HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANhttp://Global.MitsubishiElectric.com
GRAPHIC OPERATION TERMINAL
HIME-L066-A1310 (MEE) Printed in JapanNew publication, effective Oct. 2013
Specifications subject to change without notice.
Handy GOT lineup GT16 Light body including the latest GT16 functions
6.5 inch / VGA / 1.2kg
List of functions according to Handy GOT model
5.7 inch / QVGA / Approx. 0.79kg GT14 Standard model with advanced
features and communication interfaces
Powerful HMI control in the palm of your hands.
5.7 inch / QVGA / 1.0kg GT11 Portable 5.7 inch
operation terminal
STN 256 colorsSTN monochrome16 gray scales
TFT 65,536 colorsTFT monochrome16 gray scales
TFT 65,536 colors
New standard for 5.7 inch Handy GOT
High-end Handy model
Front sizeApprox.
24% smallerWeight
Approx. -0.21kg
Resolution and colors
FunctionalityNEW
Compact Connectivity
GRAPHIC OPERATION TERMINAL
Product SpecificationsSeries Model name Contents, Specifications
GT14 Handy GOT main unit
GT1455HS-QTBDE TFT 65,536 colors
GT1450HS-QMBDE TFT monochrome 16 gray scales
Emergency Stop Switch Guard Cover GT14H-50ESCOV Cover for preventing the emergency stop switch incorrect
operation
Protective sheet GT14H-50PSC Clear 5 sheets
Battery GT11-50BATBattery for clock data, alarm history, recipe data, time action setting value, advanced alarm, advanced recipe, logging, hard copy, and SRAM user area backups
Connection cable
External cable
GT14H-C30-42PFor connecting GOT and Connector conversion box. Connector conversion box: GT16H-CNB-42S
3 m
GT14H-C60-42P 6 m
GT14H-C100-42P 10 m
GT11H-C30-37P For connecting GOT and Connector conversion box, for connecting GOT and Relay cable. Connector conversion box: GT11H-CNB-37S, GT16H-CNB-37S Use C or later version.
3 m
GT11H-C60-37P 6 m
GT11H-C100-37P 10 m
GT11H-C30For connecting GOT and Relay cable. Use C or later version.
3 m
GT11H-C60 6 m
GT11H-C100 10 m
GT11H-C30-32P
For connecting GOT and CC-Link interface unit GT11H(S)-CCL.
3 m
GT11H-C50-32P 5 m
GT11H-C80-32P 8 m
GT11H-C130-32P 13 m
FA device connection relay cable
GT11H-C15R4-8P For FX PLC connection(PLC side MINI-DIN 8pin) Use C or later version. 1.5 m
GT11H-C15R4-25PFor A/QnA CPU/FX1, FX2, FX2C PLC connection(PLC side D-sub 25pin) Use C or later version.
1.5 m
GT11H-C15R2-6P For Q CPU connection(PLC side MINI-DIN 6pin) Use C or later version. 1.5 m
Connector conversion box
GT16H-CNB-42S Box for converting 42pin connectors into terminal blocks, D-Sub 9pin connectors, or Ethernet RJ-45 connectors
GT16H-CNB-37S Box for converting D-Sub 37pin connectors into terminal blocks or Ethernet RJ-45 connectors
GT11H-CNB-37S Box for converting D-Sub 37pin connectors into terminal blocks or D-Sub 9pin connectors
CC-Link Interface unitGT11HS-CCL
For connecting GOT and CC-Link.GT11H-CCL
SD CardL1MEM-2GBSD SD memory card 2GB
L1MEM-4GBSD SDHC memory card 4GB
Manual GT14HS-U-E GT14 Handy GOT User's Manual MODEL CODE: 09R825
• Windows is registered trademarks of Microsoft Corporation in the United States and other countries. • Ethernet is a trademark of Xerox Corporation in the United States. • VNC is a registered trademark of RealVNC Ltd. in the United States and other countries. • All other company names and product names used in this document are trademarks or registered trademarks of
their respective companies.
Registration Safety WarningTo ensure proper use of the products in this document, please be sure to read the instruction manual prior to use.
