63g Multilin
Gen
erat
or P
rote
ctio
n
• Completeprotectionforsmalltomediumsizedgenerators• CompleteIEC61850ProcessBussolutionprovidingresource
optimizationandminimizingtotalP&Clifecyclecosts• Combinedgeneratorandtransformerprotection• Advancedautomationcapabilitiesforprovidingcustomized
protectionandcontrolsolutions• RobustnetworksecurityenablingCriticalInfrastructure
Protectionthroughusercommandlogging,anddualpermissionaccesscontrol
• ApplicationflexibilitywithmultipleI/Ooptionsandprogrammablelogic(FlexLogic™)
• High-endfaultanddisturbancerecordingeliminatingtheneedforredundantrecordingdevices
• Ambienttemperaturemonitoringwithalarmingwhenoutsidetemperatureexceedsupperthresholds
• High-speedpeer-to-peercommunicationsallowingreductionofrelaytorelaywiringandassociatedinstallationcosts
• EmbeddedIEC61850Protocol
• Smalltomediumsizedgeneratorstypicallydrivenbesteam,gasorhydraulicturbines
• PumpedStorageGenerators
• CombinedGeneratorandTransformerinthezoneofprotection
• DistributedGenerator(DG)interconnectprotectionperIEEE1547
• Metering-current,voltage,power,energy,frequency• Oscillography–analoganddigitalparametersat
64samples/cycle• EventRecorder-1024timetaggedeventswith0.5msscanof
digitalinputs• DataLogger-16channelswithsamplingrateupto
1sample/cycle• SettingSecurityAuditTrailfortrackingchangestoG30
configuration
Monitoring and Metering
Protection and Control• Overallunitdifferentialincludingtransformer• Restrictedgroundfault• Splitphaseprotection• Lossofexcitation,overexcitation• Thirdharmonicneutralundervoltage• Generatorunbalance• Reverseandlowforwardpower• Accidentalenergization• Synchronismcheck• Phasesequencereversalforpumpedstorage
EnerVistaTM Software• GraphicalLogicDesignerandLogicMonitortosimplify
designingandtestingprocedures• EnerVistaTMIntegratorprovidingeasyintegrationofdatain
theG30intoneworexistingmonitoringandcontrolsystems
Communications• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,
RS232,RS422,G.703,C37.94• MultipleProtocols-IEC61850,DNP3.0Level2,ModbusRTU,
ModbusTCP/IP,IEC60870-5-104,EthernetGlobalData(EGD)• DirectI/O–secure,high-speedexchangeofdatabetween
URsfortransformertrippingapplications• EmbeddedManagedEthernetSwitchwith4-100MbitFiber
opticportsand2copperports
G30GEnEraTor
ProTECTion SySTEMSmalltomediumgenerators&combinedgeneratorsandtransformerprotection
FEaTurES
aPPliCaTionS
KEy BEnEFiTS
• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingG30functions• Redundantarchitecturefordependabilityandsecurity
iEC 61850 Process Bus interface
www.GEMultilin.com64
G30Generator Protection SystemG
ener
ator
Pro
tect
ion
Protection and ControlThe G30 Generator protection systemprovides comprehensive protection forsmall to medium sized steam, hydraulicand combustion-turbine generatorsas well as applications that have boththe generator and transformer inthe same zone of protection. The G30is ideal for protecting single and multi-polegeneratorswith singleor split phasewindingsconfigurationofgenerators.TheG30 includes advanced automation andcommunication capabilities, extensiveI/O options, and powerful fault recordingfeatures that can simplify fault anddisturbancetroubleshootingandminimizegenerator downtime. As part of the URfamily,theG30providessuperiorprotectionandcontrolthatincludes:
Generator/Transformer Differential
High-speedpercentdifferentialprotectionis provided for detecting and clearingboth generator stator and transformerwinding faults that occur in the zone ofprotection of a single generator. Thedifferential protection element has built-in phase compensation and magnitudecompensationcharacteristicsthatallowfordealingwiththeinherentoffsetthatoccurswith CTs located on different windingsof the transformer. These compensationcharacteristics eliminate the need forinstalling additional interposing CTs to
account for the difference in parametersmeasuredbytherelay.
