+ All Categories
Home > Documents > GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for...

GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for...

Date post: 11-May-2020
Category:
Upload: others
View: 10 times
Download: 0 times
Share this document with a friend
29
D 1 GENERAL MECH. ABBREVIATIONS @ AT & AND AFF ABOVE FINISHED FLOOR AJC ABOVE CEILING AC AD ADJ. AFMS AFUE AHU AMCA ARCH AS ASH RAE ASTM AUX. AWS AWG AIR CONDITIONER AUTOMATIC DAMPER ADJUSTABLE AIRFLOW MEASURING STATION ANNUAL FUEL UTILIZATION EFFICIENCY AIR HANDLING UNIT AIR MOVEMENT & CONTROL ASSOCIATION ARCHITECTURAL OR ARCHITECT AIR SEPARATOR AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR CONDITIONING ENGINEERS AMERICAN SOCIETY FOR TESTING AND MATERIALS AUXILIARY AMERICAN WELDING SOCIETY AMERICAN WIRE GAUGE - AV AIR VENT c - B B BD BLDG B/F, B/S BTU,BTUh CAV CCC CD CFM CLG CMU co C02 CONC CONN. CONT. COP COR CT CTF cu cw CWP CWR cws D DB, Tdb Db A DOC DIA DIV ON DP dP, PO DSFC DSHP DSS DWG ox EA EAT EER EF EFF EH ELEC EMCS ERU ET ESP EWT EXT EXH EXIST. BOILER BACKDRAFT DAMPER BUILDING BELOW FLOOR, BELOW SLAB BRITISH THERMAL UNITS, BTUs PER HOUR CONSTANT AIR VOLUME CLOSED CIRCUIT COOLER CONDENSATE DRAIN LINE CUBIC FEET PER MINUTE COOLING CONCRETE MASONRY UNIT CLEANOUT CARBON DIOXIDE CONCRETE CONNECT, CONNECTING, CONNECTION CONTINUED COEFFICIENT OF PERFORMANCE CONTRACTING OFFICER'S (OWNER'S) REPRESENTATIVE COOLING TOWER COOLING TOWER FILTER CONDENSING UNIT CONDENSER WATER CONDENSER WATER PUMP CONDENSER WATER RETURN CONDENSER WATER SUPPLY DEPTH DRY BULB (TEMPERATURE) DECIBELS DIRECT DIGITAL CONTROLS DIAMETER DIVISION DOWN DEEP DELTA PRESSURE, PRESSURE DROP DUCTLESS SPLIT FAN COIL UNIT DUCTLESS SPLIT HEAT PUMP DUCTLESS SPLIT SYSTEM DRAWING DIRECT EXPANSION EXHAUST AIR ENTERING AIR TEMPERATURE ENERGY EFFICIENCY RATIO EXHAUST FAN EFFICIENCY ELECTRIC UNIT HEATER ELECTRICAL ENERGY MONITORING AND CONTROL SYSTEM ENERGY RECOVERY UNIT EXPANSION TANK EXTERNAL STATIC PRESSURE ENTERING WATER TEMPERATURE EXTERIOR EXHAUST EXISTING DEG. F ("F) DEGREES FAHRENHEIT FCU FAN COIL UNIT FD FIRE DAMPER, FLOOR DRAIN FFE FINISHED FLOOR ELEVATION FLA FULL LOAD AMPS FOB, FOT FLAT ON BOTTOM, FLAT ON TOP FSD FIRE SMOKE DAMPER FT FOOT OR FEET FT. WG FEETWATERGAUGE I 2 I 3 GENERAL MECH. ABBREVIATIONS (CONT.) GENERAL MECHANICAL NOTES GA GC GPM H HGR HP HR HSPF HTG HTR HVAC HXR HZ IMC IN INWC INWG IPLV KW L LAT LBS LBF/IN2 LWT MAX MBH MCA MD MERV MECH MFR,MFG MIN MOCP MSS MTD MUW MVD NO. NPLV NTS OA OD PO PH PPM PRV QTY RA RG RH RL RM RPM RS SA so SEER SF SMACNA SP ss T'STAT TEMP TG THA THR TYP UH UL v VAV VD VFD VSD w WI W/0 WB,Twb WD WG WL WMS WHSP I GAGE GENERAL CONTRACTOR GALLONS PER MINUTE HEIGHT HOT GAS REHEAT HEAT PUMP HOUR HEATING SEASONAL PERFORMANCE FACTOR HEATING HEATER HEATING, VENTILATING AND AIR CONDITIONING HEAT EXCHANGER HERTZ INTERNATIONAL MECHANICAL CODE INCHE(S) INCHES WATER COLUMN INCHES WATER GAUGE INTEGRATED PART LOAD VALUE KILOWATTS LENGTH LEAVING AIR TEMPERATURE POUNDS POUND FORCE PER SQUARE INCH LEAVING WATER TEMPERATURE MAXIMUM 1,000 x BTUs MINIMUM CIRCUIT AMPACITY MOTORIZED DAMPER MINIMUM EFFICIENCY REPORTING VALUE MECHANICAL MANUFACTURER, MANUFACTURING MINIMUM MAXIMUM OVER CURRENT PROTECTION MANUFACTURER'S STANDARDIZATION SOCIETY MOUNTED MAKE UP WATER (DOMESTIC) MANUAL VOLUME DAMPER NUMBER NET PART LOAD VALUE NOT TO SCALE OUTSIDE AIR OUTSIDE DIAMETER PRESSURE DROP PHASE PARTS PER MILLION PRESSURE RELIEF VALVE QUANTITY RETURN AIR RETURN GRILLE RELATIVE HUMIDITY REFRIGERANT LIQUID ROOM REVOLUTIONS PER MINUTE REFRIGERANT SUCTION SUPPLY AIR SMOKE DAMPER, SMOKE DETECTOR SEASONAL ENERGY EFFICIENCY RATIO SUPPLY FAN SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION STATIC PRESSURE STAINLESS STEEL THERMOSTAT TEMPERATURE TRANSFER GRILLE TOTAL HEAT ABSORPTION TOTAL HEAT REJECTION TYPICAL UNIT HEATER UNDERWRITERS LABORATORY VOLTAGE VARIABLE AIR VOLUME VOLUME DAMPER VARIABLE FREQUENCY DRIVE VARIABLE SPEED DRIVE WATT WITH WITHOUT WET BULB (TEMPERATURE) WIDE, WIDTH WATER GAUGE WALL LOUVER WIRE MESH SCREEN WATER SOURCE HEAT PUMP 1. THE MECHANICAL SYSTEMS HAVE BEEN DESIGNED TO AND SHALL BE INSTALLED TO COMPLY WITH THE FOLLOWING UFC'S: UFC 1-200-01: GENERAL BUILDING REQUIREMENTS UFC 3-310-04: SEISMIC DESIGN FOR BUILDINGS UFC 3-400-02: ENGINEERING WEATHER DATA UFC 3-401-01: MECHANICAL ENGINEERING UFC 3-410-01: HEATING, VENTILATION, AND AIR CONDITIONING SYSTEMS (JULY 2013, CHANGE 1, OCTOBER 2014) UFC 3-450-01: NOISE AND VIBRATION CONTROL UFC 4-010-01: DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS (FEBRUARY 2012, CHANGE 1, OCTOBER 2013) 2. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS MADE. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER. 3. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT. 4. AT START OF CONSTRUCTION, THE HVAC CONTRACTOR AND EACH OF THE SUBCONTRACTORS SHALL PREPARE TYPED LISTS OF ALL EQUIPMENT THAT THEY ARE SUPPLYING REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION. 5. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. 6. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE. 7. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT. 8. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES. 9. THE HVAC CONTRACTOR SHALL COORDINATE ALL WALL, FLOOR AND ROOF PENETRATIONS WITH THE GENERAL CONTRACTOR. 10. THE HVAC CONTRACTOR SHALL CAULK WITH SILICONE ALL GAPS BETWEEN WALL, CEILING AND FLOOR OPENINGS AND HVAC EQUIPMENT PENETRATIONS. THE HVAC CONTRACTOR SHALL PATCH LARGE GAPS BEFORE CAULKING IS APPLIED. 11. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE SHALL BE PROVIDED BY THE HVAC CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE. 12. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND THE PRESSURE CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM, NOT LESS THAN 2 IN.W.G., SEAL CLASS B (LEAKAGE CLASS 6, OR 4% OF THE TOTAL AIR FLOW THROUGH THE DUCT). DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR DIMENSIONS. 13. VOLUME DAMPERS SHALL BE PROVIDED AT EACH MAIN BRANCH TAKE-OFF AND IN SUCH OTHER LOCATIONS WHERE REQUIRED TO PROPERLY BALANCE THE SYSTEM. 14. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE SHOWN. 15. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF ENGINEER. PROVIDE TURNING VANES IN ALL 45" AND 90" SQUARE ELBOWS. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING EDGE. IF TURNING VANES LONGER THAN 36 INCHES ARE REQUIRED, THEY SHALL BE DOUBLE THICKNESS TYPE FOR STRENGTH. 16. FLEXIBLE DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION DEVICE INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS. I I 4 17. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH. BENDS IN FLEXIBLE DUCTWORK SHALL BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE CRUSHED OR DISTORTED IN ITS FINAL CONFIGURATION. 18. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT. FLEXIBLE DUCT CONNECTORS OR SOUND ATTENUATION DEVICES SHALL BE USED ON CONNECTION TO AIR HANDLING EQUIPMENT TO REDUCE NOISE TRANSFER INTO OCCUPIED SPACES. 19. OPEN-ENDED AIR TRANSFER DUCTS AND OPEN-ENDED RETURN AIR DUCTS IN THE CEILING PLENUM SHALL BE UNOBSTRUCTED FOR A MINIMUM DISTANCE OF 24 INCHES FROM THE OPENING TO ALLOW FOR FREE AIRFLOW. 20. TRANSFER DUCTS SHALL HAVE INTERNAL ACOUSTIC LINING OR BE SIZED WITH SUFFICIENT BENDS TO REDUCE NOISE TRANSFER. OPEN-ENDED TRANSFER DUCTS SHALL HAVE DUCT "BOOT" FOR SOUND ATTENUATION. 21. SUPPLY AIR DIFFUSERS SHALL BE4-WAY BLOW UNLESS OTHERWISE SHOWN BY FLOW ARROWS ON THE DRAWINGS. 22. DIMENSIONS SHOWN FOR DIFFUSERS AND GRILLES ARE NECK DIMENSIONS. 23. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY ARCHITECTURAL REFLECTED CEILING PLAN. 24. LOUVERS SHALL BE FURNISHED AND INSTALLED BY THE GENERAL CONTRACTOR UNLESS OTHERWISE NOTED ON THE DRAWINGS. 25. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR BLANKING OFF ALL INACTIVE PORTIONS OF LOUVERS UTILIZED FOR INTAKE OR DISCHARGE FOR HVAC EQUIPMENT. ENTIRE LOUVERS NOT UTILIZED BY THE HVAC CONTRACTOR SHALL BE BLANKED OFF BY THE LOUVER MANUFACTURER. REFER TO ARCHITECTURAL DRAWINGS FOR LOUVER LOCATIONS AND HVAC DRAWINGS FOR HVAC EQUIPMENT CONNECTIONS. 26. LOUVER PLENUMS SHALL BE PITCHED BACK TOWARD THE BOTTOM OF THE LOUVER. WHERE THIS IS NOT POSSIBLE, PROVIDE DRAIN PIPING, WITH TRAP, FROM BOTTOM OF LOUVER TO NEAREST FLOOR DRAIN. 27. THE HVAC CONTRACTOR SHALL FURNISH ACCESS PANELS TO ACCESS ALL DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD CEILINGS OR IN WALLS. ACTUAL NUMBERS SHALL BE FIELD DETERMINED. 28. EXACT LOCATIONS OF THERMOSTATS, C02 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS AND C02 SENSORS 48" TO THE CENTER OF THE SENSOR AFF. 29. ALL SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 90.1-2007. INTERIOR SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED FOR A MINIMUM VALUE OF R-6. EXTERIOR SUPPLY AND RETURN AIR DUCTWORK SHALL BE INSULATED FOR A MINIMUM VALUE OF R-8, AND PROVIDED WITH WEATHER-PROOF COVER. 30. SIZE REFRIGERANT LINES PER MANUFACTURER'S INSTRUCTIONS FOR ACTUAL LINE LENGTHS AND EQUIPMENT ELEVATIONS INSTALLED. RECORD LINE LENGTHS AND TOTAL REFRIGERANT CHARGE AND REPORT DATA TO ENGINEER FOR LEED ENHANCED REFRIGERANT CALCULATIONS. USE OF HCFC AND CFC REFRIGERANTS PROHIBITED. EXTERIOR REFRIGERANT LINES SHALL BE INSULATED. PROTECT EXTERIOR REFRIGERANT LINE LENGTHS EXCEEDING 3 FEET WITH ALUMINUM JACKETING. 31. ALL PIPING CONTAINING WATER SHALL BE INSULATED AND HEAT-TRACED WHERE EXPOSED TO FREEZING TEMPERATURES. I I I 5 32. HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF CONDENSATE DRAIN PIPING WITH THE PLUMBING CONTRACTOR. HVAC CONTRACTOR SHALL PROVIDE CONDENSATE PUMPS AS REQUIRED WHERE SUFFICIENT SLOPE IS NOT AVAILABLE FOR STANDARD GRAVITY DRAIN, WITH OVERRIDE SWITCH TO POWER DOWN THE ASSOCIATED AIR HANDLING EQUIPMENT IN CASE OF CONDENSATE PUMP FAILURE. CONDENSATE DRAIN PIPING SHALL BE SLOPED FOR GRAVITY AT A MINIMUM OF 1/8" PER FOOT. 33. PROVIDE EXPANSION LOOPS OR APPROVED FLEXIBLE PIPE EXPANSION DEVICES FOR PIPING SYSTEMS WITH OPERATING TEMPERATURES ABOVE 70"F OR BELOW 50"F. PIPE SUPPORTS FOR PIPING SYSTEMS WITH EXPANSION DEVICES OR EXPANSION LOOPS SHALL HAVE ROLLER SUPPORTS. 34. PROVIDE SUPPORTS FOR ALL PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS. STRAP SUPPORTS INSTALLED IN DIRECT CONTACT WITH PIPING OR DUCTWORK SHALL HAVE INSULATION APPLIED ALL AROUND STRAP FOR CONTINUOUS INSULATION VALUE FOR THE PIPE OR DUCT. FOR SUPPORT OF PRE-INSULATED PIPING OR DUCTWORK, USE HIGH-DENSITY INSULATION ON BOTTOM OF PIPE OR DUCT TO PREVENT CRUSHING OR PROVIDE SADDLES OR SHIELDS TO PREVENT CRUSHING OF INSULATION. ADHERE THE SADDLE TO THE INSULATION POSITIONED SUPPORT IT LOCATED IN CENTER OF THE SADDLE WHILE SYSTEM IS AT NOMINAL OPERATING TEMPERATURE. PIPE HANGERS AND SUPPORTS SHALL BE IN ACCORDANCE WITH MSS SP-58. 35. PROVIDE AUTOMATIC AIR VENTS AT ALL HIGH POINTS OF THE CONDENSER WATER PIPING SYSTEM. PROVIDE DRAIN VALVES AT THE LOW POINTS IN THE SYSTEM FOR DRAINAGE. 36. CONTRACTOR TO COORDINATE WITH STRUCTURAL TO PROVIDE HOUSEKEEPING PADS FOR MECHANICAL EQUIPMENT PER TYPICAL HOUSEKEEPING PAD DETAIL. 37. PROVIDE SHUT-OFF VALVES AT ALL PIPE CONNECTIONS TO EQUIPMENT AND FLEXIBLE CONNECTIONS. 38. ALL HANGING EQUIPMENT SHALL BE BRACED IN ACCORDANCE WITH STANDARD 19 OF UFC 4-010-01. ALL OVERHEAD UTILITIES AND OTHER FIXTURES WEIGHING 31 POUNDS OR MORE (EXCLUDING DISTRIBUTED SYSTEMS SUCH AS PIPING NETWORKS THAT COLLECTIVELY EXCEED THAT WEIGHT) USING EITHER RIGID OR FLEXIBLE SYSTEMS TO MINIMIZE THE LIKELIHOOD THAT THEY WILL FALL AND INJURE BUILDING OCCUPANTS. DESIGN ALL EQUIPMENT MOUNTINGS TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN THE DOWNWARD DIRECTION. THIS STANDARD DOES NOT PRECLUDE THE NEED TO DESIGN EQUIPMENT MOUNTINGS FOR FORCES REQUIRED BY OTHER CRITERIA SUCH AS SEISMIC STANDARDS. Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company. . 0 Zo f-0 o"' a:: "' 0 f- ::> z za w oo.::::! (.) >< u. z 0 ii: w Cl SHEET IDENTIFICATION M-001 SHEET 132 OF 209 TYPE B-3 SUBMITTAL .
Transcript
Page 1: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

1

GENERAL MECH. ABBREVIATIONS @ AT & AND AFF ABOVE FINISHED FLOOR

AJC ABOVE CEILING

AC AD ADJ. AFMS AFUE AHU AMCA ARCH AS ASH RAE

ASTM

AUX. AWS AWG

AIR CONDITIONER AUTOMATIC DAMPER ADJUSTABLE AIRFLOW MEASURING STATION ANNUAL FUEL UTILIZATION EFFICIENCY AIR HANDLING UNIT AIR MOVEMENT & CONTROL ASSOCIATION ARCHITECTURAL OR ARCHITECT AIR SEPARATOR AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR CONDITIONING ENGINEERS

AMERICAN SOCIETY FOR TESTING AND MATERIALS AUXILIARY AMERICAN WELDING SOCIETY AMERICAN WIRE GAUGE

- AV AIR VENT

c

-

B

B BD BLDG B/F, B/S BTU,BTUh CAV CCC CD CFM

CLG

CMU

co C02

CONC

CONN.

