+ All Categories
Home > Documents > Generator Protection Class presentation

Generator Protection Class presentation

Date post: 03-Apr-2018
Category:
Upload: mohammad-ibnul-hossain
View: 240 times
Download: 14 times
Share this document with a friend

of 123

Transcript
  • 7/28/2019 Generator Protection Class presentation

    1/123

    Completed by :Mohammad Ibnul Hossain

    Executive Engineer (Operation)Tongi 80(105) MW GT Power Station

    Bangladesh Power Development BoardE-mail : [email protected]

    GENERATOR PROTECTION

  • 7/28/2019 Generator Protection Class presentation

    2/123

  • 7/28/2019 Generator Protection Class presentation

    3/123

  • 7/28/2019 Generator Protection Class presentation

    4/123

    Possible Faults

  • 7/28/2019 Generator Protection Class presentation

    5/123

    Abnormal operating condition

    overcurrent / overload unbalanced load

    over temperature over- and undervoltage over- and underexcitation

    over- and underfrequency

    over-fluxing

    asynchronous running

    out of step

    generator motoring failures in the machine control system (i.e. AVR orgovernor failure)

    failures in the machine cooling system

  • 7/28/2019 Generator Protection Class presentation

    6/123

    In abnormal condition ,

    those dont need immediate trip the unit generator

    Or transformer but cant continue , at some stage

    we must trip-out the system.

  • 7/28/2019 Generator Protection Class presentation

    7/123

    Different Power Plant Electrical Layout

  • 7/28/2019 Generator Protection Class presentation

    8/123

    Damage to the stator core in case of earth-fault

    The stator cant withstand with a small amount of ground current evenWith short period of time.

    Arrangement must be taken to limit the ground fault current not more

    than 10 amp.

  • 7/28/2019 Generator Protection Class presentation

    9/123

    How it is done ?

    it is achieved by grounding

    Here we see different types of alternatives.

    Solidly grounded through a resistor typically in Europe

    Grounding transformer , typically for U.S

    Stator winding Earthing Practice :