NEW NEW
Item
GT1
1 H
andy
GT1
4 H
andy
GT1
6 H
andy
Main unit functions
Boot OS installation P P P
Start from external memory Memory ― P P
OS installation P P P
Project data read/write P P P
Resource data read P P P
FA transparent function*1 P P P
Multi-channel function*2 ―P
Up to 2ch
PUp to 4ch
Gateway function OS ― P P
SoftGOT-GOT link function ― ― P
File transfer function (FTP client) ― P P
Screen design
Specifications
Base screen, window screen P P P
Super-impose window P P P
Overlap window P P P
Dialog window display P P P
Graphic drawing
BMP image display P P P
JPEG image display ― P P
DXF data P P P
IGES data P P P
Fonts
Standard fonts (basic) *3 P P P
Standard fonts (optional) * 4 OS ― P P
High-quality font P P P
TrueType font, TrueType font (7 segments) P P P
Windows® font P P P
Stroke basic font (extended) OS ― P P
Logo character function P P P
Common settings
Parts (object + figure) layer function P P P
Screen change P P P
Station No. switching ― P P
Multilingual support function P P P
Password P P P
System information P P P
Peripheral unit setting P P P
Boot logo P P P
Comment registration P P P
Part registration P P P
Data operation function P P P
Offset function P P P
Security functionSecurity level authentication P P P
Operator authentication ― P P
*1 : Only user alarms can be used.
*2 : Multi-channel possible only with Ethernet connections
*3 : Japanese, Japanese (supporting European languages), Chinese (Simplified), Chinese (Simplified, supporting European languages), Chinese (Traditional, supporting European languages)
*4 : Chinese (Simplified), Chinese (Traditional), Japanese
*5 : Used together with logging function
*6 : GT14 Handy and GT16 Handy have "advanced alarm monitoring/display"
*7 : Battery is required.
OS Extended function/Option OS required Memory The external memory required (varies according to model.)
Item
GT1
1 H
andy
GT1
4 H
andy
GT1
6 H
andy
Common settings
Object settings
Lamp display P P P
Touch switch P P P
Numeric display/input P P P
Data list display P P P
Historical data list display*5 OS ― P P
ASCII display/input P P P
Kana-Kanji conversion function(Enhanced version) OS ― P P
Clock display P P P
Comment display P P P
Extended alarm monitoring/display( Memory ) ― P P
Alarm display P P P
Alarm history display( Memory ) P P P
Floating alarm display*6 P ― ―
Parts display P P P
Parts movement P P P
Panel meter display P P P
Level display P P P
Trend graph P P P
Historical trend graph*5 OS ― P P
Line graph P P P
Bar graph P P P
Statistical graph P P P
Scatter graph P P P
Status observation function P P P
Advanced recipe function OS ― P P
Recipe function OS P P P
Time action function P P P
Others
Hardcopy functionOS Memory
File saving in CF card ― P P
Printing on printer ― ― ―
GOT remote access function (VNC® server function setting) ― P P
Screen call function P P P
Operation log function OS ― ― P
Document display function OS ― ― P
Logging function OS ( Memory ) ― P P
Script function OSProject script/Screen script P P P
Object script ― P P
Device data transfer function OS ― P P
Maintenance functions
System monitor function OS P P P
List editor for A OS P P P
List editor for FX OS P P P
SFC monitor function OS ― ― P
Ladder monitor function OS ― ― P
Intelligent unit monitor function OS ― ― P
Q motion monitor function OS ― ― P
Servo amplifier monitor function OS ― ― P
Network monitor function OS ― ― P
Backup/restoration function OS Memory ― P P
Maintenance time notification function*7 ― ― P
Performance Specifications
ItemSpecifications
GT1455HS-QTBDE GT1450HS-QMBDE
Displaysection
Type TFT color liquid crystal display TFT monochrome (black/white) liquid crystal display
Screen size 5.7 inchResolution 320 × 240 [dots]Display size 115 (W) × 86 (H) [mm]
Display character16-dot standard font: 20 characters × 15 lines12-dot standard font: 26 characters × 20 lines
Display color 65,536 colors Monochrome 16 gray scalesDisplay angle Left/Right: 80 degrees, Top: 80 degrees, Bottom: 60 degreesIntensity of LCD only 400 [cd/m2] 8-level adjustment 230 [cd/m2] 8-level adjustmentLife Approx. 50,000h. (Time for contrast to become 1/5 at operating ambient temperature of 25ºC )
Backlight LED type Backlight off/screen saving time can be set.
Life Approx. 70,000h or longer. (Time for display intensity to reach 50% at operating ambient temperature of 25ºC )
Touch panel
Type Analog resistive filmKey size Minimum 2 × 2 dots (per key)Number of points touched simultaneously Simultaneous presses not allowed. (Only 1 point can be touched.)
Life 1 million times (operating force 0.98N max.)
