of 16
7/25/2019 GISmon Sw Man e305
1/16
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
PD Power Diagnostix
GISmonitorPartial Discharge Monitoring
Software Manual
Rev. 3.05
7/25/2019 GISmon Sw Man e305
2/16
GISmonitor Partial Discharge Monitoring
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
Contents
I
Introduction .............................................................................................................................................. 1
II GISm o n i t o r Software ............................................................................................................................... 1
II.1
Detailed Data of a Sensor ...................................................................................................................... 2
II.2 Alarm and Warning Event Lists ............................................................................................................. 3
II.3 Status Overview ..................................................................................................................................... 4
II.4 Analysis Function ................................................................................................................................... 5
II.4.1 Zooming and Shifting of the Graph ................................................................................................ 5
III Configuration of the Software ................................................................................................................ 7
III.1 Project Settings ...................................................................................................................................... 7
III.2
Creating and Positioning of Sensors ..................................................................................................... 8
III.3 General Setting ...................................................................................................................................... 9
III.4 Rack Settings ....................................................................................................................................... 10
III.5
Device Settings .................................................................................................................................... 11
III.6 Alarmsettings ....................................................................................................................................... 13
III.6.1 Alarm Configuration ...................................................................................................................... 13
III.6.2
Alarm Output Configuration .......................................................................................................... 13
III.7 Load and Save a Project ..................................................................................................................... 14
III.8
Password Request ............................................................................................................................... 14
Copyright 2014 by Power Diagnostix. All rights reserved. No part of the content of this manual may be
reproduced or transmitted in any form or by any other means without the written permission of the publisher.
Product and company names herein may be the trademarks of their respective owners.
7/25/2019 GISmon Sw Man e305
3/16
GISmonitor Partial Discharge Monitoring
1
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
I Introduction
The GISmonitorsoftware visualizes the current readings of the partial discharge sensors of a GIS and indi-
cates alarm events or error messages. The main panel of the software shows a schematic of the GIS with
the position of the individual sensors. Each sensor is linked with a specific input channel of a GISmonitor.
The GISmonitorcollects and stores the data of each connected sensor. This data is then read and analyzed
by the GISmonitorsoftware and presented to the user in a variety of different visualizations.
II GISmonitorSoftware
The GISmonitorsoftware starts up in the Single Line Diagram. The sensors are visualized by colored hori-
zontal and vertical bars as shown in the figure below:
The schematic of the GIS is a drawing file, which is loaded by the software, whereas the sensors can be
positioned in the software individually. Sensors can be created, positioned and removed in the Edit Mode.
The configuration of the schematic and sensors is provided by Power Diagnostix during commissioning.
You can change the sensor colors in the Sensor/Colormenu. Default settings are green, yellow and blue for
appropriately working sensors of different phases. Black or grey sensors indicate false initiation or no con-
nection to the related GISmonitor. In case the connection between the GISmonitorand a sensor is lost, an
orange flashing frame will appear around the associated bar. In case of a warning the sensors color will turn
to orange, in case of an alarm to red.
7/25/2019 GISmon Sw Man e305
4/16
GISmonitor Partial Discharge Monitoring
2
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
II.1 Detailed Data of a Sensor
Double-clicking on a sensor displays a panel which shows the last trending data and the last values of this
sensor.
On the upper left hand site the name and the associated rack of the sensor is displayed. The Last NQS
Valueand Last Qp Valueof the trending file are shown as well as the set alarm levels. On the upper right
hand site the last stored pattern is displayed. The graphs beneath show the NQS and Qp trending values
for the last three days of the trending file. This time interval can be set by selecting the Options/Trending
Graph/Displayed Trending Records menu item. To get more detailed information about the sensor, the
Analysispanel can be opened by clicking the Analysisbutton. The Analysis panel provides the complete
trending data and allows the comparison between different sensors (Please refer to chapter II.4).
Press the Printbutton to either print the current panel or to save it as a file on the IPC.
7/25/2019 GISmon Sw Man e305
5/16
GISmonitor Partial Discharge Monitoring
3
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
II.2 Alarm and Warning Event Lists
All alarms and warnings are stored and can be displayed in the Eventslist. The Eventslist can be reached
via the tab menu in the top of the GISmonitorsoftware. The Sensor Alarm Event Listin the upper left dis-
plays all sensor alarm and warning events. By clicking on a specific event, the corresponding colored pat-
tern is illustrated on the upper right. The General Events List in the bottom displays all maintenance andhardware alarms. Each event is tagged with a timestamp and provides information about the location, the
type of error and a short description. To acknowledge an event, you can click the OK button, which w ill tag
the event with date and time of acknowledgement.
