FA7 VAM350FA7 VAM500FA7 VAM650FA7 VAM800FA7 VAM1000FA7 VAM1500FA7 VAM2000FA7Air fl ow rate m3/h 150 250 350 500 650 800 1,000 1,500 2,000Sound pressure level (max.) (1) dBA 27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.5External static pressure (max.) Pa 69 64 98 98 93 137 157 137 137Temperature exchange effi ciency % 74 72 75 74 74 74 75 75 75Enthalpy exchange effi ciency heating % 58 58 61 58 58 60 61 61 61

cooling % 64 64 65 62 63 65 66 66 66Dimensions H mm 269 269 285 285 348 348 348 710 710

W mm 760 760 812 812 988 988 988 1,498 1,498D mm 509 509 800 800 852 852 1,140 852 1,140

Weight kg 24 24 33 33 48 48 61 132 158Duct diameter mm ø 100 ø 150 ø 150 ø 200 ø 200 ø 250 ø 250 ø 350 ø 350Power supply VE 1 ~, 50Hz, 220-240V

(1) Sound pressure level is measured in heat exchange mode.

158

HRV

Page 30: General Catalogue VRV

159

Heat Recovery Ventilation

• Heat purge (economiser): heat accumulated indoors is discharged at night

• Integration of humidifi cation and air conditioning into HRV unit

• Increased static pressure thanks to improved fan performance

• Individual control via HRV remote control• Connectable to current Daikin control systems:

VKM-GAM

Ventilation, DX coil & humidifi er VKM50GAM VKM80GAM VKM100GAMFresh air conditioning load Cooling kW 4.71 7.46 9.12

Heating kW 5.58 8.79 10.69Air fl ow rate UH - H - L m3/h 500 - 500 - 440 750 - 750 - 640 950 - 950 - 820Sound pressure level - 220V UH - H - L dBA 37 - 35.5 - 32 38.5 - 36 -33 39 -37 - 34Sound pressure level - 240V UH - H - L dBA 38 - 36 - 34 40 - 37.5 - 35.5 40 - 38 - 35.5Static pressure UH - H - L Pa 160 - 120 - 100 140 - 90 - 70 110 - 70 - 60Temperature exchange effi ciency UH - H - L % 76 - 76 - 77.5 78 - 78 - 79 74 - 74 - 76.5Enthalpy exchange effi ciency - cooling UH - H - L % 64 - 64 - 67 66 - 66 - 68 62 - 62 - 66Enthalpy exchange effi ciency - heating UH - H - L % 67 - 67 - 69 71 - 71 - 73 65 - 65 - 69Humidifi er type natural evaporating humdifi erHumidifi cation capacity kg/h 2.70 4.00 5.40Dimensions Height mm 387 387 387

Width mm 1,764 1,764 1,764Depth mm 832 1,214 1,214

Weight kg 102 120 125Power supply V1 1 ~, 220-240V, 50Hz

VKM-GA

Ventilation & DX coil VKM50GA VKM80GA VKM100GAFresh air conditioning load Cooling kW 4.71 7.46 9.12

Heating kW 5.58 8.79 10.69Air fl ow rate UH - H - L m3/h 500 - 500 - 440 750 - 750 - 640 950 - 950 - 820Sound pressure level - 220V UH - H - L dBA 38 - 36 - 33.5 40 - 37.5 - 34.5 40 - 38 - 35Sound pressure level - 240V UH - H - L dBA 39 -37 - 33.5 41.5 - 39 - 37 41 - 39 - 36.5Static pressure UH - H - L Pa 180 - 150 - 110 170 - 120 - 80 150 - 100 - 70Temperature exchange effi ciency UH - H - L % 76 - 76 - 77.5 78 - 78 - 79 74 - 74 - 76.5Enthalpy exchange effi ciency - cooling UH - H - L % 64 - 64 - 67 66 - 66 - 68 62 - 62 - 66Enthalpy exchange effi ciency - heating UH - H - L % 67 - 67 - 69 71 - 71 - 73 65 - 65 - 69Dimensions Height mm 387 387 387

Width mm 1,764 1,764 1,764Depth mm 832 1,214 1,214

Weight kg 96 109 114Power supply V1 1 ~, 220-240V, 50Hz

159

HRV

Page 31: General Catalogue VRV

160160

Page 32: General Catalogue VRV

161

161

In order to realise maximum effi ciency, commercial air conditioning systems must be subject to precise, 24 hour control.