  • 7/28/2019 Generator Protection Class presentation

    10/123

    87 Differential59 over -voltages

    24V/HZ over fluxing

    49S stator Over load

    51 over -current

    64s Ground Fault stator

    Inter-turn

    64R Ground fault Rotor

    71 pole slipping

    40 Loss of excitation

    32 Reverse Power81 O/U Frequency

    Turbine

    Rotor Stator

    Allocation of Protection Function

    46 Negative Phase Sequence

  • 7/28/2019 Generator Protection Class presentation

    11/123

    No.DESCRIPTION

    2Time-delay relay

    21

    Distance relay24

    Over excitation / Volts per Hertz

    25 Synchronism-check relay

    27 Under voltage relay

    27TN Third-Harmonic Under voltage relay

    30 Annunciator device

    32 Reverse power relay

    37 Undercurrent or underpower relay

    40 Field excitation relay

    46 Negative sequence overcurrent relay

  • 7/28/2019 Generator Protection Class presentation

    12/123

    47 Negative sequence overvoltage relay

    49 Thermal relay

    50 instantaneous AC overcurrent relay

    50DT Split Phase Differential

    50/27 inadvertent Energizing

    50BF Breaker Failure

    51 AC Inverse Time Overcurrent relay

    52 Circuit breaker

  • 7/28/2019 Generator Protection Class presentation

    13/123

    59Overvoltage relay

    59DThird-Harmonic Voltage Differential Ratio

    60 Voltage balance or loss of potential relay

    63 Pressure device

    64F Field Ground relay

    64B Brush Lift-Off Detection

    64S100% Stator Ground Protection by LowFrequency Injection

    67 AC directional overcurrent relay

    68 Power Swing Blocking

    69Permissive relay

    59N Single Phase Overvoltage Relay

  • 7/28/2019 Generator Protection Class presentation

    14/123

    74 Alarm relay

    76 DC overcurrent relay

    78 Out-of-step relay

    79 AC reclosing relay

    81 Frequency relay

    81R Rate of Change Frequency relay

    83 Transfer device

    85 Carrier or pilot-wire relay

    86 Lock out relay

    87 Differential relay

    94 Auxiliary tripping relay

  • 7/28/2019 Generator Protection Class presentation

    15/123

    Consequence of stator short circuit

    Insulation. windings and stator core can be

    damaged

    Large forces, caused by large fault currents. can

    give damage to other components in the plant

    Risk of explosion and fire

    Mechanical stress on generator- and turbine

    shafts

    Stator Short Circuit

  • 7/28/2019 Generator Protection Class presentation

    16/123

    Detection of stator short circuits

    Protection functions Generator differential protection

    Unit differential protection Directional negative sequence overcurrent

    protection

    Under impedance protection

    Phase overcurrent protection Voltage dependent phase overcurrent protection Under voltage protection

    Phase overcurrent protection of the unit

    transformer

  • 7/28/2019 Generator Protection Class presentation

    17/123

    Phase to phase fault in the stator winding

    Endangering condition

    Overcurrent Protected object

    Stator winding

    Consequences Heating Forces

    Smelted stator core

  • 7/28/2019 Generator Protection Class presentation

    18/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff

    51

    OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    GENERATOR AND UNIT TRANS FORMER UNIT SCHEME

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP+ REX0061

    UnitX

    for.

    46

    Neg.Pha.

  • 7/28/2019 Generator Protection Class presentation

    19/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87ODiff(x-f)

    51

    OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    GENERATOR AND UNIT TRANS FORMER UNIT SCHEME

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Distance

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP+ REX0061

    UnitX

    for.

    87Oo/a Diff

    Udr.Imp.pro.

    46

    Neg.Pha.

  • 7/28/2019 Generator Protection Class presentation

    20/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87ODiff(x-f)

    51

    OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    GENERATOR AND UNIT TRANS FORMER UNIT SCHEME

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Distance

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP+ REX0061

    UnitX

    for.

    87Oo/a Diff

    Udr.Imp.pro.

    46

    Neg.Pha.

  • 7/28/2019 Generator Protection Class presentation

    21/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87ODiff(x-f)

    51

    OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    GENERATOR AND UNIT TRANS FORMER UNIT SCHEME

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Distance

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP+ REX0061

    UnitX

    for.

    87Oo/a Diff

    Udr.Imp.pro.

    46

    Neg.Pha.

  • 7/28/2019 Generator Protection Class presentation

    22/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87ODiff(x-f)

    51

    OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    GENERATOR AND UNIT TRANS FORMER UNIT SCHEME

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Distance

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP+ REX0061

    UnitX

    for.

    87Oo/a Diff

    Udr.Imp.pro.

    46

    Neg.Pha.

    Diff ti l P t ti

  • 7/28/2019 Generator Protection Class presentation

    23/123

    Let us , Consider , X protected EquipmentCT1 and CT2 same transformation ratioThe current flow in the primary and secondary sides of power

    transformer are identical, assuming ideal transformer.The secondary current i1 and i2 are equal in magnitude and oppositein direction.So, the net current in the differential coil is zero at load condition

    (without fault), and the relay will not operate .

    Differential Protection

    XI1 I2

    i1i2

    TC

    i1

    i2

    i1 i2

    Diff. Relay

    CT1 CT2

  • 7/28/2019 Generator Protection Class presentation

    24/123

    Differential Protection

    XI1 I2

    i1

    i2

    TC

    i1

    i2

    i1 i2

    Diff. Relay

    CT1 CT2

    External Fault happens ,

    Then , I1 and I2 increases as well as i1 and i2 increasesBut the phase angle of i1 and i2 will be the same ,

    So , the net current in the TC or Operating Coil = 0

    So, the relay will not operate

  • 7/28/2019 Generator Protection Class presentation

    25/123

    XI1 I2

    i1

    i2

    TC

    i1

    i2

    i1 i2

    Diff. Relay

    CT1 CT2

    Differential Protection

    is another source to feed the fault ,

    So I2 0 ,

    I diff = i1 + i2 which is very highAnd trips the Differential Relay

  • 7/28/2019 Generator Protection Class presentation

    26/123

    Biased differential relay

    XI1 I2

    i1

    i2

    Op

    i1

    i2

    i1 i2

    Biased Diff. Relay

    CT1 CT2

    Res. Res.