CONT.

COP

COR

CT

CTF

cu cw CWP

CWR

cws

D

DB, Tdb

Db A DOC DIA DIV ON DP

dP, PO

DSFC DSHP DSS DWG ox EA EAT EER EF EFF EH ELEC EMCS ERU ET ESP EWT EXT EXH EXIST.

BOILER BACKDRAFT DAMPER BUILDING BELOW FLOOR, BELOW SLAB BRITISH THERMAL UNITS, BTUs PER HOUR CONSTANT AIR VOLUME CLOSED CIRCUIT COOLER CONDENSATE DRAIN LINE CUBIC FEET PER MINUTE

COOLING CONCRETE MASONRY UNIT

CLEANOUT

CARBON DIOXIDE

CONCRETE

CONNECT, CONNECTING, CONNECTION

CONTINUED

COEFFICIENT OF PERFORMANCE

CONTRACTING OFFICER'S (OWNER'S) REPRESENTATIVE COOLING TOWER

COOLING TOWER FILTER

CONDENSING UNIT

CONDENSER WATER

CONDENSER WATER PUMP

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

DEPTH

DRY BULB (TEMPERATURE)

DECIBELS

DIRECT DIGITAL CONTROLS DIAMETER DIVISION DOWN DEEP

DELTA PRESSURE, PRESSURE DROP

DUCTLESS SPLIT FAN COIL UNIT DUCTLESS SPLIT HEAT PUMP DUCTLESS SPLIT SYSTEM DRAWING DIRECT EXPANSION EXHAUST AIR ENTERING AIR TEMPERATURE ENERGY EFFICIENCY RATIO EXHAUST FAN EFFICIENCY ELECTRIC UNIT HEATER ELECTRICAL ENERGY MONITORING AND CONTROL SYSTEM ENERGY RECOVERY UNIT EXPANSION TANK EXTERNAL STATIC PRESSURE ENTERING WATER TEMPERATURE EXTERIOR EXHAUST EXISTING

DEG. F ("F) DEGREES FAHRENHEIT FCU FAN COIL UNIT FD FIRE DAMPER, FLOOR DRAIN FFE FINISHED FLOOR ELEVATION FLA FULL LOAD AMPS FOB, FOT FLAT ON BOTTOM, FLAT ON TOP FSD FIRE SMOKE DAMPER FT FOOT OR FEET FT. WG FEETWATERGAUGE

I 2 I 3

GENERAL MECH. ABBREVIATIONS (CONT.) GENERAL MECHANICAL NOTES

GA GC GPM

H HGR HP HR HSPF HTG HTR HVAC HXR HZ

IMC IN INWC INWG IPLV

KW

L LAT LBS LBF/IN2 LWT

MAX MBH MCA MD MERV MECH MFR,MFG MIN MOCP MSS MTD MUW MVD

NO. NPLV NTS

OA OD

PO PH PPM PRV

QTY

RA RG RH RL RM RPM RS

SA so SEER SF SMACNA

SP ss

T'STAT

TEMP TG

THA THR TYP

UH UL

v VAV VD VFD VSD

w WI W/0 WB,Twb WD WG WL WMS WHSP

I

GAGE GENERAL CONTRACTOR GALLONS PER MINUTE

HEIGHT HOT GAS REHEAT HEAT PUMP HOUR HEATING SEASONAL PERFORMANCE FACTOR HEATING HEATER HEATING, VENTILATING AND AIR CONDITIONING HEAT EXCHANGER HERTZ

INTERNATIONAL MECHANICAL CODE INCHE(S) INCHES WATER COLUMN INCHES WATER GAUGE INTEGRATED PART LOAD VALUE

KILOWATTS

LENGTH LEAVING AIR TEMPERATURE POUNDS POUND FORCE PER SQUARE INCH LEAVING WATER TEMPERATURE

MAXIMUM 1,000 x BTUs MINIMUM CIRCUIT AMPACITY MOTORIZED DAMPER MINIMUM EFFICIENCY REPORTING VALUE MECHANICAL MANUFACTURER, MANUFACTURING MINIMUM MAXIMUM OVER CURRENT PROTECTION MANUFACTURER'S STANDARDIZATION SOCIETY MOUNTED MAKE UP WATER (DOMESTIC) MANUAL VOLUME DAMPER

NUMBER NET PART LOAD VALUE NOT TO SCALE

OUTSIDE AIR OUTSIDE DIAMETER

PRESSURE DROP PHASE PARTS PER MILLION PRESSURE RELIEF VALVE

QUANTITY

RETURN AIR RETURN GRILLE RELATIVE HUMIDITY REFRIGERANT LIQUID ROOM REVOLUTIONS PER MINUTE REFRIGERANT SUCTION

SUPPLY AIR SMOKE DAMPER, SMOKE DETECTOR SEASONAL ENERGY EFFICIENCY RATIO SUPPLY FAN SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION STATIC PRESSURE STAINLESS STEEL

THERMOSTAT

TEMPERATURE TRANSFER GRILLE

TOTAL HEAT ABSORPTION

TOTAL HEAT REJECTION TYPICAL

UNIT HEATER UNDERWRITERS LABORATORY

VOLTAGE VARIABLE AIR VOLUME VOLUME DAMPER VARIABLE FREQUENCY DRIVE VARIABLE SPEED DRIVE

WATT WITH WITHOUT WET BULB (TEMPERATURE) WIDE, WIDTH WATER GAUGE WALL LOUVER WIRE MESH SCREEN WATER SOURCE HEAT PUMP

1. THE MECHANICAL SYSTEMS HAVE BEEN DESIGNED TO AND SHALL BE INSTALLED TO COMPLY WITH THE FOLLOWING UFC'S:

• UFC 1-200-01: GENERAL BUILDING REQUIREMENTS • UFC 3-310-04: SEISMIC DESIGN FOR BUILDINGS • UFC 3-400-02: ENGINEERING WEATHER DATA • UFC 3-401-01: MECHANICAL ENGINEERING • UFC 3-410-01: HEATING, VENTILATION, AND AIR

CONDITIONING SYSTEMS (JULY 2013, CHANGE 1, OCTOBER 2014)

• UFC 3-450-01: NOISE AND VIBRATION CONTROL • UFC 4-010-01: DOD MINIMUM ANTITERRORISM

STANDARDS FOR BUILDINGS (FEBRUARY 2012, CHANGE 1, OCTOBER 2013)

2. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS MADE. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.

3. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.

4. AT START OF CONSTRUCTION, THE HVAC CONTRACTOR AND EACH OF THE SUBCONTRACTORS SHALL PREPARE TYPED LISTS OF ALL EQUIPMENT THAT THEY ARE SUPPLYING REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.

5. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

6. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.

7. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT.

8. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.

9. THE HVAC CONTRACTOR SHALL COORDINATE ALL WALL, FLOOR AND ROOF PENETRATIONS WITH THE GENERAL CONTRACTOR.

10. THE HVAC CONTRACTOR SHALL CAULK WITH SILICONE ALL GAPS BETWEEN WALL, CEILING AND FLOOR OPENINGS AND HVAC EQUIPMENT PENETRATIONS. THE HVAC CONTRACTOR SHALL PATCH LARGE GAPS BEFORE CAULKING IS APPLIED.

11. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE SHALL BE PROVIDED BY THE HVAC CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.

12. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND THE PRESSURE CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM, NOT LESS THAN 2 IN.W.G., SEAL CLASS B (LEAKAGE CLASS 6, OR 4% OF THE TOTAL AIR FLOW THROUGH THE DUCT). DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR DIMENSIONS.

13. VOLUME DAMPERS SHALL BE PROVIDED AT EACH MAIN BRANCH TAKE-OFF AND IN SUCH OTHER LOCATIONS WHERE REQUIRED TO PROPERLY BALANCE THE SYSTEM.

14. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE SHOWN.

15. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF ENGINEER. PROVIDE TURNING VANES IN ALL 45" AND 90" SQUARE ELBOWS. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING EDGE. IF TURNING VANES LONGER THAN 36 INCHES ARE REQUIRED, THEY SHALL BE DOUBLE THICKNESS TYPE FOR STRENGTH.

16. FLEXIBLE DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION DEVICE INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.

I

I 4

17. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH. BENDS IN FLEXIBLE DUCTWORK SHALL BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE CRUSHED OR DISTORTED IN ITS FINAL CONFIGURATION.

18. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT. FLEXIBLE DUCT CONNECTORS OR SOUND ATTENUATION DEVICES SHALL BE USED ON CONNECTION TO AIR HANDLING EQUIPMENT TO REDUCE NOISE TRANSFER INTO OCCUPIED SPACES.

19. OPEN-ENDED AIR TRANSFER DUCTS AND OPEN-ENDED RETURN AIR DUCTS IN THE CEILING PLENUM SHALL BE UNOBSTRUCTED FOR A MINIMUM DISTANCE OF 24 INCHES FROM THE OPENING TO ALLOW FOR FREE AIRFLOW.

20. TRANSFER DUCTS SHALL HAVE INTERNAL ACOUSTIC LINING OR BE SIZED WITH SUFFICIENT BENDS TO REDUCE NOISE TRANSFER. OPEN-ENDED TRANSFER DUCTS SHALL HAVE DUCT "BOOT" FOR SOUND ATTENUATION.

21. SUPPLY AIR DIFFUSERS SHALL BE4-WAY BLOW UNLESS OTHERWISE SHOWN BY FLOW ARROWS ON THE DRAWINGS.

22. DIMENSIONS SHOWN FOR DIFFUSERS AND GRILLES ARE NECK DIMENSIONS.

23. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY ARCHITECTURAL REFLECTED CEILING PLAN.

24. LOUVERS SHALL BE FURNISHED AND INSTALLED BY THE GENERAL CONTRACTOR UNLESS OTHERWISE NOTED ON THE DRAWINGS.

25. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR BLANKING OFF ALL INACTIVE PORTIONS OF LOUVERS UTILIZED FOR INTAKE OR DISCHARGE FOR HVAC EQUIPMENT. ENTIRE LOUVERS NOT UTILIZED BY THE HVAC CONTRACTOR SHALL BE BLANKED OFF BY THE LOUVER MANUFACTURER. REFER TO ARCHITECTURAL DRAWINGS FOR LOUVER LOCATIONS AND HVAC DRAWINGS FOR HVAC EQUIPMENT CONNECTIONS.

26. LOUVER PLENUMS SHALL BE PITCHED BACK TOWARD THE BOTTOM OF THE LOUVER. WHERE THIS IS NOT POSSIBLE, PROVIDE DRAIN PIPING, WITH TRAP, FROM BOTTOM OF LOUVER TO NEAREST FLOOR DRAIN.

27. THE HVAC CONTRACTOR SHALL FURNISH ACCESS PANELS TO ACCESS ALL DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD CEILINGS OR IN WALLS. ACTUAL NUMBERS SHALL BE FIELD DETERMINED.

28. EXACT LOCATIONS OF THERMOSTATS, C02 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND

ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS AND C02 SENSORS 48" TO THE CENTER OF THE SENSOR AFF.

29. ALL SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 90.1-2007. INTERIOR SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULA TED FOR A MINIMUM VALUE OF R-6. EXTERIOR SUPPLY AND RETURN AIR DUCTWORK SHALL BE INSULATED FOR A MINIMUM VALUE OF R-8, AND PROVIDED WITH WEATHER-PROOF COVER.

30. SIZE REFRIGERANT LINES PER MANUFACTURER'S INSTRUCTIONS FOR ACTUAL LINE LENGTHS AND EQUIPMENT ELEVATIONS INSTALLED. RECORD LINE LENGTHS AND TOTAL REFRIGERANT CHARGE AND REPORT DATA TO ENGINEER FOR LEED ENHANCED REFRIGERANT CALCULATIONS. USE OF HCFC AND CFC REFRIGERANTS PROHIBITED. EXTERIOR REFRIGERANT LINES SHALL BE INSULATED. PROTECT EXTERIOR REFRIGERANT LINE LENGTHS EXCEEDING 3 FEET WITH ALUMINUM JACKETING.

31. ALL PIPING CONTAINING WATER SHALL BE INSULATED AND HEAT-TRACED WHERE EXPOSED TO FREEZING TEMPERATURES.

I

I

I

5

32. HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF CONDENSATE DRAIN PIPING WITH THE PLUMBING CONTRACTOR. HVAC CONTRACTOR SHALL PROVIDE CONDENSATE PUMPS AS REQUIRED WHERE SUFFICIENT SLOPE IS NOT AVAILABLE FOR STANDARD GRAVITY DRAIN, WITH OVERRIDE SWITCH TO POWER DOWN THE ASSOCIATED AIR HANDLING EQUIPMENT IN CASE OF CONDENSATE PUMP FAILURE. CONDENSATE DRAIN PIPING SHALL BE SLOPED FOR GRAVITY AT A MINIMUM OF 1/8" PER FOOT.

33. PROVIDE EXPANSION LOOPS OR APPROVED FLEXIBLE PIPE EXPANSION DEVICES FOR PIPING SYSTEMS WITH OPERATING TEMPERATURES ABOVE 70"F OR BELOW 50"F. PIPE SUPPORTS FOR PIPING SYSTEMS WITH EXPANSION DEVICES OR EXPANSION LOOPS SHALL HAVE ROLLER SUPPORTS.

34. PROVIDE SUPPORTS FOR ALL PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS. STRAP SUPPORTS INSTALLED IN DIRECT CONTACT WITH PIPING OR DUCTWORK SHALL HAVE INSULATION APPLIED ALL AROUND STRAP FOR CONTINUOUS INSULATION VALUE FOR THE PIPE OR DUCT. FOR SUPPORT OF PRE-INSULATED PIPING OR DUCTWORK, USE HIGH-DENSITY INSULATION ON BOTTOM OF PIPE OR DUCT TO PREVENT CRUSHING OR PROVIDE SADDLES OR SHIELDS TO PREVENT CRUSHING OF INSULATION. ADHERE THE SADDLE TO THE INSULATION POSITIONED SUPPORT IT LOCATED IN CENTER OF THE SADDLE WHILE SYSTEM IS AT NOMINAL OPERATING TEMPERATURE. PIPE HANGERS AND SUPPORTS SHALL BE IN ACCORDANCE WITH MSS SP-58.

35. PROVIDE AUTOMATIC AIR VENTS AT ALL HIGH POINTS OF THE CONDENSER WATER PIPING SYSTEM. PROVIDE DRAIN VALVES AT THE LOW POINTS IN THE SYSTEM FOR DRAINAGE.

