+ All Categories
Home > Documents > Grid Integration of offshore wind farms using a Hybrid ...€¦ · ratio (SCR) of 2.5. At the LCC...

Grid Integration of offshore wind farms using a Hybrid ...€¦ · ratio (SCR) of 2.5. At the LCC...

Date post: 19-Apr-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
1
Grid Integration of offshore wind farms using a Hybrid HVDC composed by an MMC with an LCC-based HVDC system Raymundo Enrique Torres-Olguin* & Alejandro Garces+ SINTEF Energy Research* & Universidad Tecnológica de Pereira+ Objective This paper presents a hybrid HVDC-transmission system composed by a Full- Bridge Modular Multilevel Converter (FB-MMC) and a Line-commutated Con- verter (LCC) to integrate offshore wind farms into the main grid. The operational characteristics of a three-terminal hybrid-HVDC system, two LCC stations and one MMC station, is investigated using PSCAD/EMTDC. Introduction In recent literature, the feasibility of grid integration of offshore wind farms using hybrid HVDC systems composed by voltage source converters (VSC) and line- commutated converters (LCC), have been investigated. Such a hybrid HVDC sys- tems are attractive mainly because their low power losses compared to a VSC-based HVDC systems. However, hybrid HVDC systems have serious limitations when an ac fault occurs at the LCC inverter. System description The proposed configuration is shown in Fig. 1. It consists of two ac grids (AC1 and AC2) interconnected by a bipolar HVDC system with 12-pulse line-commutated converters. This HVDC transmission line is interconnected to an FB-MMC by means of a T-connection. This FB-MMC integrates offshore resources along the transmission line. Figure: Proposed Hybrid HVDC for integration of OWF. Proposed control design The design of the controllers is divided into four sections: the LCC rectifier, the LCC inverter, the MMC, and the offshore wind farm. The LCC rectifier regulates the power extracted from one grid to another. In normal operation, the LCC rectifier operates in a constant DC current mode. The LCC inverter control objective is to regulate the DC link voltage. As power control is performed by the wind turbines, the main responsibility of the MMC is to establish the offshore ac voltage. Generally, a commutation failure (CF) occurs in LCC inverters when there is a significant voltage drop on the ac side. FB-MMC topologies can clear dc fault currents since they are build using full-bridge sub-modules which are able of suppressing the fault current against dc faults as shown as follows. S1 S2 S3 D1 D2 S4 D3 D4 Figure: Full bridge MMC DC fault response Simulation Results The simulations were conducted under different conditions to investigate the op- erating characteristics of the proposed system. These conditions include start-up procedure, and ac and dc faults. 0 0.5 1 1.5 2 -0.5 0.0 0.5 1.0 voltage rms [p.u.] (a) 0 0.5 1 1.5 2 -0.5 0.0 0.5 1.0 1.5 active power [p.u.] (b) 0 0.5 1 1.5 2 -0.5 0.0 0.5 1.0 1.5 dc current [p.u.] (c) 0 0.5 1 1.5 2 -0.5 0.0 0.5 1.0 1.5 dc voltage [p.u.] (d) LCC rectifier LCC inverter MMC (a) Start-up process 10 20 30 40 -0.5 0.0 0.5 1.0 voltage rms [p.u.] (a) 10 20 30 40 -0.5 0.0 0.5 1.0 1.5 active power [p.u.] (b) 10 20 30 40 -0.5 0.0 0.5 1.0 1.5 dc current [p.u.] (c) 10 20 30 40 -0.5 0.0 0.5 1.0 1.5 time(s) dc voltage [p.u.] (d) LCC rectifier LCC inverter MMC (b) Response to the wind condition 2.4 2.5 2.6 2.7 2.8 2.9 3 -0.5 0.0 0.5 1.0 voltage rms [p.u.] (a) 2.4 2.5 2.6 2.7 2.8 2.9 3 -0.5 0.0 0.5 1.0 1.5 active power [p.u.] (b) 2.4 2.5 2.6 2.7 2.8 2.9 3 0.0 1.0 2.0 dc current [p.u.] (c) 2.4 2.5 2.6 2.7 2.8 2.9 3 -0.5 0.0 0.5 1.0 1.5 dc voltage [p.u.] (d) LCC rectifier LCC inverter MMC (c) Response to ac fault (inverter side) 2.4 2.5 2.6 2.7 2.8 2.9 3 -0.5 0.0 0.5 1.0 voltage rms [p.u.] (a) 2.4 2.5 2.6 2.7 2.8 2.9 3 -0.5 0.0 0.5 1.0 1.5 active power [p.u.] (b) 2.4 2.5 2.6 2.7 2.8 2.9 3 0.0 1.0 2.0 dc current [p.u.] (c) 2.4 2.5 2.6 2.7 2.8 2.9 3 -0.5 0.0 0.5 1.0 1.5 dc voltage [p.u.] (d) LCC rectifier LCC inverter MMC (d) Response to dc fault Figure: [Top to bottom] (a) ac voltages (rms), (b) dc currents, (c) active powers, (d) dc voltages Conclusions AC fault is a very serious condition in a hybrid configuration because the commutation failure in line-commutated converters is translated into a dc fault in the voltage source converters. Full bridge MMC can provide a solution to this problem since they provide an available current path through the series connected capacitors of each MMC sub-modules. Contact email: [email protected]
Transcript
Page 1: Grid Integration of offshore wind farms using a Hybrid ...€¦ · ratio (SCR) of 2.5. At the LCC inverter side, the ac voltage is 230 kV at 50 Hz with SCR of 2.5. FB-MMC is connected

Grid Integration of offshore wind farmsusing a Hybrid HVDC composed by anMMC with an LCC-based HVDC system

Raymundo Enrique Torres-Olguin* & Alejandro Garces+SINTEF Energy Research* & Universidad Tecnológica de Pereira+

Objective

This paper presents a hybrid HVDC-transmission system composed by a Full-Bridge Modular Multilevel Converter (FB-MMC) and a Line-commutated Con-verter (LCC) to integrate offshore wind farms into the main grid. The operationalcharacteristics of a three-terminal hybrid-HVDC system, two LCC stations andone MMC station, is investigated using PSCAD/EMTDC.

Introduction

In recent literature, the feasibility of grid integration of offshore wind farms usinghybrid HVDC systems composed by voltage source converters (VSC) and line-commutated converters (LCC), have been investigated. Such a hybrid HVDC sys-tems are attractive mainly because their low power losses compared to a VSC-basedHVDC systems. However, hybrid HVDC systems have serious limitations when anac fault occurs at the LCC inverter.

System description

The proposed configuration is shown in Fig. 1. It consists of two ac grids (AC1 andAC2) interconnected by a bipolar HVDC system with 12-pulse line-commutatedconverters. This HVDC transmission line is interconnected to an FB-MMC bymeans of a T-connection. This FB-MMC integrates offshore resources along thetransmission line.

Figure: Proposed Hybrid HVDC for integration of OWF.

Proposed control design

The design of the controllers is divided into four sections: the LCC rectifier, theLCC inverter, the MMC, and the offshore wind farm.•The LCC rectifier regulates the power extracted from one grid to another. Innormal operation, the LCC rectifier operates in a constant DC current mode.

•The LCC inverter control objective is to regulate the DC link voltage.•As power control is performed by the wind turbines, the main responsibility ofthe MMC is to establish the offshore ac voltage.

•Generally, a commutation failure (CF) occurs in LCC inverters when there isa significant voltage drop on the ac side. FB-MMC topologies can clear dcfault currents since they are build using full-bridge sub-modules which areable of suppressing the fault current against dc faults as shown as follows.

S1

S2

S3D1

D2 S4

D3

D4

Figure: Full bridge MMC DC fault response

Simulation Results

The simulations were conducted under different conditions to investigate the op-erating characteristics of the proposed system. These conditions include start-upprocedure, and ac and dc faults.