MemoryC drive Flash memory (Internal), 9Mbytes (for storing project data)
Life (Number of write times): 100,000 timesD drive SRAM (internal), 512Kbytes (battery backup)
Battery
GT11-50BAT lithium battery
Backup target Clock data, alarm history, recipe data, time action setting value, advanced alarm, advanced recipe, logging, hard copy and SRAM user area
Life Approx. 5 years (Operating ambient temperature of 25ºC )
Built-ininterface
RS-232RS-422
RS-232, RS-422/485, 1ch each Transmission speed: 115200/57600/38400/19200/9600/4800bpsConnector shape: Round type 32pins (Male)Application: For communicating with a controllerTerminating resistor: 330Ω (Fixed)
EthernetData transfer method: 100BASE-TX, 10BASE-T, 1chConnector shape: Round type 32pins (Male)Application: For communicating with a controller, or using the gateway function, connecting a PC (project data upload/download, OS installation, FA transparent function)
USB
Host USB(Full Speed 12Mbps), Host, 1ch Connector shape: TYPE-AApplication: Data transfer, data storage
DeviceUSB(Full Speed 12Mbps), device 1ch Connector shape: Mini-BApplication: For connecting a personal computer (Project data upload/download, OS installation, FA transparent function )
SD card SD standard, 1ch Supported memory card: SDHC memory card, SD memory cardApplication: For uploading/downloading project data, OS installation, storing logging data
Switch
Operation switch 6 switches (6 contacts/common) N/O contact, Maximum rating 10mA/24V DC, Life: 1,000,000 times
Grip switch1 switch (single wiring) (IDEC HE3B-M2PB)Enable switch (deadman switch) 3-position system of OFF↔ON↔OFF2 N/O contacts Maximum rating 1A/24V DC (resistance load),Maximum rating 0.3A/24V DC (induction load), Life: 100,000 times
Emergency stop switch
1 switch (single wiring) (IDEC XA1E-BV303R)3 N/C contacts Maximum rating 1A/24V DC (resistance load),Maximum rating 0.3A/24V DC (induction load), Life: 100,000 times
Keylock switch(2-position switch)
1 switch (single wiring) (IDEC AS6M-2KT1PB)2-notch type (Manual stop at each position/A key can be inserted and removed on only the left side./On the right side, a key cannot be removed./Two keys are provided.)2-position, Maximum rating 1A/24V DC (resistance load),Maximum rating 0.3A/24V DC (induction load), Life: 100,000 times
SD card access switch
Prohibits accessing the SD card when removing the card from the GOT.ON: SD card being accessed (SD card removal prohibited)OFF: SD card not accessed (SD card removal possible)
Buzzer output Single tone (tone length adjustable)Protective structure IP65f (valid when the external cable is connected, except for the connector conversion box side)Weight Approx. 0.79kg (GT14 Handy main unit only)Compatible software package GT Designer3 ver. 1.71Z or later
External DimensionsPower Supply Specifications
ItemSpecifications
GT1455HS-QTBDE GT1450HS-QMBDEInput power supply voltage 24V DC(+10% -15%)Power consumption 8.4W or less (350mA/24V DC) 7.5W or less (310mA/24V DC)
Backlight off 7.0W or less (290mA/24V DC)Inrush current 30A or less (maximum load) 2msPermissible instantaneouspower failure time Within 5ms
Unit: mm (inch)
• Actual screen may appear different from this leaflet.
Compact Connectivity
Connector conversion boxGT11H-CNB-37S
HUB
Connector conversion boxGT16H-CNB-37S
1. Serial communication connection 2. Ethernet communication connection
System con�guration examples
Making Ethernet connection
External connection cable External connection cable
Flexibly adapts to the communications used in your system. (Refer to the connection diagram above for external connection cable.)
Ethernet
or
RS-232or
RS-422
Connector conversion boxGT16H-CNB-42S
GT16H-CNB-42S*
Connector conversion boxes (option)
Ethernet communication connection
External connection cables for GT16 H-CNB-42S connection
Serial communication connection High-performance type
GT14H-C30-42P (3m)GT14H-C60-42P (6m)GT14H-C100-42P (10m)
*: Required for Ethernet connection.
GT11H-CNB-37S
GT16H-CNB-37S*
NEW
NEW
The three-position (OFF-ON-OFF) type deadman switch is adopted as an interlock for preventing operation mistakes and prohibiting operation of a machine. The switch can directly control external equipment to give immediate stop commands to a machine.
Grip switch
Interlock is reset when the switch is pressed or released.
release release
OFF−ON−OFF
This switch immediately activates a connected safety device. A “normally-closed contact” is adopted to assure safety. In addition, the switch guard cover is o�ered as an optional attachment to prevent accidental operation.
Emergency stop switch
This interface supports the FA transparent function to connect a cable from a personal computer without opening the unit or panel. This interface can then connect the PC transparently to a Mitsubishi programmable controller, inverter, servo unit, or robot.
