GeneralSpecifications
GP10/GP20Paperless Recorder(Portable type)
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
GS 04L52B01-01EN
GS 04L52B01-01EN©Copyright Octorber 2012
16th Edition June. 14, 2017
OVERVIEWThe GP10/GP20 are portable type paperless recorders that display real-time measured data on a touch screen and save data on an external storage medium (SD card).For the input/output module specification, please see GX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YA Input/Output Module and GX90UT PID Control Module General Specification (GS 04L53B01-01EN, GS 04L53B01-31EN.)● Thenumberofanaloginputisamaximumof
100channelsinGP10withexpandableI/O*1, GM sub unit*1,amaximumof100channelsinGP20standardtype(GP20-1)withexpandableI/O,andamaximumof450channels*2inGP20largememorytype(GP20-2)withexpandableI/O,GMsubunit.*1Aunitforexpandingthenumberofchannels.*2Max.numberofinput/outputchannelsis500
channels.● TheGP10/GP20havethelargeinternalmemory
(GP10/GP20-1: 500MB, GP20-2: 1.2 GB), and prolongedrecordandpreservationarepossible.
● Astheinputsignal,aDCvoltage,thermocouple,resistancetemperaturedetector,DI(DCVinput(TTL),contactsignal),ormA(DCcurrent)canbeset to each channel.
● Analogoutputiscapableofretransmissionoutputofvarioustypesofchannelsandalsomanualoutput.
Itprovidescurrentoutputwithchannelsthatareisolated.(Analogoutputmodule)
● Inputandoutputhavemodulestructureanditcanextendthemeasily.(GP10:max.3*,GP20:max.10*)* IncaseofusingexpandableI/O,GMsubunit,
GP10canextendtwounits,GP20canextend9units.
● Amoduletypeisseventypes,ananaloginput,aanalog output, a digital input, a digital output, a digitalinput/output,apulseinput,andaPIDcontrol.
● Upto6unitsofexpandableI/OunitsandGMsubunits can be connected to the GP10/GP20. Each expandableI/OandGMsubunitcanincorporateamaximumofsixmodules.WithexpandableI/O,GMsubunitconnected,GP10andthelargememorytypeGP20canusemultiplechannels.Furthermore,theI/OportscanbeinstalledinseparatelocationsfromwhereGP10/GP20islocated,helpingyoureducewiringrequirementsandbuildadecentralizedconfiguration.
● Theintuitiveoperationbyflick,pinchin,andpinchout are possible.
● Thepasttrendunderrecordingcanbeseamlesslydisplayed on a trend screen.
● Moreover,themeasurementdataofthetimespecifiedonthecalendarscreencanbesearchedand displayed.
● Variousfunctions,suchasafreehandmessage,aPDF/Exceloutputofareportfile,adirectoutputtoanetworkprinter,ascalemovementofatrenddisplay, and a buzzer, are equipped.
● ItcanbehookeduptonetworkviaEthernet,whichenablestoinformbyEmailandtomonitoronWebsiteaswellastotransferfilesbyusingFTP.Also,itcancommunicatewithModbus/RTUorModbus/TCP.
● Inhigh-speedmeasurement,measurementattheshortestintervalof1msispossiblebyusingahighspeedanaloginputmodule(high-speedAI).
● Indualintervalmeasurement,measurementcanbeperformedbysettingtwodifferentscanintervals.
● ThePIDcontrolfunctionenablesPIDcontrolonupto20loops(6loopsfortheGP10/GP20-1)byinstallingaPIDcontrolmodule.
● Theprogramcontrolfunctionenablesprogramcontrolofupto99patternsbyusingaPIDcontrolmoduleandprogramcontrolfunction(/PGoption).Upto32timeeventsand32PVeventscanbesetforeachsegment.
* ForPIDcontrolmodule,PIDcontrolFunction,andprogramcontrolfunction(/PG),seetheGX90UTPIDControlModuleGeneralSpecifications(GS04L53B01-31EN)
*ThecontentsofthisgeneralspecificationscorrespondtotheGP10/GP20withreleasenumber4andstylenumber2.
Releasenumber:firmwareIDnumber Stylenumber:hardwareIDnumber
GP10 GP20
Release R4
2
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
● Varioustypesofcomputationarepossiblewiththemathfunction(/MToption).Thereportfunctionenablescreationofhourly,daily,andmonthlyreportsandothertypesofdata.Logicmathoutputsresultsofcomputationas0sor1stointernalswitchesandDOchannels.
● AsetupofGPcanbeperformedon-linefromthewebbrowseronPC.Asetupbyoff-lineisalsopossible.
● UniversalViewersoftwareallowsaPCtodisplaywaveformsonitsscreenandtoprintoutwaveforms.
● Themeasuringaccuraciesnotedinthegeneralspecificationshaveamarginoferrorthattakesintoaccounttheproduct'scomponentsandtheequipmentusedforadjustmentandtesting.However,theactualvaluescalculatedfromtheaccuracytestingdatauponshipmentoftheinstrumentfromthefactoryareasfollows.Inputtype Measuring accuracy*1(typicalvalue*2)
DCV 20mV ±(0.01%ofrdg+5μV)
60mV ±(0.01%ofrdg+5μV)
6 V (1-5 V) ±(0.01%ofrdg+2mV)
TC*3 R ± 1.1 °C
K ±(0.01%ofrdg+0.2°C)for0.0to 1370.0 °C;±(0.15%ofrdg+0.2°C)for-200.0 to 0.0 °C
K (-200 to 500 °C)
±0.2°Cfor0.0to500.0°C;±(0.15%ofrdg+0.2°C)for-200.0 to 0.0 °C)
J ±0.2°Cfor0.0to1100.0°C;±(0.10%ofrdg+0.2°C)for-200.0 to 0.0 °C
T ±0.2°Cfor0.0to400.0°C;±(0.10%ofrdg+0.2°C)for-200.0 to 0.0 °C
N ±(0.01%ofrdg+0.2°C)for0.0to 1300.0 °C;±(0.22%ofrdg+0.2°C)for-200.0 to 0.0 °C
RTD Pt100 ±(0.02%ofrdg+0.2°C )
Pt100(high resolution)
±(0.02%ofrdg+0.16°C)
*1 AppliestoGX90XA-10-U2,A/Dintegrationtime16.67msormore,Generaloperatingconditions:23±2ºC,55±10%RH,supplyvoltage90–132,180–264VAC,supplyfrequencywithin50/60Hz±1%,warm-upof30minutesormore,novibrationsorotherhindrancestoperformance.
*2 Forthemeasuringaccuracy(guaranteed),seethemodule'sgeneralspecifications(GS04L53B01-01EN).
*3 Thesevaluesdonotincludethereferencejunctioncompensationaccuracy.
rdg:readingvalue
MAIN UNIT SPECIFICATIONS■ FUNCTIONALSPECIFICATION
Input/OutputSpecifications PleaseseeGX90XA/GX90XD/GX90YD/GX90WD/
GX90XP/GX90YAI/OModuleandGX90UTPIDControlModuleGeneralSpecifications.Model Name General
SpecificationNo.GX90XA Analoginputmodule GS 04L53B01-01EN
GX90DX Digitalinputmodule
GX90YD Digitaloutputmodule
GX90WD Digitalinput/outputmodule
GX90XP Pulseinputmodule
GX90YA Analogoutputmodule
GX90UT PIDcontrolmodule GS 04L53B01-31EN
MeasuringFunctions• ThenumberofinstallablemodulesandI/O
channels(totalforGP,expandableI/OandGMsubunit)
GP10/GP20-1Item GP10/GP20-1
Numberofmodule Max.10
Numberofinput/outputmodule Max.100
GP20-2Item GP20-2
Numberofmodule Max.45
Numberofinput/outputmodule Max.500(ormax.450forAIonly)
Moduleinstallationlimitations:See“Limitations”and“NotesonModuleInstallation.”• ExpandableI/O,GMsubunitconnection Numberofconnectableunits:Upto6unitstotal
* ConnectionisnotpossibleifthemeasurementmodeissettoHighspeed.
FordetailsonexpandableI/OunitsandGMsubunits,seetherespectiveGeneralSpecifications(GS 04L53B00-01EN, GS 04L55B01-01EN).
3
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
Scaninterval:1,2,5,10,20,50,100,200,500ms,1,2,5sNote) Someintervalswillbeunavailabledependingon
thesystemconfigurationandmodules. Fordetails,seetheI/OModuleGeneral
Specifications(GS04L53B01-01EN)and“Limitations”inthismanual.
Measurmentmode:● Normal Amodeinwhichtheshortestmeasurement
intervalis100ms Numberofmeasurmentgroups:1 Filetype:Displaydata,eventdata Dataformat:Binaryortext Scaninterval:100ms(fastest) Compatiblemodules:Allmodules● Highspeed Amodeinwhichhigh-speedmeasurementis
possibleattheshortestmeasurementintervalof1ms
Numberofmeasurmentgroups:1 Filetype:Eventdataonly Dataformat:Binaryonly Scaninterval:1ms(fastest) Compatiblemodules:High-speedAI(GX90XA-
04-H0),DI(GX90XD),DIO(GX90WD) However,onemodule,eitherDIorDIO,can
beinstalled.DIinputisfixedtoremotemode.Measurementandrecordingarenotpossible.
● Dualinterval Amodeinwhichmeasurementispossible
bysettingdifferentscanintervalsonthetwomeasurementgroups.
Numberofmeasurementgroups:2 Filetype:Eventdataonly Dataformat:Binaryonly Scaninterval:
Model measurementgroup1
measurementgroup2
GP10/GP20-1 5ms(fastest) 100ms(fastest)
GP20-2 1ms(fastest) 100ms(fastest)
Compatiblemodules:AllmodulesexceptPIDcontrolmodule* Dependingonthemeasurementmode,thereisa
limittothenumberofmeasurementchannelsandrecordingchannelsatscanintervalsshorterthan100ms.See“Limitations.”