36. CONTRACTOR TO COORDINATE WITH STRUCTURAL TO PROVIDE HOUSEKEEPING PADS FOR MECHANICAL EQUIPMENT PER TYPICAL HOUSEKEEPING PAD DETAIL.

37. PROVIDE SHUT-OFF VALVES AT ALL PIPE CONNECTIONS TO EQUIPMENT AND FLEXIBLE CONNECTIONS.

38. ALL HANGING EQUIPMENT SHALL BE BRACED IN ACCORDANCE WITH STANDARD 19 OF UFC 4-010-01. ALL OVERHEAD UTILITIES AND OTHER FIXTURES WEIGHING 31 POUNDS OR MORE (EXCLUDING DISTRIBUTED SYSTEMS SUCH AS PIPING NETWORKS THAT COLLECTIVELY EXCEED THAT WEIGHT) USING EITHER RIGID OR FLEXIBLE SYSTEMS TO MINIMIZE THE LIKELIHOOD THAT THEY WILL FALL AND INJURE BUILDING OCCUPANTS. DESIGN ALL EQUIPMENT MOUNTINGS TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN THE DOWNWARD DIRECTION. THIS STANDARD DOES NOT PRECLUDE THE NEED TO DESIGN EQUIPMENT MOUNTINGS FOR FORCES REQUIRED BY OTHER CRITERIA SUCH AS SEISMIC STANDARDS.

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

.

0 Zo f-0 o"' <(~ •

a:: "' 0 f- ::> z za w oo.::::! (.) >< u.

z 0

ii: ~ w Cl

SHEET IDENTIFICATION

M-001 SHEET 132 OF 209

TYPE B-3 SUBMITTAL

.

Page 2: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

-

c

-

8

1 I

DUCTWORK LEGEND

5 24" g

+ 30x14 + f + ~

t=Ifj ~ ~ 6 6 6

fil+fKI+

----J'----

111111111

f I I f f f f f f UP -

® > >

VDr-

+ + + +

SUPPLY AIR DIFFUSER -FLOW ARROWS INDICATE AIR PATTERN. NO FLOW ARROWS SHOWN INDICATES 4-WAY PATTERN.

RETURN AIR DEVICE

EXHAUST AIR DEVICE

ROUND DUCT. DIAMETER INDICATED IN INCHES.

RECTANGULAR DUCT, SIZE INDICATED IN INCHES, FIRST NUMBER IS SIDE SHOWN

DASHED LINES INDICATE 2" ACOUSTICAL LINER

FLEXIBLE DUCT

90 DEGREE DUCT ELBOW WITH TURNING VANES

RADIUS DUCT ELBOW - ROUND OR RECTANGULAR (MIN. 1.5 RADIUS UNLESS OTHERWISE NOTED)

RECTANGULAR DUCT BRANCH TAKE-OFF WITH 45 DEGREE BRANCH INLET

SQUARE TO ROUND DUCT BRANCH TAKE-OFF WITH 45 DEGREE BRANCH INLET

FLARED SPIN-IN WITH DAMPER AND FLEX DUCT (DIFFUSER CONNECTION)

ROUND DUCT BRANCH TAKE-OFF FROM RECTANGULAR MAIN WITH CONICAL TAP

DUCT SIZE TRANSITION

FLOW ARROW

FLEXIBLE DUCT CONNECTION

SUPPLY OR OUTSIDE AIR DUCT UP

SUPPLY OR OUTSIDE AIR DUCT DOWN

RETURN OR EXHAUST AIR DUCT UP

RETURN OR EXHAUST AIR DUCT DOWN

IN-LINE 90 DEGREE RISE/DROP IN SUPPLY DUCT (RIGHT SIDE IS HIGHER)

IN-LINE 90 DEGREE RISE/DROP IN RETURN DUCT (RIGHT SIDE IS HIGHER)

RISE IN DUCT

DROP IN DUCT

DUCT MOUNTED HUMIDIFIER

VOLUME/BALANCING DAMPER "",___+-----' """'" (LABEL MAY BE OMITTED)

f

BACKDRAFT DAMPER (COUNTER-BALANCED UNLESS OTHERWISE NOTED)