    Large external fault cause false operation

    To make more stable Two Restraining ( Biasing ) coilAndOne Operating coil is introduced .What is the function of two Restraining ( Biasing ) Coils ?Restraining coils will oppose the operation of operating coil.

    The relay will operate only when the operating force > the restraining force

  • 7/28/2019 Generator Protection Class presentation

    27/123

    Tripping Characteristics of Simple Differential Relay

  • 7/28/2019 Generator Protection Class presentation

    28/123

    Tripping Characteristics of Biased Differential Relay with TwoStages (Two Slops )

  • 7/28/2019 Generator Protection Class presentation

    29/123

    Connections of CTs for differential protection of generator.

    Percentage differential relaying of a star connected generator , for phase-phase faults.

  • 7/28/2019 Generator Protection Class presentation

    30/123

    Percentage differential relay of a delta connected generator ,forphase-phase fault.

    G diff i l i O h h

  • 7/28/2019 Generator Protection Class presentation

    31/123

    Generator differential protection Operates then what

    happens ?

    Shall trip the followings :

    Turbine: close down active power

    Generator breaker: if available

    Field breaker

    Unit breaker: If no generator breaker Fire protection

    Differential Protection can be used :

  • 7/28/2019 Generator Protection Class presentation

    32/123

    Differential Protection can be used :

    The layout of what we are talking about 87G the differentialprotection of gen87T- the differential protection of step-uptransformer870- both the generator and the step-up transformer.

  • 7/28/2019 Generator Protection Class presentation

    33/123

  • 7/28/2019 Generator Protection Class presentation

    34/123

    Endangering condition Overcurrent

    Protected object

    Transformer windings

    Consequences

    Heating

    Forces

    Smelted transformer core

    Phase to phase fault in the transformer winding

    h h f l h f d

  • 7/28/2019 Generator Protection Class presentation

    35/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff

    51OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Phase to phase fault in the transformer winding

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP

    + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Ph h f l i h f i di

  • 7/28/2019 Generator Protection Class presentation

    36/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff

    51OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Phase to phase fault in the transformer winding

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP

    + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Ph h f l i h f i di

  • 7/28/2019 Generator Protection Class presentation

    37/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff

    51OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Phase to phase fault in the transformer winding

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP

    + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Ph t h f lt i th t f i di

  • 7/28/2019 Generator Protection Class presentation

    38/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff

    51OC

    50/51

    OC

    YY

    YY

    51OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Phase to phase fault in the transformer winding

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP

    + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    fault impedance < load impedance

  • 7/28/2019 Generator Protection Class presentation

    39/123

    fault impedance < load impedanceSo , the fault current > load current.If a short circuit occursthe circuit impedancetherefore a fault is accompanied by large current

    Overcurrent relays sense fault currents and also over-loadcurrents.Overcurrent protection is that protection in which the relay picksup when the magnitude of current exceeds the pickup level.The basic element in overcurrent protection is an overcurrent relay.

    The overcurrent relays are connected to the system, normally bymeans of CTs. Overcurrent

    relaying has following types :- High speed overcurrent protection.- Definite time overcurrent protection.- Inverse minimum time overcurrent protection.

    - Directional overcurrent protection (or above any type)

    Over-current protection includes the protection from

  • 7/28/2019 Generator Protection Class presentation

    40/123

    Over current protection includes the protection from

    overloads .

    Overloading of a machine or equipment means the machineis taking Current > rated current .