DisplayFunctionsDisplaygroups: Numberofgroups;GP10:30,GP20-1:50,
GP20-2: 60 Numberofchannelsthatcanbeassignedto
each group; GP10: 10, GP20: 20Displaycolor(Trend/Bargraph/Digitaldisplay): Channel:Selectfrom24colors Adesireddisplaycolorcanbeselectedfreely
usingitsRGBvalue. Background:Selectfromwhiteorblack
Displaytype:● Trenddisplay(T-Y) Displaymethod:
Direction:Horizontal,verticalTrendinterval(Recordinginterval):50ms/div
(1ms),100ms/div(2ms),250ms/div(5ms),500ms/div(10ms),1s/div(20ms),2.5s/div(50ms),5s/div(100ms),10s/div(200ms),15s/div(500ms),30s/div(1s),1min/div(2s),2min/div(4s),5min/div(10s),10min/div(20s),15min/div(30s),20min/div(40s),30min/div(1min),1h/div(2min),2h/div(4min),4h/div(8min),10h/div(20min)
• Trendintervalshorterthan30s/div(1s)cannotbesetonelectromagneticrelaytypeanaloginputmodules.
• Trendintervalshorterthan15s/div(500ms)cannotbesetonlowwithstandvoltagerelaytypeanaloginputmodules.
• Scanintervalshorterthan5s/div(100ms)cannotbespecifiedwhenthemeasurementmodeissettoHighspeedorDualinterval.
• OntheGP10/GP20-1,scanintervalshorterthan250ms/divcannotbespecifiedindualintervalmode.
Trendlinewidth:Thick,normal,thin Scale;GP10:Max.6,GP20:Max.10
Currentvaluebargraph,colorscaleband,andalarmpointmarkscanbedisplayedonthe scale.
Abitmapimagescalecanbeattached.Movingscale;Scalecanbemovedonany
waveform. Others; Grid (Auto, 4 to 12), Trip line, Message,
Zonedisplay,Partialexpandeddisplay● Historicaltrenddisplay(T-Ydisplay) Redisplaysthedisplaydataoreventdatainthe
internalmemoryorexternalstoragemedium Timeaxisoperation:Thetimeaxiscanbe
reducedorexpanded. Datasearch:Waveformsfromtheinternal
memorycanbedisplayedthroughthespecificationofadateandtime,calendar,eachsummary
All historical trends can be displayed in one screen.
● Bargraphdisplay Direction:Verticalorhorizontal Scale:Displayascaleforeachchannel
Colorscaleband,andalarmpointmarkscanbe displayed on the scale.
● Digitaldisplay Displaysmeasuredvaluesnumerically ADIinputstatecanbedisplayedasanarbitrary
characterstring(0=Off/1=On,etc.) Updaterate:0.5s
4
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
● Overviewdisplay Displayformat:Allchannels,eachgroups Displaysthemeasuredvaluesofallchannels
andthealarmstatuses Displayingroupsonlywhenthemaximum
numberofchannelsthatcanbedisplayed(30ontheGP10,100ontheGP20)isexceeded.
● Alarmsummarydisplay Displaysalogofupto1000alarms Specifyanalarmwiththecursorandjumpto
the corresponding section on the historical trend display.
● Messagesummarydisplay Timeandcontentofupto500messages
(simultaneouswriting:450,additionalwriting:50) Specifyamessagewiththecursorandjumpto
the corresponding section on the historical trend display.
● Memorysummarydisplay Displaystheinformation(upto500(GP10/GP20-
1)orupto1000(GP20-2)ofthedatainthememory
Specifyafilewiththecursorandjumptothecorresponding section on the historical trend display.
● Reportdisplay Displaysthereportdataresidingintheinternal
memory Formoredetails,see"MATHEMATICAL
FUNCTIONSWITHREPORTFUNCTION(/MT)."● Logdisplay Displaystheeventlog,errorlog,communication
log,FTPlog,Weblog,e-maillog,SNTPlog,DHCPlog,ModbuslogandSLMPlog.
● Multi-paneldisplay(OnlyforGP20) Dividesthescreenintotwotosixsectionsand
displayssomedifferentdisplayformats.● Internalswitch/relaystatedisplay DisplaystheinternalswitchandON/OFFstateof
DO OperatestheinternalswitchandON/OFFstate● Controlscreendisplay(whenaPIDcontrol
moduleisinstalled) Controlgroup,controloverview,tuning,control
summary,controlalarmsummary,programoperation,*programselection*
* Only when the /PG option is installed● Otherdisplays Networkinformationdisplay Systeminformationdisplay Systemconfigurationdisplay
Autoscroll: Thedisplayedgroupscanbeautomatically
switchedataspecifiedinterval. The display switches in ascending group order.
Namesofchannels:
Channel number; Analog input: 01 to 10 Digital input: 01 to 16 Digital output: 01 to 06 Digital input/output; DI: 01 to 08, DO: 09 to 14 Pulse input: 01 to 10 Analog output: 01 to 04 PID control Input, output: 01 to 26
X X X X
Slot number; GP10: 0 to 2, GP20: 0 to 9 Expandable I/O/GM sub unit: 0 to 5Unit number; Main unit: 0, Expandable I/O/GM sub unit: 1 to 6
Tags:• TagandTagnumberscanbedisplayed.• Tagnumber;Numberofcharacters:Upto16 Displayablecharacters:Alphanumericcharacters Tagnumberscanbeenabledordisabled.• Tag;Numberofcharacters:Upto32 Displayablecharacters:Alphanumericcharacters
Message:• Writemessagestothetrenddisplay.• Numberofmessages:100• Numberofcharacters:Upto32• Writemethod:Writeapresetmessageorwrite
anarbitrarymessageonthespot.• Writedestination:Selectonlythedisplayed
group or all groups.• Automessage:WriteamessagewhentheGP
recoversfromapowerfailurewhilememorysamplingisinprogress.
Writeamessagewhenthetrendintervalisswitchedduringmemorysampling.
Addmessage:• Writemessagestothepastdatapositions.• Message:Thesameasthe“Message”item
above Numberofwritablemessagesperfile:50
messages(including10freehandmessages)Freehandmessage:• Canbewrittenbydedicatedpen. Numberofwritablemessagesperfile:50
messages(including10Addmessages)
DataSavingFunctionsInternalmemory:• Temporarilysavesvarioustypesofdata.• Medium:Flashmemory• Filestoragecapacity; GP10, GP20-1: 500 MB GP20-2: 1.2 GB
Externalstoragemedium:• MediumSDcard(SD/SDHC)(upto32GB)• Format:FAT32orFAT16
Datatype:• Displaydata,Eventdata,Alarmsummarydata,
Manualsampleddata,Screenimagedata,Setupdata, and Report data
5
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
Displaydata:• Target:Measurement(input/outputmodule)/
math/communicationchannels,alarmsummary,messagesummary
Description:Maximumorminimumvalueperrecordlinginterval
• Recordingintervals:Determinedbythetrendinterval,recordingdatatype(displaydata/displaydata+eventdata,GP20-2)
• Numberofchannelsthatcanberecorded ForGP20-1
Trendinterval(div) Numberofchannels5 s 100
10 s 200
15 s or longer 500
ForGP20-2Trendinterval(div) Numberofchannels
Displaydata
Displaydata+Eventdata
5 s 200 100
10 s 500 200
15 s 1000 500
30 s or longer 1000 1000
Notethatthemaximumnumberofchannelsisfixedat100intheGP10.
• Datasize; Analog input data: 12 bytes/ch. Analog output data: 12 bytes/ch. DigitalI/Odata:4bytes/ch. Pulse input data: 12 bytes/ch.
Math channel data: 12 bytes/ch. Communicationchanneldata:12bytes/ch.
• Filesize:Upto18MB• NumberoffilesforGP10,GP20-1:Upto500
(includingeventdata),forGP20-2;Upto1000(includingeventdata) Operationintheinternalmemory:FIFO(FirstInFirstOut)
• Dataformat:Binaryortext• Recording:Recordsdataatalltimes.• Displaydatafilesampletime
Measurementchannel=30.MathChannel=0InternalMemory 500 MB
Trendinterval(minute/div) 30minutes
Recordinginterval(s) 60 s
Totalsampletime Approx.2.5years
Eventdata:• Target:Measurement(input/outputmodule)/
math/communicationchannels,alarmsummary,messagesummary,operationlog
Description:Instantaneousvalueperrecordinginterval
• Recordingintervals:Determinedbythescaninterval,recordingdatatype(displaydata/displaydata+eventdata)
• Numberofchannelsthatcanberecorded: Measurmentmode:Normal
ForGP20-1Recordinginterval Numberofchannels*1
100ms 100
200ms 200
500msorlonger 500
ForGP20-2Recordinginterval Numberofchannels*1
Displaydata
Displaydata+Eventdata
100ms 500 100
200ms 500 200
500ms 1000 500
1 s or longer 1000 1000
Notethatthemaximumnumberofchannelsis100 in the GP10.
Measurmentmode:HighspeedRecordinginterval Numberofchannels*1
GP10 GP20-1 GP20-21ms 2 2 10
2ms 4 4 20
5ms 10 10 50
10ms 20 20 100
20ms 40 40 150
50ms 100 100 150
100ms 100 100 200
200ms 100 200 500
500ms 100 500 1000
1 s or longer 100 500 1000
Measurmentmode:DualintervalRecordinginterval Numberofchannels *1 *2
GP10 GP20-1 GP20-21ms — — 5
2ms — — 10
5ms 5 5 25
10ms 10 10 40
20ms 20 20 50
50ms 50 50 50
100ms 100 100 100
200ms 100 100 200
500ms 100 250 600
1 s or longer 100 250 600
*1 TotalnumberincludingI/Ochannels,mathchannels,andcommunicationchannels
*2 Numberofchannelsthatcanberecordedisthesameforscangroup1andscangroup2.