DAMPER TYPE: AD -AUTOMATIC DAMPER MD - MOTORIZED DAMPER

FIRE DAMPER TYPE: FD- FIRE DAMPER, 1 HOUR RATING FD(3)- FIRE DAMPER, 3 HOUR RATING

..,;;.. ..,;;.. SMOKE DAMPER

~~FSD

+ COMBINATION FIRE/SMOKE DAMPER

I

2 I

PIPING LEGEND

---RL---

---RS---

---cws------cwR------CHWS---

--CHWR---

---co------Pe---

-------..;8

~

I

----:J

---llf----

-----111--I __ _ II

v

--+[3-t---

1 I

~~~~

---11><]---

----ll A:: 11-----1 \.1) I

----i~f--------Nf---------1: ~f---------1~--

-----lc*:Jf--------1~1-----

T

£jl FS

----\vl----4:

----'~1----

I

___ _____,0

----l@f----

REFRIGERANT LIQUID

REFRIGERANT SUCTION

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSATE DRAIN

PUMPED CONDENSATE

ELBOW UP

ELBOW DOWN

RISE OR DROP

BRANCH BOTTOM CONNECTION

BRANCH TOP CONNECTION

TEE OUTLET UP

TEE OUTLET DOWN

PIPE CAP

DIRECTION OF FLOW

DIRECTION OF SLOPE DOWN

CONCENTRIC REDUCER

ECCENTRIC REDUCER

UNION

PIPE FLANGE

PIPE ANCHOR

PIPE GUIDE

EXPANSION JOINT

STRAINER WITH SLOWDOWN VALVE, CAP AND CHAIN

GATE VALVE

BALL VALVE

FLOW MEASURING/BALANCING/ SHUT-OFF VALVE

CHECK VALVE

BUTTERFLY VALVE

3-WAY CONTROL VALVE

2-WAY CONTROL VALVE

PRESSURE REDUCING VALVE

PRESSURErrEMPERATURETAP WITH BALL VALVE

FLOW SWITCH

PRESSURE SWITCH

PLUG VALVE

MANUAL AIR VENT

AUTOMATIC AIR VENT

T&P RELIEF VALVE

PRESSURE GAUGE WITH GAUGE COCK

THERMOMETER

FLEXIBLE CONNECTION

CLEAN OUT

FLOOR CLEAN OUT

WATER METER

I

3

MISCELLANEOUS LEGEND

@ HUMIDISTAT

G) THERMOSTAT

® THERMOSTAT/HUMIDSTAT

[!] TEMPERATURE SENSOR

[BJ HUMIDITY SENSOR

® @

@

© Q)

FIRESTAT

DUCT SMOKE DETECTOR

STATIC PRESSURE SENSOR

CARBON DIOXIDE SENSOR

120 VOLT STAND BY POWER JUNCTION BOX PROVIDED BY THE ELECTRICAL CONTRACTOR JUNCTION BOX IS DEDICATED FOR USE BY THE CONTROLS CONTRACTOR.

VARIABLE FREQUENCY DRIVE

CONTROL WIRING

DRAWING NOTE REFERENCE

ROUND

OVAL OR FLAT OVAL

AIR DISTRIBUTION DEVICE TAGS

SUPPLY/RETURN/EXHAUST TAGS

.------ DIFFUSER TYPE

i 400----- AIRFLOW

TRANSFER GRILLE TAGS

..------- DIFFUSER TYPE

i ~2~4xi<':2M4----- FACE SIZE

DRAWING/DETAIL REFERENCE KEY

.---- REFER TO n.--- DETAIL NUMBER--~~

RE:2/M501 M501

L[_ SHEET NUMBER OF DETAIL

NORTH ARROW

PLAN NORTH

TRUE NORTH

HVAC DESIGN CRITERIA

LOCATION: Savannah, Georgia

STANDARD DESIGN CONDITIONS:

WINTER DESIGN DRY BULB (99.6%): 27.4oF

SUMMER DESIGN DRY BULB (0.4%): 95.SOF

SUMMER DESIGN WET BULB (0.4%): 77.2oF

I 4

LATITUDE: 32.12N

LONGITUDE: 81.20W

ELEVATION: 52 FT.

DEHUMIDIFICATION DESIGN CONDITIONS:

DEWPOINT (0.4%):

HUMIDITY RATIO (0.4%):

78.1 OF

146.1

MEAN COINCIDENT DRY BULB (0.4%): 83.5°F

*STANDARD & CRTICIAL DESIGN CONDITIONS FROM ASHRAE FUNDAMENTALS 2013

I

I

BUILDING PRESSURE BALANCE CHART

UNIT O.A. E. A.

4300CFM 3070CFM

850 CFM

TOTAL 4300CFM 3920 CFM

PRESSURIZATION: +380 CFM

I

5

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

6 Zo j-0 u"' ~~ 0 f- ::> z zo w 0 0 :=! U X u..

0:: a. I~

z 0

ti:

~ 0

SHEET IDENTIFICATION

M-002 SHEET 133 OF 209

TYPE B-3 SUBMITTAL

Page 3: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

i>: -¢ ~

0::

o' (/)

z w Cl Cl

<3, I 0 w :;:, 0

"' 0 0

"' ~ ~ ~ 0 '0

D

c

B

§_ A (/)

(')

~ 0

g) 0

"' ~ <;: 0 N

~ ~ til ~ "'o.. 1ij

S" .;;

~ ! ~N ~ (j

®

1

MECHANICAL

@I]

!. ' :·! ' ' 1

1

11 .. FliGHT E'NG!NE:ER:S--, .. . .............. ·: i ~· '.

CFUGHT COMM.

CEQ]

i'

il i

il' !I: il'

....

:,:~~

c·, L ~ i !Zf I :

~ 't'\

c======== Wl

' ' ' '

\_ , II I~ COMSEC/SIPR _!___...-.- :. : ....., ,:I

2

·II·············· ········· ·

. .. ~ "''

~ i ! =o:=t:I====::J : =JZf i. ======u=f==~~~~ r ~ ~ ~ - _, ~ I

u~~~~c=~~r=~~l : I

II -,

I\ , 'lJc , w'Jl Jrp 1 119 1 ; I 11s I

I\ I EOC i

[@ J! - llill~

. K:7l

. J.Q,I

INTEL Ul'"l'"lvf

OJI]

~ I

I./

~ .!~~~n~~ · [ ~ = :::: :~ 'fi:7l

I i ii COMM. n :~ -Fml UTILITY YARD !'"""

rs,..,_,. - - -· - _j \

. ~~(Mf IJ.El

' =·==== w I

.......

(G TRAINfNG/IESTING INSTALLATION 1J3D

COMMAND 0 CENTEWCAT 4 ~

I CiJ.IJ

0 80 '6

3

TRAINING, SCHEDULING &

CURRENT OPERATIONS SUPERVISOR

L1s1J ~ ~ *~·. ·~--BASEOPS

DE]

"\q

STAN.~L

o:EJ c~ J

-~

~~

STORAGE

154 I

.K:JI

NIGHT VISION GOGGLES -

.IV'! !Jill 18Jt=:::r n:,-=tJ.loUIKI

]

"' c.=.==ll'=

: c:=c==================7 ,=,!===== =ct i

i

= i I iJ

MEN

[J§iJ I

Jj

4

;...,

.... ..

~ PPE'

Ul

.r ~~

!1ELMET

,J:isa 1

-~

.. . ....... . ........... I·

~I'--" I <A =€i

!RtF--....... -..... -~~ .............. ··~~~~~~~gL~. ··\··~··· .. ~~

VEST.

mil

BREAK ROOM '---

[ill]

0

LMECH2

~

8

•····@ 0

OVERALL MECHANICAL PLAN SCALE: 3/32" = 1'-0"

~···

!'1- FLIGHT EQUIPMENT

[3IJ

5

II

--r:~m

I EJ t::

~Q ....... ,...u. @ ' . ·~

PACKING 0

• ~ 0 r ~-·· .. I \_SEWING/FABRICATION CJRYlNG TOWER

' DEl miJ

@)

KEY PLAN

® ® 0

PlAN NORTH

EB 8 0 8 16 24 Copyright© 2016 by Pond & Company.

~r-1·-~---~---~-­SCALE: 3/32" = 1'-0"

All rights reserved. No copying or duplication of these document~ 1s allowed without the express wntten agreement of Pond & Company.

d Zo j-0

0~ .. ;;; ~ 0 1- ::> z zo w 00 :d ox u.

z 0

ti: 0:: 0 (/) w Cl

w !.: Cl

z 0

ti: 0:: 0 (/) w Cl

SHEET IDENTIFICATION

M-101 SHEET 134 OF 209

TYPE B-3 SUBMITTAL

Page 4: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

1

® D

c

®

'

]

B

!

!

'CT-1

~~ !

II ~I

UTILITY YARD

QE]

. ~ .... @I]

FLIGHT "'M"'I&

HP-1

D DSS-1

0

II~

2

A FLIGHT COMM.

Dill

A 160

\

1ST SERGEANT

Dill

[7 ~PMANAGERS INSTALLATION I:J3D

COMMAND CENTER/CAT

@I]

MECHANICAL PLAN -AREA A SCALE: 1/8" = 1'-0"

3

OSS/GROUP CHIEF -

CHIEF .. 1 OA!'"'~n." , m~t:n;

I 140 I '

c===-=·==

ADMIN. 1-!J.EI

B 115 ou~o" V AU

4 5

GENERAL NOTES: 1. SEE SHEETS M-001 AND M-002 FOR GENERAL NOTES, ABBREVIATIONS, SYMBOLS, AND LEGENDS. 2. RETURN AIR GRILLES ARE TO BE DUCTED BACK TO MAIN DUCTWORK. 3. FIRE DAMPERS SHALL BE TYPE B UNLESS OTHERWISE NOTED. 4. PROVIDE VOLUME DAMPERS ON ALL BRANCH DUCTWORK AS REQUIRED FOR BALANCING SYSTEMS. 5. DUCT SMOKE DETECTORS SHALL BE FURNISHED BY ELECTRICAL AND INSTALLED BY MECHANICAL. 6. REFER TO ARCHITECTURAL DRAWINGS FOR SECURE WALL LOCATIONS. 7. METAL CONDUIT ON PIPE PENETRATING SECURE WALLS SHALL BE PROVIDED WITH A DIELECTRIC UNION INSIDE THE SECURE PERIMETER, ADJACENT TO THE PENETRATION. 8. PROVIDE CONCRETE EQUIPMENT PAD UNDER ALL FLOOR MOUNTED EQUIPMENT AND OUTDOOR EQUIPMENT. EXTEND PAD 6" MINIMUM BEYOND EQUIPMENT ON ALL SIDES. REFER TO STRUCTURAL DRAWINGS FOR PAD DETAILS.

KEY NOTES: 0 DOOR SHALL BE UNDERCUT FOR TRANSFER AIR. REFER TO DOOR SCHEDULES ON

ARCHITECTURAL DRAWINGS.

COVER OPEN DUCT WITH 1/2" X 1/2" WIRE MESH. @

® PROVIDE SECURITY BARS AT DUCT PENETRATION OF SECURE WALL. REFER TO DETAILS C1/M-504 AND C4/M-504.

0 ® ® (j)

® ® @)

®

75" X 19" X 42" PLENUM BOX.

24" X 18" X 36" PLENUM BOX .

24" X 18" X 24" PLENUM BOX.

TYPE B RETURN GRILLE WITH 14" X 14" DUCTWORK.

TYPE B RETURN GRILLE WITH 12" X 12" DUCTWORK.

RISE IN DUCTWORK.

DROP IN DUCTWORK.

PROVIDE WHITE NOISE MASKERS ON SECURE SIDE OF PARTITION ON DUCTWORK PENETRATING SECURE WALLS/ PENETRATIONS. BASIS OF DESIGN IS DS2400 BY DYNASOUND. PROVIDE FULL SYSTEM WITH ALL REQUIRED COMPONENTS.

@ PROVIDE TRANSFER DUCT ASSEMBLY WITH 8" X 8" TRANSFER DUCT AND TYPE B CEILING GRILLE. REFER TO DETAILA1/M-501.

PROVIDE WHITE NOISE GENERATOR ON SECURE SIDE OF WALL IN ROOM 128 COMSEC/SIPR TO SERVE WHITE NOISE MASKERS LOCATED ON SECURE SIDE OF DUCTWORK PENETRATIONS TO SECURE AREA. BASIS OF DESIGN IS DS1042 BY DYNASOUND. PROVIDE SYSTEM WITH ALL REQUIRED COMPONENETS.

8 0 8 KEY PLAN

PLAN NORTH

EB 16 Copyright© 2016 by Pond & Company.

lil'w-~--~~-- ~~-iiiiiiiiiiiil All rights reseiVed. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company. SCALE: 1/8" = 1'-0"

ci Zo f-0 ()~ .. ~~ ci f- =:> z zo w 00 ~ ox u.

~ . . 5: <( iLi

...,~ ~~ ~ e ~z 0""") .. o 0 ,; >- ..J

~ 0 OJ ll.

0 fi3 ~= w >-"' f- ..:9

z 0

t a: 0

Sl 0

z 0

t 5 (f) w 0

z co t: u~ (!) Z'"' ;:E (f) II .. 0 iii 5: wv "'=> ~--- = w en W O<X>Nz 0 Oo(f)

_, __

n.. ~ (I)<(

<(

Lti 0::: <(

'

SHEET IDENTIFICATION

M-101A SHEET 135 OF 209

TYPE B-3 SUBMITTAL

Page 5: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

c

B

®

®

B 115

V AV

I I

~ h

I II

I TRAINING/TESTING _]'l!r L

[I@] 400

BREAK ROOM

[ill] ~

0 2: ·~

1

TRAINING, SCHEDULING &

CURRENT OPERATIONS

ITill

A b 110

~ -~ ~--·· ........... 8"x10.''

10"x10"

24"x18"

l'i~ f10"x10" 'Mo-' / ' I

'&)/ ~

'I< 150

( rYP. 2)

1045

245

cD

A 150

A 150

VEST. j1 il i'

I .

0

STORAGE

IJEJ

2

A

230 10"0 !'ii'it•'

8"x1 0"

230

BRIEFING ROOM

[J:§I]

10"0

10"0

10"0

I~ 1,= 230

10"0

BASEOPS

!1s6 1

I 400

(TYP. 6)

3

--~~--. . ·· . ,''"? .,

. ~.

WEAPONS A HELMET '1161 i 5s

A j158l i A ·fs ~~ 1 00 ~)IEL!Et+c ·=:rjl:c=a:·~g)K 1 00

B E§jf~~~,.~-.~~., .. =~1 26( r;;:?1 I 16o i

8"x8"' rtfiJ --~ & )~ ; iD ' 6"x6" 1'- «>

··•····@

0

A

._ .. ·- 'f_ 6 ___ o_

''''''''~ ~ '

. , ....

I I

:q~-c--··--"

120 (TYP. 4)

FLIGHT EQUIPMENT

4

,,,. !-· "'" "

= =

H P-2 c::::::J

MECH ENCLOSURE

[ill]

'

'

"

I~ MECii

_..---[ill]

····®

0

5

GENERAL NOTES: 1. SEE SHEETS M-001 AND M-002 FOR GENERAL NOTES, ABBREVIATIONS, SYMBOLS, AND LEGENDS. 2. RETURN AIR GRILLES ARE TO BE DUCTED BACK TO MAIN DUCTWORK. 4. PROVIDE VOLUME DAMPERS ON ALL BRANCH DUCTWORK AS REQUIRED FOR BALANCING SYSTEMS. 5. DUCT SMOKE DETECTORS SHALL BE FURNISHED BY ELECTRICAL AND INSTALLED BY MECHANICAL. 6. REFER TO ARCHITECTURAL DRAWINGS FOR SECURE WALL LOCATIONS. 7. PROVIDE CONCRETE EQUIPMENT PAD UNDER ALL FLOOR MOUNTED EQUIPMENT AND OUTDOOR EQUIPMENT. EXTEND PAD 6" MINIMUM BEYOND EQUIPMENT ON ALL SIDES. REFER TO STRUCTURAL DRAWINGS FOR PAD DETAILS .

KEY NOTES: @ DOOR SHALL BE UNDERCUT FOR TRANSFER AIR. REFER TO

DOOR SCHEDULES ON ARCHITECTURAL DRAWINGS.

@ PROVIDE TRANSFER DUCT ASSEMBLY WITH 14" X 14" TRANSFER DUCT AND TYPE D CEILING GRILLES. REFER TO DETAIL A1/M-501.

®

®

®

PROVIDE TRANSFER DUCT ASSEMBLY WITH 22" X 22" TRANSFER DUCT AND TYPE D CEILING GRILLE. REFER TO DETAIL A1/M-501.

HVAC EMERGENCY SHUT-OFF SWITCH. WHEN IN "OFF" POSITION, SWITCH SHALL DE-ENERGIZE, VIA THE DOC SYSTEM, ALL HVAC FANS AND ALL INTAKE AND EXHAUST MOTORIZED DAMPERS IN THE BUILDING SHALL CLOSE.

SUPPLY DUCTWORK IN BREAK ROOM SHALL BE EXPOSED SPIRAL TYPE PAINTED BLACK TO MATCH ARCHITECTURAL CEILING FINISHES. COORDINATE FINISHES WITH ARCHITECTURAL DRAWINGS.

PROVIDE WALL SWITCH TO MANUALLY OPERATE EXHAUST FAN EF-5. INTERLOCK MOTORIZED DAMPER AT WALL LOUVER L-6TO OPEN WHEN EF-5 IS ENERGIZED.

PROVIDE TRANSFER DUCT ASSEMBLY WITH 16" X 16" TRANSFER DUCT, TYPE B CEILING GRILLE IN LOBBY 102, AND TYPE J GRILLE IN BRIEFING ROOM 103. REFER TO DETAIL A1/M-501.

PROVIDE TRANSFER DUCT ASSEMBLY WITH 12" X 10" TRANSFER DUCT, TYPE B CEILING GRILLE, AND TYPE L SIDEWALL DIFFUSER. REFER TO DETAIL A1/M-501.

® 40" X 39" X 18" PLENUM BOX.

@ TYPE J RETURN GRILLE WITH 16" X 14" RETURN DUCTWORK.

® @

TYPE B RETURN GRILLE WITH 12" X 12" RETURN DUCTWORK.

PROVIDE TRANSFER DUCT ASSEMBLY WITH 8" X 8" TRANSFER DUCT AND TYPE B CEILING GRILLES. REFER TO DETAILA1/M-501.

@ RISE IN DUCTWORK.

@ DROP IN DUCTWORK.

@ PROVIDE TRANSFER DUCT ASSEMBLY WITH 8" X 8" TRANSFER DUCT AND TYPE B CEILING GRILLE. REFER TO DETAIL A1/M-501.

@ PROVIDE FLEX CONNECTIONS IN DUCTWORK PER SMACNA FOR CROSSING EXPANSION JOINT.

A PLAN

NORTH

KEY PLAN ffi 8 0 8 16 .. .,~-~--~--­

SCALE: 1/8" = 1 '-0"

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

ci Zo f-0 (.) :£ .. <("" ' 0::"' 0 f-:::J z zo w oo:::! ox lL

Iii .... " i!: <(

I!: ~ I!: 0:: e ...., 0...., .. o 0

>:: >- --' ~ () co Q.

D fi} ~ =

w !;( Cl

0:: a. a.

w !;( Cl

z 0

ti: 0:: u (fJ w Cl

w :;.: .... <(5' z Ill t:: ~..- 0 (.!) Z(!):;2: 1-11 ··-w(i) > W f!! 0 ;., WN (fJ

> ~ -1.:::'::::-Z o a o w c.. ..- en <C

OJ <(

~ <(

'

SHEET IDENTIFICATION

M-1018 SHE8 136 OF 209

TYPE B-3 SUBMITTAL

Page 6: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

t ' j ~ ,. ;~ :.! \']

d :! ~

j'

~ "1J m OJ

I VJ (/) c OJ s: =i );! r

21312016 3:59:08 PM

C:\Revit Loca~REVIT 201411130050 GAANG Squad Ops\1130050_MECH_GIDDENSC_R14.rvt

co

(fl

~ 0

m

~ co N '

II .... g ~

0>

N I"' -~=> m

rum a.)>(') lCI=t::=o -.o"'...,""O ro ~ =ar"Sj 3"'3_/;l::r-· ((I ~ (i) '§-:::::~:iEO..,­-;::;.::::::1([)@

g,ga[€t\,) "US..st<S: g~;:g~C) o.CPro· o­Qo CD a. Z'<

><oo"O (')~ no o Oroc::o:::::~ 3(1/3:90..

"C 1/! Q) ::::. QO CLI;:E:::I::I(') ~ ::~. arto -~--oo3 " "' ~ ::> "2

"!

w 0 ~::::>'m R1:::::a.Z ~ "1J .., (J)

~ I :;:j ::I: -..! ~ -rn : o ~rn ~ ..... .., ..,

~

-< '"U

>: z

)>

G G

IJJ

G e Wl';r-~-· ---'737S7·-- 7'S--z's ,_ .. ------E-a\·-,·-·-c:::x·'?'±--- ------,-zs7-, ......... rsf·.-- "T1! !

~I ~,. I r···- r · -- -- ---lN--

I

t:;=;:J

W' 'C" ~

·····r= I

.('---+,

I - I

(")

@ G

8 J0 ' ' ~ ~

__ "!t__ _ ________ , .. ,

~ I.

~1.! ~.n

8 · *IH

Ill 'I ~

8---I

/1 l I

c "0

~---

1

I I I I I I 1 r1 I

LU __ ~ I I I I

b

.11 c • c11 ~

j,g, Sf~

fE~. +!!JI II

(00 =it \:==i:i' .... ~M=='=='· C:

~ '~ --,~ ..... ,

ILJ == 111~.-H·· ·- ___ .. ·-- -- .. ---· -- kt\:.[

~ to. {~~

c

+J r

~

~

~

L;=;

I ....

ILY

~ 7

'LJi :l L"

IIIII

.. !-~~-· ...

:! il

.'i ==I

fl Hk <.::::74; ~ §lliO) r\·.' . ~ ··-·-··--· . 0) • ----- '

cr.···· · ===t ,/ ..... , 7'"""·'·"'_.- .· ·.·. -~'j. ..1 ,''p·

' il . ---- .:1 I~Lf ~-- . i!i i ::!

f'iiO -----~~-~~ ill {,=: r+ :t¥1+ est<~& · --c ----,~~ nr11~1 ... · 11... '' I· ~< rom

8~ .~ r ~r

~s: m () I

~ -~ "1J -"1J -z G.> "1J

~ 0 0

0 0

00

G

0

@)-··

r-1 ' '

-= ~ It - ~

~. u

\

.... ·Jj

J~ '81 ,

.1 L~_l I ! .. " ... ,~CJ; I I IIEI! .. , • ....... -~~ IEJ-· ··. .g

/'~ .. •I~ .····~· I ~-~~1~-·· _··ill--' ~ ' /" n _,e-r-r- '-j 1

!!

f­Ull====~'~"

-Jr. -iJ

) L_J

:d_ ....--

'7

_;a __

'

'_1'_1. if

I

·'II~

~

--~-M···-~-~ s·······''' -, .· ' . -

' ~ • !L rr:;; .. • r== . (iffil····· . ' ··~ ..

·-' . ' 1j~~ I ·'' / C,

····l

~ ,lJJI

.. '

~ 'I·

:·)·.

. ,.

::.

'I i ' rn1_i 91.

;. .. , .. _____ ,

~ i

__ ..

-- ·-·-~

'

.. \JII 1 ..

'@I)_ _a .

~ ~ \Jlv ~ 1 1:!

'1 II {,'' I 't II

.. 1 '· ~\ i I, I ! t.r . ...

@ffi 121 121 I® ~ 1- ,- ~l'

I

I ~-

~ f-··-~ ~

J~~·rj ... H • +~± ...... ~ ··· .. ""i'l'·a·" ¥;,,

@) . :1i ~ fcl1 1m jg] . *~ ~ I .1:" -

&,~':2_,8v::;;.;,;c;~=, .. ~;= @~;;;c

EB Z"O

~s;; J!z

C-130 SQUADRON OPERATIONS FACILITY SAVANNAH/HILTON HEAD lAP, GEORGIA

PROJECT NUMBER: XDQU949500

OVERALL MECHANICAL PIPING PLAN

' :i i :. .... _ .. ------

G 0@

GEORGIA AIR NATIONAL GUARD DESIGNED BY: JTW DATE: 02/0112016

SAVANNAH, GEORGIA OWN BY: I CKD BY: I SOLICITATION NO.: CEG JTW

1----~iii!iij~iji~...----l SUBMITTED BY: CONTRACT NO.: I POl.... DRW XDQU949500 . ..... PLOTSCALE:I PLOT DATE: FILE NO.:

3500 P<JrKway t..ane, Suite 600 3132" _ 1, O'"l Norcross, GA 30092 - -Phone {678) 33M740 SIZE· Fax (678} 336.7744 • JOB N0.1130050 ANSI D

--~--

'

@ G

ARK DESCRIPTION DATE IAPPR.IMARK DESCRIPTION

0

.....

N

c..>

.!:>

(Jl

DATE PPR

Page 7: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 8: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 9: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

1 2

1 2

~J ' ' i I !

'I . I v-I

/ I~ '

Ill /I---

- !/ / I ~ I II II

f"CWR II I I

10"x10" ...... nnxan v

= F I I j2g ~ ~

I

®' .:....:

4"CWS_.../

D

22" x 22" EA DUCT

22" x 24" OA DUCT

D

v I I

4"CWS-' I

2" cws ..... "I'--

CWP-2 ERV-1

2" CWR

i (fl); ll ~ I

I

! . .,. . . . 0 •• . .

I

c MECHANICAL ROOM 133 SECTION SCALE: 1/4".= 1'-0"

® I

B

i;· I ' v -4 Jll

I R + {"' I

) 4" cws, • _:- ;-4"CWR

l> I C> . CT-1 I

) -

'

R • -r-1-I k JO I < I \-

' . ~ . . I I . ~-. ' .

' .

•I. .·.

.·•.' ·j i

·' ""' ' I I I ,.

~ .; ~

a:: o' (/} z w a a

~· () w ::;: o' "'

COOLING TOWER SECTION SCALE: 1/4" = 1'-0"

0 0

"' ~ ~ '" c. 0

" ., A ::> C' (/}

(!) z ~ (!) 0

"' 0 0

"' ~ ~ " 0 N

::;: 1-0.. ~ .... "' a:: g ""' .,

" I? .3 <0

"" ~

~ 0

~ a:: .,.; (;) ()

8" x 30" OA DUCT

22" x 30" OA DUCT

SPRINKLER RISER (REFER TO FIRE PROTECTION DRAWINGS)

k k .

/

K 1<. ~-

i/

, I

' . . -.. . . . . I . -':· <_~

3

22"x 22" EA DUCT

24"x 22" OA DUCT

4

----- 18" x 20" SA DUCT FROM WSHP-12

14" x 16" RA DUCT TO WSHP-11

18" x 20" RA DUCT TO WSHP-12

~b~L~~~u=m:= 14" x 14" SA DUCT FROM WSHP-11 I~ 8" X 8" OA DUCT

MECHANICAL ROOM 133 SECTION SCALE: 1/4" = 1'-0"

- ·r·--· :·-··r--·r"··· -

L-2 -

ll I Jl I I

* I I I '

CT-1 I I I I

I 1114 -4"CWR I I I I I

' 1 1 f I

I I 1 l I -4"CWS I 1 ! I I I II I

~ I I I I

tttt:

I ... ' ,,. .

I . .i ' ' . ·'.

. 'I/

r . -' '

COOLING TOWER SECTION SCALE: 1/4" = 1'-0"

5

GENERAL NOTES: 1. SEE SHEETS M-001 AND M-002 FOR GENERAL NOTES, ABBREVIATIONS, SYMBOLS, AND LEGENDS. 2. DUCT SMOKE DETECTORS SHALL BE FURNISHED BY ELECTRICAL AND INSTALLED BY MECHANICAL. 3. PROVIDE AIR VENTS AT ALL HIGH POINTS AND DRAIN VALVES AT ALL LOW POINTS IN THE CONDENSER WATER PIPING SYSTEM. 4. HVAC CONDENSATE PIPING SHALL BE INSULATED. 5. REFER TO SHEET M-701 FOR CONDENSER WATER PIPING SCHEMATIC. 6. PROVIDE CONCRETE EQUIPMENT PAD UNDER ALL FLOOR MOUNTED EQUIPMENT AND OUTDOOR EQUIPMENT. EXTEND PAD 6" MINIMUM BEYOND EQUIPMENT ON ALL SIDES. REFER TO STRUCTURAL DRAWINGS FOR PAD DETAILS. 7. PROVIDE INERTIA BASE FOR ALL BASE MOUNTED PUMPS.

4 0

'JI--• ---SCALE:

4

1/4" = 1'-0"

8

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

>-<( 1--

d Zo o-o (.) :£ .. <( .,. .

a:: "' 0 1- :J z zo w 00:::! ()X u_

::J(90 uO::o <(OLD u_LUO> (/)c.9'a; z - ::J o~a --Cl

~~~ LU:CO:: 0.. LU OZlD zO~ ot-::J o:::::!z 0~1-<(:C{) ::J<(LU oz-, (f)Zo a <CO:: M>O.. ~<( 0(/)

(/) z 0 1-() LU (/)

..J

(5 z <( :c () LU ~

w !;( a

z 0

ti: 1i" () (/} w a

0:: 0.. 0..

w !;( a

SHEET IDENTIFICATION

M-301 SHEET 140 OF 209

TYPE B-3 SUBMITTAL

Page 10: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

1

= D

=

c

WSHP-"-_.,-

B

I<'\ fEH~ 2" CWR

2"CWS

MD

" 3/4"CWR 3/4" cws ~ {o

16"x16"

+

16"x14"

16"x16"

'

MD

WSHP-9

2

MECHANICAL ROOM 172 SECTION SCALE: 1/4" = 1'-0"

I li ·- t

;;;;;

12"x14"--...._

14"x16"--... I'

- __,_, r---. ... 14"x14"- ,-

1"-- ---.~

~

WSHP-6- -

L ; l

I ~ .,

J- /.r--a"x8"

+ ,¥lll'

I , ,I' I' ! r

IW "'""·.,-:---

' I

"'. 7 I'. ·I

1"CWS

MECHANICAL ROOM 172 SECTION SCALE: 1/4" = 1'-0"

3

WSHP-5

0

n ,J EF-5

f \_0' -MD

I

I

II 1

I 140

' I

1

0 I

ill! f I

I

~~!=====-~==========~=

I I

\

I II I H

b ~ _x {o

140

;10"x12"

.