    Hence with overloading , there is an associated temperature

    rise .

    Overcurrent protection of overloads is generally provided by

    thermal relay.

    The permissible rise has limit based on insulation class and

    material problems.

    Over-current protection includes short-circuit protection

  • 7/28/2019 Generator Protection Class presentation

    41/123

    Over current protection includes short circuit protection.

    Short circuits can bephase faults

    earth faultswinding faults.

    Short-circuit currents are generally several times (5 to 20) full

    load current.

    Fast fault clearance is always desirable on short-circuits

    When a machine is protected by differential protection, theover-current is provided in addition as a back-up and in somecases to protect the machine from sustained through fault.

    Several protective devices are used for over-current

  • 7/28/2019 Generator Protection Class presentation

    42/123

    Several protective devices are used for over current

    protection .

    These includes

    -Fuses

    -Miniature circuit-breakers, molded-case circuit-breakers.

    -Circuit-breakers fitted with overloaded coils or tripped byover-current relays.

    -Series connected trip coils operating switching devices.

    - Over-current relays in conjunction with current

    transformers.

    Th i i t f t t ti

  • 7/28/2019 Generator Protection Class presentation

    43/123

    The primary requirements of over-current protection are :

    The protection should not operate starting currents

    permissible overcurrentCurrent surges.

    To achieve this

    The time delay is provided (in case of inverse relays)If time delay cannot be permitted

    high-set instantaneous relaying is used.

    - The protection should be co-ordinated with neighbouringover-current protections

    CHARACTERISTICS OF RELAY UNITS FOR OVER-CURRENT

  • 7/28/2019 Generator Protection Class presentation

    44/123

    PROTECTION

    There is a wide variety of relay-units. These are classified

    according to their type and characteristics.

    The major characteristic include :

    - Definite characteristic

    - Extremely Inverse

    -Inverse- Inverse characteristic

    - Very Inverse

    Inverse characteristic

  • 7/28/2019 Generator Protection Class presentation

    45/123

    Inverse characteristic

    t 1 / Iwhere I= Current in relay coil

    t = Relay limeK = Constant

    Very Inverse characteristic

    t 1 / Inwhere n = 2 to 8 , according to the requirements.

    Connection Scheme withThree Over current Relays

  • 7/28/2019 Generator Protection Class presentation

    46/123

    . Connection Scheme withThree Over-currentRelays

    Relay Coil

    OvercurrentRelayCB

    R Y B

    IR IY IB +

    AUXILLARYSWITCH

    TripCoil

    RelayContact

    Connection Scheme withThree Over-currentRelays

  • 7/28/2019 Generator Protection Class presentation

    47/123

    Relay Coil

    OvercurrentRelay

    CB

    R YB

    IR IY IB

    +

    AUXILLARYSWITCH

    TripCoil

    RelayContact

    + DEFINITETIMERELAY

    AUXILLARYRELAY

    ywith addition of a common time-delay relayand an auxiliary relay

    Stator earth fault

  • 7/28/2019 Generator Protection Class presentation

    48/123

    Stator earth fault

    Damages on the stator iron

    Increased voltage on healthy phases

    Small fault currents

    Sensitivity requirements on fault clearance

    The fault resistance is normally low atstator earth fault

    RESTRICTED EARTH-FAULT PROTECTION BY DIFFERENTIAL SYSTEM

  • 7/28/2019 Generator Protection Class presentation

    49/123

    RESTRICTED EARTH FAULT PROTECTION BY DIFFERENTIAL SYSTEM

    , Neutral is earthed through resistance to limit earth-fault currents.

    With resistance earthing, it is not possible to protect complete winding from earth-fault andthe % of winding protected depends on the value of neutral earthing resistor and the relaysettingSetting Criteria :

    The current rating of resistor, resistance value, relay setting, etc. should be selectedcarefully.Setting should be such that the protection does not operate for earth-faults on EHV

    side

    RESTRICTED EARTH-FAULT PROTECTION BY DIFFERENTIAL SYSTEM (Cont.) a

  • 7/28/2019 Generator Protection Class presentation

    50/123

    RESTRICTED EARTH FAULT PROTECTION BY DIFFERENTIAL SYSTEM (Cont.) a

    Setting Criteria (Cont.) :

    Earth faults are not likely to occur near the neutral point due to less voltage w.r.t. earth.It is a usual practice to protect about 80 to 85% of generator winding against earth-faults.

    It is a usual practice to protect about 80 to 85% of generator winding against earth-faults.

    The remaining 20 to 5% winding from neutral side left unprotected by the differentialprotection.

    In additional to differential protection, a separate earth-fault protection is provided to take

    care of the complete winding against earth faults.

    RESTRICTED EARTH-FAULT PROTECTION BY DIFFERENTIAL SYSTEM (Cont.) a

  • 7/28/2019 Generator Protection Class presentation

    51/123

    ( )

    During earth-fault the current, Ifflows through a part of the generator winding and

    neutral to ground circuit.

    The corresponding secondary current Is flows through the operating coil andrestricted earth-fault coil of the differential protection.

    The setting of the restricted earth fault relay can be selected independent of the

    setting of the overcurrent relay.

    RESTRICTED EARTH-FAULT PROTECTION BY DIFFERENTIAL SYSTEM (Cont.)

  • 7/28/2019 Generator Protection Class presentation

    52/123

    ( )

    Here, fault at pointf , Iffault current , VafVoltage

    If fault is nearer to neutral point Vafis relatively less .Hence , If is reduced .Not practicable for too sensitive setting , because it will operate in through fault of smallMagnitude for inaccurate CT and saturation of CT.

    Practice to provide 85% protection , the rest 15% is protected by another scheme.

    Discuss Next.

    100% STATOR EARTH-FAULT PROTECTION

  • 7/28/2019 Generator Protection Class presentation

    53/123

    100% STATOR EARTH FAULT PROTECTION

    Coupling TransformerGround Circuit

    Signal (12.5Hz) continuously injected Stator winding

    No Fault Signal feed into stray capacitance .

    IN FaultCapacitance is by-passed and monitoring

    Current (of 12.5 Hz) is sensed by the measuring system.

    Earth Fault in Stator Winding

  • 7/28/2019 Generator Protection Class presentation

    54/123

    Endangering condition

    Overvoltage in two healthy phases Voltage in the star point Relatively small earth fault current

    Protected object Stator winding

    Consequences Damage to the stator core Risk of second earth fault

    Earth Fault in Stator Winding

    Stator Earth Fault Protection

  • 7/28/2019 Generator Protection Class presentation

    55/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Stator Earth Fault Protection

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Stator Earth Fault Protection

  • 7/28/2019 Generator Protection Class presentation

    56/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Stator Earth Fault Protection

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Stator Earth Fault Protection

  • 7/28/2019 Generator Protection Class presentation

    57/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Stator Earth Fault Protection

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Stator Earth Fault Close to star point

  • 7/28/2019 Generator Protection Class presentation

    58/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Stator Earth Fault Close to star point

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    StatorEarth Fault Close to star point

  • 7/28/2019 Generator Protection Class presentation

    59/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    Stato a t ault Close to sta po t

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Earth fault in transformer HV winding

  • 7/28/2019 Generator Protection Class presentation

    60/123

    f f g

    Endangering condition

    Overcurrent

    Protected object

    Transformer windings

    Consequences Heating

    Forces

    Smelted transformer core

    Earth fault in transformer HV winding

  • 7/28/2019 Generator Protection Class presentation

    61/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    f f g

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Earth fault in transformer HV winding

  • 7/28/2019 Generator Protection Class presentation

    62/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    f f g

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Earth fault in transformer HV winding

  • 7/28/2019 Generator Protection Class presentation

    63/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    f f g

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    StatorEarth Fault Protection

  • 7/28/2019 Generator Protection Class presentation

    64/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Stator Earth fault in transformer HV winding

  • 7/28/2019 Generator Protection Class presentation

    65/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    f f g

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Earth fault in transformer HV winding

  • 7/28/2019 Generator Protection Class presentation

    66/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg

    f f g

    51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Earth fault in transformer LV winding

  • 7/28/2019 Generator Protection Class presentation

    67/123

    Endangering condition Overvoltage in two healthy phases

    Voltage in the star point Relatively small earth fault current

    Protected object

    Transformer winding

    Consequences

    Small possibility to damage transformer

    core Risk of second earth fault

    Earth-Fault in the LV Winding

  • 7/28/2019 Generator Protection Class presentation

    68/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Earth-Fault in the LV Winding

  • 7/28/2019 Generator Protection Class presentation

    69/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Earth-Fault in the LV Winding

  • 7/28/2019 Generator Protection Class presentation

    70/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Turn to turn turn fault in the stator winding :

  • 7/28/2019 Generator Protection Class presentation

    71/123

    Earth-Fault in the LV Winding

  • 7/28/2019 Generator Protection Class presentation

    72/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Earth-Fault in the LV Winding

  • 7/28/2019 Generator Protection Class presentation

    73/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    51N detected the fault whenIt developes

    Earth-Fault in the LV Winding

  • 7/28/2019 Generator Protection Class presentation

    74/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    51N detected the fault whenIt developes

    Rotor Earth Fault :

  • 7/28/2019 Generator Protection Class presentation

    75/123

    The field circuit of the generator is normally isolated

    from earth

    With a single earth fault in the rotor circuit it is possible

    to have continuous operation without generator

    damages

    There is however a risk of a second rotor earth fault. In

    such a case there will be large current and risk of severedamages.

    The requirement of fast fault clearance is moderate

  • 7/28/2019 Generator Protection Class presentation

    76/123

    Earth-Fault in Rotor Winding :

  • 7/28/2019 Generator Protection Class presentation

    77/123

    Endangering condition

    None

    Protected object

    Rotor windingConsequences

    Risk of evolving into double earth fault

    g

    Earth-Fault in the Rotor

  • 7/28/2019 Generator Protection Class presentation

    78/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Earth-Fault in the Rotor

  • 7/28/2019 Generator Protection Class presentation

    79/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

  • 7/28/2019 Generator Protection Class presentation

    80/123

    Loss of/Under excitation

  • 7/28/2019 Generator Protection Class presentation

    81/123

    Endangering condition

    Stator reactive current component

    Protected object Rotor and stator winding

    Consequences

    Thermal damage of rotor and statorend regions

    Asynchronous machine operation

    Voltage and current variations

    Earth-Fault in the Rotor

  • 7/28/2019 Generator Protection Class presentation

    82/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    Y

    Y

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Earth-Fault in the Rotor

  • 7/28/2019 Generator Protection Class presentation

    83/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87GGen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Generator motoring protection

  • 7/28/2019 Generator Protection Class presentation

    84/123

    Generator shall produce active power (i.e. P>0)

    When it starts to receive the active power it acts as a

    motor (i.e. P

  • 7/28/2019 Generator Protection Class presentation

    85/123

    loss of prime-mover

    low water flow (hydro) load variations I problems

    Effects

    steam units overheating of turbine and turbine blade

    hydro units cavitations of the blades

    Reverse Power Protection

  • 7/28/2019 Generator Protection Class presentation

    86/123

    Endangering condition

    Motor operation

    Protected object

    Turbine

    Consequences Excessive heating of turbine blades (steam units)

    Mechanical damages to thrust bearing (Francisturbines) Explosion risk for diesel units

    Reverse Power Protection

  • 7/28/2019 Generator Protection Class presentation

    87/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Reverse Power Protection

  • 7/28/2019 Generator Protection Class presentation

    88/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    59N

    OV

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    Negative sequence overcurrent

  • 7/28/2019 Generator Protection Class presentation

    89/123

    From asymmetric currents, a negative sequence current

    component12, is filtered out.