6
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
• Datasize; Analog input data: 6 bytes/ch. Analog output data: 6 bytes/ch. DigitalI/Odata:2bytes/ch. Pulse input data: 6 bytes/ch.
Math channel data: 6 bytes/ch. Communicationchanneldata:6bytes/ch.
• Filesize:Upto18MB• NumberoffilesforGP10,GP20-1:Upto500
(includingdisplaydata),forGP20-2;Upto1000(including display data)
• Operationintheinternalmemory:FIFO(FirstInFirstOut)
• Dataformat:Binaryortext• Mode;Free:Recordsdataatalltimes.
Trigger: Starts recording data when a certaineventoccursandrecordsforthespecifiedinterval.
Repetitiontrigger:RepeatTriggermode• Eventdatafilesampletime Measurementchannel=30.MathChannel=0
InternalMemory 500 MB
Recording period (s) 1 s
Totalsampletime Approx.1month
AlarmFunctions• Numberofalarms:Uptofouralarms(level)for
eachmeasurementchannels• Alarmtype:Highlimit,lowlimit,differencehigh
limit,differencelowlimit,highlimitonrate-of-changealarm,lowlimitonrate-of-changealarm,delayhighlimit,anddelaylowlimit
• Alarmdelaytime:1sto24hours(foreachchannel)
• Rate-of-changecalculationintervalofrate-of-changealarms:1to32timesthescaninterval(commontoallchannels)
• Hysteresis:0.0to5.0%ofthespan(foreachalarm(level))
• Alarmoutput:Outputtotheinternalswitch,relay Internalswitch/relayoperation:AND/OR
operation selectable• Display:Displaysthestatusontherespective
operationscreenandanalarmicononthestatusdisplaysectionwhenanalarmoccurs.
Displayoperation:Holdornotholdthedisplayuntilthealarmacknowledgeoperation
• Alarmhidefunction(alarmnologgingfunction) Usedforrelayandinternalswitchoutputand
eventsofeventactionandnotrecordedinalarmdisplayoralarmsummary(eachchannel)
• Alarminformation:Displaysalogofalarmoccurrencesonthealarmsummary
• Reflash:Thedurationforwhichthereflashrelaysaredeactivatedcanbesetto500ms,1s,or2s.
• IndividualalarmACKfunction: Alarmdisplayandrelayoutputcanbecancelled
onindividualalarms
EventActionFunctions• Eventaction:Executeaspecifiedoperation
whenagiveneventoccurs.• Numberofsettings:50 Events:Remotecontrolinput,etc. Numberoftimers:12 Numberofmatchtimetimers:12 Action:Specifymemorystart/stop,alarmACK,
etc.
ControlEventActionFunctionsSeeGX90UTPIDControlModuleGeneral
Specifications(GS04L53B01-31EN).
SecurityFunctions• Operationlockfunction:Limitationstotouch
operation,accesstotheexternalstoragemedium,andvariousoperations
• Loginfunction:Onlyregistereduserscanoperate the GP.
Itcanbesettoeachoftouchoperationandcommunicationaccess.
SystemadministratorsandUsers:50(totally) NumberofAuthorityofuser:10level
ManualSampledData• Item:Instantaneousvalueatanarbitrarytime• Target:Measurement(input/outputmodule)/
math/communicationchannels• Numberofrecordingchannels; GP10,GP20-1:Max.50 GP20-2:Max.100• Maximumnumberofdatavaluesthattheinternal
memorycanstore:400• Dataformat:Text
ReportData• Item:Reportateachscheduledtimeofreport• Target:Measurement(input/outputmodule)/
math/communicationchannels• Maximumnumberofreportsthattheinternal
memorycanstore:800• Dataformat:Text
SnapshotData• Item:Displayedscreenimagedata• Dataformat:PNG• Outputdestination:Externalmediumor
communicationoutput
SetupData• Item:GPsetupdata• Dataformat:text• Output/readdestination(forsaving/loading):
Externalmedium
ClockFunctions• Clock:Withacalendarfunction• Accuracy:±5ppm(0to50°C),excludingadelay
(of1second,maximum)causedeachtimethepower is turned on.
• Timedifferencebetweenunits:±2msmax.(timedifferencebetweenaGPandI/OBaseUnit(ExpandableI/O))
7
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
• Timesetting:Usingtouchoperation,communicationcommand,eventactionfunction,orSNTPclientfunction
• Timeadjustmentmethod: Limitinwhichthetimeisgraduallyadjusted:
Selectfromtheavailablesettingsbetween5sand 15 s.
Whethertochangeanout-of-limitoperationimmediatelyorreportitasanerrorcanbeselected.
Whilememorysampling:Correctsthetimeby1msforeachsecond.
Whilememoryisstopped:Immediatelychangethetime.
• DST:Thedate/timeforswitchingbetweenstandardtimeandDSTcanbespecified.
• Timezone:SetsthetimedifferencefromGMT.• Dateformat:Select"YYYY/MM/DD","MM/DD/
YYYY","DD/MM/YYYY"or"DD.MM.YYYY". MMexpressioncanbeselectedfromthenumericcharacterorellipsis.Ex.January:01orJan Thedelimitercanbeselectedfrom"/",".","-".
EthernetCommunicationFunctions• Electricalspecifications:ConformstoIEEE802.3• Connection:Ethernet(10BASE-T/100BASE-TX)• Max.segmentlength:100m• Max.connectingconfiguration:CascadeMax.4
level(10BASE-T),Max.2level(100BASE-TX)• Connector:RJ-45• Protocols:TCP,UDP,IP,ICMP,ARP,DHCP,
HTTP,FTP,SMTP,SNTP,Modbus,anddedicated protocols
• E-mailclient:Automaticallysende-mailatspecifiedtimes.
E-mailissentbyeventsasbelow.- Alarmoccurring/alarmcanceling(Max.50ch)- Recoverfrompowerfailure- Report data generating- Storagemediumerror,FTPclientfunction
error- Specifiedtimeperiod
POPbeforeSMTPandSMTPauthentication(PLAINandCRAM-MD5)isavailable.
• FTPclient:AutomaticallytransferdatafilestotheFTPserver.
Applicablefiles:Displaydata,eventdata,screenimagedata,reportdata,etc.
• FTPServer:Transferfiles,deletefiles,manipulatedirectories,andoutputfilelistsoftheGP.
Numberofthesimultaneousconnection:Max.4• Webserver:Webapplication,GPreal-time
monitoringandsettingchanges/operationscanbeperformedwiththeWebbrowser.
Numberofthesimultaneousconnection:Max.4• SNTPclient:InquiresthetimetotheSNTP
serverandsetstheGP.• SNTPserver:OutputstheGPtime. Timeresolution:5ms• DHCPclient:Automaticallyobtainthenetwork
addresssettingsfromtheDHCPserver.
• Modbusclient*:Readsdatafromanotherdeviceand writes to the registers.
Numberofconnectablesever; GP10,GP20-1:Max.16 GP20-2:Max.32 *: Required /MC option• Modbusserver:Loadsmeasurementandmath
channel data Loadsandwritescommunicationchanneldata Somecontrolcommandssuchasmemorystart Modbusclient*registeraccesslimitations
*: Required /MC option Numberofthesimultaneousconnection:Max.4• Setting/Measurementserver:Operate,set,and
outputdataoftheGPusingadedicatedprotocol. Numberofthesimultaneousconnection:Max.4• DARWINcompatiblecommunicationserver:
SupportssomeDARWINcommands CommunicationwithGPispossibleusing
DARWINcommunicationcommands. • Output-relatedcommands:Output
measurement(IO)channeldata,Outputcalculation channel data, Output relay status, Outputthepositionofthedecimalpointforthemeasurement(IO)channel,Outputthepositionofthedecimalpointforthecalculationchannel,Outputtheinformationonsystemconfiguration
• Setup-relatedcommands:Range,Scaleunit,Alarm,Time,Movingaverage,zone
• Operation-relatedcommands:Resetalarm,Resettimer,StartMATHcalculation,Rebuildsystem,Initialize,Inputcommunication,OutputcommunicationDO,Writemessage
BatchFunction• Function:Datamanagementusingbatchnames.
Entertextfieldsandbatchcommentsinthedatafile.• Batchname:Addedtothefilenameofthe
displaydataandeventdata. Structure:Batchnumber(upto32characters)+
lotnumber(upto8digits) Use/notuseselectableforlotnumber,on/off
selectableforautoincrementfunction.• Textfield:Addstexttothedisplaydataandevent
data. Thereare24availabletextfields. Upto20titlecharactersand30othercharacters
canbeenteredperfield.• Batchcomment:Addstexttothedisplaydata
andeventdata. 3comments(max.50characters)areavailable.
PrinterOutputFunction• SnapshotDatacanbeprintedoutwithany
LAN-connected printer supporting the HP PCL5c language and the port 9100.
8
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
SSLCommunicationFunctions Communicationthatsendsandreceivesinformation
encrypted by the SSL (Secure Socket Layer) protocol is possible.• Serverfunction: Supportedservers:HTTPserverandFTPserver
(Portnumber:443whenencryptionisused) Privatekey:CreatedinGPandsavedinthe
internalmemory Servercertificate:Servercertificatescreatedby
userscanbesavedintheinternalmemory. Self-signedcertificatescanbecreatedinGP.• Clientfunction: Supportedclients:FTPclient(onlyExplicitmode
is supported) and SMTP client (only STARTTLS is supported)
Trustedcertificate:Trustedcertificates(atotalofupto80KB)canbesavedintheinternalmemory.
ElectronicSignatureFunction Electronicsignaturescanbeaddedtoreportfiles
createdinPDFformatusingthePDFformcreationfunction.Anelectronicsignatureisprovidedeachtimeareportfileiscreated.• Certificateforelectronicsignature:Certificates
forelectronicsignaturescreatedbyuserscanbesavedintheinternalmemory.