2nd Harmonic inrush inhibit
The G30 utilizes a 2nd Harmonic InrushInhibit function to block the G30 fromtripping under transformer inrushconditions that can otherwise causethe differential element to maloperate.This element can be configured toinclude energization of different types oftransformersbyusingeitheratraditionaloradaptivemodeof2ndHarmonicrestraint.
The adaptive 2nd harmonic restraintmaintains protection dependability andspeed on internal faults while ensuringsecurityduringinrushconditionsevenwithweaksecondharmonics.
overexcitation inhibit
An increase in transformer voltage ordecrease in system frequencymay resultin overexcitation of the transformer. It isoften desirable to prevent operation ofthe percent differential element in thesecasesthereforeafirthharmonicinhibitis
PTs Located on Transformer HV Side
G30 Generator Protection System
24
34
50G27X 59X
METERING87GT
40 50P 50N 51P 51N 46 67N
51G27TN
67P
64REF
67_250/27
27P 59P 59_2 59N 81O 81U 81R
25CLOSETRIP
Functional Block Diagram
The G30 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into HMI or SCADA monitoring and control systems like Viewpoint Monitoring as shown.
G30 - Protection, Metering, Monitoring and Control
DeviceNumber Function24 VoltsPerHertz25 SynchronismCheck27P PhaseUndervoltage27TN ThirdHarmonicNeutralUndervoltage27X AuxiliaryUndervoltage27/50 AccidentalEnergization32 DirectionalPower40 LossofExcitation46 StatorCurrentUnbalance50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50SP SplitPhaseInstantaneousOvercurrent51G GroundTimeOvercurrent51P PhaseTimeOvercurrent59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage59_2 NegativeSequenceOvervoltage67_2 NegativeSequenceDirectionalOvercurrent67N NeutralDirectionalOvercurrent67P PhaseDirectionalOvercurrent81O Overfrequency81R RateofChangeofFrequency81U Underfrequency87GT Generator/TransformerDifferential87RGF RestrictedGroundFault
ANSIDeviceNumbers&Functions
www.GEMultilin.com 65
G30Generator Protection System
Gen
erat
or P
rote
ctio
n
No Transformer
G30 Generator Protection System
24
34
87G 50G27X 59X
METERING87
40 50P 50N 51P 51N 46 67N
51G27TN
67P 67_250/27
27P 59P 59_2 59N 81O 81U 81R
25CLOSETRIP
integratedintopercentdifferentialfunctionto protect for overexcitation conditionsresulting from an increased V/Hz ratio.Theoverexcitation inhibitworksonaper-phasebasisandisuserdefinable.
Split Phase Protection
Split phase protection is provided forsensitivedetectionforinter-turnfaultsandcanberuninconjunctionwiththeprimarystatordifferentialprotection. Independentsettingsareprovidedonaper-phasebasisand a single-slope bias characteristic isusedtoallowoperationonmachineswithasectionofwindingbypassed.
restricted Ground Fault (rGF)
Restricted Ground Fault protection (alsoknown as zero sequence differential)extendsprotectioncoveragetotheneutralpoint of the stator winding, where faultcurrentsmay be below the pickup of themain stator differential element. The low-impedanceRGFprotectionprovidedbytheG30 uses an optimized adaptive restraintsignal that provides security for externalfault conditions that may cause CTsaturationwhilestillmaintainingsensitivityforinternalfaults.
Sensitive Directional Power
Two separate directional power elementsare provided to detect reverse and lowforward power conditions that is oftenneeded for ensuring power only flows inone direction through the breaker. Eachelement responds to either reverse orlow forwardpower flowandcanbeusedto provide independent alarm and tripsettings.
loss of Excitation
Generator loss of excitation protectionis provided via two negative offset mhocharacteristics as per IEEE C37.102.Independentpickuptimedelaysettingsandblocking input provide security for blownVTfusesandpowerswingconditions.