I I

I

I

. ' ;: ..

DRYING TOWER 171 SECTION SCALE: 1/4" = 1'-0"

4 5

GENERAL NOTES: 1. SEE SHEETS M-001 AND M-002 FOR GENERAL NOTES, ABBREVIATIONS, SYMBOLS, AND LEGENDS. 2. PROVIDE AIR VENTS AT ALL HIGH POINTS AND DRAIN VALVES AT ALL LOW POINTS IN THE CONDENSER WATER PIPING SYSTEM. 3. REFER TO SHEET M-701 FOR CONDENSER WATER PIPING SCHEMATIC. 4. PROVIDE CONCRETE EQUIPMENT PAD UNDER ALL FLOOR MOUNTED EQUIPMENT AND OUTDOOR EQUIPMENT. EXTEND PAD 6" MINIMUM BEYOND EQUIPMENT ON ALL SIDES. REFER TO STRUCTURAL DRAWINGS FOR PAD DETAILS.

KEY NOTES: (D RUN 18" X 18" EA DUCT DOWN TO 12" BELOW ROOF DECK.

COVER OPEN DUCT WITH 1/2" X 1/2" WIRE MESH.

0 ®

20" X 25" X 24" PLENUM BOX.

RUN 6" DRYER EXHAUST DUCT FROM DRYER TO EXTERIOR WALL AND TERMINATE WITH WALL CAP.

PROVIDE FLEX CONNECTIONS IN DUCTWORK PER SMACNA FOR CROSSING EXPANSION JOINT.

4

IJ8• -- 0 4 8

~iiiiiliiiiiii~!iiiii--SCALE: 1/4" = 1'-0" Copyright © 2016 by Pond & Company.

All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

ci Zo j-0 0~ .. ~"" . O:m 0 1- ::> z zo w Oo-' ox Li:

(/) z 0 i= u w (/) _j

(5 z :i u w 2

w ';;: 0

z 0

!i: a: (.) UJ w 0

z 0

!i: a: 0

f3 0

SHEET IDENTIFICATION

M-302 SHEET 141 OF 209

TYPE B-3 SUBMITTAL

Page 11: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

M-301 -

c

B

1

..... (z ~-301 -,..

. ' ' '"

~ .... - /~ IV -"OMn. IJ.L ... ~ F//l":: :::: :::: -:- - "x16"

® xx >'r··~-·~-~~-E~· ~l..:..~=~·A"v14" I/ lin' Y "V -::- ... A

~zsj~~~-H ' 1 ' -18"x20" W /l'x I 'x_ /: .

WSI-'o • Y 1 ·18"x20" '"'n\ '<::n\ ' / ,~~;

-~''''''''

!. ................... 1 - lVI

' ..

MECHANICAL ROOM 133 HVAC PLAN SCALE: 1/4" = 1'-0"

M-302

16"x16"_____,/

MECHANICAL ROOM 172 HVAC PLAN SCALE: 1/4" = 1'-0"

2

0

< ?

< <

.

X X ,· X X\ X'

\

3 4

14 1 lfi!:DHJl, ................................................. .

4"CWS

XX> XX> XX

- _@ fi=====F(~2~X3)~!fi:~~ ~~~': R~~~ ~ D D r.l r !jQJ ! ! :-}V ':..-. @>-

2" CWR.-f" ! I krrn··io";::~~ 4"CWR f fft V'

2" cws-1' I ,( r ,---a"~ BP-1_.% I ' ' ~- ERV-1 -- I f--'

I 0 '-- CWP- f- v /2" cws

"-... -........___3" cws

r- ............... - -3"CWR

[·~~~­: I ~~~--~£~~~~ ~ ~

I \__ CWP- "

I -~~_j=f====fiF====r= r,lftE:=~1 ~1/~2'~' cws ,!1 4" CWR ID liiT - ~.- • 1 1/2" CWn

..... '"---4" cws

~e1 . ~~~~-----11 ___ ~-~;;;;;;· ;;;;;;;;;;;;;;JJ_ ____ _.; ~~· CWR .""'-.... -:+-: Ei-~--=~---····J··-~=--=--="~-~-~--~~mHt'~·-TUllz:::-~-~ ' ~ • L..... - IVi I '-WSHP-11 0

0 MECHANICAL ROOM 133 PIPING PLAN SCALE: 1/4" = 1'-0"

1"CWR . ....-...,

2" cws

2"CWR

WSHP-8

D WSHP-5

WSHP-6

1"CWS

2"CWR

2"CWS

11/2" CWR

~~~1 1/2" cws

MECHANICAL ROOM 172 PIPING PLAN SCALE: 1/4" = 1 '-0"

5

GENERAL NOTES: 1. SEE SHEETS M-001 AND M-002 FOR GENERAL NOTES, ABBREVIATIONS, SYMBOLS, AND LEGENDS. 2. ALL FIRE DAMPERS SHALL BE TYPE B UNLESS OTHERWISE NOTED. FIRE DAMPER RATING SHALL MATCH WALL RATING. 3. LOUVERS SHALL BE MOUNTED MINIMUM 10'-0" ABOVE GRADE PER ATFP REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS. 4. DUCT SMOKE DETECTORS SHALL BE FURNISHED BY ELECTRICAL AND INSTALLED BY MECHANICAL. 5. PROVIDE AIR VENTS AT ALL HIGH POINTS AND DRAIN VALVES AT ALL LOW POINTS IN THE CONDENSER WATER PIPING SYSTEM. 6. HVAC CONDENSATE PIPING SHALL BE INSULATED. 7. REFER TO SHEET M-701 FOR CONDENSER WATER PIPING SCHEMATIC. 8. PROVIDE CONCRETE EQUIPMENT PAD UNDER ALL FLOOR MOUNTED EQUIPMENT AND OUTDOOR EQUIPMENT. EXTEND PAD 6" MINIMUM BEYOND EQUIPMENT ON ALL SIDES. REFER TO STRUCTURAL DRAWINGS FOR PAD DETAILS. 9. PROVIDE INERTIA BASE FOR ALL BASE MOUNTED PUMPS. 10. ALL PIPING IN MECHANICAL ROOMS SHALL BE PROTECTED WITH A PVC OR METAL JACKET UP TO 6 FEET . 11. PROVIDE AUXILIARY DRAIN PANS UNDER ALL VERTICAL WSHP'S. REFER TO DETAIL A3/M-503.

KEY NOTES:

(D CLEAR AREA INDICATED IS REQUIRED FOR SPRINKLER PIPING BUILDING ENTRANCE. REFER TO FIRE PROTECTION DRAWINGS.

HEAT TRACE OUTDOOR CONDENSER WATER PIPING AND MAKE-UP WATER AT 8 W/LF. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL CONTRACTOR. PROTECT PIPING WITH UV RESISTANT JACKET.

SUPPORT PIPING WITH PIPE STANDS.

COVER OPEN END DUCT WITH 1/2" X 1/2" WIRE MESH.

G)

0 ® ROUTE BOILER'S INTAKE AND VENT PER MANUFACTURER'S

RECOMMENDATIONS. PROVIDE INTAKE AND VENT OF MATERIAL RECOMMENDED BY THE BOILER MANUFACTURER AND APPROVED BY LOCAL CODES.

® RUN 4" BOILER INTAKE AND VENT THRU EXTERIOR WALL AND TERMINATE WITH WITH MANUFACTURER'S VENT TERMINATION KIT.

FIELD ROUTE CONDENSATE PIPE FROM ERV-1 AND WSHP'S TO NEAREST FLOOR DRAIN. PIPE SHALL BE MINIMUM FULL SIZE OF EQUIPMENT DRAIN CONNECTION. REFER TO PLUMBING DRAWINGS FOR FLOOR DRAIN LOCATIONS.

® PROVIDE EMERGENCY SHUT-DOWN SWITCH TO SHUT DOWN BOILER.

® RUN 30" X 22" OA DUCT DN FROM ROOF HOOD RH-1 AND CONNECT TO ERV-1.

RUN BOILER CONDENSATE DRAIN LINE TO NEAREST FLOOR DRAIN. DRAIN LINE SHALL PASS THROUGH ACID NEUTRALIZATION KIT PRIOR TO DISCHARGING TO FLOOR DRAIN.

@ PROVIDE 4" COOLING TOWER BYPASS WITH 3-WAY CONTROL VALVE.

@ 25" X 20" X 24" PLENUM BOX.

@ 28" X 29" X 24" PLENUM BOX.

@ SUSPEND HORIZONTAL EXPANSION TANK FROM STRUCTURE.

@ RUN 30" X 8" MAKE-UP AIR DUCT DOWN FROM ROOF HOOD, RH-1. TERMINATE DUCT 12" BELOW ROOF DECK.

@ RUN 6" DRYER EXHAUST DUCT FROM DRYER TO EXTERIOR WALL AND TERMINATE WITH WALL CAP.

® FIELD ROUTE 2" COOLING TOWER DRAIN LINE TO NEARBY HUB DRAIN. TERMINATE DRAIN LINE AT HUB DRAIN WITH AIR GAP FITTING. REFER TO PLUMBING DRAWINGS.

RUN 2" MAKE-UP WATER LINE FROM COOLING TOWER AND CONNECT TO DOMESTIC WATER DOWNSTREAM OF BACKFLOW PREVENTER. REFER TO PLUMBING DRAWINGS FOR CONTINUATION. REFER TO DETAIL A1/M-505.

@ PROVIDE FLEX CONNECTIONS IN DUCTWORK PER SMACNA FOR CROSSING EXPANSION JOINT .

@ BAS PANEL LOCATION. CONTROLS CONTRACTOR SHALL VERIFY ACTUAL QUANTITY OF PANELS REQUIRED. COORDINATE WITH ELECTRICAL FOR REQUIRED POWER AND DATA OUTLETS. PLAN

NORTH

4 0 4 8 EB lill'J-§j.-~-~-~~---

SCALE: 1/4" = 1'-0"

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

ci Zo f--0 0~ .. ;::! ~ ci I-:::> z zo w 00::::! ox u.

(/) z :5 Q_

...J

<3 z <( :r: () UJ :2 0 UJ (9

~ z UJ

z 0

ti: ;;:: () (/) w 0

z 0 ;:: "-5 (/) w 0

SHEET IDENTIFICATION

M-401 SHEET 142 OF 209

TYPE B-3 SUBMITTAL

Page 12: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

c

B

~

"' ;;: u' (/)

z w 0 0 a II () w ::. o' "' 0 0

"' ~ ~ -.;; 0. 0 ., "' A " 0' (/)

{!) z ~ Cl 0

"' 0 0

"' ~ ~ "" ;; "' ::. 5 a.

N w 0 t>:

~ 'iii " c'i 0

...J

"' "' ;; > ~ & f;j zj

BUILDING WALL OR FLOOR

FILL OPENING WITH GROUT OR SEALANT

DEPENDING ON BUILDING MATERIALS

PENETRATED.

1

DUCT ~

1/2" TO 5/8" ANNULAR SPACE-PACK WITH FIBERGLASS MATERIAL

--'--........., '----'-- ~ SEAL ALL AROUND WITH RESILIENT NON-HARDENING SEALER (TYP.).

@) ?c~~~.fsENETRATION DETAIL

MOUNTING SCREW (TYP) INTO METAL STUD/SUPPORT

GYP. BOARD

19==/ ~

DIRECTIONAL VANES

REGISTER DAMPER, IF APPLICABLE

DUCT

DUCT FLANGE, ALL SIDES

METAL STUD/SUPPORT

@) ~~~E~-~LL GRILLE DETAIL

DIMENSIONS INDICATED IN PLAN VIEW ARE INSIDE CLEAR

[]] []] r ACOUSTICAL LINING - NON-FIBROUS

[]]rWALL

[]] ~~=[]]=~t=

CEILIN~ ....L....L.....11J,.-L--'-• + t -GRILLE ELEVATION VIEW GRILLE

@ Yc~~~~ER DUCT DETAIL

2 3

1" MIN. ON TOP AND BOTTOM

MAIN DUCT

SEAL ALL AROUND

....-- ADJUSTABLE ELBOW RINGS

EQUAL TO REQ'D BRANCH DUCT DIA. SEAL

ALL AROUND

@ ~~~~~L BRANCH TAKE-OFF FITTING DETAIL

r--- VOLUME DAMPER

SECURE FLEX DUCT TO TAP AND DIFFUSER WITH 1/2" GALVANIZED ADJUSTABLE BAND CLAMP OR NYLON STRAP.

SQUARE TO ROUND DUCT SUPPLY DUCT

INSULATED FLEX DUCT (5'-0" MAX.)

PROVIDE INSULATION ON

---.----~ TOP OF DIFFUSER (U.N.O.)

SUPPLy L CEILING DIFFUSER

@ ~~~~;_y DIFFUSER DETAIL

STRAP HANGERS (TABLE 1)

w

TABLE 1

RODS (TABLE 2)

L

.-------:?1

NOTE2

~- ALTERNATE

STRAP HANGERS (PAIR) SPACED NUTS W+D 1 0"-0" 8'-0" 5' ... Q"

NGLE (TABLE 3)

MAX. MAX. MAX. OR LESS

72" 1"x22 GA 1"x22 GA 1"x22 GA L

96"

120"

168"

192"

192+"

1"x20 GA 1"x22 GA

1"x18 GA 1"x22 GA

1"x18 GA

1"x16 GA

SPECIAL ANALYSIS REQUIRED

TABLE2

RODS (TABLE 2)

NGLE (TABLE 3)

NUTS

ALLOWABLE HANGER LOAD MAX. TABLE 3 TRAPEZE ANGLE LOAD MAX.

STRAPS LBS.

2-1"X22 GA 520

2-1"X20 GA 640

2-1"X18 GA 840

2-1"X16 GA 1400

RODS LBS. L 2"x2"x1/4" 2-1/2"x2-1/2"x1/4"

2-1/4" DIA. 540 36" 1200 LBS 1940 LBS

48" 1160 LBS 1900 LBS 2-3/8" DIA. 1360 60" 1060 LBS 1800 LBS 2-1/2" DIA. 2500 72" 900 LBS 1640 LBS 2-5/8" DIA. 4000 84" 660 LBS 1400 LBS

2-3/4" DIA. 6000 96" 320 LBS 1060 LBS

NOTES:

1. TABULATED DATA FROM SMACNAALLOWS FOR DUCT REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD.

2. PROVIDE HIGH DENSITY INSERT AT TRAPEZE FOR INSULATED DUCTS.

RECTANGULAR DUCT HANGERS DETAIL SCALE: N.T.S .

4

------ 1" MIN. ON TOP AND BOTTOM

-------- 1/4 BRANCH DUCT WIDTH, BUT MIN. 4"

1~- EQUAL TO REQ'D BRANCH DUCT DIMENSIONS

5

SUPPLY

~r _/l.r--

0,.

RETURN/EXHAUST ~

45°~ ----J'-

"<: RECTANGULAR BRANCH ~ ~BRANCH DUCT DUCT

1\1\1 -- BALANCING DAMPE R

I H

l

45°

ROUND-...._ BRANCH DUCT

A v

SUPPLY _/l.r--

RETURN/EXHAUST ~I'--

I \ I \ I ----BALANCING DAMPER

NOTE: STANDARD BELLMOUTH FITTINGS (WITH R=D/5) MAY BE SUBSTITUTED FOR BRANCH FITTINGS

CS BRANCH DUCT CONNECTION DETAIL SCALE: N.T.S.

RADIUS = H, MINIMUM

CURVED ELBOW UNLESS NOTED OTHERWISE ON PLANS, ANGLES SHOWN SHALL APPLY

15 DEGREE MAXIMUM '----.....1.J. --

15 DEGREE MAXIMUM

DIVERGING DUCT TRANSITION UNLESS NOTED OTHERWISE ON PLANS, ANGLES SHOWN SHALL APPLY

20 DEGREE MAXIMUM 30 DEGREE MAXIMUM

20 DEGREE MAXIMUM 30 DEGREE MAXIMUM

TRANSITION AT EQUIPMENT UNLESS NOTED OTHERWISE ON PLANS, ANGLES SHOWN SHALL APPLY

--...,.~~.. 20 DEGREE MAXIMUM

20 DEGREE MAXIMUM

CONVERGING DUCT TRANSITION UNLESS NOTED OTHERWISE ON PLANS, ANGLES SHOWN SHALL APPLY

@) ?c~~~-T~RANSITIONS DETAIL Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

"' ci ~ z

ci 0 z ~ 0 Zo

~ ~ f-.0 u"'

0 f- ~* w 0 f-::J

!;;: :J za 0 8~ 0 UJ

~ ~~ ~ t>: ...., 0..., 0

:;.: "' ~ u Ill 0 0 w w

~ I: z Cl ~ Cii ZCJ

~w £D

w ::J 0 o<J (/)

0 t>: <!. ::J <!. Cl (9 ;:;! t>:

0 z 0 w

~ {!)

:C z <!. t>: z < z

<!. <!. ~ (9

t>: (/)

0 w {!)

ci z ~ u: w ~ t ...J a. w _,~

<<;> U· (/)~

1- II o~

-'"' a.~

8 w $ "5

w ~ z

w !;;: 0

z 0

5: tr ~ w 0

z 0

f iY u ffl 0

0 w-N<l> ... z (f)<(

0 ~~~~Nf!

j~~~ ~ ~ ~ 0

<')~$'~ ~ lli~~6 o.. e <11-u;. z g~_gi~ «>ZO..W..--,.

(f) ...J

~ w Cl ...J

C1 ~ I (.) w ~

SHEET IDENTIFICATION

M-501 SHEET 143 OF 209

TYPE B-3 SUBMITTAL

Page 13: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

c

B

~ .,f

0:: o' en z w 0 0

~I 0 w ::;: o'

"' 0 0

"' ~ ~ .. 0. 0 "0

"' A " 0" en (!)

~ (!) 0

"' 0 0

"' ~ ~ " ~ 0

"' ::;: ~ <l.

"' w

0 £>: r.: 'iii 0 g ,:.;

....1 <D

"' 0 >

" ~ C(

~ (j

1

12" INTEGRAL WALL SLEEVE BY FIRE DAMPER MANUFACTURER, SLEEVE TO BE 18 GAMIN. WITH 3/16" EXPANSION CRACK ON THREE SIDES BETWEEN SLEEVE AND STRUCTURE, SEAL EXPANSION JOINT WITH FIRE RETARDANT NON-HARDENING MASTIC

2

~-WALL

.----- RETAINING ANGLES ALL FOUR SIDES, RETAINING ANGLES BY FIRE DAMPER MANUFACTURER

INSULATED L!...::~===j~~~~~L-=-==- STRAP FASTENING TO ALLOW

,~~~~~~-rlJ MANUAL TESTING OF DAMPER

ACCESS DOOR --+---"' STRAP FASTENING TO BE ACCESSIBLE THRU ACCESS PANEL

CURTAIN TYPE OUT OF THE AIR STREAM FIRE DAMPER

L

7

HANG FROM TRUSS STRUCTURE ABOVE

FLEXIBLE J CONNECTION

~

r 'n

3

,. ANGLE SUPPORT

HANGER ROD

r 'n

=

AIRFLOW

VIBRATION ISOLA TOR (TYP)

FLEXIBLE

'

4

2"X2"X1/4" CLIP

INSULATION IF APPLICABLE--....

CONDENSER WATER PIPE--..._

5

r--- CONCRETE FLOOR SLAB

WALL SLEEVE _________ _) '---BREAKAWAY JOINT (TYP)

'---EXTERNAL DUCT INSULATION (TYP)

L___ UL-APPROVED FIRESTOP FOAM INSULATION BETWEEN PIPE AND SLEEVE

NOTES:

1.

2.

3.

FIRE DAMPER RATING SHALL MEET OR EXCEED THE FIRE-RATING OF THE BARRIER IN WHICH IT IS INSTALLED, 1 1/2 HR MINIMUM RATING.

PROVIDE FIRE DAMPER FOR ROUND DUCT OR USE TRANSITIONS FOR ROUND TO SQUARE DUCT.

STATIC FIRE DAMPERS ARE PREFERRED IN SYSTEMS WHERE FANS AUTOMATICALLY TURN OFF IN CASE OF FIRE. DYNAMIC FIRE DAMPERS ARE REQUIRED IN ANY SYSTEM WHERE FANS ARE NOT AUTOMATICALLY STOPPED IN CASE OF FIRE. WHERE ACCESSIBILITY IS EXTREMELY LIMITED, MULTI-BLADE OR MOTOR-OPERATED FIRE DAMPERS SHALL BE USED.

VERTICAL FIRE DAMPER DETAIL SCALE: N.T.S.

INDOOR UNIT

WALL MOUNTING BRACKET FURNISHED BY FCU MFGR.

WALL SLEEVE WITH CAPS FURNISHED BY FCU MFGR.

3/4"0 DRAIN LINE TO FLOOR SINK

TOP OF UNIT± 8' AFF

CONNECTION CABLE TO THERMOSTAT

THERMISTOR CABLE

j INSULATED RS AND RL REFRIGERANT LINES

AIRFLOW

4" THICK CONCRETE PAD

POWER&HIGH VOLTAGE CONTROL TO INDOOR UNIT

OUTDOOR UNIT. SECURE TO CONCRETE PAD.

(MIN. 4" EXTENSION ALL SIDES)

DUCTLESS SPLIT SYSTEM DETAIL SCALE: N.T.S.

• A ..

A

• A

• A

rll

61N. MAX

NOTE:

KEYED NOTES:

G) MOUNTING PLATES.

@ ANGLE IRON.

@ INTERMEDIATE SUPPORT BRACKET. SPACING AS REQUIRED TO SUIT PIPE SIZES.

@ STEEL PROTECTIVE JACKETS OVER POLYURETHANE PROTECTED HARDWOOD INSERTS. LENGTH OF INSERTS SHALL NOT BE LESS THAN 8.0 IN.

@ U BOLT CLAMP

@ANCHORS, 4 PER PLATE.

1. THIS DETAIL WITH PIPE INSULATION AND PROTECTIVE JACKET SHALL ALSO APPLY TO NON-INSULATED PIPES.

2. EMBED ANCHORS IN GROUTED CMU CELLS. 3. MOUNT TOP OF BRACKET APPRO X. 6 IN. A.F.F. 4. HORIZONTAL SPACING BETWEEN BRACKETS IS NOT TO

EXCEED 41N. AT LEAST TWO BRACKETS ARE TO BE USED FOR MULTIPLE PIPES.

NOM. SIZE THRU 3/4" PIPE 7FT.

TUBING 5 FT.

@) ~~E ~~OOR PENETRATION

1/2" DIA. HANGER RODS W/36" MAX SPACING ON EACHC HANNEL

PROVIDE INS SHIELD & INS ALL PIPING

-

_,_,I

ULATION ERTFOR

MAXIMUM PIPE/TUBING SUPPORT SPACING, FEET

1 1-1/4 1-1/2 2 2-1/2 3 4 5 6 7 7 9 10 11 12 14 16 17 6 7 8 8 9 10 12 13 14

'

I[]JJ .. T

8 10 12 14 19 22 23 25 16 - - -

rBAND

11 1-5/8" 12 GAGE CHANNEL

R 2" X 2" X 1/4" ANGLE 0

16 18 20 24 27 28 30 32 - - - -

VERTICAL PIPE SUPPORT DETAIL NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE

SCALE: N.T.S.

REMOVABLE WEATHERPROOF

HOUSING ---f-=-=-=-:i===~~~~~;=JT~l

FAN MOTOR WITH VIBRATION ISOLATORS

CENTRIFUGAL FAN-----..

SEE ARCH DRAWINGS FOR ROOFING DET

L

CONTINUOUS BIRD SCREEN

STANDARD CURB BASE, FASTEN PER MANUFACTURERS RECOMMENDATIONS

UPBLAST POWER ROOF VENTILATOR DETAIL SCALE: N.T.S.

PIP

TYPICAL PIPE SUPPORT DETAIL SCALE: N.T.S.

I 1/

lNG~ //// ..

I ' '

~~) 7

...

/////

' " I

1/

"3M-BARRIER" / INSTALL PERM

RECOMMENDA

FIRE RATED PACKING, ANUFACTURER'S TIONS.

a) ~ SCHEDULE 40 B LACK STEEL

SLEEVE, GROU T SOLID INTO WALL.

~ ALL FIRE RATEDW

PIPE FIRE RATED WALL PENETRATION SCALE: N.T.S.

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

<D ci 0 z ci z ~ 0 Zo

S2 ~ f-0 o"' "' ~~ 0 1-

Lii (} 1-::J

~ :J za 0 oo if) ox

ii~ s ~ C( .., 0""" 0

;;: "' ;;: () al

al Q 0 w w ;;: I= z (!) al

~ (ij Z(!) ;;:w al w ::J

0 oO if)

0 C( <( ::J <( (!)