    Negative sequence stator currents rotate in a oppositedirection from the rotor and consequently induce a

    100Hz current component into the rotor.

    As a consequence rotor ends can over-heat.

    k is the indicator of how long (Sec.) a

    generator can withstand one/unit Neg.seq.Cur.

    Negative phase sequence (46)

  • 7/28/2019 Generator Protection Class presentation

    90/123

    Causes

    unbalanced loads untransposed transmission circuits

    unbalanced system faults

    series faults

    CB pole discrepancy open circuits

    Features

    Characteristic adjustable to I22t = KK determines the right tripping time , which is

    provided by the manufacturer (one/unit Neg.seq.Cur)

    StatorEarth Fault Protection

  • 7/28/2019 Generator Protection Class presentation

    91/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    StatorEarth Fault Protection

  • 7/28/2019 Generator Protection Class presentation

    92/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Broken stator winding

  • 7/28/2019 Generator Protection Class presentation

    93/123

    Endangering condition

    Unsymmetrical currents

    Protected object

    Stator windings

    Rotor

    Consequences

    Rotor overheating

    Vibrations

    Broken transformer winding

  • 7/28/2019 Generator Protection Class presentation

    94/123

    Endangering condition Unsymmetrical currents

    Protected object Stator windings

    Rotor

    Consequences

    Rotor overheating Vibrations

    Diff l k fl

    StatorEarth Fault Protection

  • 7/28/2019 Generator Protection Class presentation

    95/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Pole slip / out of step protection

  • 7/28/2019 Generator Protection Class presentation

    96/123

    Asynchronous running of a synchronous machine with the rest ofthe system but with excitation intact

    Big mechanical impact on turbine and shaft

    Pole Slip typically caused by: Long fault clearance time (especially close by 3Ph faults arecritical) Inadvertent tripping of a transmission line (increase oftransmission impedance between generator and load) Loss of large generator unit

    Pole slip / out of step protection

    E d i diti

  • 7/28/2019 Generator Protection Class presentation

    97/123

    Endangering condition High stator current

    Possible system blackout

    Protected object

    Rotor shaft and stator winding

    Consequences

    Mechanical damages to shaft Asynchronous machine operation (withfield intact) Voltage and current variations

    Diff l B k fl

    Pole slip / out of step protection

  • 7/28/2019 Generator Protection Class presentation

    98/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Diff l B k fl OC

    Pole slip / out of step protection

  • 7/28/2019 Generator Protection Class presentation

    99/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    Neg.Pha.

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Low frequency

  • 7/28/2019 Generator Protection Class presentation

    100/123

    Endangering condition

    Under-frequency

    Protected object

    Transformer

    Steam turbine

    Consequences

    Over-excitation

    Steam turbine vibrations

    Diff rel Brk flr OC Th

    Low frequency

  • 7/28/2019 Generator Protection Class presentation

    101/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Diff rel Brk flr OC Th

    Low frequency

  • 7/28/2019 Generator Protection Class presentation

    102/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87Oo/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    High Frequency

  • 7/28/2019 Generator Protection Class presentation

    103/123

    Endangering condition

    Over-frequency

    Protected object Turbine

    Rotor

    Consequences

    Mechanical stresses

    Turbine vibrations

    Diff rel Brk flr OC Th

    Low frequency

  • 7/28/2019 Generator Protection Class presentation

    104/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Diff rel Brk flr OC Th

    Low frequency

  • 7/28/2019 Generator Protection Class presentation

    105/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78

    Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

  • 7/28/2019 Generator Protection Class presentation

    106/123

    Over Voltage Protection:

  • 7/28/2019 Generator Protection Class presentation

    107/123

    Endangering condition

    Over-voltage Improper voltage regulation

    Protected object

    Electrical circuits

    Consequences

    Increased risk for earth-faults

    Over-excitation

    g

    Diff rel Brk flr OC Therm

    Over Voltage Protection:

  • 7/28/2019 Generator Protection Class presentation

    108/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Diff rel Brk flr OC Therm

    Over Voltage Protection:

  • 7/28/2019 Generator Protection Class presentation

    109/123

    Y

    G

    87 N

    Diff.rel.50BFBrk.flr.