Frequency rate of Change
Thefouravailablefrequencyrateofchange(df/dt) elements can be used to provideprotection against system disturbancesthrough load shedding and to provideanti-islandingprotection. Theseelementsmonitorthespeedbywhichthefrequencychangesinanydirection,throughvoltage,current,andfrequencysupervision.
Pump Storage Generator
The G30 can be used for protectinggenerators that are also run as pumpstorage motors without the need forswitchingtheCTsecondarycircuitry. TheG30 is able to automatically compensatefor the phase reversal that occurs whenthegeneratorisbeingrunasamotor.
Synchronism Check
The G30 provides elements to monitordifferences in voltage magnitudes,phase angles, and frequencies toperform synchronism check across up totwo breakers. The G30 can be used inconjunctionwithanexternalsynchronizeras an independent check of thesynchronizerpriortoclosingthegeneratorbreaker.
iEC 61850 Process BusThe IEC 61850 Process Bus module isdesigned to interfacewith theGEMultilinHardFiber System, allowing bi-directionalIEC61850fiberopticcommunications.TheHardFiberSystemisdesignedtointegrateseamlesslywiththeexistingUniversalRelay
The Adaptive 2nd Harmonic Inhibit function will stop blocking the differential element as soon as the 2nd harmonic level drops below the pickup level if the angle of the 2nd Harmonic to Fundamental ratio is close to 0° or 180° (Point A). If the angle of the 2nd Harmonic to Fundamental ratio is close to 90°or 270°, this is a indication that the transformer is an inrush condition even if the magnitude drops below the pickup level, the Adaptive 2nd Harmonic Inhibit function will continue to block the differential element for an extended period of time (Point B).
2nd Harmonic Blocking Characteristic
www.GEMultilin.com66
G30Generator Protection SystemG
ener
ator
Pro
tect
ion
applications,includingprotectionfunctions,FlexLogic,meteringandcommunications.
TheGEMultilinHardFiberSystemoffersthefollowingbenefits:
• CommunicatesusingopenstandardIEC61850messaging
• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations
• IntegrateswithexistingG30’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule
• DoesnotintroducenewCyberSecurityconcerns
VisittheHardFiberSystemproductpageontheGEMultilinwebsiteformoredetails.
advanced automationTheG30incorporatesadvancedautomationfeatures including powerful FlexLogic™programmable logic, communication,andSCADA capabilities that far surpass whatis found in the average generator relay.TheG30 integrates seamlesslywith otherURrelaysforcompletesystemprotection,includingtheunitandauxiliarytransformers,andBalanceofPlantprotection.
Flexlogic™
FlexLogic™ is the powerful UR platformprogramming logic engine that providestheabilityofcreatingcustomizedprotectionand control schemes thereby minimizingthe need, and the associated costs, ofauxiliarycomponentsandwiring.Using FlexLogic™, the G30 can beprogrammed to provide required trippinglogic along with custom scheme logicfor generator breaker control (includinginterlocking with external synchronizers),transfer tripping schemes for remotebreakers and dynamic setting groupchanges.
Scalable HardwareTheG30isavailablewithamultitudeofI/Oconfigurationstosuitthemostdemandingapplicationneeds.Theexpandablemodulardesign allows for easy configuration andfutureupgrades.
• MultipleCT/VTconfigurationsallowforimplementationofmanydifferentialschemes,includingconcurrentsplit-phaseanddifferentialprotection
• Upto80digitalinputsandupto56digitaloutputsareavailable
• Typesofdigitaloutputsincludetrip-ratedForm-AandSolidStateRelay(SSR)mechanicallylatching,andForm-Coutputs
• RTDsandDCmAinputsareavailabletomonitorequipmentparameterssuchastemperature&pressure
Monitoring and MeteringTheG30 includeshighaccuracymeteringand recording for all AC signals. Voltage,current,andpowermeteringarebuiltintothe relay as a standard feature. Currentand voltage parameters are availableas total RMS magnitude, and asfundamental frequency magnitude andangle.
