+ All Categories
Home > Documents > Governor and AGC Control

Governor and AGC Control

Date post: 17-Jan-2017
Category:
Upload: duongdung
View: 223 times
Download: 0 times
Share this document with a friend
26
Governor and AGC Control of System Frequency TRE Technical Workshop March 31, 2009 Bob Green Garland Power and Light
Transcript
Page 1: Governor and AGC Control

Governor and AGC Controlof System Frequency

TRE Technical WorkshopMarch 31, 2009

Bob GreenGarland Power and Light

Page 2: Governor and AGC Control

Two generators equipped withgovernors having output feedback

Page 3: Governor and AGC Control

Schematic of a governor with output feedback

Page 4: Governor and AGC Control

Response of governor with output feedback

Page 5: Governor and AGC Control

Steady-state speed characteristic (droop) curve

Page 6: Governor and AGC Control

R(per unit), the slope of the “droop” curve, is defined as f(p.u.)/ P(p.u.), where f(p.u.)= f(HZ) / 60.0,and P(p.u.)= P(MW) / Unit Capacity.For a 600 MW unit that has a governor response of 20 MW for a frequency excursion that settles out at 59.9 HZ, R=f(p.u.) / P(p.u.) = (0.1/60)/(20/600)=0.05 or 5% droop.

Once the droop is known, the MW response to frequency deviation can be determined by (P/f)=(1/R), or P=(1/R) X f.For the 600 MW unit with 5% droop, (P/600)=(1/0.05) X (f/60), or P=200MW/HZ

Calculation of steady-state speed characteristic

Page 7: Governor and AGC Control

So, how do governors with the steady-state speed characteristic interact when there are multiple generators in a power system?

What determines the steady state system frequency after a load is

added to the system?

Page 8: Governor and AGC Control

Multiple Generator Governor ResponseConsider an isolated power system with three generators on-line and operating at 60HZ. The load is 360 MW and the generator outputs for units #1, #2 and #3 are 80MW, 120MW and 160MW, respectively.A load of 21MW (P) is added. What frequency does the system settle at? How much does each unit pick-up (MW)?Since R(p.u.)=( f(HZ)/60)/( P(MW)/Capacity), then (P/f)=(1/R) X Capacity/60).

UNIT CAPACITY R (DROOP) P/f#1 300MW 0.100 (10%) 50MW/HZ#2 450MW 0.075 (7.5%) 100MW/HZ#3 600MW 0.050 (5%) 200MW/HZSolution:Unit #1: P1=50 X fUnit #2: P2=100 X fUnit #3: P3=200 X fPi=350f=21MW,and f=21/350=0.06HZFrequency=60-0.06=59.94HZ

P1=50 X 0.06=3MWP2=100 X 0.06=6MWP3=200 X 0.06=12MW check: Pi=21MW

Page 9: Governor and AGC Control

Three generators serving 360MW

Page 10: Governor and AGC Control

Three generators serving 367MW

Page 11: Governor and AGC Control

Three generators serving 374MW

Page 12: Governor and AGC Control

Three generators serving 381MW

Page 13: Governor and AGC Control

The system frequency reaches steady-state at a value that causes the sum of the on-line generator output MW to be

equal to the system load MW.With this type of governor, when the

system load increases, the system frequency decreases and visa versa.

How do we control frequency to 60HZ, no matter what the load is?

Page 14: Governor and AGC Control

Power system equipped for supplemental control

Page 15: Governor and AGC Control

Addition of a speed changer

Page 16: Governor and AGC Control

Steady-state speed characteristic with speed changer

Page 17: Governor and AGC Control

Power output as a function of frequency

Page 18: Governor and AGC Control

How does the addition of the speed changer to the governor

facilitate the control of frequency?

Hint: The system frequency reaches steady-state at a value

that causes the sum of the on-line generator output MW to be equal

to the system load MW.

Page 19: Governor and AGC Control

From a central site, you increase or decrease the 60HZ set-points until the sum of the 60HZ set-points is

equal to the system load. Then the frequency will stabilize at 60HZ.

This form of supplemental control is called Automatic Generation Control

(AGC) and more specifically, Load Frequency Control (LFC).

Page 20: Governor and AGC Control

Load of 367MW and 60HZ SPs increased by 7 MW

Page 21: Governor and AGC Control

Load as a function of frequency (load damping)

Page 22: Governor and AGC Control

Governor and load characteristic curve intersection

Page 23: Governor and AGC Control
Page 24: Governor and AGC Control

Illustration of typical governor dead band

Page 25: Governor and AGC Control

Generation oscillations at the dead band frequency

Page 26: Governor and AGC Control

Primary Control Secondary or Supplementary ControlCommon Name Governor Control/Response AGC Control/ResponseFunction-Generic Holds the system together as load changes

occur and also as un-commanded generation excursions occur

Shifts generation between units to achieve security and economic objectives plus restores frequency to the rated value.

Function-Technical Provides the correct amount of mechanical input to turbines to match the electrical output of the corresponding generators

Changes the 60HZ governor set-points of the units to achieve scheduled values established by the market.

Control Input Frequency/rotational speed of the turbine In ERCOT, the SCE for the portfolio of unitsControl Time Constant Fast - Seconds Slower - Tens of seconds and minutesStyle of Control Local within the Units/PGCs—A QSE has no

direct control over governor response.Centralized from ERCOT to Units via QSEs

Performance Optimization

Having more governors on-line (with a given droop characteristic) will minimize the magnitude of frequency deviations

Having more units being controlled by AGC will minimize the duration of frequency deviations

Key Parameters Steady state speed characteristic (droop), governor dead-band, first stage boiler pressure (steam units) and head (hydro units)

Base power schedule plus deployments of balancing energy, regulation energy, responsive and non-spinning reserve. AGC dead-band, gains and frequency bias term.

Market Characteristics If there ever is a governor response market, there will probably be bids, awards and settlement, but the market will never deploy the governor response.

Bids, awards, deployments and settlement through the Ancillary Service Market. Performance monitoring of individual Services is approximate and complicated.

Disturbance Timeline Initial governor response (to point B) is over completely by the time units start receiving secondary control signals in response to the disturbance.

There needs to be recognition of governor response and coordination between RRS and RegUp deployments to insure smooth , rapid and sustained frequency recovery.


Recommended