Sensor alarm and warning events can be reset by using the Reset-Buttonsin the middle left. Maintenance
and hardware alarms can be reset by using the Reset Buttonsin the bottom left.
The even lists can be exported as .xlsx files by clicking the Export Alarm Eventsor Export General Events
button. The list shows the alarm and warning events sorted by the time they occur. It also shows whether
the alarm has triggered the relays of the I/O card (SCADA Alarm).
7/25/2019 GISmon Sw Man e305
6/16
GISmonitor Partial Discharge Monitoring
4
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
II.3 Status Overview
The GISmonitorsoftware is providing a status overview of the hole monitoring system in the Statustab. The
colored overview indicates among others the status of the lightning protection, the heating, the network ring,
the ventilation and the uninterruptible power supply (USV) for every Partial Discharge Measurement Acqui-
sition Rack(PDMAR).
A green colored box indicates the device is in operation, while dark grey signifies the device is not operat-
ing. If the device is not integrated in this rack, the overview will indicate this by light grey whereas white
signifies no connection to this device.
7/25/2019 GISmon Sw Man e305
7/16
GISmonitor Partial Discharge Monitoring
5
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
II.4 Analysis Function
For a detailed analysis of the trending data of the sensors, the Analysispanel can be opened by pressing
theAnalysisbutton. Up to eight sensors can be selected.
On the left hand site there is a list with all defined sensors. In the middle there are the NQS and Qp trending
graphs and the pattern of the selected sensors. On the right hand site there are the NQS and Qp values of
the sensors at the cursor position. The data of a sensor is displayed, if the sensor is selected in the list on
the left hand site. To select a sensor, just click on it. To select more than one sensor, press and hold theCTRL key and click on the additional sensor. The data of up to 8 sensors can be displayed at the same
time. Moving the cursor shows the NQS and Qp values at the cursor position and displays the pattern next
to this time.
II.4.1 Zooming and Shifting of the Graph
Zooming and shifting of the graph in x direction is done using the zoom bar underneath the graph. By mov-
ing the mouse over the ends of the bar, the cursor changes to a left and right double arrow. By pressing the
left mouse button and dragging the cursor at the same time, the bar size and position can be modified. The
relation of the modified bar size to its maximum size determines range of trending information shown with
the main display. Moving the mouse to the middle of the bar changes the cursor to a hand pointer. Pressing
the left mouse button and dragging the cursor at the same time, the bar is moved which subsequently ad-
7/25/2019 GISmon Sw Man e305
8/16
GISmonitor Partial Discharge Monitoring
6
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
justs the displayed period. The data of the trending file determines the maximum time displayed. The mini-
mum possible time shown is ten times the time interval between two data sets in the file. The resolution of
the y-axis is adjusted by double clicking in the area of the y-axis scaling.
7/25/2019 GISmon Sw Man e305
9/16
GISmonitor Partial Discharge Monitoring
7
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
III Configuration of the Software
The GISmonitorsoftware is being provided by Power Diagnostix fully setup and individually configurated for
your On-line Partial Discharge Monitoring System. There should be no need to change the following op-
tions. Be aware that changing the set up might corrupt the software functionality by worsen the detection
and identification of partial discharges or preventing alarm and warning output. Some changes will lead to a
temporary disconnection between the PDMCR and the PDMAR. There will be no data recorded during this
timeframe.
It is highly recommended to create a backup by File/Save Project prior to all setup changes. To prevent a
loss of data the software additionally creates an autosave.gisfile every five minutes.
III.1 Project Settings
The main panel of the software displays a schematic of the GIS. The drawing file and the headline for the
schematic can be selected by Edit/Project Settings.
On the left side of the Project Settingsdialog box, the name for each bay can be selected. On the right side
a user-defined name of the substation and a headline for the drawing can be selected. The headline ap-
pears above the schematic in the main panel. The file with the schematic of the GIS must be of a WMF
format. By clicking the Filenamebutton the file can be selected. The Previewfield displays the selected file.
The GIS enclosure type can be set up as single or three phase enclosures. Pressing the OKbutton, will
load the selected file and display it on the main panel.
7/25/2019 GISmon Sw Man e305
10/16
GISmonitor Partial Discharge Monitoring
8
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
III.2 Creating and Positioning of Sensors
Creating and positioning a sensor is only possible in Edit Mode. The Edit Modecan be activated by either
pressing the Edit Modebutton or by selecting View/Mode/Edit.If thePassword Request Mode(see chapter
III.8) is enabled also the administrator password has to be typed in. The Edit Modeis indicated by the red-
colored button at the bottom left and some items are added to the toolbar at the upper left.
Vertical or horizontal sensors can be placed by double clicking on the Single-Line Diagram.The size of the
bar indicating the sensor and the font size of the labeling can be set individually. The sensor settings can be
modified in a menu opened by right clicking. The Label Alignmentmenu item allows changing the position of
the label. The label can be positioned on all four sides of the sensor and moved to any position when the
option Free Choiceis selected. The Sensor Typemenu item allows changing between horizontal and verti-
cal alignment of the bar. The Renamemenu item allows changing the label of the sensor. The Remove
menu item removes the sensor.
The Propertiesmenu item is reached by left clicking Properties. Thereby the selected sensor can be as-
signed to a specific phase and bay of the system.
7/25/2019 GISmon Sw Man e305
11/16
GISmonitor Partial Discharge Monitoring
9
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
III.3 General Setting
The General Settingsmenu can be reached via Edit/General Settings. The input field Setupallows the con-
figuration of the settings regarding the illustration of PD pattern. For instance the range of the ordinate and
the lower level of detection (LLD) can be set individually depending on the background noise level. The
constant phase shift of the displayed pattern referring to the synchronization voltage can be defined foreach phase.
In the middle of the dialogue box the synchronization and gating settings for each PDMAR can be adjusted.The synchronization can be switched between line and external synchronization. To avoid long cables for
synchronization, the outdoor cabinets use line-sync by default.
In case a disturbance antenna (DA2) is used, external gating can be enabled and a threshold can be de-
fined. This will provide noise suppression created by cell phones, corona effects and similar.
At the bottom part of the dialogue box, the settings for the trending data analysis can be adjusted. The ac-
quisition interval of trending can be selected. Depending on the settings for saving trending data and pattern
to harddisk, the estimated memory requirements are calculated and the time till depletion of disk space is
given.
7/25/2019 GISmon Sw Man e305
12/16
GISmonitor Partial Discharge Monitoring
10
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
III.4 Rack Settings
The On-line Partial Discharge Monitoring System consists of the Partial Discharge Measurement Control
Rackand a number of Partial Discharge Measurement Acquisition Racks. To configure these racks, go to
Edit/Rack Settings.
On the upper part of the dialog box, each via fiber optic network connected rack can be defined as either
indoor or outdoor rack. The settings for Indoor and Outdoor racks can be changed in the bottom left and
right of the dialog box. These settings influence the overview of monitored components presented in the
Statustab (see Chapter II.3).
7/25/2019 GISmon Sw Man e305
13/16
GISmonitor Partial Discharge Monitoring
11
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
III.5 Device Settings
The settings for the connection between the GISmonitorsoftware, the GISmonitorplug-in boards and the
UHF sensors is set up in the Device Settingsdialog box. This dialog box is opened by selecting the Ed-
it/Device Settingsmenu item.
On the upper part general settings can be modified. To define a new GISmonitor, the Newbutton must be
pressed. This creates a new entry in the tree on the left hand side. The settings for this GISmonitorcan bemade on the right hand side. First the name of this GISmonitormust be entered. This name is also the
name for the directory of this GISmonitor. Then the type of connection to this GISmonitormust be chosen.
There are two possibilities: USBand LAN. For this application the default setting is LAN. The default Port
for the GISmonitoris 10002. The IP-Addressmust be selected according to the setting of the corresponding
GISmonitor.
The data of all defined GISmonitorare stored in a predefined directory structure. The Data Directoryis the
parent directory of all data and can be selected by pressing the Data Directorybutton. Below this directory
there is one directory for each GISmonitor, labeled with its name. Inside these directories trending files are
stored, which contain the NQS and Qp trending. Each entry starts with the time stamp of this data record.
According to the Time Formatsetting, there are two different formats: Localand UTC. The default setting is
Localwhich uses the local time zone. UTCshould be selected if the data of two different time zones shall
be compared. Below these monitor directory there is one directory for each day. The label of these directo-
ries is according to the Date Formatsetting. Inside these directories the .dtc files for each day are located.