~ __, <( z 0 0 w

~ (!)

;f z C( z <(

~ ~ (!) ;;s C( 0 w (!)

ci z ~ u: Lii ~ 0

b ....1 <l.

w ..J, <(0 () -· "'~ 1- II 0' -'"' <l.~

0 0 ~

·~

Lii ~ z

z 0

~ oc 0 if) w Q

z 0

~ oc 0

f:3 Q

0 w-NOO _z 00<(

-~('.(~ 1ijg~~ g ...J-n«>~'-- 0

~<(~<b g ~C:.~-~ ~ ~ ~-;-~ g ~~_g'i~ «>Z ll...u.....,

SHEET IDENTIFICATION

M-502 SHEET 144 OF 2o9

TYPE B-3 SUBMITTAL

Page 14: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 15: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 16: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

1

D

-

c

-

B

1: -"' ~ rr (.)I en z w 0 0

~I (.) w ~I "' 0

' 0 (") ~

~

.,;; 0. 0 '0

"' " 0' A en (') z

~ 0

"' 0 0 (") ~

~ .. ~

0 N

::;: ~ a. "'

w 0 ~ ,;.:

"' 0 0 ,;; 0 -'

"' "" ~ > 0 " ~ $. N (.)

I 2 I

CW(INLET) \

~ - - - - - - - - - ( -, ~ ..,---\----\-----------,. I ' 8 1------- 72" MIN.----~

-----------, I I

.------ 72" MIN. -----1 I I I I I I

I I I I

r ' J

~ MAKEUPWATER

' L _________ _ nbb G _ ________ _j

CW (OUTLET) '---SPRAY PUMP

\_ TO HUB DRAIN

r - - - - - .=================== /r--- FAN SECTION

t-------1--,L-~-----------~ I r

I I 1-- 48" MIN. - I

1-------72" MIN.------;~ I I

I \--N--:t I ~~ \ -c:J- I L - - - - ~":::=::::::::::::::::::::::::::::::::::::::::::~:::::::::::::::::::::~ - - - - - - - - - - - J

\ ~CONCRETE MAKE UP WATER EQUIPMENT PAD

NOTES: 1. INSTALL COOLING TOWER TO MAINTAIN MIN. SERVICE CLEARANCE INDICATED AND REQUIRED PER THE TOWER MANUFACTURER.

C 1 r--:C~L~O::...;:S~E7D~C::...:.I.:....:.R C=U I:....:..T-=L:....::O;..;,.W.:....-.:....p R:....:..O.::....:......:F I=LE=-..=C..;::;O..;::;O..;::;L:..:....I N:....::G:.....T.:....:.O::::..:W:...:..E:.:R:..:....=D=E..:..:T A....:.:I.:.L _ SCALE: N.T.S.

BY HVAC CONTRACTOR ~ ~ BY PLUMBING CONTRACTOR

/PRESSURE RELIEF VALVE PIPE TO FLOOR DRAIN r BACKFLOW PREVENTER BY

PLUMBING CONTRACTOR

TO COOLING TOWERi )-~~~-~L__tj___/_11 c5 HI~ c511 I I I c5 ll I )

~/ ~-/ 'I I I \

UNION (TYP.) <() ~ STRAINER WITH BLOW

PRESSURE REDUCING VALVE DOWN VALVE, CAP & CHAIN

COOLING TOWER MAKE UP WATER CONNECTION DETAIL SCALE: N.T.S. A1

I I

3 I

I

4

1-1/2" ~

/__:....,1----.---.._ 1"'-

I

I ~~--...L....-. I" " 1-1/2" FLANGE1~ / ' " r-r- r-r-1-1/2" BALL VALVE 1- r-

1-1/2" RADIOGRAPHABLE ~Er'~ WELDING BRANCH ---------..._._,r- H

PIPING~---

3" MIN

NOTES:

THREADED CAP

1. BALL VALVE MAYBE LOCATED IN HORIZONTAL RUN OF VENT PIPE.

@)~~~~~LAIR VENT DETAIL

I

5

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

d Zo !-0 o"' g:* d 1-:::l z zo w OCJ ::::::! (.)X u.

(/) ...J

~ UJ Cl ...J <( u

~ u UJ ::;?;

z 0

5: 0:: (.) en w 0

w !;;: 0

z 0

5: 0:: (.) en w 0

SHEET IDENTIFICATION

M-505 SHEET "147 OF 209

TYPE B-3 SUBMITTAL

Page 17: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 18: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 19: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

-

c

-

B

~ -.,: ~

~· (/) z w 0 0

5, I 0 w

~· "' 0 0

"' ~ ~ ., c. 0

" ., ::J 0" A

(/)

(!) z ~ (!) 0

"' 0 0

"' ~ 'f ~

0

"' ::;; 1-()._ > 1'- w 0 "" ~ ~ 0 0? 0

...1 <0

~ 0 ~ "' 0

1

I

~ ~

AVSJ

Er -,- ,r-s , MAKE-UP ,__ __ _L__---r'' WATER

J

II

t t

-- 0 -r- 0 "'0, 1-"0,

-r- -r-

I

~~I AS-1 .------'-----

1--.-'------ 4" CWS----l~ -- n;:f---------.---------,-----------'

~ J 10 '-tj

r-9

I 0 f------=------------1

\ 7

r' ®_Q

----------

2

4" cws

MIN.FLOW .-J BYPASS~

L

lr

SHOT FEEDER I

\ I 1

L r'

CONDENSER WATER PIPING SCHEMATIC 1 SCALE: N.T.S.

I

4"CWR

r

T~ NEAREST

STORM

I 3

WSHP-11 WSHP-12 ERV-1

l l (/) a:: $ $ (f) a:: $ $ () () $ $ () () ~ £'! () ()

= N .,.. .,.. .,.. .,.. N .,.. .....

t ' 1

I

c ~

,..

\001 -f><-J-

CT-1

4"CWS-

-

I

WSHP-1 WSHP-13

l l $ $ (/) () () $ = ~ () ~ = .,.. .,.. .,.. ..... .,..

• t l

3"CWR

3" CWR I

WSHP

~ +

1- 1-EJ-EJ­

-t-0 -JCO,

+-+ -

a:: $ ()

= .....

l

TYPICAL FOR ALL WSHP'S

..

-

I

lwsHP-71

lwsHP-41 3/4"CWR 3/4"CWS

WSHP-2

(/) a:: $ $ () ()

= = .,.. .....

I

_)

WSHP-3

(/)

$ () = .....

2" DOMESTIC MAKE-UP WATER

a:: $ ()

= .,..

I

.. 4

I • I a:: (/) $ $ () () = .,.. .,..

L ~

-

(/) a:: $ $ () ()

~ ~ .,.. .,.. .,.. .,..

" 2"CWS ....

t D 2"CWR

I 5

WSHP-10 WSHP-8 WSHP-6 WSHP-9

l l (/) a:: (/) a:: $ $ $ $ (/) a:: $ $ () () () () $ $ () ()

~ ~ ()() ~ = - ~ ~ = - ~ .,.. .,.. .,.. .,.. ..... .,..

(") (") .,.. .,.. .,.. .,..

t " l I" t

GENERAL NOTES: 1. REFER TO M-801 FOR MECHANICAL GENERAL NOTES, ABBREVIATIONS, AND LEGEND. 2. FOR WATER SOURCE HEAT PUMP PIPING, REFER TO DETAILS A3/M-503 AND A 1/M-504.

KEY NOTES: 0 FOR BASE MOUNTED END SUCTION PUMP PIPING REFER TO

DETAIL C1/M-503.

® ® 0

®

FOR IN-LINE PUMP PIPING, REFER TO DETAIL D1/M-503.

FOR BOILER PIPING, REFER TO DETAIL C5/M-503.

FOR AIR SEPARATOR AND EXPANSION TANK PIPING, REFER TO DETAIL A1/M-503.

FOR SHOT FEEDER PIPING, REFER TO DETAIL C3/M-503.

WSHP-5

(/) a:: $ $ () () = = .,.. .,..

l

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

()

~ :2: w :c () (/)

(9 z a. a. ...J

(}

~ () w :2:

"" ()._

L~ w

~

z 0 ;::: ()._

oc 0 (/) w 0

~ <( ::;; 0:: ()._

i!l: w ~ 0

z 0 ;::: ()._

oc 0

~ 0

SHEET IDENTIFICATION

M-701 SHEET 150 OF 209

I TYPE B-3 SUBMITTAL

Page 20: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

c

-

B

~

" a:: I u (j) z w 0 0

~I () w :;; 01 ..., 0 0

"' ~ ~ 'iii Q.

0 .,., "' => ,. A (j)

(') z ~ (') 0

"' 0 0

"' ~ ~ -..,. 0

:;; N

<( ~ 0 w ..., ~ .n

"' "' ;,; <.> 0

"' .J

0 3 ~ " <» g; ~ i.i

1

CONTROLS LEGEND

FAN

PUMP

-

-

ENERGY WHEEL

-

-

[ill COIL- HEATING/ COOLING

MOTORIZED DAMPER

FILTERS

MOTORIZED 3-WAY CONTROL VALVE

VARIABLE FREQUENCY DRIVE

I

I

(@ CT~

IT]

~ @]

~ ~ ~ ~

® @ --]

DOC

t DOC

2

MOTOR

CURRENT TRANSDUCER

TEMPERATURE SENSOR

HUMIDITY SENSOR

CARBON DIOXIDE SENSOR

DIFFERENTIAL PRESSURE SENSOR

FLOW SENSOR! STATION

PRESSURE SWITCH

STATIC PRESSURE SENSOR

DUCT SMOKE DETECTOR

FREEZESTAT

TEMPERATURE SENSOR- PIPE

SIGNAL TO DOC SYSTEM

SIGNAL FROM DOC SYSTEM

I

I

3

CONTROLS ABBREVIATIONS

DOC BAS EA OA SA MA N.C. N.O. RH T so DP SP HSP FS POS C02 ss SPD ALM 'r0N s OAD RAD EAF OAF WHL PHL TSP ED BPV DPR

DIRECT DIGITAL CONTROL BUILDING AUTOMATION SYSTEM EXHAUST AIR· OUTSIDE AIR SUPPLY AIR MIXED AIR NORMALLY CLOSED NORMALLY OPEN RELATIVE HUMIDITY TEMPERATURE SMOKE DETECTOR DIFFERENTIAL PRESSURE STATIC PRESSURE HIGH STATIC PRESSURE FREEZESTAT POSITION CARBON DIOXIDE START/STOP SPEED ALARM KILOWATT (POWER) STATUS OUTSIDE AIR DAMPER RETURN AIR DAMPER EXHAUST AIR FAN OUTSIDE AIR FAN WHEEL PREHEAT LEAVING TEMPERATURE SETPOINT ENABLE/DISABLE BY-PASS VALVE DAMPER

I

I

4 I 5

CONTROLS GENERAL NOTES:

1. NEW SIEMENS INDUSTRIES APOGEE BUILDING AUTOMATION SYSTEM SHALL BE EQUIPPED WITH BACNET PROTOCOL. THE SYSTEM SHALL INTERFACE WITH THE BASE EMCS. REFER TO SPECIFICATION SECTION 23 09 23.13 20, BACNET DIRECT DIGITAL DIGITAL CONTROL SYSTEMS FOR HVAC.

2. CONTRACTOR SHALL FIELD VERIFY ALL VALVE SIZES AND PIPE DIMENSIONS.

3. SEE EQUIPMENT 1/0 SUMMARY FOR CONTROL POINT DESCRIPTION.

4. CONTROL CONTRACTOR SHALL SUPPLY ALL CONTROL POWER TO CONTROL EQUIPMENT SUCH AS VALVE ACTUATORS, INCLUDING BUT NOT LIMITED TO 24V AND 120V.

5. SEQUENCES OF OPERATION SHALL BE ACCOMPLISHED BY INPUTS AND OUTPUTS OF BUILDING AUTOMATION SYSTEM (BAS).

6. ALL CONTROL POINTS SHALL BE IMPLEMENTED AS INDICATED UTILIZING STANDARD OBJECT TYPES AND SHALL NOT BE IMPLEMENTED UTILIZING PROPRIETARY METHODS.

7. PROPORTIONAL (P), INTEGRAL (1), AND DERIVATIVE (D) CONTROL LOOPS AND THEIR COMBINATIONS SHALL BE USED TO MAINTAIN SETPOINTS.

8. PROVIDE PASSWORD-PROTECTED ACCESS TO "ADJUSTABLE" (ADJ) SYSTEM PARAMETERS.

9. CONTROL SETPOINTS: OPERATOR SHALL HAVE THE ABILITY TO CHANGE ALL WRITEABLE CONTROL SETPOINTS FROM THE OPERATOR WORKSTATION (OWS).

10. OPERATING STATUS FOR BELT-DRIVEN FANS NOT EQUIPPED WITH VFDS SHALL BE CONFIRMED VIA CURRENT SWITCHES WITH ADJUSTABLE TRIPS. FIXED TRIP SWITCHES MAY BE USED FOR DIRECT DRIVE PUMP AND FAN MOTORS.

11. ALARMS: INFORMATION THAT CAN PROVIDE AN ALERT TO THE OPERA TOR ABOUT THE CONTROLLED AND MONITORED EQUIPMENT SHALL BE PROGRAMMED INTO AN EFFECTIVE ALARM HANDLING SYSTEM. ALL SETPOINTS SHALL BE ADJUSTABLE ON THE ALARM REPORT SCREEN BY USING PASSWORD-PROTECTED ACCESS. ALARMS SHALL BE PRIORITIZED SUCH THAT:

11.1. HIGHER LEVEL ALARMS SUCH AS LOSS OF UTILITY POWER SHALL SUPPRESS LOWER LEVEL ALARMS SUCH AS VFD FAILURE.

11.2. FAN AND PUMP PROOF-OF-RUN ALARMS SHALL BE GENERATED FOR BOTH FAILURES TO RUN WHEN COMMANDED AND FAILURE TO STOP WHEN COMMANDED. PROPER DELAYS SHALL BE INCORPORATED INTO THE ALARMS TO ALLOW PROCESS VARIABLES AND FAN AND PUMP SPEEDS AMPLE TIME TO REACH OPERATING SETPOINTS.

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

I

"' ci ~ z

ci 0 z s 0 Zo !2 ~

,_o u"' N

~~ 0

w 0 1-:::>

!:;: :J zo 0 oo

0 (j) ()X

~ ~~ ~ ...., .. o >' "' in ~ ro 0 0

~ w ~ z

(') ~ iii ~&1 Q)

w :::> 0 ou (j)

ci z w ...l

u: w 1-

C'i § a.. 'uJ ...l ' <(0 u ·' (j)~

1- II 0' -'"' a..~

(/) _J

0 g: z 0 (.) _J

(5 z ~ (.) w ~

w :;; <( z '::1

"' a.. a.. <(

z 0

t 0::

~ 0

~ 0

w-N<fJ _z (j)<(

SHEET IDENTIFICATION

M-801 SHEET 1S1 OF 209

I TYPE B-3 SUBMITTAL

Page 21: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

1

D

-

c

-

B

1': -..j

~~ (f)

z w Cl Cl (9 II () w ::0 ol

"' 0 0

"' ~ ~ 00 c. 0 ., "' :J o- A

(f)

(!) z ~ (!) 0

"' 0 0

"' ~ ~ "' ~ 0 N

::0 ~ a.

"' w

0 ~ ~ "' 0 0 ;.; .s w "" 0 i>

~ ~ N ()

I 2

SEQUENCE OF OPERATION- ENERGY RECOVERY VENTILATOR

EQUIPMENT

I

THE AIRSIDE SYSTEMS, AS IT APPLIES TO THE BUILDING AUTOMATION SYSTEM (BAS), CONSISTS OF THE FOLLOWING:

ENERGY RECOVERY VENTILATOR, ERV-1

RUN CONDITIONS

THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE. THE OUTSIDE AIR FAN, EXHAUST AIR FAN, AND ENERGY RECOVERY WHEEL SHALL RUN CONTINUOUSLY.

OUTSIDE AND EXHAUST AIR FANS

THE OUTSIDE AIR AND EXHAUST AIR FANS SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN UNLESS SHUTDOWN ON SAFETIES. THE OUTSIDE AIR FAN SPEED SHALL BE CONTROLLED BY A VFD AND SHALL MODULATE TO MAINTAIN AN AIRFLOW SETPOINT (ADJ.) OF 4,300 CFM. THE EXHAUST AIR FAN SPEED SHALL BE CONTROLLED BY A VFD AND SHALL MODULATE TO MAINTAIN AN AIRFLOW SETPOINT (ADJ.) OF 3,070 CFM.

OUTSIDE AIR AND EXHAUST FAN DAMPERS

THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL OPEN ANYTIME THE UNIT RUNS AND SHALL CLOSE ANYTIME THE UNIT STOPS. THE FANS SHALL START ONLY AFTER THE DAMPER STATUS HAS PROVEN EACH DAMPER IS OPEN.

HEAT PUMP

DURING NORMAL OPERATION OR DURING AN ENERGY RECOVERY WHEEL FAILURE THE HEAT PUMP SHALL OPERATE TO MAINTAIN AN AIR TEMPERATURE SETPOINT OF 70" F (ADJ.).

ECONOMIZER MODE

WHEN THE ECONOMIZER IS ENABLED, THE ENERGY RECOVERY WHEEL SHALL STOP. THE ECONOMIZER CONTROL IS BASED ON COMPARATIVE ENTHALPY. OUTSIDE AIR ENTHALPY SHALL BE COMPARED TO EXHAUST AIR ENTHALPY. THE ECONOMIZER SHALL BE ENABLED WHEN THE OUTSIDE AIR ENTHALPY IS LESS THAN THE EXHAUST AIR ENTHALPY- 3 BTU/ LB. THE ECONOMIZER SHALL DISABLE WHEN THE OUTSIDE AIR ENTHALPY IS GREATER THAN THE EXHAUST AIR ENTHALPY.

DOC

ERV-n-EAD

I

~

I 1.,.. ERV-n-EAF-SPDCMD I DOC

ERV-n-EAF-SS ----c!s-,...1 DOC I ERV-n-EAF-SPD

1----Jis-;.. DOC ERV-n-EAF-ALM -----11

Doc .... 1----Ji;.. ERV-n-EAF-kW

s- DOC I DOC

ERV-n-EAF- 1--~-V~F:;:;;:!C~ S I

I

DOC

ERV-n-WHL-s

cT;

EATOWALL ""' I>

""' ( EA ~-------'i(g LOUVER

""' !>

OAFROM ~ !> OA \

INTAKEHOODL_~"'~-.~'j),--~~-~,--~,--------__J~

l> [> [> [> f>

DOC L¥J IC?21 ~ L+J

I I I I I I I I I I I I

ERV-n-OAD _j I I L

I I

DOC I I I I

DOC

ERV-n-OA-T

DOC

Lffi­J

ERV-n-OA-F­DP

DOC

3 I 4 I

FILTER DIFFERENTIAL PRESSURE MONITOR

A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE OUTSIDE AIR AND EXHAUST AIR FILTERS.

FROST CONTROL WHEN FROST IS INDICATED, THE SUPPLY FAN SHALL CYCLE OFF AND ON WHILE THE EXHAUST FAN CONTINUES TO RUN. THE SUPPLY FAN WILL CONTINUE TO CYCLE AS LONG AS FROSTING IS OCCURING. THE TIMED EXHAUST CONTROLS SHALL BE PROVIDED BY THE ERV MANUFACTURER.

ALARMS AND SHUTDOWNS