    50/51

    OC49

    Therm.

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Over-fluxing

  • 7/28/2019 Generator Protection Class presentation

    110/123

    Over fluxing protection protects generator and

    transformer magnetic core against overheating

    Specially critical during start-up and shut-down

    Wide frequency operation of the relay important forgenerator

    protection

  • 7/28/2019 Generator Protection Class presentation

    111/123

    Diff.rel. Brk.flr. OC Therm

    Over Voltage Protection:

  • 7/28/2019 Generator Protection Class presentation

    112/123

    Y

    G

    87 N

    e50BFBrk.flr.

    50/51

    OC49

    Therm.

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

  • 7/28/2019 Generator Protection Class presentation

    113/123

    Diff.rel. Brk.flr. OC Therm

    Stator Thermal Overload

  • 7/28/2019 Generator Protection Class presentation

    114/123

    Y

    G

    87 N 50BF 50/51OC

    49

    Therm.

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitX

    for.

    46

    Neg.Pha.

    Diff.rel. Brk.flr. OC Therm

    Stator Thermal Overload

  • 7/28/2019 Generator Protection Class presentation

    115/123

    Y

    G

    87 N 50BF 50/51OC

    49

    Therm.

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitXfor.

    46

    Neg.Pha.

  • 7/28/2019 Generator Protection Class presentation

    116/123

  • 7/28/2019 Generator Protection Class presentation

    117/123

    Diff.rel. Brk.flr. OC Therm.

    Stator Thermal Overload

  • 7/28/2019 Generator Protection Class presentation

    118/123

    Y

    G

    87 N 50BF 50/51 49Therm.

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitXfor.

    46

    Neg.Pha.

    Diff.rel. Brk.flr. OC Therm.

    Stator Thermal Overload

  • 7/28/2019 Generator Protection Class presentation

    119/123

    Y

    G

    87 N 50BF 50/51 49

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    O.C

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitXfor.

    46

    Neg.Pha.

    Breaker Failure (50BF)

  • 7/28/2019 Generator Protection Class presentation

    120/123

    87 N

    Diff.rel.50BFBrk.flr. OC Therm.

    Stator Thermal Overload

  • 7/28/2019 Generator Protection Class presentation

    121/123

    Y

    G

    87 N 50BF 50/51 49

    87O

    o/a Diff51OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    BF

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitXfor.

    46

    Neg.Pha.

    87 N

    Diff.rel.50BFBrk.flr. OC Therm.

    Stator Thermal Overload

  • 7/28/2019 Generator Protection Class presentation

    122/123

    Y

    G

    87 N 50BF 50/51 49

    87O

    o/a Diff51

    OC

    50/51

    OC

    YY

    YY

    51

    OC

    60

    FL81

    Freq.rel.

    50

    Ac.Eneg51/67

    OC(Idm/dir.)

    50

    BF

    87G

    Gen.st.dif

    50

    Neg.Pha.

    49

    Therm.

    59N

    O.V

    64S

    100%GFP

    50THD

    100%GFP

    + REX0060

    78Out of step

    21

    Udr.Imp.pro.

    32

    Rev. Pow.

    37

    Under curr.

    40

    FIELD.EXCIT

    24

    OVER EXCIT

    27

    UND.VOL.

    59

    OVER.VOL.

    81

    FREQ.

    64S

    100%GFP + REX0061

    UnitXfor.

    46

    Neg.Pha.

  • 7/28/2019 Generator Protection Class presentation

    123/123

    THANK YOU


Recommended