Why energy is important? Increased computing demand  Data centers are rapidly growing  Consume 10 to 100 times more energy per square foot than a typical office building Energy cost dynamics  Energy accounts for 10% of data center operational expenses (OPEX) and can rise to 50% in the next few years  Accompanying cooling system costs $2-$5 million per year April 16, Dzmitry Kliazovich
20
GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010
Transcript
Page 1: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

GreenCloud:A Packet-level Simulator of

Energy-aware Cloud Computing Data Centers

Dzmitry Kliazovich

ERCIM FellowUniversity of Luxembourg

Apr 16, 2010

Page 2: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Outline Data center architectures

Two-tier, three-tier, and three-tier high-speed

Structure of data center simulator Energy efficiency, simulator components

Case study data center simulations

April 16, 2010 2Dzmitry Kliazovich ([email protected])

Page 3: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Why energy is important? Increased computing demand

Data centers are rapidly growing Consume 10 to 100 times more energy per square foot than a

typical office building

Energy cost dynamics Energy accounts for 10% of data center operational expenses

(OPEX) and can rise to 50% in the next few years Accompanying cooling system costs $2-$5 million per year

April 16, 2010 3Dzmitry Kliazovich ([email protected])

Page 4: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Distribution of data center energy consumption

April 16, 2010 4Dzmitry Kliazovich ([email protected])

Page 5: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Data center architectures Two-tier data center architecture

Access and Core layers 1 GE and 10 GE links Full mesh core network Load balancing using ICMP

April 16, 2010 5Dzmitry Kliazovich ([email protected])

Page 6: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Data center architectures Three-tier data center architecture

Access, Aggregation, and Core layers Scales to over 10,000 servers 8-way ECMP load balancing

April 16, 2010

S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

CoreNetwork

AggregationNetwork

AccessNetwork

S

Links10 GE 1 GE

Nodes

L3 Switch L2/L3 Rack Switch Computing Server

6Dzmitry Kliazovich ([email protected])

Page 7: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Data center architectures Three-tier High-Speed data center architecture

Increased core network bandwidth 2-way ECMP load balancing 100 GE standard (IEEE 802.3ba) still in works since Nov 2007

April 16, 2010

S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

CoreNetwork

AggregationNetwork

AccessNetwork

S

Links10 GE 1 GE

Nodes

L3 Switch L2/L3 Rack Switch Computing Server100 GE

7Dzmitry Kliazovich ([email protected])

Page 8: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Data center simulator Greencloud is an extension of NS-2 network

simulator for energy-aware cloud computing simulations

Provides packet-level simulation dynamics

Focused on workload distribution strategies and energy consumption models of simulator components (servers, switches, links, etc.)

Dzmitry Kliazovich ([email protected]) 8April 16, 2010

Page 9: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Data center simulator

Dzmitry Kliazovich ([email protected]) 9April 16, 2010

CoreNetwork

AggregationNetwork

AccessNetwork

Computing Server

1 RU Rack Switch

L3 Switch

TaskSchedulerTask

Scheduler

Links10 GE 1 GE

WorkloadGenerator

CloudUserCloud

User

Data Center

Data CenterCharacteristics

TaskScheduler

TaskComAgent

L3 Energymodel

L2 Energymodel

ServerCharacteristics

TaskComSink

Connect ()

SchedulerServerEnergy model

S S S S S S S S S

WorkloadTrace File

Page 10: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Simulator components Servers

Responsible for task execution Single-core nodes Preset processing limit in MIPS or FLOPS

Supported power management modes DVFS:Dynamic Voltage/Frequency Scaling DNS: Dynamic Shutdown Both: DNS if server is idle, DVFS otherwise

Dzmitry Kliazovich ([email protected]) 10April 16, 2010

Page 11: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Simulator components Servers’ Energy Model

Dzmitry Kliazovich ([email protected]) 11April 16, 2010

Fmin

Fmax

0

0.2

0.4

0.6

0.8

1

Pfixed

Ppeak

CPU FrequencyServer load

Pow

er c

onsu

mpt

ion

CPUmemory modules, disks, I/O resources

Idle server consumes about 66% of the peak load for all CPU frequencies

Page 12: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Simulator components Switches

Most common Top-of-Rack (ToR) switches typically operate at Layer-2 interconnecting gigabit links in the access network

Aggregation and core networks host Layer-3 switches operating at 10 GE (or 100 GE)

Links Transceivers’ power consumption depends on the quality of signal

transmission in cables and is proportional to their cost 1 GE links: 0.4W is consumed for 100 meter transmissions over twisted

pair 10 GE links: 1W is consumed for 300 meter transmission over optical fiber

Supported power management modes DVFS, DNS, or both

Dzmitry Kliazovich ([email protected]) 12April 16, 2010

Page 13: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Simulator components Switches’ Energy Model

Dzmitry Kliazovich ([email protected]) 13April 16, 2010

Chassis~ 36%

Linecards~ 53%

Port transceivers~ 11%

Page 14: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Simulator components Workloads

Model cloud user applications (social networking, instant messaging, content distribution, etc.)

Workload properties Computational: MIPS, duration Communicational: workload size, its internal and

external transfers

Generation Trace-driven Using random distribution (Exp, Pareto, etc.)

Dzmitry Kliazovich ([email protected]) 14April 16, 2010

Page 15: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Simulation Setup Data center architectures

Two-tier (2T), three-tier (3T), and three-tier high-speed (3Ths)

Simulation parameters Average data center load is 30% 1536 computing servers 1, 10, and 100 GE links with 10 ns delay 4500 bytes workloads (3 Ethernet packets) 60 minutes of simulation time

Dzmitry Kliazovich ([email protected]) 15April 16, 2010

Page 16: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Simulation Setup Energy-aware “green” scheduler

Dzmitry Kliazovich ([email protected]) 16April 16, 2010

0 200 400 600 800 1000 1200 1400 1600

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Server #

Ser

ver l

oad

Servers at the peak load

Under-loaded servers,DVFS can be applied

Idle servers,DNS can be applied

Page 17: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Evaluation results Distribution of energy consumption in data center

Dzmitry Kliazovich ([email protected]) 17April 16, 2010

Servers355kW·h (82%)

Core switches0.87kW·h (0.2%)

Aggregation switches1.74kW·h (0.4%)

Access switches75.6kW·h (17.4%)

Data center433kW·h

Chassis36%

Linecards53%

Port tranceivers

11%

Switches

CPU130W (43%)

Memory36W (12%)

Disks12W (4%)

Peripherial50W (17%)

Motherboard

25W (8%)

Other48W (16%)

Computing Servers301 W

Page 18: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Evaluation results Comparison of energy-efficiency schemes

Dzmitry Kliazovich ([email protected]) 18April 16, 2010

Page 19: GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers Dzmitry Kliazovich ERCIM Fellow University of Luxembourg Apr 16, 2010.

Conclusions Energy consumption is becoming a concern in cloud computing

data centers

Developed a packet-level simulator for energy-aware data centers

Obtained results compare the performance of dynamic voltage/frequency scaling (DVFS) and dynamic server/network shutdown (DNS) schemes

Future work will focus on adding storage area network as well as on the development of novel workload consolidation and traffic aggregation techniques

Dzmitry Kliazovich ([email protected]) 19April 16, 2010