Model Numbers QSGRJ-3P-XX* 3 zones, 120-240 V ~
QSGRJ-4P-XX* 4 zones, 120-240 V ~
QSGRJ-6P-XX* 6 zones, 120-240 V ~
QSGRJ-3P-1XX* 3 zones, 1 extra button column, 120-240 V ~
QSGRJ-3P-TXX* 3 zones, translucent cover, 120-240 V ~
QSGRJ-3P-1TXX* 3 zones, 1 extra button column, translucent cover, 120-240 V ~
QSGRJ-4P-1XX* 4 zones, 1 extra button column, 120-240 V ~
QSGRJ-4P-TXX* 4 zones, translucent cover, 120-240 V ~
QSGRJ-4P-1TXX* 4 zones, 1 extra button column, translucent cover, 120-240 V ~
QSGRJ-6P-1XX* 6 zones, 1 extra button column, 120-240 V ~
QSGRJ-6P-TXX* 6 zones, translucent cover, 120-240 V ~
QSGRJ-6P-1TXX* 6 zones, 1 extra button column, translucent cover, 120-240 V ~
QSGFP- Faceplate kit
* “XX” in the model number represents color/finish code. See Colors and Finishes at the end of document.
GRAFIK EyeR QS The GRAFIK EyeR QS controls up to six zones
of light. The GRAFIK EyeR QS will operate the following sources with a continuous Square Law dimming curve or on a full conduction non-dim basis:
•Incandescent
•TungstenHalogen
•ElectronicLow-Voltage(ELV)Switched
•MagneticLow-Voltage(MLV)Transformer
•MetalHalide/HighPressureSodiumSwitched
•Neon/ColdCathode
•LutronTu-WireR Electronic Fluorescent Dimming Ballasts
The GRAFIK EyeR QS can be configured for wired (QSlink)orwireless(RFlink)communication.
LUTRON
1
2
3
4
Off
Preset
Close
Open
GRAFIK EyeR QS
1 | Lutron® 24/7 Technical Support 800.523.9466
product specifications 10.28.11369-540a
www.lutron.com
Specifications
Model Numbers See previous page
Power 120 V~, 220–240 V~(nonCE),50/60Hz
Typical Power Consumption
7W,0PowerDrawUnits(PDUs).The GRAFIK EyeR QS is not powered from the link, Pin 2 should not be connected.TypicalPowerConsumptiontestconditions: all loads off, one button LED on.
Regulatory Approvals UL,CSA,FCC,IC,SCT,NOM,CEC(Title24)
Environment Ambientoperatingtemperature:32°Fto104°F(0°Cto40°C)Ambient operating humidity: 0-90% humidity, non-condensing. Indoor use only.
Communications Low-voltagetypeIECPELV/NECRClass2wiringconnectsGRAFIK EyeR QS to processor. EachHomeWorksR QS processor has two configurable links. GRAFIK EyeR QS communicates with the processor via the QS link or RF link.
ESD Protection Tested to withstand electrostatic discharge without damage ormemoryloss,inaccordancewithIEC801-2.
Surge Protection Tested to withstand surge voltages without damage or loss ofoperation,inaccordancewithIEEEC62.41-1991RecommendedPracticeonSurgeVoltagesinLow-VoltageACPowerCircuits.
Power Failure Provides10-yearpowerfailurememory:Automaticallyrestoreslighting to levels prior to power interruption.
Mounting Installsinastandard4-gangU.S.wallbox,3`in(89mm)deepis strongly recommended. Always allow at least 4`in(114mm)clearance above and below the control unit to provide adequate space for cooling.Wallplatesnapsonwithnovisiblemeansof attachment.
Line Voltage Wiring Eachlinevoltageterminalcanacceptone12AWG(4.0mm2)wire.
IEC PELV/NEC® Class 2 QS System Low-Voltage Wiring
Systemcommunicationuseslow-voltagewiring.Wiringcanbedaisy-chainedorT-tapped.Wiringmustberunseparatelyfrom line/mains voltage. IECPELV/NEC®Class2wiringlinkrequires:Two18AWG(0.75mm2)conductorsforcontrolpower.Onetwisted,shieldedpairof22AWG(0.34mm2)fordatalink.AvailablefromLutron,P/NGRX-CBL-346S;checkcompatibilityinyourarea.Totallengthofcontrollinkmustnotexceed2000ft(610m).
Warranty 8YearLimitedWarranty.http://www.lutron.com/resiinfo
Design Features• ContainsRTISSEquipped® technology to
compensate in real time for incoming line voltagevariations:Novisibleflickerwith+/-2% changeinRMSvoltage/cycleand+/-2% change in frequency/second.
• Buttonsareprogrammabletoselectsceneorroom preset levels or positions
• Wallplatesnapsonwithnovisiblemeansofattachment.
• Canbeconfiguredforwired(QSlink)orwireless(RFlink)communication.
2 | Lutron® 24/7 Technical Support 800.523.9466
product specifications 10.28.11369-540a
www.lutron.com
Dimensions Dimensionsshownas:in(mm)
Mounting
Standard 4-gang U.S.wallbox, 3.5in(89mm)deep
Mountingscrews(4)
GRAFIK Eye® QS control unit
Hinged bottom lid
Hingedtop lid
4$in(119mm)
94 in (239mm) 4in(10
mm) 2 in (51mm)
Front View Side View
Fitsintoa4-gangU.S.backbox,3.5in(89mm)deep;LutronP/N241400
3 | Lutron® 24/7 Technical Support 800.523.9466
product specifications 10.28.11369-540a
www.lutron.com
Load Capacity
Power and Load Wiring
12
AB
C
24 V
150
mA
P/N
500
-138
26 R
ev. A
8 mm
.3125 in
12
AB
C
24 V
150
mA
P/N
500
-138
26 R
ev. A
8 mm
.3125 in
To Load 1
To Load 3
To Load 5
To Load 2
To Load 4
To Load 6
DistributionPanel
LN : GroundN: NeutralL: Hot/Live
120 V~ 50/60 Hz 220 – 240 V~ 50/60 Hz
Unit Capacity (watts) 2000W 3000W
Magnetic Low-Voltage 2000VA/1600W 3000VA/2400W
Zone Capacity (watts) 25–800W 40–1200W
Magnetic Low-Voltage 25–800VA/25–600W 40–1200VA/40–960W
Load Type Notes• WhendimmingElectronicLow-Voltage(ELV)lighting,anELVinterface(suchasPHPM-PA-DV-WH)
must be used with the control unit. Before installing an ELV light source, verify with the manufacturer that their transformer can be dimmed.
• Whencontrolling0–10Vloads,aTenVoltInterface(GRX-TVI)mustbeusedwiththecontrolunit.• Notallzonesmustbeconnected;however,connected zones must have a minimum load as
specified above.• MaximumtotallightingloadforaMagneticLow-Voltage(MLV)variesbyinputvoltage
(specified above): — 120 V~:800VA/600W — 220–240 V~:1200VA/960W
• Nozonemaybeloadedwithmorethanthecapacityspecifiedabove.Forhigherwattageapplications,or for 277 V~ applications, use Lutron®powermodulePHPM-PA,PHPM-WBX,PHPM-PA-DV,PHPM-SW,orPHPM-WBX-DV.
4 | Lutron® 24/7 Technical Support 800.523.9466
product specifications 10.28.11369-540a
www.lutron.com
QS Link Wiring
To additional QS devices
Pin2doesnotgetconnectedtotheGRAFIKEyeR QS – it does not require link power
12
AB
C
24 V
150
mA
P/N
500
-138
26 R
ev. A
8 mm
.3125 in
IECPELV/NECRClass2controlwiring:18AWG(0.75mm2) HomeWorksR QS Link 2000ft(610m)maximumtotal wire length per run
Datalink:twisted,shieldedpair22AWG to18AWG(0.25mm2 to 0.75 mm2)
FromHomeWorksR QS processor
DO NOT CONNECT PIN 2
AddTest
Setup
WiredRF
Communication
Repeater Status1 3 42 P
Hybrid Repeater
Power Repeater LinkCO
M
24 V9 V
1
MU
X
MU
X
2 3 4
ActivateTestAddTest
Setup
WiredRF
Communication
Repeater Status1 3 42 P
Hybrid Repeater
Power Repeater LinkCO
M
24 V9 V
1
MU
X
MU
X
2 3 4
ActivateTestAddTest
Setup
WiredRF
Communication
Repeater Status1 3 42 P
Hybrid Repeater
Power Repeater LinkCO
M
24 V9 V
1
MU
X
MU
X
2 3 4
ActivateTest
Hybrid Repeater
RF Link
GRAFIK EyeR QSHomeWorksRQSHybridRepeater
30ft(9m) maximum
30ft(9m) maximum
60ft(18m) maximum
30ft(9m) maximum
HomeWorksR QS RF Link1000ft(305m)maximumwire length per run
HomeWorksR QS RF Link1000ft(305m)maximumwire length per run
GRAFIK EyeR QS GRAFIK EyeR QS
5 | Lutron® 24/7 Technical Support 800.523.9466
product specifications 10.28.11369-540a
www.lutron.com
Colors and FinishesArchitectural Matte Finishes (standard) Architectural Metal Finishes (Faceplate kit only)
White WH
Ivory IV
Almond AL
Light Almond LA
Beige BE
Gray GR
Brown BR
Black BL
• Duetoprintinglimitations,colorsandfinishesshown cannot be guaranteed to perfectly match actual product colors.
• Colorchipkeychainsareavailableformoreprecise color matching: ArchitecturalMatteFinishes-AM-CK-1 ArchitecturalMetalFinishes-AMTL-CK-1
Satin Brass SB
Antique Brass QB
ClearAnodizedAluminum CLA
Black Anodized Aluminum BLA
Brass Anodized Aluminum BRA
SatinNickel SN
Bright Brass BB
Antique Bronze QZ
BrightNickel BN
BrightChrome BC
SatinChrome SC
6 | Lutron® 24/7 Technical Support 800.523.9466
product specifications 10.28.11369-540a
www.lutron.com
Colors and Finishes (continued)
• Duetoprintinglimitations,colorsandfinishesshowncannotbeguaranteed to perfectly match actual product colors.
• Colorchipkeychainsareavailableformoreprecisecolormatching: SatinFinishes-SC-CK-1
Satin Finishes (Faceplate kit only)
Taupe TP
Turquoise TQ
Plum PL
Merlot MR
Terracotta TC
Sienna SI
Midnight MN
Hot HT
Desert Stone DS
Eggshell ES
Biscuit BI
Snow SW
Palladium PD
Greenbriar GB
Bluestone BG
MochaStone MS
Goldstone GS
Stone ST
Limestone LS
7 | Lutron® 24/7 Technical Support 800.523.9466
product specifications 10.28.11369-540a
www.lutron.com