LoopcontrolFunction(WithPIDcontrolmodule)SeeGX90UTPIDControlModuleGeneral
Specifications(GS04L53B01-31EN).
OtherFunctions• Buzzer:GPmakesabuzzersoundattouch
screenoperation,orwhenalarmoccurs.• Backlightsaverfunction:Dimorturnoffthe
LCDbacklightifthereisnokeyoperationforaspecifiedtime.
• Favoritedisplay:RegisterfrequentlyuseddisplaystotheFavoriteandshowthemthroughsimpleoperation.
• ThemainalarmisindicatedusingtheMENUkeyLED.
Noalarm:Blue(sameconditionaspower-on) Alarmcondition:Red.• Userfunctionfeature:Abuttontowhichtheuser
canassignadesiredfunctionisprovided.Itcanbeassignedtoaneventtriggeredbytheeventactionfunction.
• Firmwareupdatefunction:TheWebapplication,theIOmodule,ortheexpansionmodulefirmwarecanbeupdatedbyoperatingGP.
HARDWARE SPECIFICATIONS (MAINUNIT)
DisplayDisplayunit*:GP10:5.7-inchTFTcolorLCD(640×480dots)GP20:12.1-inchTFTcolorLCD(800×600dots)* Asmallnumberofmissingorsteady-onLCD
pixelsandminorvariationsinbrightnessuniformityisanormaldisplaycharacteristicandnotamalfunction.
Touchscreen:4wireresistivetouchscreen
Construction• Material;
Case: Metal plate Bezelanddisplaycover:Polycarbonate
• Color; Case:Smokeblue(Munsell4.1PB6.0/4.5equivalent) Bezel: Light grey (Munsell 5.2PB8.2/1.0 equivalent)
• Externaldimensions: Wheninstallingmodules GP10:144(W)×168(H)×248(D)mm
GP20:288(W)×318(H)×248(D)mm Whenuninstallingmodules
GP10:144(W)×168(H)×197(D)mm GP20:288(W)×318(H)×197(D)mm (D:depthfromthepanelmountingplane)• Weight:
GP10:Approx.1.9kg,GP20:Approx.5.4kg (excludingmodules)
PowerSupply[Powersupplysuffixcode:1]• Ratedsupplyvoltage:100to240VAC• Allowablepowersupplyvoltagerange:90to132,
180to264VAC• Ratedpowersupplyfrequency:50/60Hz• Powerconsumption:Supplyvoltage
LCDbacklightoff
Normaloperation
Maximum
100VAC GP10:16VAGP20:28VA
GP10:20VAGP20:34VA
GP10:48VAGP20:90VA
240VAC GP10:24VAGP20:38VA
GP10:30VAGP20:45VA
GP10:60VAGP20:110VA
* ThefollowingcombinationsareassumedforLCDbacklightoffandnormaloperation.
GP10:1AImodule,1DOmodule,1DImoduleGP20:5AImodules,4DOmodules,1DImodule
• Modulepowersupplyvoltage:Thetotalallowablepowerconsumptionofrespectivemodulesisupto6WintheGP10andupto20WintheGP20.
• Allowableinterruptiontime:Lessthan1cycleofthepowersupplyfrequency
[Powersupplysuffixcode:2]• Ratedsupplyvoltage:12VDC• Allowablepowersupplyvoltagerange:10to20
VDC
9
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
• Powerconsumption:Supplyvoltage
LCDbacklightoff
Normaloperation
Maximum
12VDC 7VA 10VA 26VA
Isolation• Insulationresistance:BetweentheEthernet,
RS-422/485,andeachinsulationterminalsandearth:20MΩorgreaterat500VDC
• Withstandvoltage: Betweenthepowerterminalandearth(IncaseofPowersupplysuffixcode:1):3000VACat50/60Hzforoneminute
Betweenthepowerterminalandearth(IncaseofPowersupplysuffixcode:2):500VACat50/60Hzforoneminute
Betweenthecontactoutputterminalandearth:3000VACat50/60Hzforoneminute
Betweentheinput/outputmodulesandearth:DependsonthespecificationofI/Omodule.
• Grounding:Besuretosetalowgroundingresistance.
• Isolation:
Power terminal
The circuits divided by lines are insulated mutually.
Internal circuit
FAIL output terminalEthernet portRS-422/485 terminalInput and output module terminal
Input and output module internal circuitEarth (PE) terminalRS-232 terminalSD card slotUSB port
SafetyandEMCStandards• CSA: CAN/CSA22.2 No.61010.1, installation category
II(*1),andpollutiondegree2(*2) CAN/CSA-C22.2 NO. 61010-2-030 CAN/CSA-IEC61010-201*4 • UL:UL61010-1,UL61010-2-030(CSANRTL/C) UL61010-2-201(CSANRTL/C)• CE/EMCdirective: EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1• CE/Lowvoltagedirective: EN61010-1, EN 61010-2-030 InstallationcategoryII*1 Pollution degree 2 *2
Measurementcategory*3 EN61010-2-201*4
• C-Tick:EN55011compliance,ClassAGroup1• KCmarking:Electromagneticwaveinterference
preventionstandard,electromagneticwaveprotectionstandardcompliance*1 Installationcategory(overvoltagecategory)II: Describesanumberwhichdefinesatransient
overvoltagecondition. Impliestheregulationforimpulsewithstand
voltage. “II”appliestoelectricalequipmentwhich
issuppliedfromthefixedinstallationlikeadistribution board.
*2 Pollution degree 2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
*3 Measurementcategory:Dependsonthespecificationofeachmodules
*4 Thisproductisdesignedasopenequipmentundertherelevantstandard,installitasfollows:
•TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceotherthanthefront-panelcontrolareawithaninstrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelessly or in a panel.
•InstalltheGX60/GMunitinapanelwithadoor. •Theinstrumentationpanelorpanelusedfor
supportmustcomplywithCSA/UL/EN61010-2-201ormustbeatleastIP1X(degreesofprotection)andatleastIK09.
Category Measurementcategory
Description Remarks
II CATII Availableinthetestingandmeasuringcircuitsdirectly connected to a usage location (receptacle or the like) ofalow-voltagemainpowersupplyfacility.
Appliances, portable equipment,etc.
III CATIII Availableinthetestingandmeasuringcircuitsconnected to a power distributionportionofalow-voltagemainpowersupplyfacility.
Distributionboard, circuit breaker, etc.
IV CATIV Availableinthetestingandmeasuringcircuitsconnected to a power sourceofalow-voltagemainpowersupplyfacility.
verheadwire, cable systems,etc.
• WEEEDirective:CompliantNormalOperatingConditions:
• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(at5to40°C)
(no condensation)• Magneticfield:400A/morless(DCand50/60
Hz)• Vibration: 5≤f<8.4Hzamplitude3.5mm(peak) 8.4≤f≤160Hzacceleration9.8m/s2
• Shock: Non-energization,500m/s2 orless,approximate10ms,6directions(±X,±Y,±Z),3timesineachdirection
• Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontalwheninstallingthepanelmountandwallmount.
• Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpower
on
10
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
OtherSpecifications:• Memorybackup:Abuilt-inlithiumbatterybacks
up the settings and runs the clock• RecommendedreplacementperiodsofBattery:
Approximately10years(atroomtemperature)TransportandStorageConditions:
• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no
condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged
condition)
EXTERNAL DIMENSIONS AND PANEL CUTOUT DIMENSIONSGP10:
*1: with modules*2: without moduels
Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).
(*1)
(*2)MAX
8(0.
31)
8(0.
31)
144.
9(5.
70)
(0.5
9)15
196.8(7.75)
247.2(9.73)144(5.67)
144.
9(5.
70)
15 (0.5
9)
143.6(5.65)
When using the stand, GP10 is upward 12 degrees.
Rearview
Power supply, Inlet (Power supply code:1)
Power supply, Screw terminal (Power supply code:1)
I/O module (slot 1)
RS-422A/485 terminal (/C3)or RS232 terminal (/C2)USB port (/UH)Ethernet portFAIL/STATUS terminal (/FL)
I/O module (slot 2)
I/O module (slot 0)
11
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
GP20:
Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).
*1: with modules*2: without moduels
(*1)
(*2)MAX
288(11.34)
196.8(7.75)
287(
11.3
0)8(
0.31
)23 (0
.91)
247.2(9.73)
288(
11.3
4)
288(11.34) 8(0.
31)
22 (0.8
7)
Rearview
Power supplyRS-422A/485 terminal (/C3)or RS232 terminal (/C2)USB port (/UH)Ethernet portFAIL/STATUS terminal (/FL)VGA output terminal (/D5)
I/O module (slot 0)I/O module (slot 1)I/O module (slot 2)I/O module (slot 3)I/O module (slot 4)
I/O module (slot 5)I/O module (slot 6)I/O module (slot 7)I/O module (slot 8)I/O module (slot 9)
PrecautionstoBeTakenWhileWiringWithascrewterminal,werecommendthatyouuseacrimp-onlugwithaninsulationsleeve(M4forpowersupplywiring,M3forsignal wiring).Recommendedsignalwiringcrimp-onlugN1.25-MS3(JSTMfg.Co.,Ltd.)
SPECIFICATIONS OF OPTIONAL FUNCTIONS
ADVANCEDSECURITYFUNCTION(/AS) Securityandelectronicrecord/signaturefunctions
havebeenaddedthatarecompliantwiththeUSA’sFDAtitle21CFRPart11.• Enabling/disablingtheadvancedsecurity
function: Youcanenableordisabletheadvancedsecurity
function.* Thesetvaluesanddatastoredintheinternal
memoryareinitializedeachtimethefunctionisenabled or disabled.