7/25/2019 GISmon Sw Man e305
14/16
GISmonitor Partial Discharge Monitoring
12
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
These files contain amongst others the display of the GISmonitor.
After defining the GISmonitor, the links to the sensors can be set up. By clicking the Select Sensorsbutton
the following dialog box appears:
On the left hand site there are the defined GISmonitorand the linked sensors and on the right hand sitethere is a list of sensors which are not yet linked to a GISmonitor. To link a sensor to a GISmonitorselect
the channel of the GISmonitor to which the sensor is connected, select the sensor on the right hand site
and press the left arrow. To unlink a sensor, select the sensor on the left hand site and press the right ar-
row.
7/25/2019 GISmon Sw Man e305
15/16
GISmonitor Partial Discharge Monitoring
13
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
III.6 Alarmsettings
III.6.1 Alarm Configuration
The alarm settings can be configured up by selecting the Alarm/Alarm Configurationmenu item. The open-
ing dialog box is shown in the picture below.
The NQS and QP levels that trigger a warning or alarm can be set individually. The conditions for mainte-
nance alarms include a disk space warning level and maximum temperatures for the rack and the enclosure
of the GISmonitorboards. A recommended configuration will be set up by Power Diagnostix during com-
missioning.
III.6.2 Alarm Output Configuration
In case of an alarm event, the GISmonitorsoftware can trigger the output relays of an external I/O card. The
card can be set up by selecting theAlarm/Output Configurationmenu item.
There are four different events which can trigger different relay outputs of the I/O card: The NQS/Qp alarm,
a warning, a FCU alarm and a maintenance warning. Each event must be enabled separately. The NQS/Qp
alarm can be enabled by selecting theActivate PD Alarm Outputcheckbox. After that the channel or the line
of the I/O card must be selected. To verify which contacts of the clipboard are used each event box shows
the numeration of the contacts to be connected.
A warning event can be defined for the I/O card. Therefore theActivate Warning Outputcheck box must be
enabled and the channel or output line of the I/O card must be selected.
To get an alarm event in case of an FCU failure, the Activate FCU Alarm Outputmust be enabled and the
channel or the line of the I/O card must be selected.
Activating the Maintenance Alarm check box will enable the selection of a channel or line of the I/O cardwhich will be triggered in case of limited disc space or rising temperatures inside an enclosure.
7/25/2019 GISmon Sw Man e305
16/16
GISmonitor Partial Discharge Monitoring
14
Power Diagnostix Systems GmbH Vaalser Strasse 250 D-52074 Aachen Phone +49 241 74927 Fax +49 241 79521 www.pdix.com
If one or more events trigger the relays of the I/O card, the applied signal must be reset. This can be done
either manually or automatically. If Manual is selected, the signal will be reset, if the corresponding reset
button is pressed. InAutomaticmode the signal will be reset after a predefined period of time, automatically.
To check your connection to the output card, you can use the test button to simulate an alarm on each
channel.
III.7 Load and Save a Project
All your settings can be saved to restore your data and even load to switch between different settings. The
project data file (*.gis) includes the settings of the monitors, the sensors and their relations. The properties
like your chosen schematic and plant name is also saved with this file. A project file can be changed by the
File menu in the menubar or by the buttons at the bottom of the main panel.
If you want to start a new project with complete new settings you can choose New Projectin the menubar.
Please be informed that this will delete all your unsaved settings! To prevent loss of data the software cre-
ates an autosave.gisfile every five minutes.
III.8 Password Request
To ensure that only authorized people can make changes in the settings of the software, a password can be
requested. To enable this option select the Options/Enable Password Request menu item. When you
choose this option you have to set an administrator password. The password can be changed by selecting
the Edit/Administrator Passwordmenu item. This opens the following dialog box:
First the current administrator password must be entered. Then the new password can be typed in. To verify
the new password, it must be repeated. By clicking the OKbutton, the new administrator password will be
applied. The following functions require an administrator login: Editing the Properties, Changing to Edit
Mode, Editing the Monitor Settings, load, save and creating a new Project. If one of these functions are
chosen, the administrator password must be typed into the popup window. In order to avoid typing in the
password every time, there is the possibility to login as an administrator, directly. The File/Administrator
Loginmenu item allows to permanently login as an administrator, so you will not be asked for the passwordagain.