Daikin manufactures and markets a complete suite of advanced computerised central control and monitoring systems designed to simplify air conditioning management and reduce energy usage running costs.

Daikin computerised control systems not only provide the highly sophisticated regulation and day to day monitoring necessary for modern, hi tech air conditioning installations – they also provide owners, landlords and tenants of commercial buildings with valuable performance data on consumption as well as a wide range of operating parameters.

Dedicated Daikin central control can be applied to both VRV and mixed VRV/Sky Air and Split installations with up to 1,024 indoor units and can also be integrated with building management systems.

Control SystemsCENTRALISED CONTROL SYSTEMS

Centralised remote control 162Unifi ed on/off control 162Schedule timer 162

NETWORK SOLUTIONS

163

164

166

167

167

Page 33: General Catalogue VRV

162

DST301B51DCS301B51DCS302C51

Centralised Control Systems

Centralised control of the VRV system can be achieved via 3 user friendly compact controls: centralised remote control, unifi ed on/off control and schedule timer. These controls may be used independently or in combination where 1 group = several (up to 16) indoor units in combination and 1 zone = several groups in combination.A centralised remote control is ideal for use in tenanted commercial buildings subject to random occupation, enabling indoor units to be classifi ed in groups per tenant (zoning). The schedule timer programmes the schedule and operation conditions for each tenant and the control can easily be reset according to varying requirements.

DCS302C51Centralised remote controlProviding individual control of 64 groups (zones) of indoor units.

• a maximum of 64 groups (128 indoor units, max. 10 outdoor units) can be controlled

• a maximum of 128 groups (128 indoor units, max. 10 outdoor units) can be controlled via 2 centralised remote controls in separate locations

• zone control• group control• malfunction code display• maximum wiring length of 1,000m

(total: 2,000m)• air fl ow direction and air fl ow rate

of HRV can be controlled• expanded timer function

DCS301B51Unifi ed ON/OFF controlProviding simultaneous and individual control of 16 groups of indoor units.

• a maximum of 16 groups (128 indoor units) can be controlled

• 2 remote controls in separate locations can be used

• operating status indication (normal operation, alarm)

• centralised control indication• maximum wiring length of 1,000m

(total: 2,000m)

DST301B51Schedule timerEnabling 64 groups to be programmed.

• a maximum of 128 indoor units can be controlled

• 8 types of weekly schedule • a maximum of 48 hours back up

power supply• a maximum wiring length of

1,000m (total: 2,000m)

Page 34: General Catalogue VRV

163

RS45

8RS

232C

163

Network Solutions

The ideal solution for control and management up to 2,000 Sky Air and/or VRV indoor units

APPLICATION AREA

• A small commercial area of less than 40 indoor units.

• Critical applications for centralized monitoring.

SYSTEM LAYOUT

• Allows monitoring and control of up to up to 50 stores or sites and 2,000 indoor units with just one modem and phone line.

• Automates daily air conditioning operation in order to free users from the hassle of air conditioning operation/management.

• The daily schedule setting allows automatic operation afterward.

• Automates alarm (report messages) for any malfunctions / errors. Immediate report of any indoor unit breakdown to the servicing company.

• Automatic report of breakdown/ malfunction information.

• Minimizes the inconvenience of not having air conditioning via rapid messages

FUNCTIONS

• Schedule setup (Daily schedule)- Start/Stop

• Air conditioning malfunction report- Send message to monitoring

system• Manual operation

- Start/Stop, Set temperature, Operation mode, Fan speed

• Status monitoring (Start/Stop, Set temperature, Operation mode, Room temperature, Operation time, Error code)

PC for monitoring

Public phone line

Modem

Modem

Malfunction

DS-NETadapter

Max. of 10 DS-NET adapters

Page 35: General Catalogue VRV

164

Pi-port

RS-232C

164

Network Solutions

Allows detailed & easy monitoring and operation of VRV systems (max. 2 X 64 groups/indoor units).

Malfunction

Remote monitoring/control via internet, e-mailPPD data is available on the internet

Onboard Ethernet

port

Links to the wattmeter when using the PPD (option) function

Pi-port

Public line

AIRNET

PCMCIA fl ash

memory

• CSV output of PPD (option) result

third party controller (domotics, BMS, etc.)

Ethernet

new

Fire alarm

DIII-NET

Indoor units

DIO unit

DI unit

Controls drain pump lighting

etc.