USB interface (device)
SD card slot
USB deviceUSB host
One screen design program to �t all your GOT1000 needs
GT Works3MELSOFT
Handy GOT feature comparison
Screen size Display color Touch panel Ethernet Memory Memory card Handle anglechange
Dimensions(Weight)
*2
*3
5.7 inch QVGA 320×240 dots
Analog touchpanel
1ch*1
USB hostUSB device 9MB SD card — 185×145mm
(Approx. 0.79kg)
TFT 65,536 colorsTFT monochrome
16 gray scales
RS-422RS-232
*3
Serial communicationUSB
GT14Handy GOT
GT16Handy GOT
5.7 inch QVGA 320×240 dots
Matrix touchpanel — USB device 3MB CF card — 209×168mm
(1.0kg)
STN 256 colorsSTN monochrome
16 gray scales
RS-422RS-232GT11
Handy GOT
6.5 inch VGA 640×480 dots
Analog touchpanel 1ch USB host
USB device 15MB CF card 230×201mm(1.2kg)
TFT65,536 colors
RS-422/485RS-232
Many options for connection con�guration. Choose one that best �ts your needs.
NEW
*1: Cable ver. C or later.
*2: Connection for FX PLC(PLC side connector MINI-DIN 8pin).*3: Connection for A/QnA CPU/FX1,FX2,FX2C(PLC side connector D-Sub 25pin).
*4: Connection for Q CPU(PLC side connector MINI-DIN 6pin).
Logging - Collect data from connected devices
Collect data from connected FA devices, including useful data analysis and feedback, and take the data back to the o�ce.
Data collection
PLC
Temperaturecontroller GT14 Handy
Of f iceFactory
Backup/restore - For ease of use and peace of mind
Back up PLC program and parameters to external memoryvia GT14 Handy.Restore the backup for immediate recovery.
Restore
Backup
GT14 Handy
PLC
Replacement from older model
When replacing the older model (GT11), use the appropriate cable for your combination of GT14 Handy and connector conversion box.Please refer to the manual for details.
Connection example of peripheral devices
·GT Works 3·GX Works 2(FA transparent)
USBUSB
SD card
USB memory
GT14 Handy
Computer
PLC
Approx.
0.79kg
Base machine weight
3DGrip design
Ergonomic
IP65f
Environmental protection
Hand strap
USB host
USB device
GT14 Handy GOT FA equipment connection cables (option)
NEW
GT14 Handy
Connector conversion box
GT11Handy
Analog touch panelEthernet built inTFT LCD
65,536 colorsmonochrome 16 gray scales
USB hostUSB device
LED backlightSD card slot
GT1455HS-QTBDE GT1450HS-QMBDETFT 65, 536 colors
TFT monochrome16 gray scales
•The maximum Ethernet communication distance is 100m in total length.
•The maximum connection distance between the connector conversion box and the GOT is 10m.
•Up to two types of equipment can be connected.
- Supports ID recognition- Internal contact prevents system from entering
emergency stop state when removing the Handy GOT
[ ]: 30(3m), 60(6m), 100(10m)
GT11H-C[ ]-37P*1External connection cable PLC connection cable
RS-232·RS-422/485Connector conversion box
GT11H-CNB-37S
Serial communication
RS-232(max. length 6m), RS-422(max. length 13.5m),Ethernet (between GOT and HUB 100m),
and CC-Link (max. length 1213m)
[ ]: 30(3m), 60(6m), 100(10m)
GT11H-C[ ] *1External connection cable
[ ]: 30(3m), 60(6m), 100(10m) Each cable: 1.5m
GT11H-C[ ]-37P*1 GT11H-C15R4-8P*1*2 GT11H-C15R4-25P*1*3 GT11H-C15R2-6P*1*4External connection cable Relay cable
Serial communication
GT14H-C[ ]-42P
[ ]: 30(3m), 60(6m), 100(10m)
External connection cableNEWConnector conversion box
GT16H-CNB-42SID recognition supported
Ethernet
GT11H-C[ ]-37P*1
[ ]: 30(3m), 60(6m), 100(10m)
External connection cableConnector conversion box
GT16H-CNB-37S
Ethernet
Ethernet
[ ]: 30(3m), 50(5m), 80(8m), 130(13m)
GT11H-C[ ]-32PExternal connection cable
CC-link interface unit
GT11H(S)-CCL
CC-Link
PLC connection cable
FX series
L series
Other
FA equipment
Q seriesGT1455HS-QTBDEGT1450HS-QMBDEGT1455HS-QTBDEGT1450HS-QMBDE
GT14Handy GOT
NEW
High functionality and connectivity combined
in a compact and lightweight body.
Only in the GT14 Handy GOT.
SD card slot
Hook
Grip
*5
*4
*4
*8
*7
*6·RS-422/232·Ethernet
*1 : Concurrent Ethernet and serial communication not possible. : Concurrent RS-422/485 and RS-232 communication not possible. : Concurrent RS-422 and RS-232 communication not possible. *4
*6 *5
*7 *8: Store OS, project data, alarm history, recipe, logging, backup data. : Connector conversion box or relay cable required for serial communication.: Connector conversion box required for Ethernet connection. : SD card or USB memory required. : USB memory or SD card
*2 *3
USB memory
SD CARD