• Dataanti-tamperfunction: Settingsandmeasureddataaresavedas
encryptedbinaryfiles.• Datatype: Onlyfordisplayorevent Triggermodeisnotpossiblewitheventdata.• Loginfunction: Usingtheloginfunctiondescribedbelow,you
canentersecuritysettingsontheinstrument• Username• Password• UserID(dependonsetting)• Userlevelandnumberofusers: Systemadministrator(allcanbeoperated),
Generaluser(Withuserrestrictions,youcansetrestrictionsonperformingoperations and sign authority.), Monitor user(monitoringonly),totally100users
• Userrestrictionssetting:10kinds(forgeneral users)
• Passwordexpirationtime: selectformOff,1month,3month,6month• Passwordcontrolfunction: LoginsareverifiedbyaKerberosv5
authenticationserver*(onlyusernameandpassword)
Encryptionmethod:AES128-CTS-HMAC-SHA1-96AES256-CTS-HMAC-SHA1-96ARCFOUR-HMAC-MD5
Pre-Authfunction:use* Thefunctionhasconfirmedcompatibilitywith
WindowsServer2003SP2/WindowsServer2008SP2/WindowsServer2012ActiveDirectory
• Signaturefunction: Aftercheckingdatathathasfinishedbeing
recorded,youcanaddthreelevelsofelectronicsignature,selectapass/fail,andentercomments(50charactersmaximum)
• Audittrailfunction: The operation log, the settings change log and
thesettingsfilewhenthechangewasmadearesaved.
• Measurementmodelimitations HighspeedandDualintervalmeasurement
modesarenotsupported.• Modulelimitations PIDcontrolmodulesarenotsupported.
12
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
SERIALCOMMUNICATIONINTERFACE(/C2,/C3)• Connection:EIARS-232(/C2)orEIARS-
422/485(/C3)• Protocol:Dedicatedprotocol,Modbus/RTU,or
DARWINcompatiblecommunication• Setting/measurementserverfunction:Operation,
settingoroutputofmeasurementdataareavailablebydedicatedprotocol.
• Synchronization:Start-stopsynchronization• Transmissionmode(RS-422/485):
RS-422:Four-wirehalf-duplexmulti-dropconnection (1:n (n = 1 to 31)) RS485:Two-wirehalf-duplexmulti-dropconnection (1:n (n = 1 to 31))
• Baudrate:1200,2400,4800,9600,19200,38400, 57600, or 115200 bps
• Datalength7or8bits• Startbit:1bit• Stopbit:1bitor2bit• Parity:ODD,EVEN,orNONE• HandshakingOff:Off,XON:XON,XON:RS,and
CS: RS• Communicationdistance;RS-422/485:1200m
(57600bpsorless),600m(115200bps) RS-232:15m• Modbus/RTUcommunication:Readingorwriting
ofmeasurementdataonotherinstrumentsisavailablebyModbusprotocol.
Communicationchannelfunctionoption(/MC)isneededtoreadmeasurementdatafromotherinstruments.
• Operationmodes:Masterorslave• Executionofacommunicationcommandusinga
barcode:Theenteredtextcanbeexecutedasacommunicationcommand.
CUSTOMDISPLAY(/CG) UsingDXA170DAQStudio,screencreation
software,acustomscreencanbeconstructedanddisplayedinwhichdisplaycomponents(suchastrend,digital,andbargraphs)arefreelyplaced.
ThescreendataistransferredfromDAQStudiototheinternalmemoryviacommunication,orloadedfromanexternalmediumtotheinternalmemoryand displayed.• Numberofscreens:30(internalmemory)• Displaycomponents:
• Normalcomponents(digitalvalue,bargraph,tagNo.,tagcomment,simpledigitalvalue,simplebargraph,alarmmark,unit,alarmindicator,lower-limitspanvalue,upper-limitspanvalue,groupname,systemicon,memorysamplebar,date/timeview,batchname,andusername)
• Trendcomponents(trendgroupdisplay(with scale board))
• Listcomponents(alarmlistviewandmessagelistview)
• Operationcomponents(DO(DOoperable),internal switch (internal switch operable), numericvalueoperations(viewingdataofandwritingdatatocommunicationchannels), and button operations (writing numericvalues,operatingbits,switchingscreens,andexecutingcommunicationcommands)
• Textcomponents(labels)
• Figurecomponents(lineview,rectangleview,andcircleview)
• Imagecomponents(PNGimagedata)• Batchcomponents(Batchnumber,Lot
number,Textfield,Batchcomment,Batchgroupnumber*)
* OnlyonGPwiththeMultibatchfunction(/BT option)
• Controlcomponent(controller,controlalarmindicator,externalcontroller)
• Configuringscreens:Screencreationsoftware CreationusingDXA170DAQStudio(GPdoes
nothaveacreationfunction)• Saving/loadingscreendata: Aspecifiedscreenorallthescreensis/are
loadedfromanexternalstoragemediumtotheinternalmemory,oraspecifiedscreenorallthescreensintheinternalmemoryis/aresavedonanexternalstoragemedium.
VGAVIDEOOUTPUT(/D5)(OnlyforGP20)• Externaldisplay: Resolution:800×600dots(VGA) Connector:15-pinD-Sub(female)
EtheNet/IPCOMMUNICATION(PLCcommunicationprotocol)(/E1)
CanbejoinedtoanEthernet/IPnetworkasanadapter(oraserver).• LoadingdatafromtheI/Ochannelorcalculation
channel (/MT) I/Ochannel: GP10: 100, GP20-1: 100, GP20-2: 500 Calculation channel: GP10: 50, GP20-1: 100, GP20-2: 200• Loadingandwritingdatafrom/tothe
communicationchannel(/MC) Communicationchannel: GP10: 50, GP20-1: 300, GP20-2: 500• Implementationlevel:Level2• Supportedprotocols:EIP/PCCC,EIP/native• Numberofthesimultaneousconnection:Max.
10(Explicitmessage)
WTCOMMUNICATION(/E2) CollectsdatabyconnectingtoWTequipment
manufacturedbyYokogawaMeters&InstrumentsCorp.viaEthernetcommunication*.* The /MC option is required.• Supportedmodels:WT1800E(commandtype
WT1800),WT1800,WT300E(commandmodeWT300),WT500,andWT300
• Numberofconnectableunits: GP10: 8 GP20: 16• Communicationcycle:500ms/1s/2s/5s/10s/20
s/30 s• Typesofdatathatcanbeobtained:Voltage,
current,power,powerfactor,phase,electricalenergy,high-frequencywave,etc.
• Numberofdataallocations GP20:300 GP10:50
13
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
FAILOUTPUT(/FL)• Contact:Ccontact,1point• FAILoutput: The relay contact output on the rear panel
indicatestheoccurrenceofCPUfailure. Relayoperation:Energizedduringnormal
operationandde-energizedonCPUfailure.• Statusoutput:Therelaycontact,whichisde-
energizedinnormaloutputstate,isenergizedupontheoccurrenceofamemory/mediaerror,measurementerror,communicationerror,recordingstop,oralarm.
• Ratedpowersupplyvoltage:24VDCor250VAC or less
• Ratedloadcurrent:3A(DC)/3A(AC),resistanceload
• Min.loadcurrent:100mA• Recommendedreplacementperiodsofcontact: Electrical:30,000moreON-OFFoperations,
Mechanical:5,000,000moreON-OFFoperations
LogSCALE(/LG) Alogarithmicvoltagethathasbeenconvertedfrom
aphysicalvalueisappliedtotheGP,andthentheGP’sLogscale(logarithmicscale)isusedtodisplayandrecordthephysicalvalue.• Inputtype:Loginput(logarithmicinput),Pseudo
log input: An input that supports pseudo logs,Loglinearinput:Inputthatislinearonalogarithmicscale.
• Range:20mV/60mV/200mV/1V/2V/6V/20V/50V/100V
• Scalablerange:• Loginput: 1.00E-15to1.00E+15(15decade
maximum) Scale_L<Scale_U Ifthelowerlimitmantissais1.00,the
differencebetweentheexponentsmustbe1ormore.
Ifthelowerlimitmantissaisavalueotherthan1.00,thedifferencebetweentheexponentsmustbe2ormore.
• PseudoLogInput/Loglinearinput 1.00E-15to1.00E+15(15decade
maximum) Thehigherlimitmantissaisthesameas
thelowerlimitmantissa). Ifthelowerlimitmantissais1.00,thevalue
mustbebetween1.00E–15and1.00E+15,thedifferencebetweentheexponentsmustbe1ormore,andthemaximumdecadesis15.
Ifthelowerlimitmantissaisavalueotherthan1.00,thevaluemustbebetween1.01E–15and9.99E+14,thedifferencebetweentheexponentsmustbe1ormoreandthemaximumdecadesis15.
• Alarmtype:Highlimit,lowlimit,delayhighlimit,anddelaylowlimit
• Alarmsettingrange:TherangeconvertedintotheLOGscalecorrespondingto-5%to105%ofthe span width.
• Alarmhysteresis:Fixedto0
• Greenbandsettingrange:Thelowerlimittotheupperlimitofthescale.However,thelowerlimitofthedisplaypositionmustbesmallerthantheupperlimit.
• Positionofthedecimalpoint:1to2• Misc:Nonlinearinputispossiblebycorrecting
theinputvalue
MATHEMATICAL FUNCTIONS WITH REPORT FUNCTION(/MT)MathematicalFunction:• Numberofmathchannels;GP10:50,GP20-1:
100, GP20-2: 200Note) Note:Dependingonthemeasurementmode,
thereisalimittothenumberofmathchannelsatscanintervalsshorterthan100ms.See“Limitations.”
• ScanintervalMeasurementmode Scaninterval
Normal Scaninterval
High speed Scaninterval
Dualinterval Masterscaninterval*
* WhenthemeasurementmodeisDualinterval,thisitemsetswhichscanintervaltouse,theintervalofmeasurementgroup1orthatofscangroup2,forcreatingmeasuredvaluesofmathorcommunicationchannelsandothersimilaroperations.
• Numberofexpressions:• Operation: Generalarithmeticoperations:Fourarithmetic
operations(+,-,*,/),squareroot,absolute,commonlogarithm,naturallogarithm,exponential,andpower
Relationaloperations:<,≤,>,≥,=,and≠ Logicoperations:AND,OR,NOT,andXOR Statisticaloperations:TLOG(maximum,
minimum,average,sum,P-Pvaluesoftimeseriesdata)orCLOG(maximum,minimum,average,sum,P-Pvaluesofaspecifiedchannel)
Specialoperations:PRE,HOLD,RESET,andCARRY
Conditionaloperation:[a?b:c] Bitoperation:BIT Integerextractingoperation:INT Remainderextractingoperation:MOD Trigonometricfunctions:SIN,COS CP operations: CP.02, CP.CO2• Computationaccuracy:Double-precisionfloating
point• Datathatcanbeused; Channeldata:Measurementchannels(0001to
6516to6516),mathematicalchannels(GP10:A001 to A050, GP20-1: A001 to A100, GP20-2: A001toA200),Communicationchannels(GP10:C001 to C050, GP20-1: C001 to C300, GP20-2: C001toC500),Communicationchannelsrawdata (GP10: RC001 to RC050, GP20-1: C001 to C300,GP20-2: RC001 to RC500),Constants: K001toK100,Variableconstant:W001toW100,Internalswitch:S001toS100,Flag:F01toF20,Recording state (REC01), Integer data: Z000 to Z999
14
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
USBINTERFACE(/UH)• USBport:ComplieswithUSB2.0andhost
function• Numberofports:2(oneeachonthefrontpanel
and rear panel)• Connectabledevices:Onlyconnectthedevices
listedbelowtopreventdamagetothedevices.Keyboard:ComplieswithHIDClassVer.1.1 104/89keyboard(US)and109/89
keyboard (Japanese)Mouse:ComplieswithHIDClassVer.1.1Externalmedium:USBflashmemory Doesnotguaranteetheoperationofall
USBflashmemories Externalmediumsuchasaharddisk,ZIP,
MO, and optical discs are not supported.Barcodereader:USBHIDClassVer.1.1
compatible English(U.S.)standardUSBkeyboard
compatible• Executionofacommunicationcommandusinga
barcode:Theenteredtextcanbeexecutedasacommunicationcommand.
• Powersupply:5V±10%,500mA*1*1: Deviceswhichneedmorethan500mAtotalbus
powerfor2portscannotbeconnectedatthesametime.
Forlowpowereddevices(buspower<100mA):5V±5%
Forhighpowereddevices(buspower<500mA):5V±10%
AEROSPACEHEATTREATMENT(/AH)SupportsheattreatmentapplicationAMS2750/
NADCAP.Schedulemanagementforperiodicallyexecuting
calibrationcorrectionconfigurationandthelike.Incorrectioncoefficientmodeofcalibration
correction,twobiasescanbespecified:onebasedonthermocoupleandanotherbasedondevice
• Numberofmanageableschedules GP20-1:6 GP20-2: 12• Calibrationcorrectionmode: Off,Linearizerapproximation,Linearizerbias,
correctionfactor• Numberofsetpoints:2to12• Notificationcontents Title,Notificationmessage,DuedateNotificationbuzzercanbesounded.
Logicmathfunction:Afunctionthatoutputscalculatedresultsas0or1
toDOsorinternalswitches• Numberoflogiccalculationsmaths: GP10: 20, GP20-1/GP20-2: 50• Expression:Upto120characters• Computationtype:Basicarithmetic,relational,
logical, conditional, bit• Datathatcanbeused:Allchanneldata• Logicmath:LM001toLM020(GP10),LM001to
LM050 (GP20-1/GP20-2)• Outputdestination:DOchannels,internal
switches (only when set to Manual in either case)• Settingchange:Cannotbechangedduring
recording• Mathinterval:100ms(fastest)
Reportfunction:• Numberofreportchannels;GP10:50,GP20:60Note) Dependingonthemeasurementmode,thereis
alimittothenumberofreportchannelsatscanintervalsshorterthan100ms.See“Limitations.”
• ScanintervalMeasurementmode Scaninterval
Normal Scaninterval
High speed Scaninterval
Dualinterval Scanintervalofeachmeasurementgroup
• Reporttypes:Hourly+daily,daily+weekly,daily+monthly,Batch,Daycustom
• Computationtypes:Average,maximum,minimum,sum,orinstantaneousvalue
• Unitofsum:OFF,/s,/min,/hour,/day• Reporttemplates:OfficeOpenXMLspreadsheet
files(whichcanbedisplayedwithMicrosoftOfficeExcel)orPDFfilescanbeoutputorprinted out with any LAN-connected printer supporting the HP PCL5c language and the port 9100.
COMMUNICATIONCHANNELFUNCTIONS(/MC)• Numberofcommunicationchannels; GP10: 50 (C001 to C050) GP20-1: 300 (C001 to C300) GP20-2: 500 (C001 to C500)Note) Dependingonthemeasurementmode,thereis
alimittothenumberofcommunicationchannelsatscanintervalsshorterthan100ms.See“Limitations.”
• ScanintervalMeasurementmode Scaninterval
Normal Scaninterval
High speed Scaninterval
Dualinterval Masterscaninterval
* RequiredtorecorddatafromEtherNet/IP(/E1),Modbusdevices,orPCsontheGPandtowritedataintheremotedevicefromtheGPviaModbus.
15
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
MULTI-BATCHFUNCTION(/BT)Recordingstart/stopanddatafilecreationis
possibleforeachbatch.• Numberofmulti-batches: GP10/GP20-1:max.6,GP20-2:max.12• Batchsingleoperation:Memorystart/stop,math
reset,messagewriting• Batchoverviewoperation:Computationstart/
stop,reportstart/stop,manualsampling,setupdatasave/load
• Scaninterval:500ms,1s,2s,5s(commontoall batches)
• Datatype:DisplayoreventonlyTriggermodenotavailableforeventdata.
• Recordinginterval:Commontoallbatches• Datafile:Displayoreventdatafilecreatedfor
each batch• Numberofdisplaygroups: GP10:6max.perbatch
Numberofchannelspergroup:10 GP20-1:6max.perbatch
Numberofchannelspergroup:20 GP20-2:12max.perbatch
Numberofchannelspergroup:20 Channelsassignedtothedisplaygroupofeach
batch and those set as recording channels are recordedtodatafiles.
• Batchsinglesettings:Group,tripline,fileheader,datafilename,textfield,batchnumber,lotnumber
• Measurementmodelimitations HighspeedandDualintervalmeasurement
modesarenotsupported.
OPC-UASERVER(/E3)DataacquiredbytheGPcanbeaccessedthrough
Ethernetcommunicationfromahostsystem(OPC-UAclient).
• Communication Mode:OPC-UAServer Encoding:UABinary Protocol:OPCUATCP Maximumnumberofconnections:3sessions Profile MicroEmbeddedDeviceServer• Security Type: None Encryption: None Login:Anonymous,Username• Dataacquisition: Measurementvalue,alarmstatus,andalarm
value Computationvalue,alarmstatus,andalarm
value Communicationvalue,alarmstatus,andalarm
value Batchinformation PV,SP,OUT,R/S,A/M/C,R/L,Alarmstatusin
loop• Datawriting:Measurementchannel(DOchannel
only),communicationchannel,alarmvalue,batchinformation,OUT,R/S,A/M/C,R/L
• Otheracquiredinformation:Devicename,serialnumber,time,devicestatus
• Portnumber:4840(changeable:1to65535)• Numberofitems: GP10:100max.(MonitoredItem/Session) GP20:300max.(MonitoredItem/Session)
• Fastestperiod:100ms• Serviceset:Discovery FindServers,GetEndpoints
SecureChannel OpenSecureChannel,CloseSecureChannel
Session CreateSession,ActivateSession,CloseSession
View Browse,BrowseNext,TranslateBrowsePathsToNodeIds
Attribute Read,Write
MonitoredItem CreateMonitoredItems,ModifyMonitoredItems,DeleteMonitoredItems,SetMonitoringMode
Subscription CreateSubscription,ModifySubscription,DeleteSubscriptions,Publish,Republish,SetPublishingMode
SLMPCOMMUNICATION(MitsubishiPLC)(/E4)CC-LinkfamilySLMPcommunicationprotocol
function,whichenablesconnectionfromaGPto Mitsubishi Electric PLCs without sequencer programs.
TheGPoperatesasanSLMPclient.WritingGPmeasurementdatatoaPLCandreadingPLCdataintocommunicationchannels*arepossible.* Thecommunicationchannelfunction(/MCoption)
is required.• Numberofconnectiondestinationservers:16max.• Readcycle:100ms/200ms/500ms/1s/2s/5s/10s/2
0s/30s/1min• Communicableinternaldata: Specialrelay(SM),specialregister(SD),input
(X),output(Y),internalrelay(M),latchrelay(L),annunciator(F),edgerelay(V),linkrelay(B),dataregister(D),linkregister(W),timercontact(TS),timercoil(TC),currenttimervalue(TN),integrationtimercontact(SS),integrationtimercoil(SC),currentintegrationtimervalue(SN),counter contact (CS), counter coil (CC), current countervalue(CN),speciallinkrelay(SB),speciallinkregister(SW),directaccessinput(DX),directaccessoutput(DY),indexregister(Z),fileregister(R,ZR),extendeddataregister(D),extendedlinkregister(W)
Devicecodeisindicatedinparentheses.