Monitoring of room enter/exit

sign

RS-232C

DIII-NET Allows monitoring/control of up to 64 units (groups) of A/Cs

and equipment

HRV

DIII-NET PLUS adapter

Onboard modem

Forced OFF contact input

HRVIndoor units

new

Page 36: General Catalogue VRV

165165

LANGUAGES• English• French• German• Italian• Spanish

SYSTEM LAYOUT• Up to 2 x 64 indoor units can be

controlled• Onboard Ethernet port (web

browser + e-mail)• Digital i/o contacts (option)• Touch panel (full colour LCD via

icon display)

MANAGEMENT• Web application & internet

compatibility- Monitoring & control according to

user- Remote monitoring & control of

more than one building- Remote monitoring & control of

more than one building via internet• Power Proportional Distribution:

PPD (option)• PPD data is available on the internet• Easy management of electricity

consumption• Enhanced history function

CONTROL• Individual control (set point, start/stop, fan speed)

(max. 2 x 64 groups/indoor units)• Enhanced scheduling function

(8 schedules, 17 patterns)• Flexible grouping in zones• Yearly schedule• Fire emergency stop control• Interlocking control• Increased HRV monitoring and

control function• Automatic cooling / heating

change-over• Heating optimization• Temperature limit• Password security: 3 levels (general,

administration & service)• Quick selection and full control• Simple navigation

MONITORING• Visualisation via Graphical User

Interface (GUI)• Icon colour display change function• Indoor units operation mode• Error messages via e-mail & mobile

phone (option)• Indication fi lter replacement• Multi PC

COST PERFORMANCE• Labour saving• Easy installation• Compact design: limited installation

space• Overall energy saving

OPEN INTERFACE• Communication to any third party

controller (domotics, BMS, etc.) is possible via open interface

CONNECTABLE TO:• VRV• HRV• Sky Air (via interface adapter)• Split (via interface adapter)

new

Page 37: General Catalogue VRV

166

166

Network Solutions

The ideal solution for control and management of maximum 1,024 VRV indoor units.

LANGUAGES

• English• French• German• Italian• Spanish

SYSTEM LAYOUT

• Up to 1,024 indoor units can be controlled (by 4 iPUs)

• Ethernet TCPIP / 10 base / T communication

• Integrated digital contacts on the Intelligent Processing Unit (iPU)

· 19 general input ports · 2 digital outputs• Stand alone operation of the iPU

for minimum 48 hours• Compatible with UPS shutdown

software

MANAGEMENT

• Web access (option)• Power Proportional Distribution

(option)• Operational history management

(start/stop, malfunction, operation hours)

• Generation of reports (graphics & tables) (daily, weekly, monthly)

• Peak load shedding• Advanced tenant management• Sliding temperature• Eco mode (option)

CONTROL

• Individual control (setpoint, start/stop, fan speed) (max. 1,024 indoor units)

• Group control (100 groups)• Schedule control (128 programs)• Fire emergency stop control (32

programs)• Interlocking control• Setpoint limitation• Automatic cooling/heating change-over• Power failure/release control• Temperature limit (automatic start)• Timer extension

MONITORING

• Visualisation via a Graphical User Interface (GUI) featuring free layout

• Operation mode of indoor units• Fault indication• Indication fi lter replacement• Setpoint indication• Operation time monitoring • Multi PC• On-line help

COST PERFORMANCE

• Labour saving• Easy installation• Compact design: limited installation

space• Overall energy saving

CONNECTABLE TO:

• VRV• HRV• Sky Air (via interface adapter)• Split (via interface adapter)

Centralisedcontrol systems

Fire alarm Security

Intelligent Processing unit (IPU)4 units max.

HRV

Indoor units

· Operation Status Monitoring· Schedule Management· Tenant Management...etc

new

Page 38: General Catalogue VRV

167

167

LonWorks® Networks Compatible Gateway

• Interface for Lon connection to LonWorks® networks

• Communication via Lon® protocol (twisted pair wire)

• 64 units connectable per DMS-IF• Unlimited sitesize• Quick and easy installation

Integrated control system connecting VRV system with BMS system

• PPDdata is available on BMS system• Interface for BMS system• Communication via BACnet

protocol (connection via Ethernet) • 256 units connectable per

BACnet gateway• Unlimited sitesize• Easy and fast installation

Centralisedcontrol systems

HRV

Indoor units

Fire alarm Security· Elevator· Pump· Lighting ...etc

Power supply facility

Lon® BMS

Lon® (FTT-10A)

Centralisedcontrol systems

HRV

Indoor units

Fire alarm Security· Elevator· Pump· Lighting ...etc

Power supply facility

BMS

BACnetover ethernet

new


Recommended