IEEE TRANSACTIONS ON POWER DELIVERY 5

IV. Numerical results

The HVDC system, shown in Fig. 1, has been implementedusing PSCAD/EMTDC to illustrate its performance of theproposed topology. The system, which is rated at 1000 MWand 500 kV, is composed of two 12-pulse LCCs connectedthrough a long DC cable of 100 km. At the LCC rectifierside, the ac voltage is 345 kV at 50 Hz with a short circuitratio (SCR) of 2.5. At the LCC inverter side, the ac voltageis 230 kV at 50 Hz with SCR of 2.5. FB-MMC is connectedvia a 100 km DC cable at the midpoint of the other cable.The simulations were conducted under different conditionsto investigate the operating characteristics of the proposedsystem. These conditions include start-up procedure, and acfaults.

A. Start-up

Fig. 8 presents the start-up process which was explainedabove. First, all converter are disabled until t = 0.04 s. Att = 0.4 s, the LCC converters are enabled, the voltage atthe dc link ramps up since is regulated by the LCC inverteras shown in Fig. 8 (d). The holding current is provided bythe LCC rectifier as shown in Fig. 8 (c). At t = 0.3 s, TheFB-MCC is enabled. So, ac voltage ramps up to the nominalvalue as shown in Fig. 8 (a). Once the ac voltage reaches thenominal value is possible to connect the wind turbines. At t =1.0 s, each turbine is de-blocked allowing the synchronizationwith the recent imposing ac voltage. The power from windturbines changes slowly using a ramp function in order toavoid oscillations in the dc voltage as is shown in Fig. 8 (b).Fig. 8 shows that as the dc current coming from the turbineincreases the dc rectifier current decreases.

B. Response to Change in the Wind Speed

In order to investigate the response of the hybrid HVDCsystem to change in the wind speed, the emulated wind farmis tested in various conditions as shown in Fig. 9. At thebeginning, from t = 0 s to t = 15 s, there is a low windconditions, i.e. vw = 10 m/s. After t = 10 s, a ramp beginsthat increases vw at a rate of 4 m/s during 30 s. At t = 15s, a wind speed gust occurs which decreases vw amplitude3 m/s with 10 s duration. Finally, the wind speed is set atvw = 15 m/s which represents a high wind conditions [13].The nominal wind speed is considered as 12 m/s. During allthe simulations the wind is quite noisy. Noise wind data arethe following: number of noise component 250, random seednumber 50, time interval for random generation 0.35 s andnoise amplitude controlling parameter 10 rad/s [17].

Fig. 10 shows the response to the wind condition describedabove in Fig 9. Fig. 10(a) presents the rms voltage at theLCC rectifier, the LCC inverter, and the MMC, respectively.All ac voltages are maintained at their nominal values duringwind fluctuation as was expected. Fig. 10(b) shows the activepower at the LCC rectifier, at the LCC inverter and theMMC, respectively. It can be seen the power fluctuation causedby the wind in the active power at MMC. Note also thatthe power delivered by the LCC rectifier is complementary

0 0.5 1 1.5 2−0.5

0.0

0.5

1.0

volta

germ

s[p

.u.]

(a)

0 0.5 1 1.5 2−0.5

0.0

0.5

1.0

1.5

activ

epo

wer

[p.u

.]

(b)

0 0.5 1 1.5 2−0.5

0.0

0.5

1.0

1.5dc

curr

ent

[p.u

.](c)

0 0.5 1 1.5 2−0.5

0.0

0.5

1.0

1.5

dcvo

ltage

[p.u

.]

(d)

LCC rectifier LCC inverter MMC

Fig. 8. Start-up of the MMC-LCC hybrid HVDC system. (a) ac voltages(rms), (b) dc currents, (c) active powers, (d) dc voltages

10 20 30 400.0

5.0

10.0

15.0

20.0

time(s)

win

dsp

eed

[m/s

]

Fig. 9. Start-up of the MMC-LCC hybrid HVDC system. (a) ac voltages(rms), (b) dc currents, (c) active powers, (d) dc voltages

(a) Start-up process

IEEE TRANSACTIONS ON POWER DELIVERY 6

10 20 30 40−0.5

0.0

0.5

1.0

volta

germ

s[p

.u.]