Programcontrolfunction(/PG)SeeGX90UTPIDControlModuleGeneral
Specifications(GS04L53B01-31EN)
16
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
LimitationsSystemlimitations
MaximumnumberofchannelsSystem Measurment
modeMaximumnumberofmoduleconnections
MaximumnumberofchannelsInput/output Communication Math Report
GP10 Normal 10 100 50 50 50
High speed 3 12 50 50 50
Dualinterval 10 50 25 25 25
GP20-1 Normal 10 100 300 100 60
High speed 10 40 300 100 60
Dualinterval 10 50 150 50 30
GP20-2 Normal 45 500 500 200 60
High speed 10 40 500 200 60
Dualinterval 45 250 250 100 30
LimittothenumberofexpandableI/OunitsorGMsubunits•Uptosixunitscanbeconnected.•ConnectionisnotpossibleifthemeasurementmodeissettoHighspeed.
LimittothenumberofGPmainunitmodulesModule GP10 GP20-1 GP20-2
WhenGX90XA-04-H0andGX90YAareincluded
2* 9 9
WhenGX90UTisincluded 2* 8 8
* Whenthe12VDC(PowersupplySuffixCode2)model.
LimitonModules•Upto10modulesconsistingofGX90YD,GX90WD,andGX90UTcanbeinstalledintothesystem.•OneGX90WDmodulecanbeinstalledinaGP.OnemodulecanbeinstalledinaGX60(expandableI/O)andeach
GM sub unit.•OneGX90YAmodulecanbeinstalledinaGP10.TwomodulescanbeinstalledineachoftheGP20,GX60(expandableI/O)andGMsubunit.
•Upto10GX90YAmodulescanbeinstalledinaGP10/GP20-1systemandupto12inaGP20-2system.•IfthemeasurementmodeisHighspeed,aGX90XDorGX90WDmodulecanbeinstalledinthesystem.•IfthemeasurementmodeisHighspeed,onlyGX90XA-04-H0(high-speedAI),GX90XD(DI),andGX90WD(DIO)aredetected.DIandDIOarefixedtoremotemode.Measurementandrecordingarenotpossible.
•IfthemeasurementmodeisDualinterval,GX90UTisnotdetected.
LimittotheNumberofMeasurementChannelsThefollowinglimitationappliestothenumberofchannelsthatcanmeasureatscanintervalsshorterthan100ms.IfthemeasurementmodeisDualinterval,thelimitationappliesatthescangrouplevel.However,therearescanintervalsyoucannotset.
● MeasurementmodeisHighspeedGP10
Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms
Input/output 1 2 5 10 12 12
math – 1 2 5 10 25
communication – 1 2 5 10 25
Report – 1 2 5 10 25
17
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
GP20-1
Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms
Input.output 1 2 5 10 20 40
math 1 2 5 10 20 50
communication 3 6 15 30 60 150
Report 1 2 5 10 20 50
GP20-2
Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms
Input.output 5 10 25 40 40 40
math 2 4 10 20 40 100
communication 5 10 25 50 100 250
Report 2 4 10 20 40 60
● MeasurementmodeisDualintervaGP10
Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms
Input.output – – 5 10 12 12
math – – 1 2 5 12
communication – – 1 2 5 12
Report – – 1 2 5 12
GP20-1
Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms
Input.output – – 5 10 20 40
math – – 2 5 10 25
communication – – 7 15 30 75
Report – – 2 5 10 25
GP20-2
Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms
Input.output 5 10 25 40 40 40
math 1 2 5 10 20 50
communication 2 5 12 25 50 125
Report 1 2 5 10 20 30
18
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
LimittotheNumberofRecordingChannelsinEachMeasurementModeI/Ochannel+mathchannel+communicationchannel
Model Measurmentmode
Recordinginterval1ms 2ms 5ms 10ms 20ms 50ms 100ms 200ms 500ms 1sor
moreGP10 Normal – – – – – – 100 100 100 100
High speed 2 4 10 20 40 100 100 100 100 100
Dualinterval – – 5 10 20 50 100 100 100 100
GP20-1 Normal – – – – – – 100 200 500 500
High speed 2 4 10 20 40 100 100 200 500 500
Dualinterval – – 5 10 20 50 100 100 250 250
GP20-2 Normal – – – – – – 500 500 1000 1000
High speed 10 20 50 100 150 150 200 500 1000 1000
Dualinterval 5 10 25 40 50 50 100 20 600 600
NotesonModuleInstallation•WhenthereferencejunctioncompensationofthisproductisusedwiththethermocoupleinputofaGX90XA-10-U2,GX90XA-10-L1,GX90XA-10-T1orGX90XA-04-H0,ifthefollowingmoduleisinstalledtotheright(slotwiththesmallernumber)oftheGX90XAmoduleasseenfromtheGPrearpanel,thereferencejunctioncompensationaccuracyofthatmodulemaydeviatefromtheguaranteedrange(exceptwhenGX90XA-04-H0isinstalledtoadjacentslots).
GX90XA-10-C1,GX90XA-04-H0,GX90WD,GX90YA,GX90UT•OntheGP20,whenthereferencejunctioncompensationofthisproductisusedwiththethermocoupleinputofaGX90XA-10-U2,GX90XA-10-L1,GX90XA-10-T1,orGX90XA-04-H0,ifthefollowingmoduleisinstalledabove,below,totheright,ortotheleft(slotwiththesmallernumber)oftheGX90XAmoduleasseenfromtheGPrearpanel,thereferencejunctioncompensationaccuracyofthatmodulemaydeviatefromtheguaranteedrange.
GX90YA,GX90UT•IfyouwanttousetheDIofaGX90XDorGX90WD,onlyasinglemoduleinstalledintheGPmainunitcanbeused.•IfthemaximumnumberofI/OchannelsareassignedandthelastchannelisassignedtoanintermediatechannelofaconnectedI/Omodule,thatmoduleandsubsequentmoduleswillnotberecognized.
Modulen
• • •
1
10
Module1
:
81
90
:
91
100
106
:
:Maximum number of I/O channels
This module will not be detected.
Example GP10/GP20-1
DualIntervalFileSearchingofUniversalViewer
Recordingmode Linkdualintervalwaveform*1 Showdualintervalintegratedlinkview*2
Free+Free
Free+Trigger(single/repeat) – –
Trigger(single/repeat)+Trigger(single/repeat)
– –
*1 Linkdualintervalwaveform:Afunctionthatsearchesafolderforanddisplaysthefilethatformsapairwiththedisplayedfile.
*2 Showdualintervalintegratedlinkview:AfunctionthatdisplaysfromtheresultofSearchOpenoneofthefilesthatformsapair and displays both trends when it is clicked.
PIDprogrampatternsettingfromtheWebapplicationYoucannotsetfromtheWebapplication.HardwareConfiguratorisrequiredforsettingprogrampatterns.
19
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
INPUT/OUTPUT MODULE SPECIFICATIONS
ANALOGINPUTMODULE(ModelGX90XAorOption/Uxx0)
DIGITALINPUTMODULE(ModelGX90XDorOptions/CRx1)
DIGITALOUTPUTMODULE(ModelGX90YD,orOptions/CR1x,/CR2x,/CR4x)
DIGITAL INPUT/OUTPUT MODULE (ModelGX90WD)
PULSEINPUTMODULE(ModelGX90XP)
ANALOGOUTPUTMODULE(ModelGX90YA)
PIDCONTROLMODULE(ModelGX90UT)
PleaseseeGX90XA/GX90YA/GX90XD/GX90YD/GX90WD/GX90XPInput/OutputModuleandPIDControl(GS04L53B01-31EN)GeneralSpecification(GS 04L53B01-01EN.)
APPLICATION SOFTWARESMARTDAC+STANDARD• Universalviewer• Hardwareconfigurator(withProgrampattern
setting)
DownloadthelatestversionofthesoftwarefromthefollowingURL; www.smartdacplus.com/software/en/
OperatingenvironmentOS:
OS TypeWindows7 HomePremiumSP1(32-bitand64-bit
Editions)
ProfessionalSP1(32-bitand64-bitEditions)
Windows8.1 Update
ProUpdate
Windows10 Home(32-bitand64-bitEditions)
Pro (32-bit and 64-bit Editions)
Processorandmainmemory:OS Processorandmainmemory
Windows7Windows8.1Windows10
32-biteditionIntelPentium4,3GHzorfasterx64orx86,2GBormore64-biteditionIntelx64processorthatisequivalenttoIntelPentium4,3GHzorfaster,2GBormore
Browser:Supportedbrowser:InternetExplorer11HTTP1.1andJavaScriptareused.
Harddisk:• 100MBormoreoffreespace
Display:• AvideocardthatisrecommendedfortheOS
and a display that is supported by the OS, has a resolutionof1024x768orhigher,andthatcanshow65,536colors(16-bit,highcolor)ormore.
UniversalViewersoftwareTheuniversalviewercandisplaythefollowingdatagenerated by the recorder on the screen and print it out on the printer.• Displaydatafile• Eventdatafile• Reportdatafile(IncludingHour,Day,Week
Month)• Manualsampledatafile
• Viewerfunction Waveformdisplay,digitaldisplay,circulardisplay,
list display, report display, operation log display etc.
• Dataconversion: FileconversiontoASCIIorMS-Excelformat• Signinfunction
Webapplication/Hardwareconfigurator• OnlinesettingonWebbrowser(IE)• OfflinesettingonWebbrowser(IE)BothsettingscanbemadeusingbrowserssuchasInternetExplorer11.