HVAC EMERGENCY SHUTDOWN: THE UNIT SHALL SHUT DOWN BASED ON A SIGNAL FROM THE "HVAC EMERGENCY SHUTDOWN SWITCH." EMERGENCY SHUTDOWN: THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL. HIGH STATIC SHUTDOWN: THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH STATIC PRESSURE SHUTDOWN SIGNAL. MANUAL RESTART SHALL BE REQUIRED. SUPPLY AIR SMOKE DETECTION: THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SUPPLY AIR SMOKE DETECTOR STATUS. Q ~ =J. N "~tOMMANDED ON, BUT THE STATUS IS OFF. g ~ =J. N ~ COMMANDED OFF, BUT THE STATUS IS ON.

~AIR F. IN :.1u1 II COMMANDED ON, BUT THE STATUS IS OFF. ~FAN IN~ COMMANDED OFF, BUT THE STATUS IS ON.

OUTSIDE AIR DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED. OUTSIDE AIR DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN. EXHAUST AIR DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED. EXHAUST AIR DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN. LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5"F (ADJ) LESS THAN HEATING SETPOINT. FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

DOC DOC

ERV-n-EA-F- ERV-n-EA-T

DP

I r I

r-ffi- m l> t> 1/ [> EA

1\ t> f>

HP

0 OA

L+J I

DOC I I L

DOC

ERV-n-EA-RH

I I

-~

DOC

ERV-n-SA-T

~

~ I I I L

EAFROM BUILDING

DOC

ERV-n-HSP

DOC

ERV-n-SA-SD

I I

® OATOWSHP'S

cr.~~~-J-. J-. 'I

ERV-n-OAF-S

CWS/R I I I I

I I ERV-n-OAF-ALM I

DOC ""'..:!!1----..JI ERV-n-OAF-kW ERV-n-OA­

C02 ____ j L ___ _

I

ERV-n-OA-RH

1

ERV-n-OAF-SS L__--liS>~ DOC DOC ---lis-,_,l

I ERV-n-OAF-SPD c__--lis-~ DOC I ~ ERV-n-OAF-SPDCMD

DOC

ENERGY RECOVERY VENTILATOR (ERV) CONTROL SCHEMATIC SCALE: N.T.S.

I I I

5 .

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

"' ci 0 z 0 ~ 6 Zo ~ i= 1-g ('\I <( ~~ ·: o t: O::::m 0

() 1- ::J z 1-;§w :::;. zow

0 OCl =! (/) ox lL

~ 0 0:: f­z 0 0 ...!

l§ z ~ ~ :2:

w !;;: Cl

z 0

ti: 0:: i;l w Cl

z 0

ti: 0:: () (f) w Cl

SHEET IDENTIFICATION

M-802 SHEET 152 OF 2{}9

TYPE B-3 SUBMITTAL

Page 22: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 23: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 24: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 25: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 26: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 27: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

D

-

c

-

B

1 I

I ~ ~ ~ - ~ ~ ~ ~ I ~ - - - 1- - - - I I I

B-1-ED ---J,...,1 DOC I B-1-LWT

'-----J,.. .. DDC B-1-BP1-S I DOC ... ..,. __ -'

_I __ ,.. .. B-1-ALM

B-1-EWT I DDC DOC """ 1 ___ .. B-1-S

1 ,.. DDC

~

I ~

I

I

I BP-1 .-+-

L ~ --(/\) I "-- / I

L_~ .,

I

I I I I I I I I I I I I I I I I I I

[;-- J

2

[-' CWP-2-SS

1""1..,.11---~ DDC CWP-2-ALM I DDC ... ..,. __ --!·

I CWP-2-S f----J,.... DOC

CWP-2-SPDCMD ,..1 DDC I CWP-2-SPD

1----J,.... DOC CWP-2-fW\/ DDC.,..,. __ --il

I

I

DDC

A 1

CWP-1-D-PRESS

3

DDC----i CW-FLOW

--E)f

L~~~--------------- ---- ~~,

CWP-1-S-PRESS

T

' DDC

~-E)f

V\Hv~DI "--,/ CWP-2

RG--

J

I

DOC---{

DDC

CWS-T I I

I

4

CW-BPV

T I

~_j

I 5

~~DDC

CW-DP f-----J- DDC

) ) TO BUILDING I

WSHP

CWP-2-D-PRESS

.--------1,1r----------L------r',' FROM BUILDING ,~'-------'-----1: r-:~>'< I

DDC

1

I

L CWR-T f-----J- DOC

~

._I __ .,.~ CT-1-F-fW\/

CT-1-F-SPD ..,. I DOC

DDC ~ool.,.ll---- CT-1-F-SPDCMD

CT-1-F-S ...,11-----ll DDC DDC ..

1-l __ .,~ CT-1-F-ALM

CT-1-F-SS .,. 1 DDC DDC

I CWP-2-

S-PRESS IVFD - ~ ~ - - - ~ _j

1 CT-1

I ~ ~ ~ /I\ /I\

CT-1-VIB

SWTCH 1--1-DDC

DDC

L - ~Jl-.f---------l"'~---------"\rl \\--(=============~ ~ ~ __ DOC CT-1-LWT \\ )

CT-1-SP-S

1 .-----~--~-----------------._---cws-------------------~

T I

\ \-~ A I

\\ -tut------tLrl~\J- ~ ~ ~ CT-1-SP-SS

C::::::======='=:!::J 'C:7 CT L_ __________________________________________ ~-----CWR---------------------------------------------J_ __________ ~J~---,----~

~f--------l CT-1-FLOW f-----J-DDC

SPRAY PUMP

SEQUENCE OF OPERATION· CONDENSER WATER SYSTEM

EQUIPMENT

THE CONDENSER WATER SYSTEM, AS IT APPLIES TO THE BUILDING AUTOMATION SYSTEM (BAS), CONSISTS OF THE FOLLOWING EQUIPMENT:

CONDENSER WATER PUMPS, CWP-1 & CWP-2 COOLING TOWER, CT-1 BOILER, B-1 & BOILER PUMP, BP-1

CONDENSER WATER PUMP CONTROL SEQUENCE

CONDENSER WATER PUMPS: THE CONDENSER WATER PUMP MOTORS SHALL OPERATE AS LEAD/ LAG WITH ONLY THE LEAD PUMP OPERA TIN G. THE LAG PUMP SHALL BE DESIGNATED AS THE STAND-BY PUMP. THE BAS SHALL START THE LEAD CONDENSER WATER PUMP WHEN THE BUILDING IS IN NEED OF COOLING OR HEATING. THE CONDENSER WATER PUMPS HAVE VFDS. WHEN ANY CONDENSER WATER PUMP MOTOR IS STARTED, THE BAS SHALL START THE PUMP AT 25 PERCENT SPEED. WHEN THE STATUS OF THE PUMP MOTOR IS PROVEN VIA A CURRENT SWITCH INPUT TO THE BAS, THE BAS SHALL GRADUALLY INCREASE ITS SPEED BASED UPON DIFFERENTIAL PRESSURE CONTROL CRITERIA. IF THE CONDENSER WATER PUMP MOTOR DOES NOT PROVE STARTED WITHIN 5 SECS (ADJ), THE BAS SHALL CONSIDER THAT PUMP MOTOR "FAILED", GENERATE AN ALARM, AND REMOVE IT FROM ROTATION.

TO STOP A CONDENSER WATER PUMP MOTOR, THE BAS SHALL SLOWLY DECREASE THE SPEED OF THE PUMP MOTOR. THE BAS SHALL STOP THE DESIRED CONDENSER WATER PUMP WHEN IT REACHES ITS MINIMUM SPEED.

THE BAS SHALL MONITOR THE RUNTIME OF EACH CONDENSER WATER PUMP MOTOR AND DESIGNATE EACH PUMP SYSTEM AS LEAD AND LAG BASED UPON THE NEED TO EQUALIZE RUNTIME FOR EACH CONDENSER WATER PUMP MOTOR. WHEN A CONDENSER WATER PUMP IS DOWN FOR MAINTENANCE, THE BAS SHALL ALLOW THE OPERATOR TO SELECT "MAINTENANCE" AND THE BAS SHALL TAKE THIS PIECE OF EQUIPMENT OUT OF THE ROTATION.

CONDENSER WATER DIFFERENTIAL PRESSURE CONTROL: THE BAS SHALL MEASURE THE CONDENSER WATER DIFFERENTIAL PRESSURE AND MODULATE THE CONDENSER WATER PUMP VFD TO MAINTAIN DIFFERENTIAL PRESSURE SETPOINT (ADJ.), AS DETERMINED DURING TEST & BALANCE.

1 CONDENSER WATER SYSTEM CONTROL SCHEMATIC

COOLING TOWER CONTROL SEQUENCE

COOLING TOWER OPERATION:

SCALE: N.T.S.

UPON THE CALL FOR LEAD CONDENSER WATER PUMP STARTUP, THE BAS SHALL MONITOR THE CONDENSER WATER SUPPLY TEMPERATURE. WHEN THE SUPPLY WATER TEMPERATURE HAS BEEN 1°F (ADJ)ABOVE THE CONDENSER WATER SUPPLY TEMPERATURE COOLING SETPOINT FOR A PERIOD OF 600 SECONDS (ADJ), THE BAS SHALL MODULATE OPEN THE COOLING TOWER ISOLATION VALVE. AFTER THE ISOLATION VALVE IS PROVEN FULLY OPEN (OPEN TO THE TOWER) VIA POSITION INDICATION, THE BAS SHALL BEGIN THE COOLING TOWER STARTUP SEQUENCE.

UPON THE CALL FOR COOLING TOWER STARTUP, THE SPRAY PUMP SHALL START AND RUN. IF THE CONDENSER WATER SUPPLY TEMPERATURE CONTINUES TO RISE ABOVE THE COOLING SETPOINT, THE BAS SHALL START THE COOLING TOWER FAN(S). THE FAN(S) SHALL START AT 25 PERCENT SPEED OR MINIMUM SPEED TO MAINTAIN MINIMUM COOLING TOWER AIRFLOW. WHEN THE STATUS OF THE FAN MOTOR IS PROVEN VIA A VFD SPEED SIGNAL INPUT TO THE BAS, THE BAS SHALL GRADUALLY INCREASE THE FAN MOTOR AS REQUIRED TO MAINTAIN THE CONDENSER WATER SUPPLY TEMPERATURE COOLING SETPOINT. IF THE COOLING TOWER FAN MOTOR DOES NOT PROVE STARTED WITHIN 5 SECS (ADJ), THE BAS SHALL CONSIDER THE FAN MOTOR "FAILED" AND GENERATE AN ALARM.

ON A DROP IN COOLING LOAD AND THE CONDENSER WATER SUPPLY TEMPERATURE CONTINUES TO DROP BELOW THE SUPPLY TEMPERATURE COOLING SETPOINT, THE REVERSE SEQUENCE SHALL OCCUR UNTIL THE BAS CALLS FOR COOLING TOWER SHUTDOWN. ONCE THE COOLING TOWER IS DISABLED, THE BAS SHALL MODULATE THE COOLING TOWER ISOLATION VALVE CLOSED (CLOSED TO THE TOWER).

COOLING TOWER VIBRATION: THE BAS SHALL MONITOR THE VIBRATION SWITCH STATUS DURING COOLING TOWER OPERATION. IF THE STATUS CHANGES, THE COOLING TOWER SHALL SHUT DOWN AND GENERATE AN ALARM.

SYSTEM FREEZE PROTECTION

COOLING TOWER MINIMUM FLOW: WHEN NO COOLING DEMAND EXISTS AND THE OUTSIDE AIR TEMPERATURE IS EQUAL TO OR LESS THAN 40oF (ADJ), THE BAS SHALL START THE LEAD CONDENSER WATER PUMP AND MODULATE OPEN THE COOLING TOWER ISOLATION VALVE (OPEN TO THE TOWER) TO ALLOW FLOW THROUGH COOLING TOWER COIL. THE ISOLATION VALVE SHALL MODULATE TO MAINTAIN MINIMUM FLOW THROUGH THE COIL DURING FREEZE PROTECTION MODE. THE MINIMUM FLOW REQUIRED FOR FREEZE.

PROTECTION SHALL BE DETERMINED BY THE COOLING TOWER MANUFACTURER. THE CONDENSER WATER BYPASS VALVE SHALL ALSO MODULATE OPEN AS REQUIRED TO ALLOW FLOW THROUGH THE SYSTEM WHEN HEATING DEMAND IS LOW OR DURING UNOCCUPIED PERIODS.

COOLING TOWER BASIN TEMPERATURE: THE BAS SHALL MONITOR THE BASIN WATER TEMPERATURE IN THE COOLING TOWER. IF THE BASIN TEMPERATURE FALLS BELOW 45°F (ADJ), AN ALARM SHALL BE GENERATED.

CONDENSER WATER PIPE HEAT TRACING: THE CONDENSER WATER PIPING HEAT TRACING SHALL BE CONTROLLED BY A STAND-ALONE THERMOSTAT AND SHALL ACTIVATE WHEN THE OUTSIDE AIR TEMPERATURE IS EQUAL OR LESS THAN 40°F (ADJ).

CONDENSER WATER BYPASS VALVE· MIN. FLOW CONTROL

THE BAS SHALL MEASURE CONDENSER WATER FLOW THROUGH THE SYSTEM AND, AS THE CONDENSE WATER FLOW DROPS BELOW THE MINIMUM CONDENSER WATER PUMP FLOW SETPOINT, AS DETERMINED DURING TEST AND BALANCE, THE BAS SHALL MODULATE THE CONDENSER WATER BYPASS VALVE OPEN TO MAINTAIN THE MINIMUM CONDENSER WATER FLOW SETPOINT.

CONDENSER WATER TEMPERATURE CONTROL

CONDENSER WATER SUPPLY TEMPERATURE SETPOINT: THE BAS SHALL MONITOR THE CONDENSER WATER SUPPLY TEMPERATURE AND SHALL MAINTAIN THE CONDENSER WATER SUPPLY TEMPERATURE SETPOINTS AS FOLLOWS: · COOLING: THE SETPOINT SHALL BE 85°F (ADJ.). ·HEATING: THE SETPOINT SHALL BE 70°F (ADJ.).

BOILER CONTROL SEQUENCE THE BAS SHALL MONITOR AND CONTROL THE NATURAL GAS FIRED BOILER, B-1. VIA AN INTEGRATED INTERFACE WITH THE BOILER MANUFACTURER'S SUPPLIED BOILER CONTROL SYSTEM.

STARTING BOILER: THE BAS SHALL MONITOR THE CONDENSER WATER SUPPLY TEMPERATURE. WHEN THE SUPPLY WATER TEMPERATURE HAS BEEN 1oF (ADJ) BELOW THE CONDENSER WATER SUPPLY TEMPERATURE HEATING SETPOINT FOR A PERIOD OF 600 SECONDS (ADJ), THE BAS SHALL ENABLE THE BOILER. THE BOILER CONTROL SYSTEM SHALL START THE BOILER FOLLOWING THE MANUFACTURER'S START-UP SEQUENCE PROGRAMMED

DDC

INTO THE BOILER CONTROLLER, INCLUDING STARTING THE BOILER PUMP. THE BOILER PUMP SHALL BE FULLY CONTROLLED BY THE BOILER CONTROLLER. THE BAS SHALL MONITOR THE PUMP STATUS ONLY. THE BOILER SHALL RUN TO MAINTAIN THE CONDENSER WATER SUPPLY TEMPERATURE HEATING SETPOINT. STOPPING BOILER: WHEN THE SUPPLY WATER TEMPERATURE HAS BEEN 1oF (ADJ) ABOVE THE CONDENSER WATER SUPPLY TEMPERATURE HEATING SETPOINT FOR A PERIOD OF 600 SECONDS (ADJ), THE BAS SHALL DISABLE THE BOILER. THE BOILER CONTROL SYSTEM SHALL STOP THE BOILER FOLLOWING THE MANUFACTURER'S SHUT-DOWN SEQUENCE PROGRAMMED INTO THE BOILER CONTROLLER.

ALARMS AND SHUTDOWNS

ALARMS AND SHUTDOWNS:THE BOILERS SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SIGNAL. BOILER FAILURE: COMMANDED ON, BUT THE STATUS IS OFF. BOILER GENERAL ALARM COOLING TOWER FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF. COOLING TOWER FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON. COOLING TOWER FAN VFD FAULT COOLING TOWER SPRAY PUMP FAILURE: COMMANDED ON, BUT THE STATUS IS OFF. COOLING TOWER SPRAY PUMP RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON. HIGH CONDENSER WATER SUPPLY TEMP: IF THE CONDENSER WATER SUPPLY TEMPERATURE IS GREATER THAN 95° F (ADJ.). LOW CONDENSER WATER SUPPLY TEMP: IF THE CONDENSER WATER SUPPLY TEMPERATURE IS LESS THAN 60° F (ADJ.). CONDENSER WATER PUMP FAILURE: COMMANDED ON, BUT THE STATUS IS OFF. CONDENSER WATER PUMP RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON. CONDENSER WATER PUMP RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT. CONDENSER WATER PUMP VFD FAULT HIGH CONDENSER WATER DIFFERENTIAL PRESSURE: IF THE CONDENSER WATER DIFFERENTIAL PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT. LOW CONDENSER WATER DIFFERENTIAL PRESSURE: IF THE CONDENSER WATER DIFFERENTIAL PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT. LOW CONDENSER WATER FLOW: IF THE CONDENSER WATER FLOW IS 25% (ADJ.) LESS THAN SETPOINT. ~ LOW COOLING TOWER LEAVING WATER TEMP: IF THE COOLING TOWER LEAVING WATER TEMPERATURE IS LESS THAN 50° F (ADJ.).

Nn

Copyright© 2016 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.

ci Zo ,_o o""' &~ ci 1- :::> z zo w Oo-' (.) X U::

z 0 !;' § (f) w Cl

SHEET IDENTIFICATION

M-808 SHEET 158 OF 209

I I I I TYPE B-3 SUBMITTAL

Page 28: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical
Page 29: GENERAL MECH. ABBREVIATIONS GENERAL MECH. ABBREVIATIONS ... · • ufc 3-310-04: seismic design for buildings • ufc 3-400-02: engineering weather data • ufc 3-401-01: mechanical

Recommended