(a)

10 20 30 40−0.5

0.0

0.5

1.0

1.5

activ

epo

wer

[p.u

.]

(b)

10 20 30 40−0.5

0.0

0.5

1.0

1.5

dccu

rren

t[p

.u.]

(c)

10 20 30 40−0.5

0.0

0.5

1.0

1.5

time(s)

dcvo

ltage

[p.u

.]

(d)

LCC rectifier LCC inverter MMC

Fig. 10. Start-up of the MMC-LCC hybrid HVDC system. (a) ac voltages(rms), (b) dc currents, (c) active powers, (d) dc voltages

with the power from MMC in order to deliver the ratedpower at LCC inverter. Fig. 10(d) displays the dc voltagesat the terminals of LCC rectifier, LCC inverter and MMC,respectively. dc voltages are regulated satisfactorily to theirreferences. Fig. 10(b) gives the dc currents at the LCC rectifier,the LCC inverter, and the MMC, respectively. It can be seenthe complementarity between the dc current in the MMC andthe LCC rectifier.

C. AC faults

Fig. 11 illustrates the performance of the system duringsingle-phase-to-ground fault. The fault was applied on the acside of the LCC inverter at 2.5 s and was cleared after 100 ms.Fig. 11(a) shows that the rms voltage at the LCC inverterdrops about 0.3 pu during the fault. As a result, a commutation

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0

volta

germ

s[p

.u.]

(a)

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0

1.5

activ

epo

wer

[p.u

.]

(b)

2.4 2.5 2.6 2.7 2.8 2.9 3

0.0

1.0

2.0

dccu

rren

t[p

.u.]

(c)

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0

1.5

dcvo

ltage

[p.u

.]

(d)

LCC rectifier LCC inverter MMC

Fig. 11. System response during single-phase to ground fault at LCC inverter.(a) ac voltages (rms), (b) dc currents, (c) active powers, (d) dc voltages

failure occurs that causes an abrupt decrease in the dc voltageas shown in Fig. 11(d). This condition causes that the dccurrents rise rapidly as shown in Fig. 11(c). During the fault,all IGBTs in FB-MMC are blocked, so there is available onecurrent path through the series connected capacitors of theMMC submodules. Consequently, the current is limited andthe hybrid HVDC is able to recover after the fault is clear asshown in Fig. 11.

D. DC faults

Fig. 12 illustrates the performance of the system duringpole-to-ground dc fault. The fault was applied at the midpointbetween line commuted converter at 2.5 s and was clearedafter 100 ms. Fig. 12(a) shows that the rms voltage at theMMC drops to zero during the fault. This happens because

(b) Response to the wind conditionIEEE TRANSACTIONS ON POWER DELIVERY 6

10 20 30 40−0.5

0.0

0.5

1.0

volta

germ

s[p

.u.]

(a)

10 20 30 40−0.5

0.0

0.5

1.0

1.5

activ

epo

wer

[p.u

.]

(b)

10 20 30 40−0.5

0.0

0.5

1.0

1.5

dccu

rren

t[p

.u.]

(c)

10 20 30 40−0.5

0.0

0.5

1.0

1.5

time(s)

dcvo

ltage

[p.u

.]

(d)

LCC rectifier LCC inverter MMC

Fig. 10. Start-up of the MMC-LCC hybrid HVDC system. (a) ac voltages(rms), (b) dc currents, (c) active powers, (d) dc voltages

with the power from MMC in order to deliver the ratedpower at LCC inverter. Fig. 10(d) displays the dc voltagesat the terminals of LCC rectifier, LCC inverter and MMC,respectively. dc voltages are regulated satisfactorily to theirreferences. Fig. 10(b) gives the dc currents at the LCC rectifier,the LCC inverter, and the MMC, respectively. It can be seenthe complementarity between the dc current in the MMC andthe LCC rectifier.

C. AC faults

Fig. 11 illustrates the performance of the system duringsingle-phase-to-ground fault. The fault was applied on the acside of the LCC inverter at 2.5 s and was cleared after 100 ms.Fig. 11(a) shows that the rms voltage at the LCC inverterdrops about 0.3 pu during the fault. As a result, a commutation

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0

volta

germ

s[p

.u.]

(a)

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0

1.5

activ

epo

wer

[p.u

.]

(b)

2.4 2.5 2.6 2.7 2.8 2.9 3

0.0

1.0

2.0

dccu

rren

t[p

.u.]

(c)

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0

1.5

dcvo

ltage

[p.u

.]

(d)

LCC rectifier LCC inverter MMC

Fig. 11. System response during single-phase to ground fault at LCC inverter.(a) ac voltages (rms), (b) dc currents, (c) active powers, (d) dc voltages

failure occurs that causes an abrupt decrease in the dc voltageas shown in Fig. 11(d). This condition causes that the dccurrents rise rapidly as shown in Fig. 11(c). During the fault,all IGBTs in FB-MMC are blocked, so there is available onecurrent path through the series connected capacitors of theMMC submodules. Consequently, the current is limited andthe hybrid HVDC is able to recover after the fault is clear asshown in Fig. 11.

D. DC faults

Fig. 12 illustrates the performance of the system duringpole-to-ground dc fault. The fault was applied at the midpointbetween line commuted converter at 2.5 s and was clearedafter 100 ms. Fig. 12(a) shows that the rms voltage at theMMC drops to zero during the fault. This happens because

(c) Response to ac fault (inverter side)

IEEE TRANSACTIONS ON POWER DELIVERY 7

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0vo

ltage

rms

[p.u

.](a)

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0

1.5

activ

epo

wer

[p.u

.]

(b)

2.4 2.5 2.6 2.7 2.8 2.9 3

0.0

1.0

2.0

dccu

rren

t[p

.u.]

(c)

2.4 2.5 2.6 2.7 2.8 2.9 3−0.5

0.0

0.5

1.0

1.5

dcvo

ltage

[p.u

.]

(d)

LCC rectifier LCC inverter MMC

Fig. 12. System response during pole to ground fault at DC line. (a) acvoltages (rms), (b) dc currents, (c) active powers, (d) dc voltages

all-IGBT’s of FB-MMC are blocked during fault. However,the abrupt disturbance in dc current affects the voltage that isregulated by the LCC inverter, which falls to zero at seen inFig. 12(d). However, MMC struggles to keep its DC voltageand this one falls just to 0.5 pu as seen in Fig. 12(d). One moretime, since the dc current is limited, seen in Fig. 12(c),thehybrid HVDC is able to recover after the fault is clear asshown in Fig. 12.

V. Conclusions

This paper studies the feasibility of a hybrid configurationthat combines the traditional LCC HVDC with a FB-MMCfor the integration of offshore wind farm. The performanceof the system using the proposed controller has been testedunder various conditions using PSCAD/EMTDC simulations.

The cases include the start-up and the response of the systemto ac faults at the LCC inverter. AC fault is a very seriouscondition in hybrid configuration, because the commutationfailure in line-commutated converters is translated into a dcfault in the voltage source converters. This kind of convertersare quite vulnerable to dc fault since they need a free-wheelingdiode for a proper operation which is a free path to feed thefault when the fault occurs. Full bridge MMC can providea solution to this problem, since they provides an availablecurrent path through the series connected capacitors of eachMMC sub-modules. So, an MMC-LCC hybrid is able to clearan ac temporary faults at inverter LCC using the H-bridge cellsof the MMC to handle the induced dc fault. Start-up procedurehas been discussed in detail and more relevant scenarios suchas wind speed variations, and temporary dc fault are alsoincluded. The simulation also reveals that hybrid is able toride through temporary dc faults.

(d) Response to dc faultFigure: [Top to bottom] (a) ac voltages (rms), (b) dc currents, (c) active powers, (d) dc voltages

Conclusions

AC fault is a very serious condition in a hybrid configuration because thecommutation failure in line-commutated converters is translated into a dc faultin the voltage source converters. Full bridge MMC can provide a solution tothis problem since they provide an available current path through the seriesconnected capacitors of each MMC sub-modules.

Contact email: [email protected]

Recommended