20
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
MODEL AND SUFFIX CODES
Model SuffixCode Optionalcode DescriptionGP10 Paperlessrecorder(Portabletype,Smalldisplay)*13
GP20 Paperless recorder (Portable type, Large display) *13
Type -1 Standard(Max.measurementchannels:100ch)
-2 Largememory(Max.measurementchannels:500ch)*12
Displaylanguage E English,degF,DST(summer/wintertime)*9
Power supply 1 100VAC,240VAC*16
2 12VDC*17
Power cord D PowercordUL/CSAstandard
F PowercordVDEstandard
R Power cord AS standard
Q Power cord BS standard
H Power cord GB standard
N Power cord NBR standard
W Screwterminal,powercordnotincluded
Optionalfeatures /AH Aerospaceheattreatment
/AS Advancedsecurityfunction(Part11)*23
/BT Multi-batchfunction*24
/C2 RS-232 *1
/C3 RS-422/485 *1
/CG Customdisplay*15
/D5 VGAoutput*2
/E1 EtherNet/IPcommunication(PLCcommunicationprotocol)*20
/E2 WTcommunication*14
/E3 OPC-UAserver
/E4 SLMPcommunication(MitsubishiPLC)*21
/FL Failoutput,1point
/LG Log scale
/MT Mathematicalfunction(withreportfunction)*18 *19
/MC Communicationchannelfunction*21
/PG Programcontrolfunction*25
/UH USBinterface(Host2ports)
21
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
Analoginputmodule,DigitalI/Omodule:Pleaseaddthefollowingsuffixcodestothemainunitmodelandspecificationcodes.
Option Optionalcode DescriptionOptionalfeatures(Analog input) *3*11
/UC10 Withanaloginputmodule,10ch(Clampterminal)
/UC20 Withanaloginputmodule,20ch(Clampterminal)*7
/UC30 Withanaloginputmodule,30ch(Clampterminal)*8
/UC40 Withanaloginputmodule,40ch(Clampterminal)*5
/UC50 Withanaloginputmodule,50ch(Clampterminal)*5
/US10 Withanaloginputmodule,10ch(M3screwterminal)
/US20 Withanaloginputmodule,20ch(M3screwterminal)*7
/US30 Withanaloginputmodule,30ch(M3screwterminal)*8
/US40 Withanaloginputmodule,40ch(M3screwterminal)*5
/US50 Withanaloginputmodule,50ch(M3screwterminal)*5
Optionalfeatures(DigitalI/O)*4
/CR01 WithdigitalI/Omodule,(Output:0,Input:16)*8 *9 *18
/CR10 WithdigitalI/Omodule,(Output:6,Input:0)*8
/CR11 WithdigitalI/Omodule,(Output:6,Input:16)*7 *8 *9 *18
/CR20 WithdigitalI/Omodule,(Output:12,Input:0)*6
/CR21 WithdigitalI/Omodule,(Output:12,Input:16)*6 *9 *18
/CR40 WithdigitalI/Omodule,(Output:24,Input:0)*6
/CR41 WithdigitalI/Omodule,(Output:24,Input:16)*6 *9 *18
*1 /C2and/C3cannotbespecifiedtogether.*2 /D5canbespecifiedonlyfortheGP20.*3 Onlyoneoptioncanbespecified.*4 Onlyoneoptioncanbespecified.*5 /UC40,/UC50,/US40and/US50cannotbespecifiedfortheGP10.*6 /CR20,/CR21,/CR40and/CR41cannotbespecifiedfortheGP10.*7 If/UC20or/US20isspecified,/CR11cannotbespecifiedfortheGP10.*8 If/UC30or/US30isspecified,/CR01,/CR10and/CR11cannotbespecifiedfortheGP10.*9 DigitalinputmodulehaveM3screwterminals.*10 TheDisplaylanguageisselectablefromEnglish,German,French,Russian,Korean,Chinese,Japanese.(AsofMar.,2013) Toconfirmthecurrentavailablelanguages,pleasevisitthefollowingwebsite. URL:http://www.yokogawa.com/ns/language/*11Universaltype(TypeSuffixCode:-U2).Ifyouneedtheelectromagneticrelaytype(TypeSuffixCode:-T1),current(mA)
inputtype(TypeSuffixCode:-C1),Lowwithstandvoltagerelay,type(TypeSuffixCode:-L1),High-speeduniversaltype(TypeSuffixCode:-H0),4-wireRTD/resistancetype(TypeSuffixCode:-R1),purchaseitseparately.
*12LargememorytypecanbespecifiedonlyfortheGP20.*13ToconnectanexpandableI/O,GMsubunit,youwillneedoneexpansionmodulefortheGP.*14/MCmustbeseparatelyspecifiedwhentheWTcommunicationisselected.*15CreatingcustomdisplaysrequiresDXA170DAQStudio(soldseparately).(GPdoesnothaveacreationfunction.)*16PowercodecanbespecifiedthesuffixcodeD,F,R,Q,H,orN..*1712VDCpowersupplycanbespecifiedonlyfortheGP10withoutpowercode(suffixcode:W).*18Optionalcode/MT(MATH)requiredifusingtheGX90XD'sorGX90WD'spulseinput.*19The/MToption(computation)isrequiredtoperformpulseintegrationonGX90XPpulseinputmodules.*20IfyouwanttowritefromaPLCtotheGPviaEtherNet/IPcommunication,aseparatecommunicationchannel(/MC)is
required.*21IfyouwanttheGPtoloaddatafromSLMPserversviaSLMPcommunication,aseparatecommunicationchannel(/MC)is
required.*22IfyouwanttoloaddatafromotherdevicesintotheGPusingModbusclient,acommunicationchannel(/MC)isrequired.*23WhentheadvancedsecurityfunctionissettoON,thescanintervalissetto100msorlonger.Inaddition,thedualinterval
functionandPIDmodulescannotbeused.*24Whenthemulti-batchfunctionissettoON,thescanintervalissetto500msorlonger.Inaddition,thedualintervalfunction
cannot be used.*25APIDcontrolmoduleisrequiredtousetheprogramcontrolfunction.
22
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
StandardAccessoriesProduct Qty
SDmemorycard(1GB) 1
Stylus pen (touch pen) 1
Tagsheet(forGP10orGP20) 1
Sheet(paper)(forGP10orGP20) 1
Power cord 1*
Dummycover(Foremptyslots) -
* ExceptGP10powersupplysuffixcode:2
ApplicationSoftware(SoldSeparately)Model Description OS
DXA170 DAQStudiosoftware Windows7/8/8.1/10
GA10 DataLoggingSoftware Windows7/8.1/10WindowsServer2008/2012/2016
OptionalAccessories(SoldSeparately)Product Model/partno.
ModelSDmemorycard(1GB) 773001
Stylus pen (touch pen) B8740BZ
ShuntresisterforM3terminal(250Ω±0.1%) 415940
ShuntresisterforM3terminal(100Ω±0.1%) 415941
ShuntresisterforM3terminal(10Ω±0.1%) 415942
ShuntresisterforClampterminal(250Ω±0.1%) 438920
ShuntresisterforClampterminal(100Ω±0.1%) 438921
ShuntresisterforClampterminal(10Ω±0.1%) 438922
Dummycover B8740CZ
ValidationDocuments(For/ASoption)*1 773230
*1 ProvisionofValidationDocuments A license sheet containing the license key
requiredforinstallationisprovided. Downloadthevalidationdocumentfromthe
followingURL. http://www.smartdacplus.com/software/en/
Analoginput/outputmodule,DigitalI/Omodule(soldseparately):MODELandSUFFIXCode(GX90XA)MODELandSUFFIXCode(GX90XD)MODELandSUFFIXCode(GX90YD)MODELandSUFFIXCode(GX90WD)MODELandSUFFIXCode(GX90XP)MODELandSUFFIXCode(GX90YA)MODELandSUFFIXCode(GX90UT) PleaseseeGX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YAInput/OutputModuleGeneralSpecification
(GS04L53B01-01EN.)andPIDControlModule(GS04L53B01-31EN)When connecting the Expandable I/O PleaseseeGX60ExpandableI/O,GX90EXExpansionModuleGeneralSpecification(GS04L53B00-01EN.)
23
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN June. 14, 2017-00
Calibrationcertificate(soldseparately)WhenorderingtheGP10/GP20withoptions(analoginput),thecalibrationcertificateforthemodulesisincludedinandshippedwiththecalibrationcertificateofthemainunit.Whenorderingananaloginputmoduleseparately,eachmodulegetsitsowncalibrationcertificate(onecertificatepermodule).
Testcertificate(QIC,soldseparately)WhenorderingtheGP10/GP20withoptions(analog/digialI/O),theQICforeachmoduleisincludedinandshippedwiththeQICofthemainunit.WhenorderinganaloginputmodulesanddigitalI/Omodulesseparately,eachmodulegetsitsownQIC(oneQICpermodule).
User'sManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL:www.smartdacplus.com/manual/en/
ProductPurchaseSpecificationsTheGP10/GP20iscomposedofthemainunit,I/Omodules,ExpandableI/O,andExpansionmodule.TherearetwowaystopurchaseI/Omodules.OnewayistopurchasethemindividuallybyspecifyingmodelsGX90XA,GX90XD,GX90YD,GX90WDandGX90XP,GX90YA,GX90UT.Theotherwayistopurchasethemasanoption(/UCxxor/USxx).Purchasingthemasanoptionisconvenient,butthisplaceslimitationsonthenumberofanaloginputsthatyoucanobtain.Ifyouwanttousemorethan50channels,pleasepurchasetheI/Omodulesindividually.ToconnectexpandableI/O(GX60),GMsubunittoGP10orGP20,youmustpurchaseoneunitofexpansionmodule(GX90EX)forGP10/GP20inadditiontotheexpandableI/O,GMsubunit.
Trademarks TheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.
•SMARTDAC+andSMARTDACPLUSaretrademarksofYokogawaElectricCorporation.•Microsoft,MSandWindowsareregisteredtrademarksofMicrosoftCorporationUSA.•PentiumareregisteredtrademarksofIntelCorporation.•ModbusisaregisteredtrademarkofAEGSchneider.•KerberosisatrademarkofMIT.•JavaandJava-relatedtrademarksaretrademarksorregisteredtrademarksofSunMicrosystems,Inc.intheUnited
States and/or other countries.•Othercompanyand/orproductnamesareregisteredtrademarkoftheirmanufactures.