Fault and Disturbance recording
The advanced disturbance and eventrecording features within the G30 cansignificantly reduce the time needed forpostmortem analysis of power systemeventsandcreationof regulatoryreports.Recordingfunctionsinclude:
• SequenceofEvent(SOE)-1024timestampedevents
• Oscillography,
-64digital&upto40Analogchannels
• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel
• FaultReports-Powerfulsummaryreportofpre-faultandfaultvalues
The very high sampling rates and largeamounts of storage space available fordata recording in the G30 can eliminatethe need for installing costly standalonerecordingequipment.
advanced Device Health Diagnostics
The G30 performs comprehensive devicehealthdiagnostictestsduringstartupandcontinuously at runtime to test its ownmajor functions and critical hardware.These diagnostic tests monitor forconditions thatcould impactsecurityandavailability of protection, and present
FlexlogicTM Designer
Flexlogic allows for customizing the G30 to operate and control the breakers and other auxiliary devices needed to fit most generator protection schemes and applications.
www.GEMultilin.com 67
G30Generator Protection System
Gen
erat
or P
rote
ctio
n
device status via SCADA communicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issues helps improve systemuptime.
• Comprehensivedevicehealthdiagnosticperformedduringstartup
• MonitorstheCT/VTinputcircuitrytovalidatetheintegrityofallsignals
• Input,outputs,tripcircuitsandanalogchannelsarecontinuouslymonitoredforaccuracyandperformance
CommunicationsThe G30 provides advanced commun-icationstechnologiesforremotedataandengineering access,making it the easiestandmostflexiblegeneratorprotectionrelaytouseandintegrateintonewandexistinginfrastructures. Direct support for fiberoptic Ethernet provides high-bandwidthcommunications allowing for low-latencycontrols and high-speed file transfers ofrelay fault and event record information.The available redundant Ethernet optionand the embedded managed Ethernetswitchprovidethemeansofcreatingfaulttolerant communication architectures inan easy, cost-effective manner without
theneedfor intermediarycommunicationhardware.The G30 supports the most popularindustrystandardprotocolsenablingeasy,direct integration into DCS and SCADAsystems.
• IEC61850
• DNP3.0
• EthernetGlobalData(EGD)
• IEC60870-5-104
• ModbusRTU,ModbusTCP/IP
interoperability with Embedded iEC61850
Use the G30with integrated IEC61850 tolower costs associated with substationprotection, control and automation. GEMultilin’s leadership in IEC61850 comesfrom thousands of installed devices andfollows on seven years of developmentexperiencewithUCA2.0.
• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging
• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVistaViewpointEngineer
• IntegrateGEMultilinIEDsandgenericIEC61850compliantdevicesseamlesslyinEnerVistaViewpointMonitoring
Direct i/o Messaging
DirectI/Oallowsforsharingofhigh-speeddigital information between multiple URrelaysviadirectback-to-backconnectionsor multiplexed through a standard DS0multiplexer channel bank. Regardless oftheconnectionmethod,DirectI/Oprovidescontinuous real-time channel monitoringthat supplies diagnostics information onchannelhealth.Direct I/Oprovides superior relay-to-relaycommunications that can be used inadvancedinterlocking,generationrejectionandotherspecialprotectionschemes.
• Communicationwithupto16URrelaysinsingleorredundantringsratherthansimplisticpoint-to-pointconfigurations
• ConnecttostandardDS0channelbanksthroughstandardRS422,G.703orIEEEC37.94interfacesorviadirectfiberopticconnections
• Built-incontinuousloopandchannelmonitoringprovidesreal-timediagnosticsofyourcommunicationchannels–noexternalorhandheldtesterrequired
Power System Troubleshooting
The G30 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.
www.GEMultilin.com68
G30Generator Protection SystemG
ener
ator
Pro
tect
ion
Multi-language
TheG30supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista setup software, and productmanual. Easily switch between Englishand an additional language on the localdisplayswithoutuploadingnewfirmware.
EnerVistaTM SoftwareTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifiesevery aspect of using the G30 relay. TheEnerVista suite provides all the tools tomonitor the status of your generator,maintain your relay, and integrateinformation measured by the G30 intoDCS or SCADA monitoring systems.Convenient COMTRADE and Sequenceof Events viewers are an integral partof the UR Setup software included withevery UR relay, to carry out postmortemeventanalysistoensureproperprotectionsystemoperation.
EnerVista™ launchpad
EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallof thesetupandsupport toolsneeded
forconfiguringandmaintainingGEMultilinproducts. The setup software withinLaunchpad allows configuring devices inreal-timeby communicating using serial,Ethernet,ormodemconnections,orofflineby creating setting files to be sent todevicesatalatertime.
Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:
• Manuals
• ApplicationNotes
• GuideformSpecifications
• Brochures
• WiringDiagrams
• FAQs
• ServiceBulletins
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems. ViewpointMonitoring provides a
completeHMI packagewith the followingfunctionality:
• Plug&PlayDeviceMonitoring
• SystemSingle-LineMonitoring&Control
• AnnunciatorAlarmScreens
• TrendingReports
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
Viewpoint Engineer
ViewpointEngineerisasetofpowerfultoolsthatwillallowyoutoconfigureandtestURrelays at a system level in an easy-to-usegraphicaldrag-and-dropenvironment.ViewpointEngineerprovides the followingconfigurationandcommissioningutilities:
• GraphicalLogicDesigner
• GraphicalSystemDesigner
• GraphicalLogicMonitor
• GraphicalSystemMonitor
Viewpoint Maintenance
ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:
• SettingsSecurityAuditReport
• DeviceHealthReport
• SingleClickFaultDataRetrieval
EnerVista™ integrator
EnerVistaTMIntegratorisatoolkitthatallowsseamlessintegrationofGEMultilindevicesinto new or existing automation systems.IncludedinEnerVistaTMIntegratoris:
• OPC/DDEServer
• GEMultilinDrivers
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
The G30 tracks and records information about configuration changes that have been made to the relay thereby providing a method of auditing system security and engineering processes
Providing Traceability and regulatory audit Tracking
www.GEMultilin.com 69
G30Generator Protection System
Gen
erat
or P
rote
ctio
n
Typical Wiring
user interfaceThe G30 front panel provides extensivelocal HMI capabilities. The local displayis used formonitoring, statusmessaging,fault diagnosis, and device configuration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.
LEDIndicators
Multi-LanguageDisplay• English• Russian• French• Chinese
UserProgrammablePushbuttons
G60-H00-HCH-F8F-H6G-M8H-PXX-uXX-WXX
830744A2.CDR
1
PowerSupply
9
CPU
JU MX LW KV BHT DN G FPS Rminimum
GROUNDBUS
DCG30 GENERATOR MANAGEMENT RELAY
RS-232
DB-9
(front)
UR COMPUTER
1
TXD RXD
RXD TXD
SGND SGND
1 832
207645
22
CONNECTORCONNECTOR
2 23 34 45 56 67 78 89 9
6
Inputs/outputs
8
VT/CT
8
CT
TC
TC
2
1
SURGE
H6a
H8a
H5b
H7b
H8b
H5a
H7a
H6c
H8c
H5c
H7c
6G H1a
H2b
H1cH1b
H2c
H2a
H4a
H4c
H3bH3a
H4b
H3c
H1
H2
H3
H4
I
V
I
V
I
V
I
V
CRITICALFAILURE
OUTPUT
CONTROLPOWER
HILO
1
FILTERSURGE
B3a
B1b
B8a
B6b
B8b
B6a
B3b
B1aB2b
B5b
PROVIDED
F1a
F1b
F1c
F2a
F2b
F2c
F3a
F4a
F5a
F6a
F7a
F8a
F3b
F4b
F5c
F6c
F7c
F8c
F3c
F4c
VA VB
VC VXVA VB
VC VXIA ICIB IG
IA5
IC5
IB5
IG5
IA1
IC1
IB1
IG1
F5a
F6a
F7a
F5c
F6c
F7c
VA VB
VCVA VB
VC
M1a
M1b
M1c
M2a
M2b
M2c
M3a
M4a
M3b
M4b
M3c
M4c
IA ICIB IGIA5
IC5
IB5
IG5
IA1
IC1
IB1
IG1
Multilin
B
A
C
R
52
ALTERNATE
B
A
C
NOTE:
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
G30 - * 00 - H * * - F ** - H ** - M ** - P ** - u ** - W/X ** For Full Sized Horizontal MountBaseUnit G30 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable) G RS485+Multi-modeST10BaseF H RS485+Multi-modeSTRedundant10BaseF J RS485+Multi-modeST100BaseFX K RS485+Multi-modeSTRedundant100BaseFX N RS485+10/100BaseT S RS485+6port,100Mbps,ManagedEthernetSwitchSoftwareOptions 00 NoSoftwareOptions 01 EthernetGlobalData(EGD) 03 IEC61850 04 EthernetGlobalData(EGD)+IEC61850Mount/Coating H Horizontal(19"rack)-Standard A Horizontal(19"rack)-HarshEnvironmentCoating V Vertical(3/4size)-Standard B Vertical(3/4size)-HarshEnvironmentCoatingUserInterface K EnhancedEnglishFrontPanel L EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttons M EnhancedFrenchFrontPanel N EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttons Q EnhancedRussianFrontPanel T EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttons U EnhancedChineseFrontPanel V EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons F VerticalFrontPanelwithEnglishdisplayPowerSupply H 125/250VAC/DC H RH 125/250VAC/DCwithredundant125/250VAC/DC L 24-48V(DConly)CT/VTDSP 8L 8L Standard4CT/4VTw/enhanceddiagnostics 8M 8M SensitiveGround4CT/4VTw/enhanceddiagnostics 8N 8N Standard8CTw/enhanceddiagnostics 8R 8R SensitiveGround2CT/6VTw/enhanceddiagnosticsIEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX XX NoModule 4A 4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs 4C 4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs 4D 4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish 4L 4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs 67 67 67 67 67 67 8Form-A(NoMonitoring)Outputs 6C 6C 6C 6C 6C 6C 8Form-COutputs 6D 6D 6D 6D 6D 6D 16DigitalInputs 6E 6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs 6F 6F 6F 6F 6F 6F 8FastForm-COutputs 6K 6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs 6L 6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs 6M 6M 6M 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs 6N 6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs 6P 6P 6P 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs 6R 6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs 6S 6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs 6T 6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs 6U 6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs 6V 6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputsTransducerI/O 5C 5C 5C 5C 5C 5C 8RTDInputs 5E 5E 5E 5E 5E 5E 4dcmAInputs,4RTDInputs 5F 5F 5F 5F 5F 5F 8dcmAInputsInter-RelayCommunications 7A 820nm,multi-mode,LED,1Channel 7B 1300nm,multi-mode,LED,1Channel 7C 1300nm,single-mode,ELED,1Channel 7H 820nm,multi-mode,LED,2Channels 7I 1300nm,multi-mode,LED,2Channels 7J 1300nm,single-mode,ELED,2Channels 7R G.703,1Channels 7S G.703,2Channels 7T RS422,1Channels 7W RS422,2Channels 76 IEEEC37.94,820nm,multimode,LED,1Channel 77 IEEEC37.94,820nm,multimode,LED,2Channel 2A C37.94SM,1300nmSinglemode,ELED,1ChannelSinglemode 2B C37.94SM,1300nmSinglemode,ELED,2ChannelSingle 2S 6port,100Mbps,ManagedEthernetSwitch,HI(125/250VAC/DC) 2T 6port,100Mbps,ManagedEthernetSwitch,LO(24-48Vdc)ttt
www.GEMultilin.com70
G30Generator Protection SystemG
ener
ator
Pro
tect
ion
ordering
ordering note: ToviewthelatestoptionsavailablefortheG30,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.
• URApplicationsILearningCD TRCD-URA1-C-S-1
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointEngineer VPE-1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
accessories for the G30 • ViewGuideformspecifications
• Downloadtheinstructionmanual
• ReviewapplicationsNotesandsupportdocuments
• BuyaG30online
• ViewtheURFamilybrochure
Visit www.GEMultilin